GE StationPortal User Manual

Page 1
GE
Intelligent Platforms
Production Support Device
StationPortal*
IC760STA100
Hardware User’s Guide, GFK-2522A
February 2010
Page 2
GFL-002
Warnings, Cautions, and Notes
as Used in this Publication
Warning
Warning notices are used in this publication to emphasize that hazardous voltages, currents, temperatures, or other conditions that could cause personal injury exist in this equipment or may be associated with its use.
In situations where inattention could cause either personal injury or damage to equipment, a Warning notice is used.
Caution
Caution notices are used where equipment might be damaged if care is not taken.
Note: Notes merely call attention to information that is especially significant to understanding and
operating the equipment.
This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware or software, nor to provide for every possible contingency in connection with installation, operation, or maintenance. Features may be described herein which are not present in all hardware and software systems. GE Intelligent Platforms assumes no obligation of notice to holders of this document with respect to changes subsequently made.
GE Intelligent Platforms makes no representation or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability or fitness for purpose shall apply.
* indicates a trademark of GE Intelligent Platforms, Inc. and/or its affiliates. All other trademarks are the
property of their respective owners.
©Copyright 2010 GE Intelligent Platforms, Inc.
All Rights Reserved
Page 3
Notices
GE Intelligent Platforms reserves the right to make improvements to the products described in this publication at any time and without notice.
StationPortal is the trademark of GE Intelligent Platforms in the United States and other countries. Any other trademarks referenced herein are the property of their respective owners and used solely for purposes of identifying compatibility with the products of GE Intelligent Platforms. The uIP TCP/IP stack from Adam Dunkels <adam@dunkels.com>
The FCC requires the following note to be published according to FCC guidelines:
U.S., Canadian, Australian, and European regulations are intended to prevent equipment from interfering with approved transmissions or with the operation of other equipment through the AC power source.
The StationPortal product has been tested and found to meet or exceed the requirements of U.S. (47 CFR 15), Canadian (ICES-003), Australian (AS/NZS 3548), and European (EN55022) regulations for Class A digital devices when installed in accordance with the guidelines noted in this manual. These various regulations share commonality in content and test levels with that of CISPR 22 and based on this commonality testing to the each individual standard was deemed inappropriate.
is used in the StationPortal design under license
The FCC requires the following note to be published according to FCC guidelines:
Note: This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Industry Canada requires the following note to be published:
Note: This Class A digital apparatus complies with Canadian ICES-003.
Users must supply 100-240V, 50-60 Hz AC input power supply to power the StationPortal un i t covered by this manual.
This symbol is present on the enclosure where there is a risk of electric shock due to Hazardous voltage present at that point.
For a complete list of agency approvals, please refer to “Agency Approvals” on page
21.
Page 4
Contact Information
If you purchased this product through an Authorized Channel Partner, please contact the seller directly.
General Contact Information
Online technical support and GlobalCare
Additional information http://www.ge-ip.com/ Solution Provider solutionprovider.ip@ge.com
Technical Support
If you have technical problems that cannot be resolved with the information in this guide, please contact us by telephone or email, or on the web at
Americas
Online Technical Support Phone 1-800-433-2682 International Americas Direct Dial 1-780-420-2010 (if toll free 800 option is unavailable) Technical Support Email support.ip@ge.com Customer Care Email customercare.ip@ge.com Primary language of support English
Europe, the Middle East, and Africa
Online Technical Support Phone +800-1-433-2682
http://www.ge-ip.com/support
www.ge-ip.com/support
www.ge-ip.com/support
www.ge-ip.com/support
EMEA Direct Dial +352-26-722-780 (if toll free 800 option is unavailable or
if dialing from a mobile telephone) Technical Support Email support.emea.ip@ge.com Customer Care Email customercare.emea.ip@ge.com Primary languages of support English, French, German, Italian, Czech, Spanish
Asia Pacific
Online Technical Support
Technical Support Email
www.ge-ip.com/support
+86-400-820-8208 Phone
+86-21-3217-4826 (India, Indonesia, and Pakistan)
support.cn.ip@ge.com (China)
support.jp.ip@ge.com (Japan)
support.in.ip@ge.com (remaining Asia customers)
customercare.apo.ip@ge.comCustomer Care Email
customercare.cn.ip@ge.com (China)
Page 5
Contents
Welcome 1
Features 1 Functional Compatibility 1 Related Documents 1
Hardware Overview 2 Installation Instructions 4
Choosing a Mounting Location 4 Mounting Instructions 4 Connecting a Power Supply 5 Overcurrent Protection 5 Power Cord Retainer 5
Detailed Operation 6
Communications Ports 6
Ethernet Port 6 Serial Port 7 24V Discrete Input Port 8
Discrete Output Port 9 Horn 11 Configuration Reset Pushbutton 11 Lamps and Lenses 11 Pushbutton 11 Changeable Labels 11 Status Light 11
Hardware Configuration 12
Accessing the Configuration Menu 12 Configuration Parameters 14 StationPortal Device Driver 15
Error Handling 16 Troubleshooting Guidelines 18 StationPortal Specifications 19
Physical 19 AC Power Requirements 19 Functional 19 Environmental 20
Agency Approvals 21 Default Settings 22
Page 6
Page 7
Welcome
Features
Welcome
Congratulations on your purchase of a StationPortal. The StationPortal is an I/O device that connects factory floor I/O to a server-based system, such as MES and SCADA, over standard Ethernet. This eliminates the need for a complex and expensive PLC-based architecture. Operators can use the built-in devices (horn and lamps) as well as plug I/O into one of the available ports for control by a remote client.
StationPortal is shipped ready for use after a few simple configuration steps. Connect a power cord that has a standard IEC 60320-C13. Also, connect a standard unshielded, twisted-pair CAT 5 Ethernet cable between the StationPortal and a Server PC or Ethernet switch to be able to communicate with your client application. Depending on your requirements, you may connect and configure input/output devices (see page
Universal power supply input (100V–240V, 50Hz–60Hz)
Three indicator lights
Status indicators for each digital I/O point
Horn, 90 dB
Serial RS-232 Port
Ethernet port, 10/100 Mbps
Three digital inputs on a 5-pin M12 female connector
Three digital outputs on a 5-pin M12 male connector
Momentary pushbutton
Configuration over Ethernet
12).
Functional Compatibility
Clients: StationPortal is capable of communicating with a variety of clients. If Proficy* HMI/SCADA CIMPLICITY* software is to be used with StationPortal, version 8.0 or later is required. The necessary software driver can be ordered on CD as IC647NS D0 00.
Ethernet cable: Unshielded, twisted pair, UTP CAT 5 minimum
Related Documents
PROFICY HMI/SCADA – CIMPLICITY Communications Manual, StationPortal (This document is placed in the CIMPLICITY Documentation folder when the driver is installed. Also available in the StationPortal driver installation file.)
Proficy HMI/SCADA CIMPLICITY software documentation. Note: The most recent software downloads and user documentation are available on the
Support website
.
GFK-2522A 1
Page 8
Hardware Overview
Hardware Overview
The following diagrams show the locations of user-accessible controls, indicators and connectors.
Front View
Top Light
Left Light
Changeable Label
Momentary Pushbutton
MAC Address Label
(on side of unit)
Right Light Changeable Label
Horn Changeable Label
Input Status LEDs
Output Status LEDs
2 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 9
Bottom View
Hardware Overview
GFK-2522A 3
Page 10
Installation Instructions
Installation Instructions
The StationPortal unit can be installed on a wall or column.
Choosing a Mounting Location
The unit must be mounted on the flat surface of wall or column.
For adequate ventilation, allow at least 3 inches (76.2mm) of space between adjacent
equipment and all sides of the StationPortal. Ensure that specified conditions of temperature and humidity are not exceeded.
Direct sun exposure may impose increased thermal loads on the StationPortal
leading to excessive temperatures. Cabinet design and orientation must be carefully considered to avoid exceeding the operational temperature limits.
StationPortal does not have an enclosure suitable for outdoor use. For environmental
requirements, refer to page
Mounting Instructions
Note: Limit the number of times you remove and reinstall the unit. Too many installations
may damage the plastic enclosure.
1. Install two M3 screws at a horizontal distance of 3.937” (100mm) apart at the required
height.
2. Mount the StationPortal on the two screws using mounting tabs provided at the top of the
unit. Tighten the screws if required.
3.937” (100mm)
20.
Horizontal distance between the mounting Tabs: 3.937” (100mm)
Vertical distance betwee n the mounting Tabs: 11.821” (300.3mm)
11.821” (300.3mm)
3.937”(100mm)
3. For additional support, two M3 screws can be installed at the bottom of the unit at a vertical distance of 11.821” (300.3 mm) from top hole and 3.937” (100 mm) apart.
4 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 11
Connecting a Power Supply
The StationPortal operates with 100–240V AC, 50–60 Hz input power with 0.3A RMS maximum input current.
The StationPortal requires a power cord that has a standard IEC 60320-C13 plug.
Overcurrent Protection
StationPortal unit’s power supply provides overcurrent protection (including short circuits). If an overcurrent condition occurs, the power supply continually tries to restart until the overcurrent condition is removed. An internal fuse (FU1), which is rated for 250VAC at 1A, is provided in the input line as a backup. The power supply usually trips and goes into retry mode before the fuse blows. There is no additional indication if the power supply fuse blows. The fuse is not user-replaceable.
Power Cord Retainer
A clip is provided on the StationPortal unit to provide retention for a few types of power cords.
Electrical Shock Hazard: To avoid personal injury or damage to equipment, ensure that the power cord is disconnected from AC input power during the installation of the power cord and power cord retainer clip.
Installation Instructions
Warning
Note: The clip provided with the StationPortal will work best with a power cord that has a
plug or cord strain relief extending up to 2.441 inches (62mm).
GFK-2522A 5
Page 12
Detailed Operation
Detailed Operation
A StationPortal can communicate with only one client at a time. However, a single client can communicate with multiple StationPortal devices. Although the number and types of devices that each client can support will vary, Proficy HMI/SCADA CIMPLICITY supports a native interface to the StationPortal that acts as a client. Details on the number and types of devices that a CIMPLICITY instance can support are described in the CIMPLICITY documentation. The StationPortal I/O is natively addressable in the Proficy HMI/SCADA CIMPLICITY control and visualization product.
Communications Ports
Ethernet Port
The StationPortal unit provides a 10/100 Mbps Ethernet port (IEEE802.3) with an RJ45 connector on the bottom of the enclosure. An unshielded, twisted pair, UTP CAT 5 cable is the minimum required.
LED indicators on the port indicate channel status.
Port Location and Pin Assignments
Pin
Assignments
1 RX+ 2 RX­3 NC 4 NC 5 TX+ 6 TX­7 NC 8 NC
6 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 13
Detailed Operation
Serial Port
The StationPortal unit provides one serial communication port with the following specifications:
Port Specifications
Connector Type RS-232 male 9-pin D connector Baud Rate Configurable baud rates: 2400, 4800, 9600, 19,200 baud with 8 data bits Parity Configurable: Even / Odd / None Stop Bits 1 (not configurable) Flow Control None (not configurable)
Port Location and Pin Assignments
Pin Assignments
1 NC 2 RXD1 3 TXD1 4 NC 5 Ground 6 NC 7 NC 8 NC 9 NC
Note: When StationPortal unit is configured to check Even or Odd parity and equipment at
the other end of serial communication is configured for opposite parity setting, few characters will be received by StationPortal unit which result in equal parity.
GFK-2522A 7
Page 14
Detailed Operation
24V Discrete Input Port
A 5-pin M12 type female connector mounted at the bottom of the enclosure accepts three digital inputs from field. These inputs are optically isolated sink type inputs.
Pin 1 of this connector can be used as a +24V DC auxiliary power supply for input devices and to power the DC input circuits. The combination of input circuit current and external device current must not exceed 300 mA.
Input status LEDs (I1, I2, I3) on the front of the unit indicate the On/Off states of the inputs.
Port Location and Pin Assignments
Pin Assignments
1 24 VDC for
input devices 2 Input 2 3 0V for input
devices 4 Input 1 5 Input 3
Typical 24 VDC Positive Logic Input Circuit
Field
Input
Circuit
Input Connect or
+
24V
_
Input Specifications
Inputs per Module 3 (one group with a single common) Rated voltage 24V DC Input Voltage Range 0 to +30 VDC Isolation: Field to Frame Ground 1500 VAC for 1 minute. Input Current 7 mA typical at rated voltage
Input Characteristics
On–state Voltage 8.2 to 30 volts DC Off–state Voltage 0 to +5 volts DC On–state Current 1.6 mA minimum Off–state Current 0.9 mA maximum On response Time 24 ms typical Off response Time 24 ms typical
3.3V
3.3V
CPU
8 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 15
Detailed Operation
Discrete Output Port
A 5-pin M12 type male connector provides three digital outputs to the field. These are dry contact type relay outputs. An external source of AC or DC power must be supplied to operate field devices.
Hazardous voltage may be present at the outputs.
Pin Assignments
1 Common 2 Output 2 3 Common 4 Output 1 5 Output 3
\
The state of outputs (On/Off) is indicated on the output status LEDs (O1, O2, O3) on the front of the unit.
Relay Specifications
Outputs per Module 3 isolated Form A relay outputs
0 – 30VDC (5/24 VDC nominal) External Power Supply 0 – 250VAC (47 to 63 Hz), 120-240VAC nominal
Isolation, Field to Frame Ground 1500 VAC for 1 minute
Output Characteristics
5 – 30VDC (5/24 VDC nominal) Output Voltage 5 – 250VAC (47 to 63 Hz), 120-240VAC nominal
Output Current
Output Voltage Drop 0.3VDC maximum Output Leakage Current Not Applicable (open contact) Response Times (On/Off) 10ms maximum (At nominal voltage excluding contact bounce) Switching Frequency 20 cycles per minute maximum (50% duty cycle recommended) Protection None. External snubbers may be applied if necessary Relay Contact Life See “Load Current Limitations” Diagnostic Information None
10mA per point minimum 4A for 5-250VAC maximum (resistive or general purpose) 4A for 5-30VDC maximum (resistive) 2A pilot duty per output (5 to 30VDC, 5 to 250VAC) 2A lamp load per output (5 to 30VDC, 5 to 250VAC)
GFK-2522A 9
Page 16
Detailed Operation
Load Current Limitations
Operating
Voltage
5 to 250 VAC 4 Amps 2 Amps 200,000 5 to 250 VAC 0.1 Amp 0.05 Amp 1,000,000 5 to 250 VAC 1 Amp 0.5 Amp 700,000
5 to 30 VDC 4 Amps 2 Amps 200,000 5 to 30 VDC 1 Amp 0.5 Amp 700,000 5 to 30 VDC 0.1 Amp 0.05 Amp 1,000,000
* Assumes a 7ms L/R time constant (DC inductive load) or Cos φ > 0.4 (AC inductive load)
Suppression Circuits
Relay contact life, when switching inductive loads, will approach resistive load contact life if suppression circuits are used. Examples of typical suppression circuits for AC and DC loads are shown below. The 1A, 200V diode shown in the DC load typical suppression example is an industry standard 1N4935. The resistor and capacitor shown fo r AC load suppression are standard components, available from most electronics distributors.
Maximum Current for Load Type
Resistive Lamp or Solenoid *
Typical Contact Life
(Number of Operations)
10 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 17
Horn
The StationPortal horn outputs 90dB1.
Configuration Reset Pushbutton
The Reset push button is used to restore the factory configuration settings. For details, refer to the “Default Settings” section on page
To access the Reset pushbutton, press the Reset pushbutton for 3 seconds.
Lamps and Lenses
The StationPortal includes three lamps. Each lamp is individually configurable for one of three states – off, on, or blinking.
All lens covers are interchangeable and can be removed by turning them counterclockwise.
Pushbutton
The StationPortal provides an integrated momentary push-button for use in your applications.
Changeable Labels
There are slots for labels below the Right light indicator, Left light indicator, and Pushbutton. You can change the labels for the Right and Left indicator lights and the pushbutton. The dimensions of the label are 33.78 mm x 11.99 mm x 0.40 mm (L x W x D). To insert the label in the given slot, align the label to the edges of the slot and slide it inside the slot.
Detailed Operation
22.
Status Light
A status LED on the bottom of the unit indicates processor activity. This LED flashes during the normal operation of the unit.
1
Sound pressure level measured at the Station Portal unit.
GFK-2522A 11
Page 18
Hardware Configuration
Hardware Configuration
The StationPortal’s communications and operational parameters are configured usin g a Telnet connection.
Accessing the Configuration Menu
To access the Configuration Menu, connect the StationPortal unit to the Ethernet LAN or to any personal computer (PC) using an Ethernet cable. Power up the StationPortal unit.
Open the “command prompt” window on PC by clicking on “Start Run. Type “cmd” in the dialog box.
At the command prompt, type the following to access the configuration menu:
> telnet <IP address> Example: > telnet 192.168.0.35
Where <IP address> is the IP address of the StationPortal unit. The Default IP address of StationPortal is 192.168.0.35.
12 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 19
Hardware Configuration
If you do not know the IP address, it can be reset to the default settings. For details, refer to the “Default Settings” section on page
StationPortal Configuration Menu
22.
GFK-2522A 13
Page 20
Hardware Configuration
Configuration Parameters
Option Parameter Description Format
1 IP Address Sets the IP address for Ethernet communications xxx.xxx.xxx.xxx 2 Subnet Mask Sets the subnet mask for Ethernet communications xxx.xxx.xxx.xxx 3 Default Gateway Sets the default gateway for Ethernet communications xxx.xxx.xxx.xxx 4 Baud Rate Selects the baud rate for serial communications 0=2400
1= 4800 2=9600 3=19,200
5 Parity Selects the parity for serial communications 0=None
1=Odd 2=Even
6 Set default state
for outputs
Set the default states that the outputs will assume if the StationPortal is not in communication with a client.
For example, a lack of communications could be caused by the Ethernet cable being removed from either end of an Ethernet connection or upon initial device power-up.
Example: To select the following default states, enter 0123000.
Right Light – OFF Left Light – ON Top Light – Flash Horn – Hold OUTPUT1 – OFF OUTPUT2 – OFF OUTPUT3 – OFF
The factory default settings for StationPortal are to turn the Top Light ON and all other outputs (horn, outputs 1-3, etc) off. Illuminating a light when communication isn’t present allows the end-user to distinguish between a loss of power and absence of communication.
Note: Do not enter “2” as the default state of the Field outputs because they do not support Flash operation.
Note: While in this state,
try to re-establish communication with StationPortal. If communication can be established, the user’s application will once again be able to drive outputs. However, the default conditions will persist until the application does so.
Note: If the user has configured the default output state to “Hold
last state” and unit is power cycled, the Outputs will be driven to “Off” state.
Note: If the user changes the default state of the output, the new
values applies when the unit is power cycled or loss of communication occurred.
it is expected that clients will periodically
0=Off 1=On 2=Flash 3=Hold Last
State
14 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 21
Hardware Configuration
Option Parameter Description Format
7 Keep-alive time
(seconds)
8 Gigabit Switch Specifies whether StationPortal is connected to a Gigabit Switch /
L Load last saved
configuration
S Save and Exit Save the changes made to the configuration settings as the current
Q Quit without Save Exits the configuration menu without saving changes made to the
Specifies the interval (in seconds) that StationPortal waits before sending a keep-alive probe message across an idle TCP connection.
Note: StationPortal will send keep-alive probe messages if there is
no activity on the network for the time period specified by this parameter. If there is no response to its first keep-alive probe message, StationPortal will send subsequent keep­alive probe messages every 1 second. StationPortal will send a maximum of eight keep-alive probe messages on an idle network after which it will close its TCP ports.
Note: A value of 0 indicates that keep-alive messages are
disabled. In such cases, StationPortal will not be able to detect all communication losses. If communication loss isn’t properly detected, the client may be unable to reconnect to StationPortal. Thus, we recommend that a non-zero value be specified.
Controller or 10/100 Mbps switch / controller
Note: When StationPortal is connected to a 10/100 Mbps switch /
controller or to a Gigabit switch with Auto-negotiation mode disabled, this parameter should be set to “No”. This parameter should be set to “Yes” only when StationPortal is connected to a Gigabit switch / controller with Auto­negotiation mode enabled.
Reverts to the previously saved (using the “Save and Exit command”) configuration settings.
Note: StationPortal maintains a copy of only the most recently
saved configuration that is used for current operation. As a result, this option cannot be used to revert to an earlier configuration.
operational settings and exits the Configuration Menu.
configuration settings.
0 to 65535
0=No 1=Yes
“L” or ‘l’ (lower­case L)
“S” or “s”
“Q” or “q”
StationPortal Device Driver
A native CIMPLICITY device communication interface is available for the StationPortal. This software can be ordered on CD as IC647NSD000.
GFK-2522A 15
Page 22
Error Handling
Error Handling
The following table identifies possible causes and resulting StationPortal behavior for various error conditions.
Communication Errors
Communication not established
Logical Loss
Physical Loss Loss of carrier signal on the RJ-45
System Critical Errors
When the StationPortal encounters this type of error, it displays a two-digit blink code on the Top light and stops communicating with the client. Unless stated otherwise, the values of other outputs are determined by the user-defined default configuration.
Note: The displayed blink codes represent two digits as explain ed in the entries that follow. A blink is
accomplished by first illuminating the light for 500ms and then turning the light off for another 500ms. If the horn is configured for “blink/beep” state, it will sound as the Top light is on and be silent while the Top light is off.
EEPROM read error
EEPROM Write Error
Error Possible Causes Station Portal Behavior
Unit Powered up; communication has not yet been established.
Loss during normal communication. Loss during startup. Client has closed one or both of its
TCP connections to StationPortal.
connector.
Failure reading configuration settings from the EEPROM.
When processor tries to write onto EEPROM during configuration settings.
The user-defined default output state values are asserted. These values are defined via telnet as described in the “Configuration Parameters” section on page 14.
Blink Code “11”
Blink the Top LED once (“1”). Wait for 2sec (Gap between “1”
and “1”).
Blink the Top LED once (“1”). Wait for 5sec (Gap between
error codes).
Repeat the above four steps. Drive outputs to “off” (except
Top light “On”).
Blink Code “12”
Blink the Top LED once (“1”). Wait for 2sec (Gap between “1”
and “2”).
Blink the Top LED twice (“2”). Wait for 5sec (Gap between
error codes).
Repeat the above four steps.
16 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 23
Error Possible Causes Station Portal Behavior
Serial Transmit Buffer Overflow
Serial Receive Buffer Overflow
Invalid OP Code When processor fetches invalid OP
Watchdog reset When watchdog timer elapses. No Blink code.
When the serial data rate received from the client application is faster than device transmit rate.
When the serial data rate received from serial input device is faster than device transmit rate to the client application.
code.
Blink code “21”
Blink the Top LED twice (“2”) Wait for 2sec (Gap between “2”
and “1”).
Blink the Top LED once (“1”). Wait for 5sec (Gap between
error codes).
Repeat the above four steps. Blink code “22”
Blink the Top LED twice (“2”). Wait for 2sec (Gap between “2”
and “2”).
Blink the Top LED twice (“2”). Wait for 5sec (Gap between
error codes)
Repeat the above four steps. No Blink code.
System will reset and go to
default state.
System will reset and go to
default state.
Error Handling
GFK-2522A 17
Page 24
Troubleshooting Guidelines
Troubleshooting Guidelines
Problem Suggested Remedy
StationPortal unit does not respond to commands from the client
Serial data is not received or transmitted in the client’s application
Inputs are not received correctly in the client’s application
Outputs are not received correctly in the client’s application
Check StationPortal unit is powered on and "Status" LED is blinking.
Check Ethernet cable is connected properly. Check IP address, Subnet mask and Gateway address are
set properly from the hardware configuration menu. Check IP address is set correctly in the device properties in
C client’s project. Check each StationPortal unit has unique IP address set in
the hardware configuration menu.
Check StationPortal unit is powered on and "Status" LED is blinking.
Serial communication cable is connected properly with Null modem configuration.
Check baud rate and parity are set correctly in the hardware configuration menu.
Check baud rate and parity are set correctly in the client’s application.
Check StationPortal unit is powered on and "Status" LED is blinking.
Input cable is connected properly with correct pin sequence.
Check StationPortal unit is powered on and "Status" LED is blinking.
Output cable is connected properly with correct pin sequence.
18 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 25
StationPortal Specifications
See page 21 for a list of agency approvals for environmental service and safety.
Physical
Enclosure dimensions Height: 332.5 mm,
Weight 1 Kg
AC Power Requirements
Nominal Rated Voltage 120/240 VAC AC Input Voltage Range 100 to 240 VAC, 50–60 Hz Input Power (Maximum with Full
Load) Inrush Current 20A at 115VAC, 40A at 230VAC for 2.5ms
Isolation (input (L,N) to Earth): 250 VAC continuous; 1500 VAC for 1 minute
* The Inrush Current specification is given as a guide for sizing the external power source
for the StationPortal. Peak inrush current may be higher for shorter durations.
StationPortal Specifications
Width: 162 mm, Depth: 73 mm
32 Watts maximum
maximum*
Functional
Serial Communication RS-232 Port EIA232C, DB-9 (Male) Speed 2400 bps / 4800 bps / 9600 bps / 19200 bps Parity Even / Odd / None Stop Bits 1 (not configurable) Flow Control None (not configurable) Mounting hardware #4-40 screw Ethernet communication
Digital Inputs Three digital inputs with auxiliary power
Digital Outputs Three dry contact relay type digital outputs. An
Pushbutton Momentary pushbutton, over 2 million
Indicator lights Three indicator lights with changeable lens
Horn 90dB sound level
IEEE 802.3 protocol 10 BaseT/100 Base TX Auto-negotiate Full or half duplex RJ45 connectors Two status LEDs Maximum cable length: 100m
source of 300mA @ 24V
external voltage source is required
operations
covers
GFK-2522A 19
Page 26
StationPortal Specifications
Environmental
Vibration 1G @40-150Hz, 0.012in p-p @10-40Hz Shock 15G, 11ms Operating Temperature* 0°C to 60C° (32°F to 140°F) Storage Temperature -30°C to +80°C (-22°F to 176°F) Humidity 5% to 95%, non-condensing IP Rating IP20
* Rated temperature limits refer to the ambient air temperature immediately
surrounding (within 3” - 7.6 cm) the StationPortal where it is mounted. Provisions for remaining within the stated limits must be considered where additional external thermal loads are imposed on the StationPortal. These could include large heat producing motor drives or power supplies in the same cabinet.
20 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 27
Agency Approvals
Model number: IC760STA100 The StationPortal is intended to be used as Information Technology Equipment Including
Electrical Business Equipment (NWGQ, NWGQ7) and when properly installed shall comply with the following agency approvals
Agency Approvals
Description Agency Standard or
Marking
North American Safety for Information Technology Equipment
EMC Directive and Low Voltage Directive
Certification by Underwriter's Laboratories to UL60950-1: 1st Edition (2007-10-31) standard and equivalent CAN/CSA-C22.2 No. 60950-1-07 (March 2007) standard
Compliance to harmonized standards, EN55024: 1998 +A1: 2001 +A2:2003 and EN60950-1: 2006, in accordance with European Directives; Refer to Declaration of Conformity found on
Comments
the Support website.
The agency approvals listed above and on the Declaration of Conformities are believed to be accurate; however, a product’s agency approvals should be verified by the marking on the unit itself.
GFK-2522A 21
Page 28
Default Settings
Default Settings
Factory Default Settings
To restore the StationPortal configuration to the factory default settings, press the Reset pushbutton for 3 seconds.
Option Setting Factory Default Value
1 Ethernet IP address 192.168.0.35 2 Ethernet subnet mask 255.255.255.0 3 Ethernet default gateway 192.168.0.1 4 Serial baud rate 19200 5 Parity for serial communications None 6 Default States for Outputs
(Right Light, Left Light, Top Light, Horn,
and Outputs O1, O2 and O3) 7 Keep-alive time 3 sec 8 Gigabit Switch Yes
Power-On Values for above setting will be as per Last Saved values.
0010000 (All outputs in “OFF” state except Top light “ON”)
22 StationPortal Hardware User’s Guide – February 2010 GFK-2522A
Page 29
Index
A
Agency approvals, 21
B
Baud rate, 14
C
Choosing a mounting location, 4 Configuration, 12
factory default settings, 22 power-on values, 22
Configuration Reset pushbutton, 11
D
Default gateway, 14 Defaults
factory settings, 22 power-on, 22
Device driver, 15
E
Error Handling, 16 Ethernet
Default gateway, 14 IP address, 14 port, 6 Subnet mask, 14
F
Factory default settings, 22 Features, 1
H
Horn, 11
O
Operation, 6 Outputs
port, 9 suppression circuits, 10
Overcurrent protection, 5 Overview, hardware, 2
P
Parity, 14 Power up, 5 Power-on values, 22
Q
Quit without save, 15
R
Related documents, 1 Reset, 11
S
Save and exit, 15 Serial
Baud rate, 14 Parity, 14 port, 7
Set default state for outputs, 14 Specifications, 19 Subnet mask, 14 Suppression circuits, 10
T
Technical Support. See page iv
Inputs
port, 8
IP address, 14
Labels, changing, 11 Lenses, changing, 11 Load previous configuration, 15
I
L
Loading...