GE SVI II AP-2, SVI II AP-3 Quick Start Manual

Page 1
Masoneilan* Products
SVI* II AP Digital Positioner
GE Oil & Gas
(Rev. L)
*
QS2002-1
12/10 - Rev H
Page 2
About this Guide
This Quick Start Guide applies to the following instruments and supported software:
SVI II AP and SVI II AP / AD
with Firmware version 3.1.1, 3.1.3, 3.2.1 and 4.1.1with ValVue suite version 2.40.0 or greater (including PRM Plug-In &
AMS SNAP-ON)
with DTM version 1.01.0 or greaterwith a handheld communicator with DD published for SVI II AP
The information in this manual is subject to change without prior notice. The information contained in this manual, in whole or part, shall not be transcribed
or copied without GE’s written permission. In no case does this manual guarantee the merchantability of the positioner or the
software or its adaptability to a specific client needs. Please report any errors or questions about the information in this manual to your
local supplier or visit www.ge-energy.com/valves.
Copyright
All software is the intellectual property of GE Oil & Gas. The complete design and manufacture is the intellectual property of GE Oil & Gas.
Masoneilan
*
, FVP*, SVI*, and ValVue* are registered trademarks of GE Oil & Gas. All other trademarks are property of their respective companies. All information contained herein is believed to be accurate at the time of publication and is subject to change without notice
.
Copyright 2012 by GE Oil & Gas. All rights reserved. PN 055201-167 REV L
Page 3
3
Contents
Safety Symbols ..................................................................................................7
Safety Information ................................................................................7
SVI II AP Product Safety...................................................................................8
Introduction .......................................................................................................11
Installation and Set Up .........................................................................11
Using the Quick Start Guide..............................................................................13
Single Acting Positioner ....................................................................................14
Double Acting Positioner...................................................................................15
Pushbuttons and Local Display..........................................................................16
Pushbuttons ...............................................................................................................16
ValVue Software................................................................................................20
ValVue Lite ...............................................................................................................20
System Requirements ................................................................................................20
ValVue Full Trial Version ........................................................................................20
Mounting the SVI II AP.....................................................................................21
Necessary Precautions ...............................................................................................21
Mounting the SVI II AP on Rotary Valves ...............................................................22
Travel Sensor Alignment ..........................................................................................24
Mounting the SVI II AP on Reciprocating Valves ...................................................25
Checking the Magnet ................................................................................................29
Installing the SVI II AP for Double- Acting Operation.....................................30
Installing the SVI II AP Remote Position Sensor..............................................33
Remote Position Sensor Mounting Instructions ........................................................34
Configuring the SVI II AP for Remote Position Sensing .........................................37
Connecting the Tubing and Air Supply .............................................................39
Connecting the Air Supply ........................................................................................40
Wiring the SVI II AP .........................................................................................41
Connecting to the Control Loop ................................................................................41
Wiring Guidelines .....................................................................................................41
SVI II AP Setups .......................................................................................................42
Grounding Practices ..................................................................................................43
Compliance Voltage in Single Drop Current Mode ..................................................43
Page 4
GE Oil & Gas SVI II AP Quick Start Guide
4
Verify Wiring and Connections ................................................................................43
Overview .......................................................................................................... 45
Check Out Procedures....................................................................................... 45
Actuator, Linkages, or Rotary Adapter .....................................................................45
Check Out,
Configuration and Calibration ............................................................45
Verify Mounting and Linkage Adjustment ...............................................................46
Checking the Magnet .................................................................................................46
Checking the Air Supply ...........................................................................................48
Checking the Electronic Module Connections ..........................................................48
Operational Checkout........................................................................................ 50
Connecting to the Current Source .............................................................................50
Powering Up the SVI II AP .......................................................................................50
Configuration..................................................................................................... 52
Configuration with Pushbuttons ................................................................................52
Viewing Status Messages ..........................................................................................54
VIEW DATA Settings ...............................................................................................54
Calibration......................................................................................................... 55
Check-out with a HART Handheld Communicator ..................................................59
SVI II AP Maintenance..................................................................................... 61
Repair ........................................................................................................................61
Tools Needed for Cover Replacement ......................................................................61
Maintenance ..........................................................................................61
Display Cover Removal and Installation ...................................................................62
Physical and Operational Specifications........................................................... 65
Specifications and
References ..............................................................................................65
Hazardous Location Installation........................................................................ 72
Spare Parts......................................................................................................... 90
Page 5
Document Changes
Version/Date Writer Changes
H/12-2010 Don Grefe’ Changes ES-699 doc to Rev N.
See Appendix A
J/3-11 Don Grefe’ Changes ES-699 doc to Rev P.
See Appendix A
K/12-2011 Don Grefe’ Added description and proce-
dures relevant to introduction of the high throughput version. ES-699 updated.
L/10-2012 Don Grefe’ Changed the specifications to
reflect single acting supply pressure of up to 100 and dou­ble-acting up to 150 psi. Entered edits from Sandro Esposito and Stephane Leledly.
5
Page 6
GE Oil & Gas SVI II AP Quick Start Guide
6
Page 7
7
1
This section provides safety information and defines the documentation symbols.
Safety Symbols
WARNING
Indicates a potentially hazardous situation, which if not avoided could result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation, which if not avoided could result in instrument or property damage, or data loss.
NOTE
Indicates important facts and conditions.
Safety Information
Page 8
8
GE Oil & Gas
ValVue SVI II AP Quick Start
SVI II AP Product Safety
The SVI II AP digital valve positioner is intended for use with industrial compressed air or, natural gas systems only.
NOTE Installations using natural gas are Zone 0 or Div 1
installations.
Ensure that an adequate pressure relief provision is installed when the application of system supply pressure could cause peripheral equipment to malfunction. Installation must be in accordance with local and national compressed air and instrumentation codes.
General installation, maintenance or replacement
Products must be installed in compliance with all local and national
codes and standards by qualified personnel using safe site work practices. Personal Protective Equipment (PPE) must be used per safe site work practices.
Ensure proper use of fall protection when working at heights, per safe
site work practices. Use appropriate safety equipment and practices to prevent the dropping of tools or equipment during installation.
Under normal operation, compressed supply gas is vented from the SVI
II AP to the surrounding area, and may require additional precautions or specialized installations.
Intrinsically Safe Installation
Products certified as explosion proof or flame proof equipment or for use in intrinsically safe installations MUST BE:
Installed, put into service, used and maintained in compliance with
national and local regulations and in accordance with the recommendations contained in the relevant standards concerning potentially explosive atmospheres.
Used only in situations that comply with the certification conditions
shown in this document and after verification of their compatibility with the zone of intended use and the permitted maximum ambient temperature
Installed, put into service and maintained by qualified and competent
professionals who have undergone suitable training for instrumentation used in areas with potentially explosive atmospheres.
Page 9
9
Safety Information
SVI II AP Product Safety
WARNING Before using these products with fluids/compressed gases
other than air or for non-industrial applications, consult the factory. This product is not intended for use in life support systems.
WARNING Under certain operating conditions, the use of damaged
instruments could cause a degradation of the performance of the system which may lead to personal injury or death.
Under certain operating conditions the SVI II AP High Flow unit can produce noise levels greater than 85 dBA. Perform proper site monitoring and testing to verify the need for engineering or administrative controls to eliminate or reduce hazardous noise levels.
Installation in poorly ventilated confined areas, with any potential of gases other than oxygen being present, can lead to a risk of personnel asphyxiation.
Use only genuine replacement parts which are provided by the manufacturer, to guarantee that the products comply with the essential safety requirements of the European Directives.
Changes to specifications, structure, and components used may not lead to the revision of this manual unless such changes affect the function and performance of the product.
Page 10
10
GE Oil & Gas
ValVue SVI II AP Quick Start
This page intentionally left blank.
Page 11
11
2
Introduction
The SVI II AP provides for reliable operations of control valves with utmost simplicity in setup and commissioning. It is uniquely equipped with a non-contact travel sensor allowing for accurate positioning and maintenance free operations. The pneumatic train of the SVI II AP is a dual-stage amplification system with stainless steel wetted parts for durability. Intrinsically Safe, Flameproof and Explosion proof designs are offered as standard. The High Flow version is capable of 2.2 Cv air throughput. Some of the SVI II AP options include marine grade construction, local indicating LCD with push buttons for local calibration, position transmitter, discrete outputs, double-acting (not available for the High Flow version) and a remote mount position-sensing mechanism. Using Hart eDDL and FDT-DTM technologies, the Masoneilan SVI II AP digital valve positioner provides interoperability with leading control systems suppliers.
Figure 1 SVI II AP
Installation and Set Up
Page 12
SVI II AP Cover
SVI II AP Assembled
Electronics Module
Pneumatic Train and Cover (I/P Module, Relay)
Manifold
Pneumatic Relay
I/P
12
GE Oil & Gas
ValVue SVI II AP Quick Start
Figure 2 SVI II AP Components
SVI II AP Cover
Electronics Module
Cover
Relay
I/P
Manifold
(I/P Module)
Figure 3 SVI II AP High Flow Components
Page 13
13
Installation and Set Up
Using the Quick Start Guide
Using the Quick Start Guide
The SVI II AP Quick Start Guide is intended to help an experienced field engineer install, setup, and calibrate an SVI II AP in an efficient manner. This document provides basic installation and setup instructions and is not intended to replace the in-depth information contained in the SVI II AP Instruction Manual. If you experience problems that are not documented in this guide refer to the SVI II AP Instruction Manual, call your local representative, or go to www.ge-energy.com/ valves. Sales offices are listed on the last page of this document
The steps necessary to complete the SVI II AP installation and software setup are outlined in Table 1.
Table 1 SVI II AP Installation Steps
Step No. Procedure Reference
1 Attach mounting bracket to the
actuator.
See page 21 for rotary valve and reciprocating valve instructions.
2 Install the SVI II AP magnetic
assembly (rotary valves only).
See page 21 for instructions.
3 Assemble the SVI II AP on the
bracket that is mounted to the valve actuator.
See page 21 for rotary valve and reciprocating valve instructions.
4 Install the Remote Position Sensor,
if necessary.
See page 33 for instructions.
5 Connect the pneumatic tubing to
the SVI II AP.
See page 39 for instructions.
6 Connect the air supply to the SVI II
AP.
See page 40 for instructions.
7 Connect the positioner to the HART
Control Loop segment by installing the SVI II AP wiring.
See page 41 for instructions.
8 Configure/calibrate using ValVue. See page 52 and page 55 for
instructions
Configure/calibrate using a HART Hand Held Communicator
See page 59 for instructions.
Page 14
14
GE Oil & Gas
ValVue SVI II AP Quick Start
WARNING Failure to adhere to the requirements listed in this manual
may cause loss of life and property. Before installing, using, or carrying out any maintenance
tasks associated with this instrument, READ THE INSTRUCTIONS CAREFULLY. Refer to “Hazardous Location Installation” on page A-72 of this guide for detailed instructions.
Single Acting Positioner
The supply and output connections for the SVI II AP, located on bottom of the pneumatic block, are tapped 14" NPT. The output port 1 is toward the front while the supply is toward the back. Two pressure gauges, output on top, supply port on bottom, are located on the front of the pneumatic block.
The supply and output connections for the SVI II AP High Flow (Figure 5 on page 15), located on bottom and leftside of the pneumatic block, are tapped 12" NPT.
Maximum allowable air supply pressure to the SVI II AP varies according to actuator, valve size, and valve type. Refer to the serial plate of the valve to know the specified supply pressure; it must never be less than the maximum spring pressure +5 psi.
Output
Supply
Figure 4 Air Ports on Single Acting Positioner
Page 15
Output
Supply
15
Installation and Set Up
Double Acting Positioner
Figure 5 SVI II AP High Flow Air Ports on Single Acting Positioner
Double Acting Positioner
Connect Output 1, labeled(I) to the inlet port of the actuator and Output 2, labeled (
II) to the opposing actuator port (see Figure 6).
Output I
Supply
Output II
Figure 6 Air Ports on Double Acting Positioner
Page 16
16
GE Oil & Gas
ValVue SVI II AP Quick Start
Pushbuttons and Local Display
This section covers the optional local interface consisting of the LCD alphanumeric display and pushbuttons. Operation of the SVI II AP Digital Valve Positioner as a local device is controlled through the optional device-mounted pushbuttons and digital display, shown in Figure 7 on page 17. Using the display you can read the input signal, valve position, and actuator pressure. The display sequences from one variable to the next every 1.5 seconds.
Using the pushbuttons you can exit from operating mode at any time and step through a menu structure to perform a wide range of manual operation, calibration, configuration, and monitoring functions that are described later in this section. ValVue is used to perform all diagnostics functions. The pushbuttons do not support diagnostics functions.
The SVI II AP has two operational modes: Normal Operating Mode and Manual Mode and two setup modes, Configuration and Calibration. The SVI II AP also has two modes for handling of faults and power-up: Reset and Failsafe. When commissioning or checking a control valve with SVI II AP fully installed the following steps are recommended:
Change mode to Manual modeExamine and adjust all CONFIGuration itemsEnter Calibration modeRun STOPS to automatically calibrate strokeRun autoTUNE to set dynamic responseExamine the device STATUSIntroduce manual set point changes to verify dynamic performance
Pushbuttons
The local pushbuttons are located behind a hinged cover, directly below the display window. To open the cover loosen the screw and swing the cover down. Always re-fasten the cover after use to protect the pushbuttons from environmental contamination.
The three pushbuttons perform the following functions:
Left Button - Marked with *, permits you to select or accept the value or
parameter option currently displayed.
Middle Button - Marked , permits you to move back through the menu
structure to the previous item in the menu or decrement the value currently shown in the digital display. When used to decrease a displayed value, holding the button down causes the value to decrease at a faster rate.
Page 17
17
Installation and Set Up
Pushbuttons
Right Button - Marked +, permits you to move forward through the menu
structure to the next item in the menu, or to increment the value currently shown in the digital display. When used to increase a displayed value holding this button down causes the value to increase at a faster rate.
NOTE When an exclamation point (!) appears in the SVI II AP
display window, it indicates that there is instrument status available.
*
+
-
(Select)
(Forward)
(Back)
Figure 7 SVI II AP Display Pushbuttons
Page 18
18
GE Oil & Gas
ValVue SVI II AP Quick Start
Pushbutton Locks and Configuration-Lock Jumper
Before performing any of these functions with the local display you must first ensure that the pushbuttons are placed in the unlocked mode using ValVue Lite. The positioner is provided in the unlocked mode. See ValVue documentation for more details.
The SVI II AP offers several levels of accessibility. It may be desirable, after initial setup, to lock the pushbuttons so that the SVI II AP parameters cannot be inadvertently changed by the buttons. Several levels of pushbutton locks are provided.
Table 2 Pushbutton Lock Security Level
Level Access
Security Level 3 Allow Local Buttons: Buttons on the SVI II AP are fully enabled. Security Level 2 Lock Out Local Calibration and Configuration: Use the buttons to perform
operations in normal operating mode and manual mode. Do not go to configure or calibrate mode.
Security Level 1 Lock Out Local Manual: Examine variables in normal operating mode but
do not put the valve in manual operating mode. Access to calibrate or configure modes is not available.
Security Level 0 Lock Out All Buttons: The buttons are disabled (level 0).
Page 19
19
Installation and Set Up
Pushbuttons
Hardware Configuration Lock
Additional security is achieved using the hardware configuration-lock jumper shown in Figure 8. When set to the secure position, shorting the two-pin header, configuration and calibration are not permitted by the local interface or by remote communications. Pushbuttons, ValVue and handheld are locked out, except to examine configuration, calibration, and position. This is similar to Security Level 1 shown in the Pushbutton Lock Security Level table.
Display
Remote
Process Variable
Position Retransmit
Position Input
Configuration Lock Jumper
4- 20 mA Input Signal
Solid State Switch SW #1
Solid State Switch SW #2
Sensor
Figure 8 Connections to Electronics Module (via Terminal Board)
Page 20
20
GE Oil & Gas
ValVue SVI II AP Quick Start
ValVue Software
The SVI II AP is shipped with a free version of ValVue Lite and a trial version of ValVue.
ValVue Lite
ValVue Lite software is shipped with each SVI II for positioner calibration and configuration. ValVue Lite software is offered without registration. It provides sufficient functionality to fully commission, configure, and start up a positioner on a control valve.
System Requirements
ValVue Lite runs on IBM compatible computers. Minimum requirements for all versions of ValVue software are Windows XP, Windows Server 2003, Windows Server 2008, Windows 7, 64 MB RAM, a serial or USB port connected to a HART modem, and a CD-ROM drive.
ValVue Full Trial Version
The SVI II AP comes with a copy of ValVue Trial Version software that can be used for sixty days without a license. After the 60-day trial period, ValVue must be registered. ValVue, full version, provides advanced diagnostic, maintenance capabilities and basic calibration and configuration for the SVI II AP. SVI II AP performs valve diagnostics and displays stroking speed, step response, cumulative travel, cycles, and operation in near-closed position. The software stores test results for comparison with future results for predictive maintenance. Password protected access to remote instruments is set up with administration features. The fully licensed ValVue software is available as an upgrade.
Page 21
21
Installation and Set Up
Mounting the SVI II AP
Mounting the SVI II AP
This guide provides installation instructions for mounting an SVI II AP on both rotary and reciprocating actuated valves. The mounting process can be broken down into the following:
Attach the mounting bracket to the actuator.Install the magnetic assembly.Assemble the SVI II AP on the mounting bracket.
NOTE The SVI II AP should be mounted with the conduit
connections down in order to facilitate drainage of condensate from the conduit.
Necessary Precautions
To avoid injury or the process being affected when installing or replacing a positioner on a control valve, ensure that:
If the valve is located in a hazardous area make sure the area has been
certified as safe or that all electrical power to the area has been disconnected before removing any covers or disconnecting any leads.
Shut off air supply to the actuator and to any valve mounted equipment.Ensure the valve is isolated from the process by either shutting off the
process or using bypass valves for isolation. Tag shutoff or bypass valves to guard against a turn-on while work is in progress.
Bleed air from actuator and check that valve is in its unenergized
position.
It is now safe to disconnect and remove any valve mounted equipment that is being replaced.
For the procedure to mount rotary and reciprocating valves, refer to the Mounting Instructions contained in the valve’s Mounting Box kit.
Page 22
22
GE Oil & Gas
ValVue SVI II AP Quick Start
Mounting the SVI II AP on Rotary Valves
This section describes the procedure for mounting the SVI II AP on rotary control valves that have less than 60° rotation, such as a Camflex
*
or a Varimax*. Figure 9 shows a side view of a Camflex actuator and the SVI II AP actuator mounting brackets.
Figure 9 Camflex with Mounting Bracket (Side View)
Mounting the SVI II AP on a Rotary Actuator
Tools required:
316" Hex Key532" Hex Key3 mm, 4 mm, 5 mm Hex Key716" Wrench
To mount the SVI II AP:
1. Attach the SVI II AP rotary mounting bracket to the valve actuator using two
(2) 516 - 18 UNC flat-head cap screws. In the preferred mounting position, the long end of the mounting bracket is on your left when facing the actuator, for any position of the valve and actuator.
2. Bolt the extension shaft to the valve position take-off shaft using a 14 - 28
UNF socket flathead screw. Secure the machine screw holding the extension shaft with a torque of 144 in-lbs (16.269 N-m).
3. On internal valve pressure the thrust shaft is pushed out to the mechanical
stops, usually a thrust bearing. On valves where the valve position take-off is mounted directly on the end of the plug shaft, a Camflex for example, the shaft must be bearing on its stop to properly set up the SVI II AP Controller. During hydrostatic testing the shaft is thrust to its stop and a normally tightened packing retains it in that position.
Page 23
23
Installation and Set Up
Mounting the SVI II AP on
4. On vacuum service, the valve shaft may be drawn into the body by the
vacuum acting on the shaft, but the magnetic coupling must be assembled flush with the mounting bracket with the shaft pulled fully out to its thrust bearing. Check that the endplay from the vacuum position to the fully extended position is less than 0.06 in. (1.524 mm)
5. Slide the magnet holder into the extension shaft. The location of the magnets
is in the ring of the magnet holder. The magnetic axis is the imaginary line through the center of both magnets.
6. Rotate the magnet holder so that the magnet axis is vertical when the valve is
in the closed position.
7. Align the end of the magnet holder flush with the end of the mounting bracket.
Secure the magnet holder with two M6 set screws.
8. Slide the V-Seal over the magnet holder.
9. Secure the SVI II AP onto the mounting bracket using four M6 x 20 mm socket
head cap screws.
10.Ensure no interference exists with the position sensor protrusion.
11. Ensure that the V-Seal makes contact with the skirt around the position sensor
protrusion on SVI II AP housing.
Page 24
24
GE Oil & Gas
ValVue SVI II AP Quick Start
Travel Sensor Alignment
Table 3 shows the general guidelines for travel sensor alignment. Review the table prior to installing the SVI II AP on a rotary valve actuator for proper alignment of the magnet.
Table 3 Travel Sensor Alignment
Rotary
Mounting
System
Stroke Direction
Magnet
Orientation
Valve
Position
Sensor Counts
Rotary <60° Rotation
Clockwise or counterclockwise rotation
(0°)
Closed (0%) 0 +/- 1000
>60° Rotation Clockwise with increasing setpoint
(-45°)
Full Open or Full Closed
-8000 +/- 1500 or +8000 +/- 1500
>60° Rotation Counter Clockwise rotation with increasing setpoint
(+45°)
Full Open or Full Closed
-8000 +/- 1500 or +8000 +/- 1500
General Rule for other configurations
Any amount of rotation Clockwise or counterclockwise
(0°)
50% Travel (Mid-Stroke)
0 +/- 1000
Page 25
25
Installation and Set Up
Mounting the SVI II AP on
Dismantling the SVI II AP from Rotary Valves
Before carrying out any work on the device, power off the instrument or ensure that the device’s location conditions for potentially explosive atmosphere permit the safe opening of the cover.
To remove the SVI II AP Controller from a rotary valve perform Steps 1 - 9 on page 22 in reverse.
Mounting the SVI II AP on Reciprocating Valves
The process of mounting the SVI II AP on a reciprocating valve consists of mounting the unit on the actuator that is attached to the valve. This section describes the procedure for mounting the SVI II AP on Reciprocating Valves (using Masoneilan’s 87⁄88 Multi-Spring actuators as an example).
Mounting the SVI II AP on a Reciprocating Actuator
Tools required:
716" Combination Wrench (2 required)38" Combination Wrench12" Combination WrenchPhillips Head Screw Driver5 mm Hex Key Wrench
1. Ensure that the lever is pinned to the magnet assembly and held securely by
an M5 flat head screw to ensure that the magnet axis is vertical when the lever is in the valve closed position. Tighten the lever screw securely. Refer to Figure 10.
M5 Flat
Pin
head screw
Figure 10 Magnet Holder for Reciprocating Valves
Page 26
26
GE Oil & Gas
ValVue SVI II AP Quick Start
2. Mount the SVI II AP reciprocating mounting bracket to the actuator using two
(2) 516 - 18 UNC cap screws.The mounting location of the bracket depends on the size and stroke of the actuator. Refer to Figure 11 and Figure 4 on page 28.
Figure 11 Reciprocating Valve Mounting Bracket
3. Select mounting hole A, B, C or D for the stroke of the valve. For example,
hole B is shown in Figure 13 on page 27 for a size 10 actuator with 1.0" stroke. Unless otherwise specified, the SVI II AP mounting assumes that the actuator is in the normal upright position. The mounting hole in the slotted opening of the mounting bracket must be left when facing the actuator, with the actuator in the upright position.
4. Move the valve to its closed position. For air to extend, this requires using air
pressure in the actuator to fully stroke the actuator. For air to retract, actuators vent the actuator of air pressure.
5. Thread the take-off rod to the actuator stem connector. Refer to Figure 12 on
page 27. Ensure that the travel pointer located on the coupling is correctly positioned.
6. Attach the right hand threaded rod end to the SVI II AP lever using a 14 - 20 x
1" cap screw and nut as shown. The lever hole position to be used depends upon the specific valve stroke. Refer to Figure 13 on page 27 and the Reciprocating Valve Linkage Selection, Table 4 on page 28.
7. Thread the right hand lock nut and turnbuckle onto the right hand rod end
approximately two turns. Turnbuckle length is a function of actuator size. (Refer to Table 4 on page 28.)
8. Secure the magnet housing assembly, including the lever and right hand rod
end, to the bracket using four M5 X 10 mm flat head screws.
9. Attach the left hand threaded rod end to the take-off rod with 14 - 20 UNC nut
and thread the left hand lock nut onto the rod end.
Page 27
27
Installation and Set Up
Mounting the SVI II AP on
Figure 12 Reciprocating Linkage
10.Thread the turnbuckle onto the left hand threaded rod end (Figure 12).
11.Adjust the turnbuckle until the hole in the SVI II AP lever is aligned with the
indicating hole in the bracket. Tighten both turnbuckle lock nuts. Refer to Figure 11.
12.For reciprocating valves the adjustable link turnbuckle must be parallel to the
valve stem. To ensure linearity in positioning, verify that the hole in the lever aligns with the indicating hole in the bracket when the valve is in the closed position. Check that the bracket is mounted using the proper holes. (Refer Table 4 on page 28.)
13.Mount the SVI II AP to the bracket and secure with four M6 socket head cap
screws.
Figure 13 Lever for Model 87/88 Multispring Actuator
Page 28
Table 4 Reciprocating Valve Mounting Hole and Turnbuckle Length
Actuator
Size
Masoneilan
Stroke
Mounting
Hole
Lever
Hole
Turnbuckle
Length
6 and 10 0.5 - 0.8"
(12.7 - 20.32 mm)
A A 1.25"
(31.75 mm)
10 0.5 - 0.8"
(12.7 - 20.32 mm)
A A 1.25"
(31.75 mm)
10 >0.8 – 1.5"
(20.32 - 41.5 mm)
B B 1.25"
(31.75 mm)
16 0.5 - 0.8"
(12.7 - 20.32 mm)
B A 2.90"
(73.66 mm)
16 >0.8 – 1.5"
(20.32 - 41.5 mm)
C B 2.90"
(73.66 mm)
16 >1.5 – 2.5"
(41.5 - 63.5 mm)
D C 2.90"
(73.66 mm)
23 0.5 - 0.8"
(12.7 - 20.32 mm)
B A 5.25"
(133.35 mm)
23 >0.8 – 1.5"
(20.32 - 41.5 mm)
C B 5.25"
(133.35 mm)
23 >1.5 – 2.5"
(41.5 - 63.5 mm)
D C 5.25"
(133.35 mm)
28
GE Oil & Gas
ValVue SVI II AP Quick Start
Dismantling the SVI II AP from Reciprocating Valves
WARNING Before carrying out any work on the device, power off the
instrument or ensure that the local conditions for potentially explosive atmosphere permit the safe opening of the cover.
To remove the SVI II AP Controller from a reciprocating valve perform Steps 1 - 12 on page 25 in the reverse order.
Page 29
29
Installation and Set Up
Checking the Magnet
Checking the Magnet
There are two methods of checking the SVI II AP magnet:
Perform a visual inspectionUse ValVue to check the magnet
Performing a Visual Inspection
To perform a visual inspection refer to Table 3 on page 24 and ensure that the magnet is correctly oriented for the actuator/valve configuration.
Page 30
30
GE Oil & Gas
ValVue SVI II AP Quick Start
Installing the SVI II AP for Double- Acting Operation
This section explains how to mount the SVI II AP for the 84/85/86 kit for double­acting valve positioner configurations.
To mount the kit:
1. Set valve to the closed position.
2. Install the mounting assembly to the yoke (Figure 14) using helical spring
washer 5/16, flat washer 5/16 and hex screw 5/16-18x44.5 [1.75] LG.
Lever
Rod-end
Kit Mount Bracket
Figure 14 84/85/86 Valve
NOTE Mount all components snug enough to stay in place but loose
enough to tap with rubber hammer into final position.
Page 31
31
Installation and Set Up
Installing the SVI II AP for
3. Set rod-ends and brackets to stroke and size of actuator. The default setting is
a 4.00” stroke. Other stroke settings are as in Figure 15.
Figure 15 Stroke Settings
4. Mount take-off bracket to stem block at angle which keeps turnbuckle
assembly parallel to stem (Figure 16) using:
a. For top: two plain 5/16 flat washers, helical spring washer 5/16, two hex nuts
5/16-18 regular.
b. For bottom: hex nut regular 1/4-20 and hex screw 1/4-20 UNC x 22.2 [.88]
LG.
Figure 16 Bracket Configuration Strokes .5 - 2.50” and 3-6”
Page 32
32
GE Oil & Gas
ValVue SVI II AP Quick Start
5. Ensure the turnbuckle assembly is parallel to the stem and the magnets are in
the valve closed position (Figure 17) and connect to take-off bracket.
Figure 17 Magnet Position with Valve Closed
6. Verify lever is in correct position with valve closed. Adjust rod-ends, if
necessary.
Figure 18 Lever Alignment
7. Mount the SVI-II with M6-1 screws.
8. Cycle the valve open to close verifying proper components movement and
that rod-ends move free and clear from other components.
Page 33
33
Installation and Set Up
Installing the SVI II AP Remote
Installing the SVI II AP Remote Position Sensor
The Remote Position Sensor, is a remotely mounted position-sensing device that is connected electrically to an SVI II AP digital valve positioner. It is used as position feedback in applications where direct mounting of an SVI II AP to a valve actuator is not practical due, typically but not limited to, extreme vibration, heat or radiation.
The Remote Position Sensor is a potentiometer located in an enclosure which can be mounted on a valve or damper to indicate stem position when connected to a suitable receiver. There is a three wire connection provided on a screw terminal block to interconnect to the receiving device.
The SVI II AP Remote Position Sensor is suitable for installation outdoors in an industrial environment. Mounting kits are provided to permit mounting on a variety of valves.
WARNING Do not remove the instrument cover or connect to an
electrical circuit in a Hazardous Area unless the power is disconnected.
WARNING Comply with current national and local regulations for
electrical installation work. Comply with national and local explosive atmosphere
regulations. Before carrying out any work on the device, power off the
instrument or make sure that the locale conditions for potentially explosive atmosphere permit the safe opening of the cover.
Page 34
34
GE Oil & Gas
ValVue SVI II AP Quick Start
Remote Position Sensor Mounting Instructions
Tools Needed
7/16” open end wrench6 mm hex wrench2.5 mm hex wrenchBlade screwdriver
NOTE The instructions below cover mounting the Remote Mount
Sensor to both reciprocating and rotary actuators. The two mounting kits share only one part; the ¼-20 hex head cap screws. Although the assembly steps are similar, differences are noted. Refer to the Figure 19 on page 35 when reading these instructions for proper orientation.
1. Fasten the mounting bracket to the actuator yoke:
For reciprocating actuators, use the (2) 5/16-18 hex head bolts supplied.For rotary actuators, use the (2) 5/16-18 hex socket countersunk screws
supplied.
2. Connect the Remote Mount Sensor (RMS) to the mounting bracket using (4)
¼-20 hex head cap screws. Orient the RMS as shown in Figure 19, such that the conduit opening faces the ground.
3. Attach the feedback lever to the RMS output shaft:
For reciprocating mounting:
a. Slip the feedback lever onto the RMS output shaft, and thread the M5 set
screw into the hole. Ensure to align the setscrew hole of the feedback lever
with the flat of the RMS output shaft such that the setscrew contacts the flat. b. Connect the take-off rod to the split clamp of the actuator stem. c. Connect one end of the turnbuckle to the feedback lever, and the other end
to the take-off rod. (Refer to Table 5 on page 35 for turnbuckle length.)
For rotary mounting:
a. Connect the feedback lever (with the pin) to the actuator shaft (protruding
from the actuator yoke) using the supplied hardware. This hardware
includes a spacer, a spring washer and a ¼-28 hex head cap screw. b. Attach the second feedback lever (with the slot) to the RMS output shaft and
at the same time; insert the pin of the first feedback lever into the slot. It may
be necessary to loosen some of the parts in order to get everything to align
properly. c. Thread the M4 socket head cap screw into the setscrew hole of the second
feedback lever making sure it contacts the flat of the RMS output shaft.
Page 35
Remote Position Sensor Mounted
Remote Position Sensor Mounted
on Reciprocating Actuator
on Rotary Actuator
35
Installation and Set Up
Remote Position Sensor
Figure 19 SVI II AP Remote Position Sensor Installation
Table 5 Remote Position Sensor Turnbuckle Length
Actuator Size Stroke Turnbuckle Length
6 and 10 0.5 - 0.8"
(12.7 - 20.32 mm)
1.25"
(31.75 mm)
10 0.5 - 0.8"
(12.7 - 20.32 mm)
1.25"
(31.75 mm)
10 >0.8 – 1.5"
(20.32 - 41.5 mm)
1.25"
(31.75 mm)
16 0.5 - 0.8"
(12.7 - 20.32 mm)
2.90"
(73.66 mm)
16 >0.8 – 1.5"
(20.32 - 41.5 mm)
2.90"
(73.66 mm)
16 >1.5 – 2.5"
(41.5 - 63.5 mm)
2.90"
(73.66 mm)
23 0.5 - 0.8"
(12.7 - 20.32 mm)
5.25"
(133.35 mm)
23 >0.8 – 1.5"
(20.32 - 41.5 mm)
5.25"
(133.35 mm)
23 >1.5 – 2.5"
(41.5 - 63.5 mm)
5.25"
(133.35 mm)
4. Remove the M8 cover-retention screw of the RMS and unscrew the cover to gain access to the terminal strip.
Page 36
36
GE Oil & Gas
ValVue SVI II AP Quick Start
5. Route the cable from the SVI II AP to the RMS and thread the cable through the conduit at the bottom of the housing.
6. Use a blade screwdriver to loosen the screws on the terminal strip and connect the wires; black-to-black, brown-to-brown and red-to-red. Then retighten the screws.
7. Connect the cable’s shielding drain wire to the unlabeled terminal.
8. Screw on the RMS cover and replace the M8 cover-retention screw.
9. At the other end of the cable, insert the ferrules into the terminal labeled REMOTE; black-to-3, brown-to-2 and red-to-1. When performing this step, be careful not to side-load the terminal levers.
Step 1 Connect Drain Wire to Open Terminal
Step 2 When connecting cable to Remote Position Sensor make sure wire colors match:
- Red to Red
- Brown to Brown
- Black to Black
Step 3 Insert Ferrules into Remote Mount connector according to
Wire Color
Red
Brown
Black
1 2
3
Positive
Signal
Ground
the chart at the right:
Remote Mount Connector
Remote Position Sensor with Cover Removed
Wiring Instructions
Function
SVI II AP
Ferrules
Terminal Number
Figure 20 Remote Position Sensor (Cover Removed) and Wiring
Page 37
37
Installation and Set Up
Configuring the SVI II AP for
Configuring the SVI II AP for Remote Position Sensing
After the Remote Position Sensor is installed and cabled to the SVI II AP, the SVI II AP needs to be configured so that valve position is sensed by Remote Position Sensor. A digital communication software tool is provided on the CD shipped with the SVI II AP for this purpose. First you must install the software tool, SMARTS Assistant, from the CD and then using the tool, configure the SVI II AP. You may also download SMARTS Assistant from, www.masoneilan.com, downloads.
To install SMARTS Assistant (see Figure 21):
1. From the CD select and click on Install Software. The available software tools appear.
2. Click Install SMARTS Assistant ..... The program automatically installs.
Selecting Install Software
Installing SMARTS Assistant
Figure 21 Installing SMARTS Assistant from CD
Configuring the SVI II AP Using SMARTS Assistant
To configure the SVI II AP:
1. Start SMARTS Assistant Standard by clicking the desktop icon or by selecting the program through the Start menu. The Connection screen appears.
2. Click Connect as shown in Figure 22. SMARTS Assistant searches for the SVI II AP, to which the Remote Position Sensor is connected.
3. Connect the device to the software and display device information as shown in Figure 22.
4. Select Options tab and the Options screen appears as shown in Figure 22.
Page 38
38
GE Oil & Gas
ValVue SVI II AP Quick Start
5. Select the Remote PO checkbox at the left.
6. Activate the Remote Position Sensor by clicking Change Options. SMARTS Assistant changes control to the Remote Position Sensor and displays the message shown below.
7. Click OK to continue.
SMARTS Assistant Connection Screen
SVI II AP Device Connected
Options Screen -
Device Set to Use Remote Position Sensor Message
Remote Position Sensor
Selected
Figure 22 SMARTS Assistant - Commissioning the Remote Position Sensor
Page 39
39
Installation and Set Up
Connecting the Tubing and Air
Connecting the Tubing and Air Supply
The last step in hardware installation for the SVI II AP is to connect the air supply to the positioner. This section describes the process for connecting the tubing and air supply to a single and double acting positioner.
WARNING Isolate the valve from the process and disconnect air tubing
from the positioner. Disconnect air fully to avoid injury or process damage.
1. Install the tubing to the air supply port S
(arrow only for High Flow).
2. For a:
Single acting actuator: Pipe the outbound air from the output pressure
port
 I (arrow only for High Flow) to the actuator.
Double acting actuator: Pipe output pressure port one I (no letter for
High Flow) for one side of the actuator and output pressure port two

II (arrow only for High Flow) for the other side of the actuator.
3. Air supply:
Supply pressure for single acting SVI II and AP High Flow:
20 -100 psi (1.4 - 6.9 bar) (138 - 690 kPa)
Supply pressure for double acting SVI II AP:
25 - 150 psi (1.73 - 10.4 bar) (172.4 - 1034 kPa)
Minimum tubing diameter 14" (6 mm x 4 mm)
NOTE The SVI II AP Digital Valve Positioner is designed to operate
with clean, dry, oil-free, instrument grade air to ANSI-ISA-57.3 1975 (R1981) or ISA-S7.3-1975 (R1981) or with a sweet natural gas supply (SVI II AP models SVI II AP/SD through SVI II AP/AD).
Table 6
Dew Point At least 18° F (-7° C) below minimum anticipated ambient
temperature Particulate Matter Filtered to 5 microns Oil Content Less than 1 ppm w/w Contaminants Free of all corrosive contaminants
Air Supply Requirements
Page 40
40
GE Oil & Gas
ValVue SVI II AP Quick Start
CAUTION The SVI II AP High Flow digital valve positioner cannot be
placed in parallel with another volume booster. Contact the factory for further instructions regarding configuration with boosters as well as other non-standard configurations.
Connecting the Air Supply
After the tubing is installed, use the following procedure to connect the air supply.
1. Supply clean, dry compressed air to the filter regulator.
2. Turn on the air supply.
3. Adjust the filter regulator. Supply pressure must be 5 - 10 psi greater than the spring range of the actuator but may not exceed the rated actuator pressure. Refer to the valve or actuator instruction manual.
Page 41
41
Installation and Set Up
Wiring the SVI II AP
Wiring the SVI II AP
In order for the SVI II AP to communicate the positioner data the SVI II AP must be physically connected to a HART communication. The procedure below outlines wiring the SVI II AP.
Comply with current national and local regulations for electrical
installation work.
Comply with national and local explosive atmosphere regulations.Before carrying out any work on the device, power off the instrument or
make sure that the local conditions for potentially explosive atmosphere permit the safe opening of the cover.
Connecting to the Control Loop
The SVI II AP digital valve positioner MUST BE grounded according to local regulations. It is important to maintain correct polarity at all times, otherwise the positioner may not operate properly. Physically connect the SVI II AP to the HART loop using a cable specified by the HART Communication Foundation. A shielded cable is recommended.
To connect the Control Loop to the SVI II AP:
1. Connect one end of the cable to the control loop's 4 - 20mA output
2. Remove the threaded wiring covers on the positioner.
3. Connect the other end of the cable to the SVI II AP. There are two threaded openings on the positioner. Use the opening with the red plastic insert.
4. Maintain polarity + and - respectively.
Wiring Guidelines
This list contains eight guidelines for a successful implementation of DC current signal, DC power, and HART communication to the SVI II AP:
1. Compliance voltage at the SVI II AP must be 9 V at the maximum current of 20 mA.
2. Signal to the SVI II AP must be a regulated current in the range 3.2 to 22 mA.
3. Controller output circuit must be unaffected by the HART tones which are in the frequency range between 1200 and 2200 Hz.
4. Frequency range of the HART tones must have a circuit impedance of more than 220 Ohms, typically 250 Ohms.
5. HART tones may be imposed by the positioner and a communication device located anywhere on the signaling circuit.
6. Capacitance of the signaling circuit must not exceed 0.26 microfarads or 0.10 microfarads with high series resistance.
Page 42
42
GE Oil & Gas
ValVue SVI II AP Quick Start
7. Cabling must be shielded to prevent electrical noise that would interfere with the HART tones, with the shield grounded.
8. Signal must be properly grounded in only one place.
NOTE For details and calculation methods for wiring resistance, and
capacitance and for calculation of cable characteristics, refer to the HART FSK Physical Layer Specification.
SVI II AP Setups
Typical system setups are shown in Figure 23 on page 44, General Purpose and Explosion Proof (EEx d) Installation Schematic and Figure 24 on page 44, Intrinsically Safe Installation Schematic. The SVI II AP digital valve positioner can be located in a general-purpose or hazardous area protected by Explosion Proof (EEx d) methods. Wiring diagrams are generalized, actual wiring must adhere to Electrical Installation section of manual and local electrical codes. The use of a Handheld Communicator or a HART modem is not permitted in the Hazardous Area protected by Explosion Proof (EEx d) methods. In Figure 24 on page 44 the SVI II AP digital valve positioner is located in a hazardous area that is protected by Intrinsically Safe wiring practices.
The SVI II AP requires an electrical input from a 4-20 mA current source. The SVI II AP input signal can carry a HART communication protocol signal from ValVue software and a HART modem, or from a HART Hand Held Communicator. Since the process control system, the source of the input signal, is located in a non­hazardous location, setup requires an intrinsic safety barrier be placed between the process control system and the SVI II AP. If the SVI II AP is located in a hazardous area with Intrinsically Safe protection a barrier is not required for a flameproof installation. Alternatively the system can be installed as Explosion Proof flameproof. SVI II AP can communicate with a remote PC running ValVue software via a modem connected to the PC's serial or USB port. The PC, which is not intrinsically safe, must be connected to the circuit on the safe area side of the intrinsic safety barrier if the valve is located in a hazardous area.
The SVI II AP can be operated, calibrated, configured, and interrogated either by using local pushbutton and display, or by using a PC running ValVue software, HART Handheld Communicator, or any registered HART Host that supports DDs. The HART Handheld Communicator is approved for Intrinsically Safe use in accordance with FM and ATEX standards. Read and observe all handheld labeling. The SVI II AP is polarity sensitive so the positive lead must be connected to the positive (+) terminal and the negative lead to the negative (-) terminal. Reversing the input will not cause damage but the unit will not function.
Page 43
43
Installation and Set Up
Grounding Practices
Grounding Practices
To ensure proper grounding make sure that case, signal, and ground connections are made in compliance with the plants normal grounding practices. Any point in the loop can be referenced to ground, but there must never be more than one ground point. Normally ground is connected at the controller or at the intrinsic safety barrier.
The case grounding screws are located on the outside of the case at the lower right of the display cover and inside the cover. The case is isolated from all circuitry and can be grounded locally in accordance with applicable codes.
If noise or instability is present, set the positioner to MANUAL mode of operation and manually position the valve over its entire range. If the valve is stable in MANUAL mode then the problem can be noise in the control system. Recheck all wiring connections and ground points.
Compliance Voltage in Single Drop Current Mode
The SVI II AP requires 9.0 V at 20 mA and 11.0 V at 4 mA. Typical HART devices require MORE Voltage at higher current and MORE current source have LESS Voltage available at higher current. The SVI II AP is noteworthy in that it requires LESS Voltage at higher current that complements the characteristic of the source requiring only 9 V at 20 mA.
Verify Wiring and Connections
NOTE For split range installations the compliance voltage must be
capable of the minimum span being 5 mA; the upper range value must be 8 mA to 20 mA; the lower range values must be 4 mA to 14 mA.
Use the following procedure to ensure that the SVI II AP is properly powered:
1. Connect a DC voltmeter across the input terminals.
For an input current between 4 and 20 mA the voltage varies between
11 V and 9 V respective.
When voltage exceeds 11 V check that polarity is correct.If voltage is less than 9 V and polarity is correct, voltage compliance of
current source is inadequate.
2. Connect a milliampmeter in series with the current signal.
3. Verify that source can supply 20 mA to SVI II AP input. If 20 mA is not attainable, troubleshoot the source and set up.
Page 44
44
GE Oil & Gas
ValVue SVI II AP Quick Start
NOTE Improperly or inadequately grounded installations can cause
noise or instability in the control loop. The internal electronic components are isolated from ground. Grounding the case is unnecessary for functional purposes but grounding the case may be necessary to conform to local codes.
Hazardous Area
Non-Hazardous Area
Power
Supply
220 Ohms HART compliant control system output card
HART
Modem
SVI II AP
DPI620
ValVue
Figure 23 General Purpose and Explosion Proof Installation
Power
Supply
220 Ohms HART compliant control system output card
HART
Modem
SVI II AP
DPI620
ValVue
Barrier Resistance
Single Channel Zener Barrier
Figure 24 Intrinsically Safe Installation
Page 45
45
3
Overview
This section provides the calibration procedures to ensure proper valve positioning. Operational checkout, configuration and calibration procedures are described using an SVI II AP that has a display with pushbuttons.
NOTE
Perform all procedures in this section before putting the SVI II AP into operation.
Check Out Procedures
SVI II AP checkout consists of physical and operational checkout procedures. The physical checkout procedures include:
“Inspecting Actuator, Linkages, or Rotary Adapter” on page 46 “Verifying Mounting and Linkage Adjustment” on page 46 “Checking the Magnet” on page 46 “Checking the Air Supply” on page 48 “Checking the Electronic Module Connections” on page 48
Check Out, Configuration and Calibration
Page 46
46
GE Oil & Gas
ValVue SVI II AP Quick Start
Inspecting Actuator, Linkages, or Rotary Adapter
Verify that the mounting has not been damaged in shipment for a pre-mounted SVI II AP, physically inspect the actuator, linkage. Record the following information for the configuration checkout:
1. Valve Air to Open (ATO) or Air to Close (ATC)
2. Actuator pressure rating
3. Actuator bench range
4. Inherent trim characteristic of the control valve; linear, equal percentage, or other.
NOTE Refer to the valve data sheet or model number of control
valve.
Verifying Mounting and Linkage Adjustment
Inspect the mounting and make any needed adjustments before running the positioner and checking the digital configuration.
Checking the Magnet
There are two methods of checking the SVI II AP magnet:
Perform a visual inspectionUse ValVue to check the magnet
Performing a Visual Inspection
You must remove the positioner from the bracket to visually inspect the magnet orientation.
For rotary valves, such as a Camflex, or for actuators with rotation of less than 60°, the magnet assembly must be aligned as shown in Figure 25.
For rotary valves with rotations greater than 60°, the magnet assembly must be aligned as shown in Figure 26 on page 47.
NOTE For a reciprocating globe valve, it is not necessary to remove
the positioner from the bracket. Details are given below.
Page 47
47
Check Out,
Checking the Magnet
For reciprocating valves the adjustable link turnbuckle must be parallel to the valve stem. To ensure linearity in positioning, verify that the hole in the lever aligns with the indicating hole in the bracket when the valve is in the closed position. Check that the bracket is mounted using the proper holes (refer to Table 4 on page 28).
Magnet Axis with Valve Closed
Figure 25 Magnet Orientation for Camflex and Varimax with Valve Closed
Magnet
Axis
with
Valve Closed
Clockwise to Close
Clockwise to Open
45
¬
Figure 26 Magnet Orientation for 90° Valve Rotation with Valve Closed
Using ValVue to Check Magnet Position
Use this procedure to check the magnet using ValVue.
1. Connect to the positioner in accordance with the ValVue instructions.
After the positioner has been installed and set up with a HART Modem in
a HART compliant communications loop, install ValVue on the computer that is connected to the HART modem.
Run ValVue.Select the installed positioner from the list of Connected Devices.Select the: Check tab to view the current operating conditions of the
selected positioner.
Page 48
48
GE Oil & Gas
ValVue SVI II AP Quick Start
2. Read Raw Sensor Data:
When the valve is closed the value should be between – 1000 and
+1000 for a reciprocating valve or a 60° rotation rotary valve.
When the valve is at mid-travel the value should be between –1000 and
+1000 for a greater than 60° rotation rotary valve.
Checking the Air Supply
Use this procedure to check the air supply.
1. Turn on the air supply.
2. Adjust the filter regulator. Supply pressure must be a minimum of 10 psi greater than the spring range of the actuator but may not exceed the rated actuator pressure. Refer to the valve or actuator instruction manual.
3. Inspect the tubing connections between the filter-regulator and the positioner for leaks.
4. Verify that the tubing is not bent or crushed.
5. Verify that all fittings are leak tight.
NOTE Do not use Teflon pipe seal tape. The Teflon tape can shred
into particles that are harmful to the pneumatic components.
Checking the Electronic Module Connections
WARNING Do not remove the instrument cover or connect to an
electrical circuit in a Hazardous Area unless the power is disconnected.
All connections to electronic module in the SVI II AP are made through the terminal board. The SVI II AP terminal board has a terminal block with cage clamp connectors. Confirm that all applicable connections to the electronics module connectors are correct. Not all options are available for every model. Refer to Table 7 for available functionality.
Page 49
Table 7 SVI II AP Models and Functionality
Available Functionality
Positioner Model Number
SVI II AP-2 SVI II AP-3
4 - 20 mA Input Setpoint
Display/ Pushbuttons Optional Optional Remote Mount Input
Solid State Switch #1 and #2 Optional Optional 4- 20 mA Out Position Transmit Optional Optional
49
Check Out,
Checking the Electronic Module
Confirm the correctness of all applicable connections to the electronics
module.
Display
Remote
Process Variable
Position Retransmit
Position Input
Configuration Lock Jumper
4- 20 mA Input Signal
Solid State Switch SW #1
Solid State Switch SW #2
Sensor
Figure 27 Connections to Electronics Module (via Terminal Board)
NOTE When an SVI II AP is turned on it is advisable to apply the air
supply before applying the electrical input signal.
Page 50
50
GE Oil & Gas
ValVue SVI II AP Quick Start
Operational Checkout
The operational checkout of the SVI II AP consists of:
Connecting the SVI II AP to a current sourceChecking the pushbutton locksPowering up the SVI II AP
Connecting to the Current Source
Connect to a DC mA current source then check and configure with the local display and pushbuttons, if so equipped. The following section describes configuration and calibration with the optional local display and pushbuttons. If the SVI II AP is not equipped with local display use ValVue Lite and a PC with a HART modem or a HART Handheld Communicator.
NOTE When an SVI II AP is turned on it is advisable to apply the air
supply before applying the electrical input signal.
Powering Up the SVI II AP
WARNING This process can cause the valve to move. Before
proceeding be sure the valve is isolated from the process. Keep hands clear from moving parts.
NOTE When an SVI II AP is turned on it is advisable to apply the air
supply before applying the electrical input signal.
CAUTION Use of a low impedance voltage source will damage the SVI
II AP. The current source must be a true high impedance current limiting device. A proper current source explicitly enables adjustment of the current in mA, not V.
To power up the SVI II AP:
1. Loosen the four (4) cover screws and remove the cover of the SVI II AP. Connect the +- terminals to the current source + to + and - to -. See Figure 27 on page 49. Reinstall the cover and display.
Page 51
51
Check Out,
Powering Up the SVI II AP
2. Adjust current to 12 mA. On initial power up of a newly installed SVI II AP, the positioner runs in NORMAL mode using the default instrument parameters installed at the factory. The positioner cycles through the NORMAL cycle menu and LCD displays the following values:
PRES: Pressure - unit of measurement and value*SIGNALPOS (Position) An exclamation point (!) appears in the top left corner of the display
window to indicate that there is further instrument status available.
3. Proceed to Configuration and Calibration.
* For firmware version 3.2.1, the supply pressure appears on the LCD. Additionally, Stops results and Autotune results, stay displayed until cleared.
NOTE If the SVI II AP is specified without local pushbuttons and
display, local operation is not available. Configure and calibrate with ValVue and a HART modem.
Page 52
52
GE Oil & Gas
ValVue SVI II AP Quick Start
Configuration
Use the procedures that follow to: calibrate, tune, view configuration data and status messages for the SVI II AP. Observe all warnings as the valve moves during these procedures.
WARNING These procedures can cause the valve to move. Before
proceeding be sure the valve is isolated from the process. Keep hands clear from moving parts.
NOTE All calibration and configuration procedures are described
using an SVI II AP with pushbuttons and display and ValVue software.
Configuration with Pushbuttons
Prior to changing the SVI II AP configuration, check the existing configuration.
Viewing Configuration Data
To view SVI II AP configuration data:
1. Access the VIEW DATA menu from the MANUAL menu by pressing the + button.
2. In the VIEW DATA menu, press * to examine the configuration.
3. Press + to scroll through and observe the factory configuration.
4. Press + until MANPOS appears.
5. Select with *.
6. When the adjustment screen appears stroke the valve open by holding + down. The rate of set point change is slow to begin, but increases speed while the + is pressed.
7. Stroke the valve to several values
8. Verify the action is as desired.
9. Press + to move to the SETUP menu.
10.In the SETUP menu press the * button to access the CONFIGuration menu.
11. In the CONFIG menu set the configuration parameters.
12.When in CONFIGure or CALIBrate, pressing * changes values.
13.Return to NORMAL mode. The valve moves to the value set by the current calibrator.
14.Stroke the valve through its range to verify that the movement is as desired.
Page 53
53
Check Out,
Configuration with Pushbuttons
Configuration Menu
Because calibration depends on certain configuration options you must perform Configuration before you perform Calibration when installing the SVI II AP for the first time.
If a change is made in the Air-to-Open / Air-to-Close configuration option or if you move the SVI II AP to a different valve or make any change to the valve position linkage, you must run the find STOPS calibration again.
Figure 28 CONFIGure Menu
Page 54
54
GE Oil & Gas
ValVue SVI II AP Quick Start
Viewing Status Messages
To view SVI II AP status messages:
1. Press + and * to select VIEW ERR
2. Observe any internal errors. For example, there should be a RESET status caused by powering up. If the positioner was powered without air a Position Error or POSERR can appear.
3. Press + to view all faults.
4. Press * to return to MANual menu.
5. Press + until CLR ERR appears.
6. Press * CLR ERR. WAIT appears for a second or two.
VIEW DATA Settings
Table 8 VIEWDATA Settings
Typical Setting Optional Setting
SINGLE DOUBLE
ATO ATC
LINEAR EQUAL 30 EQUAL 50 QUICK 50 CUSTOM CAMFXEQ
PSI BAR KPA
0.00
TS OFF
2.00
TS ON
4.00
SIG LO
4.00
SIG LO
20.00
SIG HI
12.00
SIG HI
English French
Page 55
55
Check Out,
Calibration
Calibration
CAUTION Pilot Trim Valve Applications require the use of the Manual
Stop calibration procedure (refer to Configuration and Calibration of the SVI II AP Instruction Manual, EW2002-AP). Do not run Find Stops or the ValVue Setup Wizard on valves with Pilot Trim or damage to the valve will occur.
To calibrate the SVI II AP:
1. Observe the display following power-up. The SVI II AP powers up in the previously active mode either MANUAL or NORMAL (operating) mode:
In NORMAL mode, the display alternates between POS and SIGNAL. In MANUAL, the display alternates between POS –M and SIG.
2. With MANUAL mode displayed, press * to select the MANUAL mode.
3. Press + again; CONFIG appears. Pressing + again brings CALIB.
4. Select CALIB by pressing *. STOPS appears. The valve moves full open and back to full closed. Observe all warnings.
5. Press * to cause the valve to stroke and to automatically calibrate valve travel.
6. After the STOPS procedure finishes, press + twice until TUNE appears.
Page 56
56
GE Oil & Gas
ValVue SVI II AP Quick Start
Calibration Menu
The Calibration menu shown in Figure 29 provides access to all the calibration functions for the SVI II AP. If a change is made in the Air-To-Open/Air-To-Close configuration option or if you move the SVI II AP to a different valve or make any change to the valve position linkage, you must run the find STOPS calibration again.
Figure 29 CALIBration Menu
Page 57
57
Check Out,
Calibration
Auto Tune
This process takes 3 to 10 minutes and strokes the valve in large and small steps to set the PID parameters for best positioning response.
WARNING DO NOT perform STOPS while the valve is controlling the
process. DO NOT perform Auto Tune while the valve is controlling the process.
To auto tune the SVI II AP:
1. Press *to begin the autoTUNE procedure. As autoTUNE proceeds, numerical messages display, indicating the procedure is working.
2. When autoTUNE is complete, TUNE appears.
3. Press + repeatedly until SETUP appears.
4. Press * to return to SETUP menu;
CALIB appears.
Page 58
Normal Cycling
Menu
Normal Manual
View Data
View ERR CLR ERR
Manual Mode
Cycling Menu
View Data
Menu
View Errors
Menu
Instant Action
Normal Manual
View Data
View ERR CLR ERR
Manual
Setup
MAN POS
<value>
<value>
* - +
Config
Config Calib
*
+ ++
+
+
+
+
+
+
+
*
*
*
*
*
*
*
*
**
any key
+
+
+
+
+
+
**
*
*
any key
*
Calib
MenuMenu
58
GE Oil & Gas
ValVue SVI II AP Quick Start
Figure 30 NORMAL Operation and MANUAL Menu Structures
Page 59
59
Check Out,
Check-out with a HART
Check-out with a HART Handheld Communicator
If the SVI II AP is not equipped with optional push buttons and local display the checkout and configuration is performed using the standard HART communications interface.
Connect the HART handheld communicator to the SVI II AP as shown in
Figure 31. Refer to the product manual for the HART communicator in use.
+
-
12.00 mA
Configuration
Lock Jumper
Input Signal
DPI620
Figure 31 SVI II AP HART Communicator Connections
Be sure that the configuration lock jumper is in the unlock position. When the jumper is in the lock position (shorting the two-pin header) the handheld is not permitted to make any changes. However, parameters are readable. If fault messages appear, they must be handled before proceeding with HART communications. Before communications proceeds all error messages must be cleared. For example, the following message is displayed if the instrument has been serviced and the air is not connected.
Process applied to the non-primary variable is outside the operating limits of the field device
NOTE For HART 6 units, the Maintenance Required response under
Additional Status does not indicate any maintenance need.
Page 60
60
GE Oil & Gas
ValVue SVI II AP Quick Start
Proceed with the following steps:
1. Press NEXT.
2. Field device has more status available
3. Press NEXT
4. Ignore next 50 occurrences of status?
5. Press YES
6. Change to MANual mode
7. Scroll to line 6 EXAMINE, press
->
8. Scroll down to 5 read status.
9. Read message.
10.Press OK.
11. Repeat OK to read all messages until the display returns to read status.
12.Scroll down to 6 clear status, press
->
13.If clear fault codes not completed appears, press OK and read the message (Position Error, for example) or go to the troubleshooting guide.
14.Correct the problem (Is the air supply on?), and then go to clear status until Clear Fault codes Completed appears.
15.Press OK.
Page 61
61
4
SVI II AP Maintenance
The SVI II AP was designed based on a modular concept. All components are interchangeable allowing for easy, quick component swapping.
The only maintenance procedures recommended for the SVI II AP are:
Remove and install the coverRemove and install the I/P moduleRemove and install the pneumatic relayUpgrade to display cover
WARNING
Do not remove the instrument cover or connect to an electrical circuit in a Hazardous Area unless the power is disconnected.
Repair
Replacement of the Pneumatic Relay, I/P and cover (with or without display) are the only field repairs permitted.
Only qualified service personnel are permitted to make repairs. Only factory-supplied parts are permitted. This includes not only the major
assemblies but also mounting screws and O rings. No substitutions with non­Masoneilan parts are permitted.
Detailed replacement procedures are described in the Instruction Manual. The following summary assures the integrity of the SVI II AP.
Tools Needed for Cover Replacement
5 mm hex key for the cover3 mm hex key for the lanyard
Maintenance
Page 62
62
GE Oil & Gas
ValVue SVI II AP Quick Start
Display Cover Removal and Installation
The cover with display (shown in Figure 32) is an option for the SVI II AP. If you have an SVI II AP with a solid cover and would like to upgrade to a display cover, follow the instructions below for removal and installation.
Removing the SVI II AP Display Cover
To remove the SVI II AP display cover:
1. Using a 5 mm Hex key unscrew the four screws around the perimeter of the SVI II AP cover.
2. Lift the cover off the positioner.
Pneumatic Cover
Cover
Display
Figure 32 SVI II AP Pneumatic and Display Covers
Installing the SVI II AP Display Cover
NOTE After replacing the SVI II AP display cover you must power up
the unit (see “Powering Up the SVI II AP” on page 50 of this guide).
The replacement display cover is shipped with a lanyard to prevent the cable (that connects from the display to the terminal board) from breaking. The lanyard must be inserted under the screw in the lower left corner that attaches the terminal board to the SVI II AP housing.
Page 63
63
Maintenance
Display Cover Removal and
To Install the cover:
1. Install the lanyard and tighten the screw to 5 in/lb.
2. Using the 3 mm hex key, remove the screw from the lower left corner, connecting the terminal board to the SVI II AP housing.
3. Connect the cable from the display into the LCD connector on the terminal board.
4. Ensure that the gasket is in its groove in the housing.
5. Place the cover over the screw mounts.
6. Tighten the four screws with the 5 mm hex key.
7. After installing the new display, power up the unit (refer to “Powering Up the SVI II AP” on page 50 of this guide for further information).
NOTE The cover of the SVI II AP is a critical component for safety in
Hazardous Areas. To ensure safe operation the flat surfaces of the cover and the housing must be clean and absolutely free of particles or dents. There must be no gap between the housing and cover; torque spec is 50 in/lb.
Ensure that:
1. The gasket is seated in the groove in the housing flange.
2. No wires or retaining cable can be trapped under the cover flange.
3. The flange area is not corroded and the surface is not scarred.
4. The four cover bolts are securely tightened to 50 in/lb.
Page 64
64
GE Oil & Gas
ValVue SVI II AP Quick Start
This page intentionally left blank.
Page 65
65
A
Physical and Operational Specifications
This section provides the physical and operational specifications for the SVI II AP.
Table 9 Environmental Specifications
Operating Temperature Limits -58° F to 185° F (-50° C to 85° C) Storage Temperature Limits -58° F to 200° F (-50° C to 93° C) Temperature Effect < 0.005% / °F typical; -40° F to 180° F (< 0.01% / °C typical;
-40° C to 82° C) Supply Pressure Effect 0.05% per psi (.73% per bar) Relative Humidity 10 to 90% non-condensing Humidity Effect Less than 0.2% after 2 days at 104 °F (40° C), 95% Relative
Humidity. Insulation Resistance Greater than 10 G Ohms at 50% RH. MTBF 49 years based on MIL handbook calculation for electronic parts
and field data on mechanical parts Electromagnetic Compatibility
Electrostatic
Electrostatic discharge — No effect with contact discharge level of
4KV and air discharge level of 8 kV
(IEC 1000-4-2)
Radio frequency interference — Less than 0.2% at 10 V per meter
(EN 50140) Fast Transient Burst No effect at 2 kV (Coupling clamp IEC 1000-4-4). Vibration Influence
Measured at SVI II AP Housing
4 mm at 5 - 15 Hz - Negligible
2 G at 15 - 150 Hz Less than 2 % of span
1 G at 150 - 2000 Hz - Less than 2% of span Magnetic Field Influence Negligible at 30 A/m (EN61000-4-8)
CE MARK certified to EN50081-2 and EN50082-2
Specifications and References
Page 66
66
GE Oil & Gas
ValVue SVI II AP Quick Start
Table 10 Operational Specifications
Accuracy +/- 0.5% (typical +/-0. 10% or less) Full Span Hysteresis and Deadband +/- 0.3% Full Span Repeatability +/- 0.3% Full Span Conformity +/- 0.5% Full Span Start-Up Drift Less than 0.02% in first hour Long Term Drift Less than 0.003% per month Position Travel Limits Rotary: 18 - 140°
Reciprocating: 0.25” - 2.5“ (6 mm - 64 mm) Note: Above 2.5” (64 mm) consult factory for mounting instructions.
Flow Characteristics Applied in addition to the control valve’s inherent characteristic.
Linear Equal Percentage (of 50:1 or 30:1) Camflex Quick Opening (inverse of 50:1 equal percentage) User Configurable Tight Shut Off (0 -20% of input)
Position Auto Tune SVI II AP performs automatic determination of the
optimal valve position control parameters. In addition to P, I, D, the position algorithm uses damping, symmetry for exhaust and fill time constants, dead zone and magnitude characterization parameters. Auto Tune is optimized for 5% step changes with negligible overshoot. After the Auto Tune process is completed, the user can further adjust the positioner tuning parameters to more conservative or to more responsive values.
Proportional gain: 0 to 5, displayed as 0 to 5000 Integral time: 0 to 100 seconds - displayed as 0 to 1000 (1/10s) Derivative time: 0 to 200 milliseconds Dead Zone: 0 to +/-5% (0 to 10% deadband) Padj: +/- 3000 (depends on P) Beta (non-linear gain factor): -9 to +9 Stroking Time: 0 to 250 seconds Position compensation coefficient: 1 to 20 Boost: 0 to 20
Full open position adjustment 60 to 100% of actual stop Start Up Time (from no power) Less than 200 ms Minimum current to maintain HART 3.0 mA HART Command #3 Mapping PV= Valve Position, 0-100%
SV = Actuator Pressure, configured eng. units TV = Future QV = Future
HART 6 Commands Cmd 9 - Reads device vars w/status.
Cmd 33 - Reads device variables.
* Specifications are subject to change without notice
Page 67
Table 11 Input Signal, Power, and Display Specifications
Power Supply Loop powered from 4-20 mA control signal Compliance Voltage Rating 9.0 V at 20 mA, 11.0 V at 4.0 mA Minimum Current Signal to Start Up 3.2 mA Minimum Input Span for Split Range Operation 5 mA Upper Range Value for Split Range Operation 8 mA to 20 mA Lower Range Value for Split Range Operation 4 mA to 14 mA Wire Size 14/28 AWG Strip Length 0.22 in / 6 mm DIgital Communication HART Communication protocol revision 5 or 6 Local Display LCD, Explosion proof with two lines of nine alpha
numeric characters
Push Buttons External, Three Explosion Proof / Flameproof push
buttons
Table 12 Construction Material Specifications
Housing and Cover Aluminum ASTM B85 SG100A standard
Stainless Steel optional
Weight Standard Flow Model:
- Aluminum - 7.4 lbs./ 3.3 kg
- Stainless Steel - 16 lbs/ 7.3 kg High Flow Model:
- With Display: 9.4 lbs./ 4.2 kg
- Without Display: 8.9 lbs./ 4.0 kg
Relay and Manifold Standard Flow Model:
Single Acting - PPS, 300 Series Stainless Steel, nitrile diaphragms Double Acting - 300 Series Stainless Steel, Ryton Aluminum 6061 T6, Ryton
High Flow Model: 300 Series Stainless Steel, Ryton
Aluminum 6061 T6, Ryton I/P Motor 430 stainless steel, PPS, 300 series stainless steel Mounting Bracket 300 series stainless steel Magnet Holder Corrosion Protected Anodized Aluminum 6061 T6 Pole Ring 416 stainless steel Levers 300 Series stainless steel
67
Specifications and
Page 68
Table 13 System Connectivity
HART Physical Device Type Valve positioner; HART device type 7, Device type 202, 0, 00CA) DD Registered with HART
Communication Foundation
Yes
Integration with HART Host software ValVue AMS SNAP-ON application available, Plug-In Application For
Yokogawa PRM, ValVue For Honeywell FDM, Device Type Manager (DTM) for FDT Host
Diagnostics Standard:
Alarms, cycle counter, travel accumulator, time open, time close, time near close, Step Test, Positioner Test Advanced: Includes Standard Diagnostics and the following: Low Air Supply alarm, Valve Signature (Friction, spring range, seat profile)
Table 14 Pneumatics Single Acting Standard Flow
Air Supply Dry, oil-free, 5 micron filtered air (per ISA S7.3) Action Direct Acting Supply Pressure 20-100 psi max. (1.4 to 6.9 bar)
Regulate 5 to 10 psi above actuator spring range. Do not exceed actuator rating.
Air Delivery - Single Acting Relay 10.0 scfm (283 l/m) at 30 psi (2.1 bar) supply
16.6 scfm (470 l/m) at 60 psi (4.2 bar) supply
23.3 scfm (660 l/m) at 90 psi (6.3 bar) supply
Air Capacity (flow coefficient)
Loading CV = 0.57 Venting CV = 0.53
Air Consumption 0.2 scfm (5.7 sl/m) at 30 psi (2.1 bar) supply
0.26 scfm (7.4 sl/m) at 45 psi (3.1 bar) supply
Air Supply Failure Single Acting Relay
On supply failure the actuator output fails to atmosphere. Some overshoot may occur when air pressure returns after a period without air supply pressure. Always set control set point to 0%, and put the process control system in manual, for smooth recovery from air supply
failure. Loss of Input Signal Actuator Output fails to atmosphere Output Pressure 0-150 psi (10.3 bar) max
68
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 69
Table 15 High Flow Pneumatics Single Acting High Flow
Air Supply Dry, oil-free, 5 micron filtered air (See ISA S7.3) Action Direct Acting Supply Pressure 20 -100 psi max. (1.4 - 6.9 bar)
Regulate 5 - 10 psi (.345 bar - .69 bar) above actuator spring range. Do not exceed actuator rating.
Air Delivery - Single Acting Relay 39.0 scfm (1104 l/m) at 30 psi (2.1 bar) supply
70.6 scfm (2000 l/m) at 60 psi (4.2 bar) supply
102.0 scfm (2888 l/m) at 90 psi (6.3 bar) supply
Air Capacity (flow coefficient)
Loading CV = 2.2 Venting CV = 2.2
Air Consumption 0.28 scfm (8.0 sl/m) at 30 psi (2.1 bar) supply
0.35 scfm (10.5 sl/m) at 45 psi (3.1bar) supply
Air Supply Failure Single Acting Relay
On supply failure the actuator output drops. Some overshoot may occur when air pressure returns after a period without air supply pressure. Always set control set point to 0%, and put the process control system in
manual, for smooth recovery from air supply failure. Loss of Input Signal Output drops to low pressure. Output Pressure 0-150 psi (10 bar) max
69
Specifications and
Page 70
Table 16 Pneumatics Double Acting Standard Flow
Air Supply Dry, oil-free, 5 micron filtered air see ISA S7.3 Action Output 1 increases with increasing signal
Output 2 decreases with increasing signal
Supply Pressure for Double Acting
25 - 150 psi max. (1.73 to 10.3 bar) Do not exceed actuator rating.
Air Delivery for Double Acting
7.2 scfm (204 l/m) at 30 psi (2.1 bar) supply
12.8 scfm (362 l/m) at 60 psi (4.2 bar) supply
18.3 scfm (518 l/m) at 90 psi (6.3 bar) supply
23.8 scfm (674 l/m) at 120 psi (8.3 bar) supply
Air Capacity (flow coefficient)
Loading CV = 0.57 Venting CV = 0.53
Air Consumption for Double Acting
0.4 scfm (11.3 l/m) at 30 psi (2.1 bar) supply
0.85 scfm (24.1 l/m) at 80 psi (5.52 bar) supply
Air Supply Failure Positioner cannot control the failure position of an actuator without a spring. The
actuator can, under different conditions, fail in place, fail open, or fail close. In cases where the valve must fail to a required position additional accessories are required.
Some overshoot can occur when air pressure returns after a period without air supply pressure. Always set control set point to 0%, and put the process control system in manual, for smooth recovery from air supply failure.
Loss of Input Signal Output 1 fails to atmosphere
Output 2 fails to supply pressure.
70
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 71
Series Identification SVI AP-abcdefgh
a Style 1,2,3
1. ES Version - Easy Smart
2. SD Version - Standard Diagnostics
3. AD Version - Advanced Diagnostics
b Pneumatic Train 1,2
1. Single Acting
2. Double Acting
c Pneumatics
1. Standard flow
d Display 1,2,3,4
1. No Display and Pushbuttons
2. With Display and Pushbuttons
3. No Display and Pushbuttons, Marine
4. With Display and Pushbuttons, Marine
e Hardware Version 3
3.
f Communications 1
1. 4 to 20 mA - HART Communications
g Option Board 1,2
1. None
2. Position Retransmit
h Agency Approvals 1,4
1. ATEX/FM/CSA/Intrinsic Safety & Exprf
4. ATEX (IS, NI)
Approved Configuration Codes
SVI2 AP-
1 2 3
1 2
1 2
1 2 3 4
31121
and Limit Switches
2. High Flow (Cv2)
4
71
Specifications and
Figure 33 SVI II AP Model Numbering
Page 72
72
GE Oil & Gas
ValVue SVI II AP Quick Start
Hazardous Location Installation
The following pages provide the agency approved installation procedure for hazardous locations.
NOTE The installation procedure is accurate at time of print. For
further hazardous installation information please consult the factory.
Page 73
ES – 699
SPECIAL INSTRUCTIONS FOR INSTALLING MASONEILAN
SVI-II AP AND SVI II REMOTE IN AREAS WHERE THERE IS A
POTENTIAL FOR EXPLOSIVE GAS ATMOSPHERE OR
INFLAMMABLE DUST
Page 1 of 17
Copyright 2011. This document and all information herein is
the property of Dresser Inc.
Drawn
Levesque
4 Aug 05
Approved
Smart
4 Aug 05
ES-699 REV U
REV
Description
Date
A
Initial Release
16 Aug 05
B
Revised model code, min XP
temp was
20°C; FM/CSA no
Analog Out
27 SEP 05
C
PDev DR 0208
10/12/05
D
PDev DR 0225
11/28/05
E
ADR-002909
5/8/06
F
ADR-002948
9/6/06
G
ADR-002987
12 FEB 07
H
ADR-003099
28MAY08
J
ADR-003318
2FEB10
K
ADR-003330
25MAR10
L
ADR-003353
18MAY10
M
ADR-003412
17SEP10
N
ADR-003430
27OCT10
P
ADR-003505
7MAR11
R
ADR-003581
20SEP11
T
ADR-003626
24FEB12
U
ADR-003666
19APR12
1
INTRODUCTION
This manual covers the requirements for safe installation, repair, and operation of the SVI-II AP as it relates to operation in areas where there is a potential for explosive atmosphere or inflammable dust. Adherence to these requirements assures that the SVI-II AP will not cause ignition of the surrounding atmosphere. Hazards related to control of the process are beyond the scope of this manual. For mounting instructions on specific valves refer to the mounting instructions supplied with the mounting kit. Mounting does not affect the suitability of the SVI­II AP for use in a potentially hazardous environment. The SVI-II AP is manufactured by:
Masoneilan/Dresser
85 Bodwell Street
Avon MA – 02322 – USA
73
Specifications and
Hazardous Location Installation
Page 74
ES-699 Rev U
Page 2 of 17
2
GENERAL REQUIREMENTS
Installation and maintenance must be performed only by qualified personnel. Area Classification, Protection Type, Temperature Class, Gas Group, and Ingress protection must conform to the data indicated on the label.
Wiring and conduit must conform to all local and national codes governing the installation. Wiring must be rated for at least 5ºC above the highest expected ambient temperature.
Approved wire seals against ingress of water and dust are required and the NPT fittings must be sealed with tape or thread sealant in order to meet the highest level of ingress protection.
Where the protection type depends on wiring glands, the glands must be certified for the type of protection required.
The metal housing is a die-casting alloy which is predominately aluminum.
Before powering the SVI-II AP:
Verify that the pneumatic and electronic cover screws are tightened. This is important to maintain the ingress protection level and the integrity of the flameproof enclosure.
If the Installation is Intrinsically safe, then check that the proper barriers are installed and the field wiring meets local and national codes for an IS installation. Never install a device, which was previously installed without an intrinsically safe barrier, in an intrinsically safe system.
If the pneumatic system is powered by a combustible gas then the installation must be treated as Zone 0 or DIV I.
If the Installation is Non-Incendive, then check that all the electrical connections are made to approved devices and wiring meets local and national codes.
Verify that the markings on the label are consistent with the application.
Verify that the air supply pressure can not exceed the marking on the
respective label.
!WARNING!
Failure to adhere to the requirements
listed in this manual may cause loss
of life and property.
74
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 75
ES-699 Rev U
Page 3 of 17
3
Model Number Description of SVI-II AP
SVI2-abcdefgh Not all combinations are available.
SVI2- a b c d e f g h
0
Generic ( National
Labeling as
Required)
1
ES -Easy
Smart (1)
Single Acting
Standard
Flow
No Display No Buttons
Industrial
Hart
4 to 20 MADC
None
FM, CSA,
ATEX
, IEC
(XP, DIP, IS
, NI)
2
SD -
Standard
Diagnostics
Remote Sensing
Double
Acting
High
Capacity
Display
Buttons
Industrial
(2)
Retransmit and Digital
Out (Note
3)
3
AD -
Advanced
Diagnostics
Remote Sensing
No Display No Buttons
Offshore
Plug-in
Electronics
Module
(MNCB)
Retransmit
(Note 4)
FM, CSA ATEX (IS,
NI)
4
OD - On-Line
Diagnostics
Remote Sensing
Display
Buttons
Offshore (2)
ATEX (IS, NI)
5
PC - Process
Controller
Remote Sensing
6
FM, CSA,ATEX,IEC
(XP, DIP, IS, NI)
Nuclear
Style
Pneumatics
Capacity
Display
Electronics
Communication
Option
Hazardous
Certification
(1) Not available in a flameproof housing. (2) The SVI-II AP may be up-graded in the field by the addition of a display and buttons. (3) Not available on SVI2-0 (4) Available only on SVI2-0
4
FLAMEPROOF and DUST IGNITION PROOF REQUIREMENTS
4.1 General
The 1/2 inch NPT fittings must enter the housing at least five full turns. The cover flange must be clean and free of corrosion products.
4.2 Cable Glands
Certified cable glands are required based on the hazardous area the device is installed in. That is, the particular cable gland used must have the same certification as the tick-box checked off on the label (see Section 6).
4.3 Natural gas
Use of a pressurized gas which is ignitable in the presence of air (for
example natural gas) is not allowed as the SVI II AP supply pressure
in a flameproof (protection type “d”) installation.
75
Specifications and
Hazardous Location Installation
Page 76
ES-699 Rev U
Page 4 of 17
4.4 Bolting
“X” Marking on label- M8 X 1.25-6g cover screws must be supplied by Masoneilan. No substitution allowed. Minimum yield stress to be 296 N/mm^2 (43,000 psi)
5
INTRINSICALLY SAFE REQUIREMENTS
5.1 Div 2
WARNING: EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOW TO BE NON-HAZARDOUS.
5.2 Category II 1 (Zone 0)
For operation in hazardous area category II 1, over-voltage protection of the electrical connections need to be installed according to EN 60079-14 For operation in hazardous area category II 1 the ambient temperature needs to be lowered according to the requirements of EN 1127-1 (reduction factor of 80%). The max. allowed ambient
temperature for category 1 inclusive the requirement of EN1127-1 is: T6 : Ta = -40°C to +43°C T5 : Ta = -40°C to +55°C T4 : Ta = -40°C to +83°C
5.3 Category II 1 (Zone 0)
“X” Marking on label - Since the SVI2-abcdefgh (“SVI-II AP”) and the SVI-II Remote enclosures contain greater than 10% aluminum, care must be taken during installation to avoid impacts or friction that could create an ignition source.
76
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 77
ES-699 Rev U
Page 5 of 17
6
Description of Flameproof and Intrinsically Safe Markings
Applicable Model Numbers: SVI2-abcdefgh, where “a” thru “h” can take on the following values: a = 2,3,4,5 ; b = 1,2 ; c = 1,2 ; d = 1,2,3,4 ; e = 3 ; f = 1 ; g = 1,2,3 ; h = 1
The label may not appear exactly as shown, but must contain the following information listed below. Other information is allowed on the label.
Avon MA USA
Supply Connection Wiring Rated for 5ºC Above Max Ambient
WARNING
Refer to ES-699 for additional Cautions or Warnings
DO NOT OPEN EVEN WHEN ISOLATED WHEN FLAMMABLE / DUST ATMOSPHERES ARE PRESENT
MODEL: SVI2-abcdefgh SN –nnywwnnnn Type 4X – IP 66 T6 Ta=60ºC, T5 Ta=75ºC T4 Ta=85°C
CL I; DIV 1; GP B,C,D CL II; DIV 1; GP E,F,G CL III, DIV 1 IS – CL I; DIV 1; GP A,B,C,D IS – CL II; DIV 1; GP E,F,G IS – CL III; DIV 1
IS – CL I/II/III; DIV 1; GP A,B,C,D,E,F,G
ZELM 05ATEX0280X
Operating Temp –40 to +85ºC 30 Volts, 4-20 mA, 150 PSI
0518
011531-741-779 Rev G
Ex ia IIC T6
XP – CL I; DIV 1; GP A,B,C,D NI – CLI;DIV2;GPA,B,C,D DIP – CL II/III; DIV 1; GP E,F,G S – CL II/III; DIV 2; GP F,G
PERMANENTLY MARK THE PROTECTION TYPE CHOSEN. ONCE THE TYPE HAS BEEN MARKED, IT CAN NOT BE CHANGED.
II 1G Ex ia IIC T6 II 1D Ex iaD 20 T96°C
II 2G Ex dm IIB+H2 T6 II 2D Ex tD A21 IP66 T96°C II 3G Ex nL IIC T6 II 3D Ex tD A22 IP66 T96°C
Ex d mb IIC Gb T5; Ex tD A21 IP66 T96
ºC;
Ta=-40
ºC to +85ºC: IP66
IECEx FMG 07.0007X
IN GROUP A INSTALLATIONS, CONDUIT SEAL REQUIRED WITHIN 18 INCHES OF ENCLOSURE ENTRANCE
6.1 Manufacturers Name and Location
AVON MA USA
6.2 Markings:
(Factory Mutual)
{Certif ying Agency}
IN GROUP A INSTALLATIONS CONDUIT SEAL REQUIRED WITHIN 18 INCHES OF ENCLOSURE
IS – CL I/II/III; DIV 1; GP A, B, C, D, E, F, G {Intrinsically Safe} NI – CL I; DIV 2; GP A, B, C, D {Non-Incendive} XP – CL I; DIV 1; GP A,B, C, D {
Explosionproof
} DIP – CL II/III; DIV 1; GP E, F, G {Dust Ignitionproof} S – CL II/III; DIV 2; GP F, G {Special Protection}
77
Specifications and
Hazardous Location Installation
Page 78
ES-699 Rev U
Page 6 of 17
(CSA)
{Certifying Agency}
CL I; DIV 1; GP B, C, D {
Explosionproof
, gas}
CL II; DIV 1; GP E, F, G {
Explosionproof
, dust}
CL III, DIV 1 {
Explosionproof
, fiber} IS – CL I; DIV 1; GP A, B, C, D {Intrinsically Safe, gas} IS – CL II; DIV 1; GP E, F, G {Intrinsically Safe, dust} IS – CL III; DIV 1 {Intrinsically Safe, fiber}
(ATEX)
{EU Community
Compliance Marking}
{QAN Notified Body}
ZELM {Approval Agency} 05ATEX0280X {Certifiacte Number} II 1G Ex ia IIC T6
{Intrinsically Safe, gas}
II 1D Ex iaD 20 T96°C
{Intrinsically Safe, dust} II 2G Ex dm IIB+H2 T6 {Flameproof/ Encapsulation, gas} II 2D Ex tD A21 IP66 T96°C {Protection by
Enclosure,dust}
II 3G Ex nL IIC T6 {Limited Energy, gas} II 3D Ex tD A22 IP66 T96°C {Protection by Enclosure,
dust}
(IEC)
IECEx FMG 07.0007X {Certificate Number}
Ex ia IIC T6 {Intrinsically Safe}
Ex d mb IIC Gb T5
{Explosionproof, gas} Ex Td A21 IP66 T96°C
{Protection by enclosure,
dust}
Ta=-40°C to +85°C {Operating Temperature} IP66 {Ingress Protection}
0518
78
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 79
ES-699 Rev U
Page 7 of 17
6.3 Operating Ranges
6.3.1 Temp:
-40°C to +85°C
6.3.2 Voltage:
30 Volts
6.3.3 Pressure:
150 psig (1.03MPa)
6.3.4 Current:
4-20mA
6.4 Enclosure Type:
Type 4X-IP66
6.5 Temperature Code:
T6 Ta=60°C, T5 Ta=75°C, T4 Ta=85°C
6.6 Notes Related to Explosionproof Rating
1) “DO NOT OPEN EVEN WHEN ISOLATED WHEN FLAMMABLE GAS OR DUST ATMOSPHERES ARE PRESENT
6.7 Notes Related to Intrinsic Safety
1) INTRINISICALLY SAFE WHEN INSTALLED INSTALL Per ES-699”
2) Supply Connection Wiring Rated for 5ºC Above Max Ambient
3)
PERMANENTLY MARK THE PROTECTION TYPE CHOSEN. ONCE THE TYPE HAS BEEN MARKED, IT CAN NOT BE CHANGED”
6.8 Model Code:
SVI2-abcdefgh (see section 3 above for explanation)
6.9 Serial Number:
“SN-nnyywwnnnn”
79
Specifications and
Hazardous Location Installation
Page 80
ES-699 Rev U
Page 8 of 17
7
Description of Intrinsically Safe Markings
Applicable Model Numbers: SVI2-abcdefgh, where “a” thru “h” can take on the following values: a = 1 ; b = 1 ; c = 1, 2 ; d = 1, 2 ; e = 3 ; f = 1 ; g = 1,2 ; h = 3,4
The label may not appear exactly as shown, but must contain the following information listed below. Other information is allowed on the label.
II 3G Ex nL IIC T6
Avon MA USA
WARNING
REFER TO ES-699 FOR ADDITIONAL CAUTIONS OR WARNINGS Supply Connection Wiring Rated for 5ºC Above Max Ambient MODEL: SVI2-1bcdefgh 30 Volts, 4-20mA, 80 PSI Type 4X-IP66
DO NOT OPEN EVEN WHEN ISOLATED WHEN FLAMMABLE / DUST ATMOSPHERES ARE PRESENT
ZELM 05ATEX0280X
SN-nnywwnnnn
Operating Temp –40ºC to +85ºC
T6 Ta=60ºC, T5 Ta=75ºC, T4 Ta=85ºC
055201-188-779 Rev E
PERMANENTLY MARK THE PROTECTION TYPE CHOSEN. ONCE THE TYPE HAS BEEN MARKED, IT CAN NOT BE CHANGED.
II 2G Ex ia IIC T6
0518
Ex ia IIC T6
IECEx FMG 07.0007x
IECEx
II 2D Ex iaD 20 T96°C
7.1 Manufacturers Name and Location
AVON MA USA
7.2 Markings:
(ATEX)
{Explosionproof Mark}
{European Community
Compliance Mark}
ZELM {Certifying Agency} 05ATEX0280X {Certificate Number} II 2G Ex ia IIC T6
{Intrinsically Safe, gas}
II 2D Ex iaD 20 T96°C
{Intrinsically Safe, dust}
II 3G Ex nL IIC T6
{Limited Engery, gas}
0518
80
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 81
ES-699 Rev U
Page 9 of 17
(IEC) IECEx {IEC Logo} Ex ia IIC T6
{Intrinsically Safe}
IECEx FMG 07.0007x
{CertificateNumber}
7.3 Operating Ranges
7.3.1 Temp:
-40°C to +85°C
7.3.2 Voltage:
30 Volts
7.3.3 Pressure:
80 psig (0.55 Mpa)
7.3.4 Current:
4-20mA
7.4 Enclosure Type:
“Type 4X-IP66”
7.5 Temperature Class:
“T6 Ta=60°C, T5 Ta=75°C, T4 Ta=85°C”
7.6 Notes Related to Intrinsic Safety
1) INTRINISICALLY SAFE WHEN INSTALLED INSTALL Per ES-699”
2) “Supply Connection Wiring Rated for 5ºC Above Max Ambient”
3)
PERMANENTLY MARK THE PROTECTION TYPE CHOSEN. ONCE THE TYPE HAS BEEN MARKED, IT CAN NOT BE CHANGED”
7.7 Model Code:
SVI2-1bcdefg4 (see section 3 above for explanation)
7.8 Serial Number:
“SN-nnyywwnnnn”
81
Specifications and
Hazardous Location Installation
Page 82
ES-699 Rev U
Page 10 of 17
8
Description of Flameproof and Intrinsically Safe Markings, SVI-II Remote Mount
8.1 Manufacturers Name and Location
Dresser Inc. Masoneilan Operations Avon, MA 02322
8.2 Product Name:
“SVI-II Remote Mount
82
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 83
ES-699 Rev U
Page 11 of 17
8.3 Logos/Markings:
(Factory Mutual, US and Canada)
C
US
IS CL I, II, III; DIV 1; GP A, B, C, D, E, F, G
{Intrinsically Safe}
NI CL I; DIV 2; GP A, B, C, D {Non-Incendive, gas}
SUITABLE FOR CL II, III; DIV 2; GP F, G {Suitable for dust, Div 2}
XP CL I; DIV 1 GP B, C, D {Explosionproof, gas}
SUITABLE FOR CL II; DIV 1; GP E, F, G {Suitable for dust, Div 1}
SUITABLE FOR CL III, DIV 1 {Suitable for fibers, Div 1} T5 Ta=85°C T6 Ta=75°C
(ATEX)
8.3.1
ATEX Specific Note:
PERMANENTLY MARK THE PROTECTION TYPE CHOSEN. ONCE THE TYPE HAS BEEN MARKED, IT CAN NOT BE CHANGED
II 1 G Ex ia IIC T5 Ta=85°C, T6 Ta=75°C
{Intrinsically Safe, gas} II 1 D Ex iaD 20 IP66 T96°C
{Intrinsically
Safe, dust}
FM11ATEX0008X {Certificate
Number}
II 2 G EEx d IIB+H2 T5 Ta=85°C, T6 Ta=75°C {FlameProof,
gas}
II 2 D Ex tD A21 IP66 T96°C {FlameProof,
dust}
0518
83
Specifications and
Hazardous Location Installation
Page 84
ES-699 Rev U
Page 12 of 17
FM06ATEX0004X {Certificate
Number}
II 3 G EEx nL IIC T5 Ta=85°C, T6 Ta=°75C {Non- Incendive, gas}
II 3 D Ex tD A22 IP66 T96°C {Non- Incendive, dust}
FM06ATEX0005X {Certificate Number}
8.4 Operating Ranges
8.4.1 Temp:
-50°C ≤ Tamb ≤ +85°C
8.4.2 Electrical:
30 VDC Max, 1 Watt, Ui=6.5 Volts, li=10.5mA, Ci=0, Li=0,
Pi=68mW
8.5 Enclosure Type:
Type 4X-IP66
8.6 Temperature Class:
T6 Ta=60°C, T5 Ta=75°C, T4 Ta=85°C
8.7 Notes Related to Intrinsic Safety
1) INTRINISICALLY SAFE WHEN INSTALLED Per ES-699”
2) “Supply Connection Wiring Rated for 5ºC Above Max Ambient”
8.8 Other Notes
1) “¾ INCH 14 NPT CONDUIT THREAD”
8.9 Model Code:
“SVI2-abcdefgh” (see section 3 above for explanation)
8.10 Serial Number:
“REM-YYWWXXX (this label is located within the device)
84
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 85
ES-699 Rev U
Page 13 of 17
9
Intrinsically Safe Installation Wiring Requirements
Each intrinsically safe cable must include a grounded shield or be run in a separate metal conduit.
85
Specifications and
Hazardous Location Installation
Page 86
ES-699 Rev U
Page 14 of 17
10
Notes for Intrinsically Safe Installation
10.1 HAZARDOUS LOCATION
Refer to the device label for the description of the environment in which the device may be installed.
10.2 FIELD WIRING
Intrinsically Safe wiring must be made with grounded shielded cable or installed in grounded metal conduit. The electrical circuit in the hazardous area must be capable of withstanding an A.C. test voltage of 500 volts R.M.S. to earth or frame of the apparatus for 1 minute. Installation must be in accordance with Masoneilan guidelines. The installation including the barrier earthing requirements must comply with the installation requirements of the country of use.
Factory Mutual requirements (USA): ANSI/ISA RP12.6 (Installation of Intrinsically Safe Systems for Hazardous (Classified) Locations) and the National Electrical Code, ANSI/NFPA 70. Division 2 installations must be installed per the National Electrical Code, ANSI/NFPA 70. See also, note 4.
CSA requirements (Canada): Canadian Electrical Code Part 1. Division 2 installations must be installed per the Canadian Electrical Code Division 2 Wiring Methods. See also note 4.
ATEX requirements (EU): Intrinsically safe installations must be installed per EN60079-10 and EN60079-14 as they apply to the specific category.
10.3 SVI-II AP (+) and (-) 4-20 mA IN Terminals
These terminals power the SVI-II AP. The barrier is the Controller Output Type, for example MTL 728. Entity Parameters: Vmax= 30 Vdc; Imax=125 mA; Ci = 6.5 nF; Li = 1 uH; Pmax = 900 mW
10.4 SVI-II AP (+) and (-) 4-20mA OUT Terminals
These terminals provide a 4 to 20 mA signal related to valve position. The 4 to 20 OUT terminals behave much like the terminals of a transmitter so a Transmitter type barrier with 250 Ohm series resistance (internal or external) is used for this connection. For example, MTL 788 or 788R. Use of the 4-20 OUT feature is certified to ATEX intrinsically safe requirements and is approved for use in Zone 0. Use of the 4-20 mA OUT feature has not been certified by FM or CSA. The 4-20 mA OUT feature may not be used in an intrinsically safe installation when FM or CSA intrinsically safe approval is required. The 4-20 mA OUT feature is certified by FM and CSA for use in a DIV 2 area and in a DIV 1 area when the SVI2 is installed in accordance with flameproof requirements.
86
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 87
ES-699 Rev U
Page 15 of 17
Entity Parameters: Vmax = 30 Vdc; Imax = 125 mA; Ci = 8 nF; Li = 1 uH
max = 900 mW.
10.5 SVI-II AP (+) and (-) PV 1-5VDC Terminals
The Process Transmitter and the SVI-II AP PV Input are both barrier protected. The transmitter 4 to 20 mA signal is converted to 1 to 5 Volts at the Transmitter barrier. The 1 to 5 volt signal is monitored by the DCS and used by the SVI-II AP for the embedded process controller. The sense resistor may be in the barrier or in the Digital Control System. The Process Transmitter must be approved for use with the Process Transmitter Barrier. An example of a suitable barrier is MTL 788 or 788R An example of the PV INPUT barrier is MTL 728.
Entity Parameters of the SVI-II AP PV terminals: Vmax = 30 Vdc; Imax = 125 mA; Ci = 1 nF; Li = 0 uH; Pmax = 900 mW
10.6 SVI-II AP (+) and (-) SW Terminals
There are two independent isolated solid state switch contact outputs
on the SVI-II AP. They are labeled SW#1 and SW#2. The switches
are polarity sensitive – that is, conventional current flows INTO the
plus terminal. An examples of suitable barriers are MTL 707, MTL
787 and MTL 787S. Entity parameters are:
Vmax = 30 Vdc Imax = 125 mA Ci = 5 nF Li = 10 uH
Pmax = 900 mW
10.7 SVI-II AP (1) and (2) and (3) REMOTE Terminals
The REMOTE terminals deliver reference Voltage to an optional
remote position sensing potentiometer. Current, Voltage, and Power
are limited by the SVI-II AP.
The REMOTE terminals entity parameters are the parameters of the 4
to 20 mA INPUT barrier.
The SVI-II REMOTE MOUNT is approved for use as a remote position
sensing device with the SVI-II AP.
SVI-II AP Entity parameters are: Uo/Voc = 6.5 Volts Io/Isc = 9.6 mA Ca = 22 uF La = 300 mH Connect only to suitable potentiometer
SVI-II REMOTE MOUNT Entity parameters/Energy Limitation Parameters are:
Ui/Vmax=6.5Volts, Ii/Imax=10.5mA, Ci=0uF, Li=0, Pi=68mW
10.8 Digital In Terminals
The Digital In terminal is suitable for direct connection to a passive
switch.
Entity Parameters are: Uo/Voc = 6.5 Volts Io/Isc = 72 mA Ca = 1.25 uF La = 2 mH
Connect only to passive (Un-powered) switch.
87
Specifications and
Hazardous Location Installation
Page 88
ES-699 Rev U
Page 16 of 17
10.9 Entity Requirement
Cable capacitance and inductance plus the I.S. apparatus unprotected capacitance (Ci) and inductance (Li) must not exceed the allowed capacitance (Ca) and inductance (La) indicated on the associated apparatus. If the optional Hand Held Communicator is used on the Hazardous Area side of the barrier, then the capacity and inductance of the communicator must be added and the communicator must be agency approved for use in the hazardous area. Also, the current output of the Hand Held Communicator must be included in the current output of the associated equipment. The barriers may be active or passive and from any certified manufacturer as long as the barriers comply with the listed entity parameters.
10.10 Use in dust atmosphere
Dust-tight conduit seal must be used when installed in dust hazard environments.
10.11 A device which has previously been installed without an approved IS barrier must NEVER be used subsequently in an intrinsically safe system. Installing the device without a barrier can permanently damage the safety related components in the device making the device unsuitable for use in an intrinsically system.
11
REPAIR
WARNING: EXPLOSION HAZARD – SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN A HAZARDOUS LOCATION.
Only qualified service personnel are permitted to make repairs No part replacement is permitted on the SVI-II REMOTE. On the SVI II AP replacement of the Pneumatic Relay, I/P and Cover (with or without display) are the only field repairs permitted. Replace ONLY with genuine Masoneilan parts. Only parts supplied by Masoneilan are permitted. This includes not only the
major assemblies but also mounting screws and “O” rings. No substitutions with
non-Masoneilan parts are permitted. Detailed replacement procedures are described in the SVI-II AP Quick Start Guide. The following summary assures the safe operation of the SVI-II AP.
11.1 COVER (DISPLAY)
Make sure that: The gasket is seated in the groove in the housing flange. No wires or retaining cable can be trapped under the cover flange. The flange area is not corroded and the surface is not scared. The four cover bolts are securely tightened. Secure the four cover bolts by applying a torque of 55±5 in-lbs.
88
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 89
ES-699 Rev U
Page 17 of 17
11.2 I/P
Make sure that: The wire is not damaged when feeding it through the housing. A single “O” ring is in place on the wire-sleeve and is not damaged. The four retaining screws are snug. Inserting the wire sleeve through the housing does not require force.
11.3 Relay
Make sure that: The five “O” rings are seated in the base of the relay and are not damaged.The three mounting screws are snug.
89
Specifications and
Hazardous Location Installation
Page 90
90
GE Oil & Gas
ValVue SVI II AP Quick Start
Spare Parts
Page 91
91
Specifications and
Spare Parts
Page 92
92
GE Oil & Gas
ValVue SVI II AP Quick Start
Page 93
Relay Spare Part Kit, Standard Construction, High Flow, Single Acting SVI II AP-2
720014541-999-0000
93
Specifications and
Spare Parts
Page 94
DISTRIBUTOR
* Trademark of the General Electric Company. Other company names and product names used in this document are the registered trademarks or trademarks of their respective owners.
© General Electric Company. All rights reserved.
Visit your web-site:
www.fr-eps.com
E.P. & S. - FRANCE
24 bis rue de Picpus 75012 PARIS Tel: +33 (0)9 83 01 21 01 ventes@fr-eps.com
E.P. & S. - CAMEROON
Immeuble Carré d'Or, Rue Njo-Njo Bonapriso, DOUALA Tel: +237 6 52 12 70 95 ventes@fr-eps.com
Loading...