GE 8500 Series, Zoneline AZ85H12DAC, Zoneline 8500 Series Owner's Manual

Page 1
GEAppliances.com
Safety Instructions ........... 2
Operating Instructions
Controls—Dip Switches ......... 3–5
Controls—Terminal
Connections ...................6, 7
On/Off Switch ....................8
Ventilation Control ............... 8
Owner’s Manual and
Installation Instructions
Cool Only, Heat/Cool and
Heat Pump Models
8500 Series
Vertical
®
Zoneline
Care and Cleaning
Air Filters ........................9
Base Pan ........................ 9
Exhaust Coils ..................... 9
Electrical Supply. . . . . . . . . . . . . .11–13
Installing the Zoneline ........14–21
Preparation .....................10
Servicing ........................22
Troubleshooting Tips .......23
Normal Operating Sounds .......24
Consumer Support
Consumer Support ......Back Cover
Warranty .......................27
Español
For a Spanish version of this manual, visit our Website at GEAppliances.com.
Para consultar una version en español deeste manual de instrucciones, visite nuestrositio de internet GEAppliances.com.
Française
For a French version of this manual, visit our Website at GEAppliances.com.
Pour une version française de ce manuel d’utilisation, veuillez visiter notre site web à l’adresse GEAppliances.com.
Write the model and serial numbers here:
Model # ________________________
Serial # _________________________
You can find them on a label on the front case panel.
Air Conditioners
Printed in China
TINSEA612JBRZ 49-7639 01-10 GE
Page 2
IMPORTANT SAFETY INFORMATION. READ ALL INSTRUCTIONS BEFORE USING.
WARNING!
Risk of electric shock. Can cause injury or death. For your safety, the information in this manual must be followed to minimize the risk of fire, electric shock or personal injury.
SAFETY PRECAUTIONS
n This Zoneline must be properly installed
in accordance with the Installation Instructions before it is used. See the Installation Instructions in the back of this manual.
n Replace immediately all electric service
cords that have become frayed or otherwise damaged. A damaged power supply cord must be replaced with a new power supply cord obtained from the manufacturer and not repaired. Do not use a cord that shows cracks or abrasion damage along its length or at either the plug or connector end.
n Product must be operated with
the electrical plug supplied with the product. Do not replace the electrical plug supplied with the product.
n If the receptacle does not match the plug,
the receptacle must be changed out by a qualified electrician.
n Unplug or disconnect the Zoneline
at the fuse box or circuit breaker before making any repairs.
NOTE: We strongly recommend that any servicing be performed by a qualified individual.
n All air conditioners contain refrigerants,
which under federal law must be removed prior to product disposal. If you are getting rid of an old product with refrigerants, check with the company handling disposal about what to do.
nThese R410A Air Conditioner Systems
require contractors and technicians to use tools, equipment and safety standards approved for use with this refrigerant. DO NOT use equipment certified for R22 refrigerant only.
READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY.
SAVE THESE INSTRUCTIONS
Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions
2
Page 3
Controls–dip switches. GEAppliances.com
Controls–Dip Switches
Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support
The dip switch controls are located behind the front case panel, through an opening on the front of the unit.
To access the dip switches, remove the front case panel by removing the filter, taking out the four front screws, the upper two screws from the top of the panel and the shipping screws on each side, if present. (Discard the four side shipping screws, if present).
Side shipping screw
Side shipping screw
Dip Switches
NOTE: The owner is responsible for setting the appropriate dip switches and connecting terminals.
TL3 (C) (Temp. Limit 3–Cool) TL2 (C) (Temp. Limit 2–Cool) TL1 (C) (Temp. Limit 1–Cool)
ALL I2R (All Electric Heat) (Heat-pump models only)
FREEZ S (Freeze Sentinel)
CONST FAN (Constant ON Fan)
All Electric Heat (Heat pump models only)
When this switch is enabled (UP), heat pump operation is locked out, causing the unit to provide only electric resistance heat.
TL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat)
No Function (Reserved for future use) DUCT (Blower Fan) OCCUPIED (Occupancy Sensor)
ALL I2R (All Electric Heat)
3
Page 4
Controls–dip switches.
Freeze Sentinel (Requires room air sensor kit–RAVRMS)
When this switch is enabled (UP), it turns OFF the freeze sentinel protection feature. With the switch disabled (DOWN), the freeze sentinel is activated which automatically provides heat without user interface. This helps to prevent plumbing damage by turning the heater and fans ON at 41° F and OFF at 46° F.
Constant ON Fan
When this switch is enabled (UP), it allows the fan to run continuously.
Occupancy Sensor (Field Supplied)
FREEZE S (Freeze Sentinel)
CONST FAN (Constant ON Fan)
When this switch is enabled (UP), it allows the unit to utilize an infrared motion sensor and a door switch for occupancy detection. This feature combined with field devices automatically cycles the unit between normal operation and a preset energy management operation.
Duct
The duct select function allows the indoor fan to be operated at two variable fan speeds. When this switch is enabled (UP), the unit automatically selects either high or middle fan speed (for longer ductwork applications). When set in the down position, the unit is automatically operated in either the middle or low fan speed (for shorter ductwork applications).
OCCUPIED (Occupancy Sensor)
DUCT (Blower Fan)
Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions
4
Page 5
Temperature Limiting (Requires room air sensor kit–RAVRMS)
GEAppliances.com
Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support
Temperature limiting can reduce energy costs by limiting the lowest temperature that can be set for cooling and the highest temperature that can be set for heating. Temperature limiting is controlled by switches 1–6 on the top block
TL3 (C) (Temp. Limit 3–Cool) TL2 (C) (Temp. Limit 2–Cool) TL1 (C) (Temp. Limit 1–Cool)
Temperature limiting during COOL mode
(all temperatures shown in °F) UP DOWN Minimum Maximum NONE 1, 2, 3 60° 85° 1 2, 3 64° 85° 1, 2 3 66° 85° 2 1, 3 68° 85° 2,3 1 70° 85° 1, 2, 3 NONE 72° 85° 1, 3 2 74° 85° 3 1, 2 76° 85°
of auxiliary controls. The first three switches are used to select the cooling limits. The next three switches are used to control the heating limits.
TL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat)
Temperature limiting during HEAT mode
(all temperatures shown in °F)* UP DOWN Minimum Maximum NONE 4, 5, 6 60° 85° 4 5, 6 60° 80° 4, 5 6 60° 78° 5 4, 6 60° 76° 5,6 4 60° 74° 4, 5, 6 NONE 60° 72° 4, 6 5 60° 70° 6 4, 5 60° 65°
* Not applicable to Cool-Only models
5
Page 6
Controls—terminal connections.
Controls–Terminal Connections
The terminal connections are located behind the front case panel through an opening on the front of the unit.
To access the terminal connections, remove the front panel by removing the filter, taking out the four front screws, the upper two screws from the top of the panel and the shipping screws on each side, if present. (Discard the four side shipping screws, if present.)
Insert the building hook-up wires into the bottom of the terminals and tighten screws securely to make the desired connections.
Route the wires from the terminal connections through the unit wire guides and out through the case wire guide.
NOTE: The owner is responsible for setting the appropriate dip switches and connecting terminals.
CAUTION:
Improper CDC wiring may damage the Zoneline electronics or cause erratic Zoneline operation. No common busing is permitted. A separate wire pair must be run from each separate controlling switch to each individual Zoneline.
Route wires through wire guides
Terminal connections
Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions
6
24VAC
FAN LO
FAN HI
COMP
REV VA L
AUX HEAT
Room Air Sensor
Motion Sensor
Door Sensor
Central Desk Control
Room Air Sensor (Requires room air sensor kit – RAVRMS)
When connected, the room air sensor will allow utilization of the temperature limiting and freeze sentinel features.
NOTE: If GE thermostat RAK148D1, RAK148P1 or RAK164D1, RAK164P1 is used with the unit, the room sensor kit is not needed for temperature limiting since this feature is incorporated in the
Room Air Sensor
thermostats.
Hydronic Heating (Requires Hydronic Heating Kit – RAVHW1, RAVHW2 or RAVHW3)
Required connections for hydronic heating kit.
NOTE: R, W, C terminal connections will also be connected to the remote thermostat if applicable.
COMMON
Common–Ground White–Heater Yellow–Compressor Black–Reversing Valve Green–High Speed Fan Green–Low Speed Fan Red–24V AC only
24VAC
FAN LO
FAN HI
24VAC
FAN LO
FAN HI
Hydronic Heating
COMP
REV VAL
REV VAL
COMP
AUX HEAT
AUX HEAT
COMMON
COMMON
Page 7
Motion Sensor (Obtained locally)
The Occupancy Sensor dip switch must be in the up position to use this feature.
When connected, the wall mounted motion sensor will detect motion in the room and automatically cycle the unit between normal operation and energy management operation.
The door and motion sensors work together to automatically cycle the unit between normal operation and energy management operation.
Door Sensor (Obtained locally)
The Occupancy Sensor dip switch must be in the up position to use this feature.
When connected, the door sensor will detect when the door in the room is opened or closed. This feature must be used in conjunction with the motion sensor.
The door and motion sensors work together to automatically cycle the unit between normal and energy management operations.
Motion Sensor
24VAC
24VAC
Door Sensor
GEAppliances.com
FAN HI
FAN HI
COMP
REV VAL
AUX HEAT
COMP
REV VAL
AUX HEAT
FAN LO
FAN LO
Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support
COMMON
COMMON
Central Desk Control
When connected, the unit lock-out is released and it can be turned ON or OFF with a switch located at the Central Desk Control. A separate wire pair must be run from each separate controlling switch to each individual Zoneline. A 24V AC circuit powers the CDC system. No external power is required.
Remote Thermostat
The unit will be controlled by a remote thermostat.
IMPORTANT:
The Zoneline thermostat connections provide 24V AC only.
If using a digital/electronic wall thermostat, you must set it to the 24V AC setting. See the Installation Instructions for the wall thermostat.
NOTICE:
Damage to a wall thermostat or to the Zoneline electronics can result from improper connections. Exercise extra attention when connecting blue and black wires. No line voltage connections should be made to any circuit in the thermostat. Isolate all wires in building from line voltage.
Red–24V AC only
Green–Low Speed Fan
Green–High Speed Fan
Black–Reversing Valve
Yellow–Compressor
White–Heater
Common–Ground
24VAC
FAN LO
FAN HI
COMP
REV VAL
Central Desk Control
24VAC
FAN LO
FAN HI
COMP
REV VAL
AUX HEAT
AUX HEAT
COMMON
COMMON
7
Page 8
Other features of your Zoneline.
On/Off Switch
The unit on/off switch is located on the front of the Zoneline.
To turn on the unit, press the top of the switch in.
To turn off the unit, press the bottom
of the switch in.
NOTE: The on/off switch does not remove power from the unit.
Ventilation Control
The ventilation control lever is located on the left side of the Zoneline unit, behind the front case panel.
To access the ventilation control lever, remove the front panel by removing the filter, taking out the four front screws, the upper two screws from the top of the panel and the shipping screws on each side, if present. (Discard the four side shipping screws, if present).
When the lever is in the CLOSE position, only the air inside the room is circulated and filtered.
When the lever is in the OPEN position, some outdoor air will be drawn into the room. This will reduce the heating or cooling efficiency.
To close the vent, push the vent lever handle down, pull it forward and lock it up in place.
To open the vent, push the vent lever handle down, push it back and lock it up in place.
ON/OFF
switch
Open
Vent control (push
lever down and
pull forward or
back to operate)
Energy Tip: Keep the vent control in the CLOSE position. The room air will be filtered and circulated.
NOTE: Ventilation openings are not intended to be the source of make-up air for building ventilation systems due to the additional heating and cooling loads generated.
Close
About Heat Pumps (on some models)
Heat pumps can reduce operating costs by exchanging heat from the outside air—even when the outside temperature is below freezing— and releasing that heat indoors.
To get the best economic benefit from your heat pump, don’t change the room thermostat setting very often. Raising the heat setting 2–3 degrees will cause the Zoneline to use its electric heating elements in order to reach the new temperature setting quickly.
Do Not Operate the Air Conditioner (cool mode) in Freezing Outdoor Conditions
Air conditioners are not designed for use when
Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions
freezing outdoor conditions exist. They must not be used in freezing outdoor conditions.
8
There is a three minute minimum compressor run time at any setting to prevent short cycling.
The indoor fan motor starts before the compressor and stops after the compressor cycles off.
The electric heating elements use much more electricity than heat pumps and cost more to operate.
Page 9
Care and cleaning. GEAppliances.com
Turn off the Zoneline and disconnect the power supply before cleaning.
Indoor/Outdoor Coils
The exhaust coils on the Zoneline should be checked regularly. If they are clogged with dirt or soot, they may be professionally steam cleaned by your GE service center. You will need to remove the unit from the case to inspect the coils because the dirt build-up occurs on the exhaust side.
Outdoor coils
Have the coils cleaned regularly.
Drain
Clean the drain system regularly to prevent clogging.
Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support
Base Pan
In some installations, dirt or other debris may be blown into the unit from the outside and settle in the base pan (the bottom of the unit).
In some areas of the United States, a “gel-like” substance may be present in the base pan.
Check it periodically and clean, if necessary.
Air Filters
To maintain optimum performance, change the filter at least every 30 days.
The most important thing you can do to maintain the Zoneline is to change the filter at least every 30 days. Dirty filters reduce cooling, heating and air flow.
Changing the filter will: Decrease cost of operation, save energy, prevent clogged heat exchanger coils and reduce the risk of premature component failure.
To remove and replace the filter:
NOTICE: Do not operate
the Zoneline without the filter in place. If a filter becomes torn or damaged, it should be replaced immediately.
Operating without the filter in place or with a damaged filter will allow dirt and dust to reach the indoor coil and reduce the cooling, heating, airflow and efficiency of the unit.
Remove filter
Unit-mounted filter
Filter
Replacement filters should be purchased from your local retailer where air conditioner and furnace accessories are sold.
Filter size required is 20” x 20” x 1".
Filter
Return air grille
Access-panel with
return air grille
9
Page 10
Installation Zoneline Air Instructions Conditioners
Questions? Visit our Website at: GEAppliances.com or call 800.GE.CARES (800.432.2737).
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT
for local inspector’s use.
IMPORTANT
codes and ordinances.
Note to Installer – Be sure to leave these
instructions with the owner.
Note to Owner – Keep these instructions
for future reference.
• Proper installation is the responsibility of the installer.
• Product failure due to improper installation is not covered under the Warranty.
• You MUST use all supplied parts and use proper installation procedures as described in these instructions when installing this air conditioner.
TOOLS YOU WILL NEED
Phillips screwdriver
Saw
Save these instructions
Observe all governing
Adjustable wrench
Hammer
IMPORTANT ELECTRICAL SAFETY–READ CAREFULLY
WARNING:
• All electrical connections and wiring MUST be installed by a qualified electrician.
• Follow the National Electrical Code (NEC) and/or local codes and ordinances.
• For personal safety, this Zoneline unit and case must be properly grounded.
• Protective devices (fuses or circuit breakers) acceptable for Zoneline installations are specified on the nameplate of each unit.
• Do not use an extension cord with this unit.
• Aluminum building wiring may present special problems—consult a qualified electrician.
• When the unit is not running there is still voltage to the electrical controls.
• Disconnect the power to the unit before servicing by:
1. Removing the power cord (if it has one) from
the wall receptacle.
OR
2. Removing the branch circuit fuses or turning
the circuit breakers off at the panel.
RISK OF ELECTRIC SHOCK.
Tape measure
WARNING:
Can cause injury or death. This appliance must be properly grounded. Where a 2-prong wall outlet is encountered, it is your responsibility and obligation to have it replaced with a properly grounded 3-prong outlet.
RISK OF ELECTRIC SHOCK.
10
Page 11
Installation Instructions
ELECTRICAL REQUIREMENTS
• Use ONLY the wiring size recommended for single outlet branch circuit.
• Proper current protection is the responsibility of the owner.
Recommended branch circuit wire sizes*
Nameplate maximum circuit AWG Wire breaker size size**
15A 14 20A 12 30A 10
AWG – American Wire Gauge * Single circuit breaker from main box ** Based on copper wire, single insulated conductor at 60° C
NOTE: Use copper conductors only.
230/208 VOLT ELECTRICAL SUPPLY
A power supply kit must be used to supply power to the Zoneline unit. The appropriate kit is determined by the voltage, the means of electrical connection and the amperage of the branch circuit. See the POWER CONNECTION CHART on page 13 to select the appropriate kit.
FOR 230/208 VOLT CORD
CONNECTIONS ONLY
1. Remove the front panel by taking out the four front screws, the upper two screws from the top of the panel and the shipping screws on each side, if present. (Discard the four side shipping screws, if present.)
Side shipping screw
Side shipping screw
2. Remove the junction box cover and the junction box and discard.
Remove junction box and cover
Power supply kit
All wiring, including installation of the receptacle, must be in accordance with the NEC and local codes, ordinances and regulations.
Tandem
15 Amp
230/208 volt receptacle configuration
Perpendicular
20 Amp
3. Connect the power cord, with a loop, through the strain relief.
Large Tandem
30 Amp
Strain relief
IMPORTANT:
Power cord must have a loop.
11
Page 12
Installation Instructions
DIRECT CONNECT APPLICATIONS
FOR 230/208 VOLT DIRECT CONNECT
APPLICATIONS ONLY
Direct connection to branch circuit wiring inside
the provided junction box must be made by connecting as follows in steps 1–3 below.
Connector
REMOVE JUNCTION BOX COVER
1
• Remove the junction box cover by taking out the front two screws.
FOR 265 VOLT DIRECT CONNECT
APPLICATIONS ONLY
IMPORTANT: Connection of a 265V AC product
to a branch circuit MUST be done by direct connection in accordance with the National Electrical Code. Plugging this unit into a building mounted exposed receptacle is not permitted by code.
These models must be installed using the appropriate
GE power supply kit for the branch circuit amperage and the electrical resistance heater wattage desired. See the POWER CONNECTION CHART on page 13 to select the appropriate kit.
It is the responsibility of the installer to ensure
the connection of components is done in accordance with electrical codes.
Direct connection to branch circuit wiring inside the provided junction box must be made by connecting as follows in steps 1–3 below.
ATTACH CONDUIT
2
• Use the round knockout hole at the top of the junction box to install conduit coming from the branch circuit. Install and clamp the conduit through the conduit clamp and bring wire leads into the junction box. Leave 8" of wire free from the end of the conduit.
Junction box
Junction box cover
12
Conduit
Conduit clamp
Page 13
Installation Instructions
DIRECT CONNECT APPLICATIONS
MAKE WIRE LEAD CONNECTIONS INSIDE THE JUNCTION BOX
3
1. Make all wire connections by using appropriate UL-listed electrical connectors and techniques.
2. Select the applicable wiring situation and follow the instructions accordingly:
1-Phase 220-240 VAC
When connecting the Zoneline to a single-phase circuit
for 230V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit L1 and L2 leads. (The white lead of the power supply kit should be identified by the installer using electrical tape with some color other than green or white.) Connect the green lead of the power supply kit to the power supply and branch circuit ground.
3-Phase 208 VAC
When connecting the Zoneline to a three-phase circuit
for 208V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit L1 and L2 leads. (The white lead of the power supply kit should be identified by the installer using electrical tape with some color other than green or white.) Connect the green lead of the power supply kit to the power supply and branch
3. Be sure that all wire leads are inside the junction box and not
4. Plug the 9-pin connector into the 9-pin receptacle in the junction box.
5. Replace the junction box cover by replacing the two screws
circuit ground.
pinched between the box and the unit. The green insulated ground wire from the Zoneline MUST be connected to the branch circuit ground wire.
removed earlier.
3-Phase 208 VAC with “Crazy Leg”
When connecting the Zoneline to a three-phase circuit
with “Crazy Leg” for 208V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit Neutral and L1 leads. (The white lead of the power supply kit should be connected to neutral.) Connect the green lead of the power supply kit to the power supply and branch circuit ground.
3-Phase 253-277 VAC
When connecting the Zoneline to a three-phase circuit
for 265V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit Neutral and L1 leads. (The white lead of the power supply kit should be connected to neutral.) Connect the green lead of the power supply kit to the power supply and branch circuit ground.
Conduit
Make wire lead connections
POWER CONNECTION CHART
Power Cord Connections
230/208 Volt Wall Plug Heater Wattage
Power Supply Kits Configuration Circuit Protective Device @ 230/208 Volts
RAK3152 Tandem 15-Amp Time-Delay Fuse or Breaker 2.55/2.09 KW RAK3202 Perpendicular 20-Amp Time-Delay Fuse or Breaker 3.45/2.82 KW RAK3302 Large Tandem 30-Amp Time-Delay Fuse or Breaker 5.00/4.10 KW
Direct Connections
230/208 Volt Heater Wattage
Power Supply Kits @ 230/208 Volts Circuit Protective Device
RAK4157 2.55 KW/2.09 KW 15-Amp Time-Delay Fuse or Breaker RAK4207 3.45 KW/2.82 KW 20-Amp Time-Delay Fuse or Breaker RAK4307 5.00 KW/4.10 KW 30-Amp Time-Delay Fuse or Breaker
265 Volt Heater Wattage
Power Supply Kits @ 265 Volts Circuit Protective Device
RAK5157 2.55 KW 15-Amp Time-Delay Fuse or Breaker RAK5207 3.45 KW 20-Amp Time-Delay Fuse or Breaker RAK5307 5.00 KW 30-Amp Time-Delay Fuse or Breaker
13
Page 14
Installation Instructions
ZONELINE COMPONENTS
Case
REQUIRED ACCESSORIES
(Check the “Essential Elements” label on the unit.)
Zoneline unit
Front Case Panel
Cutout
Dimensions:
20" W x 32
1
4H
50
30
Wall Plenum
RAVWP6 - 6"D x 19
Architectural Louver
RAVAL1
RAVWP8 - 8”D x 19 RAVWP12 - 12”D x 19 RAVWP15 - 15”D x 19
Cutout
Dimensions:
W x 48H
28
Access Panel with
Return Air Grille
RAVRG1
OR
22 1⁄2
22 1⁄2
Wall Thermostat
Model Type Mechanical Thermostat Electronic Thermostat
Heat/Cool Models 4-wire 5-wire Heat Pump Models 6-wire 6-wire
Check the thermostat instructions for correct wiring and installation requirements.
3
4”W x 32”H
3
4”W x 32”H
3
4”W x 32”H
3
4”W x 32”H
Cutout
Dimensions:
3
8W x 203⁄8H
20
Return Air Grille
RAVRG2
14
Page 15
Installation Instructions
TYPICAL UTILITY CLOSET AND DIMENSIONS
(FOR REFERENCE ONLY)
UNIT INSTALLED THROUGH FRONT OF CASE
Top View
Architectural Louver
1
2
11
10”
3"
min.
Unit
front
4" min. from front of case – Unit installed through FRONT of case.
5" min. from front of case – Unit installed through SIDE of case.
3" min. from two sides of case. (5” for side install).
Option 1 Access panel with return air grille
Option 2 Return air grille
10" duct
4" min.
Door/access panel
Inside wall
3" min.
Rigid ductwork
Flexible or rigid duct
Air discharge outlet
31”
Side View
Unit
Wall plenum divider
Filter bracket
Drain fittings 3⁄4
UNIT INSTALLED THROUGH SIDE OF CASE
Top View
Architectural Louver
1
2
3”
min.
Wall
plenum
11
10
10”
Unit front
Outside wall
14” min. – Required only if optional Hydronic Heating Kit (RAVHW1, RAVHW2, RAVHW3) is to be installed. Clearance for installation should be taken into consideration if this kit is to be used.
Plenum cutout
321⁄4” H
x 20” W
duct
5” min.
Exterior/Outside
5” min.
Door/access panel
A
B
A Minimum recommended access door width: 30 B Minimum recommended access door height: 50
8”min. for drain access
Secure platform to the floor
1
Platform: 23 Min. load capacity: 175 lbs.
4 x 231⁄4” square
15
Platform
Bottom of case approx. 2” above bottom of plenum
Bottom of case approx. 2” above bottom of plenum
Outside wall
Wall plenum
Field supplied outer flashing
Page 16
Installation Instructions
UTILITY CLOSET CONNECTION LOCATIONS
IMPORTANT: Plan and locate plenum, wall plug, drains and
thermostat carefully to avoid interference. Hard-to-reach locations will make installation and service difficult!
Use rigid duct for
90° bends and tees
G
Flex duct may be used
for transitions only
Outside wall
230/208 VAC
A
C
B
C
wall receptacle
or
conduit for direct connection
F
A Thermostat cable: 91⁄2” long B Power cord: 60” long C Case width and depth: 231⁄8” D Case height: 31” E Condensate drains: 3/4” connector
• Primary Drain – Centerline of cutout is approximately 51⁄4” from left case wall and 81⁄2” from back case wall.
• Secondary Drain – Centerline of cutout is approximately 61⁄2” from left case wall and 51⁄4” from back case wall.
F Typical wall plug: 6”–12” above case G Room air sensor kit: 10’ long
Reference Dimensions
E
D
Platform
16
Page 17
Installation Instructions
RETURN AIR GRILLE INSTALLATION OPTIONS
The room return air grille may be installed toward the front or either side of the unit. Improper return air arrangements will cause performance problems.
There are three indoor return air grille installation options. Choose the option that best suits your installation requirements. Follow the Installation Instructions provided with the return air grille accessory for installation details.
NOTE: Use only one filter in the installation. The filter may be installed on the unit or in the access panel/door.
Outside wall
RAVRG1 – Access panel with
return air grille
Unit-mounted filter with a field-supplied return
air grille and access door/panel
Filter
Filter
Option 1
RAVRG2 – Return air grille
Filter
Option 3
Option 2
17
Page 18
Installation Instructions
WALL PLENUM AND ARCHITECTURAL LOUVER INSTALLATION
• Install the appropriate wall plenum through the exterior wall in accordance with the Installation Instructions provided with the plenum.
IMPORTANT: The wall plenum is not designed to carry structural loads.
Proper wall header construction is required. The plenum requires proper flashing, shim and caulk for a weather resistant installation.
Proper header for structural support. Apply proper caulking and flashing.
Properly square and level plenum.
Architectural
Louver—RAVAL1
Exterior/Outside Wall
Wall Plenum
RAVWP6 – 6D x 193⁄4W x 32H
RAVWP8 – 8 RAVWP12 – 12 RAVWP15 – 15
BUILD AND INSTALL THE ZONELINE
1
D x 19
D x 19D x 19
3
4W x 32H
3
4W x 32H
3
4W x 32H
BASE PLATFORM
1. Construct a 231⁄4” min. x 231⁄4” min. square platform with legs to raise the platform a minimum of 8”. NOTE: The platform must have a load-bearing capacity of 175 lbs. minimum.
Left side of platform
231⁄4 min.
8”min.
for
drain access
NOTE: Specific cutout size for drain connections needs to be determined by the installer for the given installation situation.
231⁄4 min.
61⁄2
51⁄4
Back of platform
Cutout for drain
51⁄4
connection(s) (see NOTE below)
81⁄2
18
Case
2. Make drain hole cutout(s):
• Primary Drain – Centerline of drain is approximately 51⁄4” from left platform edge and 81⁄2” from back platform edge.
• Secondary Drain – Centerline of drain is approximately 61⁄2” from left platform edge and 51⁄4” from back platform edge.
3. Place the platform in the utility closet
with the following clearance between it and the interior surface of the walls/door/panel:
• 4” min. from front of the case – Unit to be installed through FRONT of case
• 5” min. from front of the case – Unit to be installed through SIDE of case
• 3” min. from two sides of the case (5” for side installation).
4. Align the platform with the opening of
the wall plenum and secure to the floor using appropriate brackets and bolts.
Page 19
Installation Instructions
2
INSTALL THE DRAIN(S)
An external or an internal drain must be attached
to the primary drain connector. A secondary drain is supplied if required by state and local codes. Refer to the local codes for proper installation of the drains. If the secondary drain is not used, seal its drain port with a 3/4” MNPT plug.
External Drain
Attach a 90° PVC elbow to the unit’s female 3/4 NPT
drain connector. Use the other end of the elbow to run a 3/4 Sch. 40 PVC pipe through the knockout holes of
both the wall plenum and the architectural louver to the outside. Seal the gap between the plenum hole and PVC tube. See the Installation Instructions in the RAVAL1.
Inside wall
Side View
Female drain
3
fitting
4
PVC
90° Elbow
PVC (External drain)
Internal Drain
Attach PVC to the unit’s female 3/4 NPT drain
connector. See the Installation Instructions in the RAVAL1. Local codes may apply.
Inside wall
Side View
DUCTWORK
3
Prepare the closet ductwork for later connection
to the case. The total flow rate (CFM) and external static pressure
(ESP) available can be estimated from the chart below. Use these charts to select your fan speed setting. The
collar on top of the case accepts standard 10” duct.
Pull all duct tight. Extra duct slack can greatly increase
static pressure.
NOTICE: Flex duct can collapse and cause
airflow restrictions. Do not use flex duct for 90° bends or unsupported runs of 5 ft. or more.
Airflow – CFM @ 230 Volts and @ 265 Volts
Indoor Fan CFM
DUCT SELECT SWITCH
UP DOWN
High
ESP
(in. water)
0.0
0.1
0.2
0.3
AZ85(H/E)09AZ85(H/E)12AZ85(H/E)18
0.4
0.0
0.1
0.2
0.3
0.4
0.0
0.1
0.2
0.3
0.4
To correct for 208 volts: 0.91
Medium
CFM
520 500 480 440 400 590 570 550 480 410 600 585 570 510 450
CFM
460 415 370 265 160 500 465 430 345 260 520 485 450 375 300
Medium
CFM
460 415 370 265 160 500 465 430 345 260 520 485 450 375 300
Low CFM
360 290 220
-
­380 325 270
-
­400 340 280
-
-
Your airflow should be balanced based on many factors, such as available ESP, room CFM, and ductwork. Consult an HVAC engineer for proper applications. External static pressure (ESP) can be measured with a manometer or pitot tube. Once this ESP is established, you can calculate the CFM using the above chart.
Female drain
3
fitting
4
PVC (Internal drain)
CFM Recommendations
9,000 BTU 12,000 BTU 18,000 BTU
390 415 440 440 465 490 435 485 535
• = Recommended Mid Range
Higher CFMs tend to increase Sensible capacity, enhance room circulation and increase duct noise, while lower CFMs tend to increase Latent capacity and reduce noise.
19
Page 20
Installation Instructions
4
INSTALL AND CONNECT THE CASE
1. Remove the front case panel and pull the unit out of the case. Place the empty case onto the platform in the closet with the outdoor side facing the wall plenum opening. Align the case with plenum opening and attach with six field-supplied sheet metal screws (corrosion-resistant screws recommended).
2. Adjust all four leveling legs until the case is level.
Inside wall
Rigid ductwork
Air discharge outlet
Leveling legs
INSTALL AND GROUND
5a
THE UNIT TO THE CASE
UNIT INSTALLED THROUGH FRONT OF CASE
1. Slide the back of the unit into the case. Push the unit all of the way into the case until it stops.
NOTE: Either of the case sides may be removed
to enable the unit to be slid into the case.
2. Ground the unit to the case by installing the front case-to-unit hex-bolt and discard the two case-to-unit side screw.
Side screw
Side screw
Hex bolt
3. Using field-supplied screws, bolt the case to the platform.
4. Connect the internal or external drain(s) as necessary.
Secondary 3⁄4 drain option. If not used, seal with a MNPT plug
Primary female drain fitting
NOTE: Piping is not supplied with the unit. Obtain locally.
3
Bolt case
to platform
4
External drain
OR
Internal drain(s)
INSTALL AND GROUND
5b
THE UNIT TO THE CASE
UNIT INSTALLED THROUGH SIDE OF CASE
1. Slide the side of the unit into the case. Push the unit all of the way into the case until it stops.
NOTE: Either of the case sides may be removed
to enable the unit to be slid into the case.
2. Attach the case side panel to the main case.
3. Ground the unit to the case by installing the front unit-to-case hex-bolt and discard the two case-to­unit side screw.
Side screw
Side screw (may be installed on either side)
Hex bolt
20
Page 21
Installation Instructions
MAKE UNIT ELECTRICAL
6
CONNECTIONS
1. Connect the thermostat wires to the unit and set the dip switches to the appropriate settings.
NOTE: See the Controls–Terminal Connections
and Controls–Dip Switches sections of this manual and the manual with the separate thermostat for proper connections and settings.
Thermostat
Maximum Wiring
Length for Thermostat Connection to the Unit
66 ft. for AWG 18 60 ft. for AWG 20 40 ft. for AWG 24 AWG – American Wire Gauge
CONNECT THE TOP DUCT
7
1. Install the duct onto the air discharge outlet.
Inside wall
Rigid ductwork
Flexible or rigid ductwork
Air discharge outlet
Unit Connections
2. Make power connections to the unit.
NOTE: See the ELECTRICAL REQUIREMENTS and
DIRECT CONNECT APPLICATIONS sections,
as appropriate, of this manual for proper connections.
3. Replace the case front panel by replacing the four front screws and the two top screws.
2. Secure the top duct to the unit by turning the four case top duct adjusting screws until they are tight. Use a field supplied clamp to lock the top duct to the case.
Top duct
Clamp
Case top duct adjusting screws
21
Page 22
Installation Instructions
FINAL CHECK
8
Review this Checklist before restoring power.
• Correct line voltage?
• Single circuit only?
• HVACR type breaker/fuse?
• Ductwork connected?
• Case and unit level?
• Wall plenum caulked? Level? Flashing?
• Drain connected?
• Wall thermostat wired correctly?
• Unit wired correctly?
• Hydronic plumbing connections (if applicable)
• Hydronic wiring connections (if applicable)
CONNECT POWER
9
1. If all the above items are correct, turn the power on at the main service panel.
2. Turn the unit power switch, on the front of the unit, to ON by pressing the top of the switch in.
SERVICING
WARNING:Risk of Electric Shock,
can cause injury or death.
switch power off at the service panel and lock the area to prevent power from being switched on accidentally. When the area cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
NOTE: We strongly recommend that any servicing
be performed by a qualified individual.
For ease of service, the unit can be removed
from the case:
1. Remove the front case panel.
2. Unplug the power cord and disconnect the wall thermostat connections.
3. Raise the top duct by turning all four case top duct adjusting screws counterclockwise.
4. Remove the front and/or side case-to-unit grounding screw, if present.
5. Slide the unit out of the case.
Before servicing,
22
Page 23
Before You Call For Service… GEAppliances.com
Troubleshooting Tips
Problem Possible Causes What To Do
Zoneline does The unit is unplugged. • Make sure the Zoneline plug is pushed completely not start into the outlet.
The fuse is blown/circuit • Check the house fuse/circuit breaker box and replace breaker is tripped. the fuse or reset the breaker.
The unit is waiting for • This is normal. The Zoneline will start again after it resets. the compressor overload protector to reset.
Power failure. • There is a protective time delay (up to 3 minutes) to
prevent tripping of the compressor overload. For this reason, the unit may not start normal heating or cooling for 3 minutes after it is turned back on.
Zoneline does not cool Indoor airflow is restricted. • Make sure there are no curtains, blinds or furniture or heat as it should blocking the air discharge grille or the return air grille.
Outdoor airflow is • Make sure the architectural louver is not restricted. restricted or recirculated. This can cause the unit to cycle off due to the compressor
overload.
• Outdoor grille must have a minimum of 65% free area. Non-GE grilles may be too restrictive for proper performance. Consult your salesperson for assistance.
The air filter is dirty. • Change the filter at least every 30 days.
See the Care and Cleaning–Air Filters section.
The room may have • When the Zoneline is first turned on you need to been hot or cold. allow time for the room to cool down or warm up.
Outdoor air is • Set the vent control to the CLOSE position. entering the room.
Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support
Burning odor Dust is on the surface • This can cause a “burning” odor at the beginning of at the start of the heating element. the heating operation. This odor should quickly fade. of heating operation
The air is not always The heat pump is not • This is normal. The heat pump will produce warm air cool or hot during producing hot air. but not as hot as air produced when the higher-cost operation electric heat is used.
The fan switch may be • This causes the fan to blow room temperature air set at continuous fan. even when the compressor or heater cycles off.
The continuous air movement provides better overall temperature control.
The air does not feel The heat pump alone • Use the Electric Heat Option. This turns off the heat warm enough during produces air that feels pump and warms with electric heat only. heating operation cooler than desired. NOTE: Use of this option will result in increased energy
consumption.
23
Page 24
Things that are normal.
Normal Operating Sounds
“CLICK”
You may hear a pinging noise caused by water being picked up and thrown against the condenser on rainy days or when the humidity is high. This design feature helps remove moisture and improve efficiency.
You may hear relays click when the controls cycle on and off or are adjusted to change the room temperature.
Water will collect in the base pan during high humidity or on rainy days. The water may overflow and drip from the outdoor side of the unit.
The indoor fan runs continuously when the unit is operating in the cooling mode, unless the fan switch behind the case front panel is set at fan cycle (up). This will cause the fan to cycle on and off with the compressor. You may also hear a fan noise stop and start.
3-Minute
Delay
SILENCE
COMPRESSOR
PROTECTION
You may notice a few minutes delay in starting if you try to restart the Zoneline too soon after turning it off or if you adjust the thermostat right after the compressor has shut off. This is due to a built-in restart protector for the compressor that causes a 3-minute delay.
During the defrost cycle, both indoor and outdoor fans stop and the compressor will operate in the cooling mode to remove frost from the outdoor coil. After defrost, the unit will restart in electric heat to quickly warm the room to the desired comfort level.
To protect the compressor and prevent short cycling, the unit is designed to run for a minimum of 3 minutes after the compressor starts at any thermostat setting.
Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions
24
Page 25
Notes. GEAppliances.com
Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support
25
Page 26
Notes.
Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions
26
Page 27
Vertical Zoneline Warranty.
Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Tips Consumer Support
All warranty service provided by our Factory Service Centers, or an
®
authorized Customer Care
technician. To schedule service, on-line, visit us at GEAppliances.com, or call 800.GE.CARES (800.432.2737). For service in Canada, contact Gordon Williams Corp. at 1.888.209.0999. Please have serial number and model number availa ble when calling for service.
Staple your receipt here.
Proof of the original purchase
date is needed to obtain service
under the warranty.
For The Period Of: GE Will Replace:
One Year Any part of the Zoneline which fails due to a defect in materials or workmanship. During this
From the date of the limited one-year warranty, GE will also provide, free of charge, all labor and related service original purchase to replace the defective part.
Five Years Any part of the sealed refrigerating system (the compressor, condenser, evaporator
From the date of the and all connecting tubing) which fails due to a defect in materials or workmanship. original purchase During this four-year limited additional warranty, GE will also provide, free of charge,
all labor and related service to replace the defective part.
Five Years For the second through the fifth year from the date of original purchase, GE will replace
From the date of the certain parts that fail due to a defect in materials or workmanship. Parts covered are fan original purchase motors, switches, thermostats, electric resistance heater, electric resistance heater protectors,
compressor overload, solenoids, circuit boards, auxiliary controls, thermistors, frost controls, ICR pump, capacitors, varistors and indoor blower bearing. During this four-year limited
additional warranty, you will be responsible for any labor or on-site service costs.
What GE Will Not Cover:
n Service trips to your site to teach you how to use
the product.
n Improper installation, delivery or maintenance.
n If you have an installation problem, or if the air
conditioner is of improper cooling or heating capacity for the intended use, contact your dealer or installer. You are responsible for providing adequate electrical connecting facilities.
n In commercial locations, labor necessary to move
the unit to a location where it is accessible for service by an individual technician.
n Failure or damage resulting from corrosion due
to installation in an environment containing corrosive chemicals.
n Replacement of fuses or resetting of circuit breakers. n Filters.
n Failure of the product resulting from modifications
to the product or due to unreasonable use including failure to provide reasonable and necessary maintenance.
n Failure or damage resulting from corrosion due
to installation in a coastal environment, except for models treated with special factory-applied anti-corrosion protection as designated in the model number.
n Damage to product caused by improper power supply
voltage, accident, fire, floods or acts of God.
n Incidental or consequential damage caused
by possible defects with this air conditioner.
n Damage caused after delivery. n Product not accessible to provide required service.
EXCLUSION OF IMPLIED WARRANTIES—Your sole and exclusive remedy is product repair as provided in this Limited Warranty.
Any implied warranties, including the implied warranties of merchantability or fitness for a particular purpose, are limited to one year or the shortest period allowed by law.
This warranty is extended to the original purchaser and any succeeding owner for products purchased for use within the USA and Canada. If the product is located in an area where service by a GE Authorized Servicer is not available, you may be responsible for a trip charge or you may be required to bring the product to an Authorized GE Service location for service. In Alaska, the warranty excludes the cost of shipping or service calls to your site.
Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province. To know what your legal rights are, consult your local, state or provincial consumer affairs office or your state’s Attorney General.
Warrantor: General Electric Company. Louisville, KY 40225
27
Page 28
Consumer Support.
GE Appliances Website
Have a question or need assistance with your appliance? Try the GE Appliances Website 24 hours a day, any day of the year! For greater convenience and faster service, you can now download Owner’s Manuals, order parts or even schedule service on-line.
GEAppliances.com
Schedule Service GEAppliances.com
Expert GE repair service is only one step away from your door. Get on-line and schedule your service at your convenience any day of the year! Or call 800.GE.CARES (800.432.2737) during normal business hours. For service in Canada, contact Gordon Williams Corp. at 1.888.209.0999.
Real Life Design Studio GEAppliances.com
GE supports the Universal Design concept—products, services and environments that can be used by people of all ages, sizes and capabilities. We recognize the need to design for a wide range of physical and mental abilities and impairments. For details of GE’s Universal Design applications, including kitchen design ideas for people with disabilities, check out our Website today. For the hearing impaired, please call 800.TDD. GEAC (800.833.4322).
Parts and Accessories GEAppliances.com
Individuals qualified to service their own appliances can have parts or accessories sent directly to their homes (VISA, MasterCard and Discover cards are accepted). Order on-line today, 24 hours every day or by phone at 800.626.2002 during normal business hours.
Instructions contained in this manual cover procedures to be performed by any user. Other servicing
generally should be referred to qualified service personnel. Caution must be exercised, since improper
servicing may cause unsafe operation.
Contact Us GEAppliances.com
If you are not satisfied with the service you receive from GE, contact us on our Website with all the details including your phone number, or write to: General Manager, Customer Relations
GE Appliances, Appliance Park Louisville, KY 40225
Register Your Appliance GEAppliances.com
Register your new appliance on-line—at your convenience! Timely product registration will allow for enhanced communication and prompt service under the terms of your warranty, should the need arise. You may also mail in the pre-printed registration card included in the packing material.
Loading...