Ge ZIS480NR, ZIS360NR, ZIS420NR, ZIS 480DR, ZIS 420DR User Manual

...
GE Consumer & Industrial
TECHNICAL SERVICE GUIDE
Monogram
Inverter Compressor Side-By-Side
Refrigerators
MODEL SERIES:
ZIS_420DR ZIS_480DR
GEA01265
PUB # 31-9117 04/04
IMPORTANT SAFETY NOTICE
The information in this service guide is intended for use by individuals possessing adequate backgrounds of electrical, electronic, and mechanical experience. Any attempt to repair a major appliance may result in personal injury and property damage. The manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
WARNING
To avoid personal injury, disconnect power before servicing this product. If electrical power is required for diagnosis or test purposes, disconnect the power immediately after performing the necessary checks.
RECONNECT ALL GROUNDING DEVICES
If grounding wires, screws, straps, clips, nuts, or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.
GE Consumer & Industrial
Technical Service Guide
Copyright © 2004
All rights reserved. This service guide may not be reproduced in whole or in part in any form without written permission from the General Electric Company .
– 2 –
Table of Contents
Technical Data ........................................................................................................................ 5
Model Nomenclature .............................................................................................................. 6
Rating Plate ...................................................................................................................... 6
Mini-Manual ....................................................................................................................... 6
Serial Number ...................................................................................................................6
Component Locator Views..................................................................................................... 7
Cabinet .................................................................................................................................. 10
Machine Compartment ................................................................................................... 10
Door Closure Mechanism.................................................................................................11
Doors and Hinges .............................................................................................................11
Door Gaskets.................................................................................................................... 12
Rollers and Leveling....................................................................................................... 12
Ice and Water Dispenser ...................................................................................................... 13
Controls ............................................................................................................................ 13
Water Valve and Water Tank ......................................................................................... 14
Airflow ................................................................................................................................... 15
Damper ............................................................................................................................ 15
Fans ....................................................................................................................................... 16
Evaporator Fan ................................................................................................................ 16
Condenser Fan ................................................................................................................ 20
Defrost System ...................................................................................................................... 21
Adaptive Defrost .............................................................................................................. 21
Normal Operating Characteristics.................................................................................. 21
Defrost Heater..................................................................................................................22
Evaporator Thermistor .................................................................................................... 23
Defrost Overtemperature Thermodisc ........................................................................... 23
Control System ...................................................................................................................... 24
Touch Panel and Temperature Control Board.............................................................. 24
Thermistors ...................................................................................................................... 25
Main Control Board ......................................................................................................... 26
Main Control Board Locator T ables............................................................................... 27
Thermistors ...................................................................................................................... 32
Climate Control Drawer........................................................................................................ 33
Strip Circuit...................................................................................................................... 33
Component Locator View............................................................................................... 34
Operation ......................................................................................................................... 35
Temperature Table.......................................................................................................... 36
Climate Control Drawer Top Panel (Mullion) ................................................................ 37
Control Board and Display ............................................................................................ 37
Fan and Fan Housing...................................................................................................... 39
Dampers ........................................................................................................................... 40
Heater............................................................................................................................... 41
Thermistor........................................................................................................................ 41
Air Flow............................................................................................................................ 43
– 3 –
Table of Contents (cont.)
Compartment Lights ............................................................................................................. 44
FF/FZ Compartment Lights Diagnostic .......................................................................... 44
Door Switches ................................................................................................................. 45
Master Light Switch ........................................................................................................ 45
Temperature Overload Device (TOD)............................................................................. 45
Circuit Breakers............................................................................................................... 46
Transformers.................................................................................................................... 46
Light Bulb Replacement................................................................................................. 46
Schematics ............................................................................................................................ 49
Refrigeration System............................................................................................................ 55
Inverter Compressor........................................................................................................ 55
Inverter............................................................................................................................. 57
Accumulator .................................................................................................................... 59
System Pressure.............................................................................................................. 59
Refrigerant Charge ......................................................................................................... 59
Drier.................................................................................................................................. 60
Evaporator ....................................................................................................................... 60
Diagnostic Mode ................................................................................................................... 61
Compressor Not Running Flowchart.............................................................................. 62
Warranty ................................................................................................................................63
– 4 –
Technical Data
CONDENSER
LOOP
PROCESS
TUBE
COMPRESSOR
*ACCUMULATOR
CONDENSER
HEAT EXCHANGE
EVAPORATOR
HIGH PRESSURE
(DO NOT USE)
*INVERTER
DRYER
CONDENSER FAN
(SEE NOTE)
Note: Fan blade mounted for maximum airflow with 1/2" of shaft exposed. *Approximate location (Inverter and Accumulator).
WARNING: Disconnect power cord before servicing. Note: Reconnect all grounding devices. All parts of this appliance capable of conducting electrical current are grounded. If grounding wires, screws, straps, clips, nuts, or washers used to complete a path to ground are removed for service, they must be returned to their original positions and properly fastened. Caution: To avoid personal injury when servicing the condensing unit, stand on a ladder which will give enough support to allow removal of the top panel and safely allow access to service the unit.
ELECTRICAL SPECIFICATIONS
Max Defrost Control
W/No Door Openings ............60 hrs @ 35 min
Evap. Overtemperature Thermodisc ..............60 °F - 45
°F
Light Thermostat .....................................140 °F - 90 °F
Electrical Rating: 115 VAC 60 Hz.....................9.0 amp
Maximum Current Leakage............................ 0.75 mA
Maximum Ground Path Resistance ............ 0.14 ohms
Energy Consumption (HUMID) ................................. *
NO LOAD PERFORMANCE
Important Safety Notice:
This information is intended for use by individuals possessing adequate backgrounds of electrical, electronic, and mechanical experience. Any attempt to repair a major appliance may result in personal injury and property damage. The
manufacturer or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
REFRIGERATION SYSTEM
Compressor ...............................................833 Btu/hr
Minimum Compressor Capacity
Vacuum .......................................... 22 inches
Minimum Equalized Pressure
@ 70 °F...........................................65/65 PSIG
@ 90 °F...........................................79/80 PSIG
Refrigerant Charge (R134a) .............................12.50 oz
CONTROL POSITION 37-0 °F and AMBIENT TEMPERATURE OF
70 °F 90 °F
Fresh Food, °F ....................... 35–39 .............. 37–48
Frozen Food, °F ..................... (-4)–4 .............. (-4)–4
Percent Running Time............. 60 .................... 80
REFRIGERA TION DIAGNOSIS
To access the low-pressure side of the system, install a WR86X0097 valve only on the process tube extending from the compressor case.
TO CABINET
WIRING
COMMUNICATION
SIGNAL
*
Models ZIS360 - 45.58 kWh/mo. ZIS 360D - 48.67 kWh/mo. ZIS 420 - 47.08
kWh/mo. ZIS 420D - 51.83 kWh/mo. ZIS 480 - 49.33 kWh/mo. ZIS 480D -
56.50 kWh/mo.
**
Models ZIS360 - WR55X10166. ZIS 360D - WR55X10165. ZIS 420 ­WR55X10164. ZIS 420D - WR55X10163. ZIS 480 - WR55X10162. ZIS 480D ­WR55X10158.
RED
WHITE
GREEN/YELLOW
GROUND
ORANGE
INVERTER
BLACK
BROWN BLUE BLACK
GREEN/YELLOW
COMPRESSOR
GROUND
REPLACEMENT PARTS
HMI Temperature Control..........................................**
Overtemperature Thermodisc Light .......... WR50X10035
Overtemperature Thermodisc Evaporator .. WR50X10036
Defrost Heater ....................................... WR51X10065
Drain Trough ASM .................................. WR17X11194
Condenser Fan Motor ............................ WR60X10083
Condenser Fan Blade ............................ WR60X10049
Evaporator Fan Motor ............................ WR60X10043
Evaporator Fan Blade ............................ WR60X10050
Main Board ........................................... WR55X10400
Thermistors (2-FF , 1-FZ, 1-EV) ............... WR55X10025
Damper Assembly Fresh Food ............... WR60X10085
Evaporator ............................................ WR84X10038
Compressor .......................................... WR87X10064
Condenser............................................. WR84X10037
Filter Drier ............................................. WR86X0096
Inverter ................................................ WR55X10155
Accumulator ......................................... WR02X11264
– 5 –
Model Nomenclature
ZI
Brand/Product
Z - Monogram
Style
I - Built-In
Configuration
S - Side by Side
Color
S - Stainless B - Black W - White Blank - Trim Model
Size
480 - 48 Inches Wide
S
S
480
N
RA
LH
Door T ype
F - Flat R - Right L - Left Door Swing
Engineering
A - Initial Design B - 1st Revision C - 2nd Revision D - 3rd Revision Etc.
Model Year
R - 2004
Icemaker/Exterior
N - Nondispenser D - Dispenser
Mini-Manual and Rating Plate
Mini-Manual The mini-manual is located behind the grille panel at the top of the refrigerator. When done, return the mini-manual to its original location for future use.
Rating Plate
The rating plate, located behind the grille panel at the top of the refrigerator on the right side of the evaporator box, contains the model and serial numbers. Additionally, the rating plate specifies the minimum installation clearances, electrical voltage, frequency , maximum amperage rating, refrigerant charge, and type.
Serial Number
The first two numbers of the serial number identify the month and year of manufacture.
Example: AG123456S = Januar y, 2004
A
- JAN 2005 - H D - FEB 2004 ­F - MAR 2003 - F G - APR 2002 - D H - MAY 2001 - A L - JUN 2000 - Z M - JUL 1999 - V R - AUG 1998 - T S - SEP 1997 - S T - OCT 1996 - R V - NOV 1995 - M Z - DEC 1994 - L
G
The letter designating the year repeats every 12 years.
Example:
T - 1974 T - 1986 T - 1998
– 6 –
Component Locator Views
Master Light Switch
Inverter
Compressor
Figure 1 - Machine Compartment
Accumulator
Evaporator
Defrost Heater
Evaporator Thermistor
Evaporator Overtemperature Thermodisc (TOD)
Figure 2 - Evaporator (T op of Freezer)
– 7 –
Water Valve
Evaporator Fan Motor
Evaporator Fan
Connector
Figure 3 - Water V alve
(Center of Machine Compartment)
Figure 4 - Evaporator Fan
Circuit Breakers
Housing Under Center of Unit
Transformers
Figure 5 - Light Circuit Transformers
– 8 –
Freezer
Door Switch
Icemaker
Fresh Food
Door Switch
Temperature Touch Pad
Damper
Airflow Grille
Auger Drive
Freezer Thermistor
Water Filter
Cube Solenoid
Fresh Food Thermistors
Lower Fresh Food Lights
Temperature Overload Device (TOD)
Figure 6 - Freezer Compartment
Temperature Overload Device (TOD)
Climate Control Drawer Dampers
Figure 7 - Fresh Food Compartment
– 9 –
Climate Control Drawer Fan
Cabinet
The outer case is made of pre-painted galvanized steel. The fresh food and freezer liners are painted metal with a smooth finish. The liners are not removable or replaceable.
Machine Compartment
The machine compartment is located on the top of the unit and has a movable chassis that can be extended from the front of the unit to provide access to the refrigeration system components.
Caution: Avoid kinking the refrigeration lines when sliding the chassis out and back in.
To extend the chassis:
1. Remove the grille panel by removing 2 screws from each side (see photo).
2. Remove the wire guard and rocker switch panel.
3. Remove the condenser baffle.
Machine Compartment
The Master Light Switch is located behind the grille panel.
2 Screws
Inverter
4. Loosen the front 7/16-in. track bolts (1 on each side of the compressor) from the front of the chassis track.
5. Remove the rear 7/16-in. track bolts (1 on each side of the compressor) and the spacers under the rear of the chassis track.
6. Pull the chassis forward until it reaches the stops in the tracks, working the refrigeration tubing as you pull the chassis out.
Note.
When sliding the chassis back into position, be certain the lines and wiring have not fallen behind the chassis.
Use the grille screws for adjustment when realigning the grille.
Track Bolts
Chassis
– 10 –
Door Closure Mechanism
Doors and Hinges
The door closure mechanism uses a spring to provide positive door closure from approximately 60 degrees. The door closure mechanism actuator arm has a spring attached to the rear and is supported by guide rollers on either side of the base channel. The roller circumferences and the actuator arm detents are matched for smooth operation. The arm is attached to the door with an Allen head shoulder bolt.
The closure mechanism allows easy opening to approximately 90 degrees, where the arm has a detent to permit the door to remain open at 90 degrees with minimal tension. Once the door is opened beyond 90 degrees, the closure mechanism pulls the door open until the closure arm engages the door stop at approximately 130 degrees (factory setting, the door stop can be field set to 90 degrees). The reverse action occurs when the door is closed.
Note: The actuator arm is spring loaded with moderate spring tension.
1. Disconnect the spring from the pin and the actuator arm.
2. Remove the 3/16-in. Allen head bolt, bushing, and spacer from the door and actuator arm.
Door
Hinge
Pin
Spring
The doors are of one-piece construction with foam insulation.
The inner door panel and outer door panel cannot be separated and must be replaced as an assembly.
Door Adjustment Be sure the top hinge does not hit the cabinet trim.
Adjust the door up or down by turning the threaded hinge pin on the bottom hinge of the fresh food door.
The upper hinge on the freezer door is slotted to allow the freezer door to be adjusted left or right.
Door Removal WARNING: Use the appropriate safety equipment
and lifting techniques. Two persons may be required for door removal.
Caution: Use wood or a heavy plastic sheet to protect the floor where the door will be placed.
1. Remove all food and bins from the inner door liner and tape door to cabinet.
2. Disconnect the spring from the pin and the actuator arm.
3. Remove the Allen head bolt, bushing, and spacer from the door and actuator arm.
4. If removing the freezer door, shut of f the water supply , and disconnect the water line and electrical connector.
3/16"
Bolt
Allen Head
Bolt
GEA01267
5/16"
Actuator
Arm
Roller
Assembly
3. Remove 2 screws and the roller assembly from the rail. Replace roller if excessively worn.
5. Remove the upper hinge.
6. Lift door up and out to remove.
– 11 –
Hex Nut
Wheel
Leveling Leg
Lower Door Hinge Note: If replacing lower door hinge, note the
placement of the door stop (pin).
Hinge
1. Remove the door. Note: Note the placement of spacers and washers for
reassembly.
2. Remove 3/8-in. hex screws (4) and hinge from the underside of the cabinet.
3. Remove T-27 Torx screws (4) and hinge from the bottom of the door .
Door Gaskets
The fresh food and freezer doors have magnetic gaskets that create a positive seal to the front of the steel cabinet. The center mullion also has magnets to assist in door sealing. Improper installation of the door gasket will cause same-poled magnets to oppose one another, preventing the door from closing tightly.
The magnetic door gaskets are secured to the doors by a barbed edge that locks into a retainer channel. The side of the gasket that is nearest the handle of the door has a stripe on the inside of the barb (see photo).
Base Channel Spacer
Hinge
Door Stop
Bushing
5/16"
Bolt
GEA01268
Replacement
1. St arting at any corner , pull the old gasket out of the retaining channel.
2. Soak the new gasket in warm water to make it pliable.
3. Push the barbed edge of the gasket into the retainer channel.
Rollers and Leveling
This model has 4-point leveling provided by adjustable rollers on the rear and leveling legs on the front. It also has 2 nonadjustable front rollers that are used only for unit positioning.
T o level the unit:
1. Turn the 7/16-in. hex nut, located above the front rollers, to adjust the roller on the rear of the unit. Turn clockwise to raise, counterclockwise to lower.
2. Turn the front legs with a 1-1/4 wrench to adjust the front of the unit. T urn clockwise to raise, counterclockwise to lower.
in. open end
Stripe
(Handle Side of Door)
– 12 –
Ice and W ater Dispenser
Icemaker
Feeler Arm
Power Switch
Green
Power Light
The icemaker is mounted to the upper left wall of the freezer cabinet. Under normal operating conditions, temperatures, door openings, and food load, the icemaker is capable of producing approximately 100 to 130 cubes in a 24-hour period.
To service the icemaker, refer to GE Publication 31-9063.
Controls
The electronic controls on the dispenser are interactive. The control panel is equipped with a proximity sensor that causes the panel to light up as you approach the dispenser (approx. 2 inches).
Removal
I = On
0 = Off
1. Remove the bezel from the outside of the freezer door.
Note: On stainless steel models, the front panel must be removed. Remove screws from top, bottom, and hinge side. Pull out on hinge side.
2. Remove the screw from the bottom of the control panel. Lift up and pull the bottom of the panel out. Disconnect the connectors, and remove the control panel.
3. Remove 4 screws and the backing panel.
4. From the back side of the panel, remove the water switch and the light socket.
5. Remove 3 screws and the duct door solenoid.
Screw
4 Screws
Duct Door Solenoid
Light Socket
Water Switch
– 13 –
Water V alve and Water Tank
The water valve is mounted in the left side of the machine compartment.
A plastic water line is routed from under the unit, up the back of the cabinet, into the machine compartment, and to the water filter . A line then goes from the water filter to the water valve.
Two low-pressure plastic water lines supply water to the icemaker and door dispenser from the water valve. A plastic water line is routed from the water valve, out the back of the machine compartment, down the back of the cabinet through the bottom of the unit, and into the fresh food compartment where it is attached to the cold water tank. A line is routed from the cold water tank through the bottom of the unit into the freezer door to supply the water dispenser. The icemaker water line is routed from the water valve through the machine compartment to the icemaker. The icemaker fill tube is also plastic.
Note: No water filter should be installed if home has in-home water filtration system (reverse osmosis filter system, etc.) Replace filter with by­pass plug.
Water Valve
Screw
Screw
To Replace the W ater Valve Note: Some water may leak from the water supply
line and valve when they are disconnected.
1. Shut off the water supply to the unit.
2. Open the grille panel.
3. Remove 1 Phillips screw attaching the water valve to the filter bracket.
4. Disconnect the wiring harness connector and 3 water lines from the water valve and remove.
To Replace the Chilled Water Tank Note: Some water may leak from the water supply
line and valve when they are disconnected.
1. Shut off the water supply to the unit.
2. Remove 2 screws and the chilled water tank cover inside the fresh food compartment.
3. Remove 2 screws from the chilled water tank.
Screws
Water Tank Cover
Chilled Water Tank
4. Cut the water lines leaving enough line to reconnect. Use union WR02X10471 (5/16 x 5/16).
– 14 –
Airflow
r
Damper
The fresh food compartment receives chilled air via an electronic damper that is positioned at the top rear of the fresh food compartment. The damper is controlled by the main control board and when open, allows the evaporator fan to push chilled air from the evaporator into the fresh food compartment.
To Remove the Damper
1. Remove the light cover .
3. Remove the Styrofoam section covering the damper.
4. Disconnect the damper wiring connector.
Damper
2. Remove 4 Phillips screws and the light assembly.
Evaporator
Evap.
Fan
Duct
Entrance
Front FrontBack Back
Duct
Exit
Foam
5. Carefully pull the damper out of the mullion and remove.
Top
Return
Dampe
Air Tower
BottomFreezer Side Fresh Food Side
– 15 –
Fans
Evaporator Fan
The position of the fan blade in relation to the shroud is important. Refer to illustration for specifications.
5/16 +/- .03
Airflow
The evaporator fan is the same fan used on previous models; however a significant difference is that the main control board does not require, nor receive, input from the fan feedback/rpm (blue) wire. The fan utilizes a permanent magnet, 4-pole, DC motor that operates at three different speeds: high, medium, and low . The speed of the fan is controlled by the voltage output from the main control board. V oltage output from the control board to the fan is 13.2 VDC; however to regulate the speed of the fan, the main control board uses pulse width modulation (PWM). When operating, voltage is sent in pulses (much like a duty cycle) as opposed to an uninterrupted flow. This pulsing of 13.2 VDC produces ef fective volt age being received at the motor, which is the equivalent to a reduction in volt age. Fan speed will be selected and maintained by the main control board regulating the length and frequency of the 13.2 VDC pulse.
One complete revolution of the motor is comprised of all 4 poles. To determine the rpm of the fan, do the following: Measure the frequency being applied to the motor. Multiply this number by 15 (60 seconds divided by 4 poles). For example, a frequency measurement of 200 Hz multiplied by 15 would show a fan speed of 3000 rpm (15 x 200 = 3000). Temperature may cause some fan speed variation. Fan speed may vary +/- 5%, depending on the temperature, with higher temperatures causing slightly higher speeds.
12 VDC
12 VDC
0 VDC
High Speed (12 VDC measured)
12 VDC
9.2 VDC
0 VDC
Medium Speed (9.2 VDC measured)
12 VDC
8 VDC
0 VDC
Low Speed (8 VDC measured)
EVAPORATOR FAN SPEEDS
– 16 –
If the fan shorts, it may damage the main control board. If the resistor on the main control board is burnt, you must replace the fan and the board (see photo).
Evaporator Fan Adjustment
Evaporator and Condenser Fan Resistors
Damper - Yellow
Damper - Red
Damper - White
Comm. 2-Way Digital
J2
1
EARTH
J4 or J16
Comm. Common
Comm. +12V
Damper - Blue
5
1
J3 or J10
1
J15
Inverter Output
Inverter Common
1
J2 or J13
Fan Common
Condenser Fan
Evaporator Fan
Evaporator Fan Tach.
1
J6
2
FF2 Thermistor
FF1 Thermistor
1
10
J1 or J14
J5
1
8
Fan +12V
Custom Cool Fan
Custom Cool Damper1 +
J19
Evaporator Thermistor
FZ Thermistor
Custom Cool Damper1 -
+5V
9
6
+5V
Custom Cool Thermistor
5/16 +/- .03
Airflow
Condenser Fan Resistor
Evaporator Fan Resistor
EARTH
K7
K4
DEFROST
Defrost Heater
Line (L1)
Not Used
J8
J9
J11
J1
J7
Neutral
K5
J12
J18
Not Used
FF Door Switch
FZ Door Switch
Custom Cool Heater
Auger Motor Interlock
CUSTOM COOL
Drain Pan Heater
Water Valve
Some of the low voltage DC
PAN
HEATER
K3
WATER
K2
CRUSHER
K1
AUGER
1
Auger Motor
Crusher Solenoid
J4 or J16
J3 or J10
J1 or J14
connector labeling on this model may differ from other models. The
J2 OR J13
function and diagnostics for these connectors are identical for all models.
– 17 –
White Wire (DC Common) The white wire is the DC common wire used for
testing. During repairs, DC polarity must be observed. Reversing the DC polarity will cause a shorted motor and/or board.
Red Wire (Supply) Each motor uses an internal electronic controller
to operate the motor. Supply volt age from the main control board remains at a constant 12 VDC.
Blue Wire (Feedback/RPM) The blue wire feeds rpm (speed) information to
the main control board, allowing the board to maintain consistent fan speeds. Loss of feedback from the blue wire will result in the fan accelerating to maximum speed. Measure the fan rpm using the frequency between the blue and white wires.
Comm. 2-Way Digital
J2
1
EARTH
J4 or J16
Comm. Common
Comm. +12V
5
J15
Damper - Red
Damper - White
Damper - Blue
1
J3 or J10
1
J2 or J13
Inverter Output
Inverter Common
Damper - Yellow
10
1
Fan Common
Condenser Fan
Evaporator Fan
Custom Cool Fan
Evaporator Fan Tach.
FZ Thermistor
FF2 Thermistor
FF1 Thermistor
1
J1 or J14
J5
1
8
Fan +12V
Custom Cool Damper1 +
Custom Cool Damper1 -
+5V
Evaporator Thermistor
9
6
+5V
Custom Cool Thermistor
High speed - 205 to 215 Hz (3140 RPM) Medium speed - 155 to 165 Hz (2415 RPM) Low speed - 140 to 150 Hz (2160 RPM)
Yellow Wire (Signal) The yellow wire is the input wire from the main
control board. The main control board provides 8 VDC effective voltage for low speed, 9.2 VDC effective voltage for medium speed, and 12VDC for high speed. The fan will operate in low speed only when the fresh food thermistor is satisfied.
Note: When testing these motors:
• You cannot test with an ohmmeter.
• DC common is not AC common.
• Verify 2 volt age potentials: a. Red to white - power for internal controller.
b. Yellow to white - power for fan.
• Observe circuit polarity.
• Motors can be run for short periods using a 9-volt battery . Connect the white wire to the negative (-) battery terminal only. Connect the red and yellow wires to the positive (+) battery terminal.
EARTH
J19
1
J6
2
K7
K4
DEFROST
Defrost Heater
Line (L1)
Not Used
J8
J9
J11
J1
J7
Neutral
K5
J12
J18
Not Used
FF Door Switch
FZ Door Switch
Custom Cool Heater
Auger Motor Interlock
CUSTOM COOL
Drain Pan Heater
Water Valve
PAN
HEATER
K3
WATER
K2
CRUSHER
K1
AUGER
1
Auger Motor
Crusher Solenoid
Some of the low voltage DC connector labeling on this model may differ from other models. The function and diagnostics for these connectors are identical for all models.
– 18 –
J4 or J16
J3 or J10
J2 OR J13
J1 or J14
To Remove the Evaporator Fan
1. Remove the ice bucket.
2. Disconnect the icemaker connector. Loosen 2 screws and remove icemaker.
3. Remove 4 screws and slide the icemaker drive motor assembly forward. Disconnect the wiring connector and remove the assembly.
Screws
Icemaker Drive Motor Assembly
Screws
5. Remove 2 screws and wiring cover.
6. Remove 6 screws and evaporator fan cover.
Wiring Cover
Evaporator Fan Cover
Screws
Screws
– 19 –
7. Disconnect the evaporator fan wiring connector.
8. Remove 2 screws from the fan mounting bracket and remove the fan.
Condenser Fan
The condenser fan is a permanent-magnet, 4­pole, DC motor that will operate at 3 speeds. Fan speed (low, medium, high) corresponds with compressor speed to minimize pressure variations in the sealed system. The speed of the fan is controlled by the voltage output from the main control board. V oltage output from the control board to the fan is 13.2 VDC; however to regulate the speed of the fan, the main control board uses pulse width modulation (PWM). When operating, voltage is sent in pulses (much like a duty cycle) as opposed to an uninterrupted flow. This pulsing of 13.2 VDC produces effective voltage being received at the motor , which is the equivalent to a reduction in voltage. Fan speed will be selected and maintained by the main control board regulating the length and frequency of the
13.2 VDC pulse. .
Evaporator Fan
Screws
Wire Connector
To Remove the Fan
1. Extend the chassis (see Machine Compartment in the Cabinet chapter).
2. Pull the blade off the motor shaft.
3. Cut the wire tie securing the fan wiring to the fan bracket.
Caution: Fan connector can be separated into 3 segments (center, left side, and right side). Disconnect the fan connector at the center only.
4. Disconnect the fan connector.
5. Feed wiring through the hole in the fan shroud.
6. Remove 2 screws, top section of fan bracket, and motor.
– 20 –
Fan Bracket
Fan Bracket
Condenser Fan Motor
Screws
Defrost System
Adaptive Defrost
Adaptive Defrost can be described as a defrost system that adapts to a refrigerator’s surrounding environment and household usage.
Unlike conventional defrost systems that use electromechanical timers with a fixed defrost cycle time, Adaptive Defrost utilizes an intelligent, electronic control to determine when the defrost cycle is necessary. In order to accomplish the correct defrost cycle time, the main control board monitors the following refrigerator operations:
Length of time the refrigerator doors were open
since the last defrost cycle
Length of time the compressor has run since the last defrost cycle
Amount of time the defrost heaters were on in the last defrost cycle
Adaptive Defrost is divided into 4 separate cycles. Those operations are:
Cooling Operation
Adaptive Defrost (Pre-Chill Operation) When the main control board determines that
defrost is necessary, it will force the refrigerator into a continuous cool mode (pre-chill). During pre­chill, the freezer temperature may be driven below the set point. However, the fresh food temperature will be regulated by the evaporator fan running at low speed. Pre-chill will last for 30 minutes. These models do have an 8-hour defrost hold-off.
Adaptive Defrost (Defrost Heater Operation) After 30 minutes of pre-chill operation, the main
control board turns off the compressor, condenser fan, and evaporator fan.
During defrost operation, the main control board monitors the evaporator temperature using evaporator thermistor inputs. T ypically, the evaporator thermistor will sense a temperature of 45 °F within 16 minutes. When the thermistor senses 45 °F, the main control board will terminate defrost heater operation. Maximum defrost cycle (heater on) time is 35 minutes (main control board time out).
Pre-Chill Operation
Defrost Heater Operation
Dwell Period
(See Pub. #31-9062 for more information on Adaptive Defrost.)
Adaptive Defrost (Cooling Operation) During the cooling operation, the main control
board monitors door opening (fresh food door and freezer drawer) and compressor run times. The board counts the time the doors are open. It reduces the length of time between defrosts by 300 seconds (multiplication factor) for each second that each door is open (if both doors are open, it reduces it by twice the amount). The multiplication factor reduces compressor run time. If the doors are not opened, the compressor will run up to 60 hours between defrosts. If the doors are opened frequently and/or for long periods of time, the compressor run time between defrosts will be reduced to as little as 8 hours.
The defrost system is protected by a defrost overtemperature thermodisc (bimetal switch). The thermostat opens when the evaporator temperature raises to 60 °F and closes when the evaporator temperature lowers to 45 °F.
Adaptive Defrost (Dwell Period) After defrost heater operation has been terminated
by the main control board, a 20-minute dwell period occurs. During this period, the compressor, condenser fan, and evaporator fan remain off. The remaining frost melting from the evaporator will continue to drip and drain so that, prior to the cooling operation, the evaporator will be totally clear of any moisture. The pan heater is on for the entire 20 minute dwell period.
Normal Operating Characteristics
The fill tube heater is on when the defrost heaters are on.
Pan heaters are on when the defrost heaters are on and during dwell period (25 minutes plus defrost time).
– 21 –
Defrost Heater
Caution: Use care to avoid scratching the finish
on unit walls. The defrost heater is a single calrod-type, radiant
heater mounted on the evaporator . To remove the defrost heater:
1. Remove the evaporator fan (see Evaporator Fan procedure in the Airflow chapter).
2. Remove 8 screws and freezer ceiling panel.
3. Remove Styrofoam insulation from the bottom of the evaporator drain pan.
4. Loosen evaporator drain hose clamp.
5. Lower left side of evaporator drain pan and slide right side out of drain hose and remove.
6. Disconnect the heater wiring.
Styrofoam Insulation
Evaporator Drain Pan
Hose Clamp
7. Remove 2 screws from the left and right heater fasteners.
8. Slide the heater toward the front of the freezer compartment and remove.
Heater
Screws
– 22 –
Evaporator Thermistor
The evaporator thermistor is mounted on the upper left side of the evaporator. The defrost cycle will terminate when the main control board detects 45 °F from the evaporator thermistor. The main control board must sense 45 °F in less than 35 minutes, or the defrost cycle will time out. Average time to defrost is less than 16 minutes. Defrost time should not exceed 35 minutes. Defrost time does not include dwell period.
Defrost Overtemperature Thermodisc
The defrost overtemperature thermodisc (bimetal switch) is mounted on the evaporator and provides overtemperature protection during defrost. This thermostat will open at 60 °F and will close at 45 °F.
Evaporator Thermistor
Note: The main control board will not know if the
heater does not come on due to a broken heater, open defrost overtemperature thermodisc, or open wiring harness. The defrost heater is controlled by maximum time on the main control board or temperature at the evaporator thermistor.
Defrost Overtemperature Thermodisc
– 23 –
Control System
Touch Panel and Temperature Control Board
The temperature control assembly is located at the top front of the fresh food compartment and contains the touch panel and temperature control board.
The temperature control board receives switched DC voltage from the main control board. Input consists of pins 2 to 3. Failure of input results in default to most recent setting. Pin 1 provides digital communication between the temperature control board and the main control board. Failure of communication results in erratic control.
To remove the temperature control assembly:
1. Remove the light cover .
2. Remove 4 Phillips screws and the light assembly.
Temperature Control Assembly
Light Assembly
Touch Panel
Note: Temperature control assembly is mounted on 3 slotted fasteners. Fasteners do not need to be loosened or removed.
3. Cut the RTV around the edge of the temperature control assembly.
Note: Old RTV must be removed from the inside of the fresh food compartment and from the temperature control assembly. RTV 102 must be put in place when the temperature control panel is installed.
4. Disconnect the temperature control assembly wiring connector.
5. Slide the temperature control assembly back to release it from the slotted fasteners and lower the assembly.
6. Disconnect the wiring connector from the temperature control board.
7. Slide the touch panel out of the temperature control assembly.
Screws
8. Remove 2 screws and the temperature control board.
– 24 –
Thermistors
This main control board uses input from 4 thermistors. These thermistors are located in the fresh food section, the freezer section, and on the evaporator. The main control board monitors the thermistors to determine the temperature in these areas of the unit and determines which components to run and when to run them based on this information.
Thermistors can also be checked using diagnostic mode.
seulaVrotsimrehT
erutarepmeT
)C(seergeD
04-04-k8.661 03-22-k88 02-4-k4.84 01-41k6.72
023k3.61
0105k01 0286k2.6 0368k4
04401k6.2
05221k8.1 06041k2.1
erutarepmeT
)F(seergeD
ecnatsiseR
smho-oliKni
Note: The thermistor’s resistance has a negative coefficient. As the temperature increases, the thermistor’s resistance decreases.
– 25 –
Main Control Board
The main control board, located behind a metal cover at the top of the refrigerator in the machine compartment, manages the operation of the refrigerator by calculating response from various inputs.
Damper - White
Damper - Red
Damper - Blue
Comm. 2-Way Digital
J2
1
EARTH
J4 or J16
Comm. Common
Comm. +12V
5
1
J3 or J10
Damper - Yellow
10
FF2 Thermistor
FF1 Thermistor
FZ Thermistor
1
J1 or J14
+5V
Evaporator Thermistor
9
J1 or J14
J2 OR J13
J3 or J10
J4 or J16
Some of the low voltage DC
connector labeling on this model
may differ from other models. The
function and diagnostics for these
connectors are identical for all
models.
1
J15
Inverter Output
Inverter Common
1
J2 or J13
Fan Common
Condenser Fan
Evaporator Fan
Evaporator Fan Tach.
1
J6
2
K4
8
Fan +12V
Custom Cool Fan
J19
DEFROST
J5
1
6
+5V
Custom Cool Damper1 +
Custom Cool Damper1 -
K5
CUSTOM COOL
Custom Cool Thermistor
K7
PAN
K3
WATER
J12
HEATER
EARTH
J1
Not Used
J8
– 26 –
Defrost Heater
Line (L1)
J9
J11
J7
Neutral
J18
Not Used
Water Valve
FF Door Switch
FZ Door Switch
Custom Cool Heater
Auger Motor Interlock
Drain Pan Heater
CRUSHER
K1
K2
1
Auger Motor
Crusher Solenoid
AUGER
Main Control Board Locator Tables
ROTCENNOC NIP TUPNI TUPTUO NOITCNUF
Feedback of fresh food thermistor value. Thermistor is NTC, when temperature drops, resistance
J1 or J14 CDV
J1 or J14
1
2
J1 or J14 3
J1 or J14
4
CDV
CDV
CD
V
value increases, causing return voltage reduction. This value is used to cycle fresh food fan (when used), evaporator fan, compressor, and condensor fan. Feedback is filtered to respond to 8 degrees of change per minute.
Feedback of second fresh food thermistor value (when used). Thermistor is NTC, when temperature drops, resistance value increased, causing return voltage reduction. This value is used to cycle fresh food fan (when used), evaporator fan, compressor, and condensor fan. Feedback is filtered to respond to 8 degrees of change per minute.
Feedback of freezer thermistor value. Thermistor is NTC, when temperature drops, resistance value increases, causing return voltage reduction. This value is used to cycle evaporator fan, compressor, and condensor fan, and will not cycle fresh food fan (when used). Feedback is filtered to respond to 8 degrees of change per minute.
Feedback of evaporator thermistor value. Thermistor is NTC, when temperature drops, resistance value increases, causing return voltage reduction. This thermistor value is used to cycle the heater on during defrost when temperature is below defrost value and off when the temperature is above defrost value. This value is also read during power-up to determine if refrigerator goes into pulldown mode or cycle continuation. Feedback is unfiltered, responds immediately.
SNOITINIFEDNIPDRAOBLORTNOC
J1 or J14
ROTCENNOC NIP TUPNI TUPTUO NOITCNUF
J2 or J13
J2 or J13
J2 or J13 4
J2 or J13 7
J2 or J13
ROTCENNOC NIP TUPNI TUPTUO NOITCNUF
5
1
3
5J2 or J13
8
zH
Provides 5 VDC for thermistors and personality pins on J1.VDC
.sdeeps
CDV.dnuorgCD
CDV .MWPybdenimretedsiegatlovevitceffE.noitareporotomrofnafrotaropaveottuptuO
CDV
CDV
CDV. e.gatlovtnatsnoc,snafllaotegatlov
.MWP
V-nommocnaF
.MORPEEni
ylppusCDV-21sedivorP
SNOITINIFEDNIPDRAOBLORTNOC
nafrofMWPehtlortnocotdesusiycneuqerfkcabdeefsihT.nafrotaropavemorfkcabdeeF
PybdenimretedsiegatlovevitceffE.noitareporotomrofnafrosnednocottuptuO
vevitceffE.noitareporotomrofnaf)llihCkciuQ(llihCsserpxEottuptuO
SNOITINIFEDNIPDRAOBLORTNOC
tesdeeps,MW
ybdenimretedsiegatlo
J3 or J10
J3 or J10
J3 or J10
J3 or J10
1
2
3
4
CDV.rotomreppetsrepmaD
CDV.rotomreppetsrepmaD
CDV.rotomreppetsrepmaD
CDV.rotomreppetsrepma
D
– 27 –
ROTCENNOC NIP TUPNI TUPTUO NOITCNUF
J4 or J16
J4 or J16
J4 or J16
5J1 CDV
5J2 CDV
5J5 CDV. rotsimreht)llihCkciuQ(llihCsserpxErofCDV5sedivorP
5J6CDV
1
2
3
ROTCENNOC NIP TUPNI TUPTUO NOITCNUF
latigiD
SNOITINIFEDNIPDRAOBLORTNOC
noitacinummoC
latigiD
noitacinummoC
CDV.ylppusCDV-21
CDV.nommocC
D
oclatigidyaw-owT
SNOITINIFEDNIPDRAOBLORTNOC
erpxenehwdnuorgCDV-nommoC
deragnisuac,sesaercnieulavecnatsiser
SNOITINIFEDNIPDRAOBLORTNOC
.draobllihCkciuQdna,draobresnepsid,)draob(
.detcelessiwahtss
lihCkciuQ(llihCsserpxEnehwdnuorgCDV-nommoC
.egatlovnruterninoitcu
.detcelessiwahTsserpxEnehwrepmadrewarDlortnoCetamilCotCDV21
.detcelessi)l
lortnocerutarepmet,draoblortnocniamneewtebnoitacinumm
.detcelessi)llihCkciuQ(llihCsserpxEnehwrepmadrewarDlortnoCetamilCotCDV21
,sp
orderutarepmetnehw,CTNsirotsimrehT.rotsimreht)llihCkciuQ(llihCsserpxEfokcabdeeF
ROTCENNOC NIP TUPNI TUPTUO NOITCNUF
7J1 CAV. CAV021-rotomreguaehtotegatlov1LdehctiwS
7J2 CAV. CAV021-dionelosrehsurcehtotegatlov1LdehctiwS
7J3 CAV. C
7J4CAV .desolcsiroodrezeerfnehwhctiwsroodrezeerfmorftupni1Lseviece
7J5 CAV .CAV021-retaeh)llihCkciuQ(llihCsserpxEehtotegatlov1LdehctiwS
7J6CAV
7J7CAV
7J9CAV.nilartuenC
R
enil,lortnocnafrotaropaverof
.snoitaluclactsorfedevitpada
,lortnocnafrotaropaverof
a
A
AV021-evlavretawehtotegatlov1LdehctiwS
hctiwsnehwhctiwsrooddoofhserfmorftupni1LsevieceR
whctiwsroodrezeerfmorftupni1LsevieceR
desusitupnisihT.)neporood(sesolc
dna,snoitaluclacmralarood,snoitaluclacedomnoitcetorpr
desusitupnisihT.)neporood(sesolchctiwsneh
rood,snoitaluclactsorfedevitpada,snoitaluclacedomnoitcetorprenil
desolcroodnidesolcebtsumhctiwS.snoitcnufkcolretniroodemosdna,snoitaluclacmral
.ezigreneottengamroodtcuddnathgilresnepsidrof)desserpedhctiws(noitisop
Some of the low voltage DC connector labeling on this model may differ from other models. The function and diagnostics for these connectors are identical for all models.
– 28 –
J4 or J16
J3 or J10
J2 OR J13
J1 or J14
SNOITINIFEDNIPDRAOBLORTNOC
ROTCENNOC NIP TUPNI TUPTUO NOITCNUF
J15
J15
1
2
VDC
Common
12V variable frequency square wave to control compressor speed.
Note: The J15 connector controls compressor speed through voltage AND frequency. When the main board calls for compressor operation, J15 output between pins 1 and 2 should be approximately 5 VDC with the harness connected and approximately 12 VDC with the harness disconnected. The voltage will not change regardless of compressor speed. A change in frequency controls the compressor speed.
SNOITINIFEDNIPDRAOBLORTNOC
ROTCENNOC NIP TUPNI TUPTUO NOITCNUF
9J1 CAV
ROTCENNOC NIP TUPNI TUPTUO NOITCNUF
11J1CAV .slanimret1LdehctiwsroflaitnetoptupniCAV021-stiucricdraoblortnocotegatlov1Ltnatsno
n
C
.evitpadano
lcyctsorfedtxenehtfienimretedotnoitamrofnisihtsesudnadezigrene
SNOITINIFEDNIPDRAOBLORTNOC
sitiucricsihtgnolwohstnuocremitA.CAV021-tiucrictsorfedehtotegatlov1LdehctiwS
roevitpadasie
ROTCENNOC NIP TUPNI TUPTUO NOITCNUF
21J1 CAV. retaehnapniardehtotegatlov1
Some of the low voltage DC
L
J4 or J16
connector labeling on this model may differ from other models. The function and diagnostics for these connectors are identical for all models.
SNOITINIFEDNIPDRAOBLORTNOC
J3 or J10
J2 OR J13
J1 or J14
– 29 –
Some of the low voltage DC connector labeling on this model may differ from other models. The function and diagnostics for these connectors are identical for all models.
J4 or J16
niP roloCeriW tuptuO/tupnI gnidaeRegatloVniP-ot-niP
J3 or J10
J2 OR J13
J1 or J14
11J,9J,8JdraoBlortnoCniaM
)ediSegatloV-hgiH(srotcennoC
9JdeRtuptu
11JnworBtupn
21JkcalBtuptu
O
I
O
– 30 –
AV021=9nip7Jot9J
AV021=9nip7Jot11J
ot21J
AV021=9nip7J
niP roloCeriW tnenopmoC
1deRerutarepmeT
2nworBerutarepmeT
3egnarOerutarepmeT
draoBlortnoCniaM
)ediSCDegatloV-woL(rotcennoC4J
noitanimreT
lortnoc
lortnoc
lortnoc
tuptuO/tupnI gnidaeRegatloVniP-ot-niP
noitacinummoCnoitacinummoclatigidyaw-owT
eewteb
CDV.ylppusCDV-
CDV.nommocCD
,draoblortnocniamn
,)draob(lortnocerutarepmet
dna,draobresnepsid
.draobllihCkciuQ
21
draoBlortnoCniaM
)ediSCDegatloV-woL(rotcennoC3J
niP roloCeriW tnenopmoC
1eulBrotoMreppetSrepmaD=3nip4Jot1nip3J
2etihWrotoMreppetSrepmaD=3nip4Jot2nip3J
3deRrotoMreppetSrepma
4wolleYrotoMreppetSrepmaD=3nip4Jot4nip3J
D=3nip4Jot3nip3J
noitanimreT
/tupnI
tuptuO
rT
gnidaeRegatloVniP-ot-niP
CDV3.2egatloVgnidnatS
CDV0.6=egatloVgnileva
CDV3.2egatloVgnidnatS
CDV0.6=egatloVgnilevarT
CDV3.2egatloVgnidnatS
CDV0.6=egatloVgnilevarT
CDV3.
2egatloVgnidnatS
CDV0.6=egatloVgnilevarT
J2
EARTH
J4 or J16
niP roloCeriW tnenopmoC
1eulBnafrotaropavE
3etihWnommocnaFnommoCCDV21=8nipo
5
1
1
J3 or J10
1
J15
Inverter Output
Inverter Common
1
J2 or J13
Fan Common
Evaporator Fan
Evaporator Fan Tach.
10
J1 or J14
8
Fan +12V
Condenser Fan
Custom Cool Fan
noitanimreT
retemohcat
1
J5
1
+5V
Custom Cool Damper1 +
Custom Cool Damper1 -
draoBlortnoCniaM
/tupnI
tuptuO
tupnICDV3.6=3nipot1nip2J
9
6
Custom Cool Thermistor
K2
)ediSCDegatloV-woL(rotcennoC2J
niP roloCeriW tnenopmoC
1elpruPdoofhserF
2eulBdoofhserF
noitanimreT
1rotsimreht
2rotsimreht
3deRrotsimrehtrezeerFtupnI5.3ot8.2=5nipot3nip1J
4kcalBrotaropavE
5nworBylppusrotsimrehT
eriW
niP
roloC
1wolleY
2yarG
5nworB
6eulB
gnidaeRegatloVniP-ot-niP
t3nip2J
tnenopmoC
noitanimreT
llihCkciuQ
)looCmotsuC(
repmaD
llihCkciuQ
)looCmotsuC(
repmaD
ppuS
egatloVyl
)CDV5(
llihCkciuQ
)looCmotsuC(
rotsimrehT
rotsimreht
)CDV5(egatlov
/tupnI
tuptuO
/tupnI
tuptuO
/tupnI
tuptuO
tuptuOCDV5=3nip2Jot01nip5J
tupnIA/N
J4 or J16
J3 or J10
draoBlortnoCniaM
tupnI5.3ot8.2=5nipot1nip1J
upnI5.3ot8.2=5nipot2nip1J
t
I5.3ot8.2=5nipot4nip1J
tupn
draoBlortnoCniaM
1nip5J
J2 OR J13
/tupnI
tuptuO
tuptuOCDV5=3nip4Jot5nip1J
)ediSCDegatloV-woL(rotcennoC1J
gnidaeRegatloVniP-ot-niP
CDV
CDV
CDV
CDV
)ediSCDegatloV-woL(rotcennoC5J
gnidaeRegatloVniP-ot-niP
)ytiralopgnisrever(CDV21=2nipot
)ytiralopgnisrever(CDV21=1nipot2nip5J
J1 or J14
4wolleYnafrotaropavEtuptuOCDV6.21=3nipot4nip2J
)wol(CDV1.8
5kniPnafresnednoCtuptuOCD
6kcalBnafnapniarDdnuorGdnuorgCDV
7kcalBnafllihCkciuQnommoCCDV21=7
8deRegatlovylppusnaF
)CDV21(
tuptuOCDV21=3nipot8nip2J
V4.31=3nipot5nip2J
)deeps
nipot8nip2J
– 31 –
,).dem(CDV1.8,)hgih(
elgnissinafresnednoc(
Some of the low voltage DC connector labeling on this model may differ from other models. The function and diagnostics for these connectors are identical for all models.
Thermistors
This main control board uses input from 4 thermistors. These thermistors are located in the fresh food section, the freezer section, and on the evaporator. The main control board monitors the thermistors to determine the temperature in these areas of the unit and determines which components to run and when to run them based on this information.
seulaVrotsimrehT
erutarepmeT
)C(seergeD
04-04-k8.661 03-22-k88 02-4-k4.84 01-41k6.72
023k3.61
0105k01 0286k2.6
0368k4 04401k6.2 05221k8.1 06041k2.1
dooFhserF
lortnoC
gnitteS
erutarepmeT )F(seergeD
dooFhserF rotsimrehT
egnaRerutarepmeT
ecnatsiseR
smho-oliKni
trahCtnioPteSerutarepmeT
rezeerF
lortnoC
gnitteS
rotsimrehTrezeerF
egnaRerutarepmeT
muminiMmumixaMmuminiMmumixaM F°43F°23F°63F°5-F°01-F°0 F°53F°33F°73F°4-F°9-F°1 F°63F°4
3F°83F°3-F°8-F°2 F°73F°53F°93F°2-F°7-F°3 F°83F°63F°04F°1-F°6-F°4 F°93F°73F°14F°0F°5-F°5 F°04F°83F°24F°1F°4-F°6 F°14F°93F°34F°2F°3-F°7
24F°04F°44F°3F°2-F°8
F° F°34F°14F°54F°4F°1-F°9 F°44F°24F°64F°5F°0F°01 F°54F°34F°74F°6F°1F°11
– 32 –
Climate Control Drawer
The Climate Control Drawer can chill or thaw items quickly. It can also store items at their optimum temperatures. This Climate Control Drawer contains the following components:
Control Board
Thermistor
Dampers (2)
Fan
Heater
The main control board controls the dampers, fan, and heater based on input from the Climate Control Drawer’s control board and the thermistor.
The Climate Control Drawer compartment is sealed to reduce the effect that the drawer temperature has on the rest of the refrigerator . When the drawer features are not being used, the temperature inside the drawer will be the same as the fresh food compartment.
Strip Circuit
DAMPER
DAMPER
1
2
1
2
YELLOW
YELLOW
CONTROL
BOARD
(CONTROL HMI)
WHITE
WHITE
RED
1
BROWN
3
ORANGE
5
THERMISTOR
FAN
WHITE RED
RED
BROWN
ORANGE
BLUE
BROWN
GRAY
YELLOW
BLACK
Some of the low voltage DC connector labeling on this model may differ from other models. The function and diagnostics for these connectors are identical for all models.
J4 1 DATA
2 + 12 VDC
3 COM
J5
6
5
2
1
J2
8 +12 VDC
7 FAN
J4 or J16
MAIN
CONTROL
BOARD
HEATER 5
J3 or J10
J2 OR J13
J7
VIOLET ORANGE
HEATER
441 Ohms
J1 or J14
ORANGEORANGE
BROWN
EMI/RF
FILTER
GREEN
BROWN
AC POWER CORD
GEA01264
– 33 –
Component Locator View
Air Diffuser
Dampers
Fan
(in Fan Housing)
Light
Connector
Thermistor
(in Fan Housing)
Top Panel
(Mullion)
Heater
(in Fan Housing)
Fan Connector
9-Pin
Connector
Heater
Connector
Control Board (in T op Panel)
Climate Control Drawer compartment shown with top panel moved out
– 34 –
Operation
During all modes of operation, the main control board will cycle the dampers, fan, and heater as necessary to maintain the desired temperature. Typical operation is as follows:
Select Temp This feature maintains optimum temperatures for specific items. The CITRUS setting will maintain a drawer temperature of 43 °F by circulating warmed air or cooled
air as needed. The dampers will close and the heater will turn on if warmed air is required to maintain 43 °F. The dampers will open if cooled air is required.
The PRODUCE setting will maintain a drawer temperature of 35 °F by circulating warmed air or cooled air as needed. The dampers will close and the heater will turn on if warmed air is required to maintain 34 °F. The dampers will open if cooled air is required.
The MEA T setting will maintain a drawer temperature of 32 °F by circulating warmed air or cooled air as needed. The dampers will close and the heater will turn on if warmed air is required to maintain 32 °F. The dampers will open if cooled air is required.
The Climate Control drawer display will show the selected temperature for approximately 4 seconds after a Select Temp mode has been selected. After approximately 4 seconds, the actual temperature of the drawer will be displayed. Refer to the Temperature Table for drawer temperatures.
Express Chill This feature cools items by opening the dampers and circulating air from the freezer compartment
throughout the drawer . The fan will be on at all times during Express Chill. The Climate Control Drawer display will show the number of minutes (or minutes remaining) for the
Express Chill mode selected on the control panel. The display will not show the temperature of the drawer . Refer to the Temperature Table for drawer temperatures.
Express Thaw This feature thaws items by circulating warmed air throughout the drawer. Temperature is maintained in
the drawer by cycling a small heater on and off as needed. The dampers will be closed during Express Thaw . The fan will be on at all times during Express Thaw.
When the Express Thaw cycle is complete, the drawer will automatically adjust to 30 °F. The Climate Control Drawer display will show the number of hours (or hours remaining) for the Express
Thaw mode selected on the control panel (.5 LBS = 4 HRS, 1.5 LBS = 8 HRS, 3 LBS = 12 HRS). The display will not show the temperature of the drawer . Refer to the Temperature T able for drawer temperatures.
– 35 –
Temperature Table
When using the Temperature T able, please note the following:
FF and FZ compartments should be within 3 °F of the temperature set point when checking drawer temperature.
All temperatures listed are as measured by the thermistor and displayed by the Climate Control Drawer display.
Actual drawer temperature will be displayed in Select Temp mode only. The Climate Control Drawer display will show the selected temperature for approximately 4 seconds after a Select Temp mode has been selected. Af ter approximately 4 seconds, the actual temperature of the drawer will be displayed.
The actual-temperature display is based on the temperature that the main control board sees from the thermistor. The selected-temperature (example: CITRUS – 43 °F) is based on the logic of the Climate Control Drawer control board. If the actual temperature that is displayed is incorrect, the thermistor and main control board are suspect. If the temperature associated with the Select Temp mode is incorrect, the Climate Control Drawer control board is faulty.
WAHTSSERPXE LLIHCSSERPXE PMETTCELES
EDOM PMET EDOM PMET EDOM PMET
.SBL5.F˚64ot24
.SBL5.1F˚64ot24
.SBL3F˚64ot24
1
1
1
.NIM51F˚52
.NIM03F˚02ot51
.NIM54F˚02ot51
2
2
2
SURTICF˚34
ECUDORPF˚53
TAEMF˚23
3
4
5
Note 1 Climate Control Drawer may take up to 1 hour and 45 minutes to achieve temperature with no load in drawer (except metal tray) and minimal or no door openings. When the Express Thaw cycle is complete, the drawer will automatically adjust to 30 °F.
Note 2 Temperature should lower to 25 °F or less within 15 minutes with no load in drawer (except metal tray) and minimal or no door openings. Temperature should lower to a temperature between 15 °F to 20 °F within 30 minutes with no load in drawer (except metal tray) and minimal or no door openings. If refrigerator is defrosting, temperature in drawer may go below 15 °F.
Note 3 Climate Control Drawer may take up to 1 hour and 45 minutes to achieve temperature with no load in drawer (except metal tray) and minimal or no door openings.
Note 4 Climate Control Drawer may take up to 1 hour to achieve temperature with no load in drawer (except metal tray) and minimal or no door openings.
Note 5 Climate Control Drawer may take up to 45 minutes to achieve temperature with no load in drawer (except metal tray) and minimal or no door openings.
– 36 –
Climate Control Drawer Top Panel (Mullion)
Removal
Styrofoam Insert
1. Remove 2 storage bins and the glass panel over Climate Control Drawer.
2. Remove 4 screws from climate control top and slide back to access wire connectors.
3. Disconnect the connectors and remove the top panel.
Note: Note that there is a S tyrofoam insert in the slot at the back, right-hand corner of the top panel.
Control Board and Display
The control board and display are located in the Climate Control Drawer top panel (mullion). The control board and display are part of the mullion and cannot be replaced separately .
Input from the Climate Control Drawer’s control board and the thermistor is used by the main control board to control the dampers, fan, and heater.
Screws
Top Panel (Mullion)
Actual drawer temperature will be displayed in Select Temp mode only. The Climate Control Drawer display will show the selected temperature for approximately 4 seconds after a Select Temp mode has been selected. After approximately 4 seconds, the actual temperature of the drawer will be displayed.
The actual-temperature display is based on the temperature that the main control board sees from the thermistor. The selected temperature (example: CITRUS – 45 °F, is based on the logic of the Climate Control Drawer control board. If the actual temperature that is displayed is incorrect, the thermistor and main control board are suspect. If the temperature associated with the Select Temp mode is incorrect, the Climate Control Drawer control board is faulty .
.
– 37 –
Caution: When assembling the top panel, use care to prevent pinched wires Troubleshooting Use this diagnostic flowchart if the Climate Control Drawer control panel and display are not operating
properly. If the problem is drawer temperature and the control panel and display appear to be operating normally ,
check the thermistor, damper, fan, and heater first. If the actual drawer temperature displayed is incorrect, suspect the thermistor and main control board.
Check
communication
using diagnostic
mode.
Communication
pass?
YES
Replace Climate
Control Drawer
control board.
YES
Replace Climate
Control Drawer control
board. If problem is not
corrected, replace the
main control board.
Is a temperature or time
NO
displayed or are any
indicator lights illuminated
on the Climate Control
Drawer control panel?
Display and/or lights
Replace Climate
Control Drawer
control board.
Check for continuity on
data circuit between
J4-1 and Climate Control
Drawer control board
connector terminal 5.
Circuit OK?
Repair circuit.
NO
Disconnect connector J4 from main control board.
No display
or lights
YES
Check for 12 VDC at
main control board
between J4-2 and J4-3.
12 VDC present?
YES
Reconnect connector J4 to
main control board.
Check for 12 VDC at J4-2 at main control board between
J4-2 and J4-3.
12 VDC present?
YES
Disconnect connector from Climate
Control Drawer control board.
Check for 12 VDC at the Climate
Control Drawer control board
connector between terminals 3 and 5.
12 VDC present?
NO
NO
NO
Replace main control board.
Replace Climate
Control Drawer
control board.
Open wiring between Climate
Control Drawer control board and
main control board.
Some of the low voltage DC connector labeling on this model may differ from other models. The function and diagnostics for these connectors are identical for all models.
– 38 –
J4 or J16
9-Pin Connector
Behind Climate Control Drawer
ORANGE
J3 or J10
J2 OR J13
J1 or J14
Fan and Fan Housing
The 12 VDC fan is controlled by the main control board. The main control board turns the fan on and off based on input from the Climate Control Drawer control board and thermistor. The fan should always come on any time Express Chill or Express Thaw is selected.
Troubleshooting
Turn on Express Chill.
Check for 12 VDC at
main control board
between J2-8 and J2-7.
12 VDC present?
YES
Some of the low voltage DC connector labeling on this model may differ from other models. The function and diagnostics for these connectors are identical for all models.
NO
Check communication
using diagnostic mode.
Communication pass?
YES
Replace main control board.
J4 or J16
NO
J3 or J10
J2 OR J13
J1 or J14
Check for 12 VDC
at fan connector.
12 VDC present?
YES
· Open circuit between
fan connector and fan.
· Faulty fan.
NO
Open circuit
between main
control board and
fan connector.
Removal
1. Remove Climate Control Drawer top panel.
2. Loosen 2 bottom screws, remove 2 top screws, and remove air diffuser from fan housing.
· Open circuit between J4-1 and
Climate Control Drawer control board terminal 1.
· Faulty Climate Control drawer
control board.
· Faulty main control board.
Screws (Remove)
Screws (Loosen)
Flat Surface
Air Diffuser
– 39 –
T abs
3. This step for fan removal only: Remove screen from front of fan and fan from housing.
4. Remove 2 screws and the sheet metal cover from the right-hand side of the housing.
5. Disconnect fan connector.
9-Pin Connector
Fan Connector
6. This step for fan removal only: Cut fan wires at
Screen and Fan
fan to remove.
Note: When installing a new fan, the fan wires do not
Fan Housing
Heater Connector
have to be installed under plastic wire holders.
7. Disconnect heater connector and 9-pin connector.
8. Remove 5 screws and fan housing from fresh food compartment.
Note: When installing the diffuser onto the fan housing, the tabs must be on the bottom and the flat surface must be on top. Incorrect installation will prevent the drawer from cooling and warming properly.
Dampers
Caution: Do not manually move damper door. Manually moving damper door will damage damper.
The dampers are located between the fan housing and the center mullion. The fan housing must be removed from the fresh food compartment to replace the dampers.
Both dampers always operate at the same time. The upper damper can be viewed from the Climate Control Drawer compartment. The lower damper can be viewed from the freezer compartment. Dampers will be closed during Express Thaw and will be open during Express Chill.
The main control board opens and closes the damper based on input from the Climate Control Drawer control board and the thermistor.
After selecting Express Thaw, 12 VDC are output from the main control board for approximately 4 seconds to close the damper. This voltage can be measured at the following points:
Main control board J5-2 to J5-1 with positive (red) test
meter lead on J5-2.
9-pin connector behind Climate Control Drawer.
Check from gray wire to yellow wire with positive (red) test meter lead on gray wire.
After selecting Express Chill, 12 VDC are output from the main control board for approximately 4 seconds to open the damper. This voltage can be measured at the following points:
Main control board J5-1 to J5-2 with positive (red)
test meter lead on J5-1.
9-pin connector behind Climate Control Drawer.
Check from yellow wire to gray wire with positive (red) test meter lead on yellow wire.
Fan Housing
9-Pin Connector
Dampers
– 40 –
Heater
The 120 VAC heater is located in the fan housing. The fan housing must be removed from the fresh food compartment to access the heater.
The heater is controlled by the main control board. The main control board turns the heater on and off based on input from the Climate Control Drawer control board and the thermistor.
Heater
EMI/RF
Filter
Heater Connector Behind
Climate Control Drawer
Some of the low voltage DC connector labeling on this model may differ from other models. The function and diagnostics for these connectors are identical for all models.
Brown
Orange
Heater
438
J4 or J16
J3 or J10
J2 OR J13
AC Power Cord
Fan Housing
J1 or J14
Heater Connector
Heater resistance should be 438 W and can be checked at 2 places:
J7-5 to J7-9 at main control board. Connector J7 should be disconnected from main control board
when checking resistance.
Heater (2-pin) connector located behind the Climate Control Drawer. Connector should be
disconnected when checking resistance. The heater can usually be turned on by entering any of the Quick Thaw modes. 120 VAC output to the heater can be checked at 2 places:
J7-5 to J7-9 at main control board.
Heater (2-pin) connector located behind the Climate Control Drawer.
Thermistor
The thermistor is clipped to the inside of the fan housing. The main control board controls the dampers, fan, and heater based on input from the Climate Control
Drawer’s control board and the thermistor. Actual drawer temperature will be displayed in Select Temp mode only. The Climate Control Drawer display will show the selected temperature for approximately 4 seconds after a Select Temp mode has been selected. After approximately 4 seconds, the actual temperature of the drawer will be displayed. The actual-temperature display is based on the temperature that the main control board sees from the thermistor. The selected temperature (example: CITRUS – 43 °F) is based on the logic of the Climate Control Drawer control board. If the actual temperature that is displayed is incorrect, the thermistor and main control board are suspect. If the temperature associated with the Select Temp mode is incorrect, the Climate Control Drawer control board is faulty . All thermistors can be checked using Diagnostic Mode.
– 41 –
Access After removing the diffuser, the thermistor can be
accessed through the hole on the right-hand side of the fan. After removing the thermistor from the clip (on the inside of the fan housing), the thermistor can be removed from the fan housing through the hole in the top of the housing.
Note: When installing the diffuser onto the fan housing, the tabs must be on the bottom and the flat surface must be on top. Incorrect installation will prevent the drawer from cooling and warming properly.
Note: All thermistors can be checked using Diagnostic Mode.
Thermistor shown remov ed from clip.
Clip
9-Pin Connector
Fan Housing
Refer to the Thermistor Values chart for resistance values. Thermistor resistance can be checked at 2
Tabs (Down)
places:
J5-5 to J5-6 at main control board. Connector J5 should be disconnected from main control board
when checking resistance.
9-pin connector located behind the Climate Control Drawer. Connector should be disconnected
when checking resistance.
5 VDC output to the thermistor can be checked at 2 places:
J5-5 to J5-6 at main control board.
9-pin connector located behind the Climate Control Drawer.
Thermistor
seulaVrotsimrehT
erutarepmeT
)C(seergeD
02-4-k4.84 01-41k6.72
023k3.61
erutarepmeT )F(seergeD
ecnatsiseR
smho-oliKni
0105k01
Some of the low voltage DC connector labeling on this model may differ from other models. The function and diagnostics for these connectors are identical for all models.
– 42 –
J4 or J16
J3 or J10
J2 OR J13
J1 or J14
Air Flow
DAMPERS OPEN
Shown with top panel and drawer removed.
With the dampers open, cold air moves from the FZ compartment through the lower damper and into the fan housing. The fan blows the cold air through the diffuser into the drawer. The air returns from the drawer through the diffuser and into the fan housing. Air also moves over the top of the drawer , into the Climate Control Drawer compartment (not into the FF compartment), and then out of the compartment via the top damper.
DAMPERS CLOSED
Shown with top panel and drawer removed.
With the dampers closed, the fan moves air from the fan housing, through the diffuser, to the drawer. Air returns from the drawer, through the diffuser, to the fan compartment.
– 43 –
Compartment Lights
The new Monogram side-by-side refrigerator uses 12 VAC halogen lights in both the fresh food and freezer compartments. The fresh food compartment is equipped with two 35-watt bulbs and five 20-watt bulbs producing a total of 170 watts. The freezer compartment is equipped with two 35-watt bulbs producing a total of 70 watts. Power is supplied to all interior lighting by 2 transformers. The transformers convert 120 V AC to 12 VAC.
FF/FZ Compartment Lights Diagnostic
Check for 120 VAC at transformer. Measure
votlage at transformer connector between red
wire (FZ) or violet wire (FF) and orange wire.
YES
Measure output voltage
at transformer
YES
Open circuit
between lights and
transformer.
connector between red
and gray wires.
Are 12 VAC measured?
NO
Replace
Transformer.
Are 120 VAC measured?
NO
Check the following:
1. FF or FZ door switch
2. Sabbath switch
3. Circuit breaker (located by the transformers in tray under the FF compartment)
4. Thermal overload FZ - located at bottom of FZ Compartment FF - located at bottom of FF light tower
5. 120 VAC Wiring FZ - blue wire(s) and red wire(s) FF - yellow wire(s) and violet wires
6. Neutral wiring (orange)
– 44 –
Door Switches
The fresh food and freezer door switches are located at the top of the fresh food and freezer compartments.
The fresh food door switch closes when the door is open, providing L1 to the fresh food compartment light transformer.
The freezer door switch is a dual-pole switch. It provides L1 to the main control board when the freezer door is closed. When the freezer door is open, the switch provides L1 to the freezer compartment light transformer.
Master Light Switch
The master light switch is located behind the grille panel, on the main control board cover . The switch will open the circuits between the door switches and the transformers, disabling both transformers and stopping voltage output to the interior lights.
Main Control
Master Light Switch
Master Light Switch
Main Control
Board Cover
Board Cover
T emperature Overload Device (T OD)
A temperature overload device is wired in series with both the fresh food and freezer compartment transformers. If the interior lights should reach excessive temperatures due to a door being open for an extended period, the corresponding TOD will open the circuit that supplies 120 VAC to the transformer . The TOD will open at 150 °F and close at 90 °F.
The freezer TOD is located behind a metal cover on the back wall of the freezer compartment, at the base of the light tower. The fresh food TOD is located on the back wall of the fresh food compartment, at the base of the light tower .
Temperature Overload
Temperature Overload
Device (TOD)
Device (TOD)
Temperature Overload
Temperature Overload
Device (TOD)
Device (TOD)
Light Tower
Freezer Compartment
Light Tower
Fresh Food Compartment
– 45 –
Type 2
Type 1
Type 2
Type 1
This is a 35 watt, 12 volt,
Type MR11 bulb.
If ordering through
GE Parts and Accessories,
order part WR02X11183.
Type 2
This is a 20 watt, 12 volt,
Type T bulb.
If ordering through
GE Parts and Accessories,
order part WR02X11184.
Circuit Breakers
Two re-settable, 2-amp circuit breakers are located on the front of the transformer housing. Should a circuit breaker trip (open), it will open the transformer circuit it is associated with (freezer compartment or fresh food compartment), disabling that transformer and stopping voltage output to the interior lights.
Transformers
Power is supplied to all interior lighting by 2 transformers. One transformer is used for each compartment. The transformers supply low­voltage power to the lights by converting 120 V AC into 12 V AC.
The transformers are located in a housing under the center of the refrigerator. The housing is accessible from the front of the refrigerator. To access the transformers, remove the head screws (6) that hold the housing in place.
1
/4-in hex-
Transformers
Circuit Breakers
Note: Nuisance tripping of the circuit breakers
can occur due to higher than normal line voltage. Replacing the 2-amp circuit breakers with a new part (now rated at 3-amps) will resolve the problem.
Light Bulb Replacement
WARNING: Halogen lights generate intense heat.
Be certain power is off and lamps have sufficient time to cool before attempting to replace.
Note: The Styrofoam protector in the light lens is for shipping and must be removed prior to installation.
Power to the lamps can be turned off at the Sabbath switch, located behind the grille panel at the top of the refrigerator.
Note: Turning the temperature control to the OFF position does NOT remove power to the light circuits.
The refrigerator uses 2 types of halogen bulbs: Type 1 The columns along the back wall of the fresh food
and freezer compartments are lit up by lamps located behind the top pan in the fresh food compartment and the bottom basket in the freezer compartment. Type 1 bulbs are 35-watt and have a life expectancy of about 3500 hours.
Type 2 These lamps are located inside the light shield at
the top of the fresh food compartment and on top of the Climate Control drawer at the bottom of the fresh food compartment. Type 2 bulbs are 20-watt and have a life expectancy of about 2000 hours.
– 46 –
Upper light shield
Screws
Screws
Slots
Light housing
Support tabs
Light Shield
Type 1 Bulb Replacement WARNING: Halogen lights generate intense heat.
Be certain power is off and lamps have sufficient time to cool before attempting to replace.
1. Set the master light switch to the OFF position
and allow the lamps to cool.
2. To access the lamps in the fresh food
compartment, remove the top pan.
3. Grasp each end of the curved light shield and
pull the shield toward you to remove.
4. Remove the glass above the bulbs by pulling it
straight out. Note: Always follow bulb manufacturer’s directions
for handling and replacing bulbs.
5. Remove the bulb by holding the base and
pulling straight up. Replace with a new bulb.
6. Replace the glass by sliding it into place. Then,
replace the light shield by resting the top lip of
the shield on top of the light housing. Then,
press the sides until the tabs pop into the slots
in the housing. WARNING: The light shield must be replaced, or
the heat from the bulb could damage the refrigerator.
Type 2 Bulb Replacement WARNING: Halogen lights generate intense heat.
Be certain power is off and lamps have sufficient time to cool before attempting to replace.
1. Set the master light switch to the OFF position
and allow the lamps to cool.
2. If a water filter cartridge is installed, remove it
and replace with a filter bypass plug.
3. Holding the light shield with one hand, rotate the
support tabs until they clear the front of the light
shield. Then, push back on the light shield,
lower the shield at the front, and take out.
4. Remove the 4 screws securing the light
housing to the ceiling. There are two screws at
the front and two at the back.
5. Lower the light housing at the front, then pull it
toward you so the tabs at the back of the light
housing come out of the slots on the back wall.
The lamp assemblies will release from the
holders.
– 47 –
Lower lamp assemblies
6. Turn the lamp protector to access the bulb. Note: Always follow bulb manufacturer’s directions for
handling and replacing bulbs.
7. Remove the bulb by holding the base and pulling straight out. Replace with a new bulb and replace the lamp protector.
WARNING: Lamp protectors must be replaced, or the heat from the bulb could damage the refrigerator.
8. Holding up the light housing, place each lamp assembly in its holder. Feed the attached wires through the slots and tuck the wires outside the side of the light housing.
9. Insert the tabs on the back of the light housing in the slots on the back wall. Raise the light housing into position and secure with the four screws.
10. Replace the light shield and rotate the support tabs back out to support the front of the shield.
11. Remove the filter byp ass plug and replace with the water filter cartridge. Reset the Sabbath switch to the ON position.
Climate Control Drawer Type 2 Bulb Replacement WARNING: Halogen lights generate intense heat. Be
certain power is off and lamps have sufficient time to
cool before attempting to replace.
1. Set the master light switch to the OFF position and
allow the lamps to cool.
2. To access the lamps, remove the second produce pan.
3. The lamps at the back, which face up, can be lifted out. To access the lamp that shines into the Climate Control drawer, twist the holder until the arrow point s toward the back of the refrigerator , then lift up.
4. Turn the lamp protector to access the bulb.
Note: Always follow bulb manufacturer’s directions for
handling and replacing bulbs.
5. Remove the bulb by holding the base and pulling straight out. Replace with a new bulb and replace the lamp protector.
WARNING: Lamp protectors must be replaced, or the heat from the bulb could damage the refrigerator.
– 48 –
J4 OR J16 J3 OR J10 J1 OR J14
J2 OR J13
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 DATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
RED ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLET VIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
DEF HEATER
PAN HEATER
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39
2
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10
10
10
R=441
R=330
R=38
R=1323
ZIS360
Schematics
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
– 49 –
J4 OR J16 J3 OR J10 J1 OR J14
J2 OR J13
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 DATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
RED ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLET VIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
R=441
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
DEF HEATER
R=1323
PAN HEATER
R=330
R=38
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39
2
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10
10
10
DISPENSER
CONTROL HMI
1
RED
35
BROWN
ORANGE
ZIS360D
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
– 50 –
J4 OR J16 J3 OR J10 J1 OR J14
J2 OR J13
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 DATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
RED ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLET VIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
R=441
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
DEF HEATER
R=38
R=1323
PAN HEATER
R=330
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39
2
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10
10
10
ZIS420
– 51 –
J4 OR J16 J3 OR J10 J1 OR J14
J2 OR J13
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 DATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
RED ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLET VIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
R=441
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
R=1323
DEF HEATER
R=38
PAN HEATER
R=330
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39
2
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10
10
10
DISPENSER
CONTROL HMI
1
RED
35
BROWN
ORANGE
ZIS420D
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
– 52 –
J4 OR J16 J3 OR J10 J1 OR J14
J2 OR J13
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 DATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
RED ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLET VIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
R=1323
DEF HEATER
R=38
PAN HEATER
R=330
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39
2
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10
10
10
R=441
ZIS480
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
– 53 –
J4 OR J16 J3 OR J10 J1 OR J14
J2 OR J13
FF TEMP
CONTROL HMI
1
RED
35
BROWN
ORANGE
RED
BROWN
ORANGE
RED
3
2
1
BROWN
ORANGE
HMI
TEST
JACK
13 5
QUICK CHILL
CONTROL HMI
RED
BLUE
WHITE
RED
REDREDWHITE
WHITE
WHITEWHITE
WHITE
PINK
YELLOW
BLUE
BLACK
YELLOW
BROWN
BROWN
BROWNBROWN
BLACKWHITE
WHITE
WHITE
YELLOW
YELLOW
WHITE
WHITE
WHITE
WHITE
FF2
FZ
EVAP
QUICK CHILL
THERMISTORS
FF1
RED
BLUE
BLUE
BLUE
BROWN
BROWN
ORANGE
DAMPER
MOTHERBOARD
J4
J7
J3
J1
J5
J2
1 D ATA
DEF HTR J9
PAN HEATER J12
LINE J11
1
8 MODEL ID 42"
9 MODEL ID 48"
5 +5VDC
1 FF1
2 FF2
3 FZ
4 EVAP
2
3
4
6
5
2
1
2 +12V
3 COM
DAMPER
DAMPER
1
2
1
2
8 12VDC
3 FAN COM
5 COND FAN
4 EVAP RPM
1 EVAP RPM
7 QUICK CHILL FAN
QUICK
CHILL
FAN
EVAP
FAN
COND
FAN
EMI/RF
FILTER
RED
WHITE
ICEMAKER
WATER VALVE
DISPENSER
WATER VALVE
WHITE
WHITE
BLUE
BLUE
ORANGE
BROWN
GREEN
PURPLE
BLACK
AUGER
ORANGE
ORANGE
RED
RED ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GRAY
GRAY
FF LIGHTS
2 X 20W (40W)
3 X 20W (60W)
2 X 35W (70W)
FF COLUMN
LIGHTS
QC LIGHTS
GRAY
RED
RED
GRAYRED
GRAY
GRAY
RED
RED
REDRED
VIOLET VIOLET
BLUE
BLUE
FF DOOR
SWITCH
T2
T1
TOD
TOD
F1
F1
LIGHT SWITCH
ORANGE
ORANGE
ORANGE
ORANGE
ORANGE
GREEN
BROWN
QUICK CHILL HEATER
R=441
AC POWER CORD
VIOLET
BROWN
ORANGE
BROWN
TEST JACK
ORANGE
BLACK
BROWN
BROWN
BROWN
FZ DOOR
SWITCH
RED
PURPLE
BLACK
BLUE
BLUE
YELLOW
YELLOW YELLOW
ORANGE
VIOLET
EVAP THERMODISK
(TOD)
FILL TUBE
HEATER
R=1323
DEF HEATER
R=38
PAN HEATER
R=330
ICEMAKER
4
2
1
3
FZ DOOR OPEN 7
FF DOOR OPEN 6
NEUTRAL 9
QC HEATER 5
39
2
CUBE
FZ COLUMN
LIGHTS
2 X 35W (70W)
J15
1
2
BROWN
COMPRESSOR
INVERTER
BLUE
RED
WHITE
BLACK
10
10
10
DISPENSER
CONTROL HMI
1
RED
35
BROWN
ORANGE
ZIS480D
SOME OF THE LOW VOLTAGE
DC CONNECTOR LABELING ON
THIS MODEL MAY DIFFER FROM
OTHER MODELS. THE
FUNCTION AND DIAGNOSTICS
FOR THESE CONNECTORS ARE
IDENTICAL FOR ALL MODELS.
– 54 –
Refrigeration System
Inverter Compressor
The new inverter compressor is not controlled by 120 V AC output from the main control board, as in previous models. The compressor is controlled by the inverter .
Warning: Disconnecting the 6-pin connector does not disconnect power (120 V AC) from the inverter. The refrigerator must be unplugged before servicing the inverter or compressor.
Caution: Do not attempt to direct-start the compressor. The compressor operates on a 3-phase power supply . Applying 120 VAC to the compressor will permanently damage the unit. It is not possible to start the compressor without an inverter.
The compressor is a reciprocating, variable speed, 4-pole type. It operates on 3-phase, 80 to 230 V AC within a range of 57 to 104 Hz. Compressor speed is controlled by voltage frequency and pulse width modulation. Increasing frequency from the inverter will produce an increase in compressor speed.
Frequency of 57 Hz will produce low speed operation at 1710 rpm.
Frequency of 70 Hz will produce medium speed at 2100 rpm.
Frequency of 104 Hz will produce 3120 rpm. Note: Certain voltmeters will not be able to read voltage output or frequency from the inverter. Compressor wattages at various speeds are:
LOW - 65 watts
MED - 100 watts
HIGH - 150 watts BTU rating also varies according to operating speed. Compressor speed is based on the temperature set-point in conjunction with the cabinet temperature.
Speeds are selected according to the following cabinet temperatures:
• 6 °F to 19.5 °F above set-point = high speed
• 3.5 °F to 5.5 °F above set-point = medium speed
• 1 °F to 3 °F above set-point = low speed Note: The compressor will run at medium speed if the cabinet temperature is 20 °F or more above the
set-point. The use of 3-phase power eliminates the need for the PTCR relay , cap acitor, and individual start and run windings; therefore the start, run, and common pins found on conventional compressors are not applicable on this 3-phase model. Compressor pin functions are identical and compressor lead wire configuration is of no importance. A resistance of 9 to 11 W should be read between any 2 of the 3 pins. Should an open occur in the compressor winding or should one of the compressor lead wires become open or disconnected, the inverter will stop voltage output to the compressor .
– 55 –
High compressor torque enables the compressor to start against high pressure in the sealed system. When power has been disconnected from an operating unit, the high torque may enable the compressor to start immediately upon power restoration. The compressor, if unable to start after 12 times, will wait for 8 minutes before trying again.
Compressor and sealed system operation is extremely smooth and cool. The compressor exterior may be room temperature while operating; therefore a running unit may be difficult to detect.
To verify that the compressor is running: Disconnect power from the unit and place a hand on the compressor. Reconnect power and feel for a
vibration when the compressor tries to start. It may take up to 8 seconds before the compressor attempts to start.
To determine motor rpm: Measure the frequency of the voltage being applied to the compressor and multiply this number by 30.
For example, a frequency measurement of 70 Hz would show a compressor speed of 2100 rpm (30 x 70 = 2100).
Note: If the compressor fails to start, the inverter will briefly stop voltage output. The inverter will make 12 consecutive attempts to start the compressor (once every 12 seconds). If, after 12 attempts, the compressor has not started, an 8-minute count will occur. After 8 minutes, the inverter will attempt to start the compressor again. If the compressor starts, normal operation will resume. If the compressor fails to start, the process will be repeated. Removing power from the unit will reset the inverter count. When power is restored, the inverter will attempt to start the compressor within 8 seconds.
Note:
When ordering a replacement compressor, order both the compressor and inverter. Replace the compressor first. If, after compressor installation, the compressor fails to start, replace the inverter.
When servicing the compressor, it is important to dress the wiring to keep low voltage DC wiring and 120 V AC wiring separate.
– 56 –
Inverter
Warning: Disconnecting the 6-pin connector does not disconnect power (120 VAC) from the inverter. The refrigerator must be unplugged before servicing the inverter.
Note: Certain voltmeters will not be able to read voltage output from the inverter . If no voltage or erratic
voltage is measured, it does not necessarily indicate a faulty inverter . The inverter receives 120 V AC line-in from the power supply. The inverter converts this single-phase,
60 Hz, 120 V AC into 3-phase, 230 VAC, with frequency variations between 57 Hz and 104 Hz. This voltage is delivered to the compressor through 3 lead wires. Each wire will carry identical voltage and frequency. When checking inverter voltage output, connect the test-meter leads to any 2 of the 3 compressor lead wires. The same reading should be measured between any 2 of the 3 wires.
Note: The compressor leads must be connected to measure voltage output. If the compressor wires are not connected, or if an open occurs in one of the 3 lead wires or in the compressor, the inverter will stop voltage output.
The inverter controls compressor speed by frequency variation and by pulse width modulation (PWM). Changing frequency and PWM will cause an effective voltage between 80 and 230 VAC to be received at the compressor.
Low speed (1710 rpm) - 57 Hz
Medium speed (2100 rpm) - 70 Hz
High Speed (3120 rpm) - 104 Hz The inverter receives commands from the main control board.
The main control board will send a (PWM) run signal between 1.5 and 3.5 VDC effective voltage to the inverter. The signal voltage at the inverter should be equal to the signal voltage sent by the main control board. The inverter will select compressor speed (voltage output) based on this signal. A signal voltage from the main control board (J15 connector ) lower than faulty main control board. The main control board will only send a run signal to the inverter when the compressor should be on.
Note: When measuring signal voltage (from the main control board) at the inverter, disconnect the wire harness connector at the inverter and measure the voltage at the connector .
The inverter will monitor compressor operation and if the compressor fails to start or excessive current draw (4 amps maximum) is detected, the inverter will briefly stop voltage output. The inverter will then make 12 consecutive compressor start attempts (once every 12 seconds). If after 12 attempts the compressor has not started, an 8-minute count will initiate. After the 8-minute count, the inverter will attempt to start the compressor again. If the compressor starts, normal operation will resume. If the compressor fails to start, this process will be repeated. Removing power to the unit will reset the inverter count. When power is restored, the inverter will attempt to start the compressor within 8 seconds.
5 VDC indicates a
J15
The inverter has a built-in circuit protection to guard against damage from a failed or shorted compressor. However, if a failed compressor is diagnosed, order a new compressor and inverter. If the compressor fails to start after replacement, replace the inverter.
– 57 –
Note: When servicing the inverter , it is important to dress the wiring to keep low­voltage DC wiring and 120 V AC wiring separate.
To remove the inverter:
1. Unplug the unit.
2. Open access cover.
3. Remove the screw securing the inverter to the sheet metal dividing wall. (It may be necessary for you to move the foam spacer.)
4. Slide the inverter forward to release the back from the metal dividing wall.
Note: It may be necessary to bend the process tube in order to remove the inverter. If it is necessary to bend the process tube, use extreme care.
5. Turn the inverter horizontally and slide the inverter out of the machine compartment.
To remove the inverter cover:
Screw
Inverter
Use a small screwdriver to release the two small tabs and carefully remove the inverter cover.
Inverter
Inverter
Line-In (L1)
Line-In (L1)
Signal Wire Connector
Signal Wire Connector
(From Main Control Board)
(From Main Control Board)
Compressor Lead
Compressor Lead
Wires
Wires
Tabs
– 58 –
Accumulator
An accumulator has been installed at the inlet of the compressor to prevent liquid refrigerant (low quality) from entering the suction line. Changes in compressor speed (transition state) can temporarily reduce refrigerant quality . The accumulator compensates for this by collecting and holding up to 2 oz of liquid while allowing vapor to pass. Within minutes after the compressor speed change, the system attains a steady state (becomes stabilized), the liquid refrigerant in the accumulator vaporizes, and refrigerant quality returns to normal.
Note: Accumulator should be located above drain pan to allow any condensed moisture accumulated to fall into drain pan.
Accumulator
Steady State
INVERTER COMPRESSOR
70-135 PSIG 85-90 PSIG at 75 ˚F Ambient
CONDENSER EVAPORATOR
FILTER-DRIER
COMPRESSOR
CAPILLARY
ACCUMULATOR
MIX OF LIQUID AND VAPOR
HIGH PRESSURE LIQUID
0-5 PSIG 1-2 PSIG at 75 ˚F Ambient
HIGH PRESSURE VAPOR
70-135 PSIG 85-90 PSIG at 75 ˚F Ambient
CONDENSER EVAPORATOR
LOW PRESSURE LIQUID
MIX OF LIQUID AND VAPOR
LOW PRESSURE VAPOR
Transition State
INVERTER COMPRESSOR
COMPRESSOR
FILTER-DRIER
CAPILLARY
ACCUMULATOR
LIQUID ENTERS THE ACCUMULATOR
0-5 PSIG 1-2 PSIG at 75 ˚F Ambient
GEA01263
System Pressure
The refrigeration system should maintain a consistent pressure regardless of compressor speed. Pressure variations, due to changing compressor speed, are minimized by matching the condenser fan speed and evaporator fan speed to the compressor speed. The condenser and evaporator fans will always operate at the same speed (low, medium, or high) as the compressor. Low side system pressure should be between 0 and 5 psig dependant on ambient temperature. System pressures in an ambient temperature of 75 °F should be:
••
High Side – 85 to 90 psig
••
••
Low Side – 1 to 2 psig
••
Refrigerant Charge
The refrigerant used in the sealed system is R134a. Proper system charge is 12.5 oz; however, an additional 0.5 oz is required when adding a filter/drier . Proper system charge is critical to the operation of this unit.
– 59 –
Drier
The drier is positioned vertically in the center of the machine compartment. A copper process tube, connected to the inlet of the drier , provides access to the high-pressure side of the refrigeration system. The capillary is connected to the outlet of the drier .
Evaporator
The evaporator is made of copper and aluminum and is located above the evaporator fan at the top of the freezer compartment.
To replace the evaporator
Process Tube
Drier
1. Recover the refrigerant.
2. Remove the evaporator fan (see procedure).
3. Remove the defrost heater (see procedure).
4. Remove the defrost overtemperature thermodisc and evaporator thermistor.
5. Disconnect the ground wire from the evaporator and position all wiring to allow for evaporator removal.
6. Remove the screws securing the evaporator to the cabinet.
Caution: Protect wiring from heat during desoldering and resoldering.
7. Desolder the capillary tube from the evaporator .
8. Desolder the suction line.
9. Remove the evaporator .
10. Using a file, score the capillary tube just above the old solder and break the solder-covered section off. This will help prevent the capillary tube from becoming plugged when resoldering.
Capillary
Evaporator Thermistor
Evaporator Thermistor
Defrost Overtemperature Thermodisc
11. Position the new evaporator in the cabinet. Insert the suction line and capillary tube into the evaporator.
12. Solder the suction line to the evaporator using silfos.
13. Solder the capillary tube to the evaporator using silfos.
14. Install a replacement drier.
15. Evacuate and recharge the system using currently accepted procedures.
Refrigerant Charge
The refrigerant used in this model is type R134a. Refer to the mini-manual or model tag for the exact refrigerant charge quantity .
– 60 –
Diagnostic Mode
Enter the diagnostic mode by pressing both the freezer temperature pads (plus and minus) and the refrigerator temperature pads (plus and minus) simultaneously. All 4 pads must be held for approximately 3 seconds. A blinking “0” in both displays indicate the refrigerator has entered the test mode.
Enter the appropriate display numbers as shown below and press any pad other than the temperature pads to activate that test mode.
rezeerF
yalpsiD
01 .edoMmoorwohS.edommoorwohsnitinU
02
03
04
06
07
08 .rooDtcuDnepO.sesolcnehtsdnoces01rofsneporood
09 .tseTretaeHsseceRresnepsiD
10 .tseTsrepmaD
12 .emiTnuR%001
13 .tseTllihc-erP
14 .tseTtsorfeD.woleb2etoneeS.elcyctsorfedehtselggoT
dooFhserF
yalpsiD
epmet
scitsongaiDstluseRstnemmoC
neewtebkcehcnoitacinummoC
dnalortnocerutarepmet
.draoblortnocniam
neewtebkcehcnoitacinummoC
.resnepsiddnalortnocerutar
dnaresnepsid
.tseTfleS
.tseT
neewtebkcehcnoitacinummoC
.draoblortnocniam
)lortnocerutarepmet(IMH
fleSmetsySrosneSdnalortnoC
tcuD
olcebtsumroodFF
iyalpsidZFno"P"
.KOf
.KOfiyalpsidZFno"P"
.KOfiyalpsidZFno"P"
iddnarotsimrehthcaeskcehC
.liafrof"0"dnassap
.sdnoces
ap,nepolliwrepmadhcaE
.esolc
.ruoh1retfatuo
.nwosti
.dnuofsimelborpsnaemyalpsidZFno"F"
.dnuofsimelborpsnaemyalpsidZFno"F"
.dnuofsimelborpsnaemyalpsidZFno"F"
.et
animullilliwstnemgesciremundnas'DELllA
rof"P"syalps
06rofnoretaehssecerresnepsidehtsnruT
neht,ylfierbesu
semiT.emitehtfo%001nometsysdelaeS
nolamronotsnrutertinU.edomllihc-erpstratS
tsuM
.woleb1etoneeS
rferfideretneebtonnaC
.ffo
irferfideretneebtonnaC
.ffo
otdenepoerdnades
.edommoorwohstrats
desserpsidap"wahTsserpxE"nehW
.ffonrutlliws'DEL"wahTsserpxE"
dess
erpsidap"llihCsserpxE"nehW
.ffonrutlliws'DEL"llihCsserpxE"
ottessirotaregi
ottessirotareg
.ffosretaehnrutotniagasserp
ottessirotaregirferfideretneebtonnaC
.woleb2etoneeS.ffo
15 .teseRlortnoCniaM.tesermetsysasesuaC
16 .edoMcit
17 .F/CeergeD.CotFmorfyalpsiderutarepmetsegnahC
songaiDtixE.teserdraoblortnocerutarepmetasesuaC
Note 1: Display order is: 1) Fresh Food 1, 2) Fresh Food 2, 3) Custom Cool, 4) Evaporator,
5) Freezer. Thermistor test results are P = pass, 0 = fail, S = short to 5 VDC, B = bad amplifier (replace main control).
Note 2: You must enter the defrost test again to toggle the defrost heater off at the end of the test. The heater will not come on if the evaporator thermistor or overtemperature thermodisc is warm.
– 61 –
Compressor Not Running Flowchart
Unplug refrigerator. Warm freezer thermistor to 70 F.
Connect power and set temperature controls to
maximum settings.
Does compressor start?
YES
Adjust settings and
allow 24 hours to
stabilize.
NO
Check condenser
fan for operation.
Fan operating?
YES
NO
YES
Verify freezer
thermisor is within
proper range using
thermistor values
chart. Is thermsitor
within proper range
NO
Note: A signal voltage from the
main board to the inverter of less
than 5 VDC indicates a bad
main board.
Verify signal voltage of 5 to
12 VDC at the main control
board connector J15.
Is voltage OK?
YES
Disconnect the main control
board signal wire at the inverter
and verify signal voltage of
5 to 12 VDC.
Voltage OK?
YES
Check compressor for
proper resistance.
9 to 11 ohms should be
measured between all
pins.
Resistance OK?
NO
Go to Condenser Fan Not Running
flowchart.
NO
NO
Replace main control board.
Replace wiring
harness from main
control board to
inverter.
Replace compressor.
Note: When ordering a replacement
compressor, order the compressor and inverter. Replace the compressor first.
If the compressor does not start
replace the inverter.
Check wiring
connections. If
wiring is OK, replace
thermsitor.
YES
Replace inverter.
YES
Check for 120 VAC
(L1) at inverter.
Voltage present?
YES
Check compressor
lead wires and
connections.
Wires and
connections OK?
Repair lead wire or
NO
connection.
– 62 –
NO
Repair inverter
wiring.
Warranty
YOUR MONOGRAM REFRIGERATOR WARRANTY Staple sales slip or cancelled check here. Proof of original purchase date is needed to obtain service under warranty.
WHAT IS COVERED
From the Date of the Original Purchase
FULL TWO-YEAR WARRANTY
For two years from date of original purchase, we will provide, free of charge, parts and service labor in your home to repair or replace any part of the refrigerator that fails because of a manufacturing defect.
FULL FIVE-YEAR WARRANTY
For five years from date of original purchase, we will provide, free of charge, parts and service labor in your home to repair or replace any part of the sealed refrigerating system (the compressor, condenser, evaporator and all connecting tubing) that fails because of a manufacturing defect.
LIMITED ADDITIONAL SEVEN-YEAR WARRANTY ON THE SEALED SYSTEM
For the sixth through twelfth year from the date of the original purchase, we will provide, free of charge, replacement parts for any part of the sealed refrigerating system (the compressor, condenser, evaporator and all connecting tubing) that fails because of a manufacturing defect. You pay for the service trip to your home and for service labor charges.
LIMITED LIFETIME WARRANTY ON ACCURIDE® SLIDES
From the date of the original purchase we will provide, free of charge, replacement parts for any part of the Accuride Slides that fails because of a manufacturing defect. You pay for the service trip to your home and for service labor charges.
This warranty is extended to the original purchaser and any succeeding owner for products purchased for ordinary home use in the 48 mainland states, Hawaii and Washington, D.C. In Alaska the warranty is the same except that it is LIMITED because you must pay to ship the product to the service shop or for the service technician’s travel costs to your home.
All warranty service will be provided by our Factory Service Centers or by our authorized Customer Care® servicers during normal working hours.
Should your appliance need service, during warranty period or beyond, in the U.S.A. call 800.444.1845. In Canada: 888.880.3030.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. To know what your legal rights are in your state, consult your local or state consumer affairs office or your state’s Attorney General.
Warrantor: General Electric Company, Louisville, KY 40225
WHAT IS NOT COVERED
• Service trips to your home to teach you how to use the product.
• Replacement of house fuses or resetting of circuit breakers.
• Damage to the product caused by accident, fire, floods or acts of God.
• Failure of the product if it is used for other than its intended purpose or used commercially.
• Improper installation. If you have an installation problem, contact
your dealer or installer. You are responsible for providing adequate electrical, plumbing and other connecting facilities.
• Loss of food due to spoilage.
• Incidental or consequential damage caused by
possible defects with this appliance.
– 63 –
Loading...