GE SIGNA Prime Preinstallation Manual

SIGNA™ Prime
Preinstallation Manual
5538858-1EN Revision 4 © 2021-2022 General Electric Company *Trademark of General Electric Company
General service documentation. Copyright General Electric Company. GE proprietary. Reproduction and/or distribution is prohibited.
Preinstallation Manual

Contents

Contents
1.1 Preinstall Manual Introduction...................................................................................................................................................... 8
1.1.1 Document Purpose................................................................................................................................................................ 8
1.1.2 Intended User .......................................................................................................................................................................... 8
1.1.3 Who Should Read This Manual......................................................................................................................................... 9
1.1.4 Related Publications...........................................................................................................................................................10
1.1.5 Document Overview...........................................................................................................................................................11
1.2 Symbols Key ........................................................................................................................................................................................ 12
2.1 System Level Requirements for Installing into Existing MR Suite...............................................................................13
2.2 System components........................................................................................................................................................................14
2.2.1 Magnet Room......................................................................................................................................................................... 14
2.2.2 Equipment Room..................................................................................................................................................................14
2.2.3 Control Room.........................................................................................................................................................................14
2.2.4 Accessories.............................................................................................................................................................................14
2.2.5 System Overview .................................................................................................................................................................15
2.3 MR Suite Minimum Room Size Requirements...................................................................................................................... 17
2.4 MR System Seismic Requirements............................................................................................................................................21
2.5 Structure-borne Vibration Control Specications..............................................................................................................22
2.6 MR Suite Magnetic Field Specications...................................................................................................................................24
2.6.1 Magnetic Fringe Field .........................................................................................................................................................24
2.6.2 Interference from Changing Magnetic Fields...........................................................................................................27
2.6.3 Electrical Current .................................................................................................................................................................31
2.6.4 Non-MR System Equipment Sensitivity to Magnetic Fields..............................................................................32
2.7 Multiple MR System Requirements...........................................................................................................................................33
2.7.1 Multiple Magnets.................................................................................................................................................................. 33
2.7.2 Shared Equipment Rooms................................................................................................................................................33
2.8 MR Suite Temperature and Humidity.......................................................................................................................................35
2.8.1 Temperature and Humidity Requirements...............................................................................................................35
2.8.2 Equipment Heat Output Specications .....................................................................................................................35
2.9 Facility Coolant Requirements.................................................................................................................................................... 37
2.9.1 Integrated Cooling Cabinet (ICC) Coolant Requirements-Type B Conguration......................................37
2.9.2 18KW Chiller Coolant Requirements- Type D Conguration............................................................................39
2.9.3 Emergency Backup Facility Coolant Requirements..............................................................................................40
2.10 MR Suite Electrical Requirements...........................................................................................................................................43
2.10.1 General Electrical Requirements................................................................................................................................ 43
2.10.2 GE Supplied Main Disconnect Panel (MDP) Specications for M50022MA, M50022MB and
M50022MC................................................................................................................................................................................. 45
2.10.3 Customer-supplied Main Disconnect Panel (MDP) Requirements (exempt countries only*)..........48
2.10.4 Emergency Power Backup Specications (Optional).........................................................................................51
5538858-1EN Revision 4 SIGNA™ Prime 2/126
Preinstallation Manual
Contents
2.11 MR System Shipping and Receiving........................................................................................................................................52
2.11.1 Receiving Requirements................................................................................................................................................. 52
2.11.2 Facility Delivery Route Requirements......................................................................................................................52
2.11.3 MR System Component Shipping Specications.................................................................................................52
2.11.4 Temperature and Humidity Storage Requirements...........................................................................................55
3.1 Magnet Room Introduction...........................................................................................................................................................56
3.2 Magnet Room Structural Requirements.................................................................................................................................58
3.2.1 Overview.................................................................................................................................................................................. 58
3.2.2 Environmental Steel Limits..............................................................................................................................................58
3.2.3 Vibration Requirements....................................................................................................................................................59
3.3 Magnetic Shielded Room Requirements.................................................................................................................................60
3.4 Integrated System Cabinet (ISC) and Penetration Panel (PP) Wall Opening Requirements............................60
3.5 Finished Room Requirements..................................................................................................................................................... 67
3.5.1 Ferrous Materials in the Magnet Room......................................................................................................................67
3.5.2 Walls.......................................................................................................................................................................................... 67
3.5.3 Magnet Preinstallation Markings ..................................................................................................................................67
3.5.4 Doors, Magnet Access Openings, and Patient Viewing Windows..................................................................70
3.5.5 Finished Ceiling.....................................................................................................................................................................70
3.5.6 Magnet Room Floors...........................................................................................................................................................70
3.5.7 Storage Cabinets..................................................................................................................................................................73
3.6 Magnet Room Equipment Specications ...............................................................................................................................74
3.6.1 Magnet (MAG) Assembly Specications ....................................................................................................................74
3.6.2 Patient Table (PT) Specications...................................................................................................................................76
3.6.3 Magnet Rundown Unit (MRU) Specications and Requirements....................................................................77
3.7 Magnet Room Lighting Requirements ..................................................................................................................................... 78
4.1 Equipment Room Overview..........................................................................................................................................................80
4.2 Main Disconnect Panel (MDP) Requirements and Specications................................................................................83
4.2.1 Requirements ........................................................................................................................................................................83
4.2.2 Specications.........................................................................................................................................................................83
4.3 Integrated System Cabinet (ISC)................................................................................................................................................85
4.4 Mesh Shield and Integrated System Cabinet (ISC) Cover................................................................................................88
4.5 Integrated Cooling Cabinet (ICC) Specications .................................................................................................................89
4.6 Penetration Panel ............................................................................................................................................................................. 90
4.7 Cryocooler Compressor (CRY) Specications.......................................................................................................................90
4.8 18kW Water Chiller..........................................................................................................................................................................91
4.9 Magnet Monitor (MON) Requirements and Specications.............................................................................................96
4.9.1 Requirements ........................................................................................................................................................................96
4.9.2 Specications.........................................................................................................................................................................96
5538858-1EN Revision 4 SIGNA™ Prime 3/126
Preinstallation Manual
Contents
5.1 Operator Workspace Equipment Specications.................................................................................................................98
5.1.1 Operator Workspace Assembly.....................................................................................................................................98
5.1.2 Operator Workspace (OW) (Optional Equipment).................................................................................................99
5.1.3 Global Operator Cabinet (GOC).................................................................................................................................. 100
5.1.4 Host Display......................................................................................................................................................................... 101
5.1.5 Host Keyboard.................................................................................................................................................................... 101
5.1.6 Pneumatic Patient Alert................................................................................................................................................. 102
5.2 Oxygen Monitor (OXY) Specications (Optional Equipment)...................................................................................... 103
6.1 InSite RSvP (Remote Service Platform) Requirements.................................................................................................. 104
6.1.1 InSite RSvP Connectivity Requirements ................................................................................................................104
7.1 MR System Interconnects Specications............................................................................................................................ 105
7.1.1 Component Designator Denitions ..........................................................................................................................105
7.1.2 Available Cable Lengths................................................................................................................................................. 106
7.2 MR System Interconnects Routing Requirements...........................................................................................................110
7.2.1 Cabling Requirements..................................................................................................................................................... 110
7.3 Facility-Supplied System Interconnects Specications................................................................................................ 112
8.1 Glossary.............................................................................................................................................................................................. 115
8.2 MR Site Vibration Test Guidelines.......................................................................................................................................... 117
8.2.1 Test Measurements.......................................................................................................................................................... 117
8.2.2 Equipment (Spectral Analyzer) Set-Up.................................................................................................................... 117
8.2.3 Data Collection................................................................................................................................................................... 118
8.2.3.1 Ambient Baseline Condition............................................................................................................................ 118
8.2.3.2 Normal Condition................................................................................................................................................. 118
8.2.4 Presentation/Interpretation of Results................................................................................................................... 119
8.3 Sample Calculation AC Power Equipment Minimum Distance.................................................................................. 121
8.4 Selecting Anchor Size................................................................................................................................................................... 122
8.5 Sample control schematic for customer-supplied MDP............................................................................................... 124
Revision History........................................................................................................................................ 125
5538858-1EN Revision 4 SIGNA™ Prime 4/126
Preinstallation Manual

Language Policy

DOC0371395 - Global Language Procedure
ПРЕДУПРЕЖД ЕНИЕ
(BG)
警告
(ZH-CN)
警告
(ZH-HK)
警告
(ZH-TW)
UPOZORENJE (HR)
VÝSTRAHA (CS)
ADVARSEL (DA)
Това ръководство е налично само на китайски (ZH-CN), английски, френски, немски, японски, корейски, полски, португалски (PT-BR), руски, испански и виетнамски. Ако доставчикът на услуги на даден клиент изисква език, който е различен от тези езици, отговорност на клиента е да предостави преводачески услуги.
本手册仅提供中文 (ZH-CN)、英文、法语、德语、意大利语、日语、韩语、波兰语、葡萄牙语 (PT-BR)、俄语、西班牙语和越南语版本。如果客户的服务提供商需要其他语言,则客户有责任提
供翻译服务。
本手冊僅提供中文 (ZH-CN)、英文、法文、德文、意大利文、日文、韓文、波蘭文、葡萄牙文 (PT-BR)、俄文、西班牙文及越南文版本。如客戶的服務供應商需要這些語言以外的版本,則相關 客戶有責任提供有關的翻譯服務。
此手冊僅提供中文 (ZH-CN)、英文、法文、德文、義大利文、日文、韓文、波蘭文、葡萄牙文 (PT-BR)、俄文、西班牙文和越南文版本。假如客戶的服務提供者所需語言版本不在所列語言之 中,客戶需自行負責提供翻譯服務。
Ovaj je priručnik dostupan samo na kineskom (ZH-CN), engleskom, francuskom, njemačkom, talijan­skom, japanskom, korejskom, poljskom, portugalskom (PT-BR), ruskom, španjolskom i vijetnamskom jeziku. Ako klijentov serviser zahtijeva jezik koji nije jedan od tih jezika, odgovornost je klijenta pružiti uslugu prevođenja.
Tato příručka je k dispozici pouze v čínštině (ZH-CN), angličtině, francouzštině, němčině, italštině, japonštině, korejštině, polštině, portugalštině (PT-BR), ruštině, španělštině a vietnamštině. Pokud pos­kytovatel služeb zákazníka vyžaduje jiný jazyk než tyto jazyky, je odpovědností zákazníka poskytovat překladatelské služby.
Denne vejledning ndes kun på kinesisk (ZH-CN), engelsk, fransk, tysk, italiensk, japansk, koreansk, polsk, portugisisk (PT-BR), russisk, spansk og vietnamesisk. Hvis en kundes tjenesteudbyder kræver et andet sprog end disse sprog, er det kundens ansvar at levere oversættelsestjenester.
WAAR­SCHUWING
(NL)
WARNING (EN)
HOIATUS (ET)
VAROITUS (FI)
ATTENTION (FR)
WARNUNG (DE)
Deze handleiding is alleen beschikbaar in het Chinees (ZH-CN), Engels, Frans, Duits, Italiaans, Japans, Koreaans, Pools, Portugees (PT-BR), Russisch, Spaans en Vietnamees. Als de serviceprovider van een klant een andere taal dan deze talen vereist, is het de verantwoordelijkheid van de klant om vertaalservices te leveren.
This manual is available in Chinese (ZH-CN), English, French, German, Italian, Japanese, Korean, Polish, Portuguese (PT-BR), Russian, Spanish, and Vietnamese only. If a customer's service provider requires a language other than these languages, it is the customer's responsibility to provide translation services.
See juhend on saadaval ainult hiina (ZH-CN), inglise, prantsuse, saksa, itaalia, jaapani, korea, poola, portugali (PT-BR), vene, hispaania ja vietnami keeles. Kui kliendi teenusepakkujal on vaja juhendit mõnes muus keeles, on tõlketeenuste osutamine kliendi kohustus.
Tämä opas on saatavilla vain kiinaksi (ZH-CN), englanniksi, ranskaksi, saksaksi, italiaksi, japaniksi, kore­aksi, puolaksi, portugaliksi (PT-BR), venäjäksi, espanjaksi ja vietnamiksi. Jos asiakkaan palveluntarjoaja edellyttää muuta kuin näitä kieliä, käännöspalveluiden tarjoaminen on asiakkaan vastuulla.
Ce manuel est disponible uniquement en allemand, anglais, chinois (ZH-CN), coréen, espagnol, français, italien, japonais, polonais, portugais (PT-BR), russe et vietnamien. Si le prestataire de services d'un client nécessite que le manuel soit rédigé dans une autre langue que celles mentionnées ci-dessus, il incombe au client de le faire traduire.
Dieses Handbuch ist nur auf Chinesisch (ZH-CN), Englisch, Französisch, Deutsch, Italienisch, Japanisch, Koreanisch, Polnisch, Portugiesisch (PT-BR), Russisch, Spanisch und Vietnamesisch verfügbar. Wenn ein Dienstleister des Kunden dieses in einer anderen Sprache als die genannten benötigt, liegt es in der Verantwortung des Kunden, Übersetzungsdienstleistungen zu erbringen.
5538858-1EN Revision 4 SIGNA™ Prime 5/126
Preinstallation Manual
ΠΡΟΕΙΔΟΠΟΙ ΗΣΗ
(EL)
FIGYELMEZ­TETÉS
(HU)
AÐVÖRUN (IS)
AVVERTENZA (IT)
警告
(JA)
경고
(KO)
Αυτό το εγχειρίδιο είναι διαθέσιμο μόνο σε Κινεζικά (ZH-CN), Αγγλικά, Γαλλικά, Γερμανικά, Ιταλικά, Ιαπωνικά, Κορεατικά, Πολωνικά, Πορτογαλικά (PT-BR), Ρωσικά, Ισπανικά και Βιετναμέζικα. Εάν ο πάροχος υπηρεσιών ενός πελάτη απαιτεί γλώσσα που δεν συμπεριλαμβάνεται σε αυτές τις γλώσσες, αποτελεί ευθύνη του πελάτη να παρέχει υπηρεσίες μετάφρασης.
Ez a kézikönyv az alábbi nyelveken érhető el: angol, francia, japán, kínai (ZH-CN), koreai, lengyel, német, olasz, orosz, portugál (PT-BR), spanyol és vietnámi. Ha az ügyfél szolgáltatója ezektől eltérő nyelvű kézikönyvet szeretne, akkor az ügyfél feladata, hogy gondoskodjon a megfelelő fordításról.
Þessi handbók er aðeins fáanleg á kínversku (ZH-CN), ensku, frönsku, þýsku, ítölsku, japönsku, kóresku, pólsku, portúgölsku (PT-BR), rússnesku, spænsku og víetnömsku. Ef þjónustuaðili viðskiptavinar þarf­nast annars tungumáls en þessara tungumála er það á ábyrgð viðskiptavinarins að veita þýðingarþjó­nustu.
Questo manuale è disponibile solo in lingua cinese (ZH-CN), inglese, francese, tedesco, italiano, giap­ponese, coreano, polacco, portoghese (PT-BR), russo, spagnolo e vietnamita. Qualora un fornitore di servizi del cliente richieda una lingua diversa dall'inglese, sarà responsabilità del cliente fornire il servizio di traduzione corrispondente.
このマニュアルは、中国語 (ZH-CN)、英語、フランス語、ドイツ語、イタリア語、日本語、韓 国語、ポーランド語、ポルトガル語 (PT-BR)、ロシア語、スペイン語、およびベトナム語のみ で提供されています。お客様のサービスプロバイダがこれらの言語以外の言語を必要とする 場合は、お客様の責任において翻訳サービスを提供してください。
이 설명서는 중국어(중국어-중국), 영어, 프랑스어, 독일어, 이탈리아어, 일본어, 한국어, 폴란드어, 포르투갈어(포르투갈어-브라질), 러시아어, 스페인어, 베트남어로만 제공됩니다. 고객의 서비스 제공자가 이 언어를 제외한 다른 언어를 요구하는 경우, 번역 서비스를 제공하는 것은 고객의 책임입니다.
BRĪDINĀJUMS (LV)
ĮSPĖJIMAS (LT)
ADVARSEL (NO)
OSTRZEŻENIE (PL)
ATENÇÃO (PT-BR)
ATENÇÃO (PT-PT)
ATENŢIE (RO)
Šī rokasgrāmata ir pieejama tikai ķīniešu (ZH-CN), angļu, franču, vācu, itāliešu, japāņu, korejiešu, poļu, portugāļu (PT-BR), krievu, spāņu un vjetnamiešu valodā. Ja klientu apkalpošanas speciālistam ir nepieciešama cita valoda, kas atšķiras no šeit norādītajām, klienta pienākums ir nodrošināt tulkošanas pakalpojumus.
Šis vadovas pateikiamas tik kinų (ZH-CN), anglų, prancūzų, vokiečių, italų, japonų, korėjiečių, lenkų, portugalų (PT-BR), rusų, ispanų ir vietnamiečių kalbomis. Jei klientų paslaugų teikėjui reikalinga kita nei šios kalba, už vertimo paslaugų suteikimą atsako klientas.
Denne håndboken er bare tilgjengelig på kinesisk (ZH-CN), engelsk, fransk, tysk, italiensk, japansk, ko­reansk, polsk, portugisisk (PT-BR), russisk, spansk og vietnamesisk. Hvis en kundes tjenesteleverandør krever et annet språk, er det kundens ansvar å levere en oversettelsestjeneste.
Niniejsza instrukcja jest dostępna wyłącznie w języku chińskim (ZH-CN), angielskim, francuskim, nie­mieckim, włoskim, japońskim, koreańskim, polskim, portugalskim (PT-BR), rosyjskim, hiszpańskim i wietnamskim. Jeśli usługodawca klienta wymaga języka, który nie został wymieniony powyżej, obo­wiązkiem klienta jest zapewnienie usług tłumaczeniowych.
Este manual está disponível somente em chinês (ZH-CN), inglês, francês, alemão, italiano, japonês, coreano, polonês, português (PT-BR), russo, espanhol e vietnamita. Se o prestador de serviços de um cliente necessitar de um idioma diferente dos mencionados, o fornecimento dos serviços de tradução é de responsabilidade do cliente.
Este manual está disponível apenas em alemão, chinês (ZH-CN), coreano, espanhol, francês, inglês, italiano, japonês, polaco, português (PT-BR), russo e vietnamita. Se o fornecedor de serviços de um cliente necessitar de um idioma diferente dos listados aqui, é da responsabilidade do cliente assegurar os serviços de tradução.
Acest manual este disponibil numai în limbile chineză (ZH-CN), engleză, franceză, germană, italiană, japoneză, coreeană, poloneză, portugheză (PT-BR), rusă, spaniolă şi vietnameză. Dacă furnizorul de servicii al unui client solicită o limbă diferită faţă de aceste limbi, este responsabilitatea clientului să furnizeze servicii de traducere.
5538858-1EN Revision 4 SIGNA™ Prime 6/126
Preinstallation Manual
ОСТОРОЖНО! (RU)
UPOZORENJE (SR)
UPOZORNE­NIE
(SK)
ATENCIÓN (ES)
VARNING (SV)
OPOZORILO (SL)
Настоящее руководство доступно только на китайском (ZH-CN), английском, французском, немецком, итальянском, японском, корейском, польском, португальском (PT-BR), русском, испанском и вьетнамском языках. Если поставщику услуг заказчика требуется руководство на каком-либо другом языке, перевод руководства на необходимый язык осуществляется стороной заказчика.
Ovaj priručnik dostupan je samo na kineskom (ZH-CN), engleskom, francuskom, nemačkom, italijan­skom, japanskom, korejskom, poljskom, portugalskom (PT-BR), ruskom, španskom i vijetnamskom jeziku. Ako korisnik kao pružalac usluge zahteva neki drugi jezik od navedenih, njegova je dužnost da obezbedi prevod.
Táto príručka je dostupná len v nasledovných jazykoch: čínština (ZH-CN), angličtina, francúzština, nem­čina, taliančina, japončina, kórejčina, poľština, portugalčina (PT-BR), ruština, španielčina a vietnamčina. Ak poskytovateľ služieb daného zákazníka požaduje iný ako tieto jazyky, za poskytnutie prekladateľ­ských služieb zodpovedá zákazník.
Este manual está disponible solo en chino (ZH-CN), inglés, francés, alemán, italiano, japonés, coreano, polaco, portugués (PT-BR), ruso, español y vietnamita. Si el proveedor de servicios de un cliente requiere un idioma distinto de estos idiomas, es responsabilidad del cliente proporcionar los servicios de traducción.
Den här manualen nns endast tillgänglig på kinesiska (ZH-CN), engelska, franska, tyska, italienska, japanska, koreanska, polska, portugisiska (PT-BR), ryska, spanska och vietnamesiska. Om en kunds tjänsteleverantör behöver ett annat språk än dessa är det kundens ansvar att ordna med översätt­ningstjänster.
Ta priročnik je na voljo v kitajščini (ZH-CN), angleščini, francoščini, nemščini, italijanščini, japonščini, ko­rejščini, poljščini, portugalščini (PT-BR), ruščini, španščini in vietnamščini. Če kupčev ponudnik storitev potrebuje drug jezik, mora za prevod poskrbeti kupec.
DİKKAT (TR)
ЗАСТЕРЕЖЕН НЯ
(UK)
Bu kılavuz yalnızca Çince (ZH-CN), İngilizce, Fransızca, Almanca, İtalyanca, Japonca, Korece, Lehçe, Portekizce (PT-BR), Rusça, İspanyolca ve Vietnamca dillerinde mevcuttur. Müşteri servis sağlayıcısı bu dillerden başka bir dil talep ederse çeviri hizmeti sağlamak müşterinin sorumluluğundadır.
Цей посібник доступний лише китайською (ZH-CN), англійською, французькою, німецькою, італійською, японською, корейською, польською, португальською (PT-BR), російською, іспанською та в’єтнамською мовами. Якщо постачальник послуг замовника використовує мову, яку не вказано у цьому переліку, послуги з перекладу має забезпечити замовник.
5538858-1EN Revision 4 SIGNA™ Prime 7/126

1 Introduction

1.1 Preinstall Manual Introduction

1.1.1 Document Purpose

This preinstallation manual provides the necessary information to prepare a site for system installation. Specically, this manual provides information:
1. To dene system requirements and interactions.
2. For the eective arrangement and interconnection of system components.
3. The customer is responsible for:
a. Compliance with all local and national codes and regulations
1
(Applies to all subsections within this section)
b. Siting requirements for customer-specic site procedures (medical, MR, safety, and so on)
c. Any special architectural requirements (for example, seismic codes)
The implementation of all requirements and adherence to all specications in this manual is the responsibility of the customer or its architect and engineers. Refer any questions to the GE Healthcare Project Manager of Installation (PMI).

1.1.2 Intended User

The primary users of this manual are the customer, the customer's architectural planner, and/or the customer's contractors.
5538858-1EN Revision 4 SIGNA™ Prime 8/126
Preinstallation Manual 1.1 Preinstall Manual Introduction

1.1.3 Who Should Read This Manual

The following personnel must be aware of the content listed in the following sections:
Table 1-1 Personnel Index
Section Personnel
RF
Architect
1.1 Preinstall Manual Introduction x x x x x x x
General
Contractor
Customer
Electrician
Plumber
HVAC
Vendor
2.1 System Level Requirements for In­stalling into Existing MR Suite
2.2 System components x x
2.3 MR Suite Minimum Room Size Re­quirements
2.4 MR System Seismic Requirements x x
2.5 Structure-borne Vibration Control
Specications
2.6 MR Suite Magnetic Field Specica­tions
2.7 Multiple MR System Requirements x
2.8 MR Suite Temperature and Humidi­ty
2.9 Facility Coolant Requirements x x x x
2.10 MR Suite Electrical Requirements x x
2.11 MR System Shipping and Receiving x
3.1 Magnet Room Introduction x x
3.2 Magnet Room Structural Require­ments
x x
x
x
x x
x x x x
x
3.2.1 Overview x
3.2.2 Environmental Steel Limits x
3.2.3 Vibration Requirements x x x
3.3 Magnetic Shielded Room Require­ments
3.4 Integrated System Cabinet (ISC) and Penetration Panel (PP) Wall Opening Requirements
3.5.1 Ferrous Materials in the Magnet Room
5538858-1EN Revision 4 SIGNA™ Prime 9/126
x
x x x
x x x
Preinstallation Manual 1.1 Preinstall Manual Introduction
Table 1-1 Personnel Index (Table continued)
Section Personnel
RF
Architect
3.5.2 Walls x
3.5.3 Magnet Preinstallation Markings x
General
Contractor
Customer
HVAC
Plumber
Electrician
Vendor
3.5.4 Doors, Magnet Access Openings, and Patient Viewing Windows
3.5.5 Finished Ceiling x
3.5.6 Magnet Room Floors x x
3.5.7 Storage Cabinets x x
3.6 Magnet Room Equipment Specica-
tions
3.7 Magnet Room Lighting Require­ments
4 Equipment Room chapter x x
5 Control Room chapter x x
6 Digital Service and Connectivity chap­ter
7.1 MR System Interconnects Specica-
tions
7.2 MR System Interconnects Routing Requirements
7.3 Facility-Supplied System Intercon­nects Specications
x
x x
x x
x x
x x x
x x x
x x x x x
8.1 Glossary x x x x x x x
8.2 MR Site Vibration Test Guidelines x
8.3 Sample Calculation AC Power Equipment Minimum Distance
8.4 Selecting Anchor Size x x
8.5 Sample control schematic for cus­tomer-supplied MDP
x
x x

1.1.4 Related Publications

The preinstallation requirements in the following publications are applicable to all systems. This document and all documents referenced herein shall be provided to the Responsible Organization or Operator as a supplement to the product instructions for use and/or technical description.
5538858-1EN Revision 4 SIGNA™ Prime 10/126
Preinstallation Manual 1.1 Preinstall Manual Introduction
Table 1-2 Additional Preinstallation Requirements
Publication
Number
5850262-
5850261-
5850263-
5850260-
1
XXX is the language indicator of the manual
XXX
XXX
XXX
XXX
1
Acoustic Room Details
International Electrotechnical Commission (IEC) Electro­magnetic Compatibility (EMC)
Magnet Room Venting
RF Shielded Room

1.1.5 Document Overview

Title
Personnel who must be aware of the
content
This manual describes requirements and specications for the following:
1. General system requirements that apply to the entire MR suite
2. Shipping and delivery
3. Magnet Room
4. Equipment Room
5. Control Room
6. Interconnects within and between the rooms listed above
5538858-1EN Revision 4 SIGNA™ Prime 11/126
Preinstallation Manual 1.2 Symbols Key

1.2 Symbols Key

Table 1-3 Symbols Key
Symbol/Unit Denition
Center of gravity
Magnet isocenter
Service area
Airow
Space for airow and cables
Valve
5538858-1EN Revision 4 SIGNA™ Prime 12/126

2 General System Level

2.1 System Level Requirements for Installing into Existing MR Suite

When planning for the installation of this system in an existing GE Healthcare MR suite or a non-GE Healthcare MR suite, all requirements in this manual must be met because these rooms are considered new installations.
1. If the existing MR suite contains a GE system, the vibration environmental assessment must be done using the High Speed (magnetic eld) Stability tool.
NOTE
The customer may have to hire a vibration consultant based on the results of the analysis.
2
2. Structural vibration levels may be higher at some frequencies than other MR Systems, which may increase acoustic levels. Refer to 2.5 Structure-borne Vibration Control Specications on page 22.
3. The VibroAcoustic damping kit must be surface mounted (if the oor is recessed, it must be lled in and level).
4. Ensure the existing Magnet Room size meets the minimum room size requirement and there is enough space left for service at both sides of the magnet. Refer to MR Suite Minimum Room Size
Requirements on page 17.
5. RF vendor responsibilities:
a. The old dock anchor cannot be reused. It must be removed and the hole lled in. The new
anchor is reset after the magnet is installed. For upgrades that reuse the existing magnet, contact the PMI for further details about the potential reuse of the old dock anchor.
b. Two penetration panel openings are required and must meet the requirements in: RF Shielded
Room Requirements, 5850260.
c. RF shield attenuation must comply with: RF Shielded Room Requirements, 5850260
6. Cryogen vent may need to be relocated to align with the Magnet Cryogen Vent opening. The cryogen vent must meet all cryogen venting requirements (see Magnet Room Venting Requirements,
5850263).
5538858-1EN Revision 4 SIGNA™ Prime 13/126
Preinstallation Manual

2.2 System components

(Applies to all subsections within this section)
This system consists of the following components:

2.2.1 Magnet Room

1. 1.5T Magnet and Magnet Enclosure (MAG) and Vibroacoustic Damping Kit
2. Rear Pedestal (PED)
3. Patient Table (PT)
4. Magnet Rundown Unit (MRU)
NOTE
An optional remote MRU may be located outside the Magnet Room.
2.2 System components
5. Optional: Remote Oxygen Sensor Module (OM2)

2.2.2 Equipment Room

1. Main Disconnect Panel (MDP) (GE or customer-supplied in some regions)
2. Integrated System Cabinet (ISC)
3. Integrated Cooling Cabinet (ICC) (For Type B)
4. Penetration Panel (PP)
5. Cryocooler Compressor Cabinet (CRY)
6. 18 kW Chiller (LCS18) (For Type D)
7. Magnet Monitor (MON)

2.2.3 Control Room

1. Operator Workspace equipment (OW)
2. Pneumatic Patient Alert System (PA1)
3. Optional: Oxygen Monitor (OXY)

2.2.4 Accessories

1. Patient accessories, including RF coils, phantoms, cushions, sponges, straps, and wedges
2. Gating accessories, including patient cardiac leads, peripheral gating probe, and respiratory bellows
5538858-1EN Revision 4 SIGNA™ Prime 14/126
MAG
OXY
ISC
ICC
MRU
MDP
MON
PP
OW
PA1
Preinstallation Manual

2.2.5 System Overview

Figure 2-1 System Overview for Type B
2.2 System components
NOTE
OXY shown above is an optional component of the system.
5538858-1EN Revision 4 SIGNA™ Prime 15/126
MAG
OW
PA1
OXY
ISC
PP
MRU
MDP
MON
CRY
LCS18
Preinstallation Manual
Figure 2-2 System Overview for Type D
2.2 System components
NOTE
OXY shown above is an optional component of the system.
5538858-1EN Revision 4 SIGNA™ Prime 16/126
Preinstallation Manual

2.3 MR Suite Minimum Room Size Requirements

2.3 MR Suite Minimum Room Size Requirements
Room dimensions shown in the table below are the minimum nished room space requirements to safely install and service the MR System. Minimum dimensions are for service only. Room size may grow due to the items listed below, which are not included in the minimum area dimensions:
1. Building code requirements (for example, exit routes, door placement, seismic mounting requirements, local and national electrical codes, and so on).
2. Equipment and Magnet Room evacuation routes to comply with facility emergency procedures.
3. System requirements, including cable run locations, cryogen venting, patient observation requirements, and penetration panel placements.
4. Penetration panel closet and all associated areas.
5. GE optional equipment.
6. Non-GEHC equipment options (such as additional AC or water cooling equipment in the Equipment Room).
7. Clinical workow considerations.
8. Accessory storage. Refer to Customer Site Storage Requirements, 5182674 (available in the Customer Documentation Portal), or contact the GE Healthcare Project Manager of Installation (PMI) for any additional accessory storage requirements.
9. Magnetic eld containment, for example, the 5 gauss line to the room. If fringe eld containment is needed, see 2.6 MR Suite Magnetic Field Specications on page 24.
Table 2-1 Room Dimensions to Satisfy Recommended Minimum Service Area Requirements
Congu-
ration
Type B (ICC con-
guration)
Equipment Room
W x D
mm (in)
1826 x 2635
(71.9 x
103.7 )
Area
m2 (ft2)
4.81 (51.8)
1
Finished
Ceiling Height
mm (in)
2355 (92.7)
W x D
mm (in)
Long scan range:
3645 x 5802
(143.5 x
228.4)
Magnet Room
Area
m2 (ft2)
Long scan range:
18.8 (202.2)
2
Finished
Ceiling Height
mm (in)
2500 (98.4)
Control Room Total
W x D
mm (in)
1520 x 2130
(59.8 x
83.9)
Area
m2 (ft2)
3.24 (34.9)
System
Area
Area
m2 (ft2)
Long scan range:
26.9 (289.5)
5538858-1EN Revision 4 SIGNA™ Prime 17/126
Preinstallation Manual
Table 2-1 Room Dimensions to Satisfy Recommended Minimum Service Area Requirements (Table continued)
2.3 MR Suite Minimum Room Size Requirements
Congu-
ration
Type D (18KW chiller
congura­tion)
Equipment Room
W x D
mm (in)
1928 x 2697
(75.9 x
106.8)
Area
m2 (ft2)
5.2 (55.9)
1
Finished
Ceiling Height
mm (in)
W x D
mm (in)
Long scan range:
3645 x 5802
Magnet Room
Area
m2 (ft2)
Long scan range:
18.8 (202.2)
2
Finished
Ceiling Height
mm (in)
Control Room Total
W x D
mm (in)
1520 x 2130
Area
m2 (ft2)
3.24 (34.9)
(59.8 x
83.9)
System
m2 (ft2)
Long scan range:
27.2 (292.8)
(143.5 x
228.4)
1
See Figure 4-1 Typical Minimum Equipment Room with Service Clearances (Type B) on page 81 or Figure 4-2 Typical
Minimum Equipment Room with Service Clearances (Type D) on page 82 for specic dimensions.
2
See Figure 2-3 Recommended Minimum Magnet Service Area (Top View) on page 19 for specic dimensions.
Table 2-2 Room Dimensions to Satisfy Absolute Minimum Service Area Requirements
Congura-
tion
Equipment Room
1
Magnet Room
2
Control Room Total
System
Area
Area
Area
W x D
mm (in)
Type B (ICC
conguration)
1826 x 2635
(71.9 x
103.7 )
Type D (18KW chiller
conguration)
1928 x 2697
(75.9 x
106.8)
1
See Figure 4-1 Typical Minimum Equipment Room with Service Clearances (Type B) on page 81 or Figure 4-2 Typical
Area
m2 (ft2)
4.81 (51.8)
5.2 (55.9)
Finished
Ceiling Height
mm (in)
2355 (92.7)
W x D
mm (in)
Long scan range: 3368
x 5518 (132.6 x
217.2)
Short scan range: 3368
x 5425 (132.6 x
213.6)
Area
m2 (ft2)
Long scan range:
15.49 (166.7)
Short scan range:
15.24 (164.0)
Finished
Ceiling Height
mm (in)
2500 (98.4)
W x D
mm (in)
1520 x 2130
(59.8 x
83.9)
Area
m2 (ft2)
3.24 (34.9)
Area
m2 (ft2)
23.72 (255.3)
24.15 (259.9)
Minimum Equipment Room with Service Clearances (Type D) on page 82 for specic dimensions.
2
See Figure 2-5 Smallest Permissible Area for Minimum Magnet Ceiling Height (Top View) on page 21 and Minimum
equipment Ceiling Height for specic dimensions.
1. The center of the magnet must be located within the Magnet Room to keep the minimum service area described in Figure 2-4 Absolute Minimum Magnet Service Area (Top View) on page 20.
2. Minimum Equipment Room height from nished oor to suspended ceiling is 2355 mm (92.7 in.). For Type D conguration, if the ceiling height is between 2355mm (92.7 in.) and 2500mm (98.4 in.), a duct should be provided by local vender. See Figure 4-13 Duct (Option 1) on page 94 and Figure
4-14 Duct (Option 2) on page 95.
5538858-1EN Revision 4 SIGNA™ Prime 18/126
5802
mm
(
228.4
in)
2769 mm
(109 in)
3784 mm
(149 in)
2312
mm
(
91
in)
2018 mm
(79.4 in)
1156
mm
(
45.5
in)
1156
mm
(
45.5
in)
3645
mm
(
143.5
in)
1854
mm
(
73
in)
1791
mm
(
70.5
in)
1346 mm
(53 in)
1521 mm
(59.9 in)
1778 mm
(70 in)
635
mm
(
25
in)
497
mm
(
19.6
in)
497
mm
(
19.6
in)
699
mm
(
27.5
in)
1521 mm
(59.9 in)
Preinstallation Manual
3. Ideal Magnet Room height from nished oor to suspended ceiling is 2667 mm (105 in). Minimum Magnet Room suspended ceiling height is 2500 mm (98.5 in).
Figure 2-3 Recommended Minimum Magnet Service Area (Top View)
2.3 MR Suite Minimum Room Size Requirements
5538858-1EN Revision 4 SIGNA™ Prime 19/126
497
mm
(
19.6
in)
1854 mm
(73 in)
3368 mm
(132.6 in)
800 mm
(31.5 in)
1550 mm
(61 in)
1550 mm
(61 in)
900 mm
(35.4 in)
900 mm
(35.4 in)
396 mm (15.6 in)
1989 mm
(78.3 in)
3500 mm
(137.8 in)
1
2
3
Preinstallation Manual 2.3 MR Suite Minimum Room Size Requirements
Figure 2-4 Absolute Minimum Magnet Service Area (Top View)
Item Description
1 5425 mm (213.6 in.) - Short scan range
5518 mm (217.2 in.) - Long scan range
2 100 mm (3.9 in.) - Short scan range
193 mm (7.6 in.) - Long scan range
3 1428 mm (56.2 in.) - Short scan range
1521 mm (59.9 in.) - Long scan range
5538858-1EN Revision 4 SIGNA™ Prime 20/126
1514 mm
(59.6 in)
1854 mm
(73 in)
1524 mm
(60 in)
1524 mm
(60 in)
Preinstallation Manual 2.4 MR System Seismic Requirements
Figure 2-5 Smallest Permissible Area for Minimum Magnet Ceiling Height (Top View)
NOTE
If the ceiling height is between 2500 mm (98.5 in) and 2667 mm (105 in), the exible main lead extension for low ceiling height (2.5M Low Ceiling Kit-Passive, M7000GM) is required for ramping the magnet. Contact the GE PMI and GE Service Field Engineer for further evaluation.
4. The minimum service area shown must be kept clear of permanent or installed cabinetry, the MRU, the penetration closet, millwork, shelving, coil storage xtures, furniture, and so on.
5. The ceiling service area should be kept clear of overhead items, including sots, HVAC, plumbing components, and brackets. Permanent or installed objects in this area may prevent or delay magnet service or operation.

2.4 MR System Seismic Requirements

Contact the Project Manager of Installation with any questions.
1. The customer is responsible for seismic anchoring of GE components.
2. Center of gravity, weight, physical dimensions, and attachment points are provided for seismic calculations. Refer to the specications or illustrations for each component (see Magnet
Room Equipment Specications on page 74, Equipment Room on page 80, and Control Room on page 98 ).
5538858-1EN Revision 4 SIGNA™ Prime 21/126
Preinstallation Manual 2.5 Structure-borne Vibration Control Specications
2.5 Structure-borne Vibration Control Specications
Structure-borne acoustic issues tend to occur at MR installations above the ground oor of the facility. Two options to mitigate structure-borne acoustic transmission are:
1. GE Healthcare provides a VibroAcoustic Damping kit (which must be surface mounted). Contact the GE Healthcare Project Manager of Installation for information.
2. The customer may design and implement a custom solution in addition to the VibroAcoustic Damping kit. See Figure 2-6 Vibration Transmitted through VibroAcoustic Mat on page 22 for the plot of spectral vibration transmitted through the VibroAcoustic mat into the oor. If required, the customer should consult an acoustic engineer for a solution to further attenuate this transmitted vibration).
NOTE
The amount of vibration attenuation provided by the VibroAcoustic Damping kit will be site dependent.
Figure 2-6 Vibration Transmitted through VibroAcoustic Mat
1
2
Item
1
2 1/3 Octave Band [Hz]
5538858-1EN Revision 4 SIGNA™ Prime 22/126
Description
Acceleration [m/s2]
Vibration Amplitude (m/s2)
10
20
30 40
50
60
Frequency (Hz)
0
0.05
0.1
0.15
0.2
0.25
0.3
0
0.35
0.4
Preinstallation Manual
Figure 2-7 Low Frequency Magnet Floor Vibration (Vibration Amplitude at Each Foot)
2.5 Structure-borne Vibration Control Specications
Freq (Hz)
Amplitude (m/s2)
2 0.05
10 0.05
20 0.35
30 0.35
35 0.20
50 0.20
Low Frequency Magnet Floor Vibration Notes:
NOTE
1. Illustrations above dene the potential vibration level that may pass into the customer site. Figure 2-6 Vibration Transmitted through VibroAcoustic Mat on page 22 is the high frequency audible vibration. Figure 2-7 Low Frequency Magnet Floor Vibration (Vibration
Amplitude at Each Foot) on page 23 is low frequency vibration that may dynamically
displace the oor.
2. Vibration transfer may be the result of customer specic building construction as low levels of vibration transmit into the building through airborne and structure-borne paths. Customer MR clinicians recognize the vibration dened in the tables is typically short bursts of vibration repeated multiple times as the scan progresses.
3. The customer should consider the impact of this vibration for the evaluation and design solution.
5538858-1EN Revision 4 SIGNA™ Prime 23/126
Preinstallation Manual 2.6 MR Suite Magnetic Field Specications
2.6 MR Suite Magnetic Field Specications
(Applies to all subsections within this section)

2.6.1 Magnetic Fringe Field

The following illustrations show the static magnet isogauss plot lines for the magnet. This information must be used to evaluate potential site interaction of GE Healthcare equipment with other non-GE Healthcare equipment, interaction with ferrous materials on the site, and to locate personnel and equipment within the site.
The 0.5 mT (5G) line can expand to 4.5 m (14.76 ft.) axially and 3.5 m (11.48 ft.) radially for up to 1 second in the rare event of a quench.
The isogauss plots show an idealized magnetic eld relative to magnet isocenter. The actual eld strength can be aected by any of the following:
Magnetic shielding
Earth's magnetic eld
Other magnetic elds
Stationary or moving metal
5538858-1EN Revision 4 SIGNA™ Prime 24/126
Preinstallation Manual 2.6 MR Suite Magnetic Field Specications
Figure 2-8 Magnetic Fringe Field Side View (PM Series)
6000 mm
(236 in)
4000 mm
(157 in)
2000 mm
(79 in)
2000 mm
(79 in)
4000 mm
(157 in)
6000 mm
(236 in)
8000 mm
(315 in)
6000 mm
(236 in)
4000 mm
(157 in)
2000 mm
(79 in)
1
2000 mm
(79 in)
4000 mm
(157 in)
6000 mm
(236 in)
8000 mm
(315 in)
Item Description
1 Magnet isocenter
5538858-1EN Revision 4 SIGNA™ Prime 25/126
Preinstallation Manual 2.6 MR Suite Magnetic Field Specications
Figure 2-9 Magnetic Fringe Field Top View (PM Series)
6000 mm
(236 in)
4000 mm
(157 in)
2000 mm
(79 in)
2000 mm
(79 in)
4000 mm
(157 in)
6000 mm
(236 in)
8000 mm
(315 in)
6000 mm
(236 in)
4000 mm
(157 in)
2000 mm
(79 in)
1
2000 mm
(79 in)
4000 mm
(157 in)
6000 mm
(236 in)
8000 mm
(315 in)
Item Description
1 Magnet isocenter
5538858-1EN Revision 4 SIGNA™ Prime 26/126
6000 mm
(236 in)
200mT
(2000G)
40mT
(400G)
20mT
(200G)
10mT
(100G)
5mT
(50G)
3mT
(30G)
1mT
(10G)
0.5mT (5G)
0.3mT (3G)
0.1mT (1G)
0.05mT (0.5G)
6000 mm
(236 in)
6000 mm
(236 in)
6000 mm
(236 in)
4000 mm
(157 in)
4000 mm
(157 in)
4000 mm
(157 in)
4000 mm
(157 in)
2000 mm
(79 in)
2000 mm
(79 in)
2000 mm
(79 in)
0
0
2000 mm
(79 in)
Preinstallation Manual 2.6 MR Suite Magnetic Field Specications
Figure 2-10 Magnetic Fringe Field Front View (PM Series)
Item Description
1 Magnet isocenter

2.6.2 Interference from Changing Magnetic Fields

Metal objects moving within the magnet sensitivity lines can produce a eld disturbance during clinical imaging. If the metal object is moving it will produce a uctuating dipole type of eld which causes image artifacts. As an example, a car driven inside the moving metal line will act as a dipole and produce a time varying eld which changes the magnet's main eld during the scanning. The same vehicle may park within the moving metal line and remain parked during clinical scanning without impact to the main
eld.
5538858-1EN Revision 4 SIGNA™ Prime 27/126
Preinstallation Manual
Figure 2-11 Magnet Moving Metal Sensitivity Line Plot (Side View, PM series magnet)
2.6 MR Suite Magnetic Field Specications
6 m (236 in)
1
5 m (197 in)
2
4 m (157 in)
4
3 m (118 in)
8 m
(315 in)
7 m
(276 in)
6 m
(236 in)
5 m
(197 in)
4 m
(157 in)
3
(118 in)
3 m
2 m
(79 in)
2 m (79 in)
2 m
(79 in)
3 m
(118 in)
4 m
(157 in)
5 m
(197 in)
6 m
(236 in)
7 m
(276 in)
8 m
(315 in)
5
2 m (79 in)
3 m (118 in)
4 m (157 in)
5 m (197 in)
6 m (236 in)
Item Description Item Description
1 Trucks, Buses 4 Floor Above
2 Cars, Pickups, Vans, Ambulances 5 Magnet Room Floor
3 3 Gauss line 6 Floor Below
NOTE
The magnet isocenter, which is 1070 mm (42.1 in.) above the oor, is the origin of both the x-axis and the y-axis.
6
5538858-1EN Revision 4 SIGNA™ Prime 28/126
Preinstallation Manual 2.6 MR Suite Magnetic Field Specications
Figure 2-12 Magnet Moving Metal Sensitivity Line Plot (Top View , PM series )
6 m (236 in)
1
5 m (197 in)
2
4 m (157 in)
3 m (118 in)
8 m
(315 in)
7 m
(276 in)
6 m
(236 in)
5 m
(197 in)
4 m
(157 in)
3
3 m
(118 in)
2 m
(79 in)
2 m (79 in)
2 m
(79 in)
3 m
(118 in)
4 m
(157 in)
5 m
(197 in)
6 m
(236 in)
7 m
(276 in)
8 m
(315 in)
2 m (79 in)
3 m (118 in)
4 m (157 in)
4
5 m (197 in)
6 m (236 in)
Item Description Item Description
1 Trucks, Buses 3 3 Gauss line
2 Cars, Pickups, Vans, Ambulances 4 Center of Driving Lane
Table 2-3 Magnet Moving Metal Requirements
Metal Objects Cat-
egory
Objects 45.36 -
181.44 kg (100 - 400 lb.)
Cars, Minivans, Vans, Pickup Trucks, Ambulances
Bus, Trucks (Utility, Dump, Semi)
Objects > 181.44 kg (400 lb.), Elevators, Trains, Subways
Denition Of Distance Location
Distance from isocenter radial x axial 0.3 mT (3 G) line
Distance from isocenter measured to center of driving or parking lane radial x axial
Distance from isocenter measured to center of driving or parking lane radial x axial
Place a directional probe (for example, ux gate sensor) at isocenter of proposed mag­net location aligned along the Z-axis. Measure peak-to-peak magnetic eld change (DC).
Magnet Minimum Distance Radial X Axial
m (ft.)
4.72 x 6.40 (15.5 x 21)
5.52 x 7.47 (18.1 x 24.5)
See Note 2 below
1
5538858-1EN Revision 4 SIGNA™ Prime 29/126
Preinstallation Manual 2.6 MR Suite Magnetic Field Specications
Table 2-3 Magnet Moving Metal Requirements (Table continued)
Metal Objects Cat-
egory
Denition Of Distance Location
Magnet Minimum Distance Radial X Axial
m (ft.)
Notes:
1. Radial distances are magnet X and Y axis. Axial distances are magnet Z axis.
2. For PM magnet: EXAMPLE: For moving metal requirements of objects > 181.44 kg (400 lb.) category, you can use the time history of
the occurrence to determine what Tesla (Gauss) level to use.
a. If the site has elevators or counter weights near the magnet and the elevator can stop on the oors for longer
than 20 seconds (which is usually the case), the peak-to-peak reading (Z-axis disturbance) must be less than 618 nanotesla (6.18 milligauss).
b. If the site has a subway nearby and the eld disturbance is less than 2 seconds, the peak-to-peak Tesla (Gauss)
reading (Z-axis disturbance) must be less than 618 nanotesla (6.18 milligauss).
c. Use 618 nanotesla (6.18 milligauss) peak-to-peak.
1
5538858-1EN Revision 4 SIGNA™ Prime 30/126
20 30 40
6050
0
0
5
10
15
20
25
30
35
40
45
50
10
Excitation Frequency (Hz)
Miligauss
No Impact on Imaging
Preinstallation Manual

2.6.3 Electrical Current

1. Electrical current in high voltage power lines, transformers, motors, or generators near the magnet may aect magnetic eld homogeneity.
2. Magnetic eld interference at 50 or 60 Hz must not exceed 4 μT (40 mG) RMS at the magnet location (see Figure 2-13 Magnet Allowable Milligauss vs. Line Frequency for AC
Equipment on page 31).
3. The following equation can be used as a general guide in determining allowable current in feeder lines at a given distance from the magnet isocenter:
For 1.5T Magnet: I= (20X2)/S
a.
b. I = Maximum allowable RMS single phase current (in amps) or maximum allowable RMS line
current (in amps) in three phase feeder lines
c. S = Separation (in meters) between single phase conductors or greatest separation between
three phase conductors
d. X = Minimum distance (in meters) from the feeder lines to isocenter of the magnet
Figure 2-13 Magnet Allowable Milligauss vs. Line Frequency for AC Equipment
2.6 MR Suite Magnetic Field Specications
Refer to Sample Calculation AC Power Equipment Minimum Distance on page 121 for additional examples.
5538858-1EN Revision 4 SIGNA™ Prime 31/126
Preinstallation Manual 2.6 MR Suite Magnetic Field Specications

2.6.4 Non-MR System Equipment Sensitivity to Magnetic Fields

Site plans must include consideration for magnetic eld interaction with all customer equipment.
This section lists equipment known to be sensitive to high magnetic elds.
Use the table for reference only. The Tesla (Gauss) limits in the table are approximate for that type of equipment. Refer to OEM manuals for the equipment at your site to determine the actual Tesla (Gauss) limits.
Table 2-4 Magnetic Proximity Limits (For Reference Only)
mT (Gauss) Limit Equipment
0.05mT (0.5 G) Nuclear camera
0.1mT (1 G) Positron Emission Tomography scanner Video display (tube)
Linear Accelerator CT scanner
Cyclotrons Ultrasound
Accurate measuring scale Lithotriptor
Analog image intensiers Electron microscope
Bone Densitometers
0.3mT (3 G) Power transformers Main electrical distribution transformers
0.5mT (5 G) Cardiac pacemakers Biostimulation devices
Neurostimulators
1mT (10 G) Magnetic computer media Telephone switching stations
Hard copy imagers Water cooling equipment
Line printers HVAC equipment
Video Cassette Recorder (VCR) Major mechanical equipment room
Film processor Credit cards, watches, and clocks
X-ray tubes
Large steel equipment, including:
Emergency generators Air conditioning equipment
Commercial laundry equipment Fuel storage tanks
Food preparation area Motors greater than 5 horsepower
5mT (50 G) Metal detector for screening Telephones
LCD panels
No Limit Digital Detectors
5538858-1EN Revision 4 SIGNA™ Prime 32/126
Preinstallation Manual 2.7 Multiple MR System Requirements

2.7 Multiple MR System Requirements

(Applies to all subsections within this section)

2.7.1 Multiple Magnets

When installing multiple magnets, the 30 mT (3 G) lines must not intersect or the magnets will be interactive. Contact the GE Healthcare Project Manager of Installation (PMI) for any questions regarding magnetic eld interaction.
Figure 2-14 Two Magnet Installation (No Interaction)

2.7.2 Shared Equipment Rooms

When installing multiple MR Systems in a shared Equipment Room, of the same eld strength, the following conditions must be met:
1. The penetration panel of the other system must be separated from the penetration wall of the ISC by at least 3000 mm (118 in.).
2. Cables from dierent MR Systems must not be routed together.
3. Magnet Rooms cannot share walls.
4. Two systems cannot share common power or ground feeds.
5538858-1EN Revision 4 SIGNA™ Prime 33/126
Preinstallation Manual 2.7 Multiple MR System Requirements
Figure 2-15 Panel Separations in Shared Equipment Room (Top View)
5538858-1EN Revision 4 SIGNA™ Prime 34/126
Preinstallation Manual 2.8 MR Suite Temperature and Humidity

2.8 MR Suite Temperature and Humidity

(Applies to all subsections within this section)
This section provides temperature and humidity requirements for the MR suite.
NOTE
Make sure the HVAC system has the correct capacity for the room size, equipment heat output, and environmental conditions to maintain correct temperature and humidity for the protection of the patient.
Specic construction requirements for each room can be found in the following chapters:
Magnet Room
Equipment Room
Control Room

2.8.1 Temperature and Humidity Requirements

1. The customer is responsible for HVAC system design, purchase, and installation.
2. The temperature and humidity requirements must not be exceeded at any point during the day (both working or non-working hours).
3. A separate thermostat must be provided for the Magnet Room.
Table 2-5 Room Temperature and Humidity Requirements
Room Temperature Humidity
Range °C (°F) Change °C/Hr (°F/
Equipment Room at Inlet to Equipment
Magnet Room 15-21 (59-69.8) 3 (5) 30-60 5
Control Room 15-32 (59-89.6) 3 (5) 30-75 5
Notes:
1. Operating temperature gradient limits shall be between -3°C/Hr (-5°F/Hr) and 3°C/Hr (5°F/Hr), when averaged over 1 hour.
2. Operating humidity gradient limits shall be between -5% RH/hour and 5% RH/hour, when averaged over 1 hour.
3. Maximum ambient temperature is derated by 1°C per 300 m above 800 m (not to exceed 2600 m).
15-28 (59-82.4)
3
1
Hr)
3 (5) 30-75 5
Range %RH
Change %RH/Hr
2
2.8.2 Equipment Heat Output Specications
This section details the heat output for specic components. Actual heat output and room temperature may vary due to environmental factors, room insulation, clinical usage, and any non-GE Healthcare equipment used in the MR suite. Also, due to large variations in heat loads, the HVAC system may require unloaders, hot gas bypass, and reheat to maintain humidity levels.
5538858-1EN Revision 4 SIGNA™ Prime 35/126
Preinstallation Manual
Important
To prevent condensation in the ISC and Gradient Coil in the Magnet Room, it is required to operate the air conditioner in the Magnet Room for 24 hours a day, 7 days a week.
Table 2-6 System Maximum Heat Output for Air Cooling
2.8 MR Suite Temperature and Humidity
Component Magnet Room
W (BTU/hr)
Magnet (MAG) 1265 (4320)
Integrated System Cabinet (ISC) 3314 (11304)
18kW Chiller (LCS18) (Type D) 26100 (89057)
Integrated Cooling Cabinet (ICC) (Type B)
Magnet Monitor (MON) 60 (205)
Cryocooler Compressor (CRY) 500 (1706)
Main Disconnect Panel (MDP) 264 (900)
Operator Workspace (OW) 1450 (4947)
Equipment Room
W (BTU/hr)
1000 (3412)
Control Room
W (BTU/hr)
NOTE
Although the air cooling load averaged over a 12-hour working day is approximately 1/2 of the maxi­mum value, the HVAC system must be sized so that the maximum room gradient, temperature range, temperature change per hour, and humidity specications per 2.8.1 Temperature and Humidity Require-
ments on page 35 are not exceeded at any point during the working day.
5538858-1EN Revision 4 SIGNA™ Prime 36/126
Preinstallation Manual 2.9 Facility Coolant Requirements

2.9 Facility Coolant Requirements

(Applies to all subsections within this section)
Important
Equipment Failure. A continuous supply of facility liquid coolant to the Cryocooler Compressor is required at all times for correct system operation. Failure to provide liquid coolant with the requirements listed in this section may cause equipment failure.
2.9.1 Integrated Cooling Cabinet (ICC) Coolant Requirements­Type B Conguration
1. The facility must provide an uninterrupted supply of liquid coolant to the Integrated Cooling Cabinet (ICC) at magnet delivery. Coolant circuit must be operational at magnet delivery.
2. The facility must provide pipe/hose, power cable (3 phase + ground) and clamps to the ICC.
3. The vertical distance between the coolant connection points of the ICC and the Gradient Coil must be less than ± 5 meters (± 196.8 in.).
4. It is recommended that the customer provide and install an in-line ow meter on either the supply or return facility coolant hose. The ow meter should capable of visually displaying volumetric ow between 30 and 60 L/min (7.9 and 15.9 GPM) and congured for the properties of the cooling uid in use.
5. For sites without insite connectivity, it is recommended that the customer provide and install an in-line thermometer on the supply facility coolant hose. The thermometer should capable of visually displaying temperatures covering 5 to 15°C (41 to 59°F) and congured for the properties of the cooling uid in use.
6. The ICC, Cryocooler Compressor and Integrated System Cabinet must be located on the same level.
Table 2-7 Facility Liquid Coolant Requirements
Parameter Requirements
Availability Continuous
Antifreeze or treated process water
Minimum Flow 30 L/min (7.9 GPM)
Maximum Flow 60 L/min (15.9 GPM)
No more than 50% propylene glycol-water (PGW) or ethylene glycol-water (EGW)
Nominal Flow 40 L/min (10.6 GPM)
Maximum Pressure Drop in ICC at 30 L/min
Maximum Pressure Drop in ICC at 60 L/min
Maximum Inlet Pressure to ICC 6 bar (87 psi)
5538858-1EN Revision 4 SIGNA™ Prime 37/126
0.74 bar (10.7 psi) with 50% propylene glycol-water; 1060 kg/m3 density
0.49 bar (7.1 psi) with pure water
2.18 bar (31.6 psi) with 50% propylene glycol-water; 1060 kg/m3 density
1.67 bar (24.2 psi) with pure water
Preinstallation Manual 2.9 Facility Coolant Requirements
Table 2-7 Facility Liquid Coolant Requirements (Table continued)
Parameter Requirements
Chiller Size Minimum 20 kW
Condensation Protection Facility Plumbing to the ICC must be properly routed and insulated to prevent
equipment damage or safety hazards
Minimum Continuous Heat Load 7.5 kW
Inlet Temperature 5 to 15°C (41 to 59°F) measured at the inlet to the ICC
Customer supplied feeder hose (from main water supply to ICC)
19.1 mm (0.75 in.) minimum hose inside diameter If the hose is longer than 10 m (32.8 ft.) and shorter than 30 m (98.4 ft.), a hose
with a 25.4 mm (1 in.) minimum ID is recommended. If using 25.4 mm (1 in.) hose, an adaptor is required to reduce the inner diameter to 19.1 mm (0.75 in.) for the ICC connection.
NOTE
Rigid pipe connections are not allowed.
Table 2-8 Facility Water Quality Requirements
Parameter Requirement
pH Value 6.5 to 8.2 at 25 °C (77 °F)
Electrical Conductivity < 0.8 mmho/cm
Chloride Ion < 200 ppm
Sulfate Ion < 200 ppm
M-Alkalinity < 100 ppm
Total Hardness < 200 ppm
Calcium Hardness < 150 ppm
Ionic Silica < 50 ppm
Iron < 1.0 ppm
Copper < 0.3 ppm
Sulde Ion None, not detectable
Ammonium Ion < 1.0 ppm
Residual Chlorine < 0.3 ppm
Free Carbon Dioxide < 4.0 ppm
Stability Index 6.0 to 7.0
Suspended Matter < 10 ppm
Particle Size < 100 micron (with eld changeable lter)
5538858-1EN Revision 4 SIGNA™ Prime 38/126
Flow Meter
Customer Supplied
Facility Chilled Water
Customer Supplied Piping
Magnet Room
Integrated System
Cabinet
(ISC)
Integrated Cooling
Cabinet
(ICC)
Equipment Room
Supply
Supply
Return
Return
Water Cooling
Water Cooling
Water Cooling
Water Cooling
Cryocooler
Compressor
(CRY)
Facility
Plumbing
Unit
(FPU)
Backup Water
Customer Supplied Piping
RF Shield
Filter
(100 micron)
Customer Supplied
Magnet
(MAG)
Gradient Coil
Preinstallation Manual 2.9 Facility Coolant Requirements
Figure 2-16 MR System Water Cooling Block Diagram
2.9.2 18KW Chiller Coolant Requirements- Type D
Conguration
1. The vertical distance between the coolant connection points of the 18kw chiller (LCS18) and oor of the Magnet room must be less than ± 5 meters (± 196.8 in.).
2. The Chiller, Cryocooler Compressor and Integrated System Cabinet must be located on the same level.
5538858-1EN Revision 4 SIGNA™ Prime 39/126
Integrated
System Cabinet
(ISC)
Water Cooling
Cryocooler
Compressor
(CRY)
RF Shield
Magnet RoomEquipment Room
Backup Water
Customer Supplied Piping and Valves
Water Cooling
Return
Supply
Water Cooling
Magnet
(MAG)
Gradient Coil
Chiller
(LCS18)
Flow Meter
Customer Supplied
Preinstallation Manual
Figure 2-17 Type D Chiller Conguration Block Diagram
2.9 Facility Coolant Requirements

2.9.3 Emergency Backup Facility Coolant Requirements

The customer must balance the cost of cryogens and local controls with the cost of emergency backup facility coolant. There are two options for emergency backup, either total ICC backup or Cryocooler Compressor backup.
The facility may provide an optional emergency backup coolant supply in one of the following
congurations:
Customer provided temporary backup water cooling is allowed for the Shield/Cryo Cooler Compressor Cabinet if chiller or ICC were to experience a fault and stop operating. The backup compressor cooling design can utilize open loop city water only as temporary backup during loss of the closed loop water from the LCS18 or ICC. Long term use of open loop cooling systems will not allow a chemical equilibrium establishment and eventually contribute to failure.
NOTE
It is recommended to discharge remaining coolant in the compressor before switching back to the normal cooling. Dispose of coolant in accordance with local regulations.
1. Total ICC backup:
a. The facility is responsible for the connection of all hoses of a backup system.
b. Coolant must meet all other ICC coolant requirements listed in 2.9.1 Integrated Cooling Cabinet
(ICC) Coolant Requirements-Type B Conguration on page 37.
2. Cryocooler Compressor backup only:
Backup coolant may be routed to the ICC backup water port for the Cryocooler compressor at the location indicated in Figure 2-16 MR System Water Cooling Block Diagram on page 39 with the following requirements:
5538858-1EN Revision 4 SIGNA™ Prime 40/126
11
10
9
8
7
6
5
4
3
3.0
2.5
2.0
1.5
1.0
0.5
0 4 8 12 16 20 24 28 32
4 5 6 7 8 9 10
4 5 6 7 8 9 10
For Water
Pressure Drop and Temperature Rise
Cooling Water Inlet Temperature (°C)
Cooling Water Inlet-Outlet
Temperature (°C)
Cooling Water Flow Rate
(L/m)
Cooling Water Flow Rate
(g/m)
Cooling Water Inlet Temperature (°F)
Admissible Range
30 40 50 60 70 80 90
30 40 50 60 70 80 90
11
10
9
8
7
6
5
4
3
40
35
30
25
20
15
10
5
0
0.10
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0.00
3.0
2.5
2.0
1.5
1.0
0.5
For Antifreeze
(50/50% mixture of water and ethylene glycol or propylene glycol.)
Cooling Water Inlet Temperature (°C)
Water Flow (L/m) Water Flow (L/m)
Cooling Water Flow Rate
(L/m)
Pressure Drop
(MPa)
Cooling Water Flow Rate
(g/m)
Cooling Water Inlet Temperature (°F)
Admissible Range
Admissible Range
Admissible Range
50 Hz 60 Hz
Preinstallation Manual
(For Type B conguration) The ICC provides an emergency backup water interface on the right side
of the cabinet. City water could be used as emergency backup water if the primary facility water system were to experience a fault.
a. The emergency coolant supply must be drained to the facility through customer supplied 12.5
b. Coolant must meet all other ICC coolant requirements listed in 2.9.1 Integrated Cooling Cabinet
c. The customer is responsible for 12.5 mm (0.5 in.) pipe/hose, lters, and clamps to feed the
d. The charts below show the coolant ow rate and temperature requirements for the Cryocooler
Figure 2-18 Cryocooler Water Cooling Requirements
2.9 Facility Coolant Requirements
mm (0.5 in.) hose and must not back-feed to the ICC.
(ICC) Coolant Requirements-Type B Conguration on page 37 .
backup coolant to the ICC emergency backup port.
Compressor:
5538858-1EN Revision 4 SIGNA™ Prime 41/126
(For Type D Conguration) The emergency backup water should be connected to the compressor directly.
Preinstallation Manual 2.9 Facility Coolant Requirements
Switching the Shield/Cryo Cooler Compressor inlet/outlet cooling from the 18 kW chiller to a temporary water backup supply will result in approximately 5.5 liters (1.5 gallons) of deionized water being discharged. This discharge may have site impacts due to local regulatory codes. Make sure to understand and follow local regulatory requirements when designing and implementing a temporary backup water system. The design of the change over equipment from 18 kW chiller to city water and vise versa must not allow contamination of the closed loop system in the 18 kW chiller.
1. Customer is responsible to provide the hoses, clamps and valves for emergency backup water to accommodate GE supplied hoses (inner diameter 12.5mm (0.5 in.), outer diameter 19.8mm (0.78 in.) ).
2. Figure 2-18 Cryocooler Water Cooling Requirements on page 41 shows the coolant ow rate and temperature requirements for the Cryocooler Compressor.
3. City water, used as the emergency backup water, must not ow into the closed-loop cooling system when it returns to normal cooling conguration.
5538858-1EN Revision 4 SIGNA™ Prime 42/126
Preinstallation Manual 2.10 MR Suite Electrical Requirements

2.10 MR Suite Electrical Requirements

(Applies to all subsections within this section)

2.10.1 General Electrical Requirements

1. Customer is required to install a Main Disconnect Panel (MDP):
a. GEHC supplied MDP, M50022MA, M50022MB and M50022MC Design setup: 2.10.2 GE
Supplied Main Disconnect Panel (MDP) Specications for M50022MA, M50022MB and M50022MC on page 45
b. For Customer-supplied MDP:
i. Customer-supplied MDP may not be permissible in all regions. Contact your GE Healthcare
Project Manager of Installation (PMI) to verify local requirements.
ii. MDP Design Requirements: 2.10.3 Customer-supplied Main Disconnect Panel (MDP)
Requirements (exempt countries only*) on page 48.
iii. MDP Design Setup Figure 2-20 Customer-supplied MDP Setup on page 50.
2. At least one remote Emergency O push-button shall be installed in a location that is visible and accessible to the device operator (Control Room or Magnet Room). The push-button shall be normally closed and require operator action to release after activation (for example, twist and pull). GE Healthcare recommends installing two remote Emergency O push buttons, installed in the Control Room and Magnet Room.
3. The facility must provide system power to the MDP.
4. All associated transformers and cables must be correctly sized for system power requirements.
5. Runs E0009, E3500, and M3527 are GE-supplied. All other wiring shown in 2.10.2 GE Supplied Main
Disconnect Panel (MDP) Specications for M50022MA, M50022MB and M50022MC on page 45
and 2.10.3 Customer-supplied Main Disconnect Panel (MDP) Requirements (exempt countries
only*) on page 48 must be customer supplied and installed. A customer-supplied substitute for
E0009 can be used if the supplied run is shorter than required.
6. All feeder circuits require dedicated ground wires.
Table 2-9 Facility Power Requirements
Component Parameter Requirements
At Main Disconnect Panel (MDP)
Voltage / Frequency 480 VAC 60 ±3 Hz
415 VAC 50 ±3 Hz, 60 ±3 Hz
400 VAC 50 ±3 Hz, 60 ±3 Hz
380 VAC 50 ±3 Hz, 60 ±3 Hz
208 VAC 50 ±3 Hz, 60 ±3 Hz
200 VAC 50 ±3 Hz, 60 ±3 Hz
5538858-1EN Revision 4 SIGNA™ Prime 43/126
Preinstallation Manual 2.10 MR Suite Electrical Requirements
Table 2-9 Facility Power Requirements
Component Parameter Requirements
Daily Voltage Varia­tion
Customer to provide +10% / -10% from nominal at MDP input under all line and load conditions. This includes variation of power source and transmission losses up to the MDP.
Phase Input power to the MDP may use one of the following congurations:
A 3 phase solidly grounded WYE with Ground (3 Wire + Ground) A neutral conductor is not required for MR System operation. If a
neutral conductor is present, it can be terminated on the neutral bus provided in the GE-supplied MDP.
A 3 phase oating DELTA with Ground (3 Wire + Ground). Do not connect a corner grounded DELTA source.
NOTE
Some UPS options may require a neutral (refer to manu­facturer documentation for requirements).
Phase Balance
Power Quality Recommended THD-V of less than 2.5%
Facility Zero Voltage Reference Ground
Dierence between the highest phase line-to-line voltage and the lowest phase line-to-line voltage must not exceed 2%
The facility ground for the MR System must originate at the system power source (that is, transformer or rst access point of power into the facility) and be continuous to the MR System Main Discon­nect Panel (MDP) in the room.
Main facility ground conductor to Main Disconnect Panel (MDP) must be appropriately sized insulated copper wire.
The main facility ground to the Main Disconnect Panel (MDP) must meet local codes.
Service receptacle in Magnet Room
Pneumatic Patient Alert (PA1)
Magnet Rundown Unit (MRU)
Power Availability
Continuous facility power is required at all times for operation of the Cryocooler (CRY) to minimize cryogen consumption.
Voltage / Frequency 100-120 VAC 60 Hz
(North America) 200-240 VAC 50/60
Hz (International)
Phase 1
Maximum Current 20A (North America)
16A (International)
Voltage / Frequency 100-120 VAC 60 Hz
(North America) 200-240 VAC 50/60
Hz (International)
Phase 1
Maximum Current 20A (North America)
16A (International)
Voltage / Frequency 100-120 VAC 60 Hz
(North America) 200-240 VAC 50/60
Hz (International)
Phase 1
Receptacle required for small power tools. Lo­cal voltage and portable transformers for volt­age values.
The Control Box must be mounted within reach of the operator and within 1.5 m (5 ft.) of an electrical outlet.
Connection type: Hardwired or permanently wired directly to facility power, no plugs or connectors allowed. 25 mm (1 in.) PVC Sched­ule 40 Conduit recommended
Availability: Continuous
5538858-1EN Revision 4 SIGNA™ Prime 44/126
Preinstallation Manual 2.10 MR Suite Electrical Requirements
Table 2-9 Facility Power Requirements (Table continued)
Component Parameter Requirements
Maximum Current
1A
Circuit Breaker: Dedicated AC disconnect re­quired for both live and neutral connections
Magnet Monitor (MON)
Oxygen Monitor (OXY) Option
Voltage / Frequency 100-120 VAC 60 Hz
(North America) 200-240 VAC 50/60
Hz (International)
Phase 1
Maximum Current 3A
Voltage / Frequency 100-120 VAC 60 Hz
(North America) 200-240 VAC 50/60
Hz (International)
Phase 1
Maximum Current 0.9A
Power at the outlet must be continuously available.
Connection type: Hardwired in unit
Table 2-10 System Power Demand
System Equipment Power Draw (kVA) through MDP
Power Demand (Type B) Power Demand (Type D)
ISC PDU 50 Millisecond Power 61 61
ISC PDU Continuous Power 20 20
ICC 3.7 -
18 kW Chiller - 11.8
Cryocooler Compressor 9 9
Total for 50 Millisecond Power 73.8 73.8
Total for Continuous 32.8 40.6
2.10.2 GE Supplied Main Disconnect Panel (MDP) Specications for M50022MA, M50022MB and M50022MC
The customer is responsible for determining the suitability of the GE Supplied MDP with respect to governing electrical codes.
The GE Healthcare MDP consists of the following:
A 3-pole main circuit breaker rated for the total current of all the sub-breaker circuits.
A 3-pole circuit breaker rated for the current of the PDU circuit.
A 3-pole circuit breaker rated for the current of the 18 kW Chiller/ICC circuit.
A 3-pole circuit breaker rated for the current of the cryocooler compressor circuit.
All circuit breakers have a short circuit current interrupting rating of 25000 Amps at 480V and ICC
rating of 25000 Amps at 415V.
Auto restart on the Cryocooler compressor and chiller circuit following loss and restoration of power.
5538858-1EN Revision 4 SIGNA™ Prime 45/126
Preinstallation Manual
Two remote Emergency O Buttons to be installed external to the MDP. Emergency O removes power from all outputs when activated. MDP supports maximum E-o cable length of 100 meters when remote EPO push buttons are installed in the eld.
Terminal blocks that can accept wire sizes for M50022MA is listed under Table 2-12 GE Supplied
MDP - Range of Standard Conductors Accepted for M50022MA on page 47.
Terminal blocks that can accept wire sizes for M50022MB and M50022MC are listed under
Table 2-13 GE Supplied MDP - Range of Standard Conductors Accepted for M50022MB and M50022MC on page 48
Provision for terminating facility incoming neutral wire on the neutral terminal block.
Multiple ground terminal blocks as required by panel design.
GE MDPs M50022MA and M50022MC are listed and labeled by Nationally Recognized Testing Lab
(NRTL) in accordance with UL 508A and bears UL and CE mark. These MDPs are certied as per "UL 508A and IEC 61439-2" standards.
GE MDP M50022MB bears manufacturer's CE marking in accordance with the EU Low Voltage Directive 2014/35/EU and Electromagnetic Compatibility Directive 2014/30/EU and is certied as per "IEC 61439-2" standards.
Power on indicators for main breaker output power.
2.10 MR Suite Electrical Requirements
Two isolated, normally open contact pairs that open when E-O is pressed or facility power is interrupted for use with optional accessories.
Capability for single point lock-out/tag-out for the entire system (Mains Disconnect / Input Breaker) and a means to lock-out/tag-out each output breaker independently. All LOTO points support a standard sized hasp for lock-out.
5538858-1EN Revision 4 SIGNA™ Prime 46/126
CB#1
System Cabinet (SC)
CB#3
CB#5
CB#4
CB#2
L1
L2
L3
K
G
Light
A
B
F
Terminal strip
NC
C
G
Xfmr
Fuses
RF shield
Run E3500
Run M3527
Ground
Run E0009
GE Main Disconnect Panel
(MDP)
Penetration
Panel
(PP)
24 VAC Auto Restart Control Circuit
Emergency off Safety Circuit
Control Room "Emergency Off" Button (E02)
Magnet Room
"Emergency Off"
Button (E01)
Power Distribution
Unit (PDU)
Cable SUPPLIED BY CUSTOMER
Equipment SUPPLIED BY GE
Equipment SUPPLIED BY CUSTOMER
Cable SUPPLIED BY GE
Cryo Cooler Compressor (CRY)
E
Type B: ICC Type D: 18kW Chiller
D
NC
NC
Terminal for
Power
Monitor
Preinstallation Manual 2.10 MR Suite Electrical Requirements
Figure 2-19 GE supplied Main Disconnect Panel (MDP) Setup
Table 2-11 GE Supplied MDP Breaker Sizes
Circuit Breaker Breaker Size
CB1 100A
CB2 60A
CB3 25A
CB5 25A
Table 2-12 GE Supplied MDP - Range of Standard Conductors Accepted for M50022MA
A 4-85 12-3/0 16-185 6-350
B 6-55 10-1/0 16-185 6-350
Item Phase Ground
C 6-35 10-1 6-35 10-1
5538858-1EN Revision 4 SIGNA™ Prime 47/126
sq mm AWG/kcmil sq mm AWG/kcmil
Preinstallation Manual 2.10 MR Suite Electrical Requirements
Table 2-12 GE Supplied MDP - Range of Standard Conductors Accepted for M50022MA (Table contin­ued)
Item Phase Ground
sq mm AWG/kcmil sq mm AWG/kcmil
D 4-85 12-3/0 2.5-25 14-4
E (ICC) 2.5-6 14-10 2.5-6 14-10
E (Chiller) 4-6 12-8 4-6 12-8
F 4-85 12-3/0 2.5-25 14-4
G 2.5-6 14-10 2.5-6 14-10
K 0.5-2.5 22-12 N/A N/A
Table 2-13 GE Supplied MDP - Range of Standard Conductors Accepted for M50022MB and M50022MC
Item Phase Ground
sq mm AWG/kcmil sq mm AWG/kcmil
A 6-70 10-2/0 16-120 6-250
B 6-35 10-2 16-120 6-4/0
C 6-35 10-1 6-35 10-1
D 2.5-50 14-1/0 2.5-25 14-4
E (ICC) 2.5-6 14-10 2.5-6 14-10
E (Chiller) 4-6 12-8 4-6 12-8
F 2.5-50 14-1/0 2.5-25 14-4
G 2.5-6 14-10 2.5-6 14-10
K 0.5-2.5 22-12 N/A N/A

2.10.3 Customer-supplied Main Disconnect Panel (MDP) Requirements (exempt countries only*)

NOTE
* The requirements listed below apply only to exempt countries. Please contact your GE Healthcare Project Manager of Installation (PMI) for the list of exempt countries.
WARNING
PERSONNEL INJURY OR EQUIPMENT DAMAGE
Customer supplied MDP must have correctly sized wires and rated components to meet the MR System Power Requirements.
NOTE
Refer to 8.5 Sample control schematic for customer-supplied MDP on page 124.
1. MDP shall provide Auto-Restart to the Cryocooler Compressor, Chiller and ICC.
2. Manual Restart Capability
5538858-1EN Revision 4 SIGNA™ Prime 48/126
Preinstallation Manual
a. The MDP shall disconnect the PDU circuits upon power loss.
b. The MDP shall require a manual restart on the PDU circuits when power is reapplied after an
3. Emergency O Circuit
a. The MDP shall have an emergency o control circuit that disables power to the entire MR
b. The emergency o circuit shall be actuated by a push button on the panel, and shall also be
c. Manual reset of the emergency o circuit shall be required to restore power to the entire
4. The MDP shall include three breakers, as specied in Figure 2-20 Customer-supplied MDP
Setup on page 50 and Table 2-14 Customer-supplied MDP - Required Breaker Sizes on page 50.
Output breakers will feed the terminal block on ISC, 18KW chiller/ ICC and Cryocooler Compressor.
5. Lock-out/Tag-out:
a. The MDP shall provide single point lock-out/tag-out for the entire system and a means to
b. The lock-out/tag-out feature shall accommodate a standard sized lock hasp.
2.10 MR Suite Electrical Requirements
outage.
System.
capable of being actuated by two remotely located push buttons.
system.
lock-out/tag-out each output breaker independently.
c. The lock-out/tag-out features shall be accessible from the outside of the panel, without the
need to open the panel door(s).
6. The MDP shall have a Power ON indicator (Green light) on the panel.
7. The MDP shall meet national/local regulations.
8. The MDP shall provide terminations for all grounds entering, leaving and residing within the panel.
9. The MDP shall provide terminations of appropriate size for all power wiring entering and leaving the panel. Refer to Figure 2-20 Customer-supplied MDP Setup on page 50 All wire types, color, and sizing are to be selected in accordance with governing electrical codes.
5538858-1EN Revision 4 SIGNA™ Prime 49/126
Integrated
System Cabinet
(ISC)
CB#5
L1
L2
L3
G
Light
Terminal strip
C
G
Xfmr
Fuses
RF shield
Run E3500
Run M3527
Ground
Run E0009
Main Disconnect Panel
(MDP)
Penetration
Panel
(PP)
Auto Restart Control Circuit
Emergency off Safety Circuit
Control Room "Emergency Off" Button (E02)
Magnet Room
"Emergency Off"
Button (E01)
Power Distribution
Unit (PDU)
Cable SUPPLIED BY CUSTOMER
Equipment SUPPLIED BY GE
Equipment SUPPLIED BY CUSTOMER
Cable SUPPLIED BY GE
Cryo Cooler Compressor (CRY)
CB#1
CB#2
E
Type B: ICC Type D: 18kW Chiller
CB#3
NC
NC
NC
Preinstallation Manual 2.10 MR Suite Electrical Requirements
Figure 2-20 Customer-supplied MDP Setup
Table 2-14 Customer-supplied MDP - Required Breaker Sizes
Circuit Breaker Breaker Size
CB1 100A
CB2 60A - 63A
CB3 25A
CB5 25A
Table 2-15 Customer Supplied MDP - Range of Standard Conductors Accepted
C 6-35 10-1 6-35 10-1
Item Phase Ground
E (ICC) 2.5-6 14-10 2.5-6 14-10
E (Chiller) 4-6 12-8 4-6 12-8
5538858-1EN Revision 4 SIGNA™ Prime 50/126
sq mm AWG/kcmil sq mm AWG/kcmil
Preinstallation Manual 2.10 MR Suite Electrical Requirements
Table 2-15 Customer Supplied MDP - Range of Standard Conductors Accepted (Table continued)
Item Phase Ground
sq mm AWG/kcmil sq mm AWG/kcmil
G 2.5-6 14-10 2.5-6 14-10
2.10.4 Emergency Power Backup Specications (Optional)
The following facility backup power is recommended for continuous operation of the cryocooler compressor and Magnet Monitor:
NOTE
If the compressor must operate on emergency backup power, it still requires chilled water dened in the 2.9.3 Emergency Backup Facility Coolant Requirements on page 40.
Dedicated, single power supply to the compressor
Magnet Monitor emergency power (110V / 220V, 3A). Refer to Magnet Monitor (MON) Requirements
and Specications on page 96.
Emergency O Circuit (E-O) for the emergency backup to the compressor. LOTO is required for the power source between the generator and compressor.
A transfer switch to remove the primary power source from the compressor when in emergency backup power mode.
Table 2-16 Specications for Emergency Power to Cryocooler Compressor
Parameter Requirements
Power Line Voltage AC 380, 400, 415V (±10%) / 50 Hz, 3 phase (3 Wire + Ground)
AC 480V (±10%) / 60 Hz, 3 phase (3 Wire + Ground) Commercial Power Source
WARNING
Do not use an inverter for the main power source.
Operating Current Max. 13A (Both 50 and 60 Hz)
Starting current 75 / 80 A (50 / 60 Hz)
Maximum Fuse or Circuit Breaker Size 30A
Power Requirement Minimum 9 kVA
Power Consumption Max. 8.3 kW / Steady State 7.5 kW at 60 Hz
Max. 7.2 kW / Steady State 6.5 kW at 50 Hz
5538858-1EN Revision 4 SIGNA™ Prime 51/126
Preinstallation Manual

2.11 MR System Shipping and Receiving

(Applies to all subsections within this section)
Important
All shipping dimensions and weights are approximate and may vary based on ship-to location, required rigging, or other requirements. Some shipping or access routes may have requirements in addition to those listed in this section. Contact the GE Healthcare Project Manager of Installation (PMI) to verify magnet shipping, rigging, and access.

2.11.1 Receiving Requirements

1. The customer must provide an area for unloading system components from the truck and delivering to the MR suite
NOTE
2.11 MR System Shipping and Receiving
Contact GE healthcare project manager for magnet handling document to be used by rigging companies.
2. The customer is responsible for ensuring:
a. All oors along the route will support the weight of the magnet (GE Healthcare recommends a
structural analysis)
b. Doors or other openings are suciently wide to allow passage
c. Sucient room is provided for any required rigging tools

2.11.2 Facility Delivery Route Requirements

The following table lists the delivery dimensions of system components. Upon delivery, verify the component dimensions and weight. The delivery route must be planned to accommodate the dimensions listed.
Table 2-17 Delivery Route Requirements
Component
ISC 1100 43.3 2032 80 970 38.2 770 1698
Cryogen Dimensions vary depending on dewar type used. Verify with cryogen supplier.
Width Height Depth Weight
mm in. mm in. mm in. kg lb.
Magnet See 2.11.3 MR System Component Shipping Specications on page 52.
LCS18 See 18 kW Chiller dimensions in 4.8 18kW Water Chiller on page 91
ICC See ICC dimensions in Figure 4-8 Integrated Cooling Cabinet (ICC) on page 89
2.11.3 MR System Component Shipping Specications
MR System component shipping dimensions and weight are listed below:
5538858-1EN Revision 4 SIGNA™ Prime 52/126
Preinstallation Manual 2.11 MR System Shipping and Receiving
Table 2-18 MR System Components Shipping Specications
Component
W x D x H Weight
mm in. kg lb.
Magnet (as shipped with lifting bars)
Magnet (Crated for In­ternational Shipping)
2289 x 2388 x
2238
2438 x 2899 x
2438
Enclosure 2300 x 2180 x
1205
2440 x 1190 x
480
LCS18 1350 x 1100 x
2090
1200 x 1020 x
750
1050 x 650 x 700 41.34 x 25.59 x
650 x 650 x 870 25.59 x 25.59 x
ISC 1420 x 1160 x
2300
Notes
90.12 x 94 x 88.1 4990 11100 Domestic with tarped wood frame
96 x 114 x 96 5715 12600
90.55 x 85.83 x
239 526.90 Pallet
47.44
96.06 x 46.85 x
106 233.69 Pallet
18.90
53.15 x 43.31 x
450 992.08 Crate
82.28
47.24 x 40.16 x
50 110.23 Accessory *Carton
29.53
35 77.16 Accessory *Carton
27.56
105 231.49 Accessory *Carton
34.25
55.91 x 45.67 x
986 2173.76Crate
90.55
1870 x 1230 x
940
ICC 1150 x 1150 x
2188
GOC 850 x 550 x 790 33.46 x 21.65 x
73.62 x 48.43 x
37.01
45.28 x 45.28 x
86.14
125 275.58 Accessory *Carton
400 882 Crate
84 185.19 Carton
31.10
SPT Phantom Set 864 x 826 x 1524 34 x 32.5 x 60 159 350 On cart casters with box cover
Rear Pedestal 1170 x 850 x
1330
Interconnect Kit 1400 x 850 x
1020
Low Height Fixed Pa­tient Table
Cryocooler Compres-
2600 x 700 x
1000
660 x 711 x 1067 26 x 28 x 42 125 275 Pallet with box cover
46.06 x 33.46 x
52.36
55.12 x 33.46 x
40.24
102.4 x 27.5 x
39.4
115 253.53 Carton
148 326.28 Carton
220 485 Pallet
sor
5538858-1EN Revision 4 SIGNA™ Prime 53/126
2289 mm*
(90.1 in)*
2094 mm
(82.4 in)
2238 mm
(88.1 in)
2233 mm
(87.9 in)
2388 mm**
(94 in)**
Preinstallation Manual
Figure 2-21 Magnet Dimensions (as Shipped)
NOTE
2.11 MR System Shipping and Receiving
* Width can be reduced by 56mm (2.2 in.) if right center enclosure is removed.
** The short beam length is 2000 mm (78.7 in) and is available as P/N 5796140.
Table 2-19 MR System Component Replacement Shipping
Component
Replacement RF Body Coil Magnet Room 762 x 762 x 1524 30 x 30 x 60 70 155
Replacement BRM Gradient Coil Assembly on a Shipping Cradle/Cart
Gradient Coil Replacement Tool Kit Crate
Component Loca-
tion
mm in. kg lb.
Magnet Room 889 x 2444 x 1420 35 x 96.2 x 55.6 1491 3287
At site near magnet
787 x 2184 x 952 31 x 86 x 37.5 340 750
room
Specications
W x D x H Weight
NOTE
The dimensions and weights listed for the components in Table 2-19 MR System Component
Replacement Shipping Specications on page 54 include packaging.
5538858-1EN Revision 4 SIGNA™ Prime 54/126
Preinstallation Manual 2.11 MR System Shipping and Receiving
Figure 2-22 Gradient Coil Cart

2.11.4 Temperature and Humidity Storage Requirements

MR systems and components must be stored within the environmental requirements listed below.
NOTE
Some equipment is liquid-cooled. After coolant is added, the equipment must be kept from freezing. Phantoms and the coolant itself must also be kept from freezing.
Table 2-20 Transportation and storage environmental conditions for system components
Temperature Humidity
Range °C (°F) Change °C/Hr (°F/Hr) Relative % (Non-condens-
ing)
-30~55 (-22~131) 20 (68) 10 - 90 30
Change %/Hr
5538858-1EN Revision 4 SIGNA™ Prime 55/126

3 Magnet Room

3.1 Magnet Room Introduction

The Magnet Room is best understood as a series of layers, or “rooms within a room.” Each of these rooms has a specic function and associated requirements. All requirements in this chapter must be followed to ensure safe and correct operation of the MR System.
1. The Magnetic shielded room contains the MR Magnet fringe eld within a conned space. A site survey is required to determine magnet shield requirements (not all sites require magnetic shielding). Because of the added cost of magnetic shielding, room location should be carefully considered.
2. The Acoustic room is a layer used to help attenuate the noise produced during a scan. An acoustic engineer is strongly recommended to assess the environment.
3. The RF shielded room is critical to the correct MR System operation. RF shielding prevents interaction of external RF radiation with MR System operation and it also prevents MR System RF radiation from interfering with external systems, such as aircraft control. Special care must be used when installing all xtures penetrating the RF shield (for example, vents, electrical conduit, penetration panels) to ensure the integrity of the RF shield is maintained. Refer to RF Shielded Room Requirements, 5850260.
3
4. The Finished room includes the wall coverings, ceiling tile, ceiling grid, other xtures, Magnet (MAG) and Patient Table (PT). When planning the nished room, ensure the following:
a. All building codes are met (such as maintaining egress routes).
b. Items which may generate or create RF interference (including orescence lighting) are not
allowed for installation within the Magnet Room.
c. Customer is responsible for the selection and installation of all locally required safety devices
(for example, smoke detectors, oxygen monitors, and so on).
d. Smoke detectors should be located outside of the Magnet Room (for example, within the
return air duct) whenever possible. If code does not allow this, use only simple two wire non-addressable smoke detectors in the Magnet Room.
e. Ferrous or metallic items which could become projectiles when the magnet is installed
(including wall coverings, ceiling tile, ceiling grid, or other xtures) are not used or are correctly secured.
5538858-1EN Revision 4 SIGNA™ Prime 56/126
4
5
6
7
3
2
1
Preinstallation Manual
Figure 3-1 Magnet Room Layers
3.1 Magnet Room Introduction
Item Description Item Description
1 Door 2 Window
3 Penetration wall(s) 4 Finished room
5 RF shielding 6 Acoustic barrier
7 Magnetic shielding -
NOTE
The sequence of the room layers can vary based on siting needs.
5538858-1EN Revision 4 SIGNA™ Prime 57/126
Preinstallation Manual

3.2 Magnet Room Structural Requirements

3.2 Magnet Room Structural Requirements
This section lists the structural requirements that must be considered when performing site evaluation and planning of the Magnet Room.

3.2.1 Overview

1. When preparing a building plan or evaluating a potential site for an MR System, take care to ensure the MR suite will not interact with the surrounding environment (that is, magnetic, acoustic, environmental steel, and vibration).
2. The customer is responsible for vibration testing required to verify suitability of a proposed site. All test results and any questions regarding testing, results, or analysis must be forwarded to the GE Healthcare Project Manager of Installation (PMI).

3.2.2 Environmental Steel Limits

A static magnetic eld extends in a three-dimensional space around the magnet isocenter. Environmental steel within the static magnetic eld aects the uniformity (or homogeneity) of the eld. Field uniformity is critical to both image quality and chemical shift analysis (spectroscopy). An analysis of the environmental steel is required within a 3 m (9.84 ft.) spherical radius of the magnet isocenter. Environmental steel includes pipes, beams, concrete rebar, or any other structural steel in the oors, walls, or ceiling.
The following oor items must be limited per Table 3-1 Steel Mass Limits to Magnet Isocenter (3 x 3 m
(10 x 10 ft.) Area Under Magnet) on page 59.
1. Non-movable steel construction material such as rebar and metal decking
2. Existing or proposed RF/magnetic shielding or shim plates
3. Table 3-1 Steel Mass Limits to Magnet Isocenter (3 x 3 m (10 x 10 ft.) Area Under
Magnet) on page 59 denes the limits of use as a guideline to help the customer understand
allowable amounts of ferrous rebar, steel decking, or other components as they design the MR suite and Magnet Room oor structure.
4. The customer must provide detail dening ferrous material below the magnet to the Project Manager so the GE Healthcare MR Siting and Shielding (MRSS) team can review for compliance.
5538858-1EN Revision 4 SIGNA™ Prime 58/126
Preinstallation Manual
Table 3-1 Steel Mass Limits to Magnet Isocenter (3 x 3 m (10 x 10 ft.) Area Under Magnet)
3.2 Magnet Room Structural Requirements
Limits Of Steel Mass kg/m2 (lb./ft2)
0 (0) 0-76 (0-3)
9.8 (2) 76-127 (3-5)
14.7 (3) 127-254 (5-10)
39.2 (8) 254-330 (10-13)
98.0 (20) 330+ (13+)

3.2.3 Vibration Requirements

Excessive vibration can aect MR image quality. Vibration testing must be performed early in the site planning process to ensure vibration is minimized. Both steady state vibration (exhaust fans, air conditioners, pumps, and so on) and transient vibrations (trac, pedestrians, door slamming, and so on) must be assessed (see 3.2.3 Vibration Requirements on page 59). Specic requirements for vibration mitigation, include:
1. The Magnet (MAG) cannot be directly isolated from vibration. Any vibration issue must be resolved at the source.
Distance Below Top Surface Of Floor mm (in.)
2. MR Suite HVAC must have vibration isolation.
3. A vibration analysis must be performed at the proposed site with the results (and any mitigation) forwarded to the GE Healthcare Project Manager of Installation (PMI). See the 8.2 MR Site Vibration
Test Guidelines on page 117.
4. A transient vibration test must only be performed after a steady-state test has been performed and all steady-state sources of vibration have been mitigated.
5. Transient vibration levels above the specied limits in the 8.2 MR Site Vibration Test
Guidelines on page 117 must be given to the PMI for review.
6. Any transient vibration that causes vibration to exceed the steady-state level must be mitigated.
7. The vibration test consultant must account for non-mechanically induced signals such as test equipment instabilities, thermal drift or RF interference.
5538858-1EN Revision 4 SIGNA™ Prime 59/126
Acceleration (g’s) 10
-6
(RMS) above ambient baseline
Excitation Frequency (Hz)
Preinstallation Manual 3.3 Magnetic Shielded Room Requirements
Figure 3-2 Magnet Steady State Vibration Specications for PM magnet

3.3 Magnetic Shielded Room Requirements

Magnetic shielding prevents interaction between the magnet and nearby sensitive devices. Because of the added cost of magnetic shielding, room location should be carefully considered. All sites, including upgrade sites, must be evaluated for magnetic shielding requirements. Existing magnetic shielding at an upgrade site may not be sucient for the new system. Contact the GE Healthcare Project Manager of Installation (PMI) to request a site evaluation.
See MR Suite Magnetic Field Specications on page 24 for detailed magnetic proximity limit information.
1. The GE Healthcare Project Manager of Installation (PMI) works with the customer to coordinate the magnetic shielding site evaluation.
2. The customer is responsible for installation of all magnetic shielding.
3. If rear wall magnetic shield or steel RF wall is closer than 2500mm (98.4 in.) from isocenter, it should be veried by GEHC PMI.

3.4 Integrated System Cabinet (ISC) and Penetration Panel (PP) Wall Opening Requirements

The Penetration Panel must be covered on both sides and ISC must be covered on the magnet room side for safety. If GE-supplied adjustable covers are not used, the customer must furnish covers or enclosures with key or tool required for opening to limit access to the panel. The mounting and clearance dimensions for the Penetration Panel and the ISC are shown in this section.
Figure 3-3 Wall Opening Detail for ISC (Equipment or Operator Room Side) on page 61 shows wall
cuto detail for the ISC (Equipment or Operator Room side).
5538858-1EN Revision 4 SIGNA™ Prime 60/126
Preinstallation Manual
Figure 3-3 Wall Opening Detail for ISC (Equipment or Operator Room Side)
3.4 Integrated System Cabinet (ISC) and Penetration Panel (PP) Wall Opening Requirements
2165 ± 5 mm
(85.24 ± 0.2 in)
1975 mm
(77.76 in)
140 mm
(5.5 in)
1735 ± 5 mm
(68.31 ± 0.2 in)
*
(24.8 ± 0.2 in)
975 ± 5 mm
630 ± 5 mm
555 ± 5 mm
(21.9 ± 0.2 in)
1100 mm (43.31 in)
65 mm *
(2.6 in)
(38.39 ± 0.2 in)
1
2
3
4
15 mm
(0.59 in)
1050 ± 5 mm
(41.3 ± 0.2 in)
185 mm **
(7.28 in)
Item Description Item Description
1 Finished Wall 4 Wall Cut Out
2 Finished Wall Cut Out 5 Equipment Room Finished Floor
3 ISC Cover Outline 6 Exposed area of RF Shield (Gray Color Area)
6
NOTE
* This value is the length when the wall cuto width is 970 mm (38.2 in.). ** This value is the length when the wall cuto height is 1730 mm (68.11 in.). Cabinet left side has cooling plumbing assembly. Wall cut out area is not symmetric with cabinet center.
5
5538858-1EN Revision 4 SIGNA™ Prime 61/126
Preinstallation Manual
Figure 3-4 RF Shield
3.4 Integrated System Cabinet (ISC) and Penetration Panel (PP) Wall Opening Requirements
9
150 mm~ 250 mm
(5.91 in)~ (9.84 in)
6 7 8
10
134 2
0 ~ 450 mm *
(0 ~ 17.72 in)
170 mm ~ 180 mm
(6.69 in) ~ (7.09 in)
100 mm (3.94 in)
Item Description Item Description
1 ISC 6 Magnet Room Finished Wall
2 Mesh Shield 7 RF Shield Wall
3 ISC Back Cover Support 8 Equipment Room Finished Wall
4 ISC Back Cover 9 Magnet Room
5 Equipment Room Finished Floor 10 Equipment Room
~ 110 mm
~ (4.33 in)
NOTE
* Cables exit the enclosure in this area. Cover height is adjustable. Dimension is referenced from the equipment room nished oor.
5
5538858-1EN Revision 4 SIGNA™ Prime 62/126
1735 ± 5 mm
(68.3 ± 0.2 in)
905 mm
(35.6 in)
40 mm* (1.6 in)*
975 ± 5 mm
(38.4 ± 0.2 in)
>169 mm
>(6.65 in)
>234 mm
>(9.21 in)
1065 ± 15 mm (41.9 ± 0.6 in)
30 ± 5 mm
(1.2 ± 0.2 in)
30 ± 5 mm
(1.2 ± 0.2 in)
30 ± 5 mm
(1.2 ± 0.2 in)
40 mm* (1.6 in)*
40 mm**
(1.6 in)**
A
5
6
1
2
3
7
4
Preinstallation Manual
NOTE
The single-point ground bar is prepared by the customer. Locate it according to the Grounding Requirements in RF Shielded Room Requirements, 5850260.
Figure 3-5 Wall Opening Detail for ISC (Magnet Room Side) on page 63 shows wall cuto detail for the
ISC (Magnet Room Side).
Figure 3-5 Wall Opening Detail for ISC (Magnet Room Side)
3.4 Integrated System Cabinet (ISC) and Penetration Panel (PP) Wall Opening Requirements
Item Description Item Description
1 Finished Wall 4 Wall Cut Out
2 Finished Wall Cut Out 5 Magnet Room Finished Floor
3 ISC Cover Outline 6 Exposed area of RF Shield (Gray Color Area)
7 Penetration Panel (Can be located on the left
NOTE
* This value is the length when the wall cuto width is 970 mm (38.2 in.). ** This value is the length when the wall cuto height is 1730 mm (68.11 in.).
5538858-1EN Revision 4 SIGNA™ Prime 63/126
Figure 3-6 Wall Opening Detail for Penetration Panel (PP) on page 64 shows wall cuto detail for the
Penetration Panel from both room sides.
or on the right side of the ISC)
A The value depends on the height from Equip-
ment Room oor
Preinstallation Manual
Figure 3-6 Wall Opening Detail for Penetration Panel (PP)
3.4 Integrated System Cabinet (ISC) and Penetration Panel (PP) Wall Opening Requirements
30 ± 5 mm
(1.2 ± 0.2 in)
680 ± 2 mm
(26.7 ± 0.1 in)
750 mm
(29.5 in)
A***
30 ± 5 mm
(1.2 ± 0.2 in)
21 mm*
(0.8 in)
35 mm **
(1.4 in)
250 mm
(9.8 in)
206 ± 2 mm
(8.1 ± 0.1 in)
4
30 ± 5 mm
(1.2 ± 0.2 in)
21 mm*
(0.8 in)
1
2
3
Item Description Item Description
1 Finished Wall Cut Out 3 Wall Cut Out
2 Cover Outline 4 Exposed area of RF Shield
NOTE
* This value is the length when the wall cuto width is 208 mm (8.19 in.). ** This value is the length when the wall cuto height is 680 mm (26.77 in.). *** Cables exit the enclosure in this area.
Figure 3-7 Screw Locations for Mesh Shield and Penetration Panel (Magnet Room Side) on page 65
shows the screw locations for the Mesh Shield and Penetration Panel.
5538858-1EN Revision 4 SIGNA™ Prime 64/126
(B)
1000 mm
(39.37in)
(A)
1700 mm
(66.93 in)
1785 mm
(70.38 in)
(C)
700 mm
(27.56 in)
(D)
975 mm (38.4 in)
1735 mm
(68.3 in)
17.5 mm (0.69 in)
12.5 mm (0.49 in)
Preinstallation Manual 3.4 Integrated System Cabinet (ISC) and Penetration Panel (PP) Wall Opening
Requir
ements
Figure 3-7 Screw Locations for Mesh Shield and Penetration Panel (Magnet Room Side)
220 mm
(8.66 in)
Item Description Item Description
A 35 Screws, Pitch 50 mm (1.97 in.) x 34=1700
mm (66.9 in.)
B 21 Screws, Pitch 50 mm (1.97 in.) x 20=1000
mm (39.37 in.)
Total Scr
ews
2(A+B+C+D) - 4=150 Prepare 170 screws to install the PP and Mesh Shield.
NOTE
1.
M6 screws are used to install the Mesh Shield and PP. The Mesh shield and PP will be installed from the
C 15 Screws, Pitch 50 mm (1.97 in.) x 14=700
mm (27.56 in.)
D 6 Screws, Pitch 44 mm (1.73 in.) x 5=220 mm
(8.66 in.)
Magnet Room side.
2. It is the RF vendor's responsibility to prepare M6 screws according to the site condition. The Mesh Shield and PP will be installed during the system installation by the mechanical installer.
3. For a wooden RF shield wall: use M6 wood screws.
4. For an RF shield wall that has holes for the screws: use M6 screws and M6 nuts.
5538858-1EN Revision 4 SIGNA™ Prime 65/126
Preinstallation Manual
Figure 3-8 Duct or Pit Top View
3.4 Integrated System Cabinet (ISC) and Penetration Panel (PP) Wall Opening Requirements
5
4
1
2
3
Item Description Item Description
1 Magnet Room Finished Wall
2 RF Shield
3 Equipment Room Finished Wall
4 Duct or Pit Area
5 Magnet Room
6 Equipment Room
C
ISC
A
C
6
A
B
C
The ISC back Cover depth is adjustable from 150 mm (5.9 in.) to 250 mm (9.8 in.).
The Penetration Panel Covers depth is adjustable from 300 mm (11.8 in.) to 400 mm (15.75 in.).
The Mesh Shield is adjustable from 100 mm (3.9 in.) to 110 mm (4.3 in.).
B
B
NOTE
When cutting the duct or pit for cable routing, make sure the ISC Cover can cover the cuto for the cable.
It is recommended to extend the Mesh Shield in between 100 mm (3.9 in.) and 110 mm (4.3 in.). However, the Mesh Shield can be extended to 180 mm (7.1 in.) without any slack. In case there is any reason that the ISC cannot be located closely enough to the RF Shield, it is local site engineer's responsibility to extend the Mesh Shield more than 110 mm (4.3 in.). Consider oor level under the ISC when extending the Mesh Shield more than 110 mm (4.3 in.).
5538858-1EN Revision 4 SIGNA™ Prime 66/126
Preinstallation Manual 3.5 Finished Room Requirements

3.5 Finished Room Requirements

3.5.1 Ferrous Materials in the Magnet Room

1. Non-ferrous (non-metallic) materials or components should be used in the Magnet Room.
2. Ferrous components or material in the Magnet Room that could be removed for servicing, cleaning, or replacement must be secured to prevent the ferrous material from becoming a projectile (ferrous components or material must also be identied as ferrous to prevent untrained personnel from working on the ferrous material while the magnet is energized).

3.5.2 Walls

Refer to Acoustic Room Details, 5850262. Hard, bare wall surfaces may create a harsh Magnet Room acoustic environment due to reection of sound waves. Finished walls with acoustic properties can reduce reected noise.
1. GE Healthcare recommends nished walls to protect the RF shielding.
2. Walls and any millwork, cabinets, storage areas, acoustic coverings, and so on, must remain outside the minimum service area.
3. A metallic electrical conduit inside walls and ceilings may be used. Conduit for receptacles must be metallic.

3.5.3 Magnet Preinstallation Markings

For correct cryogen venting, the magnet vent adaptor must align correctly with the ceiling vent when the magnet is installed.
1. The magnet isocenter position must be clearly marked, and the marking must be identiable throughout construction.
NOTE
If there is no ceiling grid in the room, we recommend to also mark the magnet isocenter location on the ceiling. This can serve as a reference for positioning a new vent pipe, or can be used to reproduce the oor markings if they become lost during construction.
Refer to Magnet Room Venting Requirements, 5850263 for the location of the magnet vent.
5538858-1EN Revision 4 SIGNA™ Prime 67/126
Preinstallation Manual
2. If no ceiling vent pipe exists prior to construction, the location of the magnet isocenter and magnet z-axis orientation must be marked on the Magnet Room oor as shown below.
Figure 3-9 Marking Magnet Isocenter (in a Room Without a Vent Pipe)
3.5 Finished Room Requirements
Figure 3-10 Marking the Magnet Isocenter and the Z-Axis Orientation on the Floor
3. If a ceiling vent pipe already exists at the start of construction, the magnet isocenter marking must be correctly aligned relative to the position of the vent pipe. Refer to Magnet Room Venting Requirements, 5850263, for vent location.
NOTE
We recommend:
Marking the center of the vent pipe.
Using a cross line laser or other accurate method to transcribe it to the oor directly
below.
5538858-1EN Revision 4 SIGNA™ Prime 68/126
1
2
Preinstallation Manual 3.5 Finished Room Requirements
Marking the magnet isocenter relative to the vent pipe marking on the oor. The positioning template (5810898 or 5810898-2 ) can be used as a marking aid.
Figure 3-11 Marking the Center of the Vent Pipe
Item Description
1 Vent center
2 Magnet isocenter
Figure 3-12 Marking the Vent Pipe and Magnet Isocenter on the Floor
Item
1 Vent center
2 Magnet isocenter
Description
5538858-1EN Revision 4 SIGNA™ Prime 69/126
Preinstallation Manual 3.5 Finished Room Requirements

3.5.4 Doors, Magnet Access Openings, and Patient Viewing Windows

1. The nished opening of the Magnet Room main door must be at least 1092 mm (43 in.) wide to allow for helium dewars and patient tables.
2. Threshold height must not exceed 15 mm (0.6 in.) on both sides of the door with a maximum 10-degree threshold inclination.
3. IEC requires the patient, while in the bore, be in full view of the operator.
NOTE
GE Healthcare recommends using a window, although other means (for example, camera and video display) may be used as long as all IEC requirements are met.
The recommended dimensions for the patient viewing windows are 1219 mm wide x 762 mm high (48 in. wide x 30 in. high).
The recommended distance from the bottom edge of the patient viewing window to the nished oor is 1067 mm (42 in.).
4. The magnet delivery requires an opening into the room to allow access for the magnet delivery, rigging, and personnel access.

3.5.5 Finished Ceiling

1. The customer is responsible for the nished ceiling.
2. The nished ceiling grid must be non-ferrous.
3. Ceiling preparation should be completed prior to magnet delivery.

3.5.6 Magnet Room Floors

1. The nished oor must support the weight of all components throughout operation and service life. This includes the magnet, patient table, and gradient coil replacement cart.
NOTE
For gradient coil replacement, eld engineers remove the patient table from the Magnet Room before they move the gradient coil replacement cart into the Magnet Room.
2. The nished oor must be water resistant to protect the suboor and shielding from water damage.
5538858-1EN Revision 4 SIGNA™ Prime 70/126
Preinstallation Manual
3. The customer is responsible for providing ooring to prevent ESD (Electrostatic Discharge) buildup to 8 kV for protection of the sensitive MR equipment.
4. Magnet, Enclosure, and Patient Table areas must be at and level within 3 mm (0.125 in.), with the magnet in place, within the shaded area shown in Figure 3-13 Magnet Room Floor Levelness
Area on page 71.
Figure 3-13 Magnet Room Floor Levelness Area
3.5 Finished Room Requirements
4925 mm (193.9 in)
1823 mm (71.77 in)
1320 mm (51.97 in)
1130 mm (44.49 in)
5. The VibroAccoustic Dampening kit for both seismic and non-seismic mounting is M6001AH. See
Figure 3-14 Magnet Mounting Detail - Patient End is on the Left Side on page 72 for details.
6. Seismic anchors must be isolated from rebar.
7. A 102 mm (4 in.) rebar-free area is necessary under the table dock anchor, in the position shown in
Figure 3-14 Magnet Mounting Detail - Patient End is on the Left Side on page 72.
Important
The table dock anchor hole is drilled only after magnet installation.
5538858-1EN Revision 4 SIGNA™ Prime 71/126
1339 mm
(52.7 in)
673 mm (26.5 in)
673 mm
(26.5 in)
1346 mm
(53 in)
1346 mm
(53 in)
81 mm
(3.2 in)
102 mm
(4 in)
75 mm (2.9 in)
673 mm
(26.5 in)
673 mm
(26.5 in)
125 mm
(4.9 in)
102 mm
(4 in)
1903 mm
(74.9 in)
Preinstallation Manual
Figure 3-14 Magnet Mounting Detail - Patient End is on the Left Side
3.5 Finished Room Requirements
8. RF shield seams, joints, or overlaps must not be located under the VibroAcoustic mats.
5538858-1EN Revision 4 SIGNA™ Prime 72/126
Preinstallation Manual 3.5 Finished Room Requirements

3.5.7 Storage Cabinets

NOTE
GE Healthcare no longer provides a storage solution for system phantoms.
1. The customer shall provide storage for phantoms in the magnet room (for example, a cart, shelving unit or cabinet). Storage needs to be large enough to accommodate system phantoms listed in Table 1-1 of Customer Site Storage Requirements, 5182674 (available in the Customer Documentation Portal).
2. The storage solution can not interfere with the magnet room minimum service area.
5538858-1EN Revision 4 SIGNA™ Prime 73/126
1
2 3
Preinstallation Manual 3.6 Magnet Room Equipment Specications
3.6 Magnet Room Equipment Specications
(Applies to all subsections within this section)
3.6.1 Magnet (MAG) Assembly Specications
1. 1.5T Platform magnet weight, with cryogens at maximum capacity: 4760 kg (10494 lb.)
2. Rear pedestal weight: 66kg (146lb).
Figure 3-15 Magnet Enclosure Dimensions
Item Description
1 Top view
2 Front view
3 Side view
5538858-1EN Revision 4 SIGNA™ Prime 74/126
Preinstallation Manual 3.6 Magnet Room Equipment Specications
Figure 3-16 Recommended duct space behind rear pedestal
2
3
W 300 mm (11.8 in)
4
* H 200 mm (7.87 in)
260 mm
1
280 mm
(11 in)
(10.24 in)
1834.5 mm (72.2 in)
5
Item Description Item Description
1 Cover for rear cable access 4 Floor duct
2 Magnet 5 From magnet isocenter
3 Rear pedestal 6 Finished oor
Figure 3-17 Limitation of Duct size for Minimum Room layout
W 425 mm (16.73 in) * H 400 mm (15.75 in)
1
4 5
W 300 mm (11.8 in) * H 200 mm (7.87 in)
1
260 mm
(7.5 in)
2
3
145 mm (5.71 in)
30 mm
(1.18 in)
260 mm
(7.5 in)
2
90 mm
(3.54 in)
6
1128.8 mm (44.4 in)
1993 mm
(78.5 in)
Item
512 mm
(20.16 in)
309 mm (12.17 in)
30 mm
(1.18 in)
150 mm
(5.9 in)
30 mm
(1.18 in)
620 mm (24.2 in)
30 mm
(1.18 in)
Description Item Description
1 Floor duct 4 From magnet isocenter to oor duct
2 Finished oor 5 From magnet isocenter
3 Rear pedestal - -
5538858-1EN Revision 4 SIGNA™ Prime 75/126
A: 696 mm (27.4 in) B: 501 mm (19.7 in) C: 696 mm (27.4 in) D: 747 mm (29.4 in)
A: 689 mm (27.1 in) B: 884 mm (34.8 in) C: 689 mm (27.1 in) D: 638 mm (25.1 in)
A: 808 mm (31.8 in) B: 707 mm (27.8 in) C: 808 mm (31.8 in) D: 600 mm (23.6 in)
1385 mm
(54 in)
572 mm
(22.5 in)
405 mm (15.9 in)
965 mm
(38 in)
30 mm
(1.2 in)
490 mm
(19.3 in)
1
1
Preinstallation Manual 3.6 Magnet Room Equipment Specications
NOTE
Add edge guar
ds or tape to the cut edge of rear pedestal covers.
30 mm (1.18 in.) minimum clearance is required between rear pedestal and surface of duct.
Shaded area of rear pedestal shows the cutout area.
3.6.2 Patient Table (PT) Specic
1. Low Height Fixed Table weight, empty: 136 kg (300 lb.)
2. Low Height Fixed Table weight, including maximum patient weight of 200 kg (440 lb.) and accessories: 365 kg (803 lb.)
Figure 3-18 Low Height Fixed Table
ations
2134 mm
(84 in)
Item Description Item Description
1 2 Seismic mounting holes, 13.5mm (17/32 in.) A 336 kg (739.2 lb.): Patient is on the table being
B 196 kg (431.2 lbs): Patient is moved 1470 mm
(58 in.) into the bor
e and scanning. Table is at
the highest position.
D 136 kg (299.2 lbs): Patient is not on the table.
T
able is at the highest position.
5538858-1EN Revision 4 SIGNA™ Prime 76/126
pr
epared for scanning, not in the bore. Table is
at the highest position.
C 336 kg (739.2 lb.): Patient is on the table and
cradle is 50 mm (2 in.) into the bore. Table is at the highest position.
- -
Preinstallation Manual 3.6 Magnet Room Equipment Specications
3.6.3 Magnet Rundown Unit (MRU) Specications and Requirements
1. Location: The bottom edge of the MRU must be mounted 1524 ± 25 mm (60 ± 1 in.) above the Magnet Room oor near the front of the magnet enclosure.
2. Weight: 3.2 kg (7 lb.)
3. Magnetic Field Limit: 20 mT (200 G)
4. The MRU is installed by the facility contractor.
Figure 3-19 Magnet Rundown Unit (MRU)
Item Description
1 Cable access
2 Power access
5538858-1EN Revision 4 SIGNA™ Prime 77/126
Preinstallation Manual
Figure 3-20 MRU Mounting Pattern

3.7 Magnet Room Lighting Requirements

Item Description Item Description
1 7 mm (0.275 in.) diameter mounting hole 3 Finished oor
2 26 mm (1.025 in.) diameter cable access - -
3.7 Magnet Room Lighting Requirements
1. All lighting xtures and associated components must meet all RF shielded room and RF grounding requirements (for example, track lighting is not recommended due to possible RF noise).
2. All removable lighting xtures and associated components must be non-magnetic.
3. All lighting must use direct current (the DC must have less than 5% ripple).
4. At least 300 lux must be provided at the front of the magnet for patient access and above the magnet for servicing.
5. Fluorescent lighting must not be used in the Magnet Room.
6. Lighting must be adjusted using a discrete switch or a variable DC lighting controller.
7. SCR dimmers or rheostats must not be used.
8. DC LED lighting may be used if the DC power converter and RF sources are all located outside the Magnet Room RF Shield.
NOTE
LED lighting could cause image quality issues due to RF interference. Make sure a MR-compatible LED lighting solution is chosen.
5538858-1EN Revision 4 SIGNA™ Prime 78/126
Preinstallation Manual
9. Battery chargers (for example, used for emergency lighting) must be located outside the Magnet Room.
10. LED Lighting or short lament length incandescent bulbs are recommended.
11. Linear lamps are not recommended due to the high burnout rate.
3.7 Magnet Room Lighting Requirements
5538858-1EN Revision 4 SIGNA™ Prime 79/126

4 Equipment Room

4.1 Equipment Room Overview

(Applies to all sections within this chapter)
1. The ICC and ISC must be located on the same oor.
NOTE
The ICC contains the cryocooler compressor.
The following illustration shows minimum equipment room service clearances. Refer to MR Suite
Minimum Room Size Requirements on page 17 for a list of considerations not included in the minimum
area dimensions.
NOTE
Colored areas indicate service/installation areas. These areas can overlap as necessary as shown below. See individual component descriptions and room requirements for service area details. Optional equipment is not shown; additional space may be required for options.
4
NOTE
Refer to Table 2-19 MR System Component Replacement Shipping Specications on page 54 for the dimensions of the replacement parts. The parts must be able to be positioned in front of the noted cabinet for replacement procedures after the system has been installed.
5538858-1EN Revision 4 SIGNA™ Prime 80/126
250 mm
(9.8 in)
726 mm
(28.6 in)
300 mm
(11.8 in)
1109 mm
(43.7 in)
300 mm
(11.8 in)
1000 mm
(39.4 in)
1109 mm
(43.7 in)
233 mm
(9.2 in)
991 mm
(39 in)
826 mm
(35.5 in)
76 mm
(3 in)
1826 mm
(71.9 in)
874 mm
(34.4 in)
2635 mm
(103.7 in)
800 mm
(31.5 in)
726 mm (28.6 in)
874 mm
(34.4 in)
800 mm (31.5 in)
762 mm
(30 in)
914 mm
(36 in)
644 mm (25.4 in)
381 mm
(15 in)
ISC
ICC
PP
MDP
MON
Preinstallation Manual 4.1 Equipment Room Overview
Figure 4-1 Typical Minimum Equipment Room with Service Clearances (Type B)
5538858-1EN Revision 4 SIGNA™ Prime 81/126
800 mm
(31.5 in)
800 mm (31.5 in)
804 mm (31.6 in)
1128 mm
(44.4 in)
991 mm
(39 in)
1128 mm
(44.4 in)
804 mm (31.6 in)
450 mm (17.7 in)
2697 mm
(106.8 in)
1928 mm
75.9 in)
300 mm (11.8 in)
233 mm
(9.2 in)
76 mm
(3 in)
381 mm
(15 in)
644 mm
(25.4 in)
250 mm
(9.8 in)
300 mm
(11.8 in)
1109 mm
(43.7 in)
826 mm (35.5 in)
CRY
800 mm (31.5 in)
600 mm
(23.6 in)
PP
1000 mm
(39.4 in)
1109 mm
(43.7 in)
MDP
MON
ISC
762 mm
(30 in)
914 mm
(36 in)
LCS18
Preinstallation Manual 4.1 Equipment Room Overview
Figure 4-2 Typical Minimum Equipment Room with Service Clearances (Type D)
5538858-1EN Revision 4 SIGNA™ Prime 82/126
Preinstallation Manual 4.2 Main Disconnect Panel (MDP) Requirements and Specications
4.2 Main Disconnect Panel (MDP) Requirements and
Specications

4.2.1 Requirements

1. It is recommended to install a T100 network connection with RJ45 connector near the MDP to support a power monitor.
2. The cable must be Cat 5 or better.
3. The network connection must not be routed through the Ethernet switch in the Global Operator Cabinet (GOC).
4.2.2 Specications
For M50022MA, M50022MB and M50022MC:
1. M50022MA Weight: 84 kg (186 lb).
2. M50022MB Weight: 61 kg (134 lb).
3. M50022MC Weight: 60 kg (132 lb).
4. Magnetic Field Limit: 5 mT (50 Gauss)
5538858-1EN Revision 4 SIGNA™ Prime 83/126
492 mm (19.4 in)
387 mm
(15.25 in)
233 mm (9.18 in)
914 mm
(36 in)
645 mm (25.4 in)
762 mm
(30 in)
58 mm
(2.3 in)
58 mm (2.3 in)
108 mm (4.25 in)
Ø14 mm
(Ø0.6 in)
1067 mm
(42 in)
572 mm
(22.5 in)
1099 mm
(43.25 in)
1130 mm
(44.5 in)
1
Preinstallation Manual 4.2 Main Disconnect Panel (MDP) Requirements and Specications
Figure 4-3 GEHC supplied Main Disconnect Panel (MDP) M50022MA
Item Description
1 Service Clearance
5538858-1EN Revision 4 SIGNA™ Prime 84/126
83 mm
(3.25 in)
1067 mm
(42 in)
229 mm
(9 in)
203 mm
(8 in)
914 mm
(36 in)
19 mm
(0.75 in)
19 mm
(0.75 in)
508 mm
(20 in)
4 x Ø11 mm 4 x (Ø0.4 in)
1
260 mm
(10.25 in)
762 mm
(30 in)
2
Preinstallation Manual 4.3 Integrated System Cabinet (ISC)
Figure 4-4 GEHC supplied Main Disconnect Panel (MDP) M50022MB, M50022MC
Item Description
1 Service Clearance
2 Center of gravity dimension for M50022MB is 552 mm (21.75 in)
Center of gravity dimension for M50022MC is 546 mm (21.5 in)

4.3 Integrated System Cabinet (ISC)

Weight: Approx 770 kg (1698 lb).
Magnetic Field Limit: 5 mT (50 G) (Penetration Panel (Back Panel) side)
Contact Area: 2461.76 mm² (3.82 in2) for each support. There are 6 supports in total.
5538858-1EN Revision 4 SIGNA™ Prime 85/126
6 x Ø600 mm
6 x (Ø2.4 in)
163 mm
(6.4 in)
257 mm
(10.1 in)
147 mm
(5.8 in)
175 mm
(6.9 in)
175 mm
(6.9 in)
73 mm
(2.9 in)
53 mm
(2.1 in)
50 mm (2.0 in)
50 mm (2.0 in)
50 mm (2.0 in)
50 mm (2.0 in)
73 mm (2.9 in)
34 mm (1.3 in)
1000 mm
(39 in)
1000 mm
(39 in)
969 mm
(38.1 in)
826 mm
(35.5 in)
1109 mm
(43.7 in)
400 mm
(15.75 in)
420 mm (16.5 in)
374 mm
(14.7 in)
605 mm (23.8 in)
2018 mm
(79.5 in)
495 mm (19.5 in)
6x 7x
300 mm (11.8 in)
400 mm
(15.7 in)
840 mm
(33.1 in)
1956 mm
(77 in)
52 mm (2.1 in)
111
3
2
6
5
4
4
Preinstallation Manual 4.3 Integrated System Cabinet (ISC)
Figure 4-5 Integrated System Cabinet (ISC)
Item Description Item Description
1 Service clearance 2 Ceiling
3 Airow clearance 4 Seismic anchor mounting holes (All M8-1.25)
5538858-1EN Revision 4 SIGNA™ Prime 86/126
Preinstallation Manual
Item Description Item Description
4.3 Integrated System Cabinet (ISC)
5 Customer-supplied seismic mounting bracket
shall not interfere with the highlighted area.
6 Maximum height of Customer-supplied
seismic mounting bracket
NOTE
Make sure that the seismic brackets and anchors do not conict with ISC covers and water hose routing.
Area must be level according to the specication in Figure 4-6 Area to be leveled on page 87.
Figure 4-6 Area to be leveled
1
500 mm
(19.69 in)
1
500 mm
(19.69 in)
650 mm (25.6 in)
Item Description
1 Base Center
650 mm (25.6 in)
NOTE
Shaded area must be leveled.
Specication of Floor
1. Floor slope: < ± 0.5 deg
2. Floor surface: < ± 5 mm
3. Non-compressible ooring material only. For example, no carpet allowed.
5538858-1EN Revision 4 SIGNA™ Prime 87/126
123
5
6
150 mm (5.91 in)
1050 mm
(41.3 in)
1545~1850 mm
(60.83~72.83 in)
5
6
7
8
9
800 mm (31.5 in)
150~250 mm (5.91~9.84 in)
1040 mm (40.94 in)
1804 mm
(71.02 in)
1
4
10
11
Preinstallation Manual 4.4 Mesh Shield and Integrated System Cabinet (ISC) Cover

4.4 Mesh Shield and Integrated System Cabinet (ISC) Cover

Figure 4-7 Mesh Shield and ISC Cover on page 88 shows the relationship and dimensions of ISC, RF
shield wall, Mesh Shield and Cover.
Figure 4-7 Mesh Shield and ISC Cover
Item Description Item Description
1 Cover 2 Mesh Shield ISC
3 Wall Cut Out 4 ISC
5 Magnet Room 6 Equipment Room
7 Side View of Cover 8 Front View of Cover
9 Surface attached to RF shield layer 10 Side View of ISC
11 Front View of Mesh Shield - -
5538858-1EN Revision 4 SIGNA™ Prime 88/126
348 mm
(13.7 in) 952 mm (37.5 in)
988 mm
(38.9 in)
410 mm (16.1 in)
212 mm
(8.3 in)
272 mm (10.7 in)
875 mm (34.4 in)
725 mm (28.5 in)
800 mm (31.5 in)
800 mm
(31.5 in)
1905 mm
(75.0 in)
35 mm
(1.4 in)
146 mm
(5.8 in)
150 mm
(5.9 in)
150 mm
(5.9 in)
3x
5
6
7
2
4
1 4
3
Preinstallation Manual 4.5 Integrated Cooling Cabinet (ICC) Specications
4.5 Integrated Cooling Cabinet (ICC) Specications
Weight of ICC without F-50SH compressor is 292 kg (644 lb.)
F-50SH Cryocooler Compressor weight: Approx 125 kg (276 lb.)
Magnetic Field Limit: 5 mT (50 G) (Penetration Panel side)
Figure 4-8 Integrated Cooling Cabinet (ICC)
Item Description Item Description
1 Top View 2 Front View
3 Side View 4 Service/Air Flow Clearance
5 Front Cover 6 Finished Floor
7 (6) M8 Seismic Anchor Mounting Holes - -
5538858-1EN Revision 4 SIGNA™ Prime 89/126
243.6 mm (9.6 in)
300~400 mm
(11.8~15.8 in)
723.2 mm
(28.5 in)
300~400 mm
(11.8~15.8 in)
250 mm
(9.9 in)
300 mm
(11.8 in)
750 mm
(29.5 in)
134
2
600 mm
(23.6 in)
1000 mm
(39.4 in)
600 mm
(23.6 in)
1000 mm
(39.4 in)
5
5
Preinstallation Manual 4.6 Penetration Panel

4.6 Penetration Panel

Magnetic Field Limit: 20 mT (200 gauss)
Figure 4-9 Penetration Panel (PP) and Cover
Item Description Item Description
1 Penetration Panel Front View 2 Penetration Panel and Frame Side View
3 Penetration Panel Cover Front View 4 Penetration Panel Cover Side View
5 Service clearance - -
4.7 Cryocooler Compressor (CRY) Specications
1. F-50SH Cryocooler Compressor Weight: Approx 125 kg (276 lb.)
2. Magnetic Field Limit: 10 mT (100 G)
5538858-1EN Revision 4 SIGNA™ Prime 90/126
591 mm
(23.25 in)
334 mm
(13.2 in)
330 mm
(13.0 in)
485 mm (19.1 in)
103 mm
(4.1 in)
232 mm
(9.1 in)
80 mm
(3.2 in)
600 mm
(23.6 in)
450 mm
(17.7 in)
800 mm (31.5 in)
276 mm (10.9 in)
12244
4
569
7 8
3
Preinstallation Manual 4.8 18kW Water Chiller
Figure 4-10 Cryocooler Compressor F-50SH (Water Cooled)
Item Description Item Description
1 Top view 6 Helium return
2 Front view 7 Water supply
3 Side view 8 Water return
4 Service clearance 9 Input power terminal
5 Helium supply - -

4.8 18kW Water Chiller

Specications
1. Weight:
Dry weight (without coolant): 300 kg (661 lb.)
Wet weight (with coolant): 350 kg (772 lb.)
2. Magnetic Field Limit: 5 mT (50 G)
5538858-1EN Revision 4 SIGNA™ Prime 91/126
Preinstallation Manual 4.8 18kW Water Chiller
3. If the equipment room ceiling height is between 2355 mm (92.7 in.) and 2500 mm (98.4 in.), a duct should be provided by a local vender. Refer to Figure 4-13 Duct (Option 1) on page 94 and
Figure 4-14 Duct (Option 2) on page 95 for ducting options.
4. The 18kW Chiller, ISC and Compressor must be located on the same level.
Figure 4-11 18kW Water Chiller (LCS18)
1128 mm (44.41 in)
804 mm
(31.65 in)
1552 mm
(61.1 in)
1658 mm
(65.28 in)
1769 mm (69.64 in)
1004 mm
(39.53 in)
5538858-1EN Revision 4 SIGNA™ Prime 92/126
1
2
2
343
800 mm
(31.5 in)
800 mm
(31.5 in)
2500 mm
(98.43 in)
706 mm
(27.8 in)
415 mm
(16.3 in)
474 mm (18.7 in)
140 mm
(5.5 in)
500 mm
(5.9 in)
500 mm
(5.9 in)
Ø8 mm
(Ø0.3 in)
140 mm
(5.5 in)
500 mm
(5.9 in)
500 mm
(5.9 in)
Ø8 mm
(Ø0.3 in)
Preinstallation Manual 4.8 18kW Water Chiller
Figure 4-12 Minimum Service and Heat Dissipation Space
Item Description Item Description
1 Ceiling 3 Seismic anchor mounting location
2 Service area and air intake area 4 Finished oor
5538858-1EN Revision 4 SIGNA™ Prime 93/126
Preinstallation Manual 4.8 18kW Water Chiller
Figure 4-13 Duct (Option 1)
5538858-1EN Revision 4 SIGNA™ Prime 94/126
Preinstallation Manual 4.8 18kW Water Chiller
Figure 4-14 Duct (Option 2)
5538858-1EN Revision 4 SIGNA™ Prime 95/126
Preinstallation Manual 4.9 Magnet Monitor (MON) Requirements and Specications
4.9 Magnet Monitor (MON) Requirements and
Specications

4.9.1 Requirements

1. Customer must supply T100 network connection with RJ45 connector to the Magnet Monitor (MON). Network connectivity must be active prior to magnet delivery.
2. The cable must be Cat 5 or better.
3. The network connection must not be routed through the Ethernet switch in the Global Operator Cabinet (GOC).
4.9.2 Specications
1. Mounting location: Wall installation in Equipment Room
2. Weight: 3.6 kg (8 lb.)
3. Magnetic Field Limit: 20 mT (200 gauss)
4. Power cord length: 1829 mm (72 in.)
5538858-1EN Revision 4 SIGNA™ Prime 96/126
Preinstallation Manual
Figure 4-15 Magnet Monitor (MON)
4.9 Magnet Monitor (MON) Requirements and Specications
Item Description Item Description
1 Top View 3 Service area
2 Front View - -
Figure 4-16 Magnet Monitor (MON) Mounting Patterns
5538858-1EN Revision 4 SIGNA™ Prime 97/126

5 Control Room

5.1 Operator Workspace Equipment Specications
(Applies to all sections within this chapter)

5.1.1 Operator Workspace Assembly

Figure 5-1 Operator Workspace Assembly
5
1300mm
(51.2 in)
1234 mm
(48.6 in)
750 mm
(29.5 in)
877.3 mm (34.5 in)
127 mm (5 in)
102 mm (4 in)
5538858-1EN Revision 4 SIGNA™ Prime 98/126
Preinstallation Manual 5.1 Operator Workspace Equipment Specications

5.1.2 Operator Workspace (OW) (Optional Equipment)

1. Weight: 57 kg (125 lb.)
2. Magnetic Field Limit: 5 mT (50 G)
Figure 5-2 Operator Workspace (OW) Table (Top and Front View)
Item Description
1 Four (4) 15.9 mm (5/8 in.) thru mounting holes for 9.5 mm (3/8 in.) seismic anchors
5538858-1EN Revision 4 SIGNA™ Prime 99/126
Preinstallation Manual 5.1 Operator Workspace Equipment Specications

5.1.3 Global Operator Cabinet (GOC)

1. Weight: 57.6 kg (127 lb.)
2. Magnetic Field Limit: 5 mT (50 G)
3. Anchor size: 9.5 mm (0.375 in.)
Figure 5-3 Global Operator Cabinet (GOC)
Item Description
1 Seismic anchor hole location
5538858-1EN Revision 4 SIGNA™ Prime 100/126
Loading...