GE ZTX User Manual

72R-1000 9/05
ZTX Series Automatic Transfer Switches
40-400 Amps
GE Zenith Controls
Operation and Maintenance Manual
e
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1ii
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Equipment Inspection and Storage . . . . . . . . .11
Final Equipment Inspection . . . . . . . . . . . . . . .11
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Power Connections . . . . . . . . . . . . . . . . . . . . . .12
Engine Start Control Connections . . . . . . . . .13
Exerciser Option . . . . . . . . . . . . . . . . . . . . . . . .14
Functional Test . . . . . . . . . . . . . . . . . . . . . . . . .15
Jumper Positions . . . . . . . . . . . . . . . . . . . . . . . . .6
Control Interface . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Indicator LED’s . . . . . . . . . . . . . . . . . . . . . . . . .17
Pushbuttons . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Using the Keypad Controls . . . . . . . . . . . . . . . .18
Automatic Generator Exerciser . . . . . . . . . . . .19
In-Phase Monitor Operation . . . . . . . . . . . . .110
Example Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Partial Coverage Systems . . . . . . . . . . . . . . . . .11
Total Coverage Systems . . . . . . . . . . . . . . . . . . .11
Typical Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Power Circuit Schematic . . . . . . . . . . . . . . . . . .12
Power Panel Layout . . . . . . . . . . . . . . . . . . . . . .12
Interconnect Plug . . . . . . . . . . . . . . . . . . . . . . .12
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . .13
Standard Transition 40-200 Amps . . . . . . . . . .13
Standard Transition 225-400 Amps . . . . . . . . .14
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Table of Contents
Authorized Service
For GE parts and service, call: 773 299-6600
Introduction
GE Zenith Transfer Switches are used to provide a continuous source of power for lighting and other critical loads by auto­matically transferring from source 1 power to source 2 power in the event that source 1 voltage falls below preset limits.
Voltage sensing and system control is performed via a state-of-the-art microcontroller located on the cabinet door. It is designed to give highly accurate control of the transfer switch system.
All GE Zenith transfer switches are designed for use on emergency or standby systems, and are rated for total system or motor loads. Transfer switches are UL Listed under Standard 1008 and CSA Certified under Standard C22.2 No. 178 and IEC Listed under Standard 947.
NOTES: A protective device such as a molded case circuit breaker or fused
disconnect switch MUS
T be installed on both sources of incoming
power for circuit protection and as a disconnection device.
All references made within this manual about the term “S1” or “Source 1” relate to a Normal Power Source. All references made about the term “S2” or “Source 2” relate to an Emergency or Alternative Power Source.
GE Zenith Controls 1
ZTX Operation and Maintenance Manual (72R-1000)
Each GE Zenith transfer switch is factory wired and tested. A complete information package is furnished with each switch which includes:
a. Sequence of operation. b. Description and operation of
all accessories supplied.
c. Power panel connection diagram
and schematic.
d. Description and identification of
all customer field connections.
Installation of GE Zenith transfer switches includes:
a. Mounting the transfer switch cabinet. b. Connection of all Normal, Emergency,
and Load cables or bus bars.
c. Connection of external control
circuits as required.
Mounting
Enough room should be allowed to open the cabinet doors fully for inspection and servicing of the switch per NEC and local codes.
Installation
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
The safe operation of your switch is GE Zenith’s focus. The proper storage, installation, operation and mainte­nance will help increase the life of the switch.
Equipment Inspection and Storage
Once you have received the transfer switch, inspect it for any damage. This includes damage to the enclo­sure, power panel, control panel and wiring harness. If any damage is found or suspected, file a claim as soon as possible with the carrier and notify the nearest
GE Zenith
representative.
Before installation, it is necessary to store the transfer switch in a clean dry place, protected from dirt and water. Provide ample air circulation and heat, if necessary, to prevent condensation.
5% to 95% (non-con­densing)
-30°C to +75°C (-22°F to +167°F)
-20°C to +65°C (-4°F to +149°F)
Operating Storage Temperature Temperature (Ambient): Humidity
CAUTION
Due to hazardous voltage and current, GE Zenith rec-
ommends that a
GE Zenith Certified technician or a
qualified electrician must perform the
installation and maintenance of the switch.
Final Equipment Inspection
Prior to energizing the transfer switch:
1. Remove any debris incurred, with a vacuum, due to shipment or installation.
WARNING
Do not use a blower since debris may
become lodged in the electrical and
mechanical components and cause damage.
2. Verify that all cabled connections are correct.
3. Check engine start connections and verify the correct connection of all control wires.
4. Check the lug torque values of the power connections.
NOTE
: Lug torque values are specified
in the power panel manual.
5. Make sure that all covers and barriers are installed and properly fastened.
NOTE: Power panels ship from GE Zenith
in the Normal Position.
CAUTION
Before drilling conduit entry holes or any
accessory mounting holes, cover and protect
the switch and control panel to prevent dirt
and metal fragments from entering the mechanical and electrical components.
Failure to do so may result in
damage and malfunction of the switch.
NOTE: When lifting the switch using a spreader bar,
height H must be equal to half of distance D.
2 GE Zenith Controls
ZTX Operation and Maintenance Manual (72R-1000)
OR
S
Y
S
3N3
3
r
ON
T
Y
ON
T
A
OR
Install
load
cables
first.
Tip!
Table 1
Screw Type Terminals for External Power Connections
Switch Size
(Amps)
40
80 100 150
Utility, Generator and Load Terminals
1 #8 to 3/0 AWG
Cable Per Pole Range of Wire Sizes
1 #8 to 3/0 AWG 1 #8 to 3/0 AWG 1 #8 to 3/0 AWG
Fully Rated Neutral Bar (When Required)
3 #8 to 1/0 AWG
No. of Cables Range of Wire Sizes
3 #8 to 1/0 AWG 3 #8 to 1/0 AWG 3 #8 AWG to 300 MCM
200, 225, 250*
300, 400
1 #6 AWG to 250 MCM 1 #4 AWG to 600 MCM
3 #6 AWG to 300 MCM 3 #4 AWG to 300 MCM
* IEC Rating Only
Installation
(cont’d)
Figure 1 - Power Panel
Power Connections
GE Zenith transfer switches are supplied with UL listed solderless screw type terminals as standard for the Normal, Emergency and Load power connections. Table 1 lists the number and sizes of cable lugs supplied as standard for each switch amp rating.
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Connect the Normal, Emergency, and Load conductors to the clearly marked terminals on the transfer switch. Remove surface oxides from cables by cleaning with a wire brush. Verify that all connections are correct before tightening the lugs. All cable lug connections must be tightened to the proper torque values as shown in Table 2.
NOTE: Do not run cables or wiring behind
front-connected transfer switches.
TERMINALS
TILIT
TERMINAL
LOAD
T
I
ERA ILIT
SWITCH POSITION INDICAT
E
TI
ERA
GENERAT
TERMINAL
T = Load N = Utility E = Generato
NER
GE Zenith Controls 3
ZTX Operation and Maintenance Manual (72R-1000)
Installation
(cont’d)
Control Connections
Connecting Engine Start may cause Generator to start. Before connecting, turn Generator OFF.
With the Generator breaker open and the Generator control switch off, install the Generator start connections.
Note:
N = Utility Position E = Generator Position
Manual operation is possible for maintenance purposes only. Manual operation of the switch can be checked before it is operated electrically.
With all power off, insert a Phillips screwdriver or equivalent size tool into the manual operator socket and operate the transfer switch between the Utility and Generator positions. The transfer switch should operate smoothly without binding. Return the switch to the Utility position, remove the screwdriver.
Figure 4
Table 2
Tightening Torque for Lugs
Socket Size
Across Flats
Torque
Lb. - In. Lb. - Ft.
451/8 4 1005/32 8 1203/16 10 1507/32 12 2001/4 17 2755/16 23 3753/8 31 5001/2 42 6009/16 50
The engine-start terminals are clearly identified by a label on the microcontroller backplate. In the case of manual transfer switches, or in other applications not requiring the microprocessor, clearly marked terminal blocks are provided in the upper left corner of the control panel for the engine start control wires.
Terminals for field connections to the A3 Emergency auxiliary contacts and the A4 Normal auxiliary contacts are also provided. These terminals are clearly marked and appear on the side of the power panel. On 400 amp metal frame units these terminals appear on the bracket above the operator handle.
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Figure 3
g
SERIAL NUMBER:
RA
TING
: VOLTS -
AMPS -
SYSTEM VOLTS:
MODEL NUMBER:
HZ -
PHASE -
GE Zenith Controls
Figure 2
JP
Battery Connection
4 GE Zenith Controls
ZTX Operation and Maintenance Manual (72R-1000)
Installation
(cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
ATTENTION!
This applies only to the switches with the RM4-CAT exerciser option:
Only after ATS installation, connect a commercial-grade alkaline 9V battery to the MX60 controller via the har­ness connected to the controller. The battery should be placed in the holder installed just above the controller. The battery is used to maintain the exerciser function in the event of power outage. The battery should be replaced at least once a year. If the battery is not
installed and/or replaced as recommended, an exerciser set from the front panel will lose its settings during power outages and the exerciser will not work.
Note: Batter
y life if reduced if neither source is avail­able. Typical battery life when both sources are unavailable is 21 days.
Should the battery connection become disconnected in shipping, take the controller cover off and plug the harness into the receptacle in the top right corner of the MX controller as shown in figure 2 and 5. Reinstall the cover and connect the battery.
Battery and Holder
Battery Harness
MX60 Controller
(Under Cover)
Figure 5
GE Zenith Controls 5
ZTX Operation and Maintenance Manual (72R-1000)
Functional Test
Functional testing of the automatic transfer switch (ATS) is described in this section. Before proceeding, read and understand all instructions and review the operation of all accessories provided.
To begin the test, close the Utility source circuit breaker. Referring to Figure 7, the controller will illuminate the
Utility Available LED when proper voltage is sensed. If the ATS mechanism is set on S1, the S1 position LED will also light.. Verify the phase to phase voltages at the
Utility line terminals.
Next, close the Generator source breaker and start the engine generator. The S2 (Generator) Available LED
will illuminate when proper voltage and frequency levels are sensed. After both sources have been verified, shut
down the engine generator, and put the generator’s start control in the automatic position. Complete the visual inspection of the transfer switch, and replace the cabinet cover (or close the cabinet door).
Simulate a utility outage by opening the S1 Utility side breaker. The delay to engine start timer (P) begins its timing cycle. After the P timer has completed its timing cycle, the engine start contacts close to start the generator.
When generator voltage and frequency reach the preset restore points (see Table 4) the S2 Available LED illumi- nates. Simultaneously, the delay to generator timer (W) begins its timing cycle. When the W time delay is com­pleted the ATS will transfer to Generator, the S1 position
LED goes off, and the S2 position LED illuminates.
Reclose the Utility breaker to retransfer to utility. The delay to utility timer (T) begins its timing cycle (Table
3). When the T timer has completed its timing cycle, the ATS will transfer. The optional S2 position LEDs go off, and the S1 position LED illuminates. The delay engine stop timer (U) begins its timing cycle. The generator runs unloaded for the duration of the U timing cycle. When the timer completes its timing cycle, the generator will stop. The S2 Available LED goes off.
Installation
(cont’d)
Table 3
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
ATS Timing Cycle
Action P Timer W Timer T Timer U Timer
P - 5 sec. W - 20 sec. T - 5 min. U - 5 min.
S1 Fail or Time Delay Time Delay Time Delay Time Delay
Test or S2 Start S2 Stable S1 Stable S2 Stop
Exerciser
Transfer to S2 Retransfer to S1 Engine Cool-Down
S1 returns or Test/Exerciser Ends
Table 4
Preset Settings
Utility Generator
S1 Fail Voltage 80% Nominal Line Voltage S2 Fail Voltage 80% Nominal Line Voltage
S1 Restore 90% Nominal Line Voltage S2 Restore Voltage 90% Nominal Line Voltage
S1 Fail Frequency 80% S2 Fail Frequency 90%
S1 Restore Frequency 90% S2 Restore Frequency 95%
Timers
P Timer W Timer T Timer U Timer
P - 5 sec. W - 20 sec. T - 5 min. U - 5 min.
6 GE Zenith Controls
ZTX Operation and Maintenance Manual (72R-1000)
Installation
(cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
System Voltage Settings
ZTX controller boards are preconfigured to the system voltages specified at the time of order. Exact system volt­ages are normally set at the factory, however, depend­ing on the actual application and system nominal volt­age, ZTX control boards are capable of being adjusted slightly, to meet different source characteristics for voltage as well as frequency. (See Table 5)
Figure 6 (on right) shows the variations each of the 3 basic types of controllers can be adjusted to within its nominal voltage range. Position Jumpers JP1 and JP2, as needed for voltage. Position JP3 for frequency. As with any other Jumper setting, always remove power completely from the controller before making changes.
Note: Do not change voltage Jumper positions without consulting service or technical support. Arbitrarily changing voltage jumpers can adversely affect ATS operation.
Type 1 Type 2 Type 3 Type 4 Frequency
120V 208 - 240VAC 380 - 416VAC 440 - 480VAC JP1 JP2 JP1 JP2 JP1 JP2 JP1 JP2 JP3 B B 208 A B 380 B B 440 B A 50 Hz A
- - 220 B A 416 A B 480 A A 60 Hz B
- - 240 A A - - - - - - - -
Table 5
Figure 6
Voltage / Frequency Selection Jumper Settings
240/480
JP1
JP2
BA
208/416
JP1
JP2
BA
50Hz
JP3
BA
120/380
JP1
JP2
BA
220/440
JP1
JP2
BA
60Hz
JP3
BA
GE Zenith Controls 7
ZTX Operation and Maintenance Manual (72R-1000)
Control Interface
Pushbuttons
TEST - Pressed and held for 1 second Simulates a power outage, starts the Generator and transfers the ATS to S2.
EXER SET - Sets an Automatic Exerciser
BYPASS TIMER - Pressed while E is blinking bypasses any remaining countdown Timer
CANCEL - Depending on the current state of ATS operation, ends specific functions or indications
A
B
D
C
E
G H IF
Indicator LEDs
S1 (Utility) Available Green LED. When on, indicates source is acceptable.
S1 (Utility) Position Green LED. When on, indicates ATS is connected to Utility
S2 (Generator) Available Red LED. When on, indicates source is acceptable.
S2 (Generator) Position Red LED. When on, indicates ATS is connected to Generator.
Timing/In-phase Amber LED. When blinking, indicates the ATS is timing a Delay
When on steady, indicates the ATS is waiting for both sources to synchronize with each other.
Figure 7
A
B
C
D
E
F
G
H
I
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Using the Keypad Controls
TEST KEY
The TEST KEY initiates a transfer sequence to S2 and holds the ATS in that mode until either the CANCEL key is pressed or, a situation arises to cause the ATS to go back to S1(ie, S2 actually fails).
In order to perform a TEST, the ATS must be on S1 and S1 must qualify as a "good source" by being above the FAIL thresholds for both Voltage and Frequency (see Table 2).
Once the TEST KEY is pressed for at least 1 Sec, the ATS will begin the Timer Sequence (see figure 5), attempt to start S2 generator source, and if S2 qualifies as a "good source", transfer the load to S2. (There is no P-Time in a test)
The TEST key is typically used to perform a system operational or maintenance test or, to purposely cause and hold the Load off of S1. If during the TEST, S2 fails and S1 is available, the TEST will be cancelled and the Load will be immediately retransferred to S1.
EXER SET
Whenever it is required to have a regular test performed automatically on a repeating basis, the Automatic Exerciser function can be setup using this key.
Depending on the jumper settings shown in Figure 8, the ATS can be programmed to perform a repeating 7, 14, 21 or 28 day exercise at a particular time of day.
To initiate an Automatic Exercise, the EXER SET key is pressed and held for at least 1 Sec. at the desired exercise time. The ATS will begin the Timer Sequence, attempt to start S2 generator source and if S2 qualifies as a good source, transfer the Load to S2 for the dura­tion of the Generator Run-Time. After the Generator Run-time has expired, the timing sequence will restart and the Load will be transferred back to S1, after T­time, ending by running the U-time and finally ending the call for S2.
8 GE Zenith Controls
ZTX Operation and Maintenance Manual (72R-1000)
Control Interface
(cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
TIMER BYPASS
This key is used to bypass (truncate), any of the running timers shown in Table 3. Whenever the Timing/ Inphase LED is blinking, pressing the TIMER BYPASS will end that particular delay and cause the ATS con­troller to immediately jump to the next sequence step.
Note: The BYPASS key cannot be used to truncate an In-phase transfer sequence, or the P-Timer.
CANCEL
The CANCEL key performs 3 different cancel actions depending on the ATS current state of operation:
1. If the ATS is currently performing a TEST, the CANCEL key will cancel the test.
2. If an Automatic Exerciser has been set, press­ing and holding the CANCEL key for 10 Sec. will cancel (and remove), the set exercise
3. If after in-phase monitor has passed 1 minute, waiting for sources to synchronize, will cause transfer immediatly (which may result in an out-of-phase transfer).
GE Zenith Controls 9
ZTX Operation and Maintenance Manual (72R-1000)
Control Interface
(cont’d)
Figure 8
Automatic Generator Exerciser
The ZTX automatic generator Exerciser can perform a pre-scheduled repeating test of the generator and/or the ATS mechanism depending on which jumpers are selected on the controller board. Additionally, the ATS can be preset to perform the exercise every 7, 14, 21 or 28 days. Regardless of which interval is selected, all exercisers have a preset run-duration of 10 minutes.
Selection of the exerciser interval is through three jumpers located on the controller board as shown in Figure 6. The Exerciser comes from the factory preset at 28 days and is not active. To change the exerciser interval, remove power from the controller completely, and move the jumpers at positions jp4 and jp5 to match the selected repeat-cycle from the configurations shown in Figure 7.
Selecting Exerciser with or without Load Transfer
The Exerciser function can be programmed to perform either a Load-transfer or a non-Load transfer. Selecting either is done by changing the Jumper JP6 as shown in Figure 8. To change between a Load-transfer or no-Load transfer, remove power from the controller completely and move the jumper at position JP6.
Setting and Canceling an Exerciser
In order to set an automatic Exerciser, choose the exer­ciser interval and whether a Load-transfer or no-Load transfer is desired as stated above. An exercise can only be set if S1 is available and the ATS (and Load), is on S1 source.
To establish an Exerciser
At the exact time desired, press and hold the EXER SET key for at least 1 second. The ATS will immediately start an initial exercise by attempting to start the generator, running through the Timers (figure 3) and will either only start the generator, or, will start the generator and transfer the Load from S1 to S2, for the time duration of the exerciser interval, 10 minutes. Once the Exercise is completed, the ATS will continue the timing sequence and retransfer the Load back to S1, cool down the gen­erator and terminate until the next scheduled interval time. Any time an Exerciser has been established and is scheduled, the S2 Available and S2 position LEDs quick­ly blink approximately every 4 seconds as a reminder. However, if S2 source becomes available during the time
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
the ATS is waiting for the next impending exercise, the ATS will not show a blinking indication but instead will show the S2 Available LED as solidly on to indicate the true condition of S2. Any Exercise event can be prema­turely canceled by pressing the CANCEL key.
Note: pressing the CANCEL key in the middle of an scheduled event does not cancel a set Exerciser, but only cancels the current event.
To completely clear an already-set Exerciser
A set Exerciser can be completely cleared out of memory by pressing and holding the CANCEL key for at least 10 Seconds causing the blink indication to stop.
If S2 fails to meet the criteria for a good source, during an Exercise attempt, the Controller will continue to hold the P-contacts closed for the duration of the Runtime timer then wait for the next scheduled exercise. If S2 fails during an Exercise, the Controller will abort that exercise and wait till then next scheduled exercise.
Automatic Exerciser Jumper Settings
7 Day
JP4
JP5
BA
21 Day
JP4
JP5
BA
14 Day
JP4
JP5
BA
28 Day
JP4
JP5
BA
JP6
JP6
BA
No Load
Load
10 GE Zenith Controls
ZTX Operation and Maintenance Manual (72R-1000)
Control Interface
(cont’d)
In-Phase Monitor
ZTX ATS senses when the sources are as far out as 2 Hz or as close as .01Hz in frequency differential of each other and transfers the load to and from either source in-phase. If turned on, R50 In-Phase monitor tracks the frequency of both the Utility and Generator sources allowing a smooth, synchronous transfer of the load, which is especially beneficial where conveyors, pumps and other motor loads are involved. ZTX indicates it is waiting for the sources to synchronize by holding the Timer/In-Phase LED on. When both sources have syn­chronized, the ATS will transfer the Load (within 20° of each other, if sources are within 2Hz differential), and the Timer/In-Phase LED will turn off. If the sources fail to synchronize, after 1 minute, the controller will blink the Timer/In-Phase LED once, alerting the operator that the In-Phase monitor function can be bypassed by pressing the CANCEL key, causing an immediate trans­fer (see Cancel Key function). If the CANCEL key is not pressed, the ZTX will continue to wait for an in­Phase condition to occur.
In a typical ATS application, one source is on the utility and one source is a backup system such as a gas or diesel generator. Because sources have a slight frequency difference, sources come in and out of phase. If ZTX In-Phase Monitor is on, The ZTX ATS Controller monitors both sources and transfers the Load at the ideal time to minimize back-EMF conditions.
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
In the case of both sources coming from the same source, or, one configured as WYE and the other as DELTA, the frequency difference is fixed at the same frequency or fixed but 30 degrees out of phase. In those cases, In-Phase Monitor can be turned off.
In-Phase Monitor is turned on as default from the factory. To turn In-Phase Monitor OFF or ON, take the following steps:
Turn In-Phase Monitor OFF:
1. Remove all power, (both S1 and S2) from the controller. Wait at least 20 seconds.
2. From the keypad, hold both the BYPASS and CANCEL keys down while energizing either source. If In-Phase Monitor was on, the Timer / In-phase LED will flash once for 1 second, then go out. The In-Phase Monitor is now off.
Turn In-Phase Monitor ON:
1. Remove all power, (both S1 and S2) from the controller. Wait at least 20 seconds.
2. From the keypad, hold both the BYPASS and CANCEL keys down while energizing either source. If In-Phase Monitor was off, the Timer/In-Phase LED will light and remain lit until the keys are released. The In-Phase Monitor is now on.
Timer / In-phase LED
Figure 9
GE Zenith Controls 11
ZTX Operation and Maintenance Manual (72R-1000)
Example Systems
Partial Coverage System
Total Coverage System
Figure 9
Figure 10
Loads Utility Source
Utility Panel
Transfer Switch
Generator
Circuit
Breaker
Distribution Panel
Source
Loads
Utility Source
Circuit
Breaker
Transfer Switch
Circuit
Breaker
Main
Breaker
Panel
Generator Source
All Loads
12 GE Zenith Controls
ZTX Operation and Maintenance Manual (72R-1000)
Typical Diagrams
OM
3
3
0
Power Circuit Schematic 40-240 Amps
Power Panel Layout Interconnect Plug
Figure 11
Figure 12
Figure 13
C
PTIONAL
N
1
GE Zenith Controls 13
ZTX Operation and Maintenance Manual (72R-1000)
Replacement Parts
3
Standard Transition — 40 to 200 Amps
TAG DESCRIPTION
VOLTAGE
CN/CE Solenoid
Solenoid Plunger and Link
SCN/SCE Coil Cutout Switch
A3/A4 Auxiliary Contacts
120 208 220
240 380/416 440/480
K-2207 K-2208 K-2208 K-2228 K-2212 K-2209
ALL 57P-1030
120-480V L-3078
L-3078
SCN/SCE
Coil Cutout Switch
600V L-4027
BR
Rectifier
ALL PS-5076
40 TO 200 AMPS
Figure 14
Table 7
BR
CN/CE
SP+L
A
SCN/SCE
14 GE Zenith Controls
ZTX Operation and Maintenance Manual (72R-1000)
Replacement Parts
(cont’d)
Standard Transition - 225 to 400 Amps
ge
g
n
d
s
*
*
00
g
,2,
,2,
Size
#4-6
#4-6
s
6B
E
SEPo
h
4
s
er
6
#
Figure 15
Table 8
BR
CN/CE
T1 T2 T3 TN
E1 E2 E3 EN
N1 N2 N3 NN
SN
A4
SE A3
Ta
1,2,3 N
E 1
3 N
T 1
3 N
CN/C
N/
A3/A
Descriptio
Cable Connection Lu
Wire
lenoid
sition Sense Limit Switc
Auxiliary Contact
Rectifi
Recommende
as Spare
225, 250
-2701
6-250 MCM
il Volt
08/220/240 K-224
Stock Numbers by Ampera
260, 300
-2701
00 MCM
L-3078
PS-507
4
-2701
00 MCM
GE Zenith Controls 15
ZTX Operation and Maintenance Manual (72R-1000)
Troubleshooting
Symptom Possible Cause Corrective Action
S1 or S2 Available LED not lit Sources either fully or partially unacceptable Check for under voltage
S1 or S2 breakers open Check for missing phase (s)
Check for under frequency
ATS will not retransfer Load T - Timer has not expired back to Utility Automatic Exerciser is in process
S1 Utility fully or partially unacceptable
ATS does not transfer Load to S2 S2 Generator fully or partially unacceptable Set motor-saver to dropout below (generator) Motor loads on system creating enough back- ATS Fail setpoint
EMF to keep missing phase from falling below Fail setpoint.
S2 Generator will not start X1 or X2 not connected Check Generator Start wiring
S2 Generator will not shut down U - Timer not expired Wait for U timer to expire
Automatic Exerciser in process
All LEDs off Keypad connector unplugged at Controller
Both source breakers open
ATS will not transfer in-phase In-Phase monitor not on Turn on In-Phase monitor
Frequency difference between S1 and Adjust Generator governor to hold S2 greater than 2Hz. freqency closer to Utility
ATS will not retain a Battery dead or missing Replace battery with a fresh industrial Set Automatic Exerciser grade Alkaline battery
Timer/In-Phase LED constantly on Both sources locked in frequency or one Turn In-Phase monitor off
source greater than 20° out of phase
S1 and S2 LEDs Blinking Phase Rotation Mis-match between sources Rewire sources to be same rotation
S1 Position LED Blinking SN limit switch bad or intermittent Check connection or SN limit switch
S2 Position LED Blinking SE Limit switch bad or intermittent Check connection or SE limit switch
Both S1 and S2 Positioin Solenoid bad or disconnected Requires CANCEL key to clear ­LEDs Blinking ATS contactor in mid-position check Solenoid
Requires CANCEL key to clear ­Check both limit switches
Service must be performed by qualified personnel.
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Table 9
A Product of GE Consumer & Industrial General Electric Company
830
West 40
th
Street, Chicago, IL
60609 USA
773 299-6600, Fax: 773 247-7805
www.geelectrical.com
g
GE Zenith Controls
Loading...