GE
GEH-5746E
INSTRUCTIONS
g
Lighting Solutions
READ THOROUGHLY BEFORE INSTALLING
WARNING
Risk of electric shock
• Turn power off before servicing
– see instructions
NOTE: Make all electrical connections in accordance with the National Electrical Code and any
applicable local code requirements.
WARNING
Risk of fire
• Keep combustible materials away
from lens – see instructions
• Use lamps specified on nameplate
Ultra Sport
with Hot Restart Option
CAUTION
Unit will fall if not installed properly
• Follow installation instructions
TM
Luminaire
NOTE: Do not place combustible materials within 7
feet (2 meters) of the front of the reflector lens.
This luminaire is designed for use in outdoor applications and must adhere to 25°C Max. ambient temperature limitation unless otherwise stated on nameplate.
Install and maintain it according to the following recom-
mendations.
NOTE: Verify that supply voltage is correct by
comparing it to nameplate.
SERVICE CONSIDERATIONS
Sealed Reflector Assembly
Luminaire is equipped with
a safety circuit to prevent lamp
operation if the lens is broken.
If any component such as
reflector, lens or casing is
damaged the complete
assembly must be replaced.
Relamping Door
Luminaire is shipped with
lamp in place. Door may be
opened for relamping. Door
must be sealed during operation.
Ballast Compartment
DO NOT REMOVE THIS COVER!—There are
no field serviceable components under this
cover. Ballasting components must be
maintained by factory trained service technicians only.
STEP 1 — INSTALLATION PROCEDURES
Verify that the drain holes are in the proper locations
for the intended aiming direction. If not contact the
factory.
Drain holes for
fixtures aimed below
horizontal.
STEP 2 — LUMINAIRE MOUNTING
Reference Mark
Angle Indicator
Adjustment
Bolts (2)
Crossarm Adapter
and Hardware (not supplied)
Drain holes for
fixtures aimed above
horizontal.
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation
or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be
referred to GE Lighting Solutions.
Step 3 — LUMINAIRE AIMING
Two sighting systems are provided for your convenience.
Use the sight system which is most easily accessed.
Optical Sight:
A . Rotate sight into vertical
position.
B . Align the reference
mark of top of reflector
flange with notch in
sight for proper aiming.
Base Sight
A. Rotate front and back
sight into vertical
position.
B. Align the two sighting
holes for proper aiming.
Step 4
After positioning luminaire, tighten all mounting
hardware.
STEP 5
Connect power cable to suitable supply in accordance
with all applicable codes.
INSTALLATION CLEANING
DO NOT CLEAN INTERNAL OPTICAL SYSTEM
The UltraMSport floodlight has been specially
cleaned at the factory. Field cleaning of the internal
optical system during installation is not recommended.
EXTERNAL CLEANING
Initial cleaning of the outside of the glass lens may be
required to ensure optimum optical efficiency.
Clean front glass with a mild soap and water solution,
rinse clean and wipe dry.
CAUTION
Risk of burn
• Allow lamp/fixture to cool before
handling
CLEANING INSTRUCTIONS AND CAUTIONS
Caution: do not touch quartz tube with bare hands! If
lamp is handled, finger prints, grease or oils should be
removed from the lamp with isopropyl alcohol. This will
remove materials which cause whitish spotting and
premature lamp failure. Dry lamp carefully with cotton or
clean cloth.
PERIODIC CLEANING WHEN RELAMPING
INTERNAL
Should the internal reflector system require
cleaning, use only non-abrasive, neutral (pH 6-8) cleaner
containing no chlorinated or aromatic hydrocarbons.
Rinse clean and wipe dry.
EXTERNAL
Clean front glass with a mild soap and water solution,
rinse clean and wipe dry.
LAMP REPLACEMENT
A . Insert the lamp terminal into the socket terminal
(a) at both ends of the lamp and tighten screws.
B. Snap the lamp ends into the lamp retaining clips
(b).
C. Close and rebolt the relamping door. Tighten