2. Spring Start-Up Following Winterization ……………………………………………………………………… p.23
I. TROUBLESHOOTING …………………………………………………………… p.26
J. SYSTEM SPECIFICATIONS …………………………………………………………… p.27
K. FREQUENTLY ASKED QUESTIONS …………………………………………………………… p.28
L. REPLACEMENT PROCEDURES AND PARTS LIST …………………………………………………………… p.30
This manual outlines some of the basic
principles of household water collection,
treatment, discharge and some of the features
of the Homespring Water Purifier System (the
“System”). It is not intended to be a definitive
dissertation on the principles set out above, nor
is it intended to be relied upon by anyone but
Homespring Customer Care (“Consultants”)
and Qualified Service Technicians. Any other
reliance is expressly excluded. Further, in so far
as Consultants and Homespring Qualified Service Technicians are concerned, this
document must be utilized in connection with
all authorized training procedures created by
Homespring and/or GE Water & Process
Technologies. It should be remembered that
homeowners will also be provided with an
Owner’s Manual, which will provide a more
general overview of the above mentioned
principles and features of the System.
The Homespring Water Purifier System must
be installed by a Homespring Qualified Technician and properly maintained in
accordance with the Operations and the
Owner’s Manual. Failure to properly maintain
the System will compromise performance
and/or result in the failure to control water
quality.
B. SAFETY WARNINGS
Before, during and after installation, follow the
safety instructions provided in this manual to
avoid possible serious illness or death from
contaminated water.
1. WARNING! Operational
All System Parts and Components must be
installed in accordance with all local building
and plumbing codes.
The System must be installed on a cold-water
supply line only. Failure to do so may cause
System damage, leading to personal injury
and/or physical damage.
The System has been designed, built and tested
to offer reliable service, provided if it is installed,
commissioned, operated, maintained and
tested in strict accordance with the instructions
contained in this manual. Failure to properly
maintain the System will compromise
performance and/or result in a failure to control
water quality, which may lead to delivery of
contaminated water. Consuming contaminated
water could result in serious injury or possibly
death.
To avoid System damage, ensure that a
Stainless Steel Prefilter or Carbon Prefilter is in
place during operation of the System. Failure to
do so will void all warranties. In the absence of
either filter, abrasive damage to the System
may occur. A damaged System may permit
contaminated water to enter the household
distribution system, causing illness or death.
Irreversible and premature fouling of the
System may also occur resulting in System
replacement at the owner’s expense.
Tools used to install the System should be
maintained in sterile condition so that the risk
of cross-contamination is minimized. Bacteria,
parasites, and viruses can live for long periods
of time. As a result, dangerous organisms can
be carried from one installation or maintenance
site to another and may potentially cause
serious personal injury, sickness and/or death.
Proper tool care and disinfection procedures
will minimize these risks. Always wash hands
thoroughly with soap and water after servicing
the System.
Do not attempt to remove System Cap when
System is under pressure.
Premature fouling of the System is not covered
by the warranty.
The System has a shelf life of ten months
after its manufacturing.
The System must be kept wet all times after
installation. Do not let the System dry for longer
than 12 hours. Failure to do so may damage
the System causing personal injury, physical
damage, illness and/or death and will void all warranties.
Except in emergencies, do not open the bypass
valve (if applicable); bypassing the System may
contaminate water supply and water supply
system.
ONLY OEM parts supplied by the manufacturer
are to be used when installing or servicing the
Filtration system (System). Failure to do so may
result in System damage, serious personal
injury,
2
death and/or property damage. Use of nonOEM parts will void the manufacturer’s
warranty.
2. WARNING! Biological
The System is not intended for the treatment of
water from an obvious contamination source
(such as sewage or wastewater).
Biofilm and pathogens already present in home
piping lines downstream of the system could
migrate into filtered water unless the piping has
been properly sanitized. All household piping
and distribution lines should be sanitized prior
to consuming the filtered water using proper
sanitization procedures (see your local Health
Authority). The system owner should verify the
water outlet quality at the outlet sources by
having it tested by an approved or qualified
water testing laboratory prior to consumption.
The System must be commissioned and
maintained in accordance with the Owner’s
Manual by an Authorized Service person.
Failure to properly maintain the System will
compromise performance and shorten the life
of the System and may result in delivery of
contaminated water. Consuming contaminated
water could result in serious injury or possibly
death.
3. WARNING! Emergency Bypass
Safety
If System is equipped with a Bypass Valve, do
not open Bypass Valve except in emergencies.
Opening the Bypass Valve will permit potentially
microbiologically contaminated water to enter
the household water distribution system.
Drinking contaminated water may cause
serious illness and/or death. Do not drink the
water if the System has been operated in
bypass mode.
If the System has been operated in bypass
mode and if the water is being drawn from a
well or surface water source, the System and
the household water distribution system should
be disinfected again once returned to filtration
mode.
If the System is in bypass mode, the controller
must be unplugged. Failure to do so may cause
System to dry and become damaged, leading
to personal injury, and/or physical damage and
will void all warranties.
A bypass is not required for proper operation of
the System. However, some local plumbing
codes may require a bypass. If a bypass is to be
installed, the procedure described below is to
be followed in order to provide water in an
emergency or during System malfunction.
3.1 Bypass Procedure
1. Close Inlet and Outlet Valves. (If ball valves
are installed, turn the handles perpendicular to
the water pipe.)
2. Open Bypass Valve (If ball valve is installed,
turn the handle in-line with the water pipe).
3. Unplug Controller.
3.2 To return to filtered water service:
1. Close Bypass Valve. (If ball valve is installed,
turn the handle perpendicular to the water
pipe.)
2. Open Inlet and Outlet Valves. (If ball valves
are installed, turn the handles in-line with the
water pipe.)
3. Plug in the controller.
4. Follow the Cleaning section under F. COMMISSIONING in this manual to
recommission the System.
4. WARNING! Winterization
The System will be damaged if frozen. The
System must be winterized according to the
Winterization Procedure described in this
manual. The System must be winterized prior to
temperatures falling below 32°F (0°C). Failure to
do so may cause the System to dry, freeze,
become damaged, and will void all warranties.
Operating a damaged System may lead to
personal injury, and/or physical damage.
5. WARNING! Cleaning
The MC-1 cleaner SHOULD NOT be combined
with any other chemical or cleaning solution,
especially hypochlorite or household bleach.
Failure to do so can result in serious personal
injury, illness, or death.
C. CERTIFICATIONS
Current System certifications, as well as the
limits to those certifications held, are listed
below.
The System should only be installed where it
complies with provincial, state or municipal
laws and regulations.
The System should only be used to filter cold
supply water.
1. NSF Certifications
The System conforms to ANSI/NSF 42/53 for the
claims set out below, as verified and
substantiated by test data.
The UF 211 model has been certified as:
3
System Tested and Certified by NSF
International against NSF/ANSI 42 and 53 for:
• Cyst Reduction
• Turbidity Reduction
• Particulate Reduction - Class 1
The UFC 211 Model (equipped with a Carbon
Prefilter) has been certified as:
System Tested and Certified by NSF
International against NSF/ANSI 42 and 53 for:
• Cyst Reduction
• Turbidity Reduction
• Particulate Reduction - Class 1
• Chlorine, Taste and Odor Reduction
UFC 211 model Chlorine Reduction Capacity
Rating:
130,000 / 491,400 (US gallons/liters)
Models with activated carbon filter option
certified for cyst reduction may be used on
disinfected waters that may contain filterable
cysts.
2. BioVir Laboratories
NELAP* and California Department of Health
accredited laboratory
*National Environmental Laboratory
Accreditation Program (NELAP) Accredited
#05234CA
The Homespring UF200 Series** Water Purifiers
have been tested by BioVir Laboratories Inc.
and found to meet all the requirements of the
USEPA’s Guide Standard and Protocol for
Testing Microbiological Water Purifiers (OPP
Task Force Report, 1987) as interpreted by the
BioVir Laboratories specifically for the
Homespring UF200 Series Products.
The test results were:
Bacteria Reduction: >99.99999%
Virus Reduction: >99.999%
**Applies to the following models: UF211,
UFC211
3. Water Quality Association
The Homespring UF200 Series Water Purifiers
have been tested and certified by the Water
Quality Association (WQA) to the USEPA’s Guide
Standard and Protocol for Testing
Microbiological Water Purifiers (OPP Task Force
Report, 1987) as interpreted by the WQA and to
NSF/ANSI 42 and 53.
Applies to the following models: UFC 211, UF
211.
D. CONTACT INFORMATION
GE Water & Process Technologies
3239 Dundas Street West
Oakville, ON, Canada
L6M 4B2
Phone: 1-866-418-7412
www.homespring.com
E. INSTALLATION INSTRUCTIONS
All sales, commissioning and maintenance
personnel are required to participate in a
Homespring Qualified Technician training
program to ensure that they have been trained
to maintain and diagnose the System. Since the
primary usage of the System is to remove
bacteria, certain parasites and certain viruses
from drinking water sources, this certification
program is important and mandatory for both
safety and liability reasons.
All efforts must be made to ensure that
installations are performed in a careful, sanitary
manner for the safety of the homeowner, home
occupants, and technicians.
The following section outlines the installation
procedures, the tools required in the
installation, and the commissioning procedures.
Note: The images in this manual may appear
slightly different than the actual System or
parts.
WARNING!
To reduce the risk of severe injury, illness, death
and/or property damage, read and follow all
instructions. Use only factory supplied parts,
where required.
1. System Installation Location with
other Water Treatment Devices
If other water processing devices are currently
installed in the home, the System should be
located as shown in the diagram:
4
A water softener can be placed either before
(upstream) or after (downstream) the System. If
the softener is downstream of the System, it is
recommended that a supply line of hard water
be plumbed to the kitchen so that filtered,
mineralized water can be utilized in food
preparation and for human consumption.
If a chlorinator is used to control bacterial and
virus growth in pipes, a Stainless Steel Prefilter
may be installed in the System instead of a
Carbon Prefilter.
2. System Configuration for Standard
Installations
For households on a municipal system, locate
the water main, which connects the household
to the municipal supply line. Usually this is near
the water meter. For private pump/pressure
tank style system, locate the outlet of the
pressure tank. The System must be installed
downstream of the water meter or pressure
tank in order to provide treated water to the
whole household.
The System is installed directly in-line with the
home supply, following the water meter or
pump and pressure tank.
Note: A dedicated line, diverted from the main
water line, may be installed upstream of the
System for all exterior taps, pool or hot tub
makeup valves, and irrigation systems. This
arrangement will extend the life of the System
membrane.
3. System Configuration for models
equipped with optional Surface Water
Option Kit
Systems purchased with the Surface Water
Option Kit are installed at the same location
and in the same manner as a standard System,
with the exception of additional parts, which
must be installed, as shown. Additional parts
include an Inlet Solenoid Valve, Check Valve,
and External Prefilter.
Note: The Inlet Solenoid Valve of the Surface
Water Option Kit creates a non-pressurized
draining of the System. The entire drain line,
including the floor drain, must be below the
Drain port of the System.
WARNING!
When treating surface water sources, an
External Prefilter of 25-microns nomimal mesh
size is required. Failure to provide this level of
prefiltration may lead to System damage and
will void the warranty. A damaged System may
cause serious personal injury, illness, and/or
death.
4. Tools, Supplies and Parts
WARNING!
Tools used to install the System should be
maintained in sterile condition so that the risk
of cross-contamination is minimized. Bacteria,
parasites, and viruses can live for long periods
of time. As a result, dangerous organisms can
be carried from one installation or maintenance
site to another and may potentially cause
serious personal injury, sickness and/or death.
Proper tool care and disinfection procedures
will minimize these risks.
The following list of tools and supplies are
required for the completion of this installation:
5
4.1 Tools (not provided)
- Slip joint pliers 12”
- Pipe Wrench 12”
- Adjustable wrenches
- Torpedo Level
- Fine slot drivers
- Phillips drivers: #0,1
- Nut drivers:5/16, 3/8
- Knife
- Air pump
- 1/4" Hex key
- Torch with gas
- Masonry Drill with 3/8” bit
- Robertson drivers: #1,2
- Snips
4.2 Supplies Required (not provided)
- Copper pipe
- Assorted Copper fittings
- Flux and flux brush
- Solder (Lead free)
- Tie wraps or cable ties
- Teflon® tape or pipe dope (for potable water)
- 5/8” hose for drain (comply with local
plumbing code)
- 3 water shut-off valves (same size as install
piping)
- Unscented Chlorine Bleach- 5-6% or 12%
2’ x 2’ patio stones (required only for heated
floor)
pen or pencil
- Funnel
- Hose clamps
- Suspension strap
- Ground wire
4.3 Tools supplied with Service Testing Kit
- Integrity Tester
- Cap Wrench
- Two 1/4” tubings
- Silicon Lubricant - DOW CORNING 111
- Housing Wrench
- Two Pressure Gauges
- Digital Air Pressure Gauge
- Transformer
- 2 JG Mini Ball Valve
4.4 Spare parts (Recommended)
- AA batteries
- Inlet Solenoid Valve
- Air Relief Valve
- 1/4” Mini Ball Valve with Plug
- Advanced Plus Controller
- Stainless Steel Flex Hose
- Drain Solenoid Valve
- O-ring
- 3/4" Inlet/Outlet Fitting, 1/2" Nipple.
WARNING!
Ball valves are recommended for use as the
Bypass, Inlet and Outlet Valves. Gate valves
have a tendency to leak, allowing unfiltered
water to mix with filtered water. The result may
cause personal injury, sickness and/or death.
Prior to beginning the installation, check for the
following:
• Space near point of entry of water supply
• Footprint and Height Clearance:
Vertical Systems
Footprint: minimum18"x18" (46cm x 46cm)
Height clearance: minimum 74” (188cm)
Horizontally-mounted Systems
Footprint (including 14” (36cm) of clearance
beyond the System Cap): minimum 24” x 74”
(61cm x 188cm)
Height clearance: minimum 36” (91cm)
• All Systems - level area (for floor mounting)
• Indoors with ambient temperature between
40°F-90 °F (4°C-32°C)
• Drillable floor, patio stone, or wood base
• Electrical outlet, 120VAC/230VAC, within 10’
(305cm)
• Existing water equipment (e.g. water
softeners, filters upstream and UV downstream)
• Recommended household water pressure is
2.07 bars (30 psi) minimum. If water pressure is
less than 30psi, adjust Backpluse Tank
pressure. Refer to Step 4 in the System Installation section.
• Drain within 20’ (610cm) and up to 72”
(183cm) high. If the System is to be equipped
with an Inlet Solenoid Valve, the drain cannot
be higher than the drain port (60 cm) of the
System for proper draining.
Note: All outlets downstream of the System will
provide filtered water.
7. Part Identification
8. Horizontal Mounting
If the installation requires the System to be
installed horizontally, complete the steps
described in this section. If the System is to be
installed in a vertical orientation, go to the
System Installation section.
The Horizontal Mounting Kit is to be purchased
separately. The Horizontal Mounting Kit must be
used in the installation of Horizontally-mounted
Systems.
8.1 Planning
The Horizontal Mounting Bracket must be
assembled and installed prior to the installation
of the System.
8.1.1 Mounting
The Horizontal Mounting Bracket can be
installed either on the floor or on a wall, with
adequate support. If mounted on a wall, the
Bracket must be supported by studs, or
mounted directly onto brick/block. The width of
the Bracket is 36" (91cm) on center and can be
installed directly across three wall studs if the
wall studs are spaced 18" (46 cm) apart. If the
wall studs are spaced differently, two pieces of
2x4 lumber must be mounted horizontally, at 8"
(20 cm) apart middle-to-middle, on the wall
studs to provide mounting surfaces for the
Bracket. The fasteners used in mounting the
two pieces of 2x4 lumber to the wall studs must
be strong enough to support a minimum weight
of 180lb (82 kg).
8.1.2. Spacing
For servicing, leave a minimum of 14" (36 cm)
clearance beyond the System Cap. The vertical
spacing required is 36" (91 cm) from the bottom
of the bracket. If possible, install the System at
a height convenient for servicing.
7
8.1.3 Orientation
The Horizontal Mounting Bracket can be
configured to suit installation, in which the
System Cap points to the left or the right. The
bottom of the System is cradled in the concave
feature of the Cast Iron Stand. The figure below
shows the configuration for a right-pointing
System. For left-pointing System configuration,
flip both Cast Iron Stands up side down.
8.2 Installation
8.2.1 Depending on the particular installation,
orient the cast iron stands in either a left
pointing or rightpointing System configuration.
8.2.2 Connect the two Cast Iron Cross Members
together using the three 1/4" x 1” bolts and lock
nuts.
8.2.3 Attach the two ends of the Cross Member
assembly to the Cast Iron Stands using the four
5/16” x 1 1/4” bolts and lock nuts.
8.2.4 (a) FLOOR MOUNTING
If the System is mounted on the floor, the floor
surface must be leveled. Place patio blocks
beneath the Bracket assembly and level the
blocks with sand or stone if necessary.
Drill into the concrete floor or block and anchor
the Bracket with the four supplied concrete
bolts. Three of the concrete bolts come with the
System and the forth bolt is supplied with in
Horizontal Mounting Kit. If required, use the
shims supplied with the System for leveling.
Note: If the System is being installed on a
heated floor, use a 2’x2’ patio stone for a base.
Do not drill the floor.
8.2.4 (b) WALL MOUNTING
The Bracket assembly must be mounted
directly to the wall studs or the two pieces of
2x4 lumber installed earlier. The four 2½” wallmounting anchoring bolts are for wood studs
only. If the wall is made of concrete, use
appropriate concrete bolts for this installation.
- Mark the first hole location on the stud or
lumber. Ensure that all spacing requirements
are satisfied.
- Drill a hole suitable for the supplied 2½”
anchoring bolt.
- Leaving one end of the Bracket assembly on
the ground for support, lift the opposite end of
the Bracket up, align the top mounting hole on
the Bracket assembly with the pre-drilled hole
on the wall stud, and secure the Bracket
assembly with one 2½” anchoring bolt. Do not
tighten this bolt completely.
- Swing opposite end of the Bracket assembly
upward. Level the Bracket. Mark the locations
of the remaining three anchoring bolts with a
pen or pencil.
- Lower the unattached end of the Bracket
assembly back to the floor.
- Pre-drill the three holes for the remaining
three 2½” anchoring bolts at the marked
locations.
- Lift Bracket assembly up again, insert the
three 2½” anchoring bolts, and tighten all four
anchoring bolts.
9. System Installation
9.1 The System is shipped fully assembled,
except for the System Base. Attach the System
Base to the Backpulse Tank, using the supplied
3/8” bolts and washers.
8
9.2 Stand the System upright carefully.
Note: Cut open the plastic bag before standing
the System upright.
WARNING!
Handle the System with care. The outside
surfaces of the System may be slippery with a
food-grade preservative used in the
manufacturing process.
WARNING!
If the Backpulse Tank has less than 20 psi (1.38
bars) of pressure, the integrity test will fail.
Only check the Backpulse Tank when the
System is depressurized.
9.3 The Backpulse Tank has been prepressurized to approximately 30-35 psi (2.07-
2.41 bars) from the factory. Confirm the
Backpulse Tank pressure. If the Backpulse Tank
pressure is less than 30 psi (2.07 bars), add air
using a pump. Recheck the pressure after 15
minutes to ensure that there are no leaks in the
Backpulse Tank.
9.4 The pressure may require adjustment
depending on the water system of the home.
Refer to the Table below to ensure proper tank
pressure. Air can be added or released from the
Air Bladder Valve as required.
WARNING!
Do not pressurize the Backpulse Tank to greater
than 35 psi (2.41 bars). Higher pressures may
cause the tank’s bladder to burst, leading to
ineffective daily cleaning. Ineffective cleaning
can greatly reduce the life of the System,
leading to personal injury, illness, and/or death.
Once the Backpulse Tank pressure is checked,
adjusted, and set, record final pressure on the
Service Tag and on Page 2 of the Owner’s
Manual.
10. Pipe Assembly and Installation
Ensure that all threaded connections are fitted
with NSF approved Teflon® Tape or Pipe Dope
(for potable water) to prevent leakage. For
Systems being installed on surface water
applications, the Surface Water Option Kit must
be installed.
10.1 Turn off water supply where the water
enters the home.
Vertical Systems:
Plumb the Inlet pipe at approximately 48”
(122cm) and the Outlet pipe at approximately
20” (50cm) off the ground. Install water shut-off
valves on the new plumbing. The terminal ends
of the new plumbing must be a 3/4" MNPT
adapter in order to use the supplied Stainless
Steel Flex Hoses.
Note: The water bypass in the figure only
bypasses the System. This configuration may
be required according to the local plumbing
code in your area.
Horizontally-mounted Systems:
Plumb the Inlet pipe at approximately 48”
(122cm) away and the Outlet pipe at
approximately 20” (50cm) away from the End
Cast Iron Stand. Install water shut-off valves on
the new plumbing. The terminal ends of the
new plumbing must be a 3/4" MNPT adapter in
order to use the supplied Stainless Steel Flex
Hoses.
Right-pointing System configuration shown
9
For left-pointing System configuration,
reverse horizontal orientation in FIGURE 13.
Note: The water bypass in the figure only
bypasses the System. This configuration may
be required according to the local code in your
area.
10.2 The two Inlet/ Outlet Fitting assemblies are
shipped pre-assembled, with the Mini Ball
Valves and Plugs already installed. Ensure that
the Teflon® tape at both threaded ends are in
good condition. Assemble the Inlet and Outlet
Fitting assemblies as shown.
Inlet Fitting Assembly
The directional arrow on the Inlet Solenoid
Valve must point in the direction of the water
flow.
Outlet Fitting Assembly
The directional arrow on the Check Valve must
point in the direction of the water flow.
10.3 Install the Drain Solenoid Valve (normally
closed) to the 1/2" Nipple to the Drain port of
the System. The directional arrow on the Drain
Solenoid Valve must point in the
water flow (i.e. away from the System).
the
Install the Nylon Elbow to the flow exit port of
the Drain Solenoid Valve.
Horizontally-mounted Systems
Install the 1/2" Nipple and the 1/2" Brass Elbow
provided in the Horizontal Mounting Kit at the
Drain port of the System. Install the Drain
Solenoid Valve to the 1/2" Brass Elbow using
another 1/2" Nipple.
10.4 Applicable to Horizontally mounted
Systems: The System Base is not required in
this installation. Peel off the adhesive backing
on the foam gasket supplied in the Horizontal
Mounting Kit. Attach the foam gasket to the
concave feature on the End Cast Iron Stand.
direction of
Lift up and place the System in the Bracket.
Orient the System to make the Inlet, Drain, and
Outlet ports facing downward. Ensure that the
channel on the back of the System locks into
the tab on the Middle Cast Iron Stand.
Using two of the 3/8” bolts supplied with the
System, fasten the bottom of the System to the
cross bar on the End Cast Iron Stand. The
Middle Cast Iron Stand is attached to the Cast
Iron Cross Member by two 1/4" bolts and lock
nuts. Unscrew the 1/4" bolt and lock nut closest
to the System.
Position the semi-circular Metal Support Strap
over the System. Align the holes on the Metal
Support Strap with the holes on the Middle Cast
Iron Stand. Reusing the 1/4" bolt and lock nut
from the last step, fasten one end of the Metal
Support Strap to the Middle Cast Iron Stand.
Use the remaining 1/4" bolt and lock nut
supplied in the Horizontal Mounting Kit to
fasten the other end of the Metal Support Strap
to the Middle Cast Iron Stand.
10
10.5 Applicable to Systems in non-surface
water applications only: Connect the Inlet and
Outlet Fitting assemblies to the 3/4" MNPT ends
of the new plumbing with the supplied Stainless
Steel Flex Hoses.
10.6 Applicable to Vertical Systems only: Once
the Inlet and Outlet plumbing connections are
made, the System must be secured to the floor.
Drill a 3/8" hole through the feet of the System
Base.
To level the System, insert the supplied shims
beneath the feet of the System Base. Check
with a level. Once leveled, fasten the System to
the floor with the supplied 1/4" x 2 1/2”anchors
(for concrete floor) or use screws (not supplied)
for wood floors.
Note: If the System is being installed on a
heated floor, use a 2’x2’ patio stone for a base.
Do not drill the floor.
10.7 Vertical Systems: Apply Teflon® tape to
the 1/4" threads on the Air Relief Valve. Using a
pair of pliers (or a hex key if applicable), remove
the plug that is located at the top of the System
Cap. Thread the Air Relief Valve into the
opening. Do not use tools to tighten the Air
Relief Valve to the System Cap as it may cause
damage. Back off the black cap of the Air Relief
Valve 1-1/2" turns to allow for proper venting.
Horizontally mounted Systems: NOTE: Ensure
that all threaded connections are fitted with
Teflon® tape or pipe dope (for potable water) to
prevent leakage.
Inlet Fitting Assembly: Follow instructions in
the System Operations Manual to assemble the
Inlet Fitting Assembly. If the Surface Water
Option Kit is installed, rotate the Inlet Solenoid
Valve right-side-up.
Drain Line Assembly: Install the 1/2" Nipple
and the 1/2" Brass Elbow provided in the
Horizontal Mounting Kit at the Drain port of the
System. Install the Drain Solenoid Valve to the
1/2" Brass Elbow using another 1/2" Nipple.
Thread the Nylon Elbow to the water flow exit
port of the Drain Solenoid Valve. Follow
instructions in the System Operations Manual
to finish the drain line assembly.
Air Vent Assemblies:
1. Using a 1/4" hex key, unscrew the two black
plastic plugs on the System Casing. The two
plugs should be facing upward when the
System is installed on the Bracket.
2. Complete the Fiber Chamber Air Vent
Assembly as shown in FIGURE 23a. Use Teflon®
tape at all connections.
Install Fiber Chamber Air Vent Assembly on the
¼" NPT port close to the Backpulse Tank. Do
not use tools and do not over-tighten the
connection. Take care not to crossthread this
connection.
3. Complete Prefilter Chamber Air Vent
Assembly as shown in FIGURE 24. A second Air
Relief Valve is provided with the Water Purifier
System. Use Teflon tape at all connections.
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.