![](/html/35/3588/3588e57feb1247306fa0a007450ad68787716043463d740ea2baf08ccad8c48e/bg1.png)
GE
Lighting Solutions
®
Tetra
(GEPS12-60U-NA)
Power Supply Features
• Supports Tetra miniMAX, Tetra MAX, Tetra PowerMAX,
Tetra PowerStrip and Tetra miniStrip LED lighting systems
• Class 2 wiring per NEC Article 725
• Dry and damp location rated
BEFORE YOU BEGIN
Read these instructions completely and carefully.
RISK OF ELECTRIC SHOCK:
• Disconnect power at fuse box or circuit breaker before servicing or
installing product.
• Properly ground Tetra® power supply.
RISK OF FIRE:
• Use only Tetra® supply wire to make connection from Tetra® power
supply to Tetra® LED strip.
• Use only approved wire for input/output connection.
Minimum size 18 AWG (0.82 mm2)
• Follow all local codes.
LED Systems Power Supply
WARNING/AVERTISSEMENT
Installation Guide
12
Volt
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation électrique à la boîte de fusibles ou au
disjoncteur avant l’entretien ou l’installation du produit.
• Assurez-vous de correctement mettre à terre l’alimentation
électrique Tetra®.
RISQUES D’INCENDIE
• N’utilisez que le l d’approvisionnement Tetra® pour faire la
connexion entre l’alimentation Tetra® et la bande DEL Tetra®.
• N’utilisez que des ls approuvés pour les entrées/sorties de
connexion. Taille minimum 18 AWG (0.82 mm2).
• Respectez tous les codes locaux.
Power Supply Installation
Input
wires
Black (line)
White (neutral)
AC line
Connect the AC line to the black
1
(line) and white (neutral) input
wires of the power supply using
18-14 AWG (0.82-2.08 mm
18-10 AWG (0.82-5.26 mm
wire connectors.
2
) or
2
) twist-on
imagination at work
To Tetra LED System
Red (+)
Connect the supply wire that is
2
attached to the Tetra LED System to
the red (+) and blue (-) output wires
of the power supply as outlined
in the “Electrical Connections”
section of your LED system’s
Installation Instructions.
Blue (-)
Output
wires
![](/html/35/3588/3588e57feb1247306fa0a007450ad68787716043463d740ea2baf08ccad8c48e/bg2.png)
NOTE: For CSA approval, a disconnect/toggle switch of appropriate rating needs to be placed within 29.5 ft. (9 m) of primary side of the
power supply. The minimum rating of the switch must be either 120 or 220 Volts AC. The switch must also support twice the amount of
input current.
NOTE: When installing power supply, connect to the appropriate sized building breaker or disconnect device for line and neutral
connections, in accordance with local, state or country regulations.
NOTE: The grounding and bonding of the power supply and overall sign shall be done in accordance with National Electric Code (NEC)
Article 600.
Power Supply Specications
Performance Data Min Typical Max
Input Voltage (VAC) 108 120-277 305
Input Frequency (Hz) - 50/60 -
Input Current (A) - - 0.58
Output Voltage (VDC) 11.0 12.0 13.0
Output Current (ADC) - - 5.0
Output Power (W) - - 60
Environmental Operating Temperature Range -40°C +25°C +60°C*
Environmental Humidity (non-condensing) 10% - 90%
Environmental Storage Temperature Range -40°C - +85°C
Dimensions 9.5 in. x 1.7 in. x 1.2 in. (240 mm x 43 mm x 30 mm)
*Maximum case temperature is 85°C
Supports
Tetra Products SKUs
Tetra miniMAX GEWHMMTS8, GEWWMMTS8-50K,
GEWWMMTS8-41K, GEWWMMTS8
GEBLMMS5, GEGLMMS5,
GERDMMS5
Tetra MAX GEWHMXTS6, GEWWMXTS6-50K,
GEWWMXTS6-41K, GEWWMXTS6
GEWHMHTS6, GEWWMHTS6-50K,
GEWWMHTS6-41K, GEWWMHTS6
GEBLMXWA5, GEGLMXWA5,
GERDMXWA5
GERCMXWA6, GEYGMXS6 162 modules/54 ft. (16.46 m) 30 ft./9.1 m 50 ft./15.2 m 80 ft./24.4 m 120 ft./36.6 m
GERCMXWL6 160 modules/80 ft. (24.38 m) 30 ft./9.1 m 50 ft./15.2 m 80 ft./24.4 m 120 ft./36.6 m
GERDMXWL6 140 modules/70 ft. (21.34 m) 30 ft./9.1 m 50 ft ./15.2 m 80 ft./24.4 m 120 ft./36.6 m
Tetra PowerMAX GEWHPMTL5, GEWWPMTL5-50K,
GEWWPMTL5-41K, GEWWPMTL5
Tetra PowerStrip GEWHSSPS3, GEWWSSPS3-50K,
GEWWSSPS3-41K, GEWWSSPS3
Tetra miniStrip GEWHBSP3, GEWWBSP3-50K,
GEWWBSP3-41K, GEWWBSP3
Remote Mounting Distance
Maximum Load
per Power Supply
18 AWG/
0.82 mm
2
16 AWG/
1.31 mm
2
14 AWG/
2.08 mm
12 AWG/
2
3.31 mm
150 modules/60 ft. (18.29 m) 30 ft./9.1 m 50 ft./15.2 m 80 ft./24.4 m 120 ft./36.6 m
90 modules/36 ft. (10.97 m) 30 ft./9.1 m 50 ft./15.2 m 80 ft./24.4 m 120 ft./36.6 m
120 modules/60 ft. (18.29 m) 30 ft./9.1 m 50 ft./15.2 m 80 ft./24.4 m 120 ft./36.6 m
80 modules/40 ft. (12.20 m) 30 ft./9.1 m 50 ft./15.2 m 80 ft./24.4 m 120 ft./36.6 m
135 modules/54 ft. (16.46 m) 30 ft./9.1 m 50 ft./15.2 m 80 ft./24.4 m 120 ft./36.6 m
38 modules/25 ft. (7.62 m) 30 ft./9.1 m 50 ft ./15.2 m 80 ft./24.4 m 120 ft./36.6 m
16 modules/17 ft. (5.18 m) 20 ft./6.1 m 25 ft./7.6 m 35 ft ./10.6 m 40 ft./12.1 m
53 modules/53ft. (16.16m) 20 ft./6.1 m 25 ft./7.6 m 35 ft./10.6 m 40 ft ./12.1 m
Conforms to the following standards:
2
GE Lighting Solutions • 1-888-MY-GE-LED • www.gelightingsolutions.com
GE Lighting Solutions, LLC is a subsidiary of the General Electric Company. Tetra is a trademark of GE Lighting Solutions, LLC. The GE brand and logo are trademarks of the General Electric Company.
© 2012 GE Lighting Solutions, LLC. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.
1 - 8 8 8 - 6 9 - 4 3 - 5 3 3