The information in this service guide is intended for use by
individuals possessing adequate backgrounds of electrical,
electronic, and mechanical experience. Any attempt to repair a
major appliance may result in personal injury and property
damage. The manufacturer or seller cannot be responsible for the
interpretation of this information, nor can it assume any liability in
connection with its use.
WARNING
To avoid personal injury, disconnect power before servicing this
product. If electrical power is required for diagnosis or test
purposes, disconnect the power immediately after performing the
necessary checks.
RECONNECT ALL GROUNDING DEVICES
If grounding wires, screws, straps, clips, nuts, or washers used to
complete a path to ground are removed for service, they must be
returned to their original position and properly fastened.
All rights reserved. This service guide may not be reproduced in whole or in part
in any form without written permission from the General Electric Company .
– 2 –
Table of Contents
Technical Data ........................................................................................................................ 5
Model Nomenclature .............................................................................................................. 6
Note: Fan blade mounted for maximum airflow with 1/2" of shaft exposed.
*Approximate location (Inverter and Accumulator).
WARNING: Disconnect power cord before
servicing.
Note: Reconnect all grounding devices.
All parts of this appliance capable of conducting
electrical current are grounded. If grounding
wires, screws, straps, clips, nuts, or washers
used to complete a path to ground are removed
for service, they must be returned to their
original positions and properly fastened.
Caution: To avoid personal injury when
servicing the condensing unit, stand on a ladder
which will give enough support to allow removal
of the top panel and safely allow access to
service the unit.
Maximum Current Leakage............................ 0.75 mA
Maximum Ground Path Resistance ............ 0.14 ohms
Energy Consumption (HUMID) ................................. *
NO LOAD PERFORMANCE
Important Safety Notice:
This information is intended for use by individuals
possessing adequate backgrounds of electrical,
electronic, and mechanical experience. Any
attempt to repair a major appliance may result in
personal injury and property damage. The
manufacturer or seller cannot be responsible for
the interpretation of this information, nor can it
assume any liability in connection with its use.
S - Stainless B - Black W - White
Blank - Trim Model
Size
480 - 48 Inches Wide
S
S
480
N
RA
LH
Door T ype
F - Flat
R - Right
L - Left Door Swing
Engineering
A - Initial Design
B - 1st Revision
C - 2nd Revision
D - 3rd Revision
Etc.
Model Year
R - 2004
Icemaker/Exterior
N - Nondispenser
D - Dispenser
Mini-Manual and
Rating Plate
Mini-Manual
The mini-manual is located behind the grille
panel at the top of the refrigerator. When done,
return the mini-manual to its original location for
future use.
Rating Plate
The rating plate,
located behind the
grille panel at the top
of the refrigerator on
the right side of the
evaporator box,
contains the model
and serial numbers.
Additionally, the rating
plate specifies the
minimum installation
clearances, electrical
voltage, frequency ,
maximum amperage
rating, refrigerant
charge, and type.
Serial Number
The first two numbers of the serial number
identify the month and year of manufacture.
Example:AG123456S = Januar y, 2004
A
- JAN2005 - H
D - FEB2004 F - MAR2003 - F
G - APR2002 - D
H - MAY2001 - A
L - JUN2000 - Z
M - JUL1999 - V
R - AUG1998 - T
S - SEP1997 - S
T - OCT1996 - R
V - NOV1995 - M
Z - DEC1994 - L
G
The letter designating
the year repeats every
12 years.
Example:
T - 1974
T - 1986
T - 1998
– 6 –
Component Locator Views
Master Light Switch
Inverter
Compressor
Figure 1 - Machine Compartment
Accumulator
Evaporator
Defrost Heater
Evaporator
Thermistor
Evaporator
Overtemperature
Thermodisc (TOD)
Figure 2 - Evaporator (T op of Freezer)
– 7 –
Water Valve
Evaporator Fan Motor
Evaporator Fan
Connector
Figure 3 - Water V alve
(Center of Machine Compartment)
Figure 4 - Evaporator Fan
Circuit Breakers
Housing Under
Center of Unit
Transformers
Figure 5 - Light Circuit Transformers
– 8 –
Freezer
Door Switch
Icemaker
Fresh Food
Door Switch
Temperature Touch Pad
Damper
Airflow Grille
Auger Drive
Freezer
Thermistor
Water Filter
Cube Solenoid
Fresh Food
Thermistors
Lower
Fresh Food
Lights
Temperature
Overload Device
(TOD)
Figure 6 - Freezer Compartment
Temperature
Overload Device
(TOD)
Climate Control
Drawer Dampers
Figure 7 - Fresh Food Compartment
– 9 –
Climate ControlDrawer Fan
Cabinet
The outer case is made of pre-painted galvanized
steel. The fresh food and freezer liners are
painted metal with a smooth finish. The liners are
not removable or replaceable.
Machine Compartment
The machine compartment is located on the top of
the unit and has a movable chassis that can be
extended from the front of the unit to provide
access to the refrigeration system components.
Caution: Avoid kinking the refrigeration lines when
sliding the chassis out and back in.
To extend the chassis:
1. Remove the grille panel by removing 2 screws
from each side (see photo).
2. Remove the wire guard and rocker switch
panel.
3. Remove the condenser baffle.
Machine Compartment
The Master Light Switch is located behind the
grille panel.
2 Screws
Inverter
4. Loosen the front 7/16-in. track bolts (1 on each
side of the compressor) from the front of the
chassis track.
5. Remove the rear 7/16-in. track bolts (1 on
each side of the compressor) and the spacers
under the rear of the chassis track.
6. Pull the chassis forward until it reaches the
stops in the tracks, working the refrigeration
tubing as you pull the chassis out.
Note.
•When sliding the chassis back into position, be
certain the lines and wiring have not fallen
behind the chassis.
•Use the grille screws for adjustment when
realigning the grille.
Track Bolts
Chassis
– 10 –
Door Closure Mechanism
Doors and Hinges
The door closure mechanism uses a spring to
provide positive door closure from approximately
60 degrees. The door closure mechanism
actuator arm has a spring attached to the rear and
is supported by guide rollers on either side of the
base channel. The roller circumferences and the
actuator arm detents are matched for smooth
operation. The arm is attached to the door with an
Allen head shoulder bolt.
The closure mechanism allows easy opening to
approximately 90 degrees, where the arm has a
detent to permit the door to remain open at 90
degrees with minimal tension. Once the door is
opened beyond 90 degrees, the closure
mechanism pulls the door open until the closure
arm engages the door stop at approximately 130
degrees (factory setting, the door stop can be field
set to 90 degrees). The reverse action occurs
when the door is closed.
Note: The actuator arm is spring loaded with
moderate spring tension.
1. Disconnect the spring from the pin and the
actuator arm.
2. Remove the 3/16-in. Allen head bolt, bushing,
and spacer from the door and actuator arm.
Door
Hinge
Pin
Spring
The doors are of one-piece construction with foam
insulation.
The inner door panel and outer door panel cannot
be separated and must be replaced as an
assembly.
Door Adjustment
Be sure the top hinge does not hit the cabinet trim.
Adjust the door up or down by turning the threaded
hinge pin on the bottom hinge of the fresh food
door.
The upper hinge on the freezer door is slotted to
allow the freezer door to be adjusted left or right.
Door Removal
WARNING: Use the appropriate safety equipment
and lifting techniques. Two persons may be
required for door removal.
Caution: Use wood or a heavy plastic sheet to
protect the floor where the door will be placed.
1. Remove all food and bins from the inner door
liner and tape door to cabinet.
2. Disconnect the spring from the pin and the
actuator arm.
3. Remove the Allen head bolt, bushing, and
spacer from the door and actuator arm.
4. If removing the freezer door, shut of f the water
supply , and disconnect the water line and
electrical connector.
3/16"
Bolt
Allen
Head
Bolt
GEA01267
5/16"
Actuator
Arm
Roller
Assembly
3. Remove 2 screws and the roller assembly
from the rail. Replace roller if excessively
worn.
5. Remove the upper hinge.
6. Lift door up and out to remove.
– 11 –
Hex Nut
Wheel
Leveling Leg
Lower Door Hinge
Note: If replacing lower door hinge, note the
placement of the door stop (pin).
Hinge
1. Remove the door.
Note: Note the placement of spacers and washers for
reassembly.
2. Remove 3/8-in. hex screws (4) and hinge from the
underside of the cabinet.
3. Remove T-27 Torx screws (4) and hinge from the
bottom of the door .
Door Gaskets
The fresh food and freezer doors have magnetic
gaskets that create a positive seal to the front of the
steel cabinet. The center mullion also has magnets to
assist in door sealing. Improper installation of the door
gasket will cause same-poled magnets to oppose one
another, preventing the door from closing tightly.
The magnetic door gaskets are secured to the doors
by a barbed edge that locks into a retainer channel.
The side of the gasket that is nearest the handle of the
door has a stripe on the inside of the barb (see photo).
Base Channel Spacer
Hinge
Door Stop
Bushing
5/16"
Bolt
GEA01268
Replacement
1. St arting at any corner , pull the old gasket out of the
retaining channel.
2. Soak the new gasket in warm water to make it
pliable.
3. Push the barbed edge of the gasket into the
retainer channel.
Rollers and Leveling
This model has 4-point leveling provided by adjustable
rollers on the rear and leveling legs on the front. It also
has 2 nonadjustable front rollers that are used only for
unit positioning.
T o level the unit:
1. Turn the 7/16-in. hex nut, located above the front
rollers, to adjust the roller on the rear of the unit.
Turn clockwise to raise, counterclockwise to lower.
2. Turn the front legs with a 1-1/4
wrench to adjust the front of the unit. T urn
clockwise to raise, counterclockwise to lower.
in. open end
Stripe
(Handle Side
of Door)
– 12 –
Ice and W ater Dispenser
Icemaker
Feeler Arm
Power Switch
Green
Power Light
The icemaker is mounted to the upper left wall of
the freezer cabinet. Under normal operating
conditions, temperatures, door openings, and food
load, the icemaker is capable of producing
approximately 100 to 130 cubes in a 24-hour
period.
To service the icemaker, refer to GE Publication
31-9063.
Controls
The electronic controls on the dispenser are
interactive. The control panel is equipped with a
proximity sensor that causes the panel to light up
as you approach the dispenser (approx. 2 inches).
Removal
I = On
0 = Off
1. Remove the bezel from the outside of the
freezer door.
Note: On stainless steel models, the front panel
must be removed. Remove screws from top,
bottom, and hinge side. Pull out on hinge side.
2. Remove the screw from the bottom of the
control panel. Lift up and pull the bottom of the
panel out. Disconnect the connectors, and
remove the control panel.
3. Remove 4 screws and the backing panel.
4. From the back side of the panel, remove the
water switch and the light socket.
5. Remove 3 screws and the duct door solenoid.
Screw
4 Screws
Duct Door
Solenoid
Light Socket
Water Switch
– 13 –
Water V alve and Water Tank
The water valve is mounted in the left side of the
machine compartment.
A plastic water line is routed from under the unit,
up the back of the cabinet, into the machine
compartment, and to the water filter . A line then
goes from the water filter to the water valve.
Two low-pressure plastic water lines supply water
to the icemaker and door dispenser from the water
valve. A plastic water line is routed from the water
valve, out the back of the machine compartment,
down the back of the cabinet through the bottom of
the unit, and into the fresh food compartment
where it is attached to the cold water tank. A line is
routed from the cold water tank through the bottom
of the unit into the freezer door to supply the water
dispenser. The icemaker water line is routed from
the water valve through the machine compartment
to the icemaker. The icemaker fill tube is also
plastic.
Note: No water filter should be installed if home
has in-home water filtration system (reverse
osmosis filter system, etc.) Replace filter with bypass plug.
Water Valve
Screw
Screw
To Replace the W ater Valve
Note: Some water may leak from the water supply
line and valve when they are disconnected.
1. Shut off the water supply to the unit.
2. Open the grille panel.
3. Remove 1 Phillips screw attaching the water
valve to the filter bracket.
4. Disconnect the wiring harness connector and
3 water lines from the water valve and remove.
To Replace the Chilled Water Tank
Note: Some water may leak from the water supply
line and valve when they are disconnected.
1. Shut off the water supply to the unit.
2. Remove 2 screws and the chilled water tank
cover inside the fresh food compartment.
3. Remove 2 screws from the chilled water tank.
Screws
Water Tank Cover
Chilled Water Tank
4. Cut the water lines leaving enough line to
reconnect. Use union WR02X10471
(5/16 x 5/16).
– 14 –
Airflow
r
Damper
The fresh food compartment receives chilled air
via an electronic damper that is positioned at the
top rear of the fresh food compartment. The
damper is controlled by the main control board and
when open, allows the evaporator fan to push
chilled air from the evaporator into the fresh food
compartment.
To Remove the Damper
1. Remove the light cover .
3. Remove the Styrofoam section covering the
damper.
4. Disconnect the damper wiring connector.
Damper
2. Remove 4 Phillips screws and the light
assembly.
Evaporator
Evap.
Fan
Duct
Entrance
FrontFrontBackBack
Duct
Exit
Foam
5. Carefully pull the damper out of the mullion and
remove.
Top
Return
Dampe
Air
Tower
BottomFreezer SideFresh Food Side
– 15 –
Fans
Evaporator Fan
The position of the fan blade in relation to the shroud is important. Refer to illustration for specifications.
5/16 +/- .03
Airflow
The evaporator fan is the same fan used on previous models; however a significant difference is that the
main control board does not require, nor receive, input from the fan feedback/rpm (blue) wire. The fan
utilizes a permanent magnet, 4-pole, DC motor that operates at three different speeds: high, medium,
and low . The speed of the fan is controlled by the voltage output from the main control board. V oltage
output from the control board to the fan is 13.2 VDC; however to regulate the speed of the fan, the main
control board uses pulse width modulation (PWM). When operating, voltage is sent in pulses (much like
a duty cycle) as opposed to an uninterrupted flow. This pulsing of 13.2 VDC produces ef fective volt age
being received at the motor, which is the equivalent to a reduction in volt age. Fan speed will be selected
and maintained by the main control board regulating the length and frequency of the 13.2 VDC pulse.
One complete revolution of the motor is comprised of all 4 poles. To determine the rpm of the fan, do
the following: Measure the frequency being applied to the motor. Multiply this number by 15 (60 seconds
divided by 4 poles). For example, a frequency measurement of 200 Hz multiplied by 15 would show a
fan speed of 3000 rpm (15 x 200 = 3000). Temperature may cause some fan speed variation. Fan
speed may vary +/- 5%, depending on the temperature, with higher temperatures causing slightly higher
speeds.
12 VDC
12 VDC
0 VDC
High Speed (12 VDC measured)
12 VDC
9.2 VDC
0 VDC
Medium Speed (9.2 VDC measured)
12 VDC
8 VDC
0 VDC
Low Speed (8 VDC measured)
EVAPORATOR FAN SPEEDS
– 16 –
If the fan shorts, it may damage the main control
board. If the resistor on the main control board is
burnt, you must replace the fan and the board (see
photo).
Evaporator Fan Adjustment
Evaporator and Condenser Fan Resistors
Damper - Yellow
Damper - Red
Damper - White
Comm. 2-Way Digital
J2
1
EARTH
J4 or J16
Comm. Common
Comm. +12V
Damper - Blue
5
1
J3 or J10
1
J15
Inverter Output
Inverter Common
1
J2 or J13
Fan Common
Condenser Fan
Evaporator Fan
Evaporator Fan Tach.
1
J6
2
FF2 Thermistor
FF1 Thermistor
1
10
J1 or J14
J5
1
8
Fan +12V
Custom Cool Fan
Custom Cool Damper1 +
J19
Evaporator Thermistor
FZ Thermistor
Custom Cool Damper1 -
+5V
9
6
+5V
Custom Cool Thermistor
5/16 +/- .03
Airflow
Condenser Fan Resistor
Evaporator Fan Resistor
EARTH
K7
K4
DEFROST
Defrost Heater
Line (L1)
Not Used
J8
J9
J11
J1
J7
Neutral
K5
J12
J18
Not Used
FF Door Switch
FZ Door Switch
Custom Cool Heater
Auger Motor Interlock
CUSTOM COOL
Drain Pan Heater
Water Valve
Some of the low voltage DC
PAN
HEATER
K3
WATER
K2
CRUSHER
K1
AUGER
1
Auger Motor
Crusher Solenoid
J4 or J16
J3 or J10
J1 or J14
connector labeling on this model
may differ from other models. The
J2 OR J13
function and diagnostics for these
connectors are identical for all
models.
– 17 –
White Wire (DC Common)
The white wire is the DC common wire used for
testing. During repairs, DC polarity must be
observed. Reversing the DC polarity will cause a
shorted motor and/or board.
Red Wire (Supply)
Each motor uses an internal electronic controller
to operate the motor. Supply volt age from the
main control board remains at a constant
12 VDC.
Blue Wire (Feedback/RPM)
The blue wire feeds rpm (speed) information to
the main control board, allowing the board to
maintain consistent fan speeds. Loss of feedback
from the blue wire will result in the fan accelerating
to maximum speed. Measure the fan rpm using
the frequency between the blue and white wires.
Comm. 2-Way Digital
J2
1
EARTH
J4 or J16
Comm. Common
Comm. +12V
5
J15
Damper - Red
Damper - White
Damper - Blue
1
J3 or J10
1
J2 or J13
Inverter Output
Inverter Common
Damper - Yellow
10
1
Fan Common
Condenser Fan
Evaporator Fan
Custom Cool Fan
Evaporator Fan Tach.
FZ Thermistor
FF2 Thermistor
FF1 Thermistor
1
J1 or J14
J5
1
8
Fan +12V
Custom Cool Damper1 +
Custom Cool Damper1 -
+5V
Evaporator Thermistor
9
6
+5V
Custom Cool Thermistor
High speed - 205 to 215 Hz (3140 RPM)
Medium speed - 155 to 165 Hz (2415 RPM)
Low speed - 140 to 150 Hz (2160 RPM)
Yellow Wire (Signal)
The yellow wire is the input wire from the main
control board. The main control board provides
8 VDC effective voltage for low speed, 9.2 VDC
effective voltage for medium speed, and 12VDC
for high speed. The fan will operate in low speed
only when the fresh food thermistor is satisfied.
Note: When testing these motors:
• You cannot test with an ohmmeter.
• DC common is not AC common.
• Verify 2 volt age potentials:
a. Red to white - power for internal controller.
b. Yellow to white - power for fan.
• Observe circuit polarity.
• Motors can be run for short periods using a
9-volt battery . Connect the white wire to the
negative (-) battery terminal only. Connect the
red and yellow wires to the positive (+) battery
terminal.
EARTH
J19
1
J6
2
K7
K4
DEFROST
Defrost Heater
Line (L1)
Not Used
J8
J9
J11
J1
J7
Neutral
K5
J12
J18
Not Used
FF Door Switch
FZ Door Switch
Custom Cool Heater
Auger Motor Interlock
CUSTOM COOL
Drain Pan Heater
Water Valve
PAN
HEATER
K3
WATER
K2
CRUSHER
K1
AUGER
1
Auger Motor
Crusher Solenoid
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
– 18 –
J4 or J16
J3 or J10
J2 OR J13
J1 or J14
To Remove the Evaporator Fan
1. Remove the ice bucket.
2. Disconnect the icemaker connector. Loosen 2
screws and remove icemaker.
3. Remove 4 screws and slide the icemaker drive
motor assembly forward. Disconnect the wiring
connector and remove the assembly.
Screws
Icemaker Drive
Motor Assembly
Screws
5. Remove 2 screws and wiring cover.
6. Remove 6 screws and evaporator fan cover.
Wiring
Cover
Evaporator Fan Cover
Screws
Screws
– 19 –
7. Disconnect the evaporator fan wiring
connector.
8. Remove 2 screws from the fan mounting
bracket and remove the fan.
Condenser Fan
The condenser fan is a permanent-magnet, 4pole, DC motor that will operate at 3 speeds. Fan
speed (low, medium, high) corresponds with
compressor speed to minimize pressure
variations in the sealed system. The speed of the
fan is controlled by the voltage output from the
main control board. V oltage output from the
control board to the fan is 13.2 VDC; however to
regulate the speed of the fan, the main control
board uses pulse width modulation (PWM). When
operating, voltage is sent in pulses (much like a
duty cycle) as opposed to an uninterrupted flow.
This pulsing of 13.2 VDC produces effective
voltage being received at the motor , which is the
equivalent to a reduction in voltage. Fan speed will
be selected and maintained by the main control
board regulating the length and frequency of the
13.2 VDC pulse. .
Evaporator Fan
Screws
Wire Connector
To Remove the Fan
1. Extend the chassis (see Machine
Compartment in the Cabinet chapter).
2. Pull the blade off the motor shaft.
3. Cut the wire tie securing the fan wiring to the
fan bracket.
Caution: Fan connector can be separated into 3
segments (center, left side, and right side).
Disconnect the fan connector at the center only.
4. Disconnect the fan connector.
5. Feed wiring through the hole in the fan shroud.
6. Remove 2 screws, top section of fan bracket,
and motor.
– 20 –
Fan Bracket
Fan Bracket
Condenser Fan Motor
Screws
Defrost System
Adaptive Defrost
Adaptive Defrost can be described as a defrost
system that adapts to a refrigerator’s surrounding
environment and household usage.
Unlike conventional defrost systems that use
electromechanical timers with a fixed defrost cycle
time, Adaptive Defrost utilizes an intelligent,
electronic control to determine when the defrost
cycle is necessary. In order to accomplish the
correct defrost cycle time, the main control board
monitors the following refrigerator operations:
•Length of time the refrigerator doors were open
since the last defrost cycle
•Length of time the compressor has run since
the last defrost cycle
•Amount of time the defrost heaters were on in
the last defrost cycle
Adaptive Defrost is divided into 4 separate cycles.
Those operations are:
•Cooling Operation
Adaptive Defrost (Pre-Chill Operation)
When the main control board determines that
defrost is necessary, it will force the refrigerator
into a continuous cool mode (pre-chill). During prechill, the freezer temperature may be driven below
the set point. However, the fresh food temperature
will be regulated by the evaporator fan running at
low speed. Pre-chill will last for 30 minutes. These
models do have an 8-hour defrost hold-off.
Adaptive Defrost (Defrost Heater Operation)
After 30 minutes of pre-chill operation, the main
control board turns off the compressor, condenser
fan, and evaporator fan.
During defrost operation, the main control board
monitors the evaporator temperature using
evaporator thermistor inputs. T ypically, the
evaporator thermistor will sense a temperature of
45 °F within 16 minutes. When the thermistor
senses 45 °F, the main control board will terminate
defrost heater operation. Maximum defrost cycle
(heater on) time is 35 minutes (main control board
time out).
•Pre-Chill Operation
•Defrost Heater Operation
•Dwell Period
(See Pub. #31-9062 for more information on
Adaptive Defrost.)
Adaptive Defrost (Cooling Operation)
During the cooling operation, the main control
board monitors door opening (fresh food door and
freezer drawer) and compressor run times. The
board counts the time the doors are open. It
reduces the length of time between defrosts by
300 seconds (multiplication factor) for each
second that each door is open (if both doors are
open, it reduces it by twice the amount). The
multiplication factor reduces compressor run time.
If the doors are not opened, the compressor will
run up to 60 hours between defrosts. If the doors
are opened frequently and/or for long periods of
time, the compressor run time between defrosts
will be reduced to as little as 8 hours.
The defrost system is protected by a defrost
overtemperature thermodisc (bimetal switch). The
thermostat opens when the evaporator
temperature raises to 60 °F and closes when the
evaporator temperature lowers to 45 °F.
Adaptive Defrost (Dwell Period)
After defrost heater operation has been terminated
by the main control board, a 20-minute dwell
period occurs. During this period, the
compressor, condenser fan, and evaporator fan
remain off. The remaining frost melting from the
evaporator will continue to drip and drain so that,
prior to the cooling operation, the evaporator will be
totally clear of any moisture. The pan heater is on
for the entire 20 minute dwell period.
Normal Operating Characteristics
•The fill tube heater is on when the defrost
heaters are on.
•Pan heaters are on when the defrost heaters
are on and during dwell period (25 minutes
plus defrost time).
– 21 –
Defrost Heater
Caution: Use care to avoid scratching the finish
on unit walls.
The defrost heater is a single calrod-type, radiant
heater mounted on the evaporator .
To remove the defrost heater:
1. Remove the evaporator fan (see Evaporator
Fan procedure in the Airflow chapter).
2. Remove 8 screws and freezer ceiling panel.
3. Remove Styrofoam insulation from the bottom
of the evaporator drain pan.
4. Loosen evaporator drain hose clamp.
5. Lower left side of evaporator drain pan and
slide right side out of drain hose and remove.
6. Disconnect the heater wiring.
Styrofoam
Insulation
Evaporator Drain Pan
Hose Clamp
7. Remove 2 screws from the left and right heater
fasteners.
8. Slide the heater toward the front of the freezer
compartment and remove.
Heater
Screws
– 22 –
Evaporator Thermistor
The evaporator thermistor is mounted on the
upper left side of the evaporator. The defrost
cycle will terminate when the main control board
detects 45 °F from the evaporator thermistor. The
main control board must sense 45 °F in less than
35 minutes, or the defrost cycle will time out.
Average time to defrost is less than 16 minutes.
Defrost time should not exceed 35 minutes.
Defrost time does not include dwell period.
Defrost Overtemperature Thermodisc
The defrost overtemperature thermodisc (bimetal
switch) is mounted on the evaporator and
provides overtemperature protection during
defrost. This thermostat will open at 60 °F and
will close at 45 °F.
Evaporator
Thermistor
Note: The main control board will not know if the
heater does not come on due to a broken heater,
open defrost overtemperature thermodisc, or
open wiring harness. The defrost heater is
controlled by maximum time on the main control
board or temperature at the evaporator thermistor.
Defrost
Overtemperature
Thermodisc
– 23 –
Control System
Touch Panel and
Temperature Control Board
The temperature control assembly is located at
the top front of the fresh food compartment and
contains the touch panel and temperature control
board.
The temperature control board receives switched
DC voltage from the main control board. Input
consists of pins 2 to 3. Failure of input results in
default to most recent setting. Pin 1 provides
digital communication between the temperature
control board and the main control board. Failure
of communication results in erratic control.
To remove the temperature control assembly:
1. Remove the light cover .
2. Remove 4 Phillips screws and the light
assembly.
Temperature Control Assembly
Light Assembly
Touch Panel
Note: Temperature control assembly is mounted
on 3 slotted fasteners. Fasteners do not need to
be loosened or removed.
3. Cut the RTV around the edge of the
temperature control assembly.
Note: Old RTV must be removed from the inside
of the fresh food compartment and from the
temperature control assembly. RTV 102 must be
put in place when the temperature control panel is
installed.
4. Disconnect the temperature control assembly
wiring connector.
5. Slide the temperature control assembly back
to release it from the slotted fasteners and
lower the assembly.
6. Disconnect the wiring connector from the
temperature control board.
7. Slide the touch panel out of the temperature
control assembly.
Screws
8. Remove 2 screws and the temperature control
board.
– 24 –
Thermistors
This main control board uses input from 4 thermistors. These thermistors are located in the fresh food
section, the freezer section, and on the evaporator. The main control board monitors the thermistors to
determine the temperature in these areas of the unit and determines which components to run and
when to run them based on this information.
Thermistors can also be checked using diagnostic mode.
seulaVrotsimrehT
erutarepmeT
)C(seergeD
04-04-k8.661Ω
03-22-k88Ω
02-4-k4.84Ω
01-41k6.72Ω
023k3.61Ω
0105k01Ω
0286k2.6Ω
0368k4 Ω
04401k6.2Ω
05221k8.1Ω
06041k2.1Ω
erutarepmeT
)F(seergeD
ecnatsiseR
smho-oliKni
Note: The thermistor’s resistance has a negative coefficient. As the temperature increases, the
thermistor’s resistance decreases.
– 25 –
Main Control Board
The main control board, located behind a metal cover at the top of the refrigerator in the machine
compartment, manages the operation of the refrigerator by calculating response from various inputs.
Damper - White
Damper - Red
Damper - Blue
Comm. 2-Way Digital
J2
1
EARTH
J4 or J16
Comm. Common
Comm. +12V
5
1
J3 or J10
Damper - Yellow
10
FF2 Thermistor
FF1 Thermistor
FZ Thermistor
1
J1 or J14
+5V
Evaporator Thermistor
9
J1 or J14
J2 OR J13
J3 or J10
J4 or J16
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
1
J15
Inverter Output
Inverter Common
1
J2 or J13
Fan Common
Condenser Fan
Evaporator Fan
Evaporator Fan Tach.
1
J6
2
K4
8
Fan +12V
Custom Cool Fan
J19
DEFROST
J5
1
6
+5V
Custom Cool Damper1 +
Custom Cool Damper1 -
K5
CUSTOM COOL
Custom Cool Thermistor
K7
PAN
K3
WATER
J12
HEATER
EARTH
J1
Not Used
J8
– 26 –
Defrost Heater
Line (L1)
J9
J11
J7
Neutral
J18
Not Used
Water Valve
FF Door Switch
FZ Door Switch
Custom Cool Heater
Auger Motor Interlock
Drain Pan Heater
CRUSHER
K1
K2
1
Auger Motor
Crusher Solenoid
AUGER
Main Control Board Locator Tables
ROTCENNOCNIPTUPNITUPTUONOITCNUF
Feedback of fresh food thermistor value. Thermistor is NTC, when temperature drops, resistance
J1 or J14CDV
J1 or J14
1
2
J1 or J143
J1 or J14
4
CDV
CDV
CD
V
value increases, causing return voltage reduction. This value is used to cycle fresh food fan
(when used), evaporator fan, compressor, and condensor fan. Feedback is filtered to respond to
8 degrees of change per minute.
Feedback of second fresh food thermistor value (when used). Thermistor is NTC, when
temperature drops, resistance value increased, causing return voltage reduction. This value is
used to cycle fresh food fan (when used), evaporator fan, compressor, and condensor fan.
Feedback is filtered to respond to 8 degrees of change per minute.
Feedback of freezer thermistor value. Thermistor is NTC, when temperature drops, resistance
value increases, causing return voltage reduction. This value is used to cycle evaporator fan,
compressor, and condensor fan, and will not cycle fresh food fan (when used). Feedback is
filtered to respond to 8 degrees of change per minute.
Feedback of evaporator thermistor value. Thermistor is NTC, when temperature drops, resistance
value increases, causing return voltage reduction. This thermistor value is used to cycle the
heater on during defrost when temperature is below defrost value and off when the temperature
is above defrost value. This value is also read during power-up to determine if refrigerator goes
into pulldown mode or cycle continuation. Feedback is unfiltered, responds immediately.
SNOITINIFEDNIPDRAOBLORTNOC
J1 or J14
ROTCENNOCNIPTUPNITUPTUONOITCNUF
J2 or J13
J2 or J13
J2 or J134
J2 or J137
J2 or J13
ROTCENNOCNIPTUPNITUPTUONOITCNUF
5
1
3
5J2 or J13
8
zH
Provides 5 VDC for thermistors and personality pins on J1.VDC
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
– 28 –
J4 or J16
J3 or J10
J2 OR J13
J1 or J14
SNOITINIFEDNIPDRAOBLORTNOC
ROTCENNOCNIPTUPNITUPTUONOITCNUF
J15
J15
1
2
VDC
Common
12V variable frequency square wave to control compressor speed.
Note: The J15 connector controls compressor speed through voltage AND frequency. When the main
board calls for compressor operation, J15 output between pins 1 and 2 should be approximately 5 VDC
with the harness connected and approximately 12 VDC with the harness disconnected. The voltage will
not change regardless of compressor speed. A change in frequency controls the compressor speed.
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
SNOITINIFEDNIPDRAOBLORTNOC
J3 or J10
J2 OR J13
J1 or J14
– 29 –
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
J4 or J16
niProloCeriWtuptuO/tupnIgnidaeRegatloVniP-ot-niP
J3 or J10
J2 OR J13
J1 or J14
11J,9J,8JdraoBlortnoCniaM
)ediSegatloV-hgiH(srotcennoC
9JdeRtuptu
11JnworBtupn
21JkcalBtuptu
O
I
O
– 30 –
AV021=9nip7Jot9J
AV021=9nip7Jot11J
ot21J
AV021=9nip7J
niProloCeriWtnenopmoC
1deRerutarepmeT
2nworBerutarepmeT
3egnarOerutarepmeT
draoBlortnoCniaM
)ediSCDegatloV-woL(rotcennoC4J
noitanimreT
lortnoc
lortnoc
lortnoc
tuptuO/tupnIgnidaeRegatloVniP-ot-niP
noitacinummoCnoitacinummoclatigidyaw-owT
eewteb
CDV.ylppusCDV-
CDV.nommocCD
,draoblortnocniamn
,)draob(lortnocerutarepmet
dna,draobresnepsid
.draobllihCkciuQ
21
draoBlortnoCniaM
)ediSCDegatloV-woL(rotcennoC3J
niProloCeriWtnenopmoC
1eulBrotoMreppetSrepmaD=3nip4Jot1nip3J
2etihWrotoMreppetSrepmaD=3nip4Jot2nip3J
3deRrotoMreppetSrepma
4wolleYrotoMreppetSrepmaD=3nip4Jot4nip3J
D=3nip4Jot3nip3J
noitanimreT
/tupnI
tuptuO
rT
gnidaeRegatloVniP-ot-niP
CDV3.2egatloVgnidnatS
CDV0.6=egatloVgnileva
CDV3.2egatloVgnidnatS
CDV0.6=egatloVgnilevarT
CDV3.2egatloVgnidnatS
CDV0.6=egatloVgnilevarT
CDV3.
2egatloVgnidnatS
CDV0.6=egatloVgnilevarT
J2
EARTH
J4 or J16
niProloCeriWtnenopmoC
1eulBnafrotaropavE
3etihWnommocnaFnommoCCDV21=8nipo
5
1
1
J3 or J10
1
J15
Inverter Output
Inverter Common
1
J2 or J13
Fan Common
Evaporator Fan
Evaporator Fan Tach.
10
J1 or J14
8
Fan +12V
Condenser Fan
Custom Cool Fan
noitanimreT
retemohcat
1
J5
1
+5V
Custom Cool Damper1 +
Custom Cool Damper1 -
draoBlortnoCniaM
/tupnI
tuptuO
tupnICDV3.6=3nipot1nip2J
9
6
Custom Cool Thermistor
K2
)ediSCDegatloV-woL(rotcennoC2J
niProloCeriWtnenopmoC
1elpruPdoofhserF
2eulBdoofhserF
noitanimreT
1rotsimreht
2rotsimreht
3deRrotsimrehtrezeerFtupnI5.3ot8.2=5nipot3nip1J
4kcalBrotaropavE
5nworBylppusrotsimrehT
eriW
niP
roloC
1wolleY
2yarG
5nworB
6eulB
gnidaeRegatloVniP-ot-niP
t3nip2J
tnenopmoC
noitanimreT
llihCkciuQ
)looCmotsuC(
repmaD
llihCkciuQ
)looCmotsuC(
repmaD
ppuS
egatloVyl
)CDV5(
llihCkciuQ
)looCmotsuC(
rotsimrehT
rotsimreht
)CDV5(egatlov
/tupnI
tuptuO
/tupnI
tuptuO
/tupnI
tuptuO
tuptuOCDV5=3nip2Jot01nip5J
tupnIA/N
J4 or J16
J3 or J10
draoBlortnoCniaM
tupnI5.3ot8.2=5nipot1nip1J
upnI5.3ot8.2=5nipot2nip1J
t
I5.3ot8.2=5nipot4nip1J
tupn
draoBlortnoCniaM
1nip5J
J2 OR J13
/tupnI
tuptuO
tuptuOCDV5=3nip4Jot5nip1J
)ediSCDegatloV-woL(rotcennoC1J
gnidaeRegatloVniP-ot-niP
CDV
CDV
CDV
CDV
)ediSCDegatloV-woL(rotcennoC5J
gnidaeRegatloVniP-ot-niP
)ytiralopgnisrever(CDV21=2nipot
)ytiralopgnisrever(CDV21=1nipot2nip5J
J1 or J14
4wolleYnafrotaropavEtuptuOCDV6.21=3nipot4nip2J
)wol(CDV1.8
5kniPnafresnednoCtuptuOCD
6kcalBnafnapniarDdnuorGdnuorgCDV
7kcalBnafllihCkciuQnommoCCDV21=7
8deRegatlovylppusnaF
)CDV21(
tuptuOCDV21=3nipot8nip2J
V4.31=3nipot5nip2J
)deeps
nipot8nip2J
– 31 –
,).dem(CDV1.8,)hgih(
elgnissinafresnednoc(
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
Thermistors
This main control board uses input from 4 thermistors. These thermistors are located in the fresh food
section, the freezer section, and on the evaporator. The main control board monitors the thermistors to
determine the temperature in these areas of the unit and determines which components to run and
when to run them based on this information.
The Climate Control Drawer can chill or thaw items
quickly. It can also store items at their optimum
temperatures. This Climate Control Drawer
contains the following components:
•Control Board
•Thermistor
•Dampers (2)
•Fan
•Heater
The main control board controls the dampers, fan,
and heater based on input from the Climate Control
Drawer’s control board and the thermistor.
The Climate Control Drawer compartment is sealed to reduce the effect that the drawer temperature
has on the rest of the refrigerator . When the drawer features are not being used, the temperature inside
the drawer will be the same as the fresh food compartment.
Strip Circuit
DAMPER
DAMPER
1
2
1
2
YELLOW
YELLOW
CONTROL
BOARD
(CONTROL HMI)
WHITE
WHITE
RED
1
BROWN
3
ORANGE
5
THERMISTOR
FAN
WHITERED
RED
BROWN
ORANGE
BLUE
BROWN
GRAY
YELLOW
BLACK
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
J4
1 DATA
2 + 12 VDC
3 COM
J5
6
5
2
1
J2
8 +12 VDC
7 FAN
J4 or J16
MAIN
CONTROL
BOARD
HEATER 5
J3 or J10
J2 OR J13
J7
VIOLETORANGE
HEATER
441 Ohms
J1 or J14
ORANGEORANGE
BROWN
EMI/RF
FILTER
GREEN
BROWN
AC POWER CORD
GEA01264
– 33 –
Component Locator View
Air
Diffuser
Dampers
Fan
(in Fan Housing)
Light
Connector
Thermistor
(in Fan Housing)
Top Panel
(Mullion)
Heater
(in Fan Housing)
Fan Connector
9-Pin
Connector
Heater
Connector
Control Board
(in T op Panel)
Climate Control Drawer compartment shown with top panel moved out
– 34 –
Operation
During all modes of operation, the main control board will cycle the dampers, fan, and heater as
necessary to maintain the desired temperature. Typical operation is as follows:
Select Temp
This feature maintains optimum temperatures for specific items.
The CITRUS setting will maintain a drawer temperature of 43 °F by circulating warmed air or cooled
air as needed. The dampers will close and the heater will turn on if warmed air is required to maintain
43 °F. The dampers will open if cooled air is required.
The PRODUCE setting will maintain a drawer temperature of 35 °F by circulating warmed air or cooled
air as needed. The dampers will close and the heater will turn on if warmed air is required to maintain
34 °F. The dampers will open if cooled air is required.
The MEA T setting will maintain a drawer temperature of 32 °F by circulating warmed air or cooled
air as needed. The dampers will close and the heater will turn on if warmed air is required to maintain
32 °F. The dampers will open if cooled air is required.
The Climate Control drawer display will show the selected temperature for approximately 4 seconds
after a Select Temp mode has been selected. After approximately 4 seconds, the actual temperature of
the drawer will be displayed. Refer to the Temperature Table for drawer temperatures.
Express Chill
This feature cools items by opening the dampers and circulating air from the freezer compartment
throughout the drawer . The fan will be on at all times during Express Chill.
The Climate Control Drawer display will show the number of minutes (or minutes remaining) for the
Express Chill mode selected on the control panel. The display will not show the temperature of the
drawer . Refer to the Temperature Table for drawer temperatures.
Express Thaw
This feature thaws items by circulating warmed air throughout the drawer. Temperature is maintained in
the drawer by cycling a small heater on and off as needed. The dampers will be closed during Express
Thaw . The fan will be on at all times during Express Thaw.
When the Express Thaw cycle is complete, the drawer will automatically adjust to 30 °F.
The Climate Control Drawer display will show the number of hours (or hours remaining) for the Express
Thaw mode selected on the control panel (.5 LBS = 4 HRS, 1.5 LBS = 8 HRS, 3 LBS = 12 HRS). The
display will not show the temperature of the drawer . Refer to the Temperature T able for drawer
temperatures.
– 35 –
Temperature Table
When using the Temperature T able, please note the following:
•FF and FZ compartments should be within 3 °F of the temperature set point when checking drawer
temperature.
•All temperatures listed are as measured by the thermistor and displayed by the Climate Control
Drawer display.
•Actual drawer temperature will be displayed in Select Temp mode only. The Climate Control Drawer
display will show the selected temperature for approximately 4 seconds after a Select Temp mode
has been selected. Af ter approximately 4 seconds, the actual temperature of the drawer will be
displayed.
•The actual-temperature display is based on the temperature that the main control board sees from
the thermistor. The selected-temperature (example: CITRUS – 43 °F) is based on the logic of the
Climate Control Drawer control board. If the actual temperature that is displayed is incorrect, the
thermistor and main control board are suspect. If the temperature associated with the Select Temp
mode is incorrect, the Climate Control Drawer control board is faulty.
WAHTSSERPXELLIHCSSERPXEPMETTCELES
EDOMPMETEDOMPMETEDOMPMET
.SBL5.F˚64ot24
.SBL5.1F˚64ot24
.SBL3F˚64ot24
1
1
1
.NIM51F˚52
.NIM03F˚02ot51
.NIM54F˚02ot51
2
2
2
SURTICF˚34
ECUDORPF˚53
TAEMF˚23
3
4
5
Note 1 Climate Control Drawer may take up to 1 hour and 45 minutes to achieve temperature with no
load in drawer (except metal tray) and minimal or no door openings. When the Express Thaw cycle is
complete, the drawer will automatically adjust to 30 °F.
Note 2 Temperature should lower to 25 °F or less within 15 minutes with no load in drawer (except
metal tray) and minimal or no door openings. Temperature should lower to a temperature between 15°F to 20 °F within 30 minutes with no load in drawer (except metal tray) and minimal or no door
openings. If refrigerator is defrosting, temperature in drawer may go below 15 °F.
Note 3 Climate Control Drawer may take up to 1 hour and 45 minutes to achieve temperature with no
load in drawer (except metal tray) and minimal or no door openings.
Note 4 Climate Control Drawer may take up to 1 hour to achieve temperature with no load in drawer
(except metal tray) and minimal or no door openings.
Note 5 Climate Control Drawer may take up to 45 minutes to achieve temperature with no load in
drawer (except metal tray) and minimal or no door openings.
– 36 –
Climate Control Drawer Top Panel
(Mullion)
Removal
Styrofoam Insert
1. Remove 2 storage bins and the glass panel
over Climate Control Drawer.
2. Remove 4 screws from climate control top
and slide back to access wire connectors.
3. Disconnect the connectors and remove the
top panel.
Note: Note that there is a S tyrofoam insert in the
slot at the back, right-hand corner of the top
panel.
Control Board and Display
The control board and display are located in the
Climate Control Drawer top panel (mullion). The
control board and display are part of the mullion
and cannot be replaced separately .
Input from the Climate Control Drawer’s control
board and the thermistor is used by the main
control board to control the dampers, fan, and
heater.
Screws
Top Panel
(Mullion)
Actual drawer temperature will be displayed in
Select Temp mode only. The Climate Control
Drawer display will show the selected temperature
for approximately 4 seconds after a Select Temp
mode has been selected. After approximately 4
seconds, the actual temperature of the drawer will
be displayed.
The actual-temperature display is based on the
temperature that the main control board sees from
the thermistor. The selected temperature
(example: CITRUS – 45 °F, is based on the logic of
the Climate Control Drawer control board. If the
actual temperature that is displayed is incorrect,
the thermistor and main control board are suspect.
If the temperature associated with the Select Temp
mode is incorrect, the Climate Control Drawer
control board is faulty .
.
– 37 –
Caution: When assembling the top panel, use care to prevent pinched wires
Troubleshooting
Use this diagnostic flowchart if the Climate Control Drawer control panel and display are not operating
properly.
If the problem is drawer temperature and the control panel and display appear to be operating normally ,
check the thermistor, damper, fan, and heater first.
If the actual drawer temperature displayed is incorrect, suspect the thermistor and main control board.
Check
communication
using diagnostic
mode.
Communication
pass?
YES
Replace Climate
Control Drawer
control board.
YES
Replace Climate
Control Drawer control
board. If problem is not
corrected, replace the
main control board.
Is a temperature or time
NO
displayed or are any
indicator lights illuminated
on the Climate Control
Drawer control panel?
Display and/or lights
Replace Climate
Control Drawer
control board.
Check for continuity on
data circuit between
J4-1 and Climate Control
Drawer control board
connector terminal 5.
Circuit OK?
Repair circuit.
NO
Disconnect connector J4
from main control board.
No display
or lights
YES
Check for 12 VDC at
main control board
between J4-2 and J4-3.
12 VDC present?
YES
Reconnect connector J4 to
main control board.
Check for 12 VDC at J4-2 at
main control board between
J4-2 and J4-3.
12 VDC present?
YES
Disconnect connector from Climate
Control Drawer control board.
Check for 12 VDC at the Climate
Control Drawer control board
connector between terminals 3 and 5.
12 VDC present?
NO
NO
NO
Replace main
control board.
Replace Climate
Control Drawer
control board.
Open wiring between Climate
Control Drawer control board and
main control board.
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
– 38 –
J4 or J16
9-Pin Connector
Behind Climate
Control Drawer
ORANGE
J3 or J10
J2 OR J13
J1 or J14
Fan and Fan Housing
The 12 VDC fan is controlled by the main control board. The main control board turns the fan on and off
based on input from the Climate Control Drawer control board and thermistor. The fan should always
come on any time Express Chill or Express Thaw is selected.
Troubleshooting
Turn on Express Chill.
Check for 12 VDC at
main control board
between J2-8 and J2-7.
12 VDC present?
YES
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
NO
Check communication
using diagnostic mode.
Communication pass?
YES
Replace main
control board.
J4 or J16
NO
J3 or J10
J2 OR J13
J1 or J14
Check for 12 VDC
at fan connector.
12 VDC present?
YES
· Open circuit between
fan connector and fan.
· Faulty fan.
NO
Open circuit
between main
control board and
fan connector.
Removal
1. Remove Climate Control Drawer top panel.
2. Loosen 2 bottom screws, remove 2 top
screws, and remove air diffuser from fan
housing.
· Open circuit between J4-1 and
Climate Control Drawer control
board terminal 1.
· Faulty Climate Control drawer
control board.
· Faulty main control board.
Screws (Remove)
Screws (Loosen)
Flat Surface
Air
Diffuser
– 39 –
T abs
3. This step for fan removal only: Remove screen
from front of fan and fan from housing.
4. Remove 2 screws and the sheet metal cover
from the right-hand side of the housing.
5. Disconnect fan connector.
9-Pin
Connector
Fan Connector
6. This step for fan removal only: Cut fan wires at
Screen and Fan
fan to remove.
Note: When installing a new fan, the fan wires do not
Fan Housing
Heater Connector
have to be installed under plastic wire holders.
7. Disconnect heater connector and 9-pin connector.
8. Remove 5 screws and fan housing from fresh food compartment.
Note: When installing the diffuser onto the fan housing, the tabs must be on the bottom and the flat
surface must be on top. Incorrect installation will prevent the drawer from cooling and warming properly.
Dampers
Caution: Do not manually move damper door. Manually moving damper door will damage damper.
The dampers are located between the fan housing and the center mullion. The fan housing must be
removed from the fresh food compartment to replace the dampers.
Both dampers always operate at the same time. The
upper damper can be viewed from the Climate Control
Drawer compartment. The lower damper can be viewed
from the freezer compartment. Dampers will be closed
during Express Thaw and will be open during Express
Chill.
The main control board opens and closes the damper
based on input from the Climate Control Drawer control
board and the thermistor.
After selecting Express Thaw, 12 VDC are output from
the main control board for approximately 4 seconds to
close the damper. This voltage can be measured at the
following points:
•Main control board J5-2 to J5-1 with positive (red) test
meter lead on J5-2.
•9-pin connector behind Climate Control Drawer.
Check from gray wire to yellow wire with positive
(red) test meter lead on gray wire.
After selecting Express Chill, 12 VDC are output
from the main control board for approximately 4
seconds to open the damper. This voltage can be
measured at the following points:
•Main control board J5-1 to J5-2 with positive (red)
test meter lead on J5-1.
•9-pin connector behind Climate Control Drawer.
Check from yellow wire to gray wire with positive
(red) test meter lead on yellow wire.
Fan Housing
9-Pin Connector
Dampers
– 40 –
Heater
The 120 VAC heater is located in the fan housing. The
fan housing must be removed from the fresh food
compartment to access the heater.
The heater is controlled by the main control board. The
main control board turns the heater on and off based on
input from the Climate Control Drawer control board and
the thermistor.
Heater
EMI/RF
Filter
Heater Connector Behind
Climate Control Drawer
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
Brown
Orange
Heater
438 Ω
J4 or J16
J3 or J10
J2 OR J13
AC Power
Cord
Fan Housing
J1 or J14
Heater Connector
Heater resistance should be 438 W and can be checked at 2 places:
•J7-5 to J7-9 at main control board. Connector J7 should be disconnected from main control board
when checking resistance.
•Heater (2-pin) connector located behind the Climate Control Drawer. Connector should be
disconnected when checking resistance.
The heater can usually be turned on by entering any of the Quick Thaw modes.
120 VAC output to the heater can be checked at 2 places:
•J7-5 to J7-9 at main control board.
•Heater (2-pin) connector located behind the Climate Control Drawer.
Thermistor
The thermistor is clipped to the inside of the fan housing.
The main control board controls the dampers, fan, and heater based on input from the Climate Control
Drawer’s control board and the thermistor.
Actual drawer temperature will be displayed in Select Temp mode only. The Climate Control Drawer
display will show the selected temperature for approximately 4 seconds after a Select Temp mode has
been selected. After approximately 4 seconds, the actual temperature of the drawer will be displayed.
The actual-temperature display is based on the temperature that the main control board sees from the
thermistor. The selected temperature (example: CITRUS – 43 °F) is based on the logic of the Climate
Control Drawer control board. If the actual temperature that is displayed is incorrect, the thermistor and
main control board are suspect. If the temperature associated with the Select Temp mode is incorrect,
the Climate Control Drawer control board is faulty .
All thermistors can be checked using Diagnostic Mode.
– 41 –
Access
After removing the diffuser, the thermistor can be
accessed through the hole on the right-hand side of
the fan. After removing the thermistor from the clip
(on the inside of the fan housing), the thermistor
can be removed from the fan housing through the
hole in the top of the housing.
Note: When installing the diffuser onto the fan
housing, the tabs must be on the bottom and the
flat surface must be on top. Incorrect installation
will prevent the drawer from cooling and warming
properly.
Note: All thermistors can be checked using
Diagnostic Mode.
Thermistor shown
remov ed from clip.
Clip
9-Pin
Connector
Fan
Housing
Refer to the Thermistor Values chart for resistance
values. Thermistor resistance can be checked at 2
Tabs (Down)
places:
•J5-5 to J5-6 at main control board. Connector J5 should be disconnected from main control board
when checking resistance.
•9-pin connector located behind the Climate Control Drawer. Connector should be disconnected
when checking resistance.
5 VDC output to the thermistor can be checked at 2 places:
•J5-5 to J5-6 at main control board.
•9-pin connector located behind the Climate Control Drawer.
Thermistor
seulaVrotsimrehT
erutarepmeT
)C(seergeD
02-4-k4.84Ω
01-41k6.72Ω
023k3.61Ω
erutarepmeT
)F(seergeD
ecnatsiseR
smho-oliKni
0105k01Ω
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
– 42 –
J4 or J16
J3 or J10
J2 OR J13
J1 or J14
Air Flow
DAMPERS OPEN
Shown with top panel and drawer removed.
With the dampers open, cold air moves from the FZ compartment through the lower damper and into
the fan housing. The fan blows the cold air through the diffuser into the drawer. The air returns from the
drawer through the diffuser and into the fan housing. Air also moves over the top of the drawer , into the
Climate Control Drawer compartment (not into the FF compartment), and then out of the compartment
via the top damper.
DAMPERS CLOSED
Shown with top panel and drawer removed.
With the dampers closed, the fan moves air from the fan housing, through the diffuser, to the drawer. Air
returns from the drawer, through the diffuser, to the fan compartment.
– 43 –
Compartment Lights
The new Monogram side-by-side refrigerator uses 12 VAC halogen lights in both the fresh food and
freezer compartments. The fresh food compartment is equipped with two 35-watt bulbs and
five 20-watt bulbs producing a total of 170 watts. The freezer compartment is equipped with two
35-watt bulbs producing a total of 70 watts. Power is supplied to all interior lighting by 2 transformers.
The transformers convert 120 V AC to 12 VAC.
FF/FZ Compartment Lights Diagnostic
Check for 120 VAC at transformer. Measure
votlage at transformer connector between red
wire (FZ) or violet wire (FF) and orange wire.
YES
Measure output voltage
at transformer
YES
Open circuit
between lights and
transformer.
connector between red
and gray wires.
Are 12 VAC measured?
NO
Replace
Transformer.
Are 120 VAC measured?
NO
Check the following:
1. FF or FZ door switch
2. Sabbath switch
3. Circuit breaker (located by the transformers in
tray under the FF compartment)
4. Thermal overload
FZ - located at bottom of FZ Compartment
FF - located at bottom of FF light tower
5. 120 VAC Wiring
FZ - blue wire(s) and red wire(s)
FF - yellow wire(s) and violet wires
6. Neutral wiring (orange)
– 44 –
Door Switches
The fresh food and freezer door switches are located at the top of the fresh food and freezer
compartments.
The fresh food door switch closes when the door is open, providing L1 to the fresh food compartment
light transformer.
The freezer door switch is a dual-pole switch. It provides L1 to the main control board when the freezer
door is closed. When the freezer door is open, the switch provides L1 to the freezer compartment light
transformer.
Master Light Switch
The master light switch is located behind the grille
panel, on the main control board cover . The
switch will open the circuits between the door
switches and the transformers, disabling both
transformers and stopping voltage output to the
interior lights.
Main Control
Master Light Switch
Master Light Switch
Main Control
Board Cover
Board Cover
T emperature Overload Device (T OD)
A temperature overload device is wired in series with both the fresh food and freezer compartment
transformers. If the interior lights should reach excessive temperatures due to a door being open for an
extended period, the corresponding TOD will open the circuit that supplies 120 VAC to the transformer .
The TOD will open at 150 °F and close at 90 °F.
The freezer TOD is located behind a metal cover on the back wall of the freezer compartment, at the
base of the light tower. The fresh food TOD is located on the back wall of the fresh food compartment,
at the base of the light tower .
Temperature Overload
Temperature Overload
Device (TOD)
Device (TOD)
Temperature Overload
Temperature Overload
Device (TOD)
Device (TOD)
Light Tower
Freezer Compartment
Light Tower
Fresh Food Compartment
– 45 –
Type 2
Type 1
Type 2
Type 1
This is a 35 watt, 12 volt,
Type MR11 bulb.
If ordering through
GE Parts and Accessories,
order part WR02X11183.
Type 2
This is a 20 watt, 12 volt,
Type T bulb.
If ordering through
GE Parts and Accessories,
order part WR02X11184.
Circuit Breakers
Two re-settable, 2-amp circuit breakers are located
on the front of the transformer housing. Should a
circuit breaker trip (open), it will open the
transformer circuit it is associated with (freezer
compartment or fresh food compartment),
disabling that transformer and stopping voltage
output to the interior lights.
Transformers
Power is supplied to all interior lighting by 2
transformers. One transformer is used for each
compartment. The transformers supply lowvoltage power to the lights by converting 120 V AC
into 12 V AC.
The transformers are located in a housing under
the center of the refrigerator. The housing is
accessible from the front of the refrigerator. To
access the transformers, remove the
head screws (6) that hold the housing in place.
1
/4-in hex-
Transformers
Circuit Breakers
Note: Nuisance tripping of the circuit breakers
can occur due to higher than normal line
voltage. Replacing the 2-amp circuit breakers
with a new part (now rated at 3-amps) will
resolve the problem.
Light Bulb Replacement
WARNING: Halogen lights generate intense heat.
Be certain power is off and lamps have sufficient
time to cool before attempting to replace.
Note: The Styrofoam protector in the light lens is
for shipping and must be removed prior to
installation.
Power to the lamps can be turned off at the
Sabbath switch, located behind the grille panel at
the top of the refrigerator.
Note: Turning the temperature control to the OFF
position does NOT remove power to the light
circuits.
The refrigerator uses 2 types of halogen bulbs:
Type 1
The columns along the back wall of the fresh food
and freezer compartments are lit up by lamps
located behind the top pan in the fresh food
compartment and the bottom basket in the freezer
compartment. Type 1 bulbs are 35-watt and have a
life expectancy of about 3500 hours.
Type 2
These lamps are located inside the light shield at
the top of the fresh food compartment and on top
of the Climate Control drawer at the bottom of the
fresh food compartment. Type 2 bulbs are 20-watt
and have a life expectancy of about 2000 hours.
– 46 –
Upper light
shield
Screws
Screws
Slots
Light housing
Support tabs
Light Shield
Type 1 Bulb Replacement
WARNING: Halogen lights generate intense heat.
Be certain power is off and lamps have sufficient
time to cool before attempting to replace.
1. Set the master light switch to the OFF position
6. Replace the glass by sliding it into place. Then,
replace the light shield by resting the top lip of
the shield on top of the light housing. Then,
press the sides until the tabs pop into the slots
in the housing.
WARNING: The light shield must be replaced, or
the heat from the bulb could damage the
refrigerator.
Type 2 Bulb Replacement
WARNING: Halogen lights generate intense heat.
Be certain power is off and lamps have sufficient
time to cool before attempting to replace.
1. Set the master light switch to the OFF position
and allow the lamps to cool.
2. If a water filter cartridge is installed, remove it
and replace with a filter bypass plug.
3. Holding the light shield with one hand, rotate the
support tabs until they clear the front of the light
shield. Then, push back on the light shield,
lower the shield at the front, and take out.
4. Remove the 4 screws securing the light
housing to the ceiling. There are two screws at
the front and two at the back.
5. Lower the light housing at the front, then pull it
toward you so the tabs at the back of the light
housing come out of the slots on the back wall.
The lamp assemblies will release from the
holders.
– 47 –
Lower lamp
assemblies
6. Turn the lamp protector to access the bulb.
Note: Always follow bulb manufacturer’s directions for
handling and replacing bulbs.
7. Remove the bulb by holding the base and pulling
straight out. Replace with a new bulb and replace the
lamp protector.
WARNING: Lamp protectors must be replaced, or the
heat from the bulb could damage the refrigerator.
8. Holding up the light housing, place each lamp
assembly in its holder. Feed the attached wires
through the slots and tuck the wires outside the side
of the light housing.
9. Insert the tabs on the back of the light housing in the
slots on the back wall. Raise the light housing into
position and secure with the four screws.
10. Replace the light shield and rotate the support tabs
back out to support the front of the shield.
11. Remove the filter byp ass plug and replace with the
water filter cartridge. Reset the Sabbath switch to the
ON position.
Climate Control Drawer Type 2 Bulb Replacement
WARNING: Halogen lights generate intense heat. Be
certain power is off and lamps have sufficient time to
cool before attempting to replace.
1. Set the master light switch to the OFF position and
allow the lamps to cool.
2. To access the lamps, remove the second produce
pan.
3. The lamps at the back, which face up, can be lifted
out. To access the lamp that shines into the Climate
Control drawer, twist the holder until the arrow point s
toward the back of the refrigerator , then lift up.
4. Turn the lamp protector to access the bulb.
Note: Always follow bulb manufacturer’s directions for
handling and replacing bulbs.
5. Remove the bulb by holding the base and pulling
straight out. Replace with a new bulb and replace the
lamp protector.
WARNING: Lamp protectors must be replaced, or the
heat from the bulb could damage the refrigerator.
– 48 –
J4 OR J16 J3 OR J10J1 OR J14
J2 OR J13
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 DATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
REDORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLETVIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
DEF HEATER
PAN HEATER
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39Ω
2Ω
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10Ω
10Ω
10Ω
R=441Ω
R=330Ω
R=38Ω
R=1323Ω
ZIS360
Schematics
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
– 49 –
J4 OR J16 J3 OR J10J1 OR J14
J2 OR J13
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 DATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
REDORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLETVIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
R=441Ω
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
DEF HEATER
R=1323Ω
PAN HEATER
R=330Ω
R=38Ω
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39Ω
2Ω
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10Ω
10Ω
10Ω
DISPENSER
CONTROL HMI
1
RED
35
BROWN
ORANGE
ZIS360D
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
– 50 –
J4 OR J16 J3 OR J10J1 OR J14
J2 OR J13
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 DATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
REDORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLETVIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
R=441Ω
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
DEF HEATER
R=38Ω
R=1323Ω
PAN HEATER
R=330Ω
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39Ω
2Ω
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10Ω
10Ω
10Ω
ZIS420
– 51 –
J4 OR J16 J3 OR J10J1 OR J14
J2 OR J13
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 DATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
REDORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLETVIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
R=441Ω
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
R=1323Ω
DEF HEATER
R=38Ω
PAN HEATER
R=330Ω
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39Ω
2Ω
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10Ω
10Ω
10Ω
DISPENSER
CONTROL HMI
1
RED
35
BROWN
ORANGE
ZIS420D
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
– 52 –
J4 OR J16 J3 OR J10J1 OR J14
J2 OR J13
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 DATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
REDORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLETVIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
R=1323Ω
DEF HEATER
R=38Ω
PAN HEATER
R=330Ω
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39Ω
2Ω
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10Ω
10Ω
10Ω
R=441Ω
ZIS480
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
– 53 –
J4 OR J16 J3 OR J10J1 OR J14
J2 OR J13
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 D ATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
REDORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLETVIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
R=441Ω
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
R=1323Ω
DEF HEATER
R=38Ω
PAN HEATER
R=330Ω
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39Ω
2Ω
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10Ω
10Ω
10Ω
DISPENSER
CONTROL HMI
1
RED
35
BROWN
ORANGE
ZIS480D
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
– 54 –
Refrigeration System
Inverter Compressor
The new inverter compressor is not
controlled by 120 V AC output from
the main control board, as in
previous models. The compressor
is controlled by the inverter .
Warning: Disconnecting the 6-pin
connector does not disconnect
power (120 V AC) from the inverter.
The refrigerator must be unplugged
before servicing the inverter or
compressor.
Caution: Do not attempt to
direct-start the compressor.
The compressor operates on a
3-phase power supply . Applying
120 VAC to the compressor will permanently damage the unit. It is not possible to start the
compressor without an inverter.
The compressor is a reciprocating, variable speed, 4-pole type. It operates on 3-phase, 80 to 230 V AC
within a range of 57 to 104 Hz. Compressor speed is controlled by voltage frequency and pulse width
modulation. Increasing frequency from the inverter will produce an increase in compressor speed.
•Frequency of 57 Hz will produce low speed operation at 1710 rpm.
•Frequency of 70 Hz will produce medium speed at 2100 rpm.
•Frequency of 104 Hz will produce 3120 rpm.
Note: Certain voltmeters will not be able to read voltage output or frequency from the inverter.
Compressor wattages at various speeds are:
•LOW - 65 watts
•MED - 100 watts
•HIGH - 150 watts
BTU rating also varies according to operating speed.
Compressor speed is based on the temperature set-point in conjunction with the cabinet temperature.
Speeds are selected according to the following cabinet temperatures:
• 6 °F to 19.5 °F above set-point = high speed
• 3.5 °F to 5.5 °F above set-point = medium speed
• 1 °F to 3 °F above set-point = low speed
Note: The compressor will run at medium speed if the cabinet temperature is 20 °F or more above the
set-point.
The use of 3-phase power eliminates the need for the PTCR relay , cap acitor, and individual start and run
windings; therefore the start, run, and common pins found on conventional compressors are not
applicable on this 3-phase model. Compressor pin functions are identical and compressor lead wire
configuration is of no importance. A resistance of 9 to 11 W should be read between any 2 of the 3 pins.
Should an open occur in the compressor winding or should one of the compressor lead wires become
open or disconnected, the inverter will stop voltage output to the compressor .
– 55 –
High compressor torque enables the compressor to start against high pressure in the sealed system.
When power has been disconnected from an operating unit, the high torque may enable the
compressor to start immediately upon power restoration. The compressor, if unable to start after 12
times, will wait for 8 minutes before trying again.
Compressor and sealed system operation is extremely smooth and cool. The compressor exterior may
be room temperature while operating; therefore a running unit may be difficult to detect.
To verify that the compressor is running:
Disconnect power from the unit and place a hand on the compressor. Reconnect power and feel for a
vibration when the compressor tries to start. It may take up to 8 seconds before the compressor
attempts to start.
To determine motor rpm:
Measure the frequency of the voltage being applied to the compressor and multiply this number by 30.
For example, a frequency measurement of 70 Hz would show a compressor speed of 2100 rpm (30 x
70 = 2100).
Note: If the compressor fails to start, the inverter will briefly stop voltage output. The inverter will make
12 consecutive attempts to start the compressor (once every 12 seconds). If, after 12 attempts, the
compressor has not started, an 8-minute count will occur. After 8 minutes, the inverter will attempt to
start the compressor again. If the compressor starts, normal operation will resume. If the compressor
fails to start, the process will be repeated. Removing power from the unit will reset the inverter count.
When power is restored, the inverter will attempt to start the compressor within 8 seconds.
Note:
•When ordering a replacement compressor, order both the compressor and inverter. Replace the
compressor first. If, after compressor installation, the compressor fails to start, replace the inverter.
•When servicing the compressor, it is important to dress the wiring to keep low voltage DC wiring and
120 V AC wiring separate.
– 56 –
Inverter
Warning: Disconnecting the 6-pin connector does not disconnect power (120 VAC) from the
inverter. The refrigerator must be unplugged before servicing the inverter.
Note: Certain voltmeters will not be able to read voltage output from the inverter . If no voltage or erratic
voltage is measured, it does not necessarily indicate a faulty inverter .
The inverter receives 120 V AC line-in from the power supply. The inverter converts this single-phase,
60 Hz, 120 V AC into 3-phase, 230 VAC, with frequency variations between 57 Hz and 104 Hz. This
voltage is delivered to the compressor through 3 lead wires. Each wire will carry identical voltage and
frequency. When checking inverter voltage output, connect the test-meter leads to any 2 of the 3
compressor lead wires. The same reading should be measured between any 2 of the 3 wires.
Note: The compressor leads must be connected to measure voltage output. If the compressor wires
are not connected, or if an open occurs in one of the 3 lead wires or in the compressor, the inverter will
stop voltage output.
The inverter controls compressor speed by frequency variation and by pulse width modulation (PWM).
Changing frequency and PWM will cause an effective voltage between 80 and 230 VAC to be received at
the compressor.
•Low speed (1710 rpm) - 57 Hz
•Medium speed (2100 rpm) - 70 Hz
•High Speed (3120 rpm) - 104 Hz
The inverter receives commands from the main control board.
The main control board will send a (PWM) run signal between 1.5
and 3.5 VDC effective voltage to the inverter. The signal voltage at
the inverter should be equal to the signal voltage sent by the main
control board. The inverter will select compressor speed (voltage
output) based on this signal. A signal voltage from the main
control board (J15 connector ) lower than
faulty main control board. The main control board will only send a
run signal to the inverter when the compressor should be on.
Note: When measuring signal voltage (from the main control
board) at the inverter, disconnect the wire harness connector at
the inverter and measure the voltage at the connector .
The inverter will monitor compressor operation and if the
compressor fails to start or excessive current draw (4 amps
maximum) is detected, the inverter will briefly stop voltage output.
The inverter will then make 12 consecutive compressor start
attempts (once every 12 seconds). If after 12 attempts the
compressor has not started, an 8-minute count will initiate. After
the 8-minute count, the inverter will attempt to start the
compressor again. If the compressor starts, normal operation will
resume. If the compressor fails to start, this process will be repeated. Removing power to the unit will
reset the inverter count. When power is restored, the inverter will attempt to start the compressor within
8 seconds.
5 VDC indicates a
J15
The inverter has a built-in circuit protection to guard against damage from a failed or shorted
compressor. However, if a failed compressor is diagnosed, order a new compressor and inverter. If the
compressor fails to start after replacement, replace the inverter.
– 57 –
Note: When servicing the inverter , it is
important to dress the wiring to keep lowvoltage DC wiring and 120 V AC wiring
separate.
To remove the inverter:
1. Unplug the unit.
2. Open access cover.
3. Remove the screw securing the inverter to
the sheet metal dividing wall. (It may be
necessary for you to move the foam
spacer.)
4. Slide the inverter forward to release the
back from the metal dividing wall.
Note: It may be necessary to bend the
process tube in order to remove the inverter. If
it is necessary to bend the process tube, use
extreme care.
5. Turn the inverter horizontally and slide the
inverter out of the machine compartment.
To remove the inverter cover:
Screw
Inverter
Use a small screwdriver to release the two
small tabs and carefully remove the inverter
cover.
Inverter
Inverter
Line-In (L1)
Line-In (L1)
Signal Wire Connector
Signal Wire Connector
(From Main Control Board)
(From Main Control Board)
Compressor Lead
Compressor Lead
Wires
Wires
Tabs
– 58 –
Accumulator
An accumulator has been installed at the inlet of
the compressor to prevent liquid refrigerant (low
quality) from entering the suction line. Changes in
compressor speed (transition state) can
temporarily reduce refrigerant quality . The
accumulator compensates for this by collecting
and holding up to 2 oz of liquid while allowing
vapor to pass. Within minutes after the
compressor speed change, the system attains a
steady state (becomes stabilized), the liquid
refrigerant in the accumulator vaporizes, and
refrigerant quality returns to normal.
Note: Accumulator should be located above drain
pan to allow any condensed moisture
accumulated to fall into drain pan.
Accumulator
Steady State
INVERTER COMPRESSOR
70-135 PSIG
85-90 PSIG at
75 ˚F Ambient
CONDENSEREVAPORATOR
FILTER-DRIER
COMPRESSOR
CAPILLARY
ACCUMULATOR
MIX OF LIQUID AND VAPOR
HIGH PRESSURE LIQUID
0-5 PSIG
1-2 PSIG at
75 ˚F Ambient
HIGH PRESSURE VAPOR
70-135 PSIG
85-90 PSIG at
75 ˚F Ambient
CONDENSEREVAPORATOR
LOW PRESSURE LIQUID
MIX OF LIQUID AND VAPOR
LOW PRESSURE VAPOR
Transition State
INVERTER COMPRESSOR
COMPRESSOR
FILTER-DRIER
CAPILLARY
ACCUMULATOR
LIQUID ENTERS
THE ACCUMULATOR
0-5 PSIG
1-2 PSIG at
75 ˚F Ambient
GEA01263
System Pressure
The refrigeration system should maintain a consistent pressure regardless of compressor speed.
Pressure variations, due to changing compressor speed, are minimized by matching the condenser fan
speed and evaporator fan speed to the compressor speed. The condenser and evaporator fans will
always operate at the same speed (low, medium, or high) as the compressor.
Low side system pressure should be between 0 and 5 psig dependant on ambient temperature.
System pressures in an ambient temperature of 75 °F should be:
••
•High Side – 85 to 90 psig
••
••
•Low Side – 1 to 2 psig
••
Refrigerant Charge
The refrigerant used in the sealed system is R134a. Proper system charge is 12.5 oz; however, an
additional 0.5 oz is required when adding a filter/drier . Proper system charge is critical to the operation of
this unit.
– 59 –
Drier
The drier is positioned vertically in the center of the
machine compartment. A copper process tube,
connected to the inlet of the drier , provides access
to the high-pressure side of the refrigeration
system. The capillary is connected to the outlet of
the drier .
Evaporator
The evaporator is made of copper and aluminum
and is located above the evaporator fan at the top of
the freezer compartment.
To replace the evaporator
Process
Tube
Drier
1. Recover the refrigerant.
2. Remove the evaporator fan (see procedure).
3. Remove the defrost heater (see procedure).
4. Remove the defrost overtemperature
thermodisc and evaporator thermistor.
5. Disconnect the ground wire from the evaporator
and position all wiring to allow for evaporator
removal.
6. Remove the screws securing the evaporator to
the cabinet.
Caution: Protect wiring from heat during
desoldering and resoldering.
7. Desolder the capillary tube from the evaporator .
8. Desolder the suction line.
9. Remove the evaporator .
10. Using a file, score the capillary tube just above the
old solder and break the solder-covered section
off. This will help prevent the capillary tube from
becoming plugged when resoldering.
Capillary
Evaporator Thermistor
Evaporator Thermistor
Defrost Overtemperature Thermodisc
11. Position the new evaporator in the cabinet.
Insert the suction line and capillary tube into the
evaporator.
12. Solder the suction line to the evaporator using
silfos.
13. Solder the capillary tube to the evaporator using
silfos.
14. Install a replacement drier.
15. Evacuate and recharge the system using
currently accepted procedures.
Refrigerant Charge
The refrigerant used in this model is type R134a.
Refer to the mini-manual or model tag for the
exact refrigerant charge quantity .
– 60 –
Diagnostic Mode
Enter the diagnostic mode by pressing both the freezer temperature pads (plus and minus) and the
refrigerator temperature pads (plus and minus) simultaneously. All 4 pads must be held for
approximately 3 seconds. A blinking “0” in both displays indicate the refrigerator has entered the test
mode.
Enter the appropriate display numbers as
shown below and press any pad other than the
temperature pads to activate that test mode.
Note 1: Display order is: 1) Fresh Food 1, 2) Fresh Food 2, 3) Custom Cool, 4) Evaporator,
5) Freezer. Thermistor test results are P = pass, 0 = fail, S = short to 5 VDC, B = bad amplifier
(replace main control).
Note 2: You must enter the defrost test again to toggle the defrost heater off at the end of the test.
The heater will not come on if the evaporator thermistor or overtemperature thermodisc is warm.
– 61 –
Compressor Not Running Flowchart
Unplug refrigerator. Warm
freezer thermistor to 70 F.
Connect power and set
temperature controls to
maximum settings.
Does compressor start?
YES
Adjust settings and
allow 24 hours to
stabilize.
NO
Check condenser
fan for operation.
Fan operating?
YES
NO
YES
Verify freezer
thermisor is within
proper range using
thermistor values
chart. Is thermsitor
within proper range
NO
Note: A signal voltage from the
main board to the inverter of less
than 5 VDC indicates a bad
main board.
Verify signal voltage of 5 to
12 VDC at the main control
board connector J15.
Is voltage OK?
YES
Disconnect the main control
board signal wire at the inverter
and verify signal voltage of
5 to 12 VDC.
Voltage OK?
YES
Check compressor for
proper resistance.
9 to 11 ohms should be
measured between all
pins.
Resistance OK?
NO
Go to Condenser
Fan Not Running
flowchart.
NO
NO
Replace main
control board.
Replace wiring
harness from main
control board to
inverter.
Replace compressor.
Note: When ordering a replacement
compressor, order the compressor and
inverter. Replace the compressor first.
If the compressor does not start
replace the inverter.
Check wiring
connections. If
wiring is OK, replace
thermsitor.
YES
Replace inverter.
YES
Check for 120 VAC
(L1) at inverter.
Voltage present?
YES
Check compressor
lead wires and
connections.
Wires and
connections OK?
Repair lead wire or
NO
connection.
– 62 –
NO
Repair inverter
wiring.
Warranty
YOUR MONOGRAM REFRIGERATOR WARRANTY
Staple sales slip or cancelled check here. Proof of original purchase
date is needed to obtain service under warranty.
WHAT IS
COVERED
From the Date
of the Original
Purchase
FULL TWO-YEAR WARRANTY
For two years from date of original purchase, we will provide, free of charge, parts and service labor in
your home to repair or replace any part of the refrigerator that fails because of a manufacturing defect.
FULL FIVE-YEAR WARRANTY
For five years from date of original purchase, we will provide, free of charge, parts and service labor
in your home to repair or replace any part of the sealed refrigerating system (the compressor, condenser,
evaporator and all connecting tubing) that fails because of a manufacturing defect.
LIMITED ADDITIONAL SEVEN-YEAR WARRANTY ON THE SEALED SYSTEM
For the sixth through twelfth year from the date of the original purchase, we will provide, free of
charge, replacement parts for any part of the sealed refrigerating system (the compressor, condenser,
evaporator and all connecting tubing) that fails because of a manufacturing defect. You pay for
the service trip to your home and for service labor charges.
LIMITED LIFETIME WARRANTY ON ACCURIDE® SLIDES
From the date of the original purchase we will provide, free of charge, replacement parts for
any part of the Accuride Slides that fails because of a manufacturing defect. You pay for the service
trip to your home and for service labor charges.
This warranty is extended to the original purchaser and any succeeding owner for products
purchased for ordinary home use in the 48 mainland states, Hawaii and Washington, D.C.
In Alaska the warranty is the same except that it is LIMITED because you must pay to ship
the product to the service shop or for the service technician’s travel costs to your home.
All warranty service will be provided by our Factory Service Centers or by our authorized Customer
Care® servicers during normal working hours.
Should your appliance need service, during warranty period or beyond, in the U.S.A.
call 800.444.1845. In Canada: 888.880.3030.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the
above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and
you may also have other rights which vary from state to state. To know what your legal rights are in
your state, consult your local or state consumer affairs office or your state’s Attorney General.
Warrantor: General Electric Company, Louisville, KY 40225
WHAT IS NOT
COVERED
• Service trips to your home to teach you how
to use the product.
• Replacement of house fuses or resetting of
circuit breakers.
• Damage to the product caused by accident,
fire, floods or acts of God.
• Failure of the product if it is used for
other than its intended purpose or used
commercially.
• Improper installation.
If you have an installation problem, contact
your dealer or installer. You are responsible for
providing adequate electrical, plumbing and
other connecting facilities.
• Loss of food due to spoilage.
• Incidental or consequential damage caused by
possible defects with this appliance.
– 63 –
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.