GE ZBTSD400, ZBTSD300, ZBTSD200, ZBTSD160, ZBTSD120 Specification

...
Page 1
PB-5066 (6/04)
Since its introduction, the GE Zenith
ZTS Series of
transfer switches has become a hallmark of quality and performance. Reliability resulting from superior design and heavy duty construction has made the
ZTS
the industry standard for critical installations. Our emphasis on research and development, design improvements, materials, manufacturing methods, quality assurance, and service yields products that have been proven in hundreds of thousands of applications.
Subsequent to the first
ZTS units installed, our engin-
eering staff has been dedicated to the improvement and expansion of our line. Today,
GE Zenith offers the
widest selection of transfer switch products worldwide.
ZTS Automatic Transfer Switches
40-4000 Amps
ZTSD Delayed Transition Transfer Switches
40-4000 Amps
ZTSCT Closed Transition Transfer Switches
100-4000 Amps
ZBTS Automatic Transfer/Bypass Switches
100-4000 Amps
ZBTSD Delayed Transition Bypass Switches
100-4000 Amps
ZBTSCT Closed Transition Bypass Switches
100-4000 Amps
All
ZTS products meet or exceed industry requirements
allowing specification and installation confidence.
UL 1008 listed through 480 VAC
CSA C22.2 No. 178 listed through 600 VAC
IEC 947-6-1 listed through 480 VAC
ZTS Series
Automatic Transfer Switches
Codes and Standards
NFPA 70, 99, 101, 110 IEEE 446, 241NEC 517, 700, 701, 702 NEMA ICS2-447
Controls tested in accordance with:
IEEE 472 (ANSI C37.90A)EN55022 Class B (CISPR 11)
(Exceeds
EN55011 & MILSTD 461 Class 3)
EN
61000-4-2 (Level 4)
EN61000-4-3 (ENV50140) 10 v/mEN61000-4-4
EN
61000-4-5, IEEE C62.41 (1.2 X 50ms, 5
& 8 kV)
EN61000-4-6 (ENV50141)EN61000-4-11
Enclosures meet the requirements of:
UL
508, 50
ANSI
C33.76
ICS
6
NEMA
250
Quality System:
ISO 9001 Registered
Product Bulletin
GE Zenith Controls
e
Specification Assistance
GE
Zenith offers a complete range of product guide specifications to help you determine your needs.
For more information, please consult your local
GE Zenith representative,
our factory or our website at www.geindustrial.com.
Page 2
Electrical Ratings
Ratings 40 to 4000 amperes
2, 3 or 4 Poles
Open type, NEMA 1,
3R, 4, 4X and 12
Available to 600 VAC,
50 or 60 Hz
Suitable for emergency and
standby applications on all classes of load, 100% tungsten rated through 400 amps
UL 1008 listed at 480 VAC
CSA C22.2 No. 178
certified at 600 VAC
IEC 947-6-1 listed at 480 VAC
Performance Features
Contact transfer speed
less than 100 milliseconds
High close-in and
withstand capability
Temperature rise test per
UL 1008 conducted after overload and endurance tests - exceeds UL requirements
Available in ZTS (utility-
generator), ZTSU (utility­utility), ZTSG (generator­generator) and ZTSM (manual) configurations
Design and Construction Features
Double throw,
interlocked operation
Electrically operated,
mechanically held by a simple, over-center mechanism
Segmented silver tungsten
alloy contacts with separate arcing contacts on 225 amp and above
Arc quenching grids,
enclosed arc chambers, and wide contact air gap for superior source-to­source isolation on all units
Control circuit disconnect
plug and drive inhibit switch for safe maintenance
Components accessible
for inspection and maintenance without removal of the switch or power conductors
Mechanical indicator and
contact chamber cover designed for inspection, safety and position designation
The ZTS Series is the building block of our transfer switch product line. This ruggedly built power contactor family of switches has been specifically designed for transfer switch duty with dependability, versatility and user friendliness of prime concern.
ZTS switches are available in open type construction
for switchboard installation or
NEMA enclosed to
the customer’s specifications. The power panel components, consisting of power switching contacts, drive mechanism and terminal lugs, are mounted on a specially formed panel. Logic devices including microprocessor control auxiliary time delays and special accessory equipment are assembled on the door for ease of maintenance and separation from the power section. They are connected with a numbered wiring harness equipped with a disconnect plug that allows isolation of the control panel for maintenance.
ZTS Series Method of Operation
When the normal source voltage fails or drops to a predetermined point (usually 80% of nominal), if required, a circuit is closed to start the engine generator set. When the emergency source reaches 90% of rated voltage and 95% of rated frequency, the drive solenoid is energized through the emergency coil control relay, causing the main contacts to disconnect the load from the normal source and connect it to the emergency source. After the drive solenoid has completed its electrical stroke and is seated, the emergency coil control relay opens to disconnect it. The transfer switch is now mechanically locked in the emergency position.
When normal voltage is restored to a predetermined point (usually 90% of nominal), the control voltage sensing energizes. The normal side coil relay closes, and after the drive solenoid has completed its electrical stroke and is seated, the coil control relay opens to disconnect it. The transfer switch is now mechanically locked in the normal position.
Drive Mechanism
All
GE Zenith ZTS switches employ the simple “over-
center” principle to achieve a mechanically locked position in either normal or emergency and
GE Zenith’s
high speed drive assures contact transfer in 100 ms or less. High contact pressure and positive mechanical lock allow for high withstand and closing ratings, far exceeding
UL requirements. All ZTS units are listed with
UL umbrella breaker, severe breaker and current
limiting fuse ratings.
ZTS Series Automatic Transfer Switches
Neutral Switching
The
GE Zenith ZTS Series is available in true four pole
designs for multi-source power systems that require neutral switching. The neutral contact is on the same shaft as the associated main contacts. This ensures positive operation, and avoids any possibility that the neutral contact will fail to open or close, as is possible when the neutral pole is an add-on accessory. The neutral contacts are identical to the main contacts, having the same current carrying and high withstand/ closing ratings as the mains. They are designed to break last and make first to reduce the possibility of transients while switching the neutral.
Safe Manual Operation
The
ZTS manual operator consists of a large, easy-to-use
handle that fits securely for manual operation during installation and maintenance or in an emergency.
The
ZTS may be provided with an operator inhibit
switch to disconnect the electrical drive prior to maintenance. Fully enclosed wrap-around arc covers shield the main contacts and mechanical components, preventing operator exposure during manual operation.
Transferring Large Motor or Highly Inductive Loads
Some loads, especially large motors, receive severe mechanical stress if power is trans-ferred out of phase while the motor is still rotating. Also, back
EMF gener-
ated by a motor may result in excess currents that can blow fuses or trip circuit breakers.
GE Zenith
offers four solutions to these problems:
PB-5066 Page 2
1. Universal Motor Disconnect (UMD): This load
control disconnects a large motor via its control circuit for an adjustable period of time prior to transfer in either direction. For switching multiple motors, GE Zenith Accessory A62 disconnects the motors prior to transfer and brings them back on line sequentially.
2. Accessory R50: This is an in-phase monitor that compares the phase angle between both sources of power and prevents transfer until the two are approxi­mately in phase (within a self adjusting range). GE Zenith’s high speed transfer action coupled with the MX series microprocessor control logic ensure closures at or near zero degree phase difference.
3. Series ZTSD: GE Zenith offers delayed transition switching on transfer switches rated 40 amperes and above – the GE Zenith ZTSD Series. This programmed center-off position allows for the full decay of rotating motors or transformer fields. It can also be used for load shedding of selected circuits or other appli-cations which require a means to disconnect the load from either source. Major UPS system manu­facturers recommend delayed transition switches for proper restart sequencing of their systems.
4. Series ZTSCT: GE Zenith’s series of closed transition switches combine ZTSD operation during a source failure with a highly engineered control system that allows momentary paralleling (100 ms) of two acceptable sources, thereby limiting the impact of transfer on the load.
Page 3
MX250 series
Microprocessor Controller
P
age 3 PB-5066
LEDs are used in a recognizable line configuration for continuous monitoring of switch position. A new LCD display shows source availability, exercise time delay operation and system source condition. A new simplified adjustment is featured for voltage, frequency and time delay settings.
The control operates off a close differential 3 phase under-voltage sensing of source 1, factory standard setting 90% pickup, 80% dropout; under­frequency sensing of source 1 factory setting 95% pickup; voltage and frequency sensing of source 2, factory standard setting 90% pickup voltage, 95% pickup frequency. All factory settings are operator adjustable (see table below).
A test is standard (fast test/load/no load) to simulate source 1 failure - automatically bypassed should source 2 fail.
More Enhanced Features
• Available in ALL transfer modes:
~ Open, Delayed & Bypass ~ Closed (with newly integrated transition control)
• User-friendly programmable engine exerciser, used for the engine generator with or without load, at ANY interval in a one-year period
• Operating voltages available in a single controller for most domestic and international applications
• Real-time display of ATS status, including active timer(s)
• Multiple levels of user-defined password protection
• Serial communications allowing connectivity with other ATS's, paralleling switchgear, and SCADA systems
• Time-tested synchronous logic automatically measures phase angle and frequency allowing disturbance-free transfer
• Unsurpassed statistical ATS/System monitoring available in real-time
• T3/W3 elevator pre-signal. Automatically bypassed if the selected source fails, minimizing time an elevator is without power
• Universal Motor Disconnect (UMD) sends a pre-signal, post-signal or both to any motor control center. Not bypassed in an outage, the UMD ensures safety in the event of a single phase loss
• Voltage unbalance detection standard
• Extensive 2/5/10 Warranty
Performance Features
• UL, CSA and IEC listed
• Ringing wave immunity per IEEE 472 (ANSI C37.90A)
• Condusted and Radiated Emissions per EN55022 Class B
(CISPR 11) (Exceeds EN55011 & MILSTD 461 Class 3)
• ESD Immunity test per EN61000-4-2 (Level 4)
• Radiated RF, electromagnetic field immunity test
per EN61000-4-3 (ENV50140) 10v/m
• Electrical fast transient/burst immunity test
for EN61000-4-4
• Surge immunity test per EN61000-4-5 IEEE C62.41
(1.2 x 50ms, 5 & 8 kV)
• Conducted immunity test per EN61000-4-6 (ENV50141)
• Voltage dips and interruption immunity EN61000-4-11
Technical Benefits
• Separate line voltage components for controller isolation
• Inputs optoisolated for high electrical immunity to transients and noise
• Built-in electrical operator protection
• Simplified maintenance – major components are easily replaceable
• Close differential under-voltage sensing of the normal source
• Voltage and frequency sensing of the emergency source (all settings are adjustable)
LOAD DISCONNECT TD
PRE XFR
TIME REMAINING 04:02
MORE
Entelli-Switch 250
Page 4
ZTS Series Accessory Group Matrix
PB-5066 Page 4
Standard Accessory included in the group package. Optional Accessory not included but can be added to group package. Optional Accessory. Can not be used with accessory having the same symbol. N/A Denotes an Accessory with 2 circuits as a standard. Denotes an Accessory with 3 circuits as a standard.
*
Delayed Transition Units Only.
**
Optional for 40-400 Amp
Accessories
6P A1 A1E A3 A4 Calibrate CDT CDP **DS *DT *DW E EL/P K/P L1 L2 L3 L4 *LN P1 Q2 Q3 Q7 R1-1 R1-3 R15 *R15D R16 R50 S5P S12P S13P T T3/W3 U UMD VI W YEN
MSTDS MEXES
2
2
2
2
2
2
Group Packages
MCONS
2
2
2
2
MSENS MSPES MPSGS
2
2
2
2
2
2
2
2
3
3
2
2
2
2
3
Page 5
ZTS Series
Accessory Definitions
6P
Microprocessor activated test switch (Momentary)
6A
Hardwired test switch (Maintained)
6AP
Microprocessor activated test switch (Maintained)
6B
Hardwired test switch (Maintained Auto ­Momentary Test) Key operated
6C
Hardwired test switch (Maintained Auto ­Maintained Test) Key operated
A1
Auxiliary Contact S.P.D.T. - Normal (Source 1) Failure
A1E
Auxiliary Contact S.P.D.T. - Emergency (Source 2) Failure
A3
Auxiliary Contact - closed in emergency (source 2) Additional available (10 max.) on ZTS and need to be specified
A4
Auxiliary Contact - closed in normal (source 1) Additional available (10 max.) on ZTS and need to be specified
A62
Motor disconnect and staged restart (1 contact)
AB3
Auxiliary Contact - closed in bypass emergency (source 2) (S.P.D.T.) (Standard up to 400A) Additional available (10 max.) on ZTS and need to be specified
AB4
Auxiliary Contact - closed in bypass normal (source 1) (S.P.D.T.) (Standard up to 400A) Additional available (10 max.) on ZTS and need to be specified
B9
Battery charger (ships separate from ATS)- semi­float 5 amp (need to specify input/output voltage and type LA, N, FL)
Calibrate
Microprocessor activated calibration feature
CDP
Programmable exerciser daily, 7/14/28/365 days user-selectable, with or without load.
CDT
Exerciser no load timer. Increased functionality no longer requires a jumper.
CTAP
Chicago transfer alarm panel mounted in door of enclosure. Includes 3 aux. contacts and fuse.
DS
Disconnect Switch. Disconnects source voltage to transfer power panel
DT (Delayed Transition Only)
Time Delay from Neutral Switch position to Source 1 on retransfer
DW (Delayed Transition Only)
Time Delay from Neutral Switch position to Source 2 on retransfer
E
Engine Start Relay
EL/P
Event log of last 16 events
F
Fan contact, closed when engine runs.
HT(1)(2)
Heater and Thermostat 208/240V (1) 380/600V (2) mounted and interwired in enclosure. (requires larger enclosure for 40-200A)
K
Frequency Meter - Door mounted
K/P
Frequency Indication on the controller
L
LNP Center-off position LCD-Indicator Indicating LED lights:
L1 Indicates Switch in Source 2 position. L2 Indicates Switch in Source 1 position. L3 Indicates Source 1 available. L4 Indicates Source 2 available.
M1
Single Phase Amp Meter
M2
Three Phase Amp Meter
M80
Digital Meter Measures and displays true RMS volts, amps and frequency in a three-phase power system.
M82
Digital Meter Includes M80 functions plus Watts, KVA, KVAR, PF, etc. w/Modbus RS485 port
M83
Digital Meter Includes M82 functions plus THD capability and Modbus RS485 port
M84
Digital Meter Includes M83 functions plus unbalance 128 samples/cycle data logging, waveform capture and sag/swell capture.
P
age 5 PB-5066
Page 6
ZTS Series
Accessory Definitions
PB-5066 Page 6
M85
Digital Meter Includes M84 functions plus unbalance 256 samples/cycle data logging, waveform capture and sag/swell capture.
M86
Digital Meter Includes M85 functions plus large graphical screen display with Ethernet communications port.
N1
Running Time Indicator - Door mounted
N2
Operation Counter - Door Mounted
P1
Engine Start Timer (adjustable to 6 sec.)
P2
Engine Start Timer (adjustable to 300 sec.)
Q2
Peak shave/remote load test/area protection ­Relay (S.P.D.T.) (Need to specify voltage - 120 VAC, 24 VAC, 24 VDC - 120V default standard)
Q3
Inhibit transfer to emergency (Source 2) (load add relay) - Relay (S.P.D.T.) (Need to specify voltage ­120 VAC, 24 VAC, 24 VDC - 120V default standard)
Q7
Inhibit transfer to normal (Source 1) - Relay (S.P.D.T.) (Need to specify voltage - 120 VAC, 24 VAC, 24 VDC - 120V default standard)
R1-1/R1-3
Over Voltage sensing for normal (Source 1)
single (R1-1) or three (R1-3) phase
R15/R15D
Load Shed. Should Source 2 become overloaded, a signal can be given to switch to the dead or Mid position.
R16
Phase rotation sensing of Normal (Source 1) and Emergency (Source 2)
R26/R26D
Interruptable Power Rate Provisions. Allow transfer out of Source 1 position to Mid position or dead Source 2. Alarm and Pre-Signal circuit included. (Need to specify voltage - 120 VAC, 24 VAC, 24 VDC - 120V default standard)
R50
In Phase monitor between Normal (Source 1) and Emergency (Source 2) to allow transfer
S5P
Microprocessor activated auto/manual retransfer selector switch for trnsferring to Normal (Source 1) (includes microprocessor activated YN accessory)
S12P
Microprocessor activated auto/manual retransfer selector switch for trnsferring to Normal (Source 1) (includes microprocessor activated YN & YE accessory)
S13P
Microprocessor activated commit/no commit on transferring to Emergency (Source 2) (with enable/disable)
S14
Keyed selector switch for (retransfer to normal-test-auto)
SW1
Auto/Off/Start Engine control selector ­Door mounted (keyed or non-keyed operation available)
SW2
Auto/Off Engine control selector - Door mounted (keyed or non-keyed operation available)
SW3
Source Priority Selector Switch - Door mounted Allows selection of Source 1 or Source 2 to be the Prime Source. Transfer Switch will transfer to selected Prime Source if that Source is available. (keyed or non-keyed operation available)
T
Retransfer to normal adjustable time delay
T3/W3
Pre-signal contact on transfer to Normal (Source 1) or Emergency (Source 2) during test.
U
Engine stop /cool adjustable cool down timer
UMD
Pre and ppost transfer output adjustable time range. Functions in both directions. Includes 2 circuits. Additional circuits available.
VI
Voltage imbalance between phases (3 Phase only)
W
Adjustabvle time delay on transfer to Emergency (Source 2)
YEN
Bypass transfer timers function (soft switch in control)
ZNET
Microprocessor Communication Module
Page 7
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
200,000
200,000
200,000
200,000
200,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
ZTS4 (2) 40 50 400 30,000 22,000 10,000 10,000
ZTS8 (2) 80 100 400 30,000 22,000 10,000 10,000
ZTS10 (2) 100 125 400 30,000 22,000 10,000 10,000
ZTS15 (2) 150 200 400 30,000 22,000 10,000 10,000
ZTS22 (2) 225 300 800 50,000 42,000 35,000 35,000
ZTS26 (2) 260 350 800 50,000 42,000 35,000 35,000
ZTS40 (2) 400 600 800 50,000 42,000 35,000 35,000
ZTS60 600 750 800 65,000 50,000 50,000 42,000
ZTS80 800 1000 1600 65,000 50,000 50,000 42,000
ZTS100 1000 1250 1600 85,000 65,000 50,000 42,000
ZTS120 1200 1500 1600 85,000 65,000 50,000 42,000
ZTS160 1600 2000 2500 100,000 85,000 100,000 85,000
ZTS200 2000 2500 2500 100,000 85,000 100,000 85,000
ZTS300 3000 4000 4000 100,000 85,000 100,000 85,000
ZTS400 4000 6000 5000 100,000 85,000 100,000 85,000
ZBTS10 (2) 100 125 800 50,000 42,000 35,000 35,000
ZBTS15 (2) 150 200 800 50,000 42,000 35,000 35,000
ZBTS22 (2) 225 300 800 50,000 42,000 35,000 35,000
ZBTS26 (2) 260 350 800 50,000 42,000 35,000 35,000
ZBTS40 (2) 400 600 800 50,000 42,000 35,000 35,000
ZBTS60 600 750 800 65,000 50,000 50,000 42,000
ZBTS80 800 1000 1600 85,000 65,000 50,000 42,000
ZBTS100 1000 1250 1600 85,000 65,000 50,000 42,000
ZBTS120 1200 1500 1600 85,000 65,000 50,000 42,000
ZBTS160 1600 2000 2500 100,000 85,000 100,000 85,000
ZBTS200 2000 2500 2500 100,000 85,000 100,000 85,000
ZBTS300 3000 4000 4000 100,000 85,000 100,000 85,000
ZBTS400 4000 6000 5000 100,000 85,000 100,000 85,000
ZTSD4 (2) 40 50 800 50,000 42,000 35,000 35,000
ZTSD8 (2) 80 100 800 50,000 42,000 35,000 35,000
ZTSD10 (2) 100 125 800 50,000 42,000 35,000 35,000
ZTSD15 (2) 150 200 800 50,000 42,000 35,000 35,000
ZTSD22 (2) 225 300 800 50,000 42,000 35,000 35,000
ZTSD26 (2) 260 350 800 50,000 42,000 35,000 35,000
ZTSD40 (2) 400 600 800 50,000 42,000 35,000 35,000
1. For each rating attained in above table, the heat run was performed after the overload and endurance tests.
2. These models also listed for 100% tungsten lamp loads.
3. Consult factory for coordinated breaker types and ratings.
4. All transfer switches are rated in coordination with the protective device installed. Lower rated devices than those shown may be utilized and the system rated accordingly.
5. Consult the factory for
IEC ratings.
GE Zenith
Model No.
UL 1008
ZTS Switch
Rating
GE Zenith ZTS Switches
Rated for Total Systems or Motor Loads (1)
Withstand and Closing Current Ratings per UL 1008 and CSA
Maximum
Fuse Size
Amps
Maximum
Circuit Amps
at 480 VAC
(
UL)
Maximum
Circuit Amps
at 600 VAC
(
CSA)
Maximum
Circuit
Breaker
Size Amps
Maximum
Circuit Amps
at 480 VAC
(
UL)
Maximum
Circuit Amps
at 600 VAC
(
CSA
)
Maximum
Circuit Amps
at 480 VAC (
UL)
Maximum
Circuit Amps
at 600 VAC (
CSA)
Current Limiting Fuse
Specific Coordinated
Breaker Rating (3)
Any Molded Case
Breaker Rating
GE
Zenith ZTS Series Automatic Transfer Switches have been subjected to an extensive test program to show that they comply with and exceed UL 1008 standards, as well as the various performance specifications used by most government agencies and major electrical engineering firms throughout the world. The primary test to ensure the quality and dependability of an automatic transfer switch is its ability to close into and withstand high fault currents. The table shows the Underwriters Laboratories and Canadian Standards certified withstand and closing current ratings in symmetrical
RMS
amperes at 480 and 600 volts AC.
ZTS Series Withstand Ratings
P
age 7 PB-5066
200,000
200,000
200,000
200,000
200,000
N/A
200,000
200,000
ZTSD60 (2) 600 750 800 65,000 50,000 50,000 42,000
ZTSD80 (2) 800 1000 1200 65,000 N/A 50,000 N/A
ZTSD100 (2) 1000 1250 1600 85,000 65,000 50,000 42,000
ZTSD120 (2) 1200 1500 1600 85,000 65,000 50,000 42,000
Page 8
ZTS Series Withstand Ratings
PB-5066
P
age 8
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
150,000
N/A
150,000
150,000
150,000
150,000
150,000
150,000
200,000
200,000
200,000
200,000
200,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
200,000
200,000
200,000
200,000
ZTSCT10 (2)
ZTSCT15 (2)
ZTSCT22 (2)
ZTSCT26 (2)
ZTSCT40 (2)
ZTSCT60 600 750 800 65,000 50,000 50,000 42,000
ZTSCT80 800 1000 1200 65,000 N/A 50,000 N/A
ZTSCT100 1000 1250 1600 85,000 65,000 50,000 42,000
ZTSCT120 1200 1500 1600 85,000 65,000 50,000 42,000
ZTSCT160 1600 2000 2500 100,000 85,000 100,000 85,000
ZTSCT200 2000 2500 2500 100,000 85,000 100,000 85,000
ZTSCT300 3000 4000 4000 100,000 85,000 100,000 85,000
ZTSCT400 4000 6000 5000 100,000 85,000 100,000 85,000
ZBTSD10 (2) 100 125 800 50,000 42,000 35,000 35,000
ZBTSD15 (2) 150 200 800 50,000 42,000 35,000 35,000
ZBTSD22 (2) 225 300 800 50,000 42,000 35,000 35,000
ZBTSD26 (2) 260 350 800 50,000 42,000 35,000 35,000
ZBTSD40 (2) 400 600 800 50,000 42,000 35,000 35,000
ZBTSD60 600 750 800 65,000 50,000 50,000 42,000
ZBTSD80 800 1000 1600 85,000 65,000 50,000 42,000
ZBTSD100 1000 1250 1600 85,000 65,000 50,000 42,000
ZBTSD120 1200 1500 1600 85,000 65,000 50,000 42,000
ZBTSD160 1600 2000 2500 100,000 85,000 100,000 85,000
ZBTSD200 2000 2500 2500 100,000
85,000
100,000 85,000
ZBTSD300 3000 4000 4000 100,000 85,000 100,000 85,000
ZBTSD400 4000 6000 5000 100,000 85,000 100,000 85,000
ZTSD160 (2)
1600
2000 2500
100,000
85,000
100,000
85,000
ZTSD200 (2) 2000 2500 2500 100,000 85,000 100,000 85,000
ZTSD300 (2) 3000 4000 4000 100,000 85,000 100,000 85,000
ZTSD400 (2) 4000 6000 5000 100,000 85,000 100,000 85,000
GE Zenith
Model No.
UL 1008
ZTS Switch
Rating
GE Zenith ZTS Switches
Rated for Total Systems or Motor Loads (1)
Withstand and Closing Current Ratings per UL
1008 and
CSA
Maximum
Fuse Size
Amps
Maximum
Circuit Amps
at 480 VAC
(
UL)
Maximum
Circuit Amps
at 600 VAC
(
CSA)
Maximum
Circuit
Breaker
Size Amps
Maximum
Circuit Amps
at 480 VAC
(
UL)
Maximum
Circuit Amps
at 600 VAC
(
CSA)
Maximum
Circuit Amps
at 480 VAC (
UL)
Maximum
Circuit Amps
at 600 VAC (
CSA
)
Current Limiting Fuse
Specific Coordinated
Breaker Rating (3)
Any Molded Case
Breaker Rating
200,000
200,000
200,000
200,000
200,000
200,000
200,000
200,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
150,000
ZBTSCT10 (2) 100 ZBTSCT15 (2) 150
ZBTSCT22 (2) 225
ZBTSCT26 (2) 260
ZBTSCT40 (2) 400
ZBTSCT60 600 750 800 65,000 50,000 50,000 42,000
ZBTSCT80 800 1000 1600 85,000 65,000 50,000 42,000
ZBTSCT100 1000 1250 1600 85,000 65,000 50,000 42,000
ZBTSCT120 1200 1500 1600 85,000 65,000 50,000 42,000
ZBTSCT160 1600 2000 2500 100,000 85,000 100,000 85,000
ZBTSCT200 2000 2500 2500 100,000
85,000
100,000 85,000
ZBTSCT300 3000 4000 4000 100,000 85,000 100,000 85,000
ZBTSCT400 4000 6000 5000 100,000 85,000 100,000 85,000
100
150
220
260
400
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
200,000 150,000750 800 65,000 50,000 50,000 42,000
Page 9
40, 80
100, 150
225
260, 400
600
1600 2000
3000
4000
800, 1000, 1200
2, 3
4
2, 3
4
2, 3
4
3 4
3 4
3 4
2, 3
4
24 (61) 24 (61)
46 (117) 46 (117)
66 (168) 74 (188)
90 (229) 90 (229)
90 (229) 90 (229)
90 (229) 90 (229)
74 (188) 74 (188)
18 (46) 18 (46)
24 (61) 24 (61)
24 (61) 30 (76)
30 (76) 36 (91)
30 (76) 36 (91)
40 (102)
46.5 (118)
30 (76)
40 (102)
11.13 (28)
11.13 (28)
14.13 (36)
14.13 (36)
19.75 (50)
19.75 (50)
48 (122) 48 (122)
48 (122) 48 (122)
60 (152) 60 (152)
19.75 (50)
19.75 (50)
A A
A A
B B
C C
C C
C C
B B
21 (10) 24 (11)
70 (32) 75 (34)
165 (75) 185 (84)
345 (156) 450 (204)
465 (211) 670 (304)
770 (349)
1025 (465)
190 (86) 210 (95)
57 (26) 60 (27)
165 (75) 170 (68)
380 (172) 430 (195)
1010 (458) 1160 (526)
1130 (513) 1395 (633)
1595 (723) 1850 (839)
455 (206) 540 (245)
1 – 7
1 – 7
1 – 8
1 – 8
1 – 10
1 – 10
1 – 8
Ampere
Rating
Poles
Height
(A)
Width
(B)
Depth
(C)
Reference
Figure
Open
Type
NEMA 1
Application Notes
NEMA 1 Enclosed Weight
ZTS Model Transfer Switches
1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent to English measurements in inches and pounds.
2. Includes 1.25" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc.
3. All dimensions and weights are approximate and subject to change without notice.
4. Special enclosures (NEMA 3R, 4, 12, etc.) dimensions and layout may differ. Consult the
GE Zenith factory for details.
5. Normal and emergency may be ordered inverted on any switch. The load may be inverted 600-1200 amps. Consult the factory for details.
6. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact the
GE Zenith factory.
7. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc.
8. Add 4" in height for removable lifting lugs.
9. Lug adapters for 3000-4000 amp limits may be staggered length for ease of entrance. Consult the
GE
Zenith factory for details.
10. Ventilation louvers on both sides of enclosure at 3000 and 4000 amps. One must be clear for airflow with standard cable connections.
Application Notes:
Notes:
*
Line and load terminals are located in rear and arranged for bus bar connection. Terminal lugs are available at additional cost. Contact factory for more details.
1. Special terminal lugs and neutral bars are available at additional cost. Contact factory and advise cable sizes and number of conductors per pole.
2. Fully rated neutral provided on 3 phase, 4 wire system.
3. Normal and emergency may be ordered inverted on any switch. Load may be inverted 600-1200 amps. Consult the factory for details. es:
4. Lug adapters for 3000-4000 amp units may be staggered length for ease of entrance. Consult the factory for details.
5. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact the
GE Zenith factory.
AL-CU UL Listed Solderless
Screw-Type Terminals for
External Power Connections
Switch Normal, Switch Normal
Size Emergency, Size Emergency,
Amps & Load Terminals Amps & Load Terminals
Cables/ Wire Cables/ Wire
Pole Ranges Pole Ranges
40-150 1 #8 to 3/0 800/1000 4 #2 AWG to
AWG /1200 600 MCM
225 1 #4 AWG to 1600
600 MCM
260 1 #4 AWG to 2000
600 MCM
400 1 #4 AWG to 3000
600 MCM
600 2 #2 AWG to 4000
600MCM
*
P
age 9 PB-5066
ZTS Series
Dimensional Specifications / Power Connection Terminals
A
CB
Figure A
A
C
B
Figure B
Figure C
Page 10
A Product of GE Industrial Systems General Electric Company
830 West 40
th
Street, Chicago, IL 60609 USA
773 299-6600, Fax: 630 850-6899
www.geindustrial.com
g
GE Zenith Controls
ZTS Series
Ordering Information
Model/Type
Ampere
Size
Switched
Poles
Enclosure
Type
Operational
Voltage
Accessories
A
B
Consult Table Below
0
4
40 amps
N
Type 1 Enclosed
Open Style Unit
B
2 Poles
F
4 Poles
E
3 Poles
B 0
Entelli-Switch 250
Microprocessor
Control Unit
Standard (Open Transition)
Z
Example
ZTSCT0B0040F-N0140STD
This number string shows the correct format for a
ZTS Model Automatic Transfer Switch with closed transition,
an Entelli-Switch 250 microprocessor control unit, Utility - Generator, 400 amps, 4 pole,
NEMA Type 1 enclosure,
120/208V 3Ø, 4 wire, 60 Hz system with the standard group of accessories.
T
D
S
M
X
E
E
B 0
Control
Panel
Switch Types
Standard: Unless otherwise noted, the standard
switch with quick transfer will be supplied.
Delayed Transition: When ordered as the ZTSD,
the delayed transition switch offers time delay during transfer from one position to the other. This is primarily for transfer of large motor or inductive loads.
Closed Transition: When ordered as the ZTSCT,
the closed transition switch offers two basic modes of operation. During a failure of one source or an out of specification condition, the ZTSCT Model operates as a standard delayed transition switch (
ZTSD Model).
This sequence allows clear separation of an unreliable source from an available one.
Bypass: When ordered as the ZBTS, the bypass
transition switch offers a draw-out mechanism, with electrical and mechanical interlocks for secure removal after load bypass. In this way the transfer switch and/or the control panel may be tested, isolated and removed for maintenance without load interruption.
Then choose
additional
accessories
0
0
8
80 amps
0
1
0
100 amps
0
1
5
150 amps
0
2
0
200 amps
0
2
2
225 amps
0
260 amps
4
0
400 amps
0
6
0
600 amps
0
8
0
800 amps
0
0
0
1000 amps
1
2
0
1200 amps
1
6
0
1600 amps
1
0
0
2000 amps
2
6
0
2600 amps
2
0
0
3000 amps
3
Config.
0
Utility - Generator
M
Manual
U
Utility - Utility
0
0
0
2
6
0
Type 4 Enclosure
Type 12 Enclosure
Type 4X Enclosure
Type 3R Enclosure
0 1
N
1 2
N
3 R
N
0 4
N
4 X
X
0 0
T
S
Z
Delayed Transition
0
0
D
T
S
Z
Closed Transition
T
0
C
T
S
Z
Standard (Open Transition) w/ Bypass
0
0
S
B
T
Z
Delayed Transition w/ Bypass
D
0
S
B
T
Z
Closed Transition w/ Bypass
C
T
S
B
T
Z
3
0
300 amps
0
0
0
4000 amps
4
O
N
C
E
N
S
P
E
S
S
G
P
A B Voltage Phase Config. Hz
1 0 120 1 2 wire 60
2 0 120/240 1 3 wire 60
2 1 120/208 3 3 wire 60
3 0 240 3 3 wire 60
3 1 208 3 3 wire 60
3 2 220 3 3 wire 50
3 3 120/240 3 4 wire 50
3 4 110/220 3 4 wire 60
3 5 139/240 3 4 wire 60
3 8 120/240 3 4 wire 60
4 0 120/208 3 4 wire 60
4 1 127/220 3 4 wire 60
4 2 127/220 3 4 wire 50
5 0 480 3 3 wire 60
5 1 440 3 3 wire 60
5 2 440 3 3 wire 50
5 5 460 1 3 wire 50
5 7 480 1 2 wire 60
5 8 254/440 3 4 wire 60
6 0 575 3 3 wire 60
6 1 347/600 3 4 wire 60
7 0 277/480 3 4 wire 60
7 1 277 1 2 wire 60
7 4 266/460 3 4 wire 60
7 5 460 3 3 wire 60
8 0 120/240 2 4/5 wire 60
8 2 380 1 2 wire 50
9 0 240/416 3 4 wire 60
9 1 220/380 3 4 wire 60
9 2 220/380 3 4 wire 50
9 3 240/416 3 4 wire 50
9 7 380 3 3 wire 60
Note: Operating voltage must be specified at time of order. Only the most common voltages are shown above.
S
M
S
M
S
M
S
M
S
M
S
Contents contained in this document are subject to
change without notice. Contact GE to verify details.