GE SIR-LONG, SIR-LONG-D Installation Instructions Manual

Passive Infared Corner/Wall Mounted Low Voltage Occupancy Sensor
• Read all instructions on both sides of this sheet first.
• Plan all component locations carefully.
• Install in accordance with ALL local codes.
• For indoor use only.
• For Use with GE Switchpacks & Systems Only.
• Do not run any GE Low Voltage Wiring in the s
ame conduit as power conductors.
General Information
Technology: Passive Infrared (PIR) Power Requirements:
Input:
10-30 VDC from GE Controls Switchpack or GE system. Maximum current needed is 25mA per sensor
Output:
• Open collector output to switch up to ten GE Switchpacks. BAS with Isolated Form C Relay (-D
model) Isolated Form C Relay Ratings: 1A 30VDC/VAC Time Delays:Self-Adjusting, 15 seconds/test (10 min Auto), or Selectable 5, 15, 30 minutes
Coverage: 90 sq. ft. Light Level Sensing: 0 to 300 foot-candles (- R model) Operating Environment:
Temperature: 32° F – 104° F (0° C – 40° C)
• Relative Humidity: up to 90% non-condensing
Housing:
• Medium impact injection molded housing. Polycarbonate resin complies with UL94V0.
Size: 4.4" x 3.4" x 2" (112mm x 86.4mm x 50.8mm) LED Indicators: Red indicates PIR detection
Specifications
Description
The SIR-LONG Corner/Wall Mount Low Voltage Occupancy Sensor is a Passive Infrared (PIR) motion sensing
lighting control, used for energy savings and convenience. When motion is detected, the blue wire is electronically connected to the red wire, energizing the relay in the switchpack to turn ON the load. If vacancy is detected, the b
lue wire is disconnected from the red, causing the relay to open turning OFF the load. The red lead is 10 to 30 VDC
supply, the black lead is common, and the blue is the relay control. (-D models: yellow is second relay control)
PIR Technology
The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes in temperature that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone. The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and t
ime delay in real-time. By adjusting sensitivity and time delay automatically, the sensor is maximizing the potential energy savings that are available in the particular application. The Daylighting feature (-D model only: yellow control lead only) prevents lights from turning ON when the room is adequately illuminated by natural light. Walk-Through feature maximizes energy savings by not leaving the lights ON after a momentary occupancy. The sensor will switch the lights ON when it detects a person entering the area. If the sensor does not continue to detect motion 30 seconds following the initial activation, it will automatically go to a shorter 2 minute time delay. In Automatic On Mode, the lights turn ON when a person enters the room. In Manual-ON Mode, the lights are turned ON by activating a momentary switch (model # RS2-*) that is connected to the sensor. When used with 2 level lighting (-D model only), bi-level Automatic-ON can be achieved which allows Zone 1 to come ON automatically upon occupancy. Zone 2 does not come ON unless the occupant presses the optional momentary switch.
Coverage
Location
The m aximum coverage area ma y vary somewhat accordi ng to r oom sha pe and the pres ence of
obsta cles. F ollow t he cove rage di agram c oncernin g major and m inor mo tion co verage. The se nsor must have a clear view of the area to be c ontrolled. Th e sensor will n ot “see” throu gh glass. Moun ting height should not e xceed 12 fe et. Optim um mountin g height is 1 0 feet. To prevent fal se activati on, the se nsor shou ld be mou nted away from the air suppl y duct a m inimum o f 4 to 6 fe et. Mou nting at fi xture he ight is most eff ective.
Installatio
n
T
h
e
S
I
R
-
LON
G c
a
n
b
e
m
o
u
n
te
d
to
th
e
w
a
l
l
,
c
e
i
l
i
n
g
,
j
u
n
c
ti
o
n
b
ox
,
o
r
r
o
u
n
d
f
i
x
tu
r
e
w
i
th
r
a
c
e
w
a
y
.
Occup
a
ncy
S
e
ns
o
r
M
o
unt
e
d
t
o
W
a
l
l
b
o
a
rd
Occupancy Sensor Mounted to Octagon Box
Occup
a
ncy
S
e
ns
o
r
M
o
unt
e
d
t
o
D
ro
p
C
e
i
l
i
ng
Occupancy Sensor Mounted to Octagon Box with Mud Ring
Occupancy Sensor Mounted to Round Fixture with Raceway
One Sensor, One Switchpack
WARNING
RISK OF ELECTRIC SHOCK
• Turn power off before servicing
• Properly ground components
Wiring
CAUTION: Before installing or performing any service on a GE system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in compli­ance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.
1. Make sure power is turned OFFat the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements. (Use twist-on wire connectors for all connections) CAP ALL UNUSED WIRE LEADS.
3. Mount unit to wall, ceiling, junction box, or round fixture with raceway.
4. Turn power back ONat the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
16’
(4.9)
0
16’ (
4.9)
6.8
(2.1 mm)
3 ft
(1 mm)
7 ft
(2.2 mm)
10 ft
(3 mm)
43 ft
(13.2 mm)
7
5 ft
(23 mm)
92 ft
(28 mm)
9
0
l
i
n
e
ar
ft
.
co
v
e
rage
I
NSTALLATIONINSTRUCTIONS
M
odel # SIR-LONG
Model # SIR-LONG-D
Checkout and Adjustment
Adjustments should be made with the HVAC system ON. Use only insulated tools to make adjustments.
Self-Adjust
Sensor is shipped in the Self-Adjust Mode. This applies to time delay and PIR sensitivity. In preparation for the
Installer Test, the time delay is set to 15 seconds, after the sensor is installed, powered-ON and has stabilized, the unit will time-out 15 seconds after the last motion detected. Coverage and sensitivity can be confirmed by watching the Red (PIR) indicator LED on the front of the sensor, while moving around the room.
1. Walk around the room and monitor LED. LED should only turn ON for one second with each motion. (If LED do not turn ON, go to Installer Adjustments - Sensitivity Adjustments Section)
2. Stand still six to eight feet away from the sensor for five seconds. LED should not turn ON. (If any LED turns O
N, go to Installer Adjustments – Sensitivity Adjustment section)
3. Walk outside the room and wait 15 seconds for the lights to turn OFF. (If lights do not turn OFFgo to Installer Adjustments Section)
4. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)
5. The unit will remain in Test Mode for 5minutes then automatically exit Test Mode and go for 10 min. Time Delay User Mode setting.
Note:
T
o place into Test Mode, toggle DIP Switch 10 out of its current position, wait 3 seconds, and then back in to its original position. To force
i
nto 10 min User Mode move Dip Switches 1 and 2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current position,
wait 3seconds, and then back to its original position) While in Test Mode, the LEDs will flash once per 1/4 second.
Installer Adjustments
Hot
Neutral
Line
Load 1
Black Red Blue
P
urple
Gray
Orange
Switchpack
Blue
Blue
**Hot
*
*Use Black Lead for 120VAC
Use Orange Lead for 277VAC C
ap Unused Lead
White
Hot
Neutral
Line
Load 2
Switchpack
Blue
Blue
**Hot
*
*Use Black Lead for 120VAC
Use Orange Lead for 277VAC C
ap Unused Lead
White
Yellow B
rown Brown/White
Optional GE RS2-* Switch
Red (15VDC)
B
lack(Common)
Blue (Control)
SENSOR WIRE LEAD LEGEND
Black (Common) Red (10-30VDC) Blue (Control) Yellow (Control) Brown (Switch-Blue Lead Control) Brown/White (Switch-Yellow Lead Control)
S
ensor's Isolated Relay
O
range (Normally Open)
G
ray (Common)
P
urple (Normally Closed)
Red (15VDC)
B
lack(Common)
Blue (Control)
One Sensor, Multiple Switchpacks
To Additional Switchpacks 10 switchpacks Maximum
WARNING
R
ISK OF ELECTRIC SHOCK
Turn power off before servicing
Properly ground components
Manufactured for GE Lighting General Electric Company Nela Park Cleveland, OH 44112 1-877-584-2685 www.gelightingcontrols.com © 2011 GE
Sensitivity Adjustments
PIR Sensitivity
1. Stand in different areas of the room and wave your hands.
2. If the Red LED does not turn ON, check for any obstructions.
3. Stand still six to eight feet away from sensor for five seconds. LED should not turn ON.
4. If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50% by moving DIP Switch 5 UP.
Field-of-view outside the space
1. Adjust PIR sensitivity to 50% by moving DIP Switch 5 up.
Daylight Adjustments
If this feature is not needed, leave the light level at maximum (fully CW). The Daylighting feature (-D model only) prevents the lights from turning ON when the room is adequately illuminated by natural light. If there is enough light in the room regardless of occupancy, the sensor will hold the lights OFF. If there is not enough light in the room, the sensor will allow the lights to turn ON when occupied.
Full and Half Logic Modes (See DIP Switch legend): In both Full and Half Logic modes, lights connected to the yellow control lead will not turn ON upon occupancy activation, should the ambient light level exceed the preset foot-candle level.
After activation:
Full Logic Mode - should the ambient light level exceed the preset foot-candle level, the lights connected to the yellow control lead will turn OFF. The lights will remain OFF, until the ambient light level falls below the set point. Half Logic Mode – the output state of the yellow control lead will not change with ambient light changes, after occupancy activation. If the amount of natural light available rises above the setpoint , the daylight sensor will not turn the lights OFF while occupancy is being detected.
Note: Set the light level when the ambient light is at the level where no artificial light is needed. In order for this feature to function, the yellow control lead must be wired.
1. With the load ON, put the sensor into Test Mode. To place into Test Mode, toggle DIP Switch 10 out of its current position, wait 3 seconds and then back in to its original position.
2. Set DIP Switch 10 to Full or Half Logic Mode.
3. Set the Light level to Minimum (fully CCW).
4. Lea ve the room and let th e sensor ti me-out so lights ar e OFF. Enter the space and lights should remain OFF.
5. Make sure not to block the sensor from the daylight source and adjust the light level potentiometer CW in small increments until the lights are ON. (Pause 5 seconds between each adjustment)
6. Once the lights are ON, the load connected to the sensor will not turn ON if light levels are above the current illumination.
Time Delay Adjustments
People who remain very still for long periods of time may need a longer Time Delay than the default set­ting of 10 minutes. As long as Auto is enabled, the sensor will respond to each pair of false offs with no nor­mal OFF in between, by alternately making slight adjustments to either time delay (by 2 minute increments) or sensitivity, so there should be no need for manual adjustment. If manual adjustment is desired, refer to Time Delay settings in DIP Switch legend. Reset sensor time delay to factory settings by moving DIP Switches 1 and 2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current position, wait 3 seconds, and then back to its orig­inal position)
Automatic Mode
In Automatic-ON Mode, the lights turn ON when a person enters the room. If optional momentary low volt­age switches are used along with Automatic-ON Mode, activating the switch(es) while the load is ON turns the load OFF. When the load is turned OFF manually, as long as the sensor continues to detect occupancy the loads stay OFF. After the time delay expires, the lights stay OFF and the sensor goes back to Automatic ON Mode. For wiring information for the optional momentary low voltage switch(es), please see the wiring section of the installation instructions.
M
anual Mode
In Manual ON Mode, the optional momentary low voltage switch(es) is required to turn the load(s) ON. Once activated the sensor will maintain the lights ON until motion ceases and the time delay expires. While the room is occupied the BAS relay remains active. After the time delay expires, the load(s) will automatically be turned OFF and the switch(es) must be used to turn the load(s) ON unless there is motion detected within the 10 second re-trigger period.
Lighting Sweep Option
If selected, this DIP Switch option forces an initial 60 second delay upon “power up” to prevent false acti­v
ation in buildings with computer control systems.
1. Move DIP Switch 9 UP.
Override
The Override setting allows the lights to remain ON in the unlikely event of sensor failure.
1. Move DIP Switch 8 UP.
While in Override Mode, the optional low voltage momentary switch(es) will toggle the lighting load(s).
Limited Warranty
Troubleshooting
This product is warranted to be free from defects in material and workmanship and shall conform to and
perform in accordance with Seller’s written specifications for a period of five (5) years from date of shipment
for all occupancy sensors. We guarantee the performance of our product to specifications or your money
back. This warranty will be limited to the repair or replacement , at Seller’s discretion, of any such goods
found to be defective, upon their authorized return to Seller. This limited warranty does not apply if the
goods have been damaged by accident, abuse, misuse, modification or misapplication, by damage during
shipment or by improper service. There are no warranties, which extend beyond the hereinabove-limited
warranty, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IM-
PLIED WARRANTY OF FITNESS. No employee, agent, dealer, or other person is authorized to give any war-
ranties on behalf of the Seller or to assume for the Seller any other liability in connection with any of its
goods except in writing and signed by the Seller. The Seller makes no representation that the goods comply
with any present or future federal, state or local regulation or ordinance. Compliance is the Buyer’s re-
sponsibility. The use of the Seller’s goods should be in accordance with the provision of the National Elec-
trical Code, UL and/or other indu stry or military sta ndards that are pertinent to the particular end use.
Installation or use not in accordance with these codes and standards could be hazardous.
Res. #4881175
Printed in USA
Issue Possible Causes Suggestions
Lights Will Not Turn ON
automatically
Wall Switch OFF Turn Wall Switch ON.
If low voltage switch option is used, lights
may have been turned-off manually.
Press low-voltage switch.
Daylight Feature Enabled
If all lights are required to turn ON adjust
DIP Switch 10 and/or daylight potentiometer
Power interruption Check incoming voltage and/or wiring
Lights Will Not Turn ON
manually
Daylight Feature Enabled
If all lights are required adjust DIP switch 10
and/or daylight potentiometer.
Power interruption Check incoming voltage and/or wiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-877-584-2685
Lights Will Not Turn OFF
automatically
Override Make sure sensor is not in Override Mode (DIP Switch 8 up).
Sensor installed close to an air vent
Sensors should be installed 4 - 6 feet away from any air
vent and out of heavy air flow.
Sensor installed close to indirect lighting. Sensors should be mounted away from indirect lighting.
Self-adjust
It may be possible for the unit to have self-adjusted the
time delay to a 30 minute delay. If the lights do not turn
OFF after 30 minutes follow next step.
30 Minute Delay
Maximum time delay is 30 Minutes. Check DIP Switches to verify DIP Switch settings. If lights do not turn OFF at
the set time delay, check next step.
PIR activated by heat source other than occupant Move DIP Switch 5 UP.
Bypass
Check wiring to make sure sensor or switchpack are not
bypassed.
Lights Will Not Turn OFF
manually
Wiring Check Wiring
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
D
IP Switch Settings
LEDs
Power Pack One
P
ower Pack Two
(
-D model only)
(-D model only)
1
2345678910
Loading...