GE STD15C, STD16C Instructions Manual

INSTRUCTIONS
GE
K-45307K
TRANSFORMER
PERCENTAGE
TYPES
DIFFERENTIAL
STD15C
RELAYS
HARMONIC
and
STD16C
WITH
RESTRAINT
GE
Protection
205
Great
Malvern,
and
Valley
19355-1337
PA
Control
Parkway
DESCRIPTION APPLICATION CALCULATION
OF Method Current
Transformer Determination Current
Percent I
II IA hA III
Transformer
Slope
Determination
Percent Repeat
Repeat
Percent
Ratio
-
-
Slope
RATINGS
Models
Auxiliary
12STD15B
Relay
CHARACTERISTICS
and
Pickup
Overcurrent
Percentage
Harmonic
Operating
Unit
Differential
Restraint BURDENS CONSTRUCTION
Current
Transformers Through—Current Differential-Current Overcurrent
Operating
Main
Seal-in
Target
and
Case RECEIVING, ACCEPTANCE
Visual
Mechanical
Electrical
Test
INSTALLATION
HANDLING TESTS
Inspection
Inspection
Tests
Equipment
PROCEDURE
Tests
Pickup
Harmonic
Current
Through-Current
Instantaneous
Main
Dropout
of
Location
Mounting
Connections
ADJUSTMENTS
Plug
Tap
Percent
Positioning
Slope
OPERATION
Targets Disabling
of
MAINTENANCE
Contact
PERIODIC
Cleaning
TESTS
Pickup
Harmonic
Current
Through-Current
SERVICING RENEWAL
PARTS
SETTINGS
CT
of Setting
of
Error
Turns
CT
Percent
Setting
and
Control
Pickup
Restraint
Unit
Unit
AND
Restraint
Restraint
Overcurrent
Unit
Setting
STD
Type
Restraint
Restraint
GEK-45307
Connections
CT
and Ratio
and Error
Turns
Relay
Error
Turns Ratio
12STD16B
Circuit
Time
Characteristics
Characteristics
Circuit
Circuit
Unit
STORAGE
Unit
Relay
Type
and
Tap
2
STD
STD
Relay
Relay
Setting
Tap
Tap
Setting
Setting
3 3 5 5 5 5
6
8
8 9
9 10 10
10 10 11 ii 11
11
12
12 13 14 14 14
15 15 16
16
16 17 17 17
17
17
18
18 18 19 19 20
21
21
21 21 21
21
21
23
23
23
23
23 23
24
24 24
25 25
26
GEK-45
307
Relays features small
telephone-type
Percentage faults
the
by internal
Each
Type
used
for
current The
Type
three
has It
may
three the
circuits
weakest,
the
of
of
percentage
restraint
at
high
difference
fault,
STD
the
restraint
STD16C
through-current
also
be
needs
STD
current,
and
relay
protection
circuits
relay
used
require
WITH
type
and
relay
permits
while
in
waveform,
that
of
is
a
single-phase
is
for
four-circuit
through-current
no
through-current
TRANSFORMER
PERCENTAGE
STD15C
INTRODUCTION
transformer
are
harmonic
provides
that
accurate
harmonic
between
transformer
DES
of
two-winding
and
one
differential—current
designed
for
restraint
DIFFERENTIAL
AND
HARMONIC
and
STD16C
differential
restraint.
the
contact
discrimination
restraint
the
magnetizing
CR1
PTI
ON
unit.
The
power
use
with
circuits
and
transformer
restraint,
restraint.
RELAYS
RESTRAINT
relays
static
A
output.
between
enables
differential
inrush.
Type
STD15C
transformers
circuit.
three—winding
one
differential—current
protection
while
the
decision
the
current
relay
power
(see
provided
internal relay
and
Figure
fourth
unit
and
distinguish,
to
caused
is
designed
has
two
transformers
1)
circuit,
with
controls
external
through-
circuit.
when
by
to
only
being
the
a
an
be
and
The
current maximum transformer transformer selected
The
1.
the be available to
Since
increasing as accuracy
sensitivity
ratios
with
lower sensitivity.
compatible
increase
the
result
a
These
every
possible further the
purchaser’s
the
To
but
such
no
transformer
(CT),
the
following
the
relay
with
of
increasing
the
relay
the
of
of
the
1nstrucron5
ctingency
nforma
ton
purposes,
extent
required
assurance
without
or
the
in
the
However,
CT
ratio
burden
CT
ratio
reducing
CTs.
do
not
to
desi red
be
the
given
is
ratios
tap
some
purport
be
or
matter
the
with
risking
possibility
various
points
and
of
either
in
is
tends
the
met
in
should
should
products
respect
APPLICATION
and
in
the
the
lowest
the
the
preference
likely
to
maximum
to
cover
connection
parti
cular
be
described
to
relay
thermal
windings
mind:
lower
following
CT
to
improve
secondary
details
i.11
with
probleme
referred
herein
local
codes
3
taps
of
the
CT
ratio
to
be
installation,
to
meet
ratio
the
or
arise
the
and
should
overload
misoperation.
of
the
CT
ratio
and restrictions. or
the
relay
small the
compared
relative
fault
variations
General
applicable
ordinances
which
in
operation
are
Electric
ANSI,
because
be
of
power
selected,
the
relay
tap.
current
equipaent
not
Company.
selected
the
Therefore,
transformer
lowest
Where
tap,
to
performance
nez
IlntnCe.
or covered
ziWficiently
IEt
andN
varç
they
relay
the
relay
the
and
e
greatly.
to
higher
it
increasing
provide
Should
standards,
tap
a
is
lead
of
for
for
obtain
or
should
choice
desirable
the
current current
will may
burden,
CT5,
the
be
be
not
is
the
GEK—45307
2.
3.
4.
5.
6.
7.
CT
The
CT
The
should
The
the
The cooled
inrush under
secondary
secondary
relay
not
CT
ratios
relay
relay
basis)
night
consideration
manufacturer
is
the
rating
inrush
The times
characteristics
current
rated current. less
than
sufficient
be
The
CT external exactly provided
within
it
is
5%.
obvious changing of
the
relied
when
upon
the
winding.
current
exceed
under
current
If
times
8
ratios
faults.
selection
by
the
on
When
range.
range
to
load-ratio
current
twice
should
maximum
corresponding
should
operate
should
of
self-cooled
a
transformer
relay
the
tap
current
tap
to
cause
should
Since
relay
the
that
a
In
and
the
prevent
should
corresponding
tap
value,
high
be
enough
internal
not
exceed
the
instantaneous
does
be
not
consulted
transformer
as
the
transformer
tap
chosen
current,
transformers
it
current
means
the
restraint
selected
is
rarely
value,
false
be
of
by
protected
close
this
match
case,
percentage_differential
relay
control
is
operation at
not
exceed
to which
that
fault
to
rated the
have
for
must
with
harmonic
to
transformer
of
which
transformer
cannot
the
secondary
the
ends
the continuous
maximum
is
the
conditions
kVA
relay
overcurrent
self—cooled
a
the
“equivalent
that
being
be
error
an
produce
content
on
internal
provide
possible
the
be
obtained
on
of
kVA
the
thermal
secondary
of
tap
considered.
able
an
to
ratios,
currents
is
equipped
currents
characteristic
the
the
(on
(refer
the
power
value
unit).
would
to
of
less error of faults.
balanced
match
at
unbalanced
range.
thermal
forced-cooled
a
rating
of
currents
to
RATINGS).
transformer
selected
If
rating, self—cooled have
the
supply
than
of
the
the
20%
greater
secondary
secondary
secondary
the
ratio—matching
may
usually
with
all
are
load-ratio
points
matched
current
the
will
the
the
same
of
rating
relay.
not
(on
(magnetizing
transformer transformer
rating”;
magnetizing
relay
the
of
than current
current
currents
taps
be
matched control
of
the
the
at
the
relay
which
of
the
basis)
damage
self-
that
with
total
20%
may
are
ratio­middle
flows
8
at
on
is
In
8. voltage
for selected load current. voltage) restraint
It
is
not
differential
In
addition,
false
operation “sympathetic tend
to
harmonics Typical
and
3.
some
applications,
or
example
so
current
desirable
protection,
if
inrush”
flow
between
in
the
elementary
low
in
that
It
is
breakers
on
heavy
the
on
relay
diagrams
voltage
ring—bus
a
the
flowing
recommended
be
through-fault
to
since
banks
magnetizing
into
the
banks,
current
the
system
secondary
around
connected
protect
can
the
for
power
through
arrangement.
the
that
two
the
sensitivity
be
switched
inrush
bank
already
with
to
restrain
the
STD15C
transformer
windings
ring
CTs
to
a
current
parallel
the
possibility
4
four
in
on
each
separate
flowing
separately,
to
energized.
the
and
breakers
this
In
will
addition
of
transformer
of
the
one
relay.
STD16C
will
be (as
case,
not
be
the
restraining
around
protection
there
transformer
In
that
there
are
connected
shown the
thermally
to
the
two low
the
ring
banks
is
this
case,
will
illustrated
in
ratios
CT
overloaded transformer voltage
winding
bus.
with
would
possibility
a
bank,
the
be
to
the
Figure
must
(or
to
one
set
reduced.
be
causing
harmonics
insufficient
in
Figures
high
1)
load high
assure
as be
on
of
of
a
2
GEK—45307
METHOD
The
calculations
below.
CURRENT
sample
A
TRANSFORMER
Power
DETERMINATION
Determine
1. transformer
transformer.
Max.
required
calculation,
CONNECTIONS
Transformer
Delta-Wye
Wye-Del
Delta-Delta
Wye-Wye
Delta-Zigzag shift
between
secondary
CT
the
TURNS
maximum
OF
winding
Maximum
-
CALCULATION
for
determining
for
Connections
the
OF
the proper
transformer
SETTINGS
shown
Current
relay
Figure
in
Transformer
and
taps
CT
4,
Connections
outlined
are
is
then
given.
Wye-Delta Del
ta
ta-Wye Wye—Wye Delta-Delta
with
primary
TYPE
AND
line currents
may
carry
Transformer
(Line
phase
O
and
STD
RELAY
the
TAP
(Max.
maximum
SETTING
I)
forced—cooled
kVA
kV)
Delta—Delta
on
the
basis
rated
that
each
kVA
of
power
the
2.
3.
Determine power
transformer
transformer,
100%
Actually, carry of
these
calculating
voltage so
that
Select not
CT
exceed transformer selected current
be
3
times
properly
can than
For
the
full—load
or
the
100%
‘P
-
this calculation
maximum
the
ratings.
the
relay
in
ratios
the
so
either
is
that
so CT connected
the
matched
lowest
Wye-connected
Tap
Current
winding
“equivalent”
Transformer
(Line
load
currents
This
will
not
that
secondary
CT
breaker.
current).
CTs
=
rated
may
currents
is
the
operate
the
to
thermal
by
means
100%
line
carry
self-cooled
kVA
kV)
does
in requirement
secondary
thermal
ring
a
rating
Also,
I
currents
the
not
mean
continuously.
the
other
for
any
current
rating
bus,
will
select
of
the
relay
(100%
full
ratings.
that
windings
for
external
(5
for
not
CT
ratios
I)
self-cooled
windings
all
This
selecting
fault.
corresponding
amperes).
example,
exceeded
be
so
taps.
(Highest
on
is
in
the
that
the
rated
only
proportion
relay
the
to
In
CT
by
the
basis
will
a
convenient
maximum
the
ratio
the
relay
current
that
kVA
necessarily
to
tap
case
where
should
maximum
currents not
each
of
their
setting
does
Ip
load
more
the
way
a
be
5
For
Delta-connected
GEK-45307
CTs
4.
5.
Current
Tap where
Check as
low
the
as
Calculate determine differences of
mismatch.
three-winding
For
for
all
combinations
If
taps
limits,
lines,
Check relay amperes the
cannot
it
to
to
for
RMS
relay
accommodated
(Amperes)?
N
is
matching
possible.
the
percentage
ratio
the
between
The
will
obtain
see
that
fault
a
for
can
be
in
=
the
number
of
of
these
mismatch
transformers,
of
be
selected
necessary
be
a
better
the
the
at second.
1
definitely
accordance
seconds
x
LnL
N
relay
of
the
currents
match
sum
of
CT
currents
mismatch
two
relay
ratios,
normally
to
to
of
the
terminals
If
the
limited
with
48,400
secondary
divided
should
the
percent of
or
taps.
keep
choose
between
relay
period
to
the
relation:
to
as
currents
this
relay
of
the
a
turns.
relay
follows:
by not
percentage
different
a
currents
power
during
shorter
taps,
and
the
exceed
mismatch
currents
which
time,
to
keep
two—winding
on
the
tap
smaller
5%.
error
error
CT
and
will
that
transformer
a
a
values
ratio,
ratio
relay
fault
higher
the
should
within
be
is
current
mismatch
transformers,
selected.
the
is
be
one
on
taps.
applied
less
current
error
percent
checked
allowable
or
more
to
than
flows
can
The
the 220
in
be
Also external
CURRENT
CT
The
is tap figure
The
ratio
based
rating.
must
calculations performance transformer the
protected
Determine
1.
a.
b.
check
that
fault
TRANSFORMER
on
error
the
If
be
must
instantaneous
the
reduced,
listed
is
concerned,
winding,
transformer.
the
burden
For
Wye-connected
=
For
Delta-connected
=
2B
Z
the
do
not
RATIO
ERROR
be
instantaneous
as
below
which
with
none
on
+
Ne+2f
+
Ne
1000
of
suni exceed
less
unit
described
of
each
CTs
+
CTs
+
2f
+
than
are
is
2R
2R
the
150.
being
the
CT,
20%
unit
in
for
an
using
Ohms
Ohms
multiples
at
set
pickup
the
the internal fault
times
8
at
its is
CHARACTERISTICS
worst—fault
ground
current
the
following
of
tap
relay
normal
raised
supplied
current
rated
setting,
above
section.
condition,
fault
expressions:
this
between
through
on
tap
an
current.
which
value,
as
the
the
(Equation
(Equation
internal
is
far
and
CT
neutral
8 the
This
times
as
1)
2)
or
20%
CT
the
of
6
GEK-45307
where
STD
B
N e
f
R
TAPS
2.9
3.2
3.5
3.8
4.2
4.6
5.0
8.7
STD
=
number
bushing
busing
one-way
AMPS
relay
of
total
turns
CT
tempera
CT
ture) resistance
temperature)
control
temperature)
Total
X
8
burden
in
resistance
cable
Burden
TAP
AMPS
23.2
25.6
28.0
30.4
33.6
36.8
40.0
69.6
(see
bushing
per
per
lead
TABLE
for
Table
CT
turn,
lead,
resistance
I
60
Cycle
BURDEN
I)
milliohms
milliohms
Relays
OHMS
0.180
0.156
0.140
0.120
0.112
0.096
0.088
0.048
(at
(B)
(at
maximum
maximum
(at
maximum
MIN
expected
expected
expected
P.U.
0.87
0.96
1.05
1.14
1.26
1.38
1.50
2.61
AMPS
2.
3.
4.
5.
Determine
(Note: current relay CTs
Determine
Esec
From
excitation
determine
Esec. Determine
%
should
This necessary calculations error.
CT
=
8
are secondary
=
excitation
the
error
to
secondary
x
STD
For is
current
connected
IZ
curve
percent
1
E
=
Is
not
exceed choose on
selection
relay
the
supplied
are
CT
of
current
error
100
X
a
higher
current
tap
location
by
the
in
voltage
particular
20%
of
same,
wye
in
of
for
rating
of
one
CT,
or
required
corresponding
IE.
each
any
tap
on
relay
times
8
fault
so regardless delta.)
tap
by
CT
of
set
that
taps,
tap
assumed, that
at
8
of
current
the
CTs. set
of
mismatch
setting.
all
current
CT of
whether
times
tap
transformer
this
to
expression:
it
If
CTs,
error,
the
and the
setting.
secondary
does, and
fault
it
repeat
and
being
will
the
percent
used,
voltage,
be
ratio
7
GE:K-45307
PERCENT The
proper
a.
The
tap
The
b.
Set
the
The
percentage total total
20%, If
should
error
error
but
the
be
EXAMPLE
I.
Determination
1.
2.
3.
4.
5.
6.
7.
8.
SLOPE
percent
maximum
changing maximum
desired
not
movable
chosen
(REFER
Transformer Maximum 100% Assume Maximum 100% CT Relay
SETTING
range
means,
percent
percent
slope current current
the
35%,
lead
about
TO
FIGURE
I
=
Ip
CT
I
secondary
I
connections
Current
slope
of
setting
the
to
does
40%
is
used
twice
of
CT
and
=
3750/
3000/
turns
secondary
required
manual
in
of
slope
smaller
not
setting
4) Turns
Line
J
(N)
for
taps
percent.
mismatch
by
means
selected
exceed
in
(as
as
high,
and
(Line
J3
(Line
(less
I
100%
is
determined
of
of
20%,
is
used.
Figure
since
STD
kV)
kV)
than
Sec.
and
the
of
should the
the
Relay
5a)
by
the
load—ratio-control,
relay
R3
through
1,
the
(See
be
25%
for
Tap
taps.
Figure
greater
currents.
setting
example)
movable
Settings
the
sum
than
lead
A
19.7
15.7
20
0.98
0.79
Delta
1.37
6A).
is
of:
the In
used.
the
provides
B
49.5
39.6 20
Wye
ratio
general,
percent
2.47
1.98
1.98
or
If
automatic
of
maximum
if
it
exceeds
slope
no
restraint.
C
157
125
60
2.62
2.08
Delta
3.60
the
setting
10.
11.
9.
Select
currents
If
any
chosen
Ideal
Try
Relay
Check Ratio
1.98
-
1.37 Mismatch
Ratio
Mismatch
a
relay
in
current
for
it,
Relay
Taps
Mismatch of
Taps
1.44
1.44
of
Taps
1.89
other
Taps
on
-
on
-
1
tap
lines
is
and
(Set
Error
Lines
43
LinesC-B
1.82
8
for
greater new
C
=
=
one
would
ideal
B-A
0.7%
-!.j-
3.8%
8.7)
than
relay
of
the
line
be
if
they
times
V3
taps
=
1.43
1.89
Ratio
=
calculated
Ratio
currents
were
any
3.31
3.2
of
of
Sec.
increased
other,
Sec.
Line
and
for
4.78
Lines
the
the
4.6
Currents
calculate
in
the
8.7 other
Currents
tap
8.7
8.7
same
should
lines.
what
=
the
ratio.
be
1.82
8
GE
K—45
307
II.
12.
Percent ASSUME
1.
Ratio
Mismatch
(All
Check
second,
1
Ratio
(all One-way Bushing
Bushing
II
Burdens
Line
a.
b.
Line
c.
Line
of
Taps
2.72
are
that
and
Error
measured
CONTROL A
CT
B
C A
CT
B
on
A,
3,
C,
on
-2.63
less
the
sum
therefore,
resistance
resistance
II
CTs,
Z
=
=
Z=0.096
=
Z
Lines
than
of the
their
at
CABLE
Ii
using
(0.156)
2
0.312
0.096
2
(0.048)
C-A
=
5%;
therefore
1
maximum
short-time
maximum
RESISTANCE
per
turn
II
II
II
per
lead
II
II
II
II
Equation
+
0.205
+
(20x2.5)
+
0.138
+
+
1
(20x4)
+
+
(60
2.72
relay
rating
expected (R) Ce) (e) Ce) (f) (f)=525 (f)
or
Equation
+
0.568
+
1000
0.568 x
2.3)+(2
Ratio
mismatch
=
0.284
=
4
2.5
=
2.3
=
75
=
18.6
(2.0 1000
=
(2.0
of
Sec.Line
currents
of
relay
temperatures)
ohms
rnilliohms
niilliohms
2
from
x
75)
1.085 x
52.5)
0.80 x
18.6)
error
is
+
page
2
+
is
less
is
(.284)
0.568
+
Currents
not
than
not
exceeded.
6.
0.568
excessive)
220
=
amps
2.63
for
2.
3.
4.
5.
6.
IA-Repeat
1.
2.
3.
4.
5.
6.
7.
Impedance,
times
8
E
5
CT required,
JE
%
Ratio
Exciting improve
CT
tap,
voltage
Error
current
CT
Turns
ohms
performance.
100% Try also
turns
CT
for proper 100%1secondary Relay Ideal Use
Mismatch
Current
Relay
Relay
Taps
Taps
Error is
=
0.096
amperes
require
from
excitation
on
Relay
and
(necessary
matching)
(Set
less
line
C
+
(IZ)
Tap
than
0.180
to
B
Setting
change
8.7)
5%
curve
is
+
too
9
0.568
C
high;
0.833 A
T.o85
25.6
27.8 1
.00
3.4%
should
15.7 20
0.79 0.99
1.37
4.40
4.6
B
0.8
36.8
29.4 50
136% try
39.6
40
0.99
3.19
3.2
higher
C
0.833
69.6
58.0
0.5
0.8%
125
80
tap
1.56
2.70
8.7
8.7
on
CT
to
GEK-45307
Repeat
hA
1.
2.
3.
4.
5.
5. Percent
III
Percent
1.
2.
MODELS
-
Percent
Burden
Line
Line
Line
Impedance
times
8
required,
‘C
of
%
error
Slope
Assume
Relay
12STD15C
on
A,
B,
C,
CT
Ratio
load
tap
AND
Ratio
CTs
Z
=
0.192
0.156
Z 7
=
0.096
Ohms
Tap,
voltage
Error
is
less
Setting
ratio
mismatch,
12STD16C
Error
+
+ +
Amperes
required
from
excitation
than
control
0.205
0.188
0.226
20%,
from
Use
+
0.568
+
0.568
+
0.568
(17)
curve
so
maximum
IA
above
setting
25%
RATI
CT
= =
=
taps
range
(Lines
NGS
0.965
0.912
0.890
and
36.8
35.6
relay
A-B)
0.965
1.1
3.1%
taps
0.912
25.6
23.4
0.25
1.0%
are
0.890
69.6
61.9
0.17
0.3%
satisfactory.
10.0%
4.6%
14.6%
Continuous
The
through-current twice all
tap
but current transformer.
Short
220
Time
amperes
relay.
with
the
where
Short
For relay
Time
both
from
multiples
limitation current through
i
peda
in
n
one
(equal
Higher
following
=
=
=
t
the
restraint circuit
ce.
Rating
value
of
Rating
for
48,400 current
time
(Electrical
STD15C
the
should
is
a
for
the to
(Thermal)
second,
1
currents
equation:
amperes
in
seconds.
several
be
result
circuit.
breakers
transformer
any
combination
restraint
twice
may
and
STD16C
sets
calculated
of
52—1
tap
measured
be
of
on
the
Note
and
and
of
windings
value)
in
applied
the
sum
current
the
voltage
that
52—2
differential-current
taps,
carry
or
they
0
flows
the
primary
for
shorter
of
the
multiples
transformers
basis
in
rating
Figure
of
RMS
of
without
will
current,
through
of
any
lengths
should symmetrical the
external
1
being
transformer
stand
and
the
transformer
of
of
tap
not
rectifiers
fault
limited
will
twice
the
full
tap
value
restraint
differential—current
the
time
current
exceed
fault
by
of
in
current.
in
current
the
type
accordance
fed
150.
the
through—
can
transformer
stand
to
These
if
STD
the
This
flow
GEK—45
307
DC
Resistance Carry Carry Carry
AUXILIARY
STD15C
The
and
110 links
220
located
voltages.
STD
The circuit. exceeding tripping relay. relays breaker
After
(STD
or
normally
Continuously
Amps
30
Amps
10
RELAY
and
DC
relay
The
volts.
250
current
the
and
by
other
used.
for for
CONTROL
STD16C
control
on
the
is
CIRCUIT
relays
voltage,
front
provided
current—closing
If
exceeds
breaker
auxiliary)
automatic
more
30
trips,
TARGET
2.0
0.13
0.5 30
are
depending
of
with
rating
than
amperes,
de-energized
be
provisions.
AND
Amp
Ohms
Amps Secs. Secs
available
the
relay
two
one
it
is
TABLE
SEAL-IN
Tap
upon
open
of
the
circuit
an
auxiliary
necessary
II
for
the
enables
contacts
contact
by
A
manual
UNIT
0.6
0.6
1.5
0.5 4
use
relay
breaker
relay
that
an
auxiliary
Amp Ohms
Amps Secs. Secs.
with
the
connected
is
the
reset
Tap
4S, model. selection
30
is
to
must
tripping
relay
125,
to
amps
be
be
switch
0.2 7
0.25
0.2
and
250
plate
A
of
common
a
for
tripped,
used
circuit
on
is
recommended
Amp
ohms
Amps
Secs.
with
one
voltages
or
with
the
DC
of
of
Tap
or
small these
output
if
the
these
circuit
48,
not the
STD
and
PICKUP
The slopes The
indicates
AND
operating
shows
percentage
OPERATING
an approximately operating
current
milliseconds. Curves
shown time
OVERCURRENT
The transformer flowing
of
the
in
Figure
includes
overcurrent
in
that
When
only
UNIT
ampere-turns
ampere
the
AC current component
characteristic
the
percent
slope
approximate
30%
operating
5,
auxiliary
PICKUP
tap.
one
tap,
40
component
transformer
present.
of
is
plotted
unit
CT
amperes
TIME
is
tap
reduced
unit
is
For
supplies
of
is
slope
a
figure
slope
value
time
against
operating
adjusted
are
8
example:
are
current
in
the
CHARACTERISTI
shown
versus
given characteristic. (see
to
zero
of
the
differential
times
the
current,
required
transformer
relay
in
Figure
the
throughcurrent
Table
from
main
time.
to
pick
ampere
and
for
produces
to
any
unit
pickup.
Cs
7.
a
III).
value
up
turns
the
output
only
The
particular
Pickup
above
and
of
current.
when
produced
tap
This
only,
half
a
curve
The
plug
flowing
slope
dropout pickup,
the
The
the
for
pickup
since
cycle
various
for
in
the
tap
zero
at
time,
is
instantaneous
main
differential
rated
by
the
CT
value
the
of
any
percentage
transformer.
setting,
restraint
less
unit
operating
tap
is
is
differential
DC
when
than
unit
current current
in
based
(offset)
the
and
is
the
25
are
5
on
11
GEK—45
307
If
tap
ratio
matching
rating
magnetizing
that
it
is
unit
the
recommended
increasing
raised,
the
following
E
where
=
E P
=
PERCENTAGE
The
percentage restraint differential
restraining currents. be
unbalanced
(as
shown
on
through-fault
transformers
currents
become operation currents,
as Settings.
taps
on
a
self-cooled
inrush.
may
pick that
the
pickup
requirements
equation: 20
-
(2.5)
CT
error
Pickup
current
of
overcurrent
DIFFERENTIAL
differential
circuits.
current
circuit
the
in
For
by
Figure
a
relay
certain
currents.
and
cause
unbalanced.
by
the
unbalanced
previously
chosen
are
If
of
up, the
on
CT
especially CT
the
currents
overcurrent
CT
(P-8)
in
percent,
CHARACTERISTICS
In
addition
of
that
the
to
line
is
operate,
minimum
7).
This
their
characteristic ratios
currents
described
that
so
basis,
are
ratio
error
or
will
at
multiples
in
characteristics
to
the
current
indirectly
the
percentage,
High
currents
to
Percentage
caused
under
rated
the
overcurrent
greater
small
on
relay
unit.
be
more
pickup
of
operating
transformers,
energized
current
is
change,
restraint
by
Determination
CT
current
than
transformer
tap
setting
If
stringent,
of
the
tap
setting.
are
circuit,
transformer
determined
necessary
saturate
with
imperfect
unit
tap
the
overcurrent
overcurrent
provided
the
by
the
the
is
of
is
rating,
banks.
be
increased,
in
which
relay
the
secondary
by
the
to
prevent cores
result
also
matching
Turns
CT
not
greater
will
not
there
If
setting
accordance
unit
by
through—current
is
energized
is
equipped
transformer
relay
false
of
that
required
of
and
pick
this
rather
currents slope
the
the
to
the
STD
than
up
is
danger
happens,
must
with
by
with
secondary
must
setting
operation
current
secondary
prevent
secondary
Relay
the
on
than
be
the
the
a
Tap
HARMONIC
At
that
time
the
establishes
inrush,
This cause
Power
causes
false
system component. constant cycle
at
Transformer
exciting magnitude, full-load
of-circuit of
sharply practically illustrated
RESTRAINT
power
a
the
and
in
the
an
unbalance
operation
fault
The
sine
circuit
which
fault
magnetizing-inrush
impedance
occasionally
current
closure
peaked
no
current
in
Figure
CHARACTERISTICS
transformer
required
primary
flux
winding
current
if
means
currents
waveform
impedance.
occurs,
were
are
results
The
and
resulting
having
for
worst
the
on
half-cycle
voltage
during
conditions
loops
the
8.
is
of
DC
upon
currents from
RMS
an
wave.
opposite
energized,
in
the
flows
to
flow
not
a
nearly
from
component
circuit
core
value
of
of
core.
only
in
provided
pure
sinusoidal
vary
saturation.
power
They
current
half
current
This
through
the
to
sine
depends
impedance
according
with
100%
transformer
have
on
cycles.
current
differential
prevent
waveform,
voltage
magnitude
offset,
a
very
one
is
the
it.
on
to
They
distorted
side
The
supplied
is
current
generation
the
the
approaching
residual
of
two
called
relay,
plus
time
and
extremely
are
waveform
the
current
to
the
magnetizing
transformers.
which
DC
a
and
in
the
angle.
often
flux
and
zero
axis, waves
primary
would
transient
nearly
voltage
variable of
times
16
point-
made
high
up and are
12
GEK—45307
current
Any of one
DC
a
of
component
the
frequencies
relative
magnitudes fundamental fault-current
while
The
afford
wave.
the
high
an
In
fundamental
are
passed component the
magnetizing-inrush— auxiliary slight
waves
momentary in
predetermined
wave),
this
Burdens
and
value
are
substantially
power
100%
5.0
amperes.
distorted,
of
plus
fundamental
which
are
and
determine
wave
typical
is
magnetizing-inrush—current
percentage
excellent
the
means
Type
component
through
is
passed
the
through
differential-current
restraining
which
the
value,
is
restrained
(e.g.
magnetizing-inrush—current
shown
in
independent
factor.
Figures
system
2,
the
found
of
STD by
ratio
for
Table
a
phase
harmonic
suitable
restraining
and
nonsinusoidal
number
of
frequency,
3,
4,
5,
positions
waveform.
to
contain
currents
of
distinguishing
relays,
the
electric
the
operating
offset-fault—current
transformer
effect.
of
harmonics
which
on
of
the
differential—current
III
and IV.
the
percent
given
are
waveform
sine-wave
and
etc.,
of
When
only
harmonic
circuit
circuit.
Relay
relay
BURDENS
slope
burdens
the
times
the analyzed a
wave in
it
filters.
of
inside
operation
to is
set
wave).
Burdens
imposed
may
components
others,
harmonics
very
contains
the
electrically
components
the
waves
fundamental
waves
settings,
considered
be
of
called
the
fundamental
with
in
this
small
percentage
considerable
a
magnetizing-inrush—current
from
are
The
harmonic
The
the
relay,
DC
relay,
occurs
component
is
largely
on
while
is
(e.g.
and
internal
an
in
which
minimum
and
each
on
as
being
different
“harmonics,”
frequency.
reference
manner,
of
fault-current
the
separated
current
the
present
blocked
and
produces
differential-current
lower
than
fault—current
the
ratio
pickup
all
are
current
approximately
transformer
composed
frequencies;
having
to
typical
the
harmonics,
amount.
from
components
fundamental
in
by only
given
a
exceeds
values
The the
wave
the
both
the
a
are
at
TA
SETTIN
G
AMPS
2.9
3.2
3.5
3.8
4.2
4.6
5.0
8.7
*
Burden
Burden
RATED MILLIANPS
of
of
50-cycle
VOLTS
ZERO
RESTRAINT
PICKUP
AMPS
0.87
0.96
1.05
1.14
1.26
1.38
1.50
2.61 operating
relay
48
140
coil
is
DC
125 105
TABLE
OPERATING
CYCLE
60
BURDEN
VA
3.2
2.7
2.4
2.0
1.9
1.6
1.5
0.7 under
is
0
the
same
TABLE
CONTROL
III
CIRCUIT
RELAYS
IMPEDANCE
OHMS
0.128
0.108
0.096
0.080
0.076
0.064
0.060
0.028
normal
or
slightly
IV
CIRCUIT 250
88
13
*
conditions.
lower.
BURDEN
48
140
RESTRAINT
CYCLE
60
BURDEN
VA
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.5
110
96
CIRCUIT
RELAYS
IMPEDANCE
OHMS
0.052
0.048
0.044
0.040
0.036
0.032
0.028
0.020
220
80
Figure Refer
identify
6
also
shows
the
to
parts
the
the
internal
internal
more
arrangement
connection
completely.
GEK—45307
CONSTRUCTION
the
of
diagrams,
components
Figures
10
of
and
the
STD15C
11,
which
relay.
will
CURRENT
In
one
and
In each
windings
In
brought
The block
TRANSFORMERS
Type
the
each
for
winding
Type
the
with
No.
both
relays
out
primary
arrangement. (depending through-current
connected
is
inserting
When
the between the
marked
the
fourth
terminals
terminal
winding
transformer
under
the
lead.
STD15C
relay,
line-current-transformer
No.2terminates
one No.
relay,
primary
2
STD16C
only
I,
there
stud
to
circuit
5.
of
Two
whether
on
transformer
end
a
relay
6
and
corresponding
in
CT
and
to
tap
plugs
STD16C
circuit
6
1),
the
STD
that
tap
in
screw
the
at
there
No.
and
is
differential—current
a
each
of
or
relay
the
winding.
tap
the
used
is
is
connected at
7
reconnected
which
relay.
gives
through-current
4.
stud
are
winding,
corresponding
3
these
three
transformers
horizontal
is
tap
blocks.
on
four-circuit
to
rear
the
to
connects
terminal
The
the
best
circuit.
three
and
Type
a
tap
A
of
stud
of
the
it
current
transformer
Winding
separate
each
to
rows
STD15C
the
on
the
through—current
applications,
7,
relay
the
upper
row
directly
on
match
has
No.
through—current
terminating
4
studs
6,
transformer
is
completed
of
tap
STD16C),
or
differential—current
jumper
the
and
to
for
the
should
tap
the
the
the
cradle
in
movable
primary
two
terminates
1
at
a
with
in
3
one
and
through
positions
one
restraint
shown
as
normally
be
block
differential-current
lead
should
current
windings,
at
transformers,
separate
order.
that
primary
special
a
provided
are
for
row
transformer
windings
in
Figure
connected
disconnected
(above
be
the
in
stud
stud,
lead
tap
each
the
row
placed
movable
6
by
1, at
matching
are
moved
the
from
differential—current
restraint
recognized
but
quantity
RESTRAINT
bridge
rectifier
transformer.
in
so one
windings
producing
of
parallel.
connections
both
on
transformer
permit
is
The The
tap
taps current
taps
tap
plug
through-current
should
It current current energy,
be transformer transformer,
this
THROUGH-CURRENT
wave
full
A current units
restraint
are
connected
of
arranged
position
remains
that
also
restraint
CIRCUIT
unequal
are
constant.
pickup
through
some
receives
In
line—current
in
that
another
to
transformer
simultaneously
current
one
restraint.
so
small
is
the
STD16C
the
total
The
14
matching
of
output
output
flows
the
that
relay,
transformer
the
in
horizontal
a
winding
selected
not
primary
However,
it
may
the
of
is
secondary
only
windings
compared
be
secondary
the
directed
and
so
assumed
DC
secondary
row,
one
that
through
outputs
to
currents,
corresponding
of
the
differential-
the
of
the
to
to
of
each
of
the
percent
the
be
currents.
when
through—
percent
through-
operating
zero.
through
three
all
slope
a
Loading...
+ 30 hidden pages