GE ZTS Series, ZTSD Series Operation And Maintenance

Page 1
GE Zenith Controls
e
ZTS/ZTSD Series Transfer Switches 40-4000 Amps
71R-3000
5/03
Operation and Maintenance Manual
Page 2
1 1 1 1 1
1 1 1
1
1
1
1 1
1
1 1 1
1 1
1 1 1 1 1
1 1 1 1
1
1 1 1
Authorized Service
For GE parts and service, call: 773 299-6600
Table of Contents
Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Equipment Inspection and Storage . . . . . . . . . 1
Final Equipment Inspection . . . . . . . . . . . . . . . 1
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Power Connections . . . . . . . . . . . . . . . . . . . . . . 2
Engine Start Control Connections . . . . . . . . 2-3
Initial Energization . . . . . . . . . . . . . . . . . . . . 3-4
Control Connections . . . . . . . . . . . . . . . . . . . . 5
Entelli-Switch 250 Microprocessor Controller . . . . . 6
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LCD & Keypad . . . . . . . . . . . . . . . . . . . . . . . . . 7
User Setting for Voltage & Frequency . . . . . . . 8
Accessory Group Packages. . . . . . . . . . . . . . . . . 9
Accessory Definitions . . . . . . . . . . . . . . . . . 10-13
How to Set the System Clock . . . . . . . . . . . . . 13
CDT One Event Timer Exerciser . . . . . . . . . . 14
CDP Clock Exerciser . . . . . . . . . . . . . . . . . . . 15
User Setup - CFG Menu . . . . . . . . . . . . . . . . . 16
User Setup - SET Menu . . . . . . . . . . . . . . . . . 17
User Setup - System Info . . . . . . . . . . . . . . . . 18
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
ATS Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Standard Transition . . . . . . . . . . . . . . . . . . . . 19
Delayed Transition . . . . . . . . . . . . . . . . . . . . . 19
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . 20
Standard Transition . . . . . . . . . . . . . . . . . . . . 20
Delayed Transition . . . . . . . . . . . . . . . . . . . . . 20
Page
Relay/Transformer (R/T Box) . . . . . . . . . . . . . . . 21
Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Delayed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Troubleshooting & Diagnostics . . . . . . . . . . . . . . . 24
Maintenance and Testing . . . . . . . . . . . . . . . . . . . . 25
Inspection and Cleaning . . . . . . . . . . . . . . . . 25
Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . 26
Standard Transition . . . . . . . . . . . . . . . . . . . . 26
40-200 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
225-400 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
600-1200 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1600-3000 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4000 Amps
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Delayed Transition . . . . . . . . . . . . . . . . . . . . . 31
40-400 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
600-1200 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
1600-3000 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4000 Amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
ZTSH/ZTSDH/ZTSDL/ZTSHL/ZTSDHL . . . . . . 35
Standard Control Panel Layout (SSRCP) . . . . 35
Panel Mount Control Relays . . . . . . . . . . . . . . 35
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . 36
Adjustments and Settings . . . . . . . . . . . . . . . . . . . . 37
Solid State Timers . . . . . . . . . . . . . . . . . . . . . . 37
Voltage/Frequency Sensor (VSFM) . . . . . . . . 37
Solid State Phase Relay . . . . . . . . . . . . . . . . . . 37
Introduction
GE Zenith Transfer Switches are used to provide a continuous source of power for lighting and other critical loads by auto
­matically transferring from source 1 power to source 2 power in the event that source 1 voltage falls below preset limits.
Voltage sensing and system control is performed via a state-of-the-art microcontroller located on the cabinet door
. It is designed to give highly accurate control of the transfer switch system.
All GE Zenith transfer switches are designed for use on emergency or standby systems, and are rated for total system or motor loads. T
ransfer switches are UL Listed under Standard 1008 and CSA Certified under Standard C22.2 No. 178 and IEC Listed under Standard 947.
NOTES:
A protective device such as a molded case circuit breaker or fused disconnect switch MUST be installed on both sources of incoming power for circuit protection and as a disconnection device.
All references made within this manual about the term “S1” or “Source 1” relate to a Normal Power Source. All references made about the term “S2” or “Source 2” relate to an Emergency or Alternative Power Source.
Page 3

Safety

DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
The safe operation of your switch is GE Zenith’s focus. The proper storage, installation, operation and mainte­nance will help increase the life of the switch.
CAUTION
Due to hazardous voltage and current, GE Zenith rec-
ommends that a
GE Zenith Certified technician or a
qualified electrician must perform the
installation and maintenance of the switch.
Equipment Inspection and Storage
Once you have received the transfer switch, inspect it for any damage. This includes damage to the enclosure, power panel, control panel and wiring harness. If any damage is found or suspected, file a claim as soon as possible with the carrier and notify the nearest
GE
Zenith representative.
Before installation, if it is necessary, store the transfer switch in a clean dr
y place, protected from dirt and water. Provide ample air circulation and heat, if neces­sary, to prevent condensation.
Storage Temperature
Operating T
emperature
(Ambient): Humidity
-30°C to
40-400
AMP
5% to 95% +75°C (-22°F to +167°F)
(molded shell)
-20°C to +65°C (-4°F to +149°F)
(non-con-
densing)
40-4000
AMP
(all other frame and panel types)
-20°C to +60°C (-4°F to +140°F)
Final Equipment Inspection
Prior to energizing the transfer switch:
1. Remove any debris incurred, with a vacuum, due to shipment or installation.
WARNING
Do not use a blower since debris may
become lodged in the electrical and
mechanical components and cause damage.
2. Verify that all cabled connections are correct and that phase rotation of both sources match.
3. Check engine start connections.
4. Verify the correct connection of all control wires.
5. Check settings of all timers and adjust as necessar
y.
6. Adjust any optional accessories as required.
7. Check the lug torque values of the power connections.
NOTE: Lug torque values are specified
in table 2 on pg.2.
8. Make sure that all covers and barriers are installed and properly fastened.
NOTE: Power panels ship from GE Zenith
in Source 1 Position.
Each GE Zenith transfer switch is factory wired and tested. A complete information package is furnished with each switch which includes:
a. Sequence of operation. b. Description and operation of
all accessories supplied.
c. Power panel connection diagram
and schematic.
d. Description and identification of
all customer field connections.
Installation of GE Zenith transfer switches includes:
a. Mounting the transfer switch cabinet. b. Connection of Source 1, Source 2,
and Load cables or bus bars.
c. Connection of external control
circuits as required.
Mounting
Adequate lifting means must be used to mount the transfer switch into place. The recommended method for moving the transfer switch using the lifting eyes, where supplied, and a spreader bar is illustrated in Figure 1. Enough room should be allowed to open the cabinet doors fully for inspection and servicing of the switch per NEC and local codes.
CAUTION
Before drilling conduit entry holes or any
accessory mounting holes, cover and protect
the switch and control panel to prevent dirt
and metal fragments from entering the mechanical and electrical components.
Failure to do so may result in
damage and malfunction of the switch.
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
1
Page 4

Installation

DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Power Connections
SPREADER BAR
GE Zenith transfer switches are supplied with UL listed
45°
solderless screw type terminals as standard for the
H
Source 1, Source 2 and Load power connections. Table 1 lists the number and sizes of cable lugs supplied as standard for each switch amp rating.
Connect the Source 1, Source 2, and Load conductors
LIFTING EYES
to the clearly marked terminals on the transfer switch. Remove sur
face oxides from cables by cleaning with a wire brush. Verify that all connections are correct before tightening the lugs. All cable lug connections must be tightened to the proper torque values as shown in Table 2.
NOTE
: Do not run cables or wiring behind
CABINET
D
front-connected transfer switches.
NOTE
: When lifting the switch using a spreader bar,
height H must be equal to half of distance D.
Figure 1
Power Connections: Screw Type Terminals for External Power Connections
Switch Size
(Amps)
Source 1, Source 2 & Load Terminals Neutral Bar (When Required)
Cable Per Pole Range of Wire Sizes No. of Cables Range of Wire Sizes
40 1 #8 AWG to 1/0 3 #8 AWG to 1/0
80 1 #8 AWG to 1/0 3 #8 AWG to 1/0 100 1 #8 AWG to 1/0 3 #8 AWG to 1/0 150 1 #8 AWG to 3/0 3 #8 AWG to 300 MCM
200, 225, 2500 1 #6 AWG to 250 MCM 3 #6 AWG to 300 MCM 260, 300*, 400
1
#4 AWG to 600 MCM 3 #4 AWG to 300 MCM
600 2 #2 AWG to 600 MCM 8 #2 AWG to 600 MCM
800, 1000, 1200 4 #2 AWG to 600 MCM 12 #2 AWG to 600 MCM
1600, 2000
2600, 3000, 4000
Line, Load and Neutral terminals are located in the rear of switch
and arranged for bus bar locations
Table 1
Engine Start Control Connections
Engine-start control wires connect to control terminals beside the Entelli-Switch 250. Engine start terminals are indicated by a schematic symbol (the symbol indicates the contact state for a de-energized normal source). Figure 2 shows the engine-start contacts.
Make all other necessary control connections to the control panel terminal blocks per the schematics supplied with the A
TS.
NOTE: All control wires (18-12 AWG) must be
torqued to 19 in/lbs.
Tightening Torque for Lugs
Socket Size
Across Flats
Torque
Lb. - In.
Lb. - Ft.
1/8 45
4
5/32
100
8
3/16 120
10
7/32
150
12
1/4
200 17
5/16 275
23
3/8
375
31
1/2
500 42
9/16
600 50
Table 2
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Contr
ols 2
Page 5
Installation
(cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Engine Start Control Connections
The engine-start terminals are clearly identified by a label on the microcontroller backplate. In the case of manual transfer switches, or in other applications not requiring the microprocessor, clearly marked terminal blocks are provided in the upper left corner of the control panel for the engine start control wires.
Transfer Switch. Figure 5 (pg.5) shows location of engine start connections for Automatic Transfer Switch.
Terminals for field connections to the A3 Source 2 auxiliary contacts and the A4 Normal auxiliary contacts are also provided. These terminals are clearly marked and appear on the side of the power panel. On 400 amp metal frame units these terminals appear on the bracket above the operator handle.
E
Figure 2
Initial Energization
Before proceeding, refer to the information package supplied with the ATS and read and understand the information on all accessories provided.
1. Unlock the enclosure.
2. Open the enclosure.
3. Verify the correct system voltage.
NOTE: The equipment rating nameplate on
the transfer switch lists the voltage. See
Figure 3
.
4. Close Source 1 circuit. breaker.
NOTE:The controller will illuminate Source 1
Available LED if proper voltage is sensed.
5. Verify the phase to phase voltages at Source 1 line terminals.
6. Close Source 2 source circuit breaker.
7. Start the generator’s engine.
NOTE
: The controller will illuminate Source 2
Available LED when preset voltage and frequency levels are reached.
8. Verify the phase to phase voltages at Source 1 line terminals.
9. Verify that the phase rotation of Source 1 is the same as the phase rotation of Source 2.
10. Shut down the generator’s engine.
11. Place the starting control in the Automatic position.
12. Complete the visual inspection of the transfer switch.
13. Close the enclosure.
14. Lock the enclosure.
g
GE Zenith Controls
SERIAL NUMBER:
RATING: VOLTS -
HZ -
AMPS -
PHASE -
SYSTEM VOLTS:
MODEL NUMBER:
Figure 3
CAUTIONS
Certain accessories, per specific
schematics, can inhibit automatic transfer.
Engine Gen-Set could start when
engine control wires are attached.
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
3
4
5
6
1
P Relay
2
(Engine Start)
3
Contact rating is 10 Ampere at 120VAC or 28VDC Gold plated
Page 6
Installation
(cont’d)
Initial Energization (cont’d)
After all options and accessories are checked and verified, follow these steps to set up the ATS. Refer to Entelli-Switch 250 display Figure 4. The annunciation LEDs illuminate to indicate (1) source availability, (2) ATS position, and (3) Entelli-Switch 250 control function (timing).
Entelli-Switch 250
S1 OK
21:56
MON 23 APR 2002
MORE TEST
Figure 4 – LCD and keypad
1. Unlock the enclosure.
2. Open the enclosure.
3. Place the Disconnect Switch in the Inhibit.
NOTE: This step is only performed if the
“DS” Option was purchased.
4. Close the external (up-stream) Source 1 circuit breaker.
NOTES
: Source 1 Available and Source 1
Position LED’s will illuminate.
If Source 1 Available LED does not illuminate, verify that Source 1 Voltage is above the preset restore value.
The Gen-Set will start and run while Source 2 stop Delay Timer is timing.
5. Close the External (up-stream) Source 2 line circuit breaker.
6. Start the engine generator in
MANUAL mode.
NOTE: When the voltage and frequency
reach preset values, the Source 2 Available LED will illuminate.
7. Verify the phase to phase voltages at Source 2 line terminals.
8. Verify that the phase rotation of Source 2 is the same as the phase rotation of Source 1.
9. Shut down the generator's engine. (Place in Automatic Mode.)
NOTE
: Source 2 Available LED
will turn off.
NOTE: The engine generator will continue
to run for the duration of Source 2 Stop Delay Timer.
10. Place the disconnect switch to ENABLE.
11. Complete the visual inspection of the transfer switch.
12. Close the enclosure.
13. Lock the enclosure.
WARNING
When performing a hi-pot or
dielectric test on the power section,
DISCONNECT
the control panel plugs from
the microprocessor to avoid potential damage.
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
4
Page 7
Installation
(cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Control Connections
Figure 5
Clock Program Backup Battery
Remove protective
Connections
Engine Start
strip to enable clock functions
Network Connector
Input/Output
Connectors
to I/O Modules
To R/T Box
To Power
Panel
A complete information package is furnished with each transfer switch including a complete connection diagram and schematic which details all necessary control circuit field connections.
The engine start control wires connect to the engine start relay terminals located to the left of the microprocessor
. Figure 5 shows the location
of these terminals.
The terminals are clearly identified by a label on the microcontroller backplate. In the case of manual trans
­fer switches, or in other applications not requiring the microprocessor
, clearly marked terminal blocks are provided in the upper left corner of the control panel for the engine start control wires.
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
5
Page 8

Entelli-Switch 250 Controller

Entelli-Switch 250 Controller
Consists of two major assemblies:
I. The Micr
oprocessor contains the following:
A. Entelli-Switch 250 Board - Customer Input
and Output (I/O) for system inter
face. Located on the left hand side of the back of the unit (see figure 6)
1. I/O accessories that can be found here are: a. Engine start relay P output b. Pre-Signal to transfer T3, W3 and
UMD output (optional)
c. Transfer Inhibit Q3 and Q7 input
(optional) d. Remote test Q2 input (optional) e. Network interface ZNET
input/output (optional)
B. LCD and Keypad located on the exterior
of the door (see figure 7)
1. User accessibility to the following: a. LED indication of source
availability
b. LED indication of transfer
switch position
c. LCD screen indicates:
(1) timer count down (numeric) (2) event reporting (text)
d. Keypad provides user interface to:
[in conjunction with LCD screen]
(1) Setting sensors and timers (2) Configuring logic accessories
II. The R/T bo
x (relay transformer box) contains
the following: (see figure 6)
A. Relays which are required for controller output
to energize the transferring mechanism of the transfer switch at line voltage.
B. Transformers which drop line voltage
to control level for controller input.
Engine Start Relay P
I/O Interface
Board
Battery Strip
and
Access
Code Label
R/T Box
Entelli-Switch 250
Figure 6
Entelli-Switch 250
S1 OK
21:56
MON 23 APR 2002
MORE TEST
Figure 7
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
6
Page 9
Entelli-Switch 250 Controller
(cont’d)
LCD & Keypad
These options are accessible through the LCD and keypad (see figure below). To become familiar with the options loaded into a particular unit, scrolling through the SET and CFG menu will show the descriptions of the options (see pages 16-17). These menus are the very same menus that are used to access the setting and/or configuration of these options. The SET (setting) menu is primarily used to show or change, time and voltage settings. The CFG menu is primarily used to turn an option on or off. When scrolling through these menus,
no changes can be made without entry of the access code. The factory set six-digit access code is located on a white label on the back of the unit (see figure 10 pgs. 16-18).
The Entelli-Switch 250 has many logic options. Each controller is downloaded with options at the time of manufacture. The collection of options that any one controller has is specified at the time of order placement. The following pages include all the options that can reside in the controller. Not all units include all options.
Figure 8
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
7
Source 1 LED (Green) indicates Source 1 is acceptable for use
Source 1 Position LED (Green) indicates Power Panel (ATS) is closed to Source 1 position
Source 2 Position LED (Red) indicates Power Panel (ATS) is closed to Source 2 position
Source 2 (Red) indicates Source 2 is acceptable for use
LCD Screen
Current Time, Day and Date of Display
Menus (MORE, CFG, TEST)
#1 or the word on the LCD above the key. The word above the key changes depending on which screen is being displayed.
S1 OK
01: 50
FRI 31 MAY 2003
MORE CFG TEST SET
Entelli-Switch 250
#2 or the word on the LCD above the key. The word above the key changes depending on which screen is being displayed.
* E *
#3 or the word on the LCD above the key. The word above the key changes depending on which screen is being displayed.
Exercise Event "Impending"
SET Menu
Keypad
#4 or the word on the LCD above the key. The word above the key changes depending on which screen is being displayed.
Page 10
User Setting for Voltage & Frequency
Standard 3-Phase Sensing on 3 and 4 Pole Units
Source 1
Under Voltage "Restore"
Factory Default: 90% This adjustment determines the minimum acceptable voltage required to transfer to Source 1. Adjust via the SET menu. Range is 85% to 100% in 1% increments (see page 17). Once satisfied, the T timer will begin timing to transfer to Source 1.
Under Voltage "Fail"
Factory Default: 80% This adjustment determines the low voltage threshold. Adjust via the SET menu. Range is 75% to 98% in 1% increments (see page 17). "Fail" must be a minimum of 2 % below "Restore" setting. Once voltage falls below threshold, P timer begins timing to signal Source 2 Generator to start.
Under Frequency "Restore"
Factory Default: 95% This adjustment determines the minimum acceptable frequency required to transfer to Source 1. Adjust via the SET menu. Range is 90% to 100% in 1% increments (see page 17). Once satisfied, the T timer will begin timing to transfer to Source 1.
Under Frequency "Fail"
Factory Default: 90% This adjustment determines the low frequency threshold. Adjust via the SET menu. Range is 88% to 98% in 1% increments (see page 17). "Fail" must be a minimum of 2 % below "Restore" setting. Once satisfied, the T timer will begin timing to transfer to Source 1.
Over Frequency "Restore"
Factory Default: 102% This adjustment determines the minimum acceptable Over Frequency threshold at which the transfer switch is allowed to re-transfer to Source 1. Adjust via the SET menu. Range is 102% to 104% in 1% increments (see page 17). “Restore” must be a minimum of 1% below “Fail” setting.
Over Frequency "Fail"
Factory Default: 105% This adjustment determines the maximum acceptable Over Frequency
. Adjust via the SET menu. Range is 103% to 105% in 1% increments (see page 17).Once exceeded, the P timer begins timing to signal the generator to start.
Source 2
Under Voltage "Restore"
Factory Default: 90% This adjustment determines the minimum acceptable voltage required to transfer to Source 2. Adjust via the SET menu. Range is 85% to 100% in 1% increments (see page 17). Once satisfied, the W timer will begin timing to transfer to Source 2.
Under Voltage "Fail"
Factory Default: 80% This adjustment determines the low voltage threshold. Adjust via the SET menu. Range is 75% to 98% in 1% increments (see page 17). "Fail" must be a minimum of 2 % below "Restore" setting. Once voltage falls below threshold, T timer will be bypassed to expedite the transfer to Source 1.
Over Voltage "Fail"
Factory Default: 110% This adjustment determines the maximum acceptable Over V
oltage. Adjust via the SET menu. Range is 105% to 110% in 1% increments (see page 17). Once exceed­ed, the T timer will be bypassed to expedite the transfer to Source 1.
Over Voltage "Restore"
Factory Default: 105% This adjustment determines the minimum acceptable Over V
oltage threshold at which the transfer switch is allowed to transfer to Source 2. Adjust via the SET menu. Range is 103% to 105% in 1% increments (see page 17). “Restore” must be a minimum of 2% below “Fail” setting.
Under Frequency "Restore"
Factory Default: 95% This adjustment determines the minimum acceptable frequency required to transfer to Source 2. Adjust via the SET menu. Range is 90% to 100% in 1% increments (see page 17). Once satisfied, the W timer will begin timing to transfer to Source 2.
Under Frequency "Fail"
Factory Default: 90% This adjustment determines the low frequency threshold. Adjust via the SET menu. Range is 88% to 98% in 1% increments (see page 17). "Fail" must be a minimum of 2 % below "Restore" setting. Once satisfied, the W timer will begin timing to transfer to Source 2.
Over Frequency "Fail"
Factory Default: 105% This adjustment determines the maximum acceptable Over Frequency
. Adjust via the SET menu. Range is 103% to 105% in 1% increments (see page 17). Once exceeded, the T timer will be bypassed to expedite the transfer to Source 1.
Over Frequency "Restore"
Factory Default: 102% This adjustment determines the minimum acceptable Over Frequency threshold at which the transfer switch is allowed to re-transfer to Source 2. Adjust via the SET menu. Range is 102% to 104% in 1% increments (see page 17). “Restore” must be a minimum of 1% below “Fail” setting.
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls 8
Page 11

Accessory Group Packages

Table 3
Standard Accessory included in the group package. Optional Accessory not included but can be added to group package. Optional Accessory. Can not be used with accessory having the same symbol. N/A Denotes an Accessory with 2 circuits as a standard.
*
Delayed Transition Units Only.
Denotes an Accessory with 3 circuits as a standard.
**
Optional for 40-400 Amp
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
9
Accessories
6P A1 A1E A3 A4 Calibrate CDT CDP **DS *DT *DW E EL/P K/P L1 L2 L3 L4 *LN P1 Q2 Q3 Q7 R1-1 R1-3 R15 *R15D R16 R50 S5P S12P S13P T T3/W3 U UMD VI W YEN
STDS EXES
2 2
2
2
2
2
Group Packages CONS
SENS SPES PSGS
2 2
2
2
2 2
2
2
2 2
2
2
3 3
2
2
2
2
3
Page 12

Accessory Definitions

6P
Test Switch, Momentary
6A
Test Switch, Maintained Auto/Momentary Test
6AP
Test Switch, Maintained/Momentary utilizing keypad
6B
Test Switch, Maintained - Auto / Momentary - Test, Key Operated
6C
Test Switch, Maintained - Auto / Maintained - Test, Key Operated
A1
Auxiliary Contact, operates on Source 1 line failure.
A1E
Auxiliary Contact, operates on Source 2 line failure.
A3
Auxiliary Contact: Closed in emergency (Source 2) Additional Available (10 max.) and need to be specified.
A4
Auxiliary Contact: Closed in normal (Source 1) Additional Available (10 max.) and need to be specified.
A62
Sequential Universal Motor Load Disconnect Circuit. Normally closed auxiliary contacts for motor loads. Open 0-60 seconds prior to transfer, after transfer, or both in either direction then re-close in timed sequence after transfer.
AB3
Auxiliary Contact: Closed in bypass emergency (Source 2) (S.P.D.T.) (Standard up to 400 Amp) Additional Available (10 max.) and need to be specified.
AB4
Auxiliary Contact: Closed in bypass normal (Source 1) (S.P.D.T.) (Standard up to 400 Amp) Additional Available (10 max.) and need to be specified.
B9
Battery charger connections.
Calibrate
While monitoring the actual Phase to Phase voltage lev­els and Frequency with a calibrated test equipment, the Phase to Phase voltage sensing and Frequency can be adjusted accordingly
. Calibration capabilities are available for Frequency and AB, BC, CA Phase to Phase voltage for both Sources. Adjust via SET menu (see page 18)
CDP
Clock Exerciser Load/ No Load: Allows the Generator to start and run unloaded or to simulate a power failure, start Generator and run under load. Can be configured by end user for 1, 7, 14, 28, 365 day cycle. (See page 16)
CDT
Load or NO-Load. One event exerciser with adjustable Engine exercise timer. Exercise duration can be set between 5 and 60 minutes in 1 minute increments. Can be configured to run every 1, 7, 14, or 28 days. Factory Default is 20minutes. When exerciser is impending, (*E*) appears in the upper right hand corner of LCD screen. See page 15 for instructions. Configured via CFG (see page 17). Set via SET menu (see page 18).
CTAP
Alarm Panel on transfer to Source 2 with Silence button.
DS
Disconnect Switch, Auto/Inhibit. Inhibits transfer in either direction when in inhibit. Allows automatic operation when in Auto. (40-400 Amps optional, 600-4000 Amps standard)
DT (Delayed Transition Only)
Time Delay from Neutral Switch position to Source 1 position. Adjustable 0-10 minutes in 1 second incre­ments. Standard setting is 5 seconds Adjust via SET menu (see page 18)
DW (Delayed Transition Only)
Time Delay from Neutral Switch position to Source 2 position. Adjustable 0-10 minutes in 1 second incre­ments. Standard setting is 5 seconds.Adjust via SET menu (see page 18)
E
Engine Start Contact
EL/P
Event Log: Sequentially Numbered Log
of 16 events that track date, time, reason and action taken
System Data:
Total Life Transfers (N2P) Days Powered Up Total Transfers to S2 Total S1 Failures Time S1 available in Hrs Time S2 available in Hrs. (N1P)
F
Fan contact, operates when generator is running.
HT
Heater and Thermostat
K
Frequency Meter, Door mount.
K/P
Frequency Indication for S1 and S2
L
LNP Center-off position LCD-Indicator Indicating LED lights:
L1 Indicates Switch in Source 2 position. L2 Indicates Switch in Source 1 position. L3 Indicates Source 1 available. L4 Indicates Source 2 available.
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls 10
Page 13
Accessory Definitions
(cont’d)
M1
Single Phase Amp Meter
M2
Three Phase Amp Meter
M80
3000 Digital Power Monitor
M82
5200 Digital Power Meter
M83A
EPM 5300 Digital Power Meter with Modbus Port
M83B
EPM 5350 Digital Power Meter with Ethernet Port
M84
7430 Digital Power Meter , Wye or Delta
M85A
EPM 9450 Digital Power Meter, Ethernet
M85B
EPM 9450 Digital Power Meter with Internal 56K Mod.
M86A
EPM 9650 Digital Power Meter, Wye or Delta, RS232 or RS485
M86B
EPM 9650 Digital Power Meter, Wye or Delta, RS232 or RS485
N1
Running Time Meter, Door mount
N2
Operation Counter, Door Mount
P1
Time Delay Source 2 Start. Adjustable 0-10 seconds. Standard setting is 3 seconds. Adjust via SET menu (see page 18)
P2
Time Delay S2 Start. Adjustable 1/6 to 300 seconds.
Q2
Remote Peak Shave or Area Protection Circuit. Energize Q2 to simulate Source 1 Line failure causing the Generator to start and transfer the load to Source 2. Should Emergency fail during this operation, Transfer Switch will retransfer back to Source 1.
Q3
Remote inhibit transfer to Source 2 circuit. Energize Q3 input to allow transfer to Source 2. To enable Q3 option, engage Q3 jumper.
Q7
Inhibit transfer to Source 1 circuit. Energize Q7 input to prevent transfer to Source 1.
R1-1/R1-3
Source 1 Over Voltage sensing for single and three phase systems. Source 1 Over Voltage "Fail" Factory Default: 110% This adjustment determines the maximum acceptable over voltage. Adjust via the SET menu. Range is 105% to 110% in 1% increments (see page 18). Once exceeded, the P timer begins timing to signal the Generator to start.
Source 1 Over Voltage "Restore" Factor
y Default: 105% This adjustment determines the minimum acceptable over Voltage threshold at which the Transfer Switch is allowed to automatically transfer to Source 1. Adjust via SET menu. Range is 103% to 108% in 1% increments. "Restore" must be a minimum of 2% below "Fail" setting (see page 18).
R15/R15D
Load Shed Should Source 2 become overloaded, a signal can be given to switch to the dead or Mid position.
R16
Phase Rotation Sensing Can be turned on or off via CFG menu (see page 17). Factory Default is on. This feature prevents Line Source to Line Source trans­fers from occurring between dissimilar phase sequences. This condition is primarily caused by an installation error
. Connections from Source 1 and Source 2 need be verified, compared, and corrected to remedy the inconsistent phase rotation between the sources. WARNING: Turning off this feature can cause severe damage to loads.
R26
Interruptable Power Rate Provisions. Allow transfer out of Source 1 position to Source 2 or dead Source 2. Alarm and Pre-Signal circuit included.
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
11
Page 14
- - - -
Accessory Definitions
(cont’d)
R50
In Phase Monitor this feature restricts Live to Live Source Transfers to occur unless both Sources are within
7 electrical degrees or less of each other. (live Source to live Source transfers usually occur during transfer back to Source 1 or during Testing). R50 does not change the operation of the Automatic Transfer Switch in a power failure mode. After all timer functions have elapsed, the CHECKING FOR SOURCE SYNCHRO
-
NISM will be displayed as well as the direction of
transfer (S1-S2 for example denotes transfer from Source 1 to Source2). When synchronism is accomplished, transfer will take place.
Notes: - If S2 Frequency is less than S1 Fr
equency,
display will show a series of (- - - - -…..) symbols.
- If S2 Frequency is greater than S1 Frequency, display will show a series of (+++++…..) symbols.
- Each (-) or (+) symbol represents 10 electrical degr
ees out of phase. A maximum of 18 symbols
(180 electrical degrees) can be monitored.
- The number of (-) or (+) symbols decrease as the two sour
ces approach synchronism and increase as the two sources drift out of synchronism.
- If S1 and S2 Frequencies are identical, the display will show a series of alter
nating symbols (++++…) which also indicate the approximate out of phase degrees
In the event that the Sources do not come within 7 electrical degrees of each other within 60 seconds, the unit will display the message: SYNCH CHECKING and will allow the user to BYP
ASS. If the BYPASS button is pressed, the unit will display the message: WARNING MAY CAUSE DAMAGE TO THE LOAD. Pressing XFR will actually bypass the R50. Since R50 is a passive device, the length of time it takes to reach Synchronism is de
­pendent on the frequency difference between the two Sources. Source 1 is usually a Utility and the frequency is not within the control of the consumer
. Source 2 needs to be adjusted to create an adequate difference in order for the transfer to happen a timely fashion.
Note: For optimum performance, Source 2
Generator should be adjusted a Maximum of 2 Her
tz above or below the Utility frequency, minimum of 0.1 Hertz. (58 to 59.9) or (60.1 to 62) Hertz. Adjustment of Generator to 60Her
tz could cause lengthy transfer delay
.
R50 Feature can be turned ON or OFF via CFG Menu (see page 17). Factory Default if OFF.
S5P
Auto / Semi Manual selector In "Auto" position, retransfer to Source 1 is automatic after the T timer has timed out. The T time delay is bypassed if Source 2 fails. In "Manual", retransfer to Source 1 is upon depression of BYPASS DELAY button YEN or if Source 2 fails.
S12P
Auto / Manual Selector In "Auto" position, the Automatic Transfer Switch functions automatically as specified with the Switch drawings. In "Manual" the Automatic Transfer Switch will transfer to either direction upon depression of Source 1 or Source 2 transfer buttons. Should Source 1 fail, the Generator (Source 2), will automatically start. Once transferred in Manual, the Switch maintains position selected even if selected power fails.
S13P
Transfer Commit. Configured via CFG menu. (see page 17) When this Feature is set to OFF: The transfer Switch is not committed to transfer unless the outage duration is longer than the timers that precede the transfer to Source 2 position. This assumes that the outage will be an isolated event. When this Feature is set to ON: The transfer Switch is committed to transfer to Source 2 position once the W timer has begun timing, even if Source 1 power returns before the transfer to Source 2. This is to ensure that the transfer takes place, because one outage may be followed by another.
S14
Test / Auto / Source 1 Selector, Door mount
SW1
Auto/Off/Start Engine control selector, Door mount (Keyed or non-keyed operation available)
SW2
Auto / Off Engine control selector, Door mount (Keyed or non-keyed operation available)
SW3
Source Priority Selector Switch, Door mount Allows selection of Source 1 or Source 2 to be the Prime Source. Transfer Switch will transfer to selected Prime Source if that Source is available. (Keyed or non-keyed operation available)
T
Time Delay (S1) Source 1 Stable Timer. To delay trans­fer to Source 1 (immediate retransfer on Source 2 fail­ure). Adjustable 0-60 minutes in 1 second increments. Standard setting is 30 minutes. Adjust via SET menu (see page 18)
T3/W3
Elevator Pre-Signal Auxiliary Contacts: Open 0-60 seconds prior to transfer to either direction, re-closes after transfer.
U
(S2) Source 2 Stop Delay Timer. Allows Engine to run unloaded after switch retransfer to Source 1. Adjustable 0-60 minutes in 1 second increments. Standard setting is 5 minutes. Adjust via SET menu (see page 18)
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls 12
Page 15
VI
Accessory Definitions
(cont’d)
UMD
Universal Motor Load Disconnect Circuit: Auxiliary Contact opens 0-60 seconds prior to transfer in either direction, re-closes after transfer. Can be configured by end user for Pre-transfer, Post-transfer, or both.
Voltage Imbalance (Three Phase) For a three phase source, this feature monitors phase voltage ratios based on a selected range within a selected time window
. Should any phase fall below the selected lower window limit or exceed the selected higher window limit within the selected time frame, the controller initiates transfer to the other source.
Range: 5% to 20% of Nominal voltage, 10 to 30 seconds window
, user adjustable. Resolution: 1% Increments Minimum Differential: 2% between “Fail” and “Restore” settings. Factory default: 10% “Fail”, 8% “Restore”, 30 Seconds. See CFG Menu page 17 to configure ON or OFF. See SET Menu page 18 to set Percentage and time windows
W
Time Delay (S2) Source 2 Stable Timer. To delay trans­fer to Source 2. Adjustable 0-5 minutes in 1 second increments. Standard setting is 1 second. Adjust via SET menu (see page 18)
YEN
Bypass Timers Key utilizing Keypad. When applicable, the system prompts the user to press a button to bypass (T) or (W) Timers should the user so desires.
ZNET
Network Communications Interface Card
How to Set the System Clock
How to Set the System Clock
Set System Clock, time and date
· If the clock is not set, the display will show
SET SYSTEM CLOCK on the second line of the S1 OK screen.
· The S1 OK screen will show time (hours and
minutes) on the second line if the system clock has been set. (Date on third line)
Setting the System Clock
(Start from S1 OK screen)
1. Remove battery protective white plastic strip
near P relay. *
2. Press MORE then press SET.
3. Press MORE and scroll to SET SYSTEM CLOCK
using the MORE key.
4. Press SEL.
5. ENTER ACCESS CODE located on the white label
on the back of the controller.
6. Press SEL.
7. Use the up and down keys to change the hour value.
8. Press SAVE (this will enter this value and move
cursor to minutes).
9. Use the up and down keys to change the minutes.
10. Press SAVE (this will enter this value and move
cursor to month).
11. Use the up and down key up to change the month.
12. Press SA
VE (This will enter this value and complete
the clock setting).
13. Use the up and down keys to change the date.
14. Press SAVE (this will enter this value and move
cursor to year).
15. Use the up and down keys to change year.
16. Press SAVE (this will enter this value and
compete the clock setting).
17. To edit settings, press SEL and repeat steps 6-16.
18. If the setting is satisfactory, press MORE (unit then returns to the SET menu then press BACK, then ESC.)
* Replacement battery part #K-4100
Battery will last 5 years and provides power to retain clock function only (Controller functions without battery).
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
13
Page 16
CDT One Event Timer Exerciser
Load or No-Load
One event Exerciser with adjustable Timer. Exercise duration can be set between 5 and 60 minutes in 1 minute increments. Can be configured to run every 1,7,14, or 28 days. Factory default is 20 minutes.
How to CONFIGURE (CFG) and Set (SET) the Timer Exerciser
1. Beginning from the S1 OK screen, press MORE then CFG.
2. Press MORE to scroll to
CONFIG TIMER
EXERCISER screen.
3. The third line of the CONFG TIMER EXERCISER will show either DAIL
Y, WEEKLY, 14 DAY, 28 DAY,
or OFF.
4. If the third line of the CONFG TIMER EXERCISER shows DAIL
Y, WEEKLY, 14 DAY, or 28 DAY as
desired, then proceed to step 10.
5. If the third line of the CONFG TIMER EXERCISER shows OFF or if another timer selection is desired, continue.
6. Press SEL
.
7. Enter ACCESS code located on white label on the back of the controller
.
8. Press UP or DOWN to select DAIL
Y, WEEKLY,
14 DAY, or 28 DAY as desired.
9. Press SA
VE.
10. Press MORE to scroll to
CONFG TIMER
EXERCISER (XFR) or (NO XFR).
11. Press Up or Down to select XFR (Load T
ransfer)
or NO XFR (No Load Transfer).
12. Press SA
VE.
13. Press MORE repeatedly to
BACK then S1 OK screen.
Set (SET) the Exerciser:
14. Beginning from the S1 OK screen, press MORE then SET.
15. Press MORE repeatedly until EXER S2 RUN TIME screen.
16. Press SEL
17. Enter ACCESS code located on white label on the back of the controller
.
18. Press SEL
19. Cursor is indicated as a line under character to be changed. Change values with up and down keys.
20. Press SA
VE when complete.
21. Press MORE repeatedly until
SET USER SETUP
then press BACK then ESC to the S1 OK screen.
How to Initiate CDT Exerciser and to start an exercise cycle every 1, 7, 14, or 28 days
From S1 screen
1) Press TEST
2) Press MORE
3) Press ST
ART TEST TIMER (to initiate Test).
• If the CDT Exerciser is Factory configured for a Load Exerciser
, the Controller will immediately start a load exercise. The controller will start the generator, transfer the load to Source 2 and remain in Source 2 for the duration set for EXER S2 RUN TIME in the SET menu. The controller will retransfer the load back to Source 1 after the S1 stable timer has timed out and run the generator unloaded for the duration of the S2 stop delay timer (Engine Cool Down Timer).
• If the CDT Exerciser is Factory configured for a No-Load Exerciser, the Controller will immediately start a No-load exercise. The controller will start the generator and run it unloaded for the duration of the S2 stop delay timer (Engine Cool Down Timer).
Exercise will be repeated at the same time as initiated on ever
y 1, 7, 14, or 28 days according to the selection
made in the Configure CFG menu.
How to Bypass (Cancel) an exercise during an exercise cycle
1) Press BPASS
2) Allow the controller to complete the Engine cool down cycle
If the CDT Exerciser is Factor
y configured for a No-Load Exerciser Or allow the controller to complete retransfer to Source 1 If the CDT Exerciser is Factory configured for a Load Exerciser
How to Bypass the next exercise event and Keep the rest of scheduled events unchanged
1) Press Test
2) Press MORE
3) Press BYP
ASS EXER
To re-institute the next exercise event back, press CANCL BPASS
How to initiate a new exercise start time
1) Press TEST
2) Press MORE
3) Press EXER CANCL
4) Press ST
ART TIMER TEST
How to check the next exercise event
1) From S1 OK screen, press MORE three times.
2) The unit will display the PLANT EXERCISER NEXT
event in DA
YS, HOURS, and MINUTES
3) Press ESC to S1 OK
Screen.
Notes:
- *E* appears in the upper right hand corner
of LCD screen when exercise is impending.
- For Load Exerciser, actual exercise period
(ATS in S2 position)= CDT (Exerciser) timing period +T (S1 stable Timer) timing period.
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls 14
Page 17
CDP Clock Exerciser
Load / No-Load Clock Exerciser
Allows the Generator to start and run unloaded or to simulate a power failure, start Generator and run under load. Can be configured by the end user for 1, 7, 14, 28, or 365 day cycles.
• A total of 7 independent No Load exercise periods (up to 10 hours each) can be programmed for each of the daily, weekly, 14-day, and 28-day exercisers.
• A total of 12 independent No Load exercise periods (up to 10 hours) can be programmed for the 365-day Exerciser
.
How to Configure (CFG) the Exerciser
1. Beginning from the S1 OK screen, press MORE then CFG.
2. Press MORE to scroll to
CONFIG CLOCK
EXERCISER screen.
3. The third line of the CONFG CLOCK EXERCISER will show either DAIL
Y, WEEKLY, 14 DAY, 28 DAY,
365 DAY or OFF.
4. If the third line of the CONFG CLOCK EXERCISER shows DAIL
Y, WEEKLY, 14 DAY, 28 DAY, or 365 DAY as desired, press MORE repeatedly to BACK. Press ESC then proceed to the SET menu to set the EXERCISER.
5. If the third line of the CONFG CLOCK EXERCISER shows OFF, continue.
6. Press SEL
.
7. Enter ACCESS code located on white label on the back of the controller
.
8. Press UP or DOWN to select DAIL
Y, WEEKLY,
14 DAY, 28 DAY, or 365 DAY as desired.
9. Press SA
VE.
10. Press MORE repeatedly to
BACK then ESC
to S1 OK screen.
How to set (SET) the DAILY Exerciser
1. Beginning from the S1 OK screen, press MORE
then SET.
2. Press MORE repeatedly until
SET EXERCISER
screen.
3. Press SEL
.
4. Enter ACCESS code located on white label on the back of the controller
.
5. Press SEL
6. Cursor is indicated as a line under character to be changed. Change values with up and down keys. Press SA
VE after each entry to save value and to
move to the next value to be changed.
7. Press BACK when complete.
8. Press MORE repeatedly until SET USER SETUP. Press BACK then ESC to the S1 OK screen.
How to Bypass (Cancel) an exercise during an exercise cycle
1) Press BPASS
2) Allow the controller to complete the Engine cool down cycle.
If the CD Exerciser is configured or Set for a No-Load Exercise. Or allow the controller to complete retransfer to Source 1. If the CD Exerciser is configured for a Load Exerciser
How to Bypass the next exercise event and Keep the rest of scheduled events unchanged
1) Press TEST
2) Press MORE
3) Press BYP
ASS EXER
To re-institute the next exercise event back, press CANCL BPASS
How to check the next exercise event
1) From S1 OK screen, press MORE three times.
2) The unit will display the PLANT EXERCISER NEXT event in
DAYS, HOURS, and MINUTES
3) Press ESC to S1 OK
Screen.
Notes:
• In the S1 OK screen, an (*E*) appears in the upper right hand corner of LCD screen when exercise is impending.
• For Load Exerciser, actual exercise period (A
TS in S2 position)= CDT (Exerciser)
timing period +T (S1 Stable Timer) timing period.
• A value greater than zero must be entered in the Exerciser duration field to be accepted as a valid exercise period.
• The Exercise cycle will be repeated on a regular basis as programmed and initiated in the SET menu depending on what Exerciser was configured (selected) in the
CFG menu.
Figure 9
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
15
Indicates # of Exercise Periods
Indicates type of Exerciser DAILY, WEEKLY, 14-DAY, 28-DAY or 365-DAY
Indicates Exerciser start: Time for DAILY Exerciser Time & Day for WEEKLY Exerciser Time, Date & Month for 14-DAY, 28-DAY and 365-DAY Exerciser (24 Hour System)
Cursor
EXERCISER 00:00
BACK
To previous field or to exit screen.
SET
^
Up and Down Use to change values.
v
NL #1
SAVE
To save value and to move cursor to next field to be changed.
Load No-Load (CDP) Exercise Indicator
Exercise duration for this event in hours and minutes up to 10 hours per event
Page 18
Entelli-Switch 250 User Setup - CFG Menu
Turn options ON or OFF via keypad through the CFG menu
Enter six digit access code (The factory assigned six-digit access code is located on the back of the controller)
Network Communications (Option)
11
12
13
R1
Output
5
6
7
R1
Output
14
15
16
R2
Output
8
9
10
R2
Output
Contact Rating: 10A @ 277VAC or 30VDC
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
PROG 1 PROG 2 GRD (Input Sink) LS OUT NIA OUT ELEV. PRE. OUT ALARM OUT STE OUT
MOTOR DISC. OUT
TMS IN INHIB. > S1 INHIB. > S2 LS IN
1
2
3
4
5
6
7
8
9 10 11 12 13 14
+12V (Output Source) LN OUT L4 OUT L3 OUT L2 OUT L1 OUT YN IN YE IN TSNL IN Q2/TSL IN S12 IN S5 IN
11 12 13
5 6 7
14 15 16
8 9
10
R1
1 2
R2
3 4
Output Contacts
Output Contacts
{ {
From J2/J4 Output
J4-3
414
13
12 11 10
9
123
567
8
J2-3 N.O. N.C.
To J2/J4 Input
Customer
Input
Voltage
{
WARNING
1 Controller inputs must be relay isolated.
2 Controller ouputs have limited source capability.
Use only GE Zenith - specified output modules.
Entelli-Switch 250
TM
Lithium Battery Exerciser Battery
Replacement - K-4100 (BR2032) Service Life - 10 Years
+
+
During normal operation
User Access Code Default - 121212
Product Information www.geindustrial.com
24-Hour Service (773) 299-6600
J4
*
J2
*
* Input and output availability
subject to factory configuration.
Figure 10
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
16
S1 OK
01: 50
FRI 31 MAY 2003
MORE TEST
1 VAB = ___ 2 VAB = ___
VBC = ___ VBC = ___ VCA = ___ VCA = ___
MORE CFG SET ESC
CONFIG

USER SETUP

MORE BACK
—TIMER EXERCISER (CDT) 1, 7, 14, 28 Day (pg. 10 & 14)
—CLOCK EXERCISER LOAD OR NO LOAD (CDP) 1, 7, 14, 28, 365 Day (pg. 10 & 15)
—TEST KEY (6) Maintained/Momentary (pg. 10)
—TRANSFER COMMIT (S13) ON/OFF (pg. 12)
—AUTO / MANUAL (S5 or S12) ON/OFF (pg. 12)
—IN-PHASE MONITOR (R50) ON/OFF (pg. 12)
—S1 OVER VOLTAGE (R1-1 or R1-3) ON/OFF (pg. 11)
—S1 UNDER FREQUENCY ON/OFF (pg. 8)
—S2 OVER VOLTAGE ON/OFF (pg. 8)
—S2 OVER FREQUENCY ON/OFF (pg. 8)
—PHASE IMBALANCE (VI) ON/OFF (pg. 13)
—PHASE ROTATION MATCH (R16) ON/OFF (pg.11)
—LOAD DISCONNECT TD (UMD) (pg.13)
—TRANSFER ALARM (CTAP) ON/OFF (pg.10)
—NETWORK (ZNET) ON/OFF (pg. 13)
Optional Accessories
Page 19
Entelli-Switch 250 User Setup - SET Menu
Change adjustable values through the SET menu.
Enter six digit access code (The factory assigned six-digit access code is located on the back of the controller)
Figure 10
Network Communications (Option)
11
12
13
R1
Output
5
6
7
R1
Output
14
15
16
R2
Output
8
9
10
R2
Output
Contact Rating: 10A @ 277VAC or 30VDC
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
PROG 1 PROG 2 GRD (Input Sink) LS OUT NIA OUT ELEV. PRE. OUT ALARM OUT STE OUT
MOTOR DISC. OUT
TMS IN INHIB. > S1 INHIB. > S2 LS IN
1
2
3
4
5
6
7
8
9 10 11 12 13 14
+12V (Output Source) LN OUT L4 OUT L3 OUT L2 OUT L1 OUT YN IN YE IN TSNL IN Q2/TSL IN S12 IN S5 IN
11 12 13
5 6 7
14 15 16
8 9 10
1 2
3 4
Output Contacts
Output Contacts
{ {
From J2/J4 Output
J4-3
414
13
12 11 10
9
123
567
8
J2-3 N.O. N.C.
To J2/J4 Input
Customer
Input
Voltage
{
WARNING
1 Controller inputs must be relay isolated.
2 Controller ouputs have limited source capability.
Use only GE Zenith - specified output modules.
Entelli-Switch 250
TM
Lithium Battery Exerciser Battery
Replacement - K-4100 (BR2032) Service Life - 10 Years
+
+
During normal operation
User Access Code Default - 121212
Product Information www.geindustrial.com
24-Hour Service (773) 299-6600
J4
*
J2
*
* Input and output availability
subject to factory configuration.
R1
R2
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
17
S1 OK
01: 50
FRI 31 MAY 2003
MORE TEST
1 VAB = ___ 2 VAB = ___
VBC = ___ VBC = ___ VCA = ___ VCA = ___
MORE CFG SET ESC
SET
USER SETUP
MORE BACK
—SET SYSTEM CLOCK (pg.13)
—DAYLIGHT SAVINGS ON/OFF
—CLOCK EXERCISER (CDP) (pg.10 & 15)
—EXER S2 RUNTIME (CDT) (pg.10 & 14)
—S1 UNDER VOLTAGE (pg.8) Fail Restore
—S1 UNDER FREQUENCY (pg.8) Fail Restore
—S1 OVER VOLTAGE (pg.11) Fail Restore
—S1 OVER FREQUENCY (pg.8) Fail Restore
—S2 UNDER VOLTAGE (pg.8) Fail Restore
—S2 UNDER FREQUENCY (pg.8) Fail Restore
—S2 OVER VOLTAGE (pg.8) Fail Restore
—S2 OVER FREQUENCY (pg.8) Fail Restore
—SET % PHASE IMBALANCE (VI) FAIL 5%, RESTORE 3% (pg.13)
—SET PHASE IMBALANCE (VI) TIME DELAY 30 seconds (pg.13)
—TIME DELAY S2 START (P1) (pg.11)
—TIME DELAY S2 STABLE (W) (pg.13)
—LOAD PRESIGNAL TD (T3/W3) (pg.12)
—LOAD DISCONNECT TD (UMD) (pg.13)
—ATS OPEN TIME TO S2 (DW) DELAY units only (pg.10)
—TIME DELAY S1 STABLE (T) (pg.12)
—ATS OPEN TIME TO S1 (DT) DELAY units only (pg.10)
—S2 STOP DELAY (U) (pg.12)
—CALIBRATE S1 (pg.10)
—CALIBRATE S2 (pg.10)
Optional Accessories
Page 20
Entelli-Switch 250 User Setup - System Info
Figure 10
Network Communications (Option)
11
12
13
R1
Output
5
6
7
R1
Output
14
15
16
R2
Output
8
9
10
R2
Output
Contact Rating: 10A @ 277VAC or 30VDC
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
PROG 1 PROG 2 GRD (Input Sink) LS OUT NIA OUT ELEV. PRE. OUT ALARM OUT STE OUT
MOTOR DISC. OUT
TMS IN INHIB. > S1 INHIB. > S2 LS IN
1
2
3
4
5
6
7
8
9 10 11 12 13 14
+12V (Output Source) LN OUT L4 OUT L3 OUT L2 OUT L1 OUT YN IN YE IN TSNL IN Q2/TSL IN S12 IN S5 IN
11 12 13
5 6 7
14 15 16
8 9
10
R1
1 2
R2
3 4
Output Contacts
Output Contacts
{ {
From J2/J4 Output
J4-3
414
13
12 11 10
9
123
567
8
J2-3 N.O. N.C.
To J2/J4 Input
Customer
Input
Voltage
{
WARNING
1 Controller inputs must be relay isolated.
2 Controller ouputs have limited source capability.
Use only GE Zenith - specified output modules.
Entelli-Switch 250
TM
Lithium Battery Exerciser Battery
Replacement - K-4100 (BR2032) Service Life - 10 Years
+
+
During normal operation
User Access Code Default - 121212
Product Information www.geindustrial.com
24-Hour Service (773) 299-6600
J4
*
J2
*
* Input and output availability
subject to factory configuration.
View System Data
Enter six digit access code (The factory assigned six-digit access code is located on the back of the controller)
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
18
S1 OK
01: 50
FRI 31 MAY 2003
MORE TEST
—PHASE TO PHASE VOLTAGE, S1 & S2
—FREQUENCY INDICATION FOR S1 & S2 (K/P) (pg.10)
—PLANT EXERCISER: Next Impending Exerciser (shows only if set)
—SYSTEM INFO:
Serial #: Unit Serial # Rev #: Software Revision #
Event Log:
Sequentially Numbered Log of 16 events that track date, time, reason and action taken
Data: Total Life Transfers (N2P)
Days Powered Up Total Transfers to S2 Total S1 Failures Time S1 available in Hrs Time S2 available in Hrs. (N1P)
—CHANGE USER ACCESS CODE
Page 21

Testing

NOTICE
A periodic test of the transfer switch under load conditions is recommended to insure proper operation.
(See National Electric Code articles 700 and 701)
ATS Testing
Start generator and verify proper voltage, frequency and phase sequence (match to Source 1). Shut down gen set and place in Auto. Complete the visual inspection of the transfer switch, and close the cabinet door.
Initiate the test by pressing the TEST button on the LCD keypad. The controller will then prompt for your access code. After entering the code, three test options will appear— XFR LOAD, FAST TEST and NO XFR (See Figure 11).
• XFR LOAD test starts the generator and using
the current timer settings, transfers the load to Source 2.
• FAST TEST test presets timer values to a maximum
30 seconds during the test. After completion of the test, all timers are reset to their original values. (T3, W3, DT and DW remain)
• NO XFR test starts the generator but does not
transfer the load to the Source 2.
Press and hold the desired test option button until the switch transfers to Source 2 (load test) or until the generator has been run for the desired amount of time (no load test). Releasing the test button before W timer timeout will abort the test (Exception: when the transfer commit option, is configured “ON”).
To test lamps, press TEST then scroll through MORE, then press LAMP TEST. To cancel LAMP TEST press MORE.
Standard Transition
When the test is initiated, the controller initiates the Time Delay Source 2 Start Timer (Engine Start Timer "P") cycle. A manual CANCEL button is provided to cancel the test if desired. Upon completion of the (P) time delay, an Engine start Signal is sent to Source 2. When Source 2 voltage and frequency reach the preset "Restore" Values, the time delay to Source 2 Timer (W) begins its timing cycle to ensure voltage and frequency stabilization before transfer. A manual pushbutton BYPASS is provided to bypass the "W" time delay if desired. After the (W) time delay, the CCE relay energizes the CE solenoid to close the transfer switch in to Source
2. The SE limit switch activates to de-energize the CCE relay.
Restoration of Source 1 Power:
Deactivating the test switch initiates re-transfer to Source 1 sequence.The delay to Source 1 Timer (T) begins its timing cycle to ensure voltage and frequency stabilization before retransfer. A manual pushbutton BYPASS is provided to bypass the "T" time delay if desired. After the (T) time delay, the CCN relay energizes the CN solenoid to retransfer the switch to Source 1. The SN limit switch activates to de-energize the CCN relay.
Immediately after re-transfer, the S2 Stop Delay Timer (Delay to Engine Stop "U") begins its cycle to allow Source 2 Engine
SYSTEM TEST
FAST XFR NO
MORE TEST LOAD XFR
Figure 11
to run unloaded. A manual pushbutton BYPASS is provided to bypass the "U" time delay if desired. Upon completion of the (U) timing cycle, the controller sends an Engine stop signal.
Delayed Transition
Source 1 Power Failure:
When the test is initiated, the controller initiates the Time Delay Source 2 Start (Engine Start Timer "P") cycle. A manual CANCEL button is provided to cancel the test if desired Upon completion of the (P) time delay, an Engine start Signal is sent to Source 2. When Source 2 voltage and frequency reach the preset "Restore" values, the time delay to open Source 1 timer (W) begins its timing cycle to ensure voltage and frequency sta­bilization before re-transfer. A manual pushbutton BYPASS is provided to bypass the "W" time delay if desired. After the (W) time delay, the CCNO relay energizes the CNO solenoid to open the transfer switch out of Source 1 position. The time delay to Source 2 timer (DW) begins its timing cycle. After the (DW) time delay, the CCE relay energizes. The switch then completes transfer to Source 2 by energizing the CE solenoid. The SE limit switch activates to de-energize the CCE relay.
Restoration of Source 1 Power:
Deactivating the test switch initiates re-transfer to Source 1sequence.The delay to open Source 2 Timer (T) begins its tim­ing cycle to ensure voltage and frequency stabilization before retransfer. A manual pushbutton BYPASS is provided to bypass the "T" time delay if desired. After the (T) time delay, the CCEO relay energizes the CEO solenoid to open the switch out of Source 2 position. The time delay to Source 1 timer (DT) begins its timing cycle. After the (DT) time delay, the CCN relay energizes the CN solenoid to complete re-transfer of the switch to Source 1. The SN limit switch activates to de-energize the CCN relay.
Immediately after re-transfer, the S2 Stop Delay Timer (Delay to Engine Stop "U") begins its cycle to allow Source 2 Engine to run unloaded. A manual pushbutton BYPASS is provided to bypass the "U" time delay if desired. Upon completion of the (U) timing cycle, the controller sends an Engine stop signal.
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
19
Entelli-Switch 250
Page 22

Sequence of Operation

Standard Transition
Source 1 Power Failure:
When Source 1 voltage or frequency has fallen below the preset "Fail" values, the controller initiates the Time Delay Source 2 Start Timer (Engine Start Timer "P") cycle. Upon completion of the (P) time delay, an Engine start Signal is sent to Source 2. When Source 2 voltage and frequency reach the preset "Restore" Values, the time delay to Source 2 Timer (W) begins its timing cycle to ensure voltage and frequency stabilization before transfer. A manual pushbutton BYPASS is provid
­ed to bypass the "W" time delay if desired. After the (W) time delay
, the CCE relay energizes the CE solenoid to close the transfer switch in to Source 2. The SE limit switch activates to de-energize the CCE relay.
Restoration of Source 1 Power:
When Source 1 power reach the preset "Restore" values, the controller initiates re-transfer to Source 1sequence.The delay to Source 1 Timer (T) begins its timing cycle to ensure voltage and frequency stabiliza
­tion before retransfer. A manual pushbutton BYPASS is provided to bypass the "T" time delay if desired. After the (T) time delay
, the CCN relay energizes the CN solenoid to retransfer the switch to Source 1. The SN limit switch activates to de-energize the CCN relay.
Immediately after re-transfer, the S2 Stop Delay Timer (Delay to Engine Stop "U") begins its cycle to allow Source 2 Engine to run unloaded. A manual pushbut­ton BYPASS is provided to bypass the "U" time delay if desired. Upon completion of the (U) timing cycle, the controller sends an Engine stop signal.
Delayed Transition
Source 1 Power Failure:
When Source 1 voltage or frequency has fallen below the preset "Fail" values, the controller initiates the Time Delay Source 2 Start (Engine Start Timer "P") cycle. Upon completion of the (P) time delay, an Engine start Signal is sent to Source 2. When Source 2 voltage and frequency reach the preset "Restore" values, the time delay to open Source 1 timer (W) begins its timing cycle to ensure voltage and frequency stabiliza
­tion before re-transfer. A manual pushbutton BYPASS is provided to bypass the "W" time delay if desired. After the (W) time delay
, the CCNO relay energizes the CNO solenoid to open the transfer switch out of Source 1 position. The time delay to Source 2 timer (DW) begins its timing cycle. After the (DW) time delay, the CCE relay energizes. The switch then completes transfer to Source 2 by energizing the CE solenoid. The SE limit switch activates to de-energize the CCE relay.
Restoration of Source 1 Power:
When Source 1 power reach the preset "Restore" values, the controller initiates re-transfer to Source 1 sequence.The delay to open Source 2 Timer (T) begins its timing cycle to ensure voltage and frequency stabi
­lization before retransfer. A manual pushbutton BYPASS is provided to bypass the "T" time delay if desired. After the (T) time delay
, the CCEO relay energizes the CEO solenoid to open the switch out of Source 2 position. The time delay to Source 1 timer (DT) begins its timing cycle. After the (DT) time delay, the CCN relay ener
­gizes the CN solenoid to complete re-transfer of the switch to Source 1. The SN limit switch activates to de­energize the CCN relay.
Immediately after re-transfer, the S2 Stop Delay Timer (Delay to Engine Stop "U") begins its cycle to allow Source 2 Engine to run unloaded. A manual pushbut­ton BYPASS is provided to bypass the "U" time delay if desired. Upon completion of the (U) timing cycle, the controller sends an Engine stop signal.
Table 4
Timer Designations as they appear in the SET menu
ATS Type P W DW T DT U
Standard Time Delay Time Delay Time Delay S2 Stop Transition S2 Start S2 Stable S1 Stable Delay
Delayed Time Delay Time Delay ATS Open Time Delay ATS Open S2 Stop Transition S2 Start S2 Stable Time to S2 S1 Stable Time to S1 Delay
Source 1 Transfer to Source 2 T
ransfer to Source 1 Engine
Source 1
Fails Cooldown
Returns
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls 20
Page 23

Relay/Transformer (R/T Box)

Standard Transition
Each Entelli-Switch 250 microprocessor based ATS controller requires a relay/transformer box to apply line voltage to the ATS operator via coil control relays. Also required is power for the Entelli-Switch 250 printed circuit board and an application of sensing voltage proportional to line voltage. This is accomplished by the relay trans
­former box. This method of switching operator voltage and applying power and sensing voltage to the printed
1
2
(inside)
3
Figure 12
circuit board isolates the MX250 from the line voltage, further protecting the controller from harmful line tran
­sients. Two versions of the R/T box exist depending on the type of A
TS (standard transition or delayed transition).
The following layout drawings of the R/T Box compo­nents (standard and delayed transition) include a bill of materials for replacement parts. Schematics are included to indicate proper wiring.
SEC.
PRI.
SEC.
PRI.
SEC.
PRI.
1
2
3
Figure 13
40-225 Amp Molded Power Section
40-3000 Amp - All Other Standard Types
Transformer Usage (see Figure 12)
Transformer Usage (see Figure 13)
R/T Box Primary 1 VA 25 VA
Assembly Voltage XFMR XFMR
Part No. at 50/60 Hz Part No. Part No.
57P-1015 120V K-3216 K-3224 57P-1016 208-220V K-3217 K-3225 57P-1017 230-240V K-3218 K-3226 57P-1018 277V K-3219 K-3227 57P-1019 380-400V K-3220 K-3228 57P-1020 416-440V K-3221 K-3229 57P-1021 460-480V K-3222 K-3230 57P-1022 575-600V K-3223 K-3231
R/T Box Primary 1 VA 25 VA
Assembly Voltage XFMR XFMR
Part No. at 50/60 Hz Part No. Part No.
50P-1026 120V K-3216 K-3224 50P-1027 208-220V K-3217 K-3225 50P-1028 230-240V K-3218 K-3226 50P-1029 277V K-3219 K-3227 50P-1030 380-400V K-3220 K-3228 50P-1031 416-440V K-3221 K-3229 50P-1032 460-480V K-3222 K-3230 50P-1033 575-600V K-3223 K-3231
Bill of Material
Bill of Material
Item Part No. Description Qty
1 See Chart Transformer (1 VA) 2
2 See Chart Transformer (25 VA) 2
3 K-1274 Relay Flange Mounted 2
Item Part No. Description Qty
1 See Chart Transformer (25 VA) 2
2 See Chart Transformer (1 VA) 2
3 K-1260 Coil Control Relay (24V) 2
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
21
Page 24
Relay/Transformer (R/T Box)
(cont’d)
Delayed Transition
SEC.
PRI.
1
2
3
Figure 14
Transformer Usage
Bill of Material
R/T Box Primary 1 VA 25 VA
Assembly Voltage XFMR XFMR
Part No. at 50/60 Hz Part No. Part No.
50P-1034 120V K-3216 K-3224 50P-1035 208-220V K-3217 K-3225 50P-1036 230-240V K-3218 K-3226 50P-1037 277V K-3219 K-3227 50P-1038 380-400V K-3220 K-3228 50P-1039 416-440V K-3221 K-3229 50P-1040 460-480V K-3222 K-3230 50P-1041 575-600V K-3223 K-3231
Item Part No. Description Qty
1 See Chart Transformer (25 VA) 2
2 See Chart Transformer (1 VA) 2
3 K-1260 Coil Control Relay (24V) 4
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
22
PRI.
SEC.
Page 25
Relay/Transformer (R/T Box)
(cont’d)
Standard Transition R/T Box Schematic
Figure 15
Delayed Transition R/T Box Schematic
Figure 16
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
23
20
CCN
24V
21 22
XN1
10V
11 V
XN2
10V
CCE
24V
XE1
10V
30 31 32
XE2
10V
11 V
XN1 - SOURCE 1 CONTROL TRANSFORMER XN2 - SOURCE 1 3 PHASE SENSING TRANSFORMER XE1 - SOURCE 2 CONTROL TRANSFORMER XE2 - SOURCE 2 3 PHASE SENSING TRANSFORMER
SOURCE 2 24V OUTPUT
900
(18)
SOURCE 1 24V OUTPUT
800 907
3 PHASE SOURCE 2 SENSING (BLANK) (BLANK) GROUND
GND
CCE - COIL CONTROL RELAY (SOURCE 2)
901
CCN - COIL CONTROL RELAY (SOURCE 1)
801
COMMON
902 903 904 803 804 807
806 805 906 905
SINGLE PHASE SOURCE 2 SENSING
3-PHASE SOURCE 1 SENSING
SOURCE 1 CONTROL POWER
SOURCE 2 CONTROL POWER
(1)
J5
CCEO
CCN
24V
XN1
10V
20
11 V
21
XN2
10V
22
CCNO
CCE
24V
XE1
10V
32
31
30
XN1 - SOURCE1 CONTROL TRANSFORMER XN2 - SOURCE1 3 PHASE SENSING TRANSFORMER XE1 - SOURCE 2 CONTROL TRANSFORMER XE2 - SOURCE 2 3 PHASE SENSING TRANSFORMER
900
SOURCE 2 24V OUTPUT
(18)
800
SOURCE 1 24V OUTPUT
907
3 PHASE SOURCE 2 SENSING
808
CCEO - COIL CONTROL RELAY (OPEN SOURCE 2)
908
CCNO - COIL CONTROL RELAY (OPEN SOURCE 1) GROUND
901
CCE - COIL CONTROL RELAY (SOURCE 2)
801
CCN - COIL CONTROL RELAY (SOURCE 1)
902
COMMON
903 904 803 804 807 806 805 906 905
SINGLE PHASE SOURCE 2 SENSING
3-PHASE SOURCE 1 SENSING
SOURCE 1 CONTROL POWER
SOURCE 2 CONTROL POWER
(1)
J5
11 V
XE2
10V
GND
Page 26

Troubleshooting and Diagnostics

DANGER
HAZARDOUS VOLTAGES CAN CAUSE SEVERE INJURY OR DEATH.
These charts may indicate problems that require authorized GE Zenith service personnel.
Hazardous voltages may exist on termination plugs other than those that go into the Entelli-Switch 250.
General Troubleshooting
The following troubleshooting guide is used to recognize, and determine basic faults. When using this guide, it will ask several questions about the condition of the switch. This guide will then list an order of the possible faults. You will then look at the first suspected fault to determine if it is the problem. If it is not a fault, you go to the
second suspected fault. If you go through all of the suspected faults, or the chart instructs you to, call a GE Zenith Representative for further assistance.
NOTE
: When you use the troubleshooting charts, the Annunciation column refers to the LED’s on the control panel.
Symptom Annunciation Possible Cause(s) Corrective Action
Engine does not START SOURCE 2
AVAILABLE LED off
Engine start wires not terminated properly
Check engine start connections
Generator is in OFF position
Investigate why Engine Control S
witch was turned off
Engine does not stop
LCD Display ­“TD Engine Cool Down
U timing cycle not complete Check U timer setting
SOURCE 1 POSITION, and SOURCE 1 and SOURCE 2 A
VAILABLE LEDs on,
but U timer has timed out
Engine start wires not terminated cor
rectly
Check Engine Start Connections
Generator in MANUAL Place generator in AUTO
ATS will not transfer to SOURCE 2
SOURCE 2 AVAILABLE LED of
f
SOURCE 2 voltage or frequency not within acceptable parameter
s
Check: Engine Start Connections, Generator
Breaker, Generator Output,
and Engine Control Switch
ZTG Series
None Power supply connector unplugged Plug in connector
LCD Display ­“S1 _ _ _ _ TD XFR S1>S2 T
ime Remaining _ _ _ _”
W timing cycle not complete Check WTimer setting
ATS will not transfer to SOURCE 1
LCD Display ­“ATS Open T
ime Remaining _ _ _ _”
DW timing cycle not complete Check DWT
imer setting
ZTGD Series
SOURCE 1 AVAILABLE LED of
f
SOURCE 1 voltage or frequency not within acceptable parameter
s
Check utility and utility breakers
None Power supply connector unplugged Plug in connector
LCD Display ­“Diagnostic Code 001”
Limit switch or RT box connector unplugged
Call Technical Services
LCD Display ­“S1 OK
T
ime Remaining _ _ _ _
Bypass”
T timing cycle not complete Check T T
imer setting
LCD Display ­“ATS Open T
ime Remaining _ _ _ _”
TD timing cycle not complete Check DT Timer setting
Table 5
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
24
Page 27

Maintenance and Testing

CAUTION
Due to hazardous voltage and current, GE Zenith rec-
ommends that a
GE Zenith Certified technician or a
qualified electrician must perform the
installation and maintenance of the switch.
WARNING
Both power sources must be disconnected
before manual operation of the switch.
A preventive maintenance program will insure high reliability and long life for the transfer switch. The preventive maintenance program for the transfer switch should include the following items:
Inspection and Cleaning
The switch should be inspected for any accumulation of dust, dirt, or moisture, and should be cleaned by vacuuming or wiping with a dry cloth or soft brush. do not use a blower since debris may become lodged in the electrical and mechanical components and cause damage.
Remove the transfer switch barriers and check the condition of the contacts. Any surface deposits must be removed with a clean cloth (do not use emery cloth or a file). If the contacts are pitted or worn excessively, they should be replaced. A general inspection of mechanical integrity should be made to include loose, broken or badly worn parts.
Servicing
All worn or inoperative parts must be replaced using GE Zenith recommended replacement parts. Please refer to the Replacement Parts manual for specific part information and ordering procedures. Please contact the GE Zenith Technical Services Department for the Replacement Parts manual.
The operating mechanism of the transfer switch is lubricated with Lubriplate 105. The lubricant applied at the factory provides adequate lubrication for the lifetime of the switch. Should debris contaminate the mechanism, clean and apply additional Lubriplate.
GE Zenith can provide complete preventative main­tenance services. Please contact the GE Zenith Technical Services Department for additional information.
CDT battery replacement - lithium batteries may last up to 10 years, however it is recommended that batter
y replacement be included in a 3-5 year service cycle. The battery maintains the exerceser memory only and does not otherwise affect the operation.
Testing
A manual operator handle is provided with the transfer switch for maintenance purposes only. Manual operation of the switch must be checked before it is operated electrically. Both power sources
must be disconnected before manual operation of the switch.
Insert the handle and operate the transfer switch between the Source 1 and Source 2 positions. The transfer switch should operate smoothly without binding. Return the switch to Source 1 position, remove the handle, and return it to the holder provided.
After completing the inspection, cleaning and servicing of the transfer switch, reinstall the switch cover, and close and lock the cabinet door. Reclose the circuit breakers feeding the utility and generator sources to the switch.
Initiate the electrical transfer test by activating the TS test switch. P timer will time out and the micro­controller will send an engine start signal. When the W time has elapsed, the switch will complete its transfer by closing into Source 2.
Deactivating the test switch will start retransfer to Source 1. The switch will complete its retransfer to Source 1 after the time delay of the T timer. The U engine overrun timer allows the engine generator to run unloaded for a preset cool down period.
NOTE: A periodic test of the transfer switch
under load conditions is recommended to insure proper operation. (See National Electric Code articles 700 and 701).
WARNING
When performing a hi-pot or dielectric test
on the power section,
DISCONNECT the
contr
ol panel plugs from the microprocessor
to avoid potential damage.
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
25
Page 28

Replacement Parts

Standard Transition — 40 to 200 Amps
TAG DESCRIPTION
CN/CE Solenoid
Solenoid Plunger and Link
SCN/SCE Coil Cutout Switch
SCN/SCE
Coil Cutout Switch
BR Rectifier
Figure 17
VOLTAGE 40 TO 200 AMPS
120
K-2207
208
K-2208
220
K-2208
240
K-2228
277
K-2211
380/416
K-2212
440/480
K-2209
575/600
K-2213
ALL 57P-1030
120-480V L-3078
600V L-4027
ALL PS-5076
A3/A4 Auxiliary Contacts
L
-3078
26
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
BR
CN/CE
SCN/SCE
Page 29
Replacement Parts (cont’d)
Standard Transition - 225 to 400 Amps
Figure 18
ge
d
g
n
s
*
*
00
N
g
S
1
S
1
S
1
N
N
e Size
CM
CM
Co
s
0
5B
0
6B
E
Solenoid
6
0
8B
0
9B
E
Co
es
8
4
s
er
6
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
27
BR
CN/CE
T1 T2 T3 TN
N1 N2 N3 NN
SN A4
SE A3
Ta
N 1,2,3 E 1,2,3 T 1,2,3
CN/C
SN/S
A3/A
Descriptio
Cable Connection Lu
Wir
il Cutout Switch
Auxiliary Contact
Rectifi
E1 E2 E3 EN
Recommende
as Spare
225, 250
-270
il Volt
12
208/22
380/41
440/48
575/60
Stock Numbers by Ampera
260, 300
-270
#4-600 M
K-224
K-224
-
K-224
K-224
L-307
PS-507
4
-270
#4-600 M
Page 30
Replacement Parts (cont’d)
Standard Transition — 600 to 1200 Amps
Figure 19
TAG DESCRIPTION
STOCK NUMBERS BY AMPERAGE
600 800 1000 1200
N 1,2,3, N
E 1,2,3, N T 1,2,3, N
Cable Connection Lug
S1393F
(2)
S1392F
(4)
S1392F
(4)
S1392F
(4) Wire Size #2-600 MCM #2-600 MCM #2-600 MCM #2-600 MCM Stationary Contact Assembly Kit Consult Factory Arc Grid Assembly Kit 23P-1366 Movable Contact Assembly Kit Consult Factory
CN/CE Main Operating Coils Coil Volts Poles
120 2 K-2090F K-2073F K-2073F
K-2073F
240
2 K-2092F K-2070F K-2070F
K-2070F 3 K-2078F K-2070F K-2070F K-2070F 4 K-2091F K-2074F K-2074F K-2074F
208 3,4 K-2091F K-2074F K-2074F K-2074F
575/600 3,4 K-2095 K-2155 K-2155 K-2155
480
3 K-2080F K-2071F K-2071F K-2071F 4 K-2079F K-2071F K-2071F K-2071F
416 3 K-2080F K-2071F K-2071F K-2071F SN CCN Cut-out Switch 23P-1333 SE CCE Cut-out Switch 23P-1327 23P-1452 A3 Emergency Position Aux Contact (Qty 1) 23p-1327 (Qty 2) 23p-1328 (Qty 3) 23p-1334 (Qty 4) 23p-1336 A4 Normal Position Aux Contact (Qty 1) 23p-1333 (Qty 2) 23p-1334 (Qty 3) 23p-1328 (Qty 4) 23p-1330 DS Disconnect Switch Operator L-4009; ; Contact Block L-1020
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
28
ARC GRID
NN
N1
N2
N3
CN
A4
SN
A4 A3
DS
A3 SE
CE
EN
STATIONARY CONTACT
E1
E2
MOVABLE CONTACT
E3
(ARC GRID REMOVED FOR CLARITY)
Page 31
Replacement Parts (cont’d)
Standard Transition — 1600 to 3000 Amps
Figure 20
TAG DESCRIPTION
STOCK NUMBERS BY AMPERAGE
1600 2000 3000
N 1,2,3, N
E 1,2,3, N T 1,2,3, N
Cable Connection Lug
S1126F (2)
Optional
S1126F (2)
Optional
S1126F (2)
Optional Wire Size (8) #2-600 MCM (8) #2-600 MCM (8) #2-600 MCM Stationary Contact Assembly Kit 23P-1594 23P-1594 23P-1594 Arc Grid Assembly Kit 23P-1171 23P-1171 23P-1171 Movable Contact Assembly Kit 23P-1400 23P-1400 23P-1400
CN/CE Main Operating Coils Coil Volts Poles
120 2 SPO SPO SPO
240
2,3 K-2123F K-2123F K-2123F
4 K-2127F K-2127F K-2127F
208
3 K-2125F K-2125F K-2125F 4 K-2128F K-2128F K-2128F
575/600
3 K-2153F K-2153F K-2153F 4 K-2154F K-2154F K-2154F
480
3 K-2120F K-2120F K-2120F 4 K-2130F K-2130F K-2130F
416 3 K-2126F K-2126F K-2126F SN CCN Cut-out Switch 23P-1352 SE CCE Cut-out Switch 23P-1356 A3 Emergency Position Aux Contact (Qty 1) 23p-1356 (Qty 2) 23p-1357 (Qty 3) 23p-1353 (Qty 4) 23p-1355 A4 Normal Position Aux Contact (Qty 1) 23p-1352 (Qty 2) 23p-1353 (Qty 3) 23p-1357 (Qty 4) 23p-1359 DS Disconnect Switch Operator L-4009; ; Contact Block L-1020
RN, RE Rectifier 23P-1473 (Up to 240V); 23P-1582 (Up to 600V)
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
29
ARCH GRID ASSEMBLY
NN
A4
CN
SN
RN
DS
RE
A3 SE
CE
EN
STATIONARY CONTACT (ARCH GRID REMOVED FOR CLARITY)
N1
E1
N2
E2
MOVEABLE CONTACT
N3
E3
Page 32
Replacement Parts (cont’d)
Standard Transition — 4000 Amps
Figure 21
TAG DESCRIPTION
STOCK NUMBERS
N 1,2,3, N E 1,2,3, N
Cable Connection Lug
S1511F (3)
Optional
T 1,2,3, N
Wire Size
(12) #2-600 MCM Stationary Contact Assembly Kit 23P-1655 Arc Grid Assembly Kit
23P-1171
Movable Contact Assembly Kit 23P-1640
CN/CE
Main Operating Coils
Coil Volts Poles
240
3 K-2219 4 K-2219
208
3 K-2226 4 K-2226
575/600
3 K-2221 4 K-2221
480
3 K-2218 4 K-2218
416 3 K-2220
SN CCN Cut-out Switch 23P-1352
SE CCE Cut-out Switch 23P-1356 A3 Emergency Position Aux Contact (Qty 1) 23p-1356 (Qty 2) 23p-1357 (Qty 3) 23p-1353 (Qty 4) 23p-1355 A4 Normal Position Aux Contact (Qty 1) 23p-1352 (Qty 2) 23p-1353 (Qty 3) 23p-1357 (Qty 4) 23p-1359
DS Disconnect Switch Operator L-4009; ; Contact Block L-1020
RN, RE Rectifier 23P-1473 (Up to 240V); 23P-1582 (Up to 600V)
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
30
ARC GRID ASSEMBLY
CN
CE
N1
E1
MOVABLE CONTACT
N2
E2
N3
E3
NN
CN
RN
RE
CE
EN
STATIONARY CONTACT
Page 33
Replacement Parts
(cont’d)
Delayed Transition - 40 to 400 Amps
4
40-80 Amps
Figure 22
100-400 Amps
Figure 23
g
n
d
s
ge
80
00
N
g
S-2515
S
1
N
N
e
/0
CM
Co
s
SECO
Y
0
5B
58
6
0
6B
58
7
5
58
8
E
Solenoid
0
8B
58
9
0
9B
58
0
0
K
9B
58P
0
al
54
p
8
4
s
8
O
Co
ch
1
)
6
er
52
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
31
BR
(RN/RE)
CN/CE
T1 T2 T3 TN
E1 E2 E3 EN
N1 N2 N3 NN
SNO
SN/A
SE/A3
SEO
Ta
N 1,2,3 E 1,2,3 T 1,2,3
CN/C
A3/A
SNO/SE
Descriptio
Cable Connection Lu
Wire Siz
Handle-Manu
Handle-Gri
Auxiliary Contact
il Cutout Swit
Rectifier (>380V
Rectifi
Recommende
as Spare
il Volt
12
208/24
380/41
440/48
575/60
575/60
Stock Numbers by Ampera
40-
#8 MCM-3
K-224
K-224
-
K-224
K-224
-224
E30
L-307
L-307
E352
PS-507
PS-51
100-4
-270
#4-600 M
NDAR
P-110
P-110
P-110
P-110
P-111
-111
Page 34
Replacement Parts
(cont’d)
Delayed Transition - 600 to 1200 Amps
ge
g
n
d
s
p
6
0
,3
,3
,3
N
e
S-1383F
(2)
2
t
1
t
358
t
9
e Contact
0
O
O
Co
er
)
)
O
ch
)
O
ch
)
3
t
536
t
535
S Disconnect S
ch
0
O
O
s
w
.
s
e
Co
C
e
600
0
3
3
0
3
5
8
3
8
,4
6
80 3 3 480
3
58
0
3
80
,4
58
6
3
6
3
y
000
00
(4)
2
336
6
334
335
8
0
57
57
F
Figure 24
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
32
Ta
NL 1,2 EL 1,2
1,2
NN, EN, T
RN/RN RE/RE
SN/SN SE/SE A
D
CN/CN CE/CE
Volt
24
120/20
4 277/48 240/41
Descriptio
Cable Connection Lug, CU Wir
Stationary Contact Assembly Ki Arc Grid Assembly Ki Movable Contact Assembly Ki Movabl
il Rectifi
Limit Swit Limit Swit Emergency Position Auxiliary Contac Normal Position Auxiliary Contac
wit
Main Operator Solenoid
Wir
il VD
24 20
4 41
Recommende
as Spare
Pol
3
3
Stock Numbers by Ampera
00-80
500MCM-
23P-147 23P-1 23P-146 23P-147
23P-1473 (Up to 240 VAC 23P-1582 (Up to 600 VAC
23P-1535(L); 23P-1533(R 23P-1536(L); 23P-1534(R
23P-1 23P-1
Operator: L-4009; Contact Block: L-102
See Chart Belo
Solenoid Part No
K-214 K-214 K-21 K-21
Consult Factor
1
-12
2-1392
600MCM-
26P-1 23P-136 26P-1 26P-1
00-120
-
­K-21 K-21
Page 35
Replacement Parts
(cont’d)
Delayed Transition - 1600 to 3000 Amps
D
Y
3
/
O
O
O
E
/
CT
O
Figure 25
RY
CT
g
ecommended
n
s
600 2000
3000
,3
(2)
,3
l
,3
2
N
t
X
Y
Z
t
1
1
1
t
0
0
4
O
s
w
O
a
.
s
e
Co
C
e
0 120
O.
O.
0
3
0
,3
51
51
51
0
3
3
0
3
51
51
51
8
3 208
,4
51
51
51 480
3
3
80
3
0
0
0
5
3
3
0
3
.
.
0
3 480
,4
0
0
0
0
0
51
51
51
6
3
6
3
y
t
,2
y
0
0
0
2
y
1
1
1
,4
y
2
2
2
,4
y
3
3
3
GE Zenith Controls
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
33
CN
N
ARC GRI
N
ASSEMBL
N
E
Ta
N1,2 E1,2 T1,2 NLN,EL
CN/CN CE/CE
Volt
12
120/24
24
120/20
57 277/48 120/24 240/41
SN/SNO-1 SE/SEO-1, SN/SNO-3 SE/SEO-3
CE
E
MOVABL
NTA
STATIONA
NTA
Descriptio
Cable Connection Lug, CU Wire Optiona
Stationary Contact Assembly Ki Arc Grid Assembly Ki Movable Contact Assembly Ki
Main Operator Solenoid
Voltage System
Wir
Switch Bracket Assembl Switch Bracket Assembl Switch Bracket Assembl Switch Bracket Assembl
il VD
24 24
4
575/60
24 41
Operating Coil Hardware Ki
R
as Spare
23P-4134
23P-117 23P-140
Pol
2
3
3
K-21 K-21 K-21 K-216
K-216 K-21
23P-154 23P-154 23P-154 23P-154
Stock Numbers by Amperage
1
.P.
S.P.O
S-1126F
8) 600MCM-
23P-4134
23P-117 23P-140
See Chart Belo
Solenoid P
.P.O. K-21 K-21 K-21 K-216
S.P.O. S.P.O K-216 K-21
Consult Factor
23P-154 23P-154 23P-154 23P-154
23P-4134
23P-117 23P-134
rt No
.P. K-21 K-21 K-21 K-216
K-216 K-21
23P-154 23P-154 23P-154 23P-154
Page 36
Replacement Parts (cont’d)
Delayed Transition — 4000 Amps
Figure 26
TAG DESCRIPTION
STOCK NUMBERS
N 1,2,3, N E 1,2,3, N
Cable Connection Lug
S1511F (3)
Optional
T 1,2,3, N
Wire Size
(12) #2-600 MCM Stationary Contact Assembly Kit 23P-1655 Arc Grid Assembly Kit
23P-1171
Movable Contact Assembly Kit 23P-1640
CN/CE
Main Operating Coils
Coil Volts Poles
240
3 K-2215 4 K-2215
208
3 K-2227 4 K-2227
575/600
3 K-2217 4 K-2217
480
3 K-2214 4 K-2214
416 3 SPO
SN/SNO CCN Cut-out Switch 23P-1568
SE/SEO CCE Cut-out Switch 23P-1569
A3 Emergency Position Aux Contact (Qty 1) 23p-1356 (Qty 2) 23p-1357 (Qty 3) 23p-1353 (Qty 4) 23p-1355 A4 Normal Position Aux Contact (Qty 1) 23p-1352 (Qty 2) 23p-1353 (Qty 3) 23p-1357 (Qty 4) 23p-1359
DS Disconnect Switch Operator L-4009; ; Contact Block L-1020
RN, RNO, RE, REO
Rectifier 23P-1473 (Up to 240V); 23P-1582 (Up to 600V)
ZTS / ZTSD Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
34
ARC GRID ASSEMBLY
CN
CE
N1
E1
MOVABLE CONTACT
N2
E2
N3
E3
NN
EN
STATIONARY CONTACT
CN
RN
RE
CE
Page 37
ZTSH/ZTSDH/ZTSDL/ZTSHL/ZTSDHL
Standard Control Panel Layout (SSRCP)
Figure 27
JUMPER
CONNECTS
POINTS
REMOVE WHEN
ACCESSORIES USED
J1 23, 23A B1 J2 23A, 23B B2 J3 23B, 23C B3 J4 23C, 23Z JIN, TS, C/D J5 23Z, 27 T, YN J6 25, 25Z T3, R4 J7 28, 28Z S1, C, C/D J8 28Z, 29 P1 & U
J9 33A, 33Y ER1, 2, 3, J1E J10 33Z, 37 W J11 35, 35Z R4, W3
Panel Mount Control Relays
Figure 28
TAG
DESCRIPTION
L1
L2
ATS Source 2 (EMER) Position Indicator A
TS Source 1 (NORMAL) Position Indicator
Lens Source 1 (NORMAL) Lens Source 2 (EMER) Bulb Socket Source 2 (EMER) Bulb Source 1 (NORMAL) Bulb
TS Test Switch
Operator
, Momentary Contact Block N.C. Contact Mounting Base
GE Zenith Controls
ZTS/ZTSD/ZTSH/ZTSDH/ZTSDL/ZTSHL/ZTSDHL Operation and Maintenance Manual (71R-3000)
35
P1
B1
T
U
B2 B3
VFSM
CR
XN
XE
RT
JUMPERS
J1 J2 J3 J4 J5 J6 J7 J8 J9 J10 J11
SPARE
P1
B3
T
U
W
W
ATS
L2
NORMAL
SOURCE 1
L1
EMER
SOURCE 2
VFSM
PRESS TO TEST
B2
RT
HOLD UNTIL
TRANSFER
TS
B1
XN XE
CR
CE1
CN1
Page 38

Sequence of Operation

The information package supplied with the transfer switch includes a schematic diagram and description of operation of all accessories provided.
The sequence for load transfer to Source 2 begins automatically when any phase of Source 1 falls below the preset “fail” or dropout point and this undervoltage failure condition is detected by the solid state phase relays B1, B2, B3.
The phase relays drop out, de-energizing Source 1 control relay CR, and engine start timer P1 begins its timing cycle. The P1 time delay is provided to override momentar
y outages and to prevent nuisance starting of the engine generator. If Source 1 voltage returns above the “restore” or pickup setting of the phase relays, the P1 timing cycle is reset to zero by the re-energization of the CR relay.
If Source 1 voltage does not return before the P1 time delay is completed, the P1 timer drops out and sends a starting signal to the engine generator
. Source 2 voltage and frequency sensing relay VFSM monitors the voltage and frequency of Source 2. When both the voltage and the frequency of Source 2 reach the preset “restore” or pickup points, the VFSM relay initiates the transfer to Source 2 and timer W begins its timing cycle. The W timer provides an adjustable transfer delay to Source 2 as required.
When the W time delay is completed, Source 2 control relay R
T energizes and picks up the power relay, CE1 or CCE. The power relay connects voltage from Source 2 to the Source 2 switch operating circuit causing the switch to transfer its main contacts to Source 2. The switch is mechanically locked in Source 2 position. The power relay and Source 2 operator are de-ener
­gized when the SE limit switch is activated by the operator
. The SN limit switch is deactivated at the same time, readying Source 1 control circuit for retransfer when Source 1 is restored.
The sequence for retransfer to Source 1 begins automat­ically when the voltage on all phases of Source 1 reach the preset “restore” or pickup point and this condition is detected by the solid state phase relays.
When Source 1 restores, the solid state phase relays B1, B2, B3 pick up and initiate retransfer of the switch to Source 1 by energizing timer T and beginning its timing cycle. The T timer provides an adjustable delay to ensure that Source 1 has stabilized before reconnection to the load. If Source 1 fails before the T time delay is completed, the phase relays drop out and the T timing cycle is reset to zero.
When the T time delay is completed, Source 1 control relay CR energizes and picks up the power relay
, CN1 or CNN. The power relay connects voltage from Source 1 to Source 1 switch operating circuit causing the retransfer of the main switch contacts to Source 1. The switch is mechanically locked in Source 1. The power relay and Source 1 operator are de-energized when the SN limit switch is activated by the operator. The SN limit switch also energizes the engine over-run timer U and begins its timing cycle. The timer provides a period of time for the engine generator to run without load and cool down before shutdown. After the U time delay is completed, the P1 timer is energized and the engine generator is shutdown.
36
ZTS/ZTSD/ZTSH/ZTSDH/ZTSDL/ZTSHL/ZTSDHL Operation and Maintenance Manual (71R-3000)
GE Zenith Controls
Page 39

Adjustments and Settings

Solid State Timers
Solid state timers are adjustable from 0.1 second to 100 hours. The red timing indicator in the upper left corner flashes as the timer progresses through the timing cycle. When the timing cycle is completed, the indicator remains illuminated. A flathead screwdriver is required to change the setting, as shown in Figure 30.
The time unit is selected by turning the rotary switch at the lower right of the timer
. Four selections are available: “Seconds”, “Minutes”, “Hours”, “10 Hours”. The time unit selected is displayed in the window below the time setting dial.
The time range is selected by turning the rotary switch at the lower left of the timer
. Four ranges are available: “0-0.5”, “0-1.0”, “0-5.0”, “0-10.0”. The dial digits appear in the windows around the time setting knob.
Figure 29
CAUTION
Do NOT change the setting while the timer is energized. Timer malfunction or damage may occur.
The factory setting of the solid state timers used in the Zenith standard package are shown in Table 4.
Timer
Factory Setting
T 30 minutes U 5 minutes
W 1 second
Table 4
Voltage/Frequency Sensor (VFSM)
The “restore” or pickup point may be adjusted by rotating the adjustment screw as shown in Figure 31. Counter-clockwise rotation increases the pickup voltage.
“Restore”/Pickup Voltage (at 100% Frequency)
Adjustable: 80% to 95% Factor
y Set: 90%
“Restore”/Pickup Frequency
Adjustable: 80% to 100%
Figure 30
Factory Set: 95%
Solid State Phase Relay (ARSM)
The “restore” or pickup and “fail” or dropout points may be adjusted by using the following procedure. Use of a variable voltage supply (Variac) is required. The relay is illustrated in Figure 32.
1. Turn the “restore” or pickup adjustment fully clockwise.
2. Turn the “fail” or dropout adjustment fully counter-clockwise.
3. Set Variac to the desired “restore” or pickup voltage.
4. Rotate the “restore” or pickup adjustment counter­clockwise very slowly until the relay picks up. The LED will illuminate.
5. Set Variac to the desired “fail” or dropout voltage.
6. Rotate the “fail” or dropout adjustment clockwise very slowly until the relay drops out. The LED will go out.
7. Verify the setting by raising the voltage until the relay restores or picks up and lowering the voltage until the relay fails or drops out.
“Restore”/Pickup Voltage: 75% to 115% of Nominal Factory Set: 90% of Nominal
“Fail”/Dropout Voltage: 55% to 105% of Nominal Factory Set: 80% of Nominal
Figure 31
GE Zenith Controls
ZTS/ZTSD/ZTSH/ZTSDH/ZTSDL/ZTSHL/ZTSDHL Operation and Maintenance Manual (71R-3000)
37
Page 40
g
GE Zenith Controls
A Product of GE Industrial Systems General Electric Company
830 West 40
th
Street, Chicago, IL 60609 USA
773 299-6600
, Fax: 773 247-7805
www.geindustrial.com
Loading...