GEA Grasso M-Series Operating Manual

Screw Compressor Packages GEA Grasso M-Series
Operating Manual (Translation of the original text)
P_261511_1
COPYRIGHT
All Rights reserved.
GEA Refrigeration Germany GmbH
herein after referred to as the manufacturer. This restriction also applies to the drawings and diagrams contained in the documentation.
LEGAL NOTICE
These operating instructions are intended for the users of the equipment and are specifically intended for the operating company and its operating and maintenance personnel.
It is essential that the operating company and its operating and maintenance staff read these operat­ing instructions prior to transport, installation, start­up, use, maintenance, repair, disassembly and dis­posal. This obligation to read also applies to person­nel involved in activities in the life phases of the machine.
The operating company must supplement these operating instructions with instructions regarding health and safety at work and environmental protec­tion on the basis of existing national regulations for industrial safety.
In addition to these operating instructions and the binding accident prevention regulations valid for the respective country and area where the product is used, the recognised technical regulations for safe and professional work must also be observed.
These operating instructions are part of the unit. The entire documentation comprises these operating instructions and all additional operating instructions supplied with the unit. It must be kept readily availa­ble where the unit is installed. The entire documenta­tion must also be forwarded if the unit is installed at another location and if the unit is sold.
These operating instructions have been written in good faith. However, GEA Refrigeration Germany GmbH cannot be held responsible for any errors that
this document may contain or for their consequen­ces.
The manufacturer reserves the right to make techni­cal modifications during the course of further devel­opment of the equipment covered by these operating instructions.
Illustrations and drawings in these operating instruc­tions are simplified representations. As a result of the improvements and changes, it is possible that the illustrations do not exactly match the unit you are operating. The technical data and dimensions are subject to change. No claims can be made on the basis of them.
The manufacturer cannot accept liability for damages
which occur during the warranty period as a result of
improper operating conditions and conditions of use,
inadequate maintenance,
improper operation,
incorrect installation,
incorrect or improper connection of the main electrical drive,
or which result from or can be attributed to improper modifications or failure to observe the instructions;
through the use of accessories or spare parts which were not supplied or recommended by the manufacturer.
Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
2 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
SYMBOLS USED IN THIS MANUAL
Danger!
Stands for an immediate danger which leads to heavy physical injuries or to the death.
Warning!
Stands for a possibly dangerous situa­tion which leads to heavy physical injuries or to the death.
Caution!
Stands for a possibly dangerous situa­tion which could lead to light physical injuries or to damages to property.
Hint!
Stands for an important tip whose attention is important for the designa­ted use and function of the device.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 3
LAYOUT INFORMATION
Bullet points and numbered list characters Bullet points are used to separate logical contents within a section:
Bullet point 1
Types of bullet point 1.
Bullet point 2
Types of bullet point 2.
Numbered list characters are used to separate enumerations within a descriptive text:
Descriptive text with consecutive numbering:
Numbered list point 1
Numbered list point 2
Handling instructions
Handling instructions require you to do something. Several consecutive steps result in a handling sequence that should be run in the specified order. The handling sequence can be divided into separate steps.
Handling sequence
1.
Handling sequence step 1
step 1,
step 2,
step 3.
2.
Handling sequence step 2
The subsequent handling sequence is the expected result:
®
Result of the handling sequence.
Individual handling steps
Individual handling steps are marked thus:
Individual work steps
Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
4 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
TABLE OF CONTENTS
1
BASICS
11
1.1
Importance of the documentation
11
1.2
Requirements for personnel, obligation to exercise due care
11
1.3
Legal foundations (Germany)
12
1.4
Specified Use
14
1.5
Warning against foreseeable abusive use
14
1.6
CE mark
15
2
MANUFACTURER INFORMATION
16
3
CUSTOMER SERVICE
17
3.1
Technical customer service department
17
3.2
Spare parts
17
3.3
Training courses
17
3.4
Service contracts
17
4
SAFETY
18
4.1
General information for safety
18
4.2
Behaviour in the case of emergency
18
4.3
Possible residual hazards
18
4.4
Installation in explosive atmospheres, installation zones 1 and 2
19
5
TRANSPORT, STORAGE
21
5.1
General instructions
21
5.2
Delivery
21
5.3
Transport (crane transport)
21
5.4
Bearings
23
5.5
Storage (several years)
24
6
INSTALLATION
26
6.1
Basic information for installation
26
6.2
Rigid installation
26
6.3
Anti-vibration mounting
26
6.4
Electrical connection
26
6.4.1
Use in explosive atmospheres, installation zones 1 und 2
27
6.5
Sound insulation, weather protection
27
6.6
Information regarding noise emissions
27
7
DESCRIPTION OF DESIGN AND FUNCTION
29
7.1
Installation in explosive atmospheres, installation zones 1 und 2
29
7.2
Product code of screw compressor packages - Grasso SP1, SP2, SPduo and M Series
30
7.3
Technical specifications
32
7.4
Location of the product identification (name plate)
33
7.5
Information and safety labels on the product
34
7.5.1
Labelling of the pressure and temperature sensors, heater
34
7.5.2
Label of the safety valve
34
7.5.3
Labels of the screwed connections with DiNova ring
34
7.5.4
Labels of the pipelines
35
7.5.5
Marking the direction of rotation of the compressor drive motor
35
7.5.6
Marking the direction of rotation of the oil pump motor
35
7.5.7
Labels of the pressure gauge
36
7.5.8
Labeling of the control / control cabinet
36
7.5.9
Designation of the earth connection
37
7.6
Process flow diagram
37
7.7
Main components
38
7.7.1
Screw compressor
39
7.7.2
Compressor drive motor
39
7.7.3
Compressor with coupling housing
40
7.7.4
Oil separator
40
7.7.5
OMC block with oil filter system
41
7.7.6
Oil cooler
41
7.7.7
Oil pump (optional)
41
7.7.8
Suction filter - check valve combination
42
7.7.9
Controller
43
7.7.10
Fittings
43
7.7.11
Safety devices
44
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 5
7.7.12 Monitoring devices 45
7.7.13
Components installed by the client
45
7.8
General functional description
45
7.9
Refrigerant circuit
45
7.10
Oil System
46
7.10.1
Oil separation
46
7.10.2
Oil heater
46
7.10.3
Oil cooling
46
7.10.4
Oil filter
46
7.10.5
Oil pump
46
7.10.6
Oil injection
47
7.10.7
Oil circuit, OMC block
47
7.11
Capacity control
47
7.12
Technical specifications
47
7.12.1
Designed for use in explosive atmospheres!
47
7.12.2
Basic terms
48
7.12.3
Operating media
48
7.12.3.1
Refrigerant
48
7.12.3.2
Refrigeration machine oils
48
7.12.3.3
Secondary refrigerant
48
7.12.4
Operating limits
48
7.12.5
Water quality requirements, parameters
50
8
START-UP
53
8.1
Important information for start-up
53
8.2
Basics
54
8.3
Connecting the screw compressor package
54
8.3.1
Connecting the pipes
54
8.3.2
Electrical connection
55
8.4
Paint and insulation
55
8.5
Start-up procedure
55
8.5.1
Checking the electrical connection
55
8.5.2
Leak test
55
8.5.3
Drying, vacuum
56
8.5.4
Operating position of valves
57
8.5.5
Oil charge
60
8.5.5.1
Pressure compensation with the cooling system
60
8.5.5.2
Checking the direction of rotation of the oil pump motor
60
8.5.6
Checking the fault monitoring
61
8.5.7
Checking of the safety pressure limiter
61
8.5.8
Checking of the emergency-OFF button.
61
8.5.9
Adjustment of oil pressure
62
8.5.10
Checking the direction of rotation of the drive motor
62
8.5.11
Mounting the coupling
62
8.5.12
Checking the water circuits
63
8.5.13
Initial start-up
63
8.5.14
Checking the adjustment of the control slide
63
8.5.15
Checking the control slide adjustment times
63
8.5.16
Checking the oil cooler
63
8.5.17
Adjusting the amount of injection oil and the oil temperature
63
8.5.17.1
Screw compressor packages without refrigerant injection
64
8.5.17.2
Compressor units with refrigerant injection
64
8.6
Start-up after long standstill periods
64
8.7
Restarting after approx. 1 year standstill
64
9
USE, OPERATION, CONTROL
65
9.1
Use in explosive atmospheres, installation zones 1 and 2
65
9.2
Important information for the operator
65
9.3
Prerequisite for switching on
65
9.3.1
Overview of the operating modes
67
9.3.2
Setting of setpoint and limiting values as well as safety devices
69
9.4
Operation of the screw compressor package
69
9.5
Instructions regarding failures, their causes and remedies
69
10
CLEANING, MAINTENANCE, REPAIR
72
10.1
Use in explosive atmospheres, installation zones 1 and 2
72
Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
6 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
10.2 Important information for service personnel 72
10.3
Cleaning the heat exchanger
72
10.3.1
Mechanical cleaning
73
10.3.2
Chemical cleaning
73
10.4
Maintenance
73
10.4.1
General instructions
73
10.4.2
Repair work
74
10.4.2.1
Repair information
74
10.4.2.2
Repairs of pressure vessels subject to approval inspection
74
10.4.3
Maintenance intervals
74
10.4.4
Maintenance work
74
10.4.4.1
Maintenance of the screw compressor
74
10.4.4.2
Changing the block mounting filter element
75
10.4.4.3
Replacing the oil filter
75
10.4.4.4
Maintenance of the suction filter
76
10.4.4.5
Oil draining, oil filling, oil change
76
10.4.4.6
Oil pump maintenance
78
10.4.4.7
Changing the fine oil separation cartridges
78
10.4.4.8
Tightening screw fastenings
79
10.4.4.9
Coupling maintenance
79
10.4.4.10
Checking the function of check valves
79
10.4.4.11
Searching for leaks on the refrigerant side / leak test
79
10.4.4.12
Venting the refrigerant circuit
80
10.4.4.13
Refrigerant evacuation
80
10.4.4.14
Checking the bearing noise
81
10.4.4.15
Checking the solenoid valves for capacity control
81
10.4.4.16
Checking the oil heater
81
10.4.4.17
Maintenance of the compressor drive motor
81
10.4.4.18
Checking the start regime
81
10.4.4.19
Checking the safety devices
81
10.4.4.20
Checking the operating parameters
81
10.4.4.21
Maintenance of the switching cabinet
82
10.4.4.22
Checking the earth connection
83
10.4.4.23
Insulation
83
10.4.4.24
Check of the tightening torque on the adjusting elements of the fixing base.
83
11
DECOMMISSIONING
84
11.1
Shut-down in the event of dangerous situations
84
11.2
Standstill for a period <48 hours
84
11.3
Standstill for a period >48 hours
84
11.4
Measures during shutdowns
84
11.4.1
Monthly measures during standstill
85
11.4.2
Four weeks before restarting
85
12
DECOMMISSIONING, DISPOSAL
86
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 7
Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
8 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
TABLE OF FIGURES
fig. 1
CE mark
15
fig. 2
Designation of the lifting points
21
fig. 3
Stopper with shackle
22
fig. 4
Transportation with a wire rope hoist
22
fig. 5
transportation using crossbeam
23
fig. 6
Location of the product identification (type plate)
33
fig. 7
Type plate
33
fig. 8
Safety labels of the pressure and temperature sensors, heater
34
fig. 9
Label of the safety valve
34
fig. 10
Labels of the screwed connections
34
fig. 11
Labels of the pipelines
35
fig. 12
Marking the direction of rotation of the compressor drive motor
35
fig. 13
Marking the direction of rotation of the oil pump motor
35
fig. 14
Labels of the pressure gauge
36
fig. 15
Test verification for the control system
36
fig. 16
Designation of the earth connection
37
fig. 17
Process flow diagram Grasso SP1, M-series
37
fig. 18
Main components of the GEA Grasso M-Series
38
fig. 19
GEA Grasso M-Series, arrangement of the SCP
39
fig. 20
GEA Grasso M-Series, arrangement of the compressor drive motor
39
fig. 21
GEA Grasso M-Series, arrangement of the coupling housing
40
fig. 22
GEA Grasso M-Series, arrangement of the oil separator
40
fig. 23
GEA Grasso M-Series, arrangement of the OMC block with oil filter system
41
fig. 24
GEA Grasso M-Series, arrangement of the oil cooler
41
fig. 25
GEA Grasso M-Series, arrangement of the (optional) oil pump
42
fig. 26
GEA Grasso M-Series, suction filter - check valve combination
42
fig. 27
GEA Grasso M-Series, arrangement of the controller
43
fig. 28
Corrosion resistance in presence of chlorides
51
fig. 29
Vacuum required to remove moisture from refrigerating plants
56
fig. 30
Stop valve open
57
fig. 31
Stop valve closed
57
fig. 32
Check valve
57
fig. 33
Shuttable check valve
57
fig. 34
Control valve
58
fig. 35
Shuttable check valve
58
fig. 36
Solenoid valve
58
fig. 37
Change-over valve
58
fig. 38
Oil pressure control valve
58
fig. 39
Overflow valve, safety valve
59
fig. 40
Pressure controlled check valve
59
fig. 41
Quick acting valve, spring-loaded
59
fig. 42
Charging valve, drain valve
59
fig. 43
Service valve
59
fig. 44
Oil temperature limiter
60
fig. 45
Temperature controlled control valve
60
fig. 46
Motor direction of rotation
62
fig. 47
Arrangement of MIN / MAX sight glasses
78
fig. 48
Operating position of the fine oil separation cartridges
79
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 9
Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
10 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
1 BASICS
1.1 Importance of the documentation
This operating manual is directed at the users of the package/chiller and is specifically intended for the operating company and its operating and mainte­nance personnel. This operating manual must be read prior to transport, installation, commissioning, maintenance, repair, disassembly/disposal.
All work explained in this operating manual must only be carried out by technical personnel.
This operating manual must be supplemented with instructions based on prevailing national regulations regarding industrial safety, health protection and environmental protection.
In addition to this operating manual and the manda­tory accident prevention regulations applicable for the respective place of installation, the accepted technical regulations for safe work according to good professional practices must also be observed.
The operating manual is a part of the total product. The entire documentation, consisting of this operat­ing manual as well as all supplied additional instruc­tions, is to be always kept easily accessible at the place of installation of the package/chiller. The com­plete set of documentation must also accompany the package/chiller if it is sold.
1.2 Requirements for personnel, obliga­tion to exercise due care
Qualification
All work explained in this manual (assembly, electri­cal connection, commissioning, operation, etc.) may only be carried out by trained technical personnel who observe the relevant technical regulations.
Technical personnel are representatives of the unit manufacturer and persons who, as a result of their technical training, experience and personal instruc­tion in training measures, have sufficient knowledge of:
applicable international and national standards,
applicable occupational safety regulations,
applicable accident prevention regulations,
applicable environmental protection regulations,
the construction and functioning of the unit,
recognised technical regulations for safe work according to good professional practice.
The technical personnel must:
be able to assess the work assigned to them, recognise and avoid possible dangers,
be authorised by those responsible for the safety of the system to carry out the requisite work and activities.
Caution!
No arbitrary changes may be made to the control or other components belonging to the unit. Maintenance work may only be done by authorised service staff.
Special requirements for the electrical techni­cians
Work on electrical components and modules may only be carried out by an electrical technician according to the rules relevant to electrical engineer­ing. Furthermore the operator has to take care that the electrical systems, tools and fixtures are oper­ated according to the rules relevant to electrical engi­neering and applicable standards and serviced prop­erly.
In principle it is prohibited to carry out work on parts under voltage.
Fuses may only be replaced and not repaired or bypassed.
Only the fuses specified in the electrical circuit diagram may be used.
A two-pole voltage tester must be used to ensure that the parts are de-energised.
The power supply as well as the unit casing must be sufficiently grounded and tagged with a suita­ble label.
Deficiencies noticed in the electrical systems/ modules/tools and fixtures must be corrected immediately. If an acute danger exists till then,
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Basics
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 11
the package/chiller must not be operated in the defective condition.
Minimum age
The minimum age for the operation of the package/ chiller and installation is 18 years. All persons involved in the assembly and installation of the pack­age/chiller and the system must get themselves trained at regular intervals and/or familiarise them­selves with the current technical data of the device. The training and instructions is to be conducted at least once a year, unless some other interval has been agreed upon with the manufacturer.
Obligation to exercise due care
The statutory regulations for meeting the obligation to exercise due care are to be observed.
Meeting the obligation to exercise due care accord­ing to the current level of technology requires that everything that is
technically possible (use of accepted technologi­cal rules) and
economically reasonable
be done to prevent damage in a protectively safe manner.
1.3
Legal foundations (Germany)
The following standards, regulations, ordinances and laws must be strictly observed to ensure the safety and functional reliability of the packages and chillers:
EC Machinery Directive 2006/42/EC
EC Pressure Equipment Directive 2014/68/EC– AD 2000 Info Sheets
Hazardous Incident Ordinance (12. BlmSchV) with 1st failure VwV
Federal Pollution Control Act (BImSchG), 4th BimSchV
Water Resources Act (WHG), VawS
Hazardous Substances Ordinance (GefStoffV)
Recycling and Waste Management Act (KrW­AbfG)
DIN EN 378, Part 1 to Part 4 Safety-related technical requirements and environmental requirements
Accident Prevention Regulation including implementation regulations (BGR 500, chapter
2.35) on refrigeration plants, heat pumps and cooling equipment (BGV B3) regarding noise
EN 12284 Refrigerant fittings, safety related technical definitions, testing and marking
DIN 2405 Pipes in refrigeration plants, marking
VDMA specifications,in particular VDMA 24 243 and 24 020
VDI Guidelines
Instruction sheets for handling ammonia, Instruction sheet for halogenated hydrocar­bons containing fluorine BGI 648
Safety data sheet for ammonia and other refrig­erants and refrigeration oils
The list of rules and standards has been taken from Status Report No. 5 of the German Refrigeration and Air Conditioning Engineering Association "Safety and environmental protection in ammonia refrigeration plants" and also fully applies to other refrigerants.
Danger!
The additional safety instructions as defined in "Appendix E" must be observed for packages for the desig­nated use in potentially explosive atmospheres, installation zones 1 and 2 in accordance with EN 60079-10.
The following:
standards,
safety regulations,
guidelines and recognised engineering practice,
listed in these operating instructions must be observed at least!
Hint!
If the package/chiller is used in a country other than Germany, the rules and regulations applicable at the place of installation must be observed and complied with!
The mandatory accident prevention regulations applicable for the respective country and area where the product is used must also be observed.
Basics Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
12 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Failure to observe the safety instructions can lead to danger to personnel and the environment as well as damage to the unit.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Basics
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 13
1.4 Specified Use
Hint!
Observe the "Specified Use" chapter of the installation instructions for the screw compressor!
The screw compressor package must only be oper­ated up to a maximum discharge pressure in accord­ance with the type plate.
It is imperative that you comply with the applicable conditions of use with respect to pressure and tem­perature for the screw compressor package.
Do not change the setting values of the safety pres­sure switch. This would endanger the operating safety of the refrigeration plant.
If the switch-off value is set higher than 0.9 x maxi­mum operating pressure (see EN378-2) of the high pressure section of the refrigerating system, this may result in the the tank within this section of the system rupturing.
The operating regime stipulated by the manufacturer, especially for the starting phase of the screw com­pressor package, must be observed.
Operating parameters must be monitored. Operating parameters must not deviate from within the defined limits.
The screw compressor package has been designed and manufactured for a specific application under defined conditions of use. Unauthorised structural modifications are not permitted. We assume no liabil­ity for any resulting damage or injury. In the interest of further development, GEA Refrigeration Germany GmbH reserves the right to make technical modifica­tions. The screw compressor package described here corresponds to the state of the art at the time this operating manual was published.
The manufacturer must be consulted in all cases as to the permissibility of the modification if there is any change of the application or the conditions of use.
Do not make any modifications to the screw com­pressor package and the compressor control system.
These may impair the safety and functionality of the SCP. They will also void the guarantee.
The pressure equipment described here must not be used for any purpose other than the purpose speci­fied here. The units must only be installed by the supplier/installer and not by the end user. If the pres­sure equipment is not used according to the regula­tions, the safe use of the equipment is not guaran­teed. The supplier/installer or the operator – and not
the manufacturer – is responsible for all personal injury and damage to property resulting from improper use.
The pressure equipment is not designed for dynamic loads. If there is a risk of lightning strikes, the pres­sure equipment must be earthed. The supplier/instal­ler must record instructions for regular inspection of the pressure equipment in his operating manual and must specify the procedure to be followed by the end user in the event of damage. In order to prevent burns or frostbite, the pressure receptacle must not be touched during operation. This can be prevented by respective safety measures. Appropriate warning signs must be affixed. Compressor units or systems must be equipped with safety valves in accordance with EN 378. The foundation must provide sufficient rigidity.
The supplier/installer must carefully install the acces­sories for the pressure equipment. The pressure equipment must not be damaged during installation and must be painted after installation. The pressure equipment must only be filled with the refrigerant specified in the contract. The pressure units must be installed in the compressor unit or the system in such a way that vibrations or pulses cannot be transferred to the pressure units. The contacts must be installed with the power supply disconnected.
Specified use includes observance of this manual and all supplied operating manuals as well as com­pliance with the maintenance and service intervals and conditions stipulated therein.
Warranty claims and authorisation for operation become void if the equipment is not used for its specified purpose.
1.5
Warning against foreseeable abu­sive use
A package/chiller is said to have been abused, if
unauthorised refrigerants, fuels and lubricants and secondary refrigerant materials are used.
Hint!
Observe specification for the project!
electrical components are wrongly connected.
Hint!
Watch voltage and frequency!
mechanical components are wrongly connected.
Basics Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
14 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Hint!
Watch pressure and temperature!
the supporting, hanging and storage facilities are misused.
control and regulation units including control sys­tem software are tampered with.
the driving power generated by the motor is used for purposes other than the operation of the respective compressors and pumps.
1.6 CE mark
By affixing the CE mark, the manufacturer confirms the conformity of the product with the applicable EC Directives and compliance with the principle require­ments stipulated within them.
fig.1: CE mark
The CE mark is affixed to the nameplate.
The CE mark for products from GEA Refrigeration Germany GmbH is provided as defined in the Pres­sure Equipment Directive, i.e. pressure equipment is placed on the market with the required equipment parts with safety function. This complete assembly is subject to the Pressure Equipment Directive.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Basics
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 15
2 MANUFACTURER INFORMATION
GEA Refrigeration Germany GmbH is a company within GEA Refrigeration Technologies, the Refriger­ation Technology Segment of the GEA Group and provides its customers around the world with high­quality components and services for refrigeration and process technology applications.
Locations:
GEA Refrigeration Germany GmbH
Factory Berlin
Holzhauser Str. 165
13509 Berlin, Germany
Tel.: +49 30 43592-600
Fax: +49 30 43592-777
Web:
www.gea.com
E-Mail: refrigeration@gea.com
GEA Refrigeration Germany GmbH
Factory Halle
Berliner Straße 130
06258 Schkopau/ OT Döllnitz, Germany
Tel.: +49 345 78 236 - 0
Fax: +49 345 78 236 - 14
Web: www.gea.com
E-Mail: refrigeration@gea.com
Manufacturer Information Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
16 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
3 CUSTOMER SERVICE
GEA Refrigeration Germany GmbH supplies prod­ucts of high quality and reliability. In addition, the manufacturer ensures continuous operation of the refrigeration and process technology system and provides exceptional service for the components supplied.
3.1
Technical customer service depart­ment
Do you require support from the technical customer service department? Specially trained, experienced service technicians are available on call for you in order to provide assistance in case of technical prob­lems and to offer support in the framework of our after-sales service.
24/7 Hotline:
the hotlines can reached around the clock on every day of the week:
Wireless
+49 (0) 172 39 12 050
Landline, weekdays from 7 to 17 hours
+49 (30) 43 59 27 61
+49 (30) 43 59 27 62
Email:
Grasso-service@geagroup.com
outside of Germany, Austria and Switzerland please contact:
local sales office
www.gearefrigeration.de
technical support for liquid chillers with reciprocating compressors in Germany, Austria and Switzerland
24/7 Hotline
+49 (345) 78236 20
The specialists of our Technical Customer Service department support you in installations, acceptan­ces, maintenance, operating questions, on-site inspections and repairs of our products.
3.2 Spare parts
GEA Refrigeration Germany GmbH has its own prac­tical and rapidly working spare parts department to supply the necessary spare parts worldwide. Neces­sary spare parts are shipped as quickly as possible.
In most cases, you will receive your spare parts within 24 hours after placing the order.
You can contact us using the following hotlines:
Wireless, out of hours
+49 (0) 172 30 14 579
Landline, weekdays from 8 to 17 hour
+49 (30) 43 59 27 50
Fax
+49 (30) 43 59 27 58
Email
Grasso-parts@geagroup.com
Order spare parts from our G-Pos. online shop
(Grasso Parts online shop)
gea-refrigeration.de.spareparts@gea.com
3.3 Training courses
Warning!
All work on our systems must only be carried out by technical personnel! Acquire the technical know-how required for this in good time!
Comprehensive training courses are held regularly for service technicians and mechanics, thus ensuring the safe and proper use and maintenance of our sys­tems.
Email
Grasso-service@geagroup.com
3.4
Service contracts
It is possible to sign a long-term service agreement (service contract). For further information regarding the content, scope and conditions of the possible service options, please contact the Technical Cus­tomer Service department.
Email:
Grasso-service@geagroup.com
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Customer service
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 17
4 SAFETY
4.1 General information for safety
The safety aspects to be observed for operating the equipment are shown in the chapter on "Safety".
The equipment has been developed and manufac­tured according to the currently applicable state of the art and is reliable in operation. It has been tested and left the factory in a technically faultless safe con­dition.
In order to maintain this condition for the operation time, the details of the project documentation and certificates must be observed and complied with. When operating the equipment, at least the general safety regulations and the provisions and guidelines referred to in this documentation must be observed.
Only compliance with all provisions and guidelines will enable optimum protection of the personnel as well as dangers to the environment and the safe and smooth operation of the equipment.
4.2 Behaviour in the case of emergency
Hint!
Familiarise yourselves with the local evacuation plan before beginning the work.
Should an emergency situation arise despite adher­ing to the safety regulations, the package/chiller must be shut down immediately and isolated from the electrical mains.
The mains cable must be blocked in such a way it is not possible to restart the unit accidentally and marked as such.
The operator of the complete system has to take care that an isolation device, e.g. a mains switch with appropriate contact rating and an integrated indica­tor, is pre-installed in the mains cabling on site.
A separate mains cable/feed cable must be laid for the operation of the package/chiller.
The mains cable/feed cable is to be specially protec­ted and provided with an emergency stop switch.
4.3 Possible residual hazards
Warning!
Despite careful design of the machine and implementation of all the safety­relevant regulations, further risks for persons and machine during all life phases of the package/chiller cannot be fully ruled out. The additional safety instructions in the individual chapters of this manual must therefore be care­fully observed!
Residual risks that were ascertained during the risk assessment carried out for the product according to safety standard EN ISO 14121 - Safety of Machines
- are:
mechanical hazards due to sharp sheet metal edges and projecting parts,
electrical hazards as a result of inadvertently coming in contact with terminals and cables,
thermal hazards as a result of inadvertently com­ing in contact with heat exchangers and pipes,
exposure to noise,
hazards caused by vibration due to improper installation,
hazards due to working materials and other materials in case of allergies orthe like,
neglect of ergonomic principles,
combinations of various hazards,
unexpected start-up, unexpected rotation in case of incorrect electrical connections or defects,
shut-down, emergency stop when defects are detected,
changes to the rotational speed,
power failure,
failure of the control circuit or control loop,
incorrect assembly,
fracture during operation,
operating media or objects getting thrown out,
loss of stability and
personnel slipping, tripping or falling.
Safety Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
18 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Hint!
There are no radiation hazards
4.4 Installation in explosive atmos­pheres, installation zones 1 and 2
Danger!
The additional instructions for using screw compressor packages in explo­sive atmospheres, installation zones 1 and 2, must be complied with!
Function and Design
The same functional and design characteristics apply to the maintenance instructions for the use of screw compressor packages in potentially explosive atmos­pheres as described in the respective applicable operating manual.
In addition to this, the following extensions apply:
All components relevant for the use of screw compressor packages in relation to their use in potentially explosive atmospheres (concerns both electrical and non-electrical components) are separately designed and documented! The extended documentation scope (component descriptions, certificates, calculations) is part of the product documentation.
Extension to the method of working
The use of screw compressor packages is exten­ded to use in potentially explosive atmospheres, including the compression of process gases (only compression for the purposes of pressure increase). The screw compressor packages are not suitable for pumping potentially explosive mixtures. This means that, when the compressor is in intake condition, the pumped liquid must not contain any oxygen. The intake condition always refers to pressure layers in the overpressure range.
The owner operator and the system builder must use monitoring devices reflecting the respective state of the art standards to positively monitor and ensure this effect.
Safety equipment extension
If oil heaters are used in potentially explosive atmospheres (see component specification), additional, separate oil level monitoring is abso-
lutely necessary to ensure a minimum oil level above the heating elements. To this end, a sepa­rate oil level switch is used in each use case according to the necessary explosion protection specification.
Operation
The same regulations apply in regard to the operat­ing instructions for screw compressor packages in potentially explosive atmospheres as described in the applicable operating manual.
In addition to this, the following extensions apply:
In addition, the legal safety regulations apply to the people responsible for operating the screw compressor package, and must be complied with respect to the transport, assembly, operation and maintenance and if necessary the replacement of subassemblies, etc. in potentially explosive atmospheres.
The owner operators regulations must also always be observed – see also section: Safety information for compressor, Appendix E, and for package, Appendix E.
The electrical engineering regulations for instal­lations in potentially explosive atmospheres , especially EN 60079-10, apply to the installation and connection of electrical components. The relevant prescribed cabling material must be used.
The whole screw compressor package must be earthed by the owner operator.
Maintenance
The same regulations apply to the maintenance of screw compressor packages in potentially explosive atmospheres as described in the respective applica­ble operating manual.
In addition to this, the following extensions apply:
In addition, the legal safety regulations for the installation of the screw compressor packages apply to the people responsible for the mainte­nance of the screw compressor package with respect to the maintenance of individual compo­nents or assemblies or their complete replace­ment in potentially explosive atmospheres.
The maintenance may only be carried out in agreement/with the knowledge and release of the owner operator.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Safety
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 19
The maintenance and replacement regulations resulting from the operating manual for the com­ponents must be conformed with.
Appropriate special tools approved for the poten­tially explosive atmosphere must be used.
Only original spare parts may be used. If original spares are not used, the guarantee is invalidated or the owner is liable in the event of damage.
Each maintenance inspection (see maintenance book) must also include checking the secure fit of the threaded connections for the coupling safety hood.
Safety Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
20 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
5 TRANSPORT, STORAGE
5.1 General instructions
Caution!
Adequate lighting must be ensured during loading and unloading as well as for storage in order to avoid injuries and damage to property.
There is a danger of impacts and stumbling due to protruding parts on the equipment (e.g. valve caps). There is also the danger of being cut on sharp edges and surfaces. There is a danger of crushing parts of the body during the transport work. Personal protective equipment (work clothing, work books, gloves) must be worn during all activities on the equipment.
Hint!
These operating instructions must be read prior to transport, storage and delivery to the installation site. It is imperative to strictly observe the instructions and information given!
All work explained in these operating instructions must only be carried out by qualified personnel.
5.2 Delivery
Shipment is made in the type of packing stipulated in the order. The screw compressor package is gener­ally supplied without packing.
The screw compressor package has an inert gas filler in the refrigerant circuit.
Warning!
The compressor(s) of the screw com­pressor package is/are
not filled with oil. The screw compressor package must not be started, therefore, before proper assembly and start-up.
5.3 Transport (crane transport)
Warning!
The screw compressor packages are not intended for transport with a fork lift truck!
Screw compressor packages are high-quality prod­ucts, which must be handled with due care during transport. Protect the equipment from impact and set it down carefully.
When transported by crane, the screw compressor package must have the same position as in opera­tion (frame downwards!). Only use the lifting points provided. The lifting points are marked!
fig.2: Designation of the lifting points
Caution!
It is forbidden to attach SCPs to fit­tings or pipes or at the eyebolts / lift­ing rings of the compressor, the elec­tric motor, the tank or the switching cabinet.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Transport, Storage
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 21
Take special care not to attach the ropes near to small nominal diameter pipes or insulation and to damage them. Use spacers if necessary.
The lifting points are not arranged on one plane. The ropes must be longer than 3 m. The height differen­ces between individual lifting points must be com­pensated by suitable extensions.
Make suitable arrangements (timber or insulating material) to avoid damage to the surface.
Shackles must be used.
fig.3: Stopper with shackle
fig.4: Transportation with a wire rope hoist
Transport, Storage Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
22 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
fig.5: transportation using crossbeam
Danger!
Make certain there is no one under the suspended load during transport with the crane!
Position the screw compressor package on the transport vehicle such that it is prevented from tilting and falling. Load securing is preferably carried out by lashing to the specified points. The pipes and equip­ment of the screw compressor package must not be entered. Components must be secured against vibrations. The competent staff member or the com­pany itself is responsible for ensuring safety during transport.
Warning!
Screw compressor packages must be adequately protected from external influences during transport.
Transport packaging (optional): foil
The foil may only be removed before erecting the screw compressor package at the intended installa­tion location in the machine room. Up until this point in time, the foil serves to protect the screw compres­sor package against external influences.
5.4 Bearings
When the screw compressor packages are deliv­ered, check for possible transport damage and report any damage to the manufacturer in writing.
The storage area of screw compressor units shall be roofed, plain and paved and secured against access of unauthorized persons. Place the screw compres­sor package onto timber planks and have it protected from jerks or impacts.
Warning!
Screw compressor packages must be adequately protected from external influences (humidity, frost, extreme heat) during storage. This usually con­cerns lengthy standing times outdoors before installation and start-up of the refrigeration plant. The manufacturer recommends the use of plastic sheet­ing to cover the whole product.
The venting slits of the electric motors must always be covered!
Storage temperature: 5°C ... 40°C
The composition of the paint on the screw compres­sor package is designed for installation in the machine room (inside installation). Contact with water (including water spray) must be avoided.
Warning!
The screw compressor package is fil­led with dry gas (e.g. nitrogen) before delivery which prevents any change of the properties of any already filled operating medium (e.h. refrigerating machine oil). Check the gas filling once a week and recharge to the specified overpressure if required.
Turn the shaft of the compressor at least every four weeks (approx. 10 revolutions).
The transport packing (foil if present), that needs to be opened for turning the compressor shaft and for checking the gas filling, must be closed again after carrying out the activities in order to ensure protec­tion against external influences. The packing (foil if present) must be replaced as needed and for lengthy storage times.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Transport, Storage
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 23
Warning!
Regular ventilation of the screw com­pressor package packaging (if present) must be ensured in order to prevent condensation on the surfaces of the machine.
Long-term storage
With a standstill of the compressor of more than 16 weeks prior to start-up, there is a danger that the shaft seal may stick on the shaft and therefore be damaged on start-up. Because of this, removal and cleaning of the shaft seal is mandatory in order to ensure that it functions correctly.
1.
Use two pressure screws to remove the cover of the shaft seal, including the stationary gasket inserted in it.
2.
Removal of the seal package arranged on the shaft with the associated slide ring by hand or, if tightly seated, extraction by means of an appli­ance. If the seating is loose, the seal package may adhere to the stationary seal and will be pulled out when removing the cover.
3.
Clean the shaft seat with a lint-free cloth. Grease it lightly and push the sealing package back onto the shaft again.
4.
After pushing onto the shaft, the seal package must be manually compressed against the spring pressure which acts on it. At the same time, it must be checked whether the gasket springs out again.
5.
Then re-fit the cover of the shaft seal.
Warning!
Danger of cuts and crushing injuries.
6.
If storage is longer than 26 weeks, all O-rings must be renewed.
5.5 Storage (several years)
Hint!
The instructions in the "Transport, storage" chapter must be heeded.
The following storage conditions must be maintained when storing screw compressor packages that are equipped with a control.
1.
Storage temperature > 10°C
2.
Air humidity < 50%
If the screw compressor package is intended to be stored, the following preparatory measures must be carried out ex-works (especially protection against internal and external corrosion):
All process connections on the screw compres­sor package are sealed tight.
The screw compressor package is charged with dry gas to 1 bar.
A suction pressure gauge has been installed.
The facing sides of the mounted coupling hubs have been greased. (Does not apply to sliding bearing compressor drive motors)
Hint!
In case of the use of high-voltage motors: the operating manual of the manufacturer is to be followed, espe­cially regarding any anti-condensation heater required.
Free-standing motor and main flow shafts have been conserved.
The space on the screw compressor for the shaft seal has been greased.
The connections on the oil cooler water side have been sealed.
The following maintenance work must be carried out at the storage location during storage:
1.
Visual inspection of the general condition of the screw compressor package.
2.
Cyclical rotation of the screw compressor shaft (about 10 revolutions per month and the com­pressor drive motor (see operating manual).
Hint!
Does not apply to sliding bearing com­pressor drive motors.
3.
Check the transport fill pressure with a pressure gauge at the connection of item 405 (see P+I flow chart). If this value < 1 bar, replenish dried gas via the valve of item 85 (see P+I flow chat). All valves are already opened at the factory for a common pressure range.
Transport, Storage Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
24 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Caution!
After completion of the storage period and prior to re-delivery, a general review in the factory or a general examination at the storage location, performed by the technical customer service technician of GEA Refrigera­tion Germany GmbH, is recommended. Please pay attention to the information in the "Start-up" chapter.
The general check includes changing the O-ring on the compressor shaft seal as well as replacing the shaft seal of the oil pump.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Transport, Storage
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 25
6 INSTALLATION
6.1 Basic information for installation
Caution!
During the installation, make sure that substances escaping from leaks do not reach into the soil, groundwater or surface water. The applicable legal regulations must be heeded at the place of installation (e.g.for Germany: German Federal Water Act WHG).
All foundation calculations, the selection of materials and the soil analysis are the designer's or owner’s responsibility.
A plan must be produced for proper and professional assembly prior to the installation. The electrical and operating media connections must be established. It must be borne in mind that, in addition to the installa­tion area of the screw compressor package, there must be sufficient space available for the pipes as well as for operating during maintenance activities.
Install the screw compressor package on a level sur­face. The difference from the horizontal must not be more than 0.3 %. Provide enough space for mainte­nance work.
Under normal conditions, the screw compressor package stands solidly on the installation surface due to its own dead weight. We recommend that you provide ribbed rubber plates for shock absorption between the support surface and screw compressor package feet or machine base frame.
If greater damping is required (installation on a floor ceiling or on the roof), vibration dampers must be provided. The appropriate type of vibration damper must be determined and realised for this case. Also decouple the secondary refrigerant lines using com­pensators when vibration absorbers are used.
The welding seams must be inspected in accordance with the Pressure Equipment Directive after welding work by the customer or operator on pipe line con­nections and flanges.
6.2
Rigid installation
The frame of the screw compressor unit/ liquid chiller is placed on foundation bolts on a prepared founda­tion. The frame must be levelled with suitable shims such that the coarse alignment (radial and angular
misalignment ≤ 0.25 mm) at the coupling is attained again. Then tighten the foundation bolts.
6.3 Anti-vibration mounting
The frame of the screw compressor unit must be aligned with the levelling bolts until the coarse align­ment (radial and angular misalignment (radial and angle offset ≤ 0.25 mm) at the coupling is attained again.
Before tightening the foundation bolts of the isola­tors, check that the isolators over the spring (pre­dominantly made of rubber) are free and do not lie on the foundation.
6.4 Electrical connection
Danger!
Contact with live components is pro­hibited.
Produce the earth connection accord­ing to the designation in the general assembly drawing. See chapter "Des­ignation of the earth connection".
Before starting work, make sure that all parts to be connected are de-energised, e.g. by removing the main fuse in all phases or installing a jumper wire.
The insulation resistance of the electrical tools and fixtures and wiring is to be checked. The connection may only be undertaken if this value lies in the allow­able range.
All electrical connections must be established and all electrical consumers/sensors must be connected according to the circuit diagram.
Installation Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
26 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
6.4.1 Use in explosive atmospheres, installation zones 1 und 2
Danger!
The same regulations apply to the operating instructions for screw com­pressor packages in potentially explo­sive atmospheres as described in the respective applicable operating man­ual.
In addition to this, the following exten­sions apply:
1.
The relevant electrical engineering regulations for installations in potentially explosive atmos­pheres , especially EN 60079-10, apply to the installation and con­nection of electrical components. Relevant prescribed cabling mate­rial must be used.
2.
The whole screw compressor package must be earthed by the owner operator.
6.5 Sound insulation, weather protec-
tion
If the screw compressor package is intended for out­door installation, it must be provided with a suitable housing for sound insulation and weather protection by the customer. The weather protection must pro­vide the machine with adequate protection against the climatic conditions at the installation location.
Hint!
The screw compressor package is not intended for unprotected outdoor installation. Protection against exter­nal influences, especially dirt, dust and moisture (wetness), is essential.
The manufacturer will not accept liability for damage due to incorrect outdoor installation.
6.6
Information regarding noise emis­sions
The noise information provides approximate parame­ters and apply to the installation without any secon­dary noise protection measures.
The information has a tolerance of ±3 dB.
The precise data depend closely on the emission values for the motors, which are manufacturer dependent.
Should local conditions require adherence to noise levels, a calculation should be made using the spe­cific motor data in individual cases.
Sound insulation measures, such as motor encapsu­lation or complete package encapsulation can ach­ieve a significant reduction in sound level.
Wearing hearing protection with sufficient noise reduction is recommended in rooms with running screw compressor packages.
Caution!
According to EU Directive 2003/10/EC, the allowable exposure limit value regarding the daily noise exposure level is 80 db(A). In the event of noise levels above this limit value the sys­tem operator must provide the opera­tor with information on exposure to noise and personal hearing protection and ensure that this is also worn (2003/10/EC Article 6).
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Installation
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 27
Sound power level LWA in dB(A)
Compressor drive motor output in kW
Compressor type/theoretical throughput volume in m3/h at 4500 RPM
H
721
L
833
M
1056
N
1316
55
Max 103 103 103 103
Min 96 96 96 96
75
Max 104 104 104 104
Min 97 97 97 97
90
Max 105 105 105 105
Min 98 98 98 98
110
Max 106 106 106 106
Min 99 99 99 99
132
Max 107 107 107 107
Min 100 100 100 100
160
Max 108 108 108 108
Min 101 101 101 101
200
Max 109 109 109 109
Min 102 102 102 102
250
Max
110 110
Min
103 103
315
Max
111
Min
103
Installation Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
28 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
7 DESCRIPTION OF DESIGN AND FUNCTION
7.1 Installation in explosive atmospheres, installation zones 1 und 2
Danger!
The same functional and design characteristics apply to the maintenance instructions for the use of SCPs in potentially explosive atmospheres as described in the respective applicable operating manual.
In addition to this, the following extensions apply:
1.
All components relevant for the use of SCPs in relation to their use in potentially explosive atmospheres (concerns both electrical and non-electrical components) are separately designed and documented – see product description!
2.
Extension to the method of working The use of SCPs is extended to use in potentially explosive atmospheres, including the
compression of process gases (only compression for the purposes of pressure increase). The SCPs are not suitable for pumping potentially explosive mixtures. This means, when the compressor is in intake condition, the pumped liquid must not contain any oxygen. The intake condition always refers to pressure layers in the overpressure range.
The owner operator and the system builder must use monitoring devices reflecting the respective state of the art standards, to positively monitor and ensure this effect.
3.
Safety equipment extension If oil heaters are used in potentially explosive atmospheres (see also component specifi-
cations in the product description) additional, separate oil level monitoring is absolutely necessary to ensure a minimum oil level above the heating elements. To this end, a sepa­rate oil level switch is used in each use case according to the necessary explosion protec­tion specifications – see also the component specifications in the product description.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 29
7.2 Product code of screw compressor packages - Grasso SP1, SP2, SPduo and M Ser­ies
X
Model size screw compressor package
The ND screw compressor will be provided for the screw compressor packages in the Grasso SP2 series (two-stage).
Y Versions of the screw compressor package
9 Screw compressor version variations
A Oil cooling
(X1)
Screw compressor size HP side
Only for screw compressor packages in the Grasso SP2 series (two-stage).
X / (X1) Screw compressor package size
Code letter Theoretical volume flow
at 2940 min-1 in m³/h
Code letter Theoretical volume flow
at 2940 min-1 in m³/h
C 231
T 1460
D 265
V 1740
E 321
W 1940
G 372
Y 2390
H 471
Z 2748
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
30 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Code letter Theoretical volume flow
at 2940 min-1 in m³/h
Code letter Theoretical volume flow
at 2940 min-1 in m³/h
L 544
XA 3250
M 690 / 708
XB 4150
N 860 / 870
XC 4900
P 805
XD 5800
R 1040
XE 7170
S 1290
XF 8560
* Grasso M Series
Y Screw compressor package version
Design type Screw compressor package
Refrigerant
NH
3
Refrigerant
R22
HFC
Refrigerant
Refrigerant
R290 and
R600a
CO2 and
Special
media
Horizontal oil separator installed below A H R F O
Oil separator installed vertically B K S G P
Oil separator horizontally in series C L T
Grasso SPduo/ mechanical suspension D M V Y W
Grasso SP2 (two-phase) E N U
9 Screw compressor versions
1 Standard refrigerating compressor Vi = 1.8; 2.0; 2.2; 2.6; 3.0
2 Standard refrigerating compressor Vi = 3.6
3 Standard refrigerating compressor Vi = 4.8
4 Standard refrigerating compressor Vi = 5.5
5 Standard refrigerating compressor Vi = variable
6 Booster Vi = fixed
7 Heat pump compressor Vi = fixed or variable
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 31
8 -- --
9 Speed regulated Vi = variable
A Oil cooling
Code letter Oil cooling
A Water-cooled oil cooler
B Refrigerant cooled oil cooler
C Refrigerant injection
D Water and refrigerant cooled oil cooler
E Water or refrigerant cooled oil cooler and refrigerant injection
F Without oil cooler
Examples of designation
XA B - 6 A Singe stage screw compressor package Grasso SP1 with screw compressor 3250 m³/h
(XA), refrigerant NH3 and vertically installed oil separator (B), booster with fixed internal vol­ume ratio (6)with oil fine separation and water-cooled oil cooler (A)
T A - 2 A Singe stage screw compressor package Grasso SP1 or SSP1 with screw compressor 1460
m³/h (T), refrigerant NH3 and horizontally installed oil separator (A), fixed internal volume ratio Vi = 3.6 (2)
with oil fine separation and water-cooled oil cooler (A)
N A - 3 B Screw compressor package Grasso M with screw compressor 873 m³/h (N), refrigerant NH
3
and horizontally installed oil separator (A), fixed internal volume ratio Vi = 4.8 (3)with oil fine separation and refrigerant-cooled oil cooler (A)
LD - 2 A Screw compressor package Grasso SPduo with 2 of screw compressors 544 m³/h (L),
refrigerant NH3 and DuoPack version or multiple configuration (D), fixed internal volume ratio Vi = 3.6 (2) with oil fine separation and water-cooled oil cooler (A)
W E - 6 A (L) Two-stage screw compressor package with LP screw compressor 1940 m³/h (W), refriger-
ant NH3 two-stage package (E), LP-compressor as booster (6), with oil fine separation and water-cooled oil cooler (A), HP-compressor 544 m³/h (L)
7.3 Technical specifications
Packages / chillers are designed and manufactured for special fields of application. For technical specifi­cations see the following.
order specification,
list of parameters,
general assembly drawing,
P+I diagram.
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
32 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
7.4 Location of the product identification (name plate)
The type plate contains the most important technical data pertaining to the product. This data and the con­tractual agreements define the limits of designated use.
As standard, the type plate is fixed to the oil separa­tor (deviations of the location are possible).
fig.6: Location of the product identification (type plate)
fig.7: Type plate
GEA Refrigeration Germany GmbH
Contact data of the manufac­turer
Type: Type designation of the screw
compressor package
Serial no.: Serial number of the screw
compressor package
Year of construc­tion:
Year of construction of the screw compressor package
Weight without fill­ing:
Weight of the screw compres­sor package when empty
Refrigerant: Information regarding the
refrigerant used
Max. operating pressure:
Information regarding the max. operating pressure
Volume flow:
Information regarding the vol­ume flow
The default languages are English and German
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 33
7.5 Information and safety labels on the product
Danger!
The safety-related labels on the pack­age/chiller must be followed!
7.5.1 Labelling of the pressure and
temperature sensors, heater
(safety labels)
fig.8: Safety labels of the pressure and temperature sensors,
heater
Importance of the labels:
Before replacing pressure and temperature sensors without dip tube, it must be ensured that the pipes into which the sensors are mounted are not pressur­ised. The pressure-free state can be achieved by closing the shut-off valves before the sensor to be replaced.
Before replacing oil heater it must be ensured that the oil separator into which the oil heater is screwed in is not pressurised.
Hint!
Not applicable to oil heaters of the HLP type series.
7.5.2 Label of the safety valve
(safety labels)
fig.9: Label of the safety valve
Importance of the labels
The safety valve must be connected to a blow-off line.
7.5.3
Labels of the screwed connec­tions with DiNova ring
(handling instructions)
fig.10: Labels of the screwed connections
The informative label for all screwed connections with DiNova ring (handling instructions) is attached to the electric motor in a clearly visible manner.
Importance of the labels:
If any leakage occurs at a screwed connection (escaping gases or vapours), the screwed connec­tion must be tightened:
Counter-hold the screwed pipe connection using a wrench. Tighten the pipe nut about 1/4 to 1/
3
rotation beyond the point where the increase in the force if felt.
®
The leakage is remedied.
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
34 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
7.5.4 Labels of the pipelines
(information plate)
Pipelines in refrigeration plants must be labelled as follows (DIN 2405):
Refrigerant
Direction of flow
State of phase
fig.11: Labels of the pipelines
1 Arrow head (indication of the direction of flow)
2 Horizontal stripe (indication of the state of
phase), green = liquid // blue = gaseous cold // red = gaseous hot
3 Information field (label of the refrigerant)
7.5.5 Marking the direction of rotation of the compressor drive motor
(information plate)
fig.12: Marking the direction of rotation of the compressor drive
motor
The direction of arrow indicates the direction of rota­tion of the compressor drive motor
7.5.6
Marking the direction of rotation of the oil pump motor
(information plate)
fig.13: Marking the direction of rotation of the oil pump motor
The direction of arrow indicates the direction of rota­tion of the oil pump motor
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 35
7.5.7 Labels of the pressure gauge
(information plate)
fig.14: Labels of the pressure gauge
1 Description of the pressure gauge measuring
point
The description of the pressure gauge measuring point is attached directly underneath the pressure gauge. The gauge board can be arranged horizon­tally as well as vertically.
7.5.8 Labeling of the control / control cabinet
(information plate)
Label on the rear side of the control unit of the control system (visible after opening the switch­ing cabinet):
Project name
Make number of the package/chiller
MPI address
Label on the inside of the switching cabinet:
Test verification for the control system
fig.15: Test verification for the control system
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
36 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
7.5.9 Designation of the earth connec­tion
Safety labels
fig.16: Designation of the earth connection
Importance of the labels
Ensure that the product is properly grounded before start-up. Connect the earth connection. The neces­sary mounting hardware and cables are not included in scope of supply.
Hint!
The cross-section of the ground wire must be at least 10 mm². Alternatively, two separately installed and separately connected ground wire must be used, ensuring the minimum cross-section in the sum.
7.6 Process flow diagram
fig.17: Process flow diagram Grasso SP1, M-series
1 Suction side
2 Compressor
3 Oil separator
4 Pressure side
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 37
7.7 Main components
Screw compressor packages within the Grasso M-series series consist of the following main assemblies and components:
fig.18: Main components of the GEA Grasso M-Series
Hint!
The documentation of the main components is part of the product docu­mentation (see product description or operating manuals of the supplier, e.g. for the compressor drive motor).
10 Screw compressor See installation instructions for the screw com-
pressor
15 Compressor drive motor See operating manual of the compressor drive
motor
20 Oil separator See component documentation
25 OMC block (possible as separate oil filter for greater amounts of oil) See component documentation
30 * Oil cooler See component documentation
40 * Oil pump (possible as an external oil pump for booster) See component documentation
45 ** Suction filter See component documentation
55 ** Check valve - suction side See component documentation
60 Check valve - pressure side See component documentation
95 Coupling housing See component documentation
180 Controller See control unit documentation
360 * Oil heater See component documentation
Safety devices See component documentation
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
38 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
* not shown in the picture
** integrated into the screw compressor
7.7.1 Screw compressor
fig.19: GEA Grasso M-Series, arrangement of the SCP
The screw compressors are characterised by a com­pact design, high reliability, high quality components and ease of maintenance.
Screw compressors are dual rotor positive displace­ment machines that run according to the displace­ment principle and operate by oil injection.
Screw compressors are operated with refrigerant (standard: ammonia NH3, other refrigerants upon
request). For the refrigerant, refrigerating machine oil is chosen in accordance with lubricating oil informa­tion for screw compressors.
Various series and sizes of screw compressors are available for different fields of application.
The screw compressors are driven directly by the compressor drive motor via a flexible coupling.
Hint!
The documentation of the screw com­pressor (installation instructions, part lists, drawings) is an integral product documentation.
7.7.2 Compressor drive motor
fig.20: GEA Grasso M-Series, arrangement of the compressor
drive motor
Standard: The compressors are driven via a cou­pling by means of an air-cooled 2-pole IP23 electric motor with an operating voltage of 400 V; 50 Hz.
Option: Other protection classes, operating voltages and frequencies as well as speed-controlled motors are available on request.
Hint!
The documentation of the electric motor (operating manual) is an integral part of the product documentation.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 39
7.7.3 Compressor with coupling hous­ing
fig.21: GEA Grasso M-Series, arrangement of the coupling
housing
The coupling housing contains the coupling and is used for the attachment of the compressor drive motor. The elastic design of the coupling brings about the neutralisation of otherwise disturbing influ­ences such as axial or radial forces, vibrations or off­set.
Speed fluctuations and speed shocks are damped and cushioned, torsional vibrations are reduced.
Hint!
The documentation of the coupling is a part of the product documentation.
7.7.4 Oil separator
fig.22: GEA Grasso M-Series, arrangement of the oil separator
The design of the oil separators is standardised and features reduced oil carry-over and low oil consump­tion.
The oil separator is installed horizontally.
Hint!
The documentation of the oil separator (operating and maintenance instruc­tion, acceptance certificate) is a inte­gral part of the product documenta­tion.
Oil heater
Electric oil heaters are built into the oil separator to heat the oil refrigerant mixture in the oil separator during the standstill of the screw compressor pack­age. The oil heater prevents condensation of the refrigerant into the oil and, thus, any foaming of the oil during start-up.
Oil heaters are equipped with:
Temperature controller for protection against overheating
(Switching temperature 110°C)
Temperature limiter in case of faults, e.g. pro­tection against dry running
(permanently set to 150°C)
The oil heater is switched on when the screw com­pressor package is stopped and is switched off auto­matically on starting. A manual switch-off for long standstill periods is recommended.
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
40 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Hint!
The documentation of the oil heater (operating and maintenance instruc­tion, acceptance certificate) is a part of the product documentation.
7.7.5 OMC block with oil filter system
fig.23: GEA Grasso M-Series, arrangement of the OMC block
with oil filter system
The OMC block contains the oil distributor system in the oil circuit. Necessary control and shutoff fittings are integrated in the OMC-block. Connections for temperature and pressure sensors as well as service ports are present. The OMC block is combined with a standardised filter system and oil pump unit and forms the central control and regulation unit within the oil circuit.
Optionally, the OMC-block can be equipped with a 3­way valve element (for ensuring a minimum oil tem­perature when starting the compressor).
Hint!
The documentation for the OMC block (operating manual, acceptance certifi­cate) is an integral part of the product documentation.
7.7.6 Oil cooler
fig.24: GEA Grasso M-Series, arrangement of the oil cooler
The oil cooler is used for cooling the oil heated in the compressor in order to ensure sufficient oil viscosity for supplying to the compressor.
Hint!
The documentation of the oil cooler (operating manual, acceptance certifi­cate) is an integral part of the product documentation.
7.7.7 Oil pump (optional)
Special design for minor pressure differences (booster)
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 41
fig.25: GEA Grasso M-Series, arrangement of the (optional) oil
pump
The oil pump is an important component of the oil circuit. It is used for pumping and distributing refrig­erating machine oil.
The oil pump ensures that the oil is distributed to the individual lubrication points (e.g. journal bearing, bal­ance piston and packing gland of the compressor).
Hint!
The documentation of the oil pump (operating manual, acceptance certifi­cate) is an integral part of the product documentation.
7.7.8 Suction filter - check valve com­bination
fig.26: GEA Grasso M-Series, suction filter - check valve com-
bination
The suction filter - check valve combination contrib­utes substantially to the high working reliability of the components and the overall product.
The suction filter - check valve combination prevents dirt particles carried by the suction flow from entering into the screw compressor.
Hint!
The documentation of suction filter ­check valve combination is an integral part of the compressor documenta­tion.
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
42 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
7.7.9 Controller
fig.27: GEA Grasso M-Series, arrangement of the controller
The screw compressor package is equipped with a GEA Omni™-type controller.
The GEA Omni consists of the control unit with oper­ator keypad and display unit, indicator lights for "Running", "Warning" and "Alarm", the emergency stop button, the output relays and the casing.
The GEA Omni is mounted directly on the package as standard. As an option, the GEA Omni can be installed in a control centre.
The GEA Omni performs the following functions as standard:
Display of all important physical and technical parameters, e.g. Pressure, temperature, motor current, capacity, number of operating hours, operating mode and status signals
Automatic start up and shut down of the screw compressor package and capacity control dependent on the suction pressure or an exter­nal temperature,
Monitoring of all operating parameters
Compressor capacity limitation, in case the measured discharge pressure, suction pressure, secondary refrigerant temperature or motor cur­rent indicate overload
Fault memory with date and time
Wire failure detection for all analogue input sig­nals
Password protection for preventing unauthorised access to important parameters
Non-volatile saving of program
Possibility of communication with master control­ler via MPI
(optionally via Profibus-DP, Modbus RTU or Modbus TCP)
Hint!
The documentation of the controller (operating manual, circuit diagram, parameter list, communication guide­line) forms part of the product docu­mentation.
7.7.10 Fittings
The term fitting generally designates a control ele­ment of the machine. Among other things, the term fitting is also used for valves if these are used for the control and regulation of fluid flows in the piping.
Furthermore, all kinds of installations in piping, such as sight glasses, measurement apertures, filters and similar are also designated as fittings. Therefore, fit­tings also include all kinds of valves, such as:
Stop valves
Check valves
Safety valves
Throttle valves
Each fitting has its own field of use, according to the pressure or temperature in the pipe, the size of the pipe, the sealing requirements for the fitting, the reduction and direction of the flow of liquid as well as the medium itself.
The safety fittings are used to limit the pressure in systems which are under pressure.
Each fitting is designed for the specific application. The fittings can be operated manually or by motor,by gear motors, or pneumatic or hydraulic cylinders, for example. In reset fittings, the flow of fluid in the pipe causes automatic closing of the valve.
Depending on the model, different closing elements (e.g.valve discs, flaps, pushers) close the pipe con­nected to the fitting.
Hint!
The documentation of the fittings (acceptance certificates) forms part of the product documentation.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 43
7.7.11 Safety devices
The following safety devices are fitted onto the SCPs of the GEA Grasso M-series type series:
Drive motor safety devices Rated current limitation (016)
The rated current limitation is realised by the com­pressor control system: When the rated motor cur­rent is exceeded, the control slide of the compressor is driven in the MIN direction until the motor current reaches a permissible level. The normal output con­trol then comes back into force.
Thermistor (017)
The thermistor shuts down the compressor drive motor when the temperature of the compressor drive motor windings exceeds the allowable value.
Pressure-controlled check valve integrated into the compressor (055)
The check valve function prevents pressure equali­sation with the LP side of the plant and simultaneous prevents a reverse rotation of the screw compressor.
Check valve - pressure side (060)
The pressure side check valve prevents refrigerant from re-condensing in the oil separator.
Oil pressure regulating valve (075)
The oil pressure control valve regulates the differen­tial pressure between the oil pump discharge side and the discharge pressure of the package. The oil pressure control valve is integrated into the OMC­block (oil management centre).
Safety device to prevent the discharge pressure from being exceeded (pressure transducer 105)
The compressor control system switches off the screw compressor package when the specified limit value has been exceeded.
Limit value = see parameter list
Safety device to prevent the differential pressure between the oil pressure after oil pump (pressure transducer 110) and the discharge pressure (pressure transducer 105) oil circuit monitoring from falling too low
The compressor control system switches off the screw compressor package when the pressure differ­ence between oil pressure after oil pump and dis­charge pressure falls below the specified limit value after a delay period.
Limit value = see parameter list
Safety device to prevent the discharge tempera­ture from being exceeded (resistance thermome­ter 120)
The compressor control system switches off the screw compressor package when the specified limit value has been exceeded.
Limit value = see parameter list
Safety device to prevent the oil temperature from being exceeded (resistance thermometer 125)
The compressor control system switches off the screw compressor package when the specified limit value has been exceeded.
Limit value = see parameter list
The minimum oil viscosity for safe compressor oper­ation is ≥ 7 cSt. In case of oils that are soluble in refrigerant, the minimum oil viscosity is to be ensured depending on the discharge pressure and temperature, oil temperature, as well as the type of oil.
Overflow valve (340)
The overflow valve protects the compressor against impermissible high pressure. The overflow valve (provided that delivered unassembled) must be con­nected with the suction pipe on site.
Triggering pressure = see parameter list and P+I flow chart
The overflow valve is designed in accordance with DIN EN 13136 "Refrigerating systems and heat pumps - pressure relief devices and associated pip­ing - methods for calculation".
Warning!
If not fitted on delivery, the overflow valve must be connected to the suc­tion side when installing the SCP in the refrigeration plant!
Safety valve (345) on the oil separator
The safety valve protects the screw compressor package against impermissible high pressure.
Triggering pressure =
see parameter list and P+I
flow chart
If the screw compressor package is installed into a refrigeration system comprising an emergency blow­off station, only the oil separator connection is used.
The valve is available as an option, depending on the required acceptance.
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
44 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
The safety valve is designed in accordance with DIN EN 13136 "Refrigerating systems and heat pumps ­pressure relief devices and associated piping - meth­ods for calculation".
Safety pressure limiter (350)
Safety pressure limiter with two separate trigger con­tacts, one of which can only be reset using a tool. The safety pressure limiter switches off the compres­sor drive motor if the discharge pressure rises above the set point.
Switching off pressure 1 = see parameter list Switching off pressure 2 = see parameter list
If it cannot be ruled out that the liquid refrigerant might attain more than 90% of the oil separator’s vol­ume, then the customer must install an additional safety valve to prevent expansion of the liquid in the oil separator (design in accordance with DIN EN 13136, arranged according to EN 378-2 Annex F).
7.7.12
Monitoring devices
The following operating values will be continually monitored in a standard screw compressor package:
Suction pressure
Discharge pressure
Oil pressure oil circuit monitoring
Suction temperature
Discharge temperature
Oil temperature
absolute primary slide position
Motor current
Suction pressure saturation temperature
Saturation temperature of condensing pressure
Number of running hours
Difference between oil and discharge pressures (oil circuit monitoring)
Set point of controled value in °C
Real point of controled value in °C
Internal volume ratio
Used refrigerant
Controled value
Used options
Oil pressure after oil filter - optional -
Differential pressure of oil pressure after oil filter and discharge pressure (oil filter monitoring) ­optional -
7.7.13 Components installed by the cli­ent
Warning!
The components and parts the cus­tomer installs in particular the secon­dary refrigerant and cooling medium circuits as well as the oil circuit need to made from materials suitable for the fluids flowing through them. Further­more, in the event of modifications to the product by the customer, the effects on the safety devices are to be checked.
GEA Refrigeration Germany GmbH does not assume any liability for dam­age arising and the violation of the safety regulations which result from the use of unsuitable materials or through modification to the product which is not considered in the original safety concept.
7.8 General functional description
Screw compressor packages are refrigeration sys­tem components and serve to compress refrigerants such as ammonia (or other operating media on request).
Operation as a heat pump is also possible.
7.9 Refrigerant circuit
The screw compressor draws in refrigerant vapour via the suction check valve and suction filter and then discharges the compressed vapour into the plant via the oil separator and discharge check valve.
The suction-side check valve prevents a sudden pressure equalisation with the low pressure side of the chiller, while also preventing reverse rotation of the screw compressor.
The pressure side check valve prevents refrigerant from re-condensing in the oil separator.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 45
Hint!
The discharge check valve can be inte­grated into the oil separator for screw compressor packages with discharge side nominal diameters up to NB 150.
The suction filter prevents dirt particles carried by the suction flow from penetrating into the compressor. The filter element is characterized by a very large fil­tering area. The filter fineness is 140
μm.
Gas vibrations which can arise in the pressure cham­ber of compressors under high pressure conditions in the range of zero delivery are prevented by a gas vibration protection system. This comprises a pres­sure compensation line between the oil separator and the working chamber of the compressor.
7.10 Oil System
The screw compressors operate oil-flooded. During the compression process, refrigerating machine oil is supplied to the compressor for lubrication, sealing, noise reduction, and absorption of part of the com­pression heat. After the compression process, the oil is separated again from the refrigerant in the oil sep­arator.
7.10.1 Oil separation
The refrigerant-oil mixture is led into the first part of oil separator. The first part of the oil separator con­sists of two chambers. The first chamber employs gravity separation. The hot gas passes the demister while flowing out of the first chamber into the second chamber. The oil separated thereby is collected in the second chamber. Both the chambers of the first part of oil separator simultaneously serve as oil receivers.
In the second part of the oil separator, the fine sepa­ration of the aerosol oil portion from the refrigerant is performed by means of replaceable fine oil separa­tion cartridges. The oil separated in the fine separa­tion part of the oil separator is returned to the com­pressor via an additional orifice.
7.10.2 Oil heater
The oil heater on the oil separator is to be started when the package is shut down in order to ensure a minimum oil temperature and sufficient oil viscosity required for restarting the package. The oil heating is
not regulated. The maximum temperature of the heating rod is restricted.
7.10.3 Oil cooling
Before it is returned to the compressor for use, the oil heated up in the compressor has to be cooled down to a temperature at which it has sufficient vis­cosity.
The following oil coolers are available:
1.
liquid-cooled (non corrosive media)
water (non corrosive)
propylene glycol (25%)
ethylene glycol (35%)
Other refrigerants on request
2.
Thermosiphon
3.
Refrigerant injection
7.10.4 Oil filter
After cooling, the oil enters the oil filter which retains solid particles from the entire oil flow.
Due to its large surface, the star-folded glass fibre element has a high absorbing capacity and thus a long operating lifetime. The filter has a relative filter fineness of 25 µm.
7.10.5 Oil pump
The oil pump runs for pre- and during compressor operation.
It draws the refrigeration compressor oil from the receiver space in the oil separator, through the the oil cooler and oil filter and pumps it to the bearings, the balance piston, the shaft seal, to the capacity control system and, if fitted, to the compressor's hydraulic Vi adjustment system.
The oil pump pumps more oil than the compressor uses. This surplus quantity of oil is returned to pump suction via the spring loaded oil pressure regulating valve. The oil pressure regulating valve regulates a pressure difference between the oil pump discharge side and the unit final pressure (according to the value in the P+I diagram).
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
46 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
7.10.6 Oil injection
The injection oil is fed without a pump via the oil injection regulating valve.
The oil injection control valve is used to adjust the necessary compression discharge temperature.
The control valve is provided with a check function to prevent sucking refrigerant through the oil pump.
7.10.7 Oil circuit, OMC block
An OMC-block (oil management block) is flanged on to the oil filter as an oil distributor system. The oil flow is distributed via the bore-holes and channels to functional ranges of the screw compressor. All regu­lating valves and shut-off valves necessary for the regulation of the oil circuit are integrated into the block. As a result, a centralised control unit is availa­ble for the screw compressor package.
The oil filter with OMC-block (oil management block) is fitted with an oil drain and refilling stop valve which may be connected to a separate oil pump or receiver.
Vent valves are fitted to oil filters for maintenance and repair purposes.
The oil in oil filter may be drained for changing oil fil­ter via a separate stop valve.
7.11 Capacity control
The screw compressors are fitted with a continuous capacity control with a range of 10 -100%.
The capacity is adjusted by shortening the screw compressor stroke. The defining factor for the com­pression process is the effective rotor length; this is altered by a hydraulically operated control slide.
The position of the control slide is recorded by the position sensor. Upon reaching the MIN or MAX end position, it is signalled to the control device and the relative control slide position can be displayed in per­centage on the touch panel.
The hydraulic adjustment of the control slide is real­ised using solenoid valves, which are integrated into a single block.
The control slide travel speeds in the MIN and MAX directions should, to the extent possible, be the same during operation to ensure better compressor control.
7.12 Technical specifications
7.12.1 Designed for use in explosive atmospheres!
Danger!
When operating the screw compressor package in explosive atmospheres, the special safety instructions for use in explosive atmospheres that are men­tioned in this operating manual must be heeded.
Hint!
The screw compressor packages can basically be used in explosive atmos­pheres.
Some specifics must be heeded when using the screw compressor packages in explosive atmos­pheres of installation zones 1 and 2.
The basis for use in explosive atmospheres is the following data of the operator:
Zone division as per EN 60079-10 (or other equivalent international standards),
description of the atmosphere (required gas groups),
required temperature class.
This data is stored in the request sheet for project 055 100A. The 055 100A request sheet is part of the product documentation.
For using and placing a screw compressor package into operation within the EU, the package is manu­factured ATEX-compliant (see component selection, protection systems, regulations, etc.)
The following marginal parameters generally apply:
The screw compressor packages can be instal­led in Zones 1 and 2 in accordance with EN 60079-10.
The max. achievable temperature class is T4.
The screw compressor packages are not suita­ble for carrying explosive mixtures; the suction pressure of the package is always in the over­pressure range.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 47
7.12.2 Basic terms
Refrigerant Materials circulating in a plant (liq-
uid or gas), which by means of their change of state of the pack­age withdraw heat from another medium (cooling or heating agent) or can dissipate heat to this medium.
Secondary refrigerant
Fluids that can absorb the heat of a system and dissipate it to a refrigerant (reversible process) and are used for the cooling of a system (industrial process)
Heating agents
Media (liquid or air), which trans­port and emit the heat absorbed in the secondary refrigerant. If water is used as the heat carrier, the terms warm water or cooling water are also used.
7.12.3 Operating media
7.12.3.1
Refrigerant
The technical order specification defines the refriger­ant used. All components of the screw compressor package are designed for use with the defined refrig­erant.
Hint!
The safety data sheet for the refriger­ant used must be observed. The safety data sheet is part of the product docu­mentation.
7.12.3.2 Refrigeration machine oils
Caution!
In order to ensure an adequate load­bearing capacity of the sleeve bear­ings and to ensure the service life of the roller bearings, a minimum viscos-
ity of 7cSt (=10-6 m²/s) upstream of the compressor is required. A suitable oil must be carefully selected in consider­ation of the operating conditions.
The selection criteria and selection tables are summarised in the technical information document entitled "Lubri­cant oils for screw compressors". This technical information forms part of the product documentation.
GEA Refrigeration Germany GmbH can provide assistance in the selection of a suitable refrigeration machine oil on request.
7.12.3.3 Secondary refrigerant
Low corrosion water
Permitted brine levels: see Grasso Design Pro­gram
Hint!
For other secondary refrigerants, com­patibility with the materials used must be ensured.
7.12.4 Operating limits
The screw compressors can be operated under the most varied operating conditions within the given lim­its of application according to the requirements involved. The limits of application listed below for the screw compressors are based on the operational principle of the screw compressor and thermody­namic ratios and are based on practical operating conditions and design. The tabulated data apply for single, two-stage and heat pump operation. Depend­ing on the compressor the manufacturer selected, the specific operating conditions limitations may occur within the parameters in the table.
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
48 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Hint!
For specific operations the selection and evaluation will take place within the manufacturer's compressor selec­tion programme.
Caution!
To avoid "zero flow" in the compres­sor, which can damage the compres­sor, the minimum control slide posi­tion in the manufacturer's compressor selection programme must be adhered to.
"Minimal control slide position <value> % accepted start."
If the value entered is "> 0", then a lim­itation of the control slide path must be put in place in coordination with the manufacturer. The path limitation can be set created mechanically with a stop sleeve or by installing virtual con­trols (virtual stop sleeve) on the com­pressor.
Maximum permitted pressure p bar g. max.
≤28 bar
or
≤52 bar
Pressure ratio p / p
0
π - min. > 1.5
Pressure difference (p - p0)
Δp bar min. > 0.8
Suction temperature t0 (compressor inlet) t
0h
°C min. > - 60
Discharge temperature (compressor outlet)
t
e
°C max. < 120
Compressor frame size
H L
M/N
*)
28 bar
M/N
*)
52 bar
max. Drive power (kW)
50 Hz
60 Hz
300
360
300
360
300
360
530
640
max. Nominal torque
**)
Nm 960 960 960 1700
max. permissible speed
min
-1
4500 4500 4500 4500
min. permissible speed
min
-1
1000 1000 1000 1000
*)
For type M/N, the compressor drive shaft ends are different for 28 bar and 52 bar versions.
**)
When running the compressor, the maximum torque falls by 25% as opposed to electrical drives.
Hint!
All of the following requirements must be observed!
1.
Compressors for a discharge pressure up to 52 bar (currently not available) are equipped with housings made of a material of higher strength and are fitted with special components.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 49
2.
Minimum suction overheating in compressor inlet: "wet" operation is not possible.
3.
For Δ p = p - po ≤ 2.9 bar an external oil pump to be taken for compressor sizes H to N.
4.
For
π ≥ 8 gas vibration protection is required.
5.
For CO2 usage the use of a completely electri­fied oil pump for injection and function oil needs
to be checked in all types of compressors depending on the operating conditions;
6.
The discharge temperature te must be 10 K above the condensing temperature (te ≥ tc + 10 K).
7.
Due to the solubility of refrigerant in the oil fol­lowing applies:
for Ammonia:
te ≥ t
oil
+ 5 K;
te ≥ t
oil
+ 10 K,when using a PAG oil (solubil-
ity of the refrigerant in the oil).
For R22, R134a, R404A, R407C, R410A, R507, CO2, natural gas, carbohydrate mole­cules:
te ≥ t
oil
+ 10 K, wherein solubility of the
refrigerant in the oil.
To determine the permitted difference between the discharge temperature (te)
and oil intake temperature (t
oil
) the set
viscosity and the solubility diagram for the refrigerant-oil pair from the lubrica­tion supplier need to be adhered to.
8.
Ensure that the oil viscosity will be ≥7...70 cSt (= 10-6 m²/s) for the oil supply to bearings. Take
into account the drop in viscosity due to refriger­ant dissolved in the oil!
9.
Limits for temperature differences will be consid­ered in compressor selection programs.
10.
The oil temperature at the compressor inlet must be at least 18°C, the oil must be preheated if necessary.
11.
The rate of temperature change at compressor suction side should not exceed 0,1 K/s.
12.
Rotation direction: view of compressor’s driving shaft clockwise.
13.
For individual cases outside the permitted speed coordination needs to made with the manufac­turer.
p
p
0
Δp
π
t
0h
t
e
t
c
t
oil
Maximum permitted pressure
Suction pressure
Pressure difference
Pressure ratio
Suction temperature (compressor inlet)
Discharge temperature (compressor outlet)
Condensing temperature
oil inlet temperature into the compressor
Notes:
1.
During tests of a certain application case, all the conditions specified in the table must be consid­ered and adhered to.
2.
Should the given limits not be adhered to in indi­vidual cases, then the manufacturer needs to be contacted.
3.
In addition to the application limits stated in the tables, the applicable operating conditions of the compressor type in question must also be con­sidered (e. g. start-up regime, oil pressure, oil quantity etc.).
4.
Depending on the refrigeration requirements, economiser operation takes place at a control slide position between 100% and approx. 70% control slide position.
5.
When using R134a as a refrigerant and a evap- orating temperature > 60 °C consultation with the manufacturer must be made.
7.12.5
Water quality requirements, parameters
All water bearing components from the manufacturer deliver an optimum performance and provide maxi­mum protection from corrosion, provided you meet all of the limiting values recommended in VDI 3803 issue 2010-02 (Tab. B3) for non-corrosive water and adequate water conditioning.
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
50 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Hint!
If you fail to adhere to the limiting val­ues stated in VDI 3803, the manufac­turer cannot provide any warranty for water carrying parts within its supplied components.
Clarification as to whether or not it is possible to adhere to these limiting values with the respective water condi­tions should be agreed on with a spe­cialist company during the planning and design phase.
The limiting values as per VDI 3803, as required for the use of carbon steel components in non corrosive water systems, are listed below.
Water quality requirements, parameters
Criterion
Value Unit
Appearance
clear, with-
out sedi-
ment
Colour
colourless
Odour
none
pH level at 20 °C
7.5 - 9.0
Electrical conductiv­ity
LF < 220 mS/m
Soil alkali
Ca2+,
Mg
2+
< 0.5 mol/m³
General hardness, for stabilization
GH < 20 °d
Carbonate hard­ness without hard­ness stabilizer
KH < 4 °d
Chloride Cl < 150 g/m³
Sulphur
SO
4
< 325 g/m³
Water quality requirements, parameters
Criterion
Value Unit
Active biological components
KBE < 10,000 per ml
Thickness factor EZ 2 - 4
The use of carbon steel and cast iron is required in the most of applications water conditioning with cor­rosion inhibitors.
The use of stainless steel requires very special moni­toring of water in apply to Chloride contents (risk of stress crack and pitting corrosion).
Hint!
Recommend when using plate heat exchangers in the refrigerant circuit
< 100 ppm Cl while using steel 1.4301 and
maximum 40°C wall temperature in the plate heat exchanger
< 200 ppm Cl while using steel 1.4401 and
maximum 100 °C wall temperature in the plate heat exchanger
fig.28: Corrosion resistance in presence of chlorides
X
Chloride ion concentration in ppm Cl
-
Y Wall temperature heat exchanger in °C
A AISI 304
B AISI 316
C SMO 254
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Description of Design and Function
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 51
Hint!
Manufacturer's recommendation: Use uncontaminated secondary refriger­ants and cooling media, in particular in chillers and when using of plate heat exchangers.
The media quality must be assured by means of an appropriate filter on the inlet to the heat exchanger. The mesh for such a filter must be
≤ 0.9 mm!
Should the chiller be required to remain in operation during filter clean­ing, double filters must be used. Pres­sure loss through the filter must be taken into consideration on the build­ing side when configuring the pump.
The manufacturer recommends enlisting the services of a reputable water conditioning company.
Description of Design and Function Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
52 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
8 START-UP
8.1 Important information for start-up
Warning!
Contact with live components is pro­hibited.
Hint!
The Customer Service department of GEA Refrigeration Germany GmbH offer comprehensive support for start­ing up the screw compressor package. For contact details, please refer to the chapter entitled "Technical customer service".
Warning!
The screw compressor package must only be operated by suitably skilled personnel who are familiar with the contents of the operating manual for screw compressor packages.
The safety regulations for refrigeration plants must always be observed in order to prevent damage to the screw compressor package and injury to the operating staff.
The screw compressor packages are tested and accepted at the works. By the time these screw compressor packages are delivered to the cus­tomer, the following work will have been carried out:
Complete installation of the cooling system and in particular:
cleaning and drying the refrigerant and oil circuits
Leak test with air
Evacuation of the refrigerant circuit and filling with protective gas (nitrogen) to a pressure of 0.3 to 0.5 bar (above atmospheric)
Electrical wiring and testing of the wiring
Factory setting for the parameters on the control
Factory setting of the safety and monitoring devi­ces
Works trial runs (at the request of the client)
The following points must be observed before commencing with the start-up:
Check of the external condition of the screw compressor package (check of insulation, trans­port damage... ).
The area around the machine in which the start­up is carried out must be marked and secured against the access of unauthorised persons. Suf­ficient lighting of the working area must be ensured to prevent personal injury and material damage.
Personal protection gear (work clothing, work boots, gloves) must be worn during all work on the screw compressor package. There is a dan­ger of impact and stumblingfrom protruding parts on the screw compressor package (e.g. valve caps). There is also the danger of cut wounds on sharp edges and rough surfaces. All activities must therefore be carried out with particular attention.
Suitable hearing protection must be worn in order to protect against damage to hearing or deafness.
Thermal hazards resulting in injuries due to burns or freezing may occur on contact with parts of the system which are at a very high or very low temperature. Personal protective equip­ment must be worn.
Suitable tools or special tools must be used.
Check that all electrical work has been carried out in accordance with the standards (e.g.protec­tive earth, insulation, shielding, covers). If neces­sary, an earth connection must be provided.
Pipes and pipe sections must be secured to ensure sufficient mechanical strength. The pipes and equipment of the screw compressor pack­age must not be entered.
Operating media (nitrogen, oil, refrigerant) can escape. Preventive measures must be taken to collect and dispose of them in an environmen­tally responsible manner (e.g.using an oil pan). Personal breathing protection must be kept ready in the event of a refrigerant leak. The safety data sheets of the oil and refrigerant used must be read prior to commencing start-up work. Familiarise yourself with the evacuation plan of the installation location.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Start-up
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 53
Danger!
Solid mounting of the coupling protec­tion must be checked. Start-up must not be carried out with the coupling protection mounted.
Check the protective gas filling (a positive pres­sure ≥ 0.2 bar must be present)
Hint!
If defects are found, notify GEA Refrig­eration Germany GmbH Service and proceed according to their instruc­tions.
8.2 Basics
The compressor must only be switched on if the screw compressor package has been correctly con­nected and filled with operating materials.
The activities described in this "Start-up" chapter must be carried out in the prescribed sequence.
The screw compressor package is operated via the terminal of the control unit.
After the target values have been entered, both auto­matic and manual operation are possible.
The software of the control device and operation via the terminal are described separately in the operat­ing manual for the control system.
8.3 Connecting the screw compressor package
Caution!
All mechanical connections must be made according to the R+I diagram which is valid for the project. The R+I diagram is part of the product docu­mentation.
Caution!
All electrical connections must be made according to the circuit diagram which is valid for the project. The cir­cuit diagram is part of the product documentation.
Check that components which have been removed for transport, separately delivered components and components provided by the customer are firmly attached.
Check that all locating bolts are tight.
8.3.1
Connecting the pipes
The nitrogen filling of the screw compressor package must be purged by opening the vent valves before the connection of the pipes.
Establish all pipe connections so that the transmis­sion of thermal expansion and vibration to the screw compressor package is limited as far as possible.
Bellows-type expansion joints made of steel, or flexi­ble metal hoses can be used for refrigerant and oil lines, bellows-type expansion joints made from rub­ber can be used for water connections.
Provide all pipe connections directly at the unit with fixed points.
Connection of:
Suction line
Pressure line
Oil cooler water connection
If units are equipped with a safety valve: Con­nect safety valve to the blow-off line.
Integrate relief valve in the suction line.
if units are equipped with a refrigerant cooled oil cooler:
Connect the refrigerant feed line from h.p. receiver (note geodetic height above oil cooler).
Connect the evaporated refrigerant line to the condenser
If refrigerant injection is used: Connect the refrig­erant feed line from condenser or h.p. receiver
If an economiser is used: Connection the suction line of the economiser to the charge connection.
Start-up Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
54 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Hint!
In principle, all the connections must be made in accordance with the P+I diagram applying to the respective project. Attach the pipes to the screw compressor package in such a way that no additional static or dynamic loads are imposed.
All the pipes and systems to be con­nected must be checked for leaks when the work is complete.
8.3.2 Electrical connection
Danger!
Contact with live components is pro­hibited.
The screw compressor package has been designed for plug-in and reliable automatic operation.
All connections must be carried out according to the current installation regulations.
Connections to the screw compressor package must be flexible and free of loads.
Hint!
Dimensioning of the inlet pipe cross­sections must be according to DIN VDE 100 Part 520.
Before starting work, make sure that all parts to be connected are de-energised, e.g. by removing the main fuse in all phases or installing a jumper wire. The insulation resistance of the electrical tools and fixtures and wiring is to be checked. The connection may only be undertaken if this value lies in the allow­able range.
Connections and almost all external connections are pre-wired at the factory.
Warning!
Produce the earth connection accord­ing to the designation in the general assembly drawing. See chapter "Des­ignation of the earth connection".
The electrical consumers and sensor must be con­nected according to the circuit diagram. All electrical connections must be made according to the circuit diagram, e.g.
Compressor drive motor
Compressor control supply
Oil heater
Oil pump
Some external components, such as the second EMERGENCY STOP switch, the ammonia sensor and the fans of the machine room, must be connec­ted by the system erector on site.
Hint!
Check that terminal screws (in the switching cabinet) are tight.
8.4 Paint and insulation
Damage to the paint and insulation during transport and installation must be carefully repaired.
8.5 Start-up procedure
The following procedures should be completed in the sequence in which they are described:
8.5.1 Checking the electrical connec­tion
Danger!
Contact with live components is pro­hibited.
Check that all electrical work has been carried out in accordance with the standards (e.g.protective earth, insulation, shielding, covers). If necessary, an earth connection must be provided.
8.5.2
Leak test
Hint!
See type plate for permissible operat­ing pressure.
The necessary safety precautions should be taken before performing the leak test.
An approx. 3-hour pressure drop test with dry nitro­gen is used for the test. Test pressure: 7 bar
A pressure drop of 2% is allowed during the 3 hours. Fluctuations in the ambient temperature must be taken into account.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Start-up
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 55
Caution!
Checking devices which could be damaged by the specified test pres­sure must be removed or blocked before the leak test is performed.
A record should be kept of the pressure test, noting the pressure in the pipes tested, the ambient temper­ature and the outside temperature in the shade at hourly intervals.
The removed measuring and control instruments should be reinstalled after completion of the leak test and if there are no leaks in the package/chiller.
Test strategy
Dry nitrogen is used as the test medium. After reach­ing the test pressure, the pressure drop is measured via the differential pressure measurement. This may only change by 0.02 bar within an hour. If the display device does not indicate a leakage through foam for­mation, the system is sealed.
Testing devices
A pressure gauge with an accuracy of 0.5% over the entire measuring range, with a digital resolution of
0.01 bar must be used for the measurement.
The testing described here is based on pressure gauges with pressure gauge and LEAK mode from Keller.
Display devices
A foaming agent must be used as the means to indi­cate leakages. A solution of 50 parts water and 1 part detergent can be used as the foaming agent. Leaks are detected through formation of foam. A leak detection spray can be used in problem areas.
Carrying out the test
1.
Wet all connecting joints (welded seams, flange connections, screw fastenings, etc.) with foaming agent. Remedy any leaks detectable from the noticeable formation of foam.
8.5.3
Drying, vacuum
After the leak tightness test has been completed, the plant must be evacuated and undergo a vacuum test for 3 hours. Evacuation is used to remove air and moisture from the plant.
A vacuum pump must be used for evacuation.
The permissible increase in vacuum is maximum
6.66 mbar over a period of 3 hours.
fig.29: Vacuum required to remove moisture from refrigerating
plants
X Room or Wall temperature in °C
Y Vacuum in mbar
A Vacuum required to remove moisture from
refrigerating plants
Measured values have to be checked and recorded hourly after reaching the required vacuum. After the vacuum pressure, the temperatures in the machine house and the outdoor temperature in shade must be entered in the log. After the vacuum test, the pressure compensation must be carried out with NH3.
Warning!
Shut the oil pump during evacuation!
See also "Evacuation on refrigerant side" in the chapter "Maintenance work".
Start-up Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
56 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
8.5.4 Operating position of valves
For the positions of the manually controllable fittings for the operation of the package/chiller, see the P+I dia­gram.
The layout and symbols used in the P+I diagram comply with the specifications of EN 1861, July 1998 Issue.
Caution!
The valves must be in operating position prior to the start-up of the package / chiller. Trouble­free operation is only possible in this manner!
fig.30: Stop valve open
Stop valve open during normal operation
fig.31: Stop valve closed
Stop valve closed during normal operation
fig.32: Check valve
Check valve during normal operation
fig.33: Shuttable check valve
Shuttable check valve open during normal operation
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Start-up
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 57
fig.34: Control valve
Control valve adjusted:
Start-up
when operating conditions change
fig.35: Shuttable check valve with integrated control function
Shuttable check valve with integrated control function open dur­ing normal operation
fig.36: Solenoid valve
Controlled by the controller (e.g. GEA Omni)
fig.37: Change-over valve
Change-over valve (3-way valve), opened from below in arrow direction
fig.38: Oil pressure control valve
Operating position: shut Δp x,x ± x bar control pressure to be set vis-à-vis reference pres-
sure (see P+I diagram)
Caution!
An oil pressure being set too high or too low may result in serious compressor damage or even the total breakdown of the compressor after just a short period of operation!
Start-up Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
58 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
fig.39: Overflow valve, safety valve
Overflow valve, safety valve
fig.40: Pressure controlled check valve
controlled self-sufficient
fig.41: Quick acting valve, spring-loaded
manually operated if necessary
fig.42: Charging valve, drain valve
½” connections
with cap
fig.43: Service valve
Connection Rp ¼”
For pressure gauge and pressure transmitter
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Start-up
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 59
fig.44: Oil temperature limiter
controlled autonomously using control element
fig.45: Temperature controlled control valve
Autonomous control via sensor
8.5.5 Oil charge
Caution!
Check the oil grade to be charged! See contract/project or recommendation of GEA Refrigeration Germany GmbH. A comprehensive overview of the allowa­ble oil types is provided in "Technical information on lubricating oils". This technical information is part of the product documentation.
For severely hygroscopic oils, the oil container must be placed under a pro­tective atmosphere.
The vacuum present in the screw compressor pack­age before pressure compensation may be utilised for charging the package with oil. A separate oil charging pump is required after the pressure com­pensation and for refilling with oil.
The connection of the oil draining or oil charging stop valve (090) must be connected with the oil charging container.
Before charging with oil, switch the valves to the operating position.
The stop valve (090) must be opened until the oil level has reached a value between the upper edge of the sight glass indicator MIN (N10b, data sheet
990565) and lower edge of the sight glass indicator MAX (N10c, data sheet 990565).
The oil separator is generally charged with oil via the oil cooler.
When charging with oil for the first time, oil must be charged via the service valve (135) too. To this end, the stop valve (065) must then be closed.
While operating the package, the oil level must be regularly checked (see chapter "Oil level check").
Caution!
Due to the use of selected compo­nents, the refrigerating machine oils tend to absorb more moisture. There­fore, when charging a compressor the oil should be allowed to come into contact with air for a short time only. The contents of an opened drum have to be used up within one working day, provided the drum is properly closed between charging.
8.5.5.1 Pressure compensation with the cooling system
Re-establish the vacuum. Carry out pressure com­pensation via the service stop valve (285).
8.5.5.2
Checking the direction of rota­tion of the oil pump motor
The oil pump is started with the driving motor electri­cally blocked (service). The stop valves are in the operating position.
Start-up Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
60 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
The direction of the arrow given for the oil pump must correspond to the direction of rotation of the oil pump motor.
Caution!
Since the slide ring shaft seal of the oil pump is dependent on the direction of rotation and can be damaged when this direction is wrong, checking must be reduced to a very short running period (less than 2 seconds).
The adjusted differential pressure between the oil pump pressure side and the unit final pressure is checked with the oil pump rotating in the correct direction. It must not fall below the prescribed set value in the P+I diagram.
While the compressor is not running and the oil has not yet reached the operating temperature, the differ­ential pressure can be slightly higher than the indica­ted value.
The differential pressure can be changed by rotating the spindle on the oil pressure control valve. (The dif­ferential pressure is increased by turning it inwards and vice versa).
8.5.6
Checking the fault monitoring
1.
Disconnect the incoming feeder of the compres­sor drive motor from the mains supply when checking the safety device (e.g. remove LV/HBC fuse links).
2.
Apply voltage to the control device.
3.
Check the built-in pressure transducer and resistance thermometer for correct wiring.
To do so, loosen the relevant contacts. The mes­sage "Broken wire <sensor XXX>" appears on the display of the control. Check that the display is correct after the contact has been re-estab­lished.
Further information can be found in the con­troller manual.
4.
Check limit values.
Limit value = see parameter list
5.
Switch on the screw compressor package/chiller from the controller.
6.
"Oil circuit monitoring failure” must be indicated after a starting delay time of 20 sec.
7.
Reconnect the oil pump motor to the mains sup­ply.
8.
Check the excitation of the solenoid valves of the adjusting device for capacity control in the Mini- mum direction.
9.
Simulate the minimum end position of the control slide and check the switching function of main switch and star-delta contactor (for motors with star-delta starting).
10.
Checking the switching function of the solenoid valve by forcing the digital outputs.
11.
Check the "Oil circuit monitoringfailure". only for external oil pumpAfter 6s, the of the compres­sor drive motor must be shut off. To do so, the valve (70) must be throttled in such a manner that the alarm value for oil difference pressure as stated on the parameter list is ot reached.
12.
Set the motor current limitation acc. to nominal motor data. See parameter list!
8.5.7 Checking of the safety pressure limiter
1.
Setting of the shut-off values as per the panel data report
2.
Switch on the compressor package
3.
Initiation of the shut-off value
4.
Check the reaction:
Compressor must shut off immediately
Fault report on the display of the control unit
8.5.8 Checking of the emergency-OFF button.
Hint!
Upon actuation, the emergency-Off button must immediately shut off the compressor.
1.
Actuation of the emergency-OFF button.
2.
Check the reaction:
Compressor must shut off immediately
Fault report in the display of the control
3.
Resetting of the emergency-OFF actuation to end the test.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Start-up
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 61
8.5.9 Adjustment of oil pressure
Danger!
The oil pressure being set too high or too low may result in serious compres­sor damage or even total breakdown of the compressor after even a short period of operation!
Before the compressor drive motor and therefore the unit can be started, the oil pressure must be set cor­rectly by adjusting the oil pressure regulating valve (075).
For adjustment solely the oil pump must be started. For units with the control GEA Omni, digital output must be forced for this.
The set value of the oil differential pressure should be taken from the P+I flow chart of the specific project.
Oil differential pressure = oil pressure item (110)
- discharge pressure item (105)
The differential pressure can be changed by rotating the spindle on the oil pressure regulating valve (the differential pressure is increased by turning it inwards and vice versa). To do so, the seal on the oil pressure control valve (075) must be removed.
In comparison to normal operation conditions, the oil differential pressure can be slightly higher if only the oil pump is operated or if the operating temperature is not reached yet (with the valve open to the same degree).
In this case, the oil differential pressure should be readjusted (according to the value in the P+I flow chart) after start of the unit and reaching of the oper­ation temperature.
8.5.10
Checking the direction of rotation of the drive motor
Warning!
The coupling must not yet connect the motor and compressor!
Secure the electric switchgear so as to prevent the compressor drive motor from being switched on accidentally.
With the control slide in the MIN or MAX position, it should be possible to rotate the compressor shaft easily and smoothly by hand. When check­ing the direction of rotation of the compressor driving motor pay attention to the conditions for switching the compressor on.
fig.46: Motor direction of rotation
A Compressor
B Motor
The compressor drive motor is started directly and then switched off again by forcing the digital outputs.
Hint!
Prior to the start-up of the compressor drive motor, the manufacturer's infor­mation, e.g. on the lubrication of the motor, must be followed at all costs.
If the direction of rotation of the motor is incor­rect, it should be corrected while the electric switchgear is secured to prevent the motor from being switched on accidentally. Then the motor must work for at least 1 hour, unencumbered and free from errors. This is important in order to dry out residual moisture in the motor (caused during transport or storage).
The coupling protection must be in place during this start-up period as required by the labour safety regulations.
After checking the direction of rotation of the drive motor, the coupling may be connected with the motor.
8.5.11 Mounting the coupling
1.
The electric switchgear is secured to prevent it from being switched on accidentally.
2.
Mount the coupling while observing the instruc­tions of the separate documentation.
3.
The values for radial and angular deviations given in the coupling documentation must be checked and corrected if necessary. The axis distance between the compressor drive motor and the compressor must be checked.
Start-up Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
62 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
4.
The real values have to record at data sheet of coupling documentation. Please send back a copy of the filled data sheet to:
GEA Refrigeration Germany GmbH
Holzhauser Straße 165
13509 Berlin
Fax: +49 (0)30 - 43 592 759
Caution!
Observe the maintenance instruction! Regrease the coupling at the prescri-
bed intervals if scheduled in the main­tenance instruction for the coupling!
8.5.12 Checking the water circuits
Check whether the cooling and cold water pumps are running and the shut-off fittings in the cooling water circuit are in their operating positions.
While the unit/ chiller is operating under project con­ditions, adjust the cooling water control so that the condensing and oil temperature lies within the per­missible range.
8.5.13 Initial start-up
After carrying out the aforementioned works, the SCP can be commissioned in accordance with the operating manual of the control device.
1.
Switch on the control voltage of the control device.
2.
Remedy and acknowledge existing fault mes­sages.
3.
Select manual operating mode.
4.
Turn on SCP.
8.5.14 Checking the adjustment of the control slide
1.
SCP is running.
2.
Select manual operating mode.
3.
The maximum end position (100%) must be reached and signalled when the "Increase power" button is pressed.
4.
The minimum end position (0%) must be reached and signalled when the "Decrease power" button is pressed.
5.
Vent the adjusting device by moving the control slide backwards and forwards about ten times.
8.5.15
Checking the control slide adjust­ment times
Caution!
Only adjustment times between 30 and 60 seconds are permissible.
The throttle valves of the solenoid valves are adjus­ted in the factory in such a manner that they ensure an optimal adjustment time of the control slide of between 30 and 60 seconds.
While running at operating temperature and pressure conditions, determine the adjustment times needed when the control slide is continually moved from the maximum end position to the minimum end position and back. For the automatic system to run smoothly, the adjustment times in either direction must be approximately the same.
The adjustment time can be adjusted with the help of throttle valves DS5 and DS6.
Hint!
See the assembly instructions for the screw compressor.
8.5.16 Checking the oil cooler
Guide value for oil temperature = see parameter list
Oil cooling with water-cooled oil cooler
The water volume must be regulated so that the cooling water volume corresponds to the project value. The inlet and outlet temperatures must be checked. The oil temperature adjusts automatically via the 3-way valve.
Checking the oil cooling with refrigerant-cooled oil cooler
No regulating or checking required.
8.5.17 Adjusting the amount of injection oil and the oil temperature
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Start-up
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 63
8.5.17.1 Screw compressor packages without refrigerant injection
The amount of injection oil and the oil temperature directly influence the discharge temperature of the compressor. The amount of injection oil is adjusted under operating conditions through the injection oil control valve.
Standard values for discharge temperature
t t
max
NH3/HP t ≥ t
oil
+ 20K 30K 95°C
NH3/LP t ≥ t
oil
approx. 45 ... 60°C 80°C
Freon/HD t ≥ t
oil
+ 15K 80°C
R22/LP t ≥ 45 ... 60°C 80°C
8.5.17.2 Compressor units with refriger­ant injection
The oil temperature is changed by setting the injec­tion oil control valve. The more the shut-off valve is throttled, the more the oil temperature decreases. If the oil temperature becomes too low or reaches the lower range, the setpoint for the discharge tempera­ture should be set higher accordingly. In the first set­ting of the oil circuit, the control valve for injection oil is opened approximately half a turn.
The discharge temperature is then regulated to the value indicated in the parameter list by means of the thermostatic expansion valve.
Guide value for compressor end temperature: t
e
= 60 + 10°C (for NH3)
Other refrigerants on request.
8.6
Start-up after long standstill periods
1.
Inserting the main fuse
2.
Switching on the control unit according to the operating manual.
3.
Checking all parameters on the control unit dis­play. See parameter list.
4.
Checking the settings of all control and safety devices.
8.7 Restarting after approx. 1 year standstill
Change the oil filter inserts (see maintenance instruction).
Switch on the oil heater at least one hour before starting the screw compressor package/chiller.
Open the stop valve on the suction side and the pressure side (or check valves which can be shut off).
If fitted: Open the stop valves (or shuttable check valves) in the suction line of the economiser.
If fitted: Open the refrigerant supply to the ther­mosyphon - oil cooler.
If fitted: Open the manual stop valve of the refrig­erant injection.
Remove all non-condensable gases by venting. To this end, check the condensing pressure and temperature (see parameter list).
Check the oil collection sump and drain if neces­sary.
Switch on the compressor and observe the oper­ating instructions of the electrical switchgear. Make a screw compressor package/chiller test run in order to test the sensor and actor technol­ogies (for operation and indicating precision).
Start-up Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
64 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
9 USE, OPERATION, CONTROL
9.1 Use in explosive atmospheres, installation zones 1 and 2
Danger!
The same regulations apply to the operating instructions for screw com­pressor packages in potentially explo­sive atmospheres as described in the respective applicable operating man­ual.
In addition to this, the following exten­sions apply:
1.
In addition, the legal safety regula­tions apply for the people respon­sible for operating the screw com­pressor package, and must be con­formed with respect to the trans­port, assembly, operation and maintenance and if necessary the replacement of sub-assemblies, etc. in potentially explosive atmos­pheres.
The operator directives must be complied with in this context – see also section: Safety instructions for compressor, Appendix E and Screw compressor package, Appendix E. Both documents are an integral part of the documenta­tion.
2.
The relevant electrical engineering regulations for installations in potentially explosive atmospheres, especially EN 60079-10, apply to the installation and connection of electrical components. Appropri­ate, prescribed cabling material must be used.
3.
The entire screw compressor pack­age must be earthed by the opera­tor.
9.2 Important information for the opera­tor
The screw compressor package must be only be operated by trained and qualified personnel who are familiar with the contents of the operating manual for GEA Refrigeration Germany GmbH screw compres­sor packages.
The safety regulations for refrigeration plants must always be observed in order to prevent damage to the screw compressor package and injury to the operating staff.
Hint!
The screw compressor package is operated via the control panel of the control unit. If the control is included in the scope of delivery, the operating staff must be familiar with the contents of the complete documentation of the control unit. The documentation for the control unit is an integral part of the product documentation.
9.3 Prerequisite for switching on
The screw compressor package has been designed for automatic operation; the control unit controls the switching on and off of the compressor and its capacity adjustment.
Continuous operation and observation of the screw compressor package is not necessary in automatic mode. The necessary steps for switching on the screw compressor package can be found in the con­troller documentation.
If the screw compressor package is controlled man­ually, it must be operated from the refrigerator room. In particular, the repair and maintenance instructions must be complied with.
The following prerequisites must be fulfilled for switching on the screw compressor package:
1.
The main power must be available and switched on.
2.
The screw compressor package must be suffi­ciently filled with refrigerant and oil.
3.
The valves must be in the operating position.
4.
The oil level in the oil separator must be within the permissible range.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Use, operation, control
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 65
5.
The cooling and cold water pumps must be in operation.
6.
The supply of cooling water or coolant to the oil cooler must be ensured.
7.
The oil heater in the oil separator must have heated the oil sufficiently.
Hint!
The oil heater in the oil separator can be switched on while the screw com­pressor package is not running. It is then automatically switched off when the screw compressor package is star­ted and switched on when it is shut down. If the ambient temperature is below 5°C, the oil heater must be switched on at least one hour before the screw compressor package is star­ted.
8.
The rated current limitation has been set accord­ing to the motor rating.
®
The screw compressor package can be switched on as per the controller operating manual.
Use, operation, control Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
66 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
9.3.1 Overview of the operating modes
Modes Signal for …
Name Remark Start/Stop Capacity +/-
0 Service Oil pump by itself
Compressor motor blocked
1 Manual
+ Manual
Manual control via Touch Panel (TP) Manual Manual
2 Manual + Auto Manual Start/Stop via TP and full automatic local
capacity control
Manual Auto
3 Auto + Auto Full automatic start/stop and local capacity control Auto Auto
4 Remote
+ HW (cont)
Start/stop and capacity demand via digital contacts (hardware) from a remote master controller. The GSC TP derives from the continuous +/- signals the pulses for capacity (indirect).
External External
continuous
5 Remote
+ HW (pulse)
Start/stop and capacity demand via digital contacts (hardware) from a remote master controller. The mas­ter also generates the +/- signals as pulses for control­ling the slide capacity directly.
External External
pulses
6 Remote
+ HW (loc. SW)
Start/Stop from a remote master controller via digital contacts (hardware). The GSC TP controls the output depending on a local setpoint (TP) and from this set­point also automatically switches the product ON/OFF.
External
+ setpoint deviation
Local
Setpoint
7 Remote
+ HW (ext. SW)
Start/Stop from a remote master controller via digital contacts (hardware). The GSC TP controls the output depending on an external setpoint (analog input) and from this setpoint also automatically switches the product ON/OFF.
External
+ setpoint deviation
Remote
Setpoint
8 Remote
+ Net (cont)
Start/stop and capacity demand via network from a remote master controller. The GSC TP derives from the continuous +/- signals the pulses for controlling the capacity (indirect).
Network Network
continuous
9 Remote
+ Net (pulse)
Start/stop and capacity demand via network from a remote master controller. The master also generates the +/- signals as pulses for controlling the capacity directly.
Network Network
pulses
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Use, operation, control
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 67
Modes Signal for …
10 Remote
+ Bus (loc. SW)
Start/stop from a central master controller via a bus signal. The GSC TP controls the output depending on a local setpoint (TP) and from this setpoint also auto­matically switches the product ON/OFF.
Network
+ setpoint deviation
Local
Setpoint
11 Remote
+ Bus (net. SW)
Start/stop from a central master controller via a bus signal. The GSC TP controls the output depending on an external setpoint sent externally via the network and from this setpoint also automatically switches the product ON/OFF.
Network
+ setpoint deviation
Network
Setpoint
Use, operation, control Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
68 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
9.3.2 Setting of setpoint and limiting values as well as safety devices
Caution!
The correct setting of all setpoint and limiting values is a prerequisite for the safe operation of the SCP.
For the setting of the setpoint and limiting values, the
1.
details (steps) in the control operating manual
and
2.
the project-related data are
instrumental. The program-based setpoint and limit­ing values as well as the setting values of the safety device are stated in the project-based parameter list. The parameter list forms part of the documenta­tion for the controller.
9.4
Operation of the screw compressor package
Caution!
Read the control documentation care­fully.
Contact the GEA Refrigeration Ger­many GmbH technical customer serv­ice if you require assistance.
The screw compressor package is operated using the control (standard: GEA Omni).
The GEA Omni is mounted directly on the screw compressor package as standard, but can also be arranged in a control centre.
The GEA Omni consists of the control unit with oper­ator keypad and display unit (TouchPanel), indicator lights for "Running", "Warning" and "Alarm", the emergency stop button, the output relays and the casing.
All switching, operating and control actions are car­ried out via this TouchPanel. The TouchPanel is the interface between the man and the machine.
GEA Omni performs the following functions as standard:
Display of all important physical and technical parameters, e.g. pressure, temperature, motor current, capacity, number of operating hours, operating mode and status signals
automatic start up and shut down of the com­pressor package and capacity control dependent on the relevant parameter for the application (e.g. the suction pressure or an external temper­ature),
Monitoring of all operating parameters,
Compressor capacity limitation if the measured discharge pressure, suction pressure, secondary refrigerant temperature or motor current indicate an overload,
Fault memory with date and time,
Wire failure detection for all analogue input sig­nals
Password protection for preventing unauthorised access to important parameters
Non-volatile saving of programme,
MPI communication with a master controller (optionally via Profibus-DP, Modbus RTU or Modbus TCP).
9.5
Instructions regarding failures, their causes and remedies
The screw compressor packages/ chillers manufac­tured by GEA Refrigeration Germany GmbH are highly advanced, automatic and extremely efficient systems. Nevertheless, faults can occur and may complicate any continuous operation of the plant or cause a failure of a part or the entire plant.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Use, operation, control
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 69
Table of malfunctions
Fault Cause Remedy
The suction pressure is too low, performance is reduced and the system overheats.
Slow loss of refrigerant through leaks in the refrigerant circuit.
Check the entire system for leaks. Eliminate leakage, replenish refrig­erant if necessary.
Pressure sensor defective. Replace pressure sensor.
Defective capacity control devices in the compressors
Check capacity control devices, especially connections of solenoid valves
Suction filters are clogged Clean or replace the filter insert.
The suction pressure increases, the compressor(s) frost up to impermis­sibly high level or make noises that suggests fluid (refrigerant) in the compressor.
The compressor/s are sucking in wet steam or liquid when started up. The safety device to prevent a too-high liquid level is not respond­ing.
Check the filling of the system, drain any refrigerant, repair safety device. Check for superheating.
The condensation pressure is too high.
There is air or other non-condensa­ble gases in the refrigerant circuit.
Vent the refrigerant circuit.
The compressor(s) will not start-up after switching on or it shuts down immediately after starting again.
The electrical circuit is interrupted by a unit in the safety chain.
Turn on the power, check safety devices and replace or correctly adjust if necessary.
No oil pressure is building up in the package/chiller. The oil circuit is disturbed by clogged oil filters or leaks.
Exchange or clean oil filter ele­ments, eliminate leaks and replen­ish oil.
The compressors do not adapt to the required capacity.
The capacity control device is mal­functioning due to disturbances in the oil circuit or mechanical influen­ces.
Check the oil circuit. The compres­sors should only be repaired by experts. Check the position detec­tor of the compressor control slide.
The compressors are shut off very often by the maximum pressure governor.
The condensation pressure is too high.
See above.
The maximum pressure governor is defective or set wrongly.
Remove the maximum pressure governor, repair it, set it correctly or replace it.
The compressors are shut off very often by the minimum pressure governor.
The suction pressure is too low.
Open all valves on the suction side of the compressors.
Use, operation, control Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
70 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Table of malfunctions
Fault Cause Remedy
The pressure governor is defective or set wrongly.
Remove the minimum pressure governor, repair it, set it correctly or replace it.
The heat transfer capacity of the evaporator decreases.
Check the evaporator for elevated oil concentration, drain oil if neces­sary.
When operting, the package/chiller is louder than permitted.
The compressor(s) or the drive motor(s) is/are defective.
Inform the GEA Refrigeration Ger­many GmbH customer service
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Use, operation, control
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 71
10 CLEANING, MAINTENANCE, REPAIR
Hint!
The obligation for signage to prevent the unintentional switch-on of the plant during cleaning, maintenance and repair must be observed.
10.1 Use in explosive atmospheres, installation zones 1 and 2
Danger!
The same regulations apply to the maintenance instructions for SCPs in potentially explosive atmospheres as described in the respective applicable operating manual.
In addition to this, the following extensions apply:
1.
In addition, for the persons responsible for main­taining the SCP, the legal safety regulations con­cerning the installation of the SCP in potentially explosive atmospheres with respect to the main­tenance of the individual components or sub­assemblies or their complete replacement apply.
2.
The maintenance may only be carried out in agreement / with the knowledge and release of the operator.
3.
The maintenance and replacement regulations resulting from the operating manual for the com­ponents are to be complied with.
4.
Appropriate special tools approved for the poten­tially explosive atmosphere must be used.
5.
Only original spare parts may be used. Other­wise, any claim of warranty is void or, in case of damage, the operator is liable for this.
6.
Each maintenance inspection (see maintenance book) must also include the checking of the secure fit of the threaded connections for the coupling safety hood.
10.2
Important information for service personnel
The following chapter is primarily aimed at the main­tenance and service personnel of the screw com­pressor package.
Hint!
Heed all safety instructions in this manual.
Familiarise yourself with the local con­ditions of the screw compressor pack­age installation site.
Adhere to all legal and local regula­tions of health, work and fire protec­tion as well as the regulations which must be heeded concerning the gases to be compressed.
Please read this manual carefully and completely prior to working on the screw compressor package.
Familiarise yourself with the special features of the screw compressor package.
Caution!
There is an increased danger of slip­ping due to contact of operating media with the floor!
The screw compressor package must be serviced by appropriately trained operating staff only. For all maintenance work, the maintenance instructions must be complied with.
A maintenance checklist is part of the product docu­mentation. The maintenance certificates in the main­tenance checklist are completed and signed as part of the inspection and maintenance by authorised fit­ters as evidence of the work done.
During the guarantee period, these confirmed main­tenance certificates are a prerequisite for any claims under the guarantee.
The responsible certified specialist company must be informed if any repairs are required.
All maintenance and service tasks have to be carried out with care to preserve the functionality of the screw compressor package. Guarantee claims will not be valid if the customer failed to follow the main­tenance instructions.
10.3
Cleaning the heat exchanger
Cleaning, maintenance, repair Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
72 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
10.3.1 Mechanical cleaning
Mechanical cleaning is a maintenance measure in order to ensure the continuous safe operation of the screw compressor package.
Components of the screw compressor packages (e.g.suction filter) can be removed for manual mechanical cleaning. Proceed in accordance with the details in the applicable component documenta­tion. After completing cleaning work, properly mount the component and check for leakage.
10.3.2 Chemical cleaning
Chemical cleaning of the screw compressor package is not recommended by GEA Refrigeration Germany GmbH.
10.4 Maintenance
10.4.1 General instructions
Danger!
Contact with live components is pro­hibited.
Maintenance work on the running screw compressor package is not per­mitted.
Work involving intervention in the refrigerant circuit must only be carried out by qualified engineers in accordance with the guarantee conditions.
The screw compressor package must always be switched off before being dismantled. Before begin­ning the work, it must be ensured that all parts sub­ject to maintenance/servicing are de-energised(e.g. by removing the main fuse or installing a shorting bridge).
The refrigerant must be removed from the applicable parts of the system parts. This work must be carried out with great care, taking into account the safety regulations, so that the maintenance personnel are not injured by the refrigerant or by the refrigeration unit oil present in the system.
Parts of the system under pressure must be com­pletely vented before opening. While carrying out the repair, it is must always be ensured that a complete pressure balance of the affected pressure chambers with the environment is preserved.
During cleaning, repair or maintenance work, the screw compressor package or its components must be protected against the penetration of moisture in order to prevent impairment of the function of the components.
The chief principle must be to keep air and moisture entering the screw compressor package to an abso­lute minimum. All foreign substances must kept as far away as possible or eliminatedincluding
welding residues,
sealing remnants,
auxiliary materials such as grease, oil or sol­vents.
Welding and soldering work may only be performed with written permission. The requisite protective measures must be defined. These include:
personal protective measures when opening the respective part of the system,
complete draining of the respective part of equip­ment,
cleaning with the appropriate cleaning agents,
concentration measurements,
ensuring sufficient ventilation and venting,
performance of all welding work with the use of forming gas.
If gas filled pipes are opened for maintenance work, these pipes must be in a gas-free condition.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Cleaning, maintenance, repair
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 73
10.4.2 Repair work
Modifications and repair work may only be carried out by qualified persons or persons with suitable training with the manufacturer's consent and must strictly comply with the rules set out in the mainte­nance instruction for the components concerned.
Hint!
The following maintenance notes must be observed:
Only spare parts made by the original component manufacturer may be used for repairs and for replac­ing wearing parts. These are available from the spare parts department.
10.4.2.1
Repair information
Important features of the technology and production process must be taken into account when repairing the plant:
complete sealing of all devices and pipes.
Dryness and cleanliness of the entire plant.
Use of welding methods causing only a minimum amount of dirt to collect in the plant.
Pipes bent on a pipe-bending machine only using refrigerating oil.
If repairing the piping system from your own stocks, we recommend that you use a pipe with NBK surface quality (annealed and descaled, mechanically or chemically descaled after annealing).
When carrying out repairs to piping systems, care should be taken to maintain the original pip­ing routes.
Only pipes of sufficient material quality, which are certified according to DIN 10216-2 should be used.
10.4.2.2 Repairs of pressure vessels
subject to approval inspection
Hint!
The responsible monitoring body (e.g.TÜV) must be notified in advance.
New inspection and approval is required after pres­sure vessels that are subject to approval have been repaired or changed. Welding may only be carried out by approved welders with a valid welder’s card.
10.4.3
Maintenance intervals
Caution!
The maintenance intervals in accord­ance with the maintenance schedule must be observed.
The maintenance schedule is an integral part of the product documentation. The maintenance schedule contains all the maintenance instructions and certifi­cations for the first 15 years of performance of the screw compressor package. The maintenance certifi­cates are completed and signed as well as acknowl­edged on the display of the control as part of the inspection and maintenance by authorised fitters as evidence of the work done.
During the warranty period, these validated mainte­nance certificates also serve as a precondition for any warranty claim put to GEA Refrigeration Ger­many GmbH.
10.4.4
Maintenance work
Hint!
The documentation for the main com­ponents is a part of the product docu­mentation. This contains important information to be considered before beginning the maintenance work.
10.4.4.1 Maintenance of the screw compressor
Maintenance works are to be periodically carried out on the screw compressor (see maintenance sched­ule). These include:
Measure axial play of bearings,
Check shaft seal,
Check primary slide movement,
Check the adjustment of the position sensor.
Cleaning, maintenance, repair Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
74 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Hint!
The maintenance works on the screw compressor are described in the installation manual of the compressor.
After 50,000 operating hours or in the 15th operating year, a general check of the screw compressor is planned by the manufacturer. Contact Customer Service in this regard.
10.4.4.2
Changing the block mounting filter element
Hint!
When must the filter element be replaced or cleaned?
The oil filter element must be replaced as specified in the maintenance check­list for the total product from GEA Refrigeration Germany GmbH.
Loss in pressure during operation is monitored by the internal control – including a preliminary alarm function for preventative replacement.
The following applies as a guide value for replacement: The filter element should be replaced after every 5000 operating hours or once each year.
Changing the filter element
1.
Shut down the screw compressor package/chiller and depressurise the blocked mounting filter on the pressure side.
2.
Remove the filter cover by loosening the four cover screws.
3.
Remove the filter element by slightly turning the mounting pin in the filter head.
4.
Check the O-ring and support ring in the filter bowl for damage and correct positioning. Replace parts if required.
5.
Replace glass fibre element, clean or replace wire mesh.
The efficiency of the cleaning depends on the type of dirt and the level of differential pressure before replacing the filter element. If, after replacing the filter element, the differential pres­sure is more than 50% of the value before replacing the filter element, wire mesh must also be replaced.
6.
Check that the type designation/manufacturer ID number on the replacement element matches the type designation/ID number on the filter’s rat­ing plate.
7.
Place the replaced or cleaned filter element back on the mounting pin by turning it slightly.
8.
Reposition the filter cover and tighten the four cover screws. Ensure that installation occurs without mechanical tension.
9.
Vent the housing of the block mounting filter.
10.4.4.3
Replacing the oil filter
1.
Switch the unit/ chiller off.
2.
If the oil filter is very dirty, it may be necessary to replace it outside the normal maintenance schedule.
3.
To change the oil filter insert, close the following valves in accordance with the P+I diagram and the oil filter documentation:
Stop valve in front of oil filter (item 65)
further stop valves in front of oil filter (if avail­able), e.g. (item 220) if a thermostatic 3-way valve (item 215) will be used
see P&I diagram
Stop valve function oil (item 70) for Grasso SP1 or (item 190) for Grasso SPduo
Control valve - injection oil with integrated check valve function (item 80)
Do not forget to note the number of valve rotations when you close the valve (item
080). When opening the valve it must be returned to its initial position (see point 10). This is necessary to ensure the final temper­ature remains unchanged and therefore to avoid possible vibrations in the oil line.
Stop valve bypass oil cooler (optional)
4.
Establish pressure compensation with the atmospheric pressure.
5.
Drain oil.
6.
Remove the cover of the oil filter.
7.
Remove the oil filter element and properly dis­pose of it if it is highly soiled.
8.
Carefully insert a new oil filter element.
9.
Close the cover of the oil filter.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Cleaning, maintenance, repair
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 75
10.
Reopen valves in accordance with item 3. The valve (80) must be returned to its initial position.
11.
After the pressure has been compensated, vent the oil filter via the vent valve.
10.4.4.4 Maintenance of the suction fil­ter
10.4.4.4.1
Changing the filter element
The maintenance interval for changing or cleaning the filter element is specified by the manufacturer of the refrigeration system.
The contamination level and mechanical condition of the filter element must be inspected at least once a year.
Before opening the filter, always make sure the filter housing is not under pressure.
Caution!
Refrigerant may leak out on opening the filter. The safety data sheets for the refrigerants in question must be consulted and any prescribed protec­tive measures observed.
To remove the element, proceed as follows:
1.
Unscrew the cover.
2.
Pull out the cover with the filter element.
3.
Remove the spring wire clamp.
4.
Twist the element away from the cover to release the bayonet catch.
5.
Detach the element from the cover.
6.
Allow the element to drain off into a suitable con­tainer.
Caution!
When carrying out maintenance, always inspect the sealing ring (O­ring) of the cover for mechanical dam­age and replace it if necessary.
7.
Reassemble all parts with the new or cleaned fil­ter element following the same procedure in reverse order.
10.4.4.4.2 Cleaning the filter element
The metal-gauze element used in the filter can be cleaned and reused several times before it has to be changed.
Manual cleaning
Immerse the soiled metal-gauze element in a clean, grease-dissolving liquid, then blow it through with compressed air from the outside inwards. Here it is important to place a cylindrical part – possibly wrap­ped in corrugated cardboard – inside the element to catch the dirt particles.
Caution!
Never use wire brushes for cleaning.
Hint!
To avoid fatigue failures of the metal gauze, strainer elements should be replaced with new, original filter ele­ments after being cleaned 4 – 5 times.
10.4.4.5 Oil draining, oil filling, oil change
10.4.4.5.1 Importance of oil change
Aged oil demonstrates an increasing loss of ability to lubricate. Because of this, all rotating components of the compressor are endangered. The filter elements become prematurely clogged and must be cleaned and replaced at shorter intervals.
The oil in the screw compressor package/chiller must be changed:
when the operating time of the oil charge has reached the technically specified oil change interval,
Warning!
Oil change intervals Oil change with ammonia as the refrig-
erant after every 5,000operating hours or after 1 year at the latest
.
Oil change with freon as the refrig­erant after 10,000operating hours or after 2 years at the latest.
Cleaning, maintenance, repair Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
76 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
if the oil becomes unacceptably contaminated­due to a major accident (e.g. water penetration into the refrigerant circuit).
The degree to which oil in refrigeration plants has aged must be checked by analysis and in compari­son of the data with those of fresh oil. Oil ageing can also be judged from the darkening of the oil colour and the deposits found in the oil filters. If the degree of ageing cannot be assessed reliably by laboratory analysis and the results of visual examination, it is advisable to change the oil at the following intervals (see maintenance checklist).
The assessment of the condition of the refrigerating machine oil by means of a general visual inspection (contamination) or laboratory analysis must be car­ried out:
after 5000 operating hours:
or
at the end of one year's operation
or
after remedying major damage.
or
if the oil is dark coloured or very cloudy.
10.4.4.5.2
Oil change, maintenance work
Take oil samples for analysis and comparison with the fresh oil data at regular intervals. Check the col­ouration of the oil visually and assess the degree of contamination.
Depending on the results, the user must decide whether to approve the postponement of filling the oil until the next assessment date or whether to have the oil changed.
Inadmissibly damp oil must be removed from the compressor unit/chiller immediately.
10.4.4.5.3 Changing the oil
1.
The screw compressor package/chiller must be run for at least half an hour to reach its operating temperature before the oil can be changed.
2.
First shut down the screw compressor package/ chiller as described in the operating instructions.
3.
Open the stop valve in the bypass line around the check valve on the suction side and the stop valve on the suction side to equalise the pres-
sure between the screw compressor package/ chiller and suction line. If screw compressor packages operated in parallel or other separate chillers are present, the refrigerant should pref­erably be drawn off at a pressure which is approx. 1 to3 bar above atmospheric pressure. Then re-close the stop valves bypass and the suction-side stop valve. Otherwise the pressure can be reduced by opening the vent valve on the suction filter and then disposing of the refrigerant as specified by law.
4.
Then drain the used oil through the oil draining/oil charging valves and dispose of it (Caution! hazardous waste!). Once this has been done, re-close the valve and if possible continue to draw off the refrigerant with a com­pressor connected in parallel or a disposal device until atmospheric pressure is almost reached.
5.
Otherwise depressurise the screw compressor package/chiller by opening the vent valve on the suction filter, taking into account the safety rules for refrigeration systems.
6.
Open the drain plugs and valves on the oil cooler, oil separator and OMC block to drain any residual oil. Then re-close the drain plugs and valves.
7.
Replace the filter element of the oil filter; replace and/or clean the filter element of the suction filter combination.
8.
Evacuate the screw compressor package/chiller using a vacuum pump.
Warning!
Shut off the oil pump!
9.
Pressurise the screw compressor package/chiller with a slight overpressure via the stop valve bypass check valve on the pressure side.
10.
Then check all components for leakages. On successful completion, perform a complete pres­sure compensation with the discharge line fol­lowed by a repeated leakage test of the screw compressor package/chiller. The oil charge oil and start-up of the screw compressor package/ chiller must be accomplished in accordance with the operating instructions.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Cleaning, maintenance, repair
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 77
10.4.4.5.4 Used oil
Refrigeration machine oil drained from the circuit is no longer suitable for use in refrigeration plants. It has to be stored or transported in appropriately label­led containers in accordance with the legal provi­sions. The operator is responsible for its proper dis­posal.
10.4.4.5.5 Draining the oil
It may be necessary to drain the oil:
to inspect or repair the compressor
and
if there is too much oil in the circuit.
The oil must be drained in accordance with points 1 to 6 of the chapter entitled "Carrying out oil change". The oil must be drained through the filling hose and into a container suitable for waste oil.
10.4.4.5.6 Check the oil level
fig.47: Arrangement of MIN / MAX sight glasses
1 Sight glass - MAX (operation)
2 Sight glass - MIN (standstill)
The oil level is checked visually via the sight glasses of the oil separator. The oil level should have a value between 1/2 filling level of sight glass N10c (MAX ­operation) and 1/2 height of sight glass N10b (MIN ­standstill).
If the oil level is too low, i.e. the oil level has a value less than 1/2 filling level of sight glass N10b (MIN ­standstill), oil must be replenished.
10.4.4.5.7 Charging with oil, topping
up with oil
See chapter entitled "Start-up, charging with oil".
Hint!
For permissible types of oil, please refer to the technical information enti­tled "Lubricating oils".
Oil removed from the compressor must not be re-used. Always use fresh oil from sealed containers! Do not mix with other types of oil.
10.4.4.6 Oil pump maintenance
Assuming correct installation in accordance with the conditions of use and correct fitting, gear pumps have the design prerequisites for long and fault-free operation.
The gear pumps require a minimum of maintenance which is, however, indispensable for fault-free opera­tion since experience has shown that a high percent­age of the faults and damage which occur are attrib­utable to the ingress of dirt and inadequate mainte­nance.
The maintenance intervals have been defined in the maintenance checklist (part of the product documen­tation).
An oil leakage of up to one drop/minute is required for the lubrication of the shaft seal and is permissi­ble.
The shaft seal is maintenance-free. If the oil leakage is too great, replace it according to the oil pump doc­umentation.
Hint!
The regular examination of all operat­ing data, such as pressure, tempera­ture, power consumption, degree of fil­ter fouling, etc., helps in the early detection of potential failure!
10.4.4.7 Changing the fine oil separa­tion cartridges
The fine oil separation cartridges should be replaced no later than after 25,000 run hours or 5 years.
Cleaning, maintenance, repair Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
78 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
If the oil carry over of the screw compressor package increases severely (oil recharging at unusually short intervals), replacement may be necessary even ear­lier.
fig.48: Operating position of the fine oil separation cartridges
1 Cartridge(s)
2 Fixing cover with O-ring
3 Hexagon-head screw
4 Self-locking hexagon nut
1.
Close the pressure and suction side shut-off fit­tings.
2.
Drain refrigerant. Evacuate screw compressor package.
3.
Check the pressure on the display of the control unit or by connecting a test pressure gauge.
4.
Dismantle the pipe bend after the oil separator.
5.
Dismantle the check valve installed in the oil separator. This step is omitted if a check valve which can be shut off is used on the pressure side.
6.
Remove the self-locking hexagon nut [4].
7.
Loosen the hexagon-head screw [3] and the fix­ing cover with O-ring [2] for fixing the fine oil sep­aration cartridges.
8.
Remove the cartridge(s) [1].
9.
Mount the new cartridge. The cartridge must be inserted into the oil separator with the O-ring first.
Assembly by carrying out steps 1-7 in reverse order.
Warning!
It is essential to apply self-locking hex­agon nut [4] again and secure it against turning backwards!
max. Tightening torque = 15 Nm
10.4.4.8 Tightening screw fastenings
Screw fastenings of components can become loose due to vibration or movement. Screw fastenings must therefore be checked regularly to ensure they are tight and retightened if necessary.
Screw fastenings must only be tightened to the maxi­mum tightening torques.
Unless otherwise stated by warning signs, the tight­ening torque is dependent on the size and strength of the screw fastening.
10.4.4.9 Coupling maintenance
1.
Switch the screw compressor package/ chiller off.
2.
Secure the electric motor against accidentally being switched on.
3.
Visually inspect the disk packs.
4.
Check the tightening torques of the fit screws.
5.
Check the alignment of the electric motor and correct it according to the steel lamination cou­pling documentation, if required.
6.
Re-grease the coupling (if provided for in the maintenance instructions for the coupling).
10.4.4.10 Checking the function of check valves
In order for a check valve to be effective, it is impor­tant to perform function checks at regular intervals.
An inspection is carried out by checking the noise behaviour of the valves during operation. After switching off the screw compressor package, mal­function on the suction side is indicated by prolonged turning back of the compressor. Malfunction on the pressure side leads to an increase of the standstill pressure in the package to the pressure level of the system pressure side.
10.4.4.11 Searching for leaks on the refrigerant side / leak test
The absence of leaks is a precondition for perfect functioning of the compressor unit/chiller unit. Leak­ing parts or connecting elements will lead to the loss of refrigerant and oil as well as the penetration of air and moisture into the low pressure side. The site of
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Cleaning, maintenance, repair
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 79
the leak must therefore be located and remedied if there is:
Loss of the inert gas charge (delivery state),
Loss of the entire refrigerant charge
or
underfilling.
Lower refrigerant levels in the containers are due to loss of refrigerant as a result of leaks. For this rea­son, all pipes, connections and valve glands should be checked regularly, especially in the initial period of assembly.
The most striking feature if there is a leak in the filled refrigerant circuit is the smell of refrigerant. The odour threshold of ammonia in the air is approx. 5 ppm and thus well below the permitted MAK values.
Methods of leak detection:
Regular visual inspections.
Smudges/dirt stains indicate leaking refrigerant/oil mixture.
Leak tests with nitrogen with a max. of 0.5% ammonia by volume, an elapsed time of more than 3 hours and application of a foaming agent to all the joints with a brush. Oil-filled compres­sors or circuit sections must only be charged with nitrogen – not air – to generate pressure.
Use of an NH3 leak detector.
Ammonia produces the following colours when leak tests are performed:
Red litmus paper turns blue,
Blotting paper impregnated with phenolph­thalein turns red (moisten).
Caution!
Due to the danger of explosion, oxy­gen must never be used to build up the pressure!
Generate a test pressure in the refrigerant circuit that meets the intended operating pressure for the leak tightness test to determine leaks on the refrigerant side, e.g. in the case of escaped inert gas or refriger­ant. When system parts are individually tested, the maximum operating pressure indicated on the respective system part for the corresponding pres­sure chamber must not be exceeded. The use of foaming agents gives the best results at test pres­sures < 5 bar.
If leaks are determined, these must be sealed imme­diately. Release the test pressure before beginning repair! Evacuate the system after repairs are com­plete and after rechecking for leaks.
10.4.4.12
Venting the refrigerant circuit
When air penetrates the refrigerant circuit, this makes itself felt in a fall-off in performance and the manometer on the discharge side of the compressor indicates a higher pressure compared to the conden­sation temperature. Any leaks must be remedied. In extreme cases, air in the circuit may interrupt the flow of refrigerant and cause the oil cooling to fail.
There are several ways of venting the system. The air or the NH3-air mixture is vented via the vent
valves of the condenser or the suction filter in water filled vessels when the package is at a standstill.
If air is in the mixture, the venting ammonia is absor­bed from water.
Hint!
Continuous venting using a Grasso purger is recommended.
10.4.4.13 Refrigerant evacuation
Hint!
Shut the oil pump during evacuation!
The purpose of evacuating the system is to remove air and moisture from the refrigerant circuit.
Evacuation is required:
after intervention in the refrigerant circuit and elimination of leaks,
before the start-up/restarting.
Evacuate the screw compressor package using a vacuum pump. The screw compressor must not be used for evacuation.
During evacuation, all affected parts of the circuit should be at room temperature at least because cold parts hinder the removal of moisture.
If there is still any moisture in the screw compressor package, this will lead to a rise in pressure. Evacua­tion must continue until the pressure no longer increases. A pressure comparison is based on a constant ambient temperature.
Cleaning, maintenance, repair Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
80 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
10.4.4.14 Checking the bearing noise
The bearings of the drive motor and the compressor must be checked for unusual running noise, espe­cially in comparison to previous maintenance. Recur­rent vibration measurements are recommended.
10.4.4.15 Checking the solenoid valves for capacity control
See the following sections in the start-up chapter:
"Checking the control slide adjustment"
"Checking the control slide adjustment times"
10.4.4.16 Checking the oil heater
Check the electrical function using a clamp-on ammeter.
Check the outer temperature of the oil separator and compare with the temperature of the machine room (while the screw compressor package is at a stand­still).
10.4.4.17 Maintenance of the compres­sor drive motor
Hint!
The compressor drive motor must be maintained in accordance with the "Motor documentation".
Maintenance of the compressor drive motor includes the following activities:
Lubrication of the motor
Lubrication intervals and quantities according to the "Motor documentation" or "Type plate".
Cleaning of the motor (externally)
Select a suitable cleaning agent according to the "Motor documentation".
10.4.4.18
Checking the start regime
See the operating manual of the compressor control system.
10.4.4.19 Checking the safety devices
See section entitled "Checking the fault monitoring" in the start-up chapter.
The safety devices are checked by moving to the switching points (limiting values). For details, see also the operating manual of the compressor control system.
Limiting value = parameter list
Moving to the switching point is achieved by throt­tling the pressure-side stop valve.
10.4.4.20 Checking the operating parameters
Hint!
The operating parameters are checked via the TouchPanel. The checking intervals recommen­ded in the table must be observed. The project-related setting values and limits are given in the parameter list.
Inform the manufacturer contract partner if the parameters are outside the allowable limits.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Cleaning, maintenance, repair
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 81
Parameter to be checked
Every 24
to 72hrs
Weekly Monthly Remark
Discharge temperature X
Minimum superheat must not be less than 15 K for NH3. For other refrigerants, the manufactur-
er's instructions must be noted.
Maximum discharge temperature 100°C, in indi­vidual cases (e.g. heat pump applications) this may be exceeded in agreement with the manu­facturer.
Oil temperature X
See parameter list!
The viscosity must not be less than 7 cSt at max. speed (rpm).
Oil pressure X
The oil pressure must be at least 0.5 bar above the final discharge pressure. An oil pressure fault may be caused by a clogged oil filter. Set­ting and monitoring of the values in accordance with the information in the parameter list.
Discharge pressure X
See project value (parameter list). Determine the superheat on the pressure side by compari­son with the final discharge temperature.
Oil level in oil separa­tor
X
See chapter "Oil level check". An oil level must be visible in the sight glasses at all times. If the oil level is below the minimum value, the oil must be recharged.
Oil heater
X
When compressor is shut down, the heater must automatically start. Visual check, the green LED indicates "Voltage ON".
Setting the safety devi­ces
X See set values in the parameter list.
Capacity control
X
Solenoid valves must switch audibly when the capacity is adjusted. Check in operating mode "1 (manual + manual)“.
Number of operating hours
X
See maintenance checklist for maintenance work to be carried out according to the number of operating hours.
10.4.4.21 Maintenance of the switching cabinet
Terminal screws must be checked for tightness and, if necessary, tightened at regular intervals (every 5,000 operating hours or at least once per year). The
Cleaning, maintenance, repair Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
82 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
contacts of the contactors must be checked for loss of contact material.
10.4.4.22
Checking the earth connection
Check the function of the earth connection frequently (see the general assembly drawing and the indica­tions on the product).
Only a specialist company must be commissioned with inspections.
10.4.4.23 Insulation
Check the insulation (if present) on components, containers and piping for damage.
Damaged insulation must be replaced. The insula­tion strength must be selected according to the tem­perature and humidity at the place of installation. Details on the insulation can be found in the P+I dia­gram.
Caution!
No screw connections must be used under the insulation if the piping is insulated. The pipes must be welded.
10.4.4.24 Check of the tightening torque on the adjusting elements of the fixing base.
The tightening torques vary depending on the strength and size of the screw used. The values for tightening torques are to be taken from the applica­ble DIN, unless otherwise specified.
Hint!
The tightening torques for the adjust­ing elements should be obtained from the data sheet. The data sheet forms part of the product documentation.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Cleaning, maintenance, repair
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 83
11 DECOMMISSIONING
11.1 Shut-down in the event of danger­ous situations
The safety equipment of the screw compressor pack­age complies with EN 378.
By means of automatic monitoring of the individual operating parameters, the control unit detects haz­ardous situations in good time and automatically switches off the screw compressor package.
The cause of the fault is displayed on the control unit and can then be corrected.
Among other things, the concept of the screw com­pressor packages is based onlow maintenance refrigerant circuits that are as well sealed as possi­ble. However, residual risks remain, especially due to possible leaks or escaping refrigerant or rotating drive parts.
Hint!
The EMERGENCY STOP switch in the switching cabinet is used to quickly switch off the chiller whenever neces­sary.
Leaking refrigerant can be detected with a gas detector (not included in the scope of delivery). This detector can be integrated in the automatic safety chain.
Please consult the safety regulations in this docu­mentation for information about what to do in the case of leaking refrigerant.
11.2
Standstill for a period <48 hours
Hint!
The obligation to label the plant as "Plant not in operation" must be observed!
If the screw compressor package is shut down for a period <48 hours, the following activities must be performed:
1.
Switch off the compressor in accordance with the operating instructions for the electrical switch­gear.
2.
If necessary, shut down all ancillary drives.
3.
Switch off the main switch of the three-phase electric system.
4.
If necessary, shut off the secondary refrigerant, heating agent or the cooling water supply.
5.
Ensure that the venting slots of the electric motors are covered under all circumstances!
®
Shut-down has been carried out
11.3
Standstill for a period >48 hours
Hint!
The obligation to label the plant as "Plant not in operation" must be observed!
If the screw compressor package is shut down for a period >48 hours, the following activities must be performed:
1.
Switch off the compressor in accordance with the operating instructions for the electrical switch­gear.
2.
Switch off all ancillary drives.
3.
Switch off the main switch of the three-phase electric system.
4.
Close the stop valve (or combined stop/check valves) on the suction side and the pressure side.
5.
Close the stop valves (or shuttable check valves) in the suction line of the economiser.
6.
Shut off the secondary refrigerant, heating agent or cooling water.
7.
Close the manual stop valve of the refrigerant injection.
8.
Ensure that the venting slots of the electric motors are covered under all circumstances!
®
Shut-down has been carried out
11.4
Measures during shutdowns
Even though the screw compressor package/ chiller is under overpressure, check the moisture content of the refrigerant and lubricating oil in case it is shut­down for a period longer than half a year. The mois-
Decommissioning Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
84 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
ture content must not differ substantially from the ini­tial values.
11.4.1
Monthly measures during stand­still
Check that the screw compressor package/ chiller is constantly under overpressure. Check the screw compressor package/chiller for leaks using a leak detector.
Start the oil pump for approx. 5 minutes.
Manually rotate the compressor shaft (min. 10 revolutions).
11.4.2 Four weeks before restarting
Check the moisture content and ageing condition of the refrigerating machine oil. Analyse the oil for this purpose. Compare the results of the anal­ysis with the values for fresh oil. We recommend an oil change after 1 year (ammonia as refriger­ant) (see Maintenance Instructions).
Check the insulation resistance of the drive motors (see the operating manual for the electric motor).
Switch on the oil pump.
Check the screw compressor package/chiller for leakages.
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Decommissioning
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 85
12 DECOMMISSIONING, DISPOSAL
Preparatory measures
Hint!
The information in the chapter "Decommissioning" must be observed.
Hint!
Care must be taken during disposal and devaluation that the various mate­rials are separated and taken for recy­cling. Disposal of component remains and components in the domestic ref­uge or on refuse tips is not permitted. The legal regulations applicable to the place of installation regarding the dis­posal of electrical equipment must be taken into account.
Dismantled components must be dis­posed of correctly and according to legal requirements.
The dismantling and disposal of the package/ chiller must be carried out in such a way that:
the plant is free of voltage and is protected against unintentional reconnection of the voltage.
Accidents to persons are prevented,
material damage is prevented,
uncontrolled escape of refrigerant or oil is prevented.
Disposal and decommissioning work must only be carried out by personnel who are qualified according to EN 13313.
Components may be under elevated pressure and the pressure must be released before open­ing them.
In case of contact with refrigerant or operating media, their hazardous properties (e.g. toxicity, inflammability) must be taken into account (see also the safety data sheet for the refrigerant). Personal protective equipment compliant with EN 378-3 must be worn.
National regulations (e.g. EN 378-4, Section 6) must be observed for the reclamation and dis­posal of refrigerants.
National regulations (e.g. EN 378-4, Appendix A) must be observed for the reclamation and dis­posal of operating media (oil).
No unauthorised persons must be within the installation area of the plant during decommis­sioning, as they could come into contact with refrigerant.
All components of the plant which are not to be re-used, as well as refrigerant and operating media, must be stored in suitable separate con­tainers. They must be treated as waste and dis­posed of safely.
Hint!
Re-use of operating media is not pos­sible!
Decommissioning, disposal Operating Manual | GEA Grasso M-Series
Screw Compressor Packages
86 GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015
Operating Manual | GEA Grasso M-Series Screw Compressor Packages
Decommissioning, disposal
GEA Refrigeration Germany GmbH | P_261511_1 | Generated 01.04.2015 87
Loading...