For a Spanish version of this manual, visit our
Website at GEAppliances.com.
Para consultar una version en español deeste
manual de instrucciones, visite nuestrositio
de internet GEAppliances.com.
Française
For a French version of this manual, visit our
Website at GEAppliances.com.
Pour une version française de ce manuel
d’utilisation, veuillez visiter notre site web à
l’adresse GEAppliances.com.
Write the model and serial numbers
here:
Model # ________________________
Serial # _________________________
You can find them on a label on the front
case panel.
Air Conditioners
Printed in China
TINSEA612JBRZ 49-7639 01-10 GE
Page 2
IMPORTANT SAFETY INFORMATION.
READ ALL INSTRUCTIONS BEFORE USING.
WARNING!
Risk of electric shock. Can cause injury or death. For your safety, the information in this manual
must be followed to minimize the risk of fire, electric shock or personal injury.
SAFETY PRECAUTIONS
n This Zoneline must be properly installed
in accordance with the Installation
Instructions before it is used.
See the Installation Instructions
in the back of this manual.
n Replace immediately all electric service
cords that have become frayed or
otherwise damaged. A damaged power
supply cord must be replaced with
a new power supply cord obtained
from the manufacturer and not repaired.
Do not use a cord that shows cracks
or abrasion damage along its length
or at either the plug or connector end.
n Product must be operated with
the electrical plug supplied with the
product. Do not replace the electrical
plug supplied with the product.
n If the receptacle does not match the plug,
the receptacle must be changed out by
a qualified electrician.
n Unplug or disconnect the Zoneline
at the fuse box or circuit breaker before
making any repairs.
NOTE: We strongly recommend that
any servicing be performed by a qualified
individual.
n All air conditioners contain refrigerants,
which under federal law must be
removed prior to product disposal.
If you are getting rid of an old product
with refrigerants, check with the
company handling disposal about
what to do.
nThese R410A Air Conditioner Systems
require contractors and technicians to
use tools, equipment and safety standards
approved for use with this refrigerant.
DO NOT use equipment certified for R22
refrigerant only.
READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY.
SAVE THESE INSTRUCTIONS
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
2
Page 3
Controls–dip switches. GEAppliances.com
Controls–Dip Switches
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
The dip switch controls are located behind
the front case panel, through an opening
on the front of the unit.
To access the dip switches, remove the front
case panel by removing the filter, taking out
the four front screws, the upper two screws from
the top of the panel and the shipping screws on
each side, if present. (Discard the four side shipping
screws, if present).
Side
shipping
screw
Side
shipping
screw
Dip
Switches
NOTE: The owner is responsible for setting
the appropriate dip switches and connecting
terminals.
No Function (Reserved for future use)
DUCT (Blower Fan)
OCCUPIED (Occupancy Sensor)
ALL I2R (All Electric Heat)
3
Page 4
Controls–dip switches.
Freeze Sentinel (Requires room air sensor kit–RAVRMS)
When this switch is enabled (UP), it turns OFF
the freeze sentinel protection feature. With the
switch disabled (DOWN), the freeze sentinel is
activated which automatically provides heat
without user interface. This helps to prevent
plumbing damage by turning the heater
and fans ON at 41° F and OFF at 46° F.
Constant ON Fan
When this switch is enabled (UP), it allows the fan
to run continuously.
Occupancy Sensor (Field Supplied)
FREEZE S (Freeze Sentinel)
CONST FAN (Constant
ON Fan)
When this switch is enabled (UP), it allows the unit
to utilize an infrared motion sensor and a door
switch for occupancy detection. This feature
combined with field devices automatically cycles
the unit between normal operation and a preset
energy management operation.
Duct
The duct select function allows the indoor
fan to be operated at two variable fan speeds.
When this switch is enabled (UP), the unit
automatically selects either high or middle fan
speed (for longer ductwork applications). When
set in the down position, the unit is automatically
operated in either the middle or low fan speed
(for shorter ductwork applications).
OCCUPIED
(Occupancy Sensor)
DUCT
(Blower Fan)
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
4
Page 5
Temperature Limiting (Requires room air sensor kit–RAVRMS)
GEAppliances.com
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
Temperature limiting can reduce energy costs
by limiting the lowest temperature that can be
set for cooling and the highest temperature that
can be set for heating. Temperature limiting is
controlled by switches 1–6 on the top block
The terminal connections are located behind
the front case panel through an opening
on the front of the unit.
To access the terminal connections, remove
the front panel by removing the filter, taking out
the four front screws, the upper two screws from
the top of the panel and the shipping screws on
each side, if present. (Discard the four side shipping
screws, if present.)
Insert the building hook-up wires into the bottom
of the terminals and tighten screws securely
to make the desired connections.
Route the wires from the terminal connections
through the unit wire guides and out through
the case wire guide.
NOTE: The owner is responsible for setting
the appropriate dip switches and connecting
terminals.
CAUTION:
Improper CDC wiring may damage the Zoneline
electronics or cause erratic Zoneline operation.
No common busing is permitted. A separate wire
pair must be run from each separate controlling
switch to each individual Zoneline.
Route wires
through
wire guides
Terminal
connections
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
6
24VAC
FAN LO
FAN HI
COMP
REV VA L
AUX HEAT
Room Air Sensor
Motion Sensor
Door Sensor
Central Desk Control
Room Air Sensor (Requires room air sensor kit – RAVRMS)
When connected, the room air sensor will allow
utilization of the temperature limiting and freeze
sentinel features.
NOTE: If GE thermostat RAK148D1, RAK148P1
or RAK164D1, RAK164P1 is used with the unit,
the room sensor kit is not needed for temperature
limiting since this feature is incorporated in the
NOTE: R, W, C terminal connections will
also be connected to the remote thermostat
if applicable.
COMMON
Common–Ground
White–Heater
Yellow–Compressor
Black–Reversing Valve
Green–High Speed Fan
Green–Low Speed Fan
Red–24V AC only
24VAC
FAN LO
FAN HI
24VAC
FAN LO
FAN HI
Hydronic Heating
COMP
REV VAL
REV VAL
COMP
AUX HEAT
AUX HEAT
COMMON
COMMON
Page 7
Motion Sensor (Obtained locally)
The Occupancy Sensor dip switch must be in
the up position to use this feature.
When connected, the wall mounted motion sensor
will detect motion in the room and automatically
cycle the unit between normal operation and
energy management operation.
The door and motion sensors work together
to automatically cycle the unit between normal
operation and energy management operation.
Door Sensor (Obtained locally)
The Occupancy Sensor dip switch must be
in the up position to use this feature.
When connected, the door sensor will detect
when the door in the room is opened or closed.
This feature must be used in conjunction with
the motion sensor.
The door and motion sensors work together
to automatically cycle the unit between normal
and energy management operations.
Motion
Sensor
24VAC
24VAC
Door Sensor
GEAppliances.com
FAN HI
FAN HI
COMP
REV VAL
AUX HEAT
COMP
REV VAL
AUX HEAT
FAN LO
FAN LO
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
COMMON
COMMON
Central Desk Control
When connected, the unit lock-out is released
and it can be turned ON or OFF with a switch
located at the Central Desk Control. A separate
wire pair must be run from each separate
controlling switch to each individual Zoneline. A
24V AC circuit powers the CDC system. No external
power is required.
Remote Thermostat
The unit will be controlled by a remote
thermostat.
IMPORTANT:
The Zoneline thermostat connections
provide 24V AC only.
If using a digital/electronic wall thermostat,
you must set it to the 24V AC setting. See the
Installation Instructions for the wall thermostat.
NOTICE:
Damage to a wall thermostat or to the
Zoneline electronics can result from improper
connections. Exercise extra attention when
connecting blue and black wires. No line
voltage connections should be made to any circuit
in the thermostat. Isolate all wires in building from
line voltage.
Red–24V AC only
Green–Low Speed Fan
Green–High Speed Fan
Black–Reversing Valve
Yellow–Compressor
White–Heater
Common–Ground
24VAC
FAN LO
FAN HI
COMP
REV VAL
Central Desk Control
24VAC
FAN LO
FAN HI
COMP
REV VAL
AUX HEAT
AUX HEAT
COMMON
COMMON
7
Page 8
Other features of your Zoneline.
On/Off Switch
The unit on/off switch is located on the front
of the Zoneline.
To turn on the unit, press the top of the switch in.
To turn off the unit, press the bottom
of the switch in.
NOTE: The on/off switch does not remove power
from the unit.
Ventilation Control
The ventilation control lever is located on the left
side of the Zoneline unit, behind the front case
panel.
To access the ventilation control lever, remove
the front panel by removing the filter, taking out
the four front screws, the upper two screws from
the top of the panel and the shipping screws on
each side, if present. (Discard the four side shipping
screws, if present).
When the lever is in the CLOSE position, only the air
inside the room is circulated and filtered.
When the lever is in the OPEN position, some
outdoor air will be drawn into the room. This
will reduce the heating or cooling efficiency.
To close the vent, push the vent lever handle
down, pull it forward and lock it up in place.
To open the vent, push the vent lever handle
down, push it back and lock it up in place.
ON/OFF
switch
Open
Vent control (push
lever down and
pull forward or
back to operate)
Energy Tip: Keep the vent control in the CLOSE
position. The room air will be filtered and circulated.
NOTE: Ventilation openings are not intended to be
the source of make-up air for building ventilation
systems due to the additional heating and cooling
loads generated.
Close
About Heat Pumps (on some models)
Heat pumps can reduce operating costs by
exchanging heat from the outside air—even
when the outside temperature is below freezing—
and releasing that heat indoors.
To get the best economic benefit from your heat
pump, don’t change the room thermostat setting
very often. Raising the heat setting 2–3 degrees
will cause the Zoneline to use its electric heating
elements in order to reach the new temperature
setting quickly.
Do Not Operate the Air Conditioner (cool mode) in Freezing Outdoor Conditions
Air conditioners are not designed for use when
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
freezing outdoor conditions exist. They must not be
used in freezing outdoor conditions.
8
There is a three minute minimum compressor run
time at any setting to prevent short cycling.
The indoor fan motor starts before the compressor
and stops after the compressor cycles off.
The electric heating elements use much
more electricity than heat pumps and cost
more to operate.
Page 9
Care and cleaning. GEAppliances.com
Turn off the Zoneline and disconnect the power supply before cleaning.
Indoor/Outdoor Coils
The exhaust coils on the Zoneline should be
checked regularly. If they are clogged with dirt
or soot, they may be professionally steam cleaned
by your GE service center. You will need to remove
the unit from the case to inspect the coils because
the dirt build-up occurs on the exhaust side.
Outdoor coils
Have the coils cleaned regularly.
Drain
Clean the drain system regularly to prevent
clogging.
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
Base Pan
In some installations, dirt or other debris may
be blown into the unit from the outside and settle
in the base pan (the bottom of the unit).
In some areas of the United States, a “gel-like”
substance may be present in the base pan.
Check it periodically and clean, if necessary.
Air Filters
To maintain optimum performance, change the filter at least every 30 days.
The most important thing you can do to maintain
the Zoneline is to change the filter at least every
30 days. Dirty filters reduce cooling, heating
and air flow.
Changing the filter will: Decrease cost of
operation, save energy, prevent clogged heat
exchanger coils and reduce the risk of premature
component failure.
To remove
and replace
the filter:
NOTICE: Do not operate
the Zoneline without the filter in place. If a filter
becomes torn or damaged, it should be replaced
immediately.
Operating without the filter in place or with
a damaged filter will allow dirt and dust to reach
the indoor coil and reduce the cooling, heating,
airflow and efficiency of the unit.
Remove filter
Unit-mounted filter
Filter
Replacement filters should be purchased
from your local retailer where air conditioner
and furnace accessories are sold.
Filter size required is 20” x 20” x 1".
Filter
Return air grille
Access-panel with
return air grille
9
Page 10
Installation Zoneline Air
Instructions Conditioners
Questions? Visit our Website at: GEAppliances.com or call 800.GE.CARES (800.432.2737).
BEFORE YOU BEGIN
Read these instructions completely and carefully.
•
IMPORTANT
for local inspector’s use.
•
IMPORTANT
codes and ordinances.
• Note to Installer – Be sure to leave these
instructions with the owner.
• Note to Owner – Keep these instructions
for future reference.
• Proper installation is the responsibility of the installer.
• Product failure due to improper installation is not
covered under the Warranty.
• You MUST use all supplied parts and use proper
installation procedures as described in these
instructions when installing this air conditioner.
TOOLS YOU WILL NEED
Phillips screwdriver
Saw
Save these instructions
–
Observe all governing
–
Adjustable wrench
Hammer
IMPORTANT ELECTRICAL
SAFETY–READ CAREFULLY
WARNING:
• All electrical connections and wiring MUST
be installed by a qualified electrician.
• Follow the National Electrical Code (NEC)
and/or local codes and ordinances.
• For personal safety, this Zoneline unit and case must
be properly grounded.
• Protective devices (fuses or circuit breakers)
acceptable for Zoneline installations are specified on
the nameplate of each unit.
• Do not use an extension cord with this unit.
• Aluminum building wiring may present special
problems—consult a qualified electrician.
• When the unit is not running there is still voltage to
the electrical controls.
• Disconnect the power to the unit before
servicing by:
1. Removing the power cord (if it has one) from
the wall receptacle.
OR
2. Removing the branch circuit fuses or turning
the circuit breakers off at the panel.
RISK OF ELECTRIC SHOCK.
Tape measure
WARNING:
Can cause injury or death. This appliance must be
properly grounded. Where a 2-prong wall outlet is
encountered, it is your responsibility and obligation
to have it replaced with a properly grounded 3-prong
outlet.
RISK OF ELECTRIC SHOCK.
10
Page 11
Installation Instructions
ELECTRICAL REQUIREMENTS
• Use ONLY the wiring size recommended for single
outlet branch circuit.
• Proper current protection is the responsibility
of the owner.
Recommended branch circuit wire sizes*
Nameplate maximum circuit AWG Wire breaker size size**
15A 14
20A 12
30A 10
AWG – American Wire Gauge
* Single circuit breaker from main box
** Based on copper wire, single insulated conductor at 60° C
NOTE: Use copper conductors only.
230/208 VOLT
ELECTRICAL SUPPLY
A power supply kit must be used to supply power
to the Zoneline unit. The appropriate kit is determined
by the voltage, the means of electrical connection
and the amperage of the branch circuit. See the
POWER CONNECTION CHART on page 13 to select the
appropriate kit.
FOR 230/208 VOLT CORD
CONNECTIONS ONLY
1. Remove the front panel by taking out the four
front screws, the upper two screws from the top
of the panel and the shipping screws on each side,
if present. (Discard the four side shipping screws,
if present.)
Side
shipping
screw
Side
shipping
screw
2. Remove the junction box cover and the junction box
and discard.
Remove
junction box
and cover
Power supply kit
All wiring, including installation of the receptacle,
must be in accordance with the NEC and local codes,
ordinances and regulations.
Tandem
15 Amp
230/208 volt receptacle configuration
Perpendicular
20 Amp
3. Connect the power cord, with a loop, through
the strain relief.
Large Tandem
30 Amp
Strain relief
IMPORTANT:
Power cord must
have a loop.
11
Page 12
Installation Instructions
DIRECT CONNECT APPLICATIONS
FOR 230/208 VOLT DIRECT CONNECT
APPLICATIONS ONLY
Direct connection to branch circuit wiring inside
the provided junction box must be made by connecting
as follows in steps 1–3 below.
Connector
REMOVE JUNCTION BOX COVER
1
• Remove the junction box cover by taking out the front
two screws.
FOR 265 VOLT DIRECT CONNECT
APPLICATIONS ONLY
IMPORTANT: Connection of a 265V AC product
to a branch circuit MUST be done by direct connection
in accordance with the National Electrical Code. Plugging
this unit into a building mounted exposed receptacle
is not permitted by code.
These models must be installed using the appropriate
GE power supply kit for the branch circuit amperage
and the electrical resistance heater wattage desired.
See the POWER CONNECTION CHART on page 13
to select the appropriate kit.
It is the responsibility of the installer to ensure
the connection of components is done in accordance
with electrical codes.
Direct connection to branch circuit wiring inside
the provided junction box must be made by connecting
as follows in steps 1–3 below.
ATTACH CONDUIT
2
• Use the round knockout hole at the top
of the junction box to install conduit coming
from the branch circuit. Install and clamp the conduit
through the conduit clamp and bring wire leads into
the junction box. Leave 8" of wire free from the end
of the conduit.
Junction box
Junction box cover
12
Conduit
Conduit
clamp
Page 13
Installation Instructions
DIRECT CONNECT APPLICATIONS
MAKE WIRE LEAD CONNECTIONS INSIDE THE JUNCTION BOX
3
1. Make all wire connections by using appropriate UL-listed electrical connectors and techniques.
2. Select the applicable wiring situation and follow the instructions accordingly:
• 1-Phase 220-240 VAC
When connecting the Zoneline to a single-phase circuit
for 230V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit L1 and L2 leads.
(The white lead of the power supply kit should be
identified by the installer using electrical tape with some
color other than green or white.) Connect the green lead
of the power supply kit to the power supply and branch
circuit ground.
• 3-Phase 208 VAC
When connecting the Zoneline to a three-phase circuit
for 208V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit L1 and L2 leads.
(The white lead of the power supply kit should be
identified by the installer using electrical tape with some
color other than green or white.) Connect the green lead
of the power supply kit to the power supply and branch
3. Be sure that all wire leads are inside the junction box and not
4. Plug the 9-pin connector into the 9-pin receptacle in the junction box.
5. Replace the junction box cover by replacing the two screws
circuit ground.
pinched between the box and the unit. The green insulated
ground wire from the Zoneline MUST be connected to the branch
circuit ground wire.
removed earlier.
• 3-Phase 208 VAC with “Crazy Leg”
When connecting the Zoneline to a three-phase circuit
with “Crazy Leg” for 208V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit Neutral and L1
leads. (The white lead of the power supply kit should
be connected to neutral.) Connect the green lead of
the power supply kit to the power supply and branch
circuit ground.
• 3-Phase 253-277 VAC
When connecting the Zoneline to a three-phase circuit
for 265V applications:
Connect the white and black leads of the Zoneline
power supply kit to the branch circuit Neutral and L1
leads. (The white lead of the power supply kit should
be connected to neutral.) Connect the green lead of
the power supply kit to the power supply and branch
circuit ground.
Conduit
Make wire lead
connections
POWER CONNECTION CHART
Power Cord Connections
230/208 Volt Wall Plug Heater Wattage
Power Supply Kits Configuration Circuit Protective Device @ 230/208 Volts
RAK3152 Tandem 15-Amp Time-Delay Fuse or Breaker 2.55/2.09 KW
RAK3202 Perpendicular 20-Amp Time-Delay Fuse or Breaker 3.45/2.82 KW
RAK3302 Large Tandem 30-Amp Time-Delay Fuse or Breaker 5.00/4.10 KW
Direct Connections
230/208 Volt Heater Wattage
Power Supply Kits @ 230/208 Volts Circuit Protective Device
RAK4157 2.55 KW/2.09 KW 15-Amp Time-Delay Fuse or Breaker
RAK4207 3.45 KW/2.82 KW 20-Amp Time-Delay Fuse or Breaker
RAK4307 5.00 KW/4.10 KW 30-Amp Time-Delay Fuse or Breaker
265 Volt Heater Wattage
Power Supply Kits @ 265 Volts Circuit Protective Device
RAK5157 2.55 KW 15-Amp Time-Delay Fuse or Breaker
RAK5207 3.45 KW 20-Amp Time-Delay Fuse or Breaker
RAK5307 5.00 KW 30-Amp Time-Delay Fuse or Breaker
13
Page 14
Installation Instructions
ZONELINE COMPONENTS
Case
REQUIRED ACCESSORIES
(Check the “Essential Elements” label on the unit.)
Zoneline unit
Front Case Panel
Cutout
Dimensions:
20" W x 32
1
⁄4”H
50”
30”
Wall Plenum
RAVWP6 - 6"D x 19
Architectural Louver
RAVAL1
RAVWP8 - 8”D x 19
RAVWP12 - 12”D x 19
RAVWP15 - 15”D x 19
Cutout
Dimensions:
”W x 48”H
28
Access Panel with
Return Air Grille
RAVRG1
OR
22 1⁄2”
22 1⁄2”
Wall Thermostat
Model Type Mechanical Thermostat Electronic Thermostat
Check the thermostat instructions for correct wiring and installation requirements.
3
⁄4”W x 32”H
3
⁄4”W x 32”H
3
⁄4”W x 32”H
3
⁄4”W x 32”H
Cutout
Dimensions:
3
⁄8”W x 203⁄8”H
20
Return Air Grille
RAVRG2
14
Page 15
Installation Instructions
TYPICAL UTILITY CLOSET AND DIMENSIONS
(FOR REFERENCE ONLY)
UNIT INSTALLED THROUGH FRONT OF CASE
Top View
Architectural Louver
1
⁄2”
11
10”
3"
min.
Unit
front
• 4" min. from front of case – Unit
installed through FRONT of case.
• 5" min. from front of case – Unit
installed through SIDE of case.
• 3" min. from two sides of case.
(5” for side install).
Option 1
Access panel with
return air grille
Option 2
Return air grille
10"
duct
4" min.
Door/access panel
Inside wall
3" min.
Rigid
ductwork
Flexible or
rigid duct
Air discharge
outlet
31”
Side View
Unit
Wall plenum
divider
Filter bracket
Drain fittings 3⁄4”
UNIT INSTALLED THROUGH SIDE OF CASE
Top View
Architectural Louver
1
⁄2”
3”
min.
Wall
plenum
11
10”
10”
Unit front
Outside wall
14” min. – Required only if optional
Hydronic Heating Kit (RAVHW1, RAVHW2,
RAVHW3) is to be installed. Clearance
for installation should be taken into
consideration if this kit is to be used.
Plenum
cutout
321⁄4” H
x 20” W
duct
5” min.
Exterior/Outside
5” min.
Door/access panel
A
B
A Minimum recommended access door width: 30”
B Minimum recommended access door height: 50
8”min.
for drain
access
Secure platform
to the floor
1
Platform: 23
Min. load capacity: 175 lbs.
”
⁄4” x 231⁄4” square
15
Platform
Bottom of case approx. 2”
above bottom of plenum
Bottom of case approx. 2”
above bottom of plenum
Outside wall
Wall plenum
Field supplied
outer flashing
Page 16
Installation Instructions
UTILITY CLOSET CONNECTION LOCATIONS
IMPORTANT: Plan and locate plenum, wall plug, drains and
thermostat carefully to avoid interference. Hard-to-reach locations
will make installation and service difficult!
Use rigid duct for
90° bends and tees
G
Flex duct may be used
for transitions only
Outside wall
230/208 VAC
A
C
B
C
wall receptacle
or
conduit
for direct
connection
F
A Thermostat cable: 91⁄2” long
B Power cord: 60” long
C Case width and depth: 231⁄8”
D Case height: 31”
E Condensate drains: 3/4” connector
• Primary Drain – Centerline of cutout is
approximately 51⁄4” from left case wall
and 81⁄2” from back case wall.
• Secondary Drain – Centerline of cutout is
approximately 61⁄2” from left case wall
and 51⁄4” from back case wall.
F Typical wall plug: 6”–12” above case
G Room air sensor kit: 10’ long
Reference Dimensions
E
D
Platform
16
Page 17
Installation Instructions
RETURN AIR GRILLE INSTALLATION OPTIONS
The room return air grille may be installed toward the front or either side of the unit. Improper return air arrangements
will cause performance problems.
There are three indoor return air grille installation options. Choose the option that best suits your installation
requirements. Follow the Installation Instructions provided with the return air grille accessory for installation details.
NOTE: Use only one filter in the installation. The filter may be installed on the unit or in the access panel/door.
Outside wall
RAVRG1 – Access panel with
return air grille
Unit-mounted filter with a field-supplied return
air grille and access door/panel
Filter
Filter
Option 1
RAVRG2 – Return air grille
Filter
Option 3
Option 2
17
Page 18
Installation Instructions
WALL PLENUM AND ARCHITECTURAL LOUVER INSTALLATION
• Install the appropriate wall plenum through the exterior wall in accordance with the Installation Instructions provided
with the plenum.
IMPORTANT: The wall plenum is not designed to carry structural loads.
Proper wall header construction is required. The plenum requires proper flashing,
shim and caulk for a weather resistant installation.
Proper header for
structural support.
Apply proper caulking
and flashing.
Properly square
and level plenum.
Architectural
Louver—RAVAL1
Exterior/Outside Wall
Wall Plenum
RAVWP6 – 6”D x 193⁄4”W x 32”H
RAVWP8 – 8
RAVWP12 – 12
RAVWP15 – 15
BUILD AND INSTALL THE ZONELINE
1
”D x 19
”D x 19
”D x 19
3
⁄4”W x 32”H
3
⁄4”W x 32”H
3
⁄4”W x 32”H
BASE PLATFORM
1. Construct a 231⁄4” min. x 231⁄4” min. square platform with legs to
raise the platform a minimum of 8”.
NOTE: The platform must have a load-bearing capacity of
175 lbs. minimum.
Left side of platform
231⁄4” min.
8”min.
for
drain
access
NOTE: Specific cutout size
for drain connections needs
to be determined by the installer
for the given installation situation.
231⁄4” min.
61⁄2”
51⁄4”
Back of platform
Cutout for drain
51⁄4”
connection(s)
(see NOTE below)
81⁄2”
18
Case
2. Make drain hole cutout(s):
• Primary Drain – Centerline of drain is
approximately 51⁄4” from left platform edge
and 81⁄2” from back platform edge.
• Secondary Drain – Centerline of drain
is approximately 61⁄2” from left platform edge
and 51⁄4” from back platform edge.
3. Place the platform in the utility closet
with the following clearance between it
and the interior surface of the walls/door/panel:
• 4” min. from front of the case –
Unit to be installed through FRONT of case
• 5” min. from front of the case –
Unit to be installed through SIDE of case
• 3” min. from two sides of the case (5” for side
installation).
4. Align the platform with the opening of
the wall plenum and secure to the floor
using appropriate brackets and bolts.
Page 19
Installation Instructions
2
INSTALL THE DRAIN(S)
An external or an internal drain must be attached
to the primary drain connector. A secondary drain
is supplied if required by state and local codes. Refer
to the local codes for proper installation of the drains.
If the secondary drain is not used, seal its drain port
with a 3/4” MNPT plug.
External Drain
Attach a 90° PVC elbow to the unit’s female 3/4” NPT
drain connector. Use the other end of the elbow to run
a 3/4” Sch. 40 PVC pipe through the knockout holes of
both the wall plenum and the architectural louver to the
outside. Seal the gap between the plenum hole and PVC
tube. See the Installation Instructions in the RAVAL1.
Inside wall
Side View
Female drain
3
fitting
⁄4”
PVC
90° Elbow
PVC
(External drain)
Internal Drain
Attach PVC to the unit’s female 3/4” NPT drain
connector. See the Installation Instructions
in the RAVAL1. Local codes may apply.
Inside wall
Side View
DUCTWORK
3
Prepare the closet ductwork for later connection
to the case.
The total flow rate (CFM) and external static pressure
(ESP) available can be estimated from the chart below.
Use these charts to select your fan speed setting. The
collar on top of the case accepts standard 10” duct.
Pull all duct tight. Extra duct slack can greatly increase
static pressure.
NOTICE: Flex duct can collapse and cause
airflow restrictions. Do not use flex duct for 90° bends
or unsupported runs of 5 ft. or more.
Your airflow should be balanced based on many
factors, such as available ESP, room CFM, and ductwork.
Consult an HVAC engineer for proper applications.
External static pressure (ESP) can be measured with a
manometer or pitot tube. Once this ESP is established,
you can calculate the CFM using the above chart.
Female drain
3
fitting
⁄4”
PVC
(Internal drain)
CFM Recommendations
9,000 BTU 12,000 BTU 18,000 BTU
390 415 440 440 465 490 435 485 535
• • •
• = Recommended Mid Range
Higher CFMs tend to increase Sensible capacity,
enhance room circulation and increase duct noise,
while lower CFMs tend to increase Latent capacity
and reduce noise.
19
Page 20
Installation Instructions
4
INSTALL AND CONNECT THE CASE
1. Remove the front case panel and pull
the unit out of the case. Place the empty case onto
the platform in the closet with the outdoor side facing
the wall plenum opening. Align the case with plenum
opening and attach with six field-supplied sheet metal
screws (corrosion-resistant screws recommended).
2. Adjust all four leveling legs until the case is level.
Inside
wall
Rigid
ductwork
Air
discharge
outlet
Leveling legs
INSTALL AND GROUND
5a
THE UNIT TO THE CASE
UNIT INSTALLED THROUGH FRONT OF CASE
1. Slide the back of the unit into the case. Push the unit
all of the way into the case until it stops.
NOTE: Either of the case sides may be removed
to enable the unit to be slid into the case.
2. Ground the unit to the case by installing the front
case-to-unit hex-bolt and discard the two case-to-unit
side screw.
Side screw
Side screw
Hex bolt
3. Using field-supplied screws, bolt the case
to the platform.
4. Connect the internal or external drain(s) as necessary.
Secondary 3⁄4” drain
option. If not used,
seal with a MNPT plug
Primary female
drain fitting
NOTE: Piping is not
supplied with the unit.
Obtain locally.
3
Bolt case
to platform
⁄4”
External
drain
OR
Internal
drain(s)
INSTALL AND GROUND
5b
THE UNIT TO THE CASE
UNIT INSTALLED THROUGH SIDE OF CASE
1. Slide the side of the unit into the case. Push the unit
all of the way into the case until it stops.
NOTE: Either of the case sides may be removed
to enable the unit to be slid into the case.
2. Attach the case side panel to the main case.
3. Ground the unit to the case by installing the front
unit-to-case hex-bolt and discard the two case-tounit side screw.
Side screw
Side screw
(may be
installed on
either side)
Hex bolt
20
Page 21
Installation Instructions
MAKE UNIT ELECTRICAL
6
CONNECTIONS
1. Connect the thermostat wires to the unit and set
the dip switches to the appropriate settings.
NOTE: See the Controls–Terminal Connections
and Controls–Dip Switches sections
of this manual and the manual with
the separate thermostat for proper
connections and settings.
Thermostat
Maximum Wiring
Length for Thermostat
Connection to the Unit
66 ft. for AWG 18
60 ft. for AWG 20
40 ft. for AWG 24
AWG – American Wire Gauge
CONNECT THE TOP DUCT
7
1. Install the duct onto the air discharge outlet.
Inside
wall
Rigid
ductwork
Flexible or rigid
ductwork
Air
discharge
outlet
Unit Connections
2. Make power connections to the unit.
NOTE: See the ELECTRICAL REQUIREMENTS and
DIRECT CONNECT APPLICATIONS sections,
as appropriate, of this manual for proper
connections.
3. Replace the case front panel by replacing the four
front screws and the two top screws.
2. Secure the top duct to the unit by turning the four
case top duct adjusting screws until they are tight.
Use a field supplied clamp to lock the top duct
to the case.
Top duct
Clamp
Case top
duct adjusting
screws
21
Page 22
Installation Instructions
FINAL CHECK
8
Review this Checklist before restoring power.
• Correct line voltage?
• Single circuit only?
• HVACR type breaker/fuse?
• Ductwork connected?
• Case and unit level?
• Wall plenum caulked? Level? Flashing?
• Drain connected?
• Wall thermostat wired correctly?
• Unit wired correctly?
• Hydronic plumbing connections (if applicable)
• Hydronic wiring connections (if applicable)
CONNECT POWER
9
1. If all the above items are correct, turn the power
on at the main service panel.
2. Turn the unit power switch, on the front of the unit,
to ON by pressing the top of the switch in.
SERVICING
WARNING:Risk of Electric Shock,
can cause injury or death.
switch power off at the service panel and lock
the area to prevent power from being switched
on accidentally. When the area cannot be locked,
securely fasten
a prominent warning device, such as a tag,
to the service panel.
NOTE: We strongly recommend that any servicing
be performed by a qualified individual.
For ease of service, the unit can be removed
from the case:
1. Remove the front case panel.
2. Unplug the power cord and disconnect the wall
thermostat connections.
3. Raise the top duct by turning all four case top duct
adjusting screws counterclockwise.
4. Remove the front and/or side case-to-unit grounding
screw, if present.
5. Slide the unit out of the case.
Before servicing,
22
Page 23
Before You Call For Service…GEAppliances.com
Troubleshooting Tips
Problem Possible Causes What To Do
Zoneline does The unit is unplugged. • Make sure the Zoneline plug is pushed completely
not start into the outlet.
The fuse is blown/circuit • Check the house fuse/circuit breaker box and replace
breaker is tripped. the fuse or reset the breaker.
The unit is waiting for • This is normal. The Zoneline will start again after it resets.
the compressor overload
protector to reset.
Power failure. • There is a protective time delay (up to 3 minutes) to
prevent tripping of the compressor overload. For this
reason, the unit may not start normal heating or cooling
for 3 minutes after it is turned back on.
Zoneline does not cool Indoor airflow is restricted. • Make sure there are no curtains, blinds or furniture
or heat as it should blocking the air discharge grille or the return air grille.
Outdoor airflow is • Make sure the architectural louver is not restricted.
restricted or recirculated. This can cause the unit to cycle off due to the compressor
overload.
• Outdoor grille must have a minimum of 65% free area.
Non-GE grilles may be too restrictive for proper
performance. Consult your salesperson for assistance.
The air filter is dirty.• Change the filter at least every 30 days.
See the Care and Cleaning–Air Filters section.
The room may have • When the Zoneline is first turned on you need to
been hot or cold. allow time for the room to cool down or warm up.
Outdoor air is • Set the vent control to the CLOSE position.
entering the room.
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
Burning odor Dust is on the surface • This can cause a “burning” odor at the beginning of
at the start of the heating element. the heating operation. This odor should quickly fade.
of heating operation
The air is not always The heat pump is not • This is normal. The heat pump will produce warm air
cool or hot during producing hot air. but not as hot as air produced when the higher-cost
operation electric heat is used.
The fan switch may be • This causes the fan to blow room temperature air
set at continuous fan. even when the compressor or heater cycles off.
The continuous air movement provides better
overall temperature control.
The air does not feel The heat pump alone • Use the Electric Heat Option. This turns off the heat
warm enough during produces air that feels pump and warms with electric heat only.
heating operation cooler than desired. NOTE: Use of this option will result in increased energy
consumption.
23
Page 24
Things that are normal.
Normal Operating Sounds
“CLICK”
You may hear a pinging noise caused by water being
picked up and thrown against the condenser on rainy
days or when the humidity is high. This design feature
helps remove moisture and improve efficiency.
You may hear relays click when the controls cycle
on and off or are adjusted to change the room
temperature.
Water will collect in the base pan during high humidity
or on rainy days. The water may overflow and drip
from the outdoor side of the unit.
The indoor fan runs continuously when the unit is
operating in the cooling mode, unless the fan switch
behind the case front panel is set at fan cycle (up).
This will cause the fan to cycle on and off with
the compressor. You may also hear a fan noise
stop and start.
3-Minute
Delay
SILENCE
COMPRESSOR
PROTECTION
You may notice a few minutes delay in starting
if you try to restart the Zoneline too soon after
turning it off or if you adjust the thermostat right after
the compressor has shut off. This is due to a built-in
restart protector for the compressor that causes
a 3-minute delay.
During the defrost cycle, both indoor and outdoor
fans stop and the compressor will operate in the
cooling mode to remove frost from the outdoor coil.
After defrost, the unit will restart in electric heat to
quickly warm the room to the desired comfort level.
To protect the compressor and prevent short cycling,
the unit is designed to run for a minimum of 3 minutes
after the compressor starts at any thermostat setting.
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
24
Page 25
Notes. GEAppliances.com
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
25
Page 26
Notes.
Consumer SupportTroubleshooting TipsCare and CleaningOperating InstructionsSafety Instructions
26
Page 27
Vertical Zoneline Warranty.
Safety InstructionsOperating InstructionsCare and CleaningTroubleshooting TipsConsumer Support
All warranty service provided by our Factory Service Centers, or an
®
authorized Customer Care
technician. To schedule service, on-line, visit
us at GEAppliances.com, or call 800.GE.CARES (800.432.2737). For service
in Canada, contact Gordon Williams Corp. at 1.888.209.0999. Please have
serial number and model number availa ble when calling for service.
Staple your receipt here.
Proof of the original purchase
date is needed to obtain service
under the warranty.
For The Period Of:GE Will Replace:
One Year Any part of the Zoneline which fails due to a defect in materials or workmanship. During this
From the date of thelimited one-year warranty, GE will also provide, free of charge, all labor and related service
original purchase to replace the defective part.
Five YearsAny part of the sealed refrigerating system (the compressor, condenser, evaporator
From the date of the and all connecting tubing) which fails due to a defect in materials or workmanship.
original purchaseDuring this four-year limited additional warranty, GE will also provide, free of charge,
all labor and related service to replace the defective part.
Five YearsFor the second through the fifth year from the date of original purchase, GE will replace
From the date of the certain parts that fail due to a defect in materials or workmanship. Parts covered are fan
original purchase motors, switches, thermostats, electric resistance heater, electric resistance heater protectors,
compressor overload, solenoids, circuit boards, auxiliary controls, thermistors, frost controls,
ICR pump, capacitors, varistors and indoor blower bearing. During this four-year limited
additional warranty, you will be responsible for any labor or on-site service costs.
What GE Will Not Cover:
n Service trips to your site to teach you how to use
the product.
n Improper installation, delivery or maintenance.
n If you have an installation problem, or if the air
conditioner is of improper cooling or heating capacity
for the intended use, contact your dealer or installer.
You are responsible for providing adequate electrical
connecting facilities.
n In commercial locations, labor necessary to move
the unit to a location where it is accessible for service
by an individual technician.
n Failure or damage resulting from corrosion due
to installation in an environment containing corrosive
chemicals.
n Replacement of fuses or resetting of circuit breakers.
n Filters.
n Failure of the product resulting from modifications
to the product or due to unreasonable use including
failure to provide reasonable and necessary
maintenance.
n Failure or damage resulting from corrosion due
to installation in a coastal environment, except
for models treated with special factory-applied
anti-corrosion protection as designated
in the model number.
n Damage to product caused by improper power supply
voltage, accident, fire, floods or acts of God.
n Incidental or consequential damage caused
by possible defects with this air conditioner.
n Damage caused after delivery.
n Product not accessible to provide required service.
EXCLUSION OF IMPLIED WARRANTIES—Your sole and exclusive remedy is product repair as provided in this Limited Warranty.
Any implied warranties, including the implied warranties of merchantability or fitness for a particular purpose, are limited
to one year or the shortest period allowed by law.
This warranty is extended to the original purchaser and any succeeding owner for products purchased
for use within the USA and Canada. If the product is located in an area where service by a GE Authorized
Servicer is not available, you may be responsible for a trip charge or you may be required to bring
the product to an Authorized GE Service location for service. In Alaska, the warranty excludes
the cost of shipping or service calls to your site.
Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages.
This warranty gives you specific legal rights, and you may also have other rights which vary from state
to state or province to province. To know what your legal rights are, consult your local, state or provincial
consumer affairs office or your state’s Attorney General.
Warrantor: General Electric Company. Louisville, KY 40225
27
Page 28
Consumer Support.
GE Appliances Website
Have a question or need assistance with your appliance? Try the GE Appliances Website 24 hours a day,
any day of the year! For greater convenience and faster service, you can now download Owner’s Manuals,
order parts or even schedule service on-line.
GEAppliances.com
Schedule Service GEAppliances.com
Expert GE repair service is only one step away from your door. Get on-line and schedule your service at
your convenience any day of the year! Or call 800.GE.CARES (800.432.2737) during normal business hours.
For service in Canada, contact Gordon Williams Corp. at 1.888.209.0999.
Real Life Design Studio GEAppliances.com
GE supports the Universal Design concept—products, services and environments that can be used by
people of all ages, sizes and capabilities. We recognize the need to design for a wide range of physical and
mental abilities and impairments. For details of GE’s Universal Design applications, including kitchen design
ideas for people with disabilities, check out our Website today. For the hearing impaired, please call 800.TDD.
GEAC (800.833.4322).
Parts and Accessories GEAppliances.com
Individuals qualified to service their own appliances can have parts or accessories sent directly to their homes
(VISA, MasterCard and Discover cards are accepted). Order on-line today, 24 hours every day or by phone
at 800.626.2002 during normal business hours.
Instructions contained in this manual cover procedures to be performed by any user. Other servicing
generally should be referred to qualified service personnel. Caution must be exercised, since improper
servicing may cause unsafe operation.
Contact Us GEAppliances.com
If you are not satisfied with the service you receive from GE, contact us on our Website with all the details
including your phone number, or write to: General Manager, Customer Relations
GE Appliances, Appliance Park
Louisville, KY 40225
Register Your Appliance GEAppliances.com
Register your new appliance on-line—at your convenience! Timely product registration will allow for enhanced
communication and prompt service under the terms of your warranty, should the need arise.
You may also mail in the pre-printed registration card included in the packing material.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.