The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be
reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and are not
necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
Page 3
Critical Power
Modifications reserved
Page 3/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Dear Customer,
We thank you for selecting our products and are
pleased to count you amongst our very valued
customers at GE.
We trust that the use of the SG Series 10-20-30-40
Uninterruptible Power Supply system, developed and
produced to the highest standards of quality, will
give you complete satisfaction.
Please read carefully the Installation Guide, which
contains all the necessary information and describes
all you need to know about the installation of the
UPS.
Thank you for choosing GE !
START-UP AND COMMISSIONING
A GE GLOBAL SERVICES FIELD ENGINEER must perform start-up and
commissioning of the UPS.
Please Contact GE. GLOBAL SERVICES at least two weeks prior to schedule
start-up and commissioning at 1-800-637-1738, or by E-mail at
Chicago, IL 60609
24/7 T: 800-637-1738
24/7 T: 773-299-6600
F: 866-765-3595
E: pqservice@ge.com
Page 4
Critical Power
Modifications reserved
Page 4/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Congratulations on your choice of a SG Series 10-20-30-40 Uninterruptible Power Supply
(UPS). It will help eliminate Load disturbances due to unexpected power problems.
This Manual describes the function of the UPS module, the purpose and location of the
switches, the meaning of the system events related to the front panel indication, and
provides procedures for starting and stopping the equipment.
Please refer to the accompanying Installations Guide, which describes how to prepare the
installation site, and it provides weight, dimensions and procedures for moving, installing
and connecting the UPS.
While every care has been taken to ensure the completeness and accuracy of this manual,
GE assumes no responsibility or liability for any losses or damages resulting from the use
of the information contained in this document.
NOTE!
SG Series 10-20-30-40 is a product that needs to be installed by a licensed and
knowledgeable contractor.
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual, please
contact your Service Center before you proceed.
This document shall not be copied or reproduced without the permission of GE.
Some of the information contained in this manual may be changed without notice to
reflect technical improvements.
Safety instructions
Read the safety instructions contained on the following pages carefully before the
installation of the UPS, options and Battery System.
Pay attention to the rectangular boxes included in the text:
They contain important information and warning concerning electrical connections and
personnel safety.
Parallel version secured with RPA
When included in the text, this symbol refers to operation needed
only for parallel system.
3.1 TRANSPORT .................................................................................................................................................................................................11
3.1.1 Dimensions and weight ........................................................................................................................................................................ 11
3.3.1 Storage of the UPS .................................................................................................................................................................................. 12
3.3.2 Storage of battery ................................................................................................................................................................................... 12
3.4 PLACE OF INSTALLATION ......................................................................................................................................................................13
3.5 VENTILATION AND COOLING ..............................................................................................................................................................16
3.7.2 Input/output over current protection and wire sizing ............................................................................................................. 20
3.7.3 Battery over current protection and wire sizing ........................................................................................................................ 21
3.8.1 Power connections .................................................................................................................................................................................. 24
3.8.2 Power connection with common input utility of SG Series 10 & 20 .................................................................................. 27
3.8.3 Power connection with common input utility of SG Series 30 & 40 .................................................................................. 28
3.8.4 Power connection dual input utility of SG Series 10 & 20 ...................................................................................................... 29
3.8.5 Power connection dual input utility of SG Series 30 & 40 ...................................................................................................... 31
3.8.6 Battery connection of SG Series 10 & 20 ....................................................................................................................................... 33
3.8.7 Battery connection of SG Series 30 & 40 ....................................................................................................................................... 34
3.8.8 Set-up for SG Series 10-20-30-40 when functioning as frequency converter ............................................................. 35
3.9 RPA PARALLEL SYSTEM CONNECTION ...........................................................................................................................................36
3.9.1 Power wiring of parallel units ............................................................................................................................................................. 36
3.9.2 Parallel control bus connection ......................................................................................................................................................... 37
3.9.3 Control bus cable location ................................................................................................................................................................... 39
4.1.1 Serial Port J3 .............................................................................................................................................................................................. 42
4.1.4 Gen Set Signaling (GEN ON) ................................................................................................................................................................. 43
4.1.5 AUX external Maintenance Bypass .................................................................................................................................................. 43
4.1.6 Auxiliary Power Supply (APS) 24 Vdc ............................................................................................................................................... 43
4.1.7 “EPO - Emergency Power Off” command connection ............................................................................................................. 44
5.1 NOTES FORM ..............................................................................................................................................................................................46
Page 6
Critical Power
Modifications reserved
Page 6/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
GENERAL
- Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
- Check for sufficient floor and elevator loading capacity.
- Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS.
Contact the nearest Service Center immediately.
- WARNING! RISK OF ELECTRICAL SHOCK:
Do not remove covers, there are no user serviceable parts inside.
- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage
remains at the terminals of the electrolytic capacitors.
- All maintenance and service work should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
- The field-wiring outlets may be electrically live, even when the UPS is disconnected from the utility.
- Dangerous voltages may be present during battery operation.
- The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
- End user must follow applicable regional occupational safety codes/regulations during installation,
operation and equipment maintenance. This may require additional field marking or labeling defining
appropriate level of PPE (Personal Protection Equipment) to reduce the risk of Arc-flash related injuries.
Contact our Technical Support for product specific information.
INSTALLATION
- This UPS must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are
correctly reattached.
- This UPS is intended for use in a controlled indoor environment free of conductive contaminants and
protected against animals intrusion.
- WARNING! HIGH EARTH LEAKAGE CURRENT:
Earth connection is essential before connecting to AC input!
- Switching OFF the unit does not isolate the UPS from the utility.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104F (40°C).
- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25C).
- It is important that air can move freely around and through the unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
STORAGE
- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55C).
- The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range 4°F (-20°C) to 104°F (40°C).
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time
depending on storage temperature).
BATTERY
- The battery-voltage is dangerous for person’s safety.
- When replacing the battery, use the same cells number, voltage (V), capacity (Ah).
All the battery used, shall be of the same manufacturer and date of production.
- Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
- Never dispose of battery in a fire: they may explode.
- Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
- Never short-circuit the batteries.
When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.
- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.
1 SAFETY RULES
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models SG Series 10-20-30-40 that should be followed
during installation and maintenance of the UPS and battery.
Page 7
Critical Power
Modifications reserved
Page 7/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY
QUALIFIED SERVICE PERSONNEL.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION BEFORE HANDLING
THE UPS AND BATTERY.
DANGER!
Full voltage and current are always present at the battery terminals.
The battery used in this system can provide dangerous voltages, extremely high currents and a
risk of electric shock.
If the terminals are shorted together or to ground they may cause severe injury.
You must be extremely careful to avoid electric shock and burns caused by contacting battery
terminals or shorting terminals during battery installation.
Do not touch uninsulated battery terminals.
A qualified service person, who is familiar with battery systems and required precautions, must
install and service the battery.
The installation must conform to national and local codes.
Keep unauthorized personnel away from the battery.
The qualified service person must take these precautions:
1 Wear protective clothing, such as rubber gloves and boots and protective eye wear
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated.
Remove rings and metal wristwatches or other metal objects and jewelry.
Do not carry metal objects in your pockets where the objects can fall into the battery
cabinet.
2 Tools must have insulated handles and must be insulated so that they will not short battery
terminals.
Do not allow a tool to short between individual or separate battery terminals or to the
cabinet or rack.
Do not lay tools or metal parts on top of the battery, and do not lay them where they could
fall onto the battery or into the cabinet.
3 Install the battery as shown on the drawing provided with the battery.
When connecting cables, never allow a cable to short across a battery’s terminals, the
string of battery, or to the cabinet or rack.
4 Align the cables on the battery terminals so that the cable lug will not contact any part of
the cabinet or rack, even if the battery is moved.
Keep the cable away from any sharp metal edges.
5 Install the battery cables in such a way that the UPS or battery cabinet doors cannot pinch
them.
6 Do not connect the battery terminal to Ground.
If any battery terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock.
7 To reduce the risk of fire or electric shock, install the battery in a temperature and humidity
controlled indoor area, free of contaminants.
8 Battery system chassis ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduits, this ground conductor must be routed in the same conduit as the
battery conductors.
9 Where conductors may be exposed to physical damage, protect the conductors in
accordance with all applicable codes.
10 If you are replacing the battery or repairing battery connections, shut OFF the UPS and
remove the battery fuses.
Safety instructions when working with battery
Page 8
Critical Power
Modifications reserved
Page 8/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
WARNING, if instruction is not followed injury or serious equipment damage may
occur!
CAUTION, internal parts have dangerous voltage present.
Risk of electric shock!
PE (Earth) – GND (Ground)
PROTECTIVE GROUNDING TERMINAL:
A terminal which must be connected to earth ground prior to making any other
connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or voltage
may be applied or supplied.
A terminal to which or from which a direct current or voltage may be applied or
supplied.
This symbol indicated the word “phase”.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.
Safety symbols and warnings
Safety warnings
The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to
the UPS system and the supplied critical loads.
The non-observance of the warnings reminding hazardous situations could result in human injury and
equipment damages.
Please pay attention to the meaning of the following warnings and symbols.
Throughout this manual the following symbols are defined:
Page 9
Critical Power
Modifications reserved
Page 9/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 2.1-1 SG Series 10 & 20 general view
Fig. 2.1-2 SG Series 10 & 20 general view with open doors
Fig. 2.1-3 SG Series 10 & 20 general view with optional 5th harmonic filter
and removed protection panels
1 Opening for top cable entry
2 Opening for bottom cable entry
3 Terminals for Utility input and load
output
4Terminals for external Battery
connection
5 Battery Shelf
CR Connectivity Rack
XA Terminals for 24Vdc Auxiliary
Power Supply connection
XB Terminals for EPO connection
SGT5000_030-040_UPS_GE_02a
SGT5000_010-020_UPS_GE_03
SGT5000_010-020_UPS_GE_04
4
1
2
5
CRXAXB
3
2 LAYOUT
2.1 LAYOUT SG Series 10 & 20
Page 10
Critical Power
Modifications reserved
Page 10/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 2.2-1 SG Series 30 & 40 general view
Fig. 2.2-2 SG Series 30 & 40 general view with open doors
Fig. 2.2-3 SG Series 30 & 40 general view with optional 5th harmonic filter
and removed protection panels
1 Opening for top cable entry
2 Opening for bottom cable entry
3 Terminals for Utility input and load
output
4Terminals for external Battery
connection
CR Connectivity Rack
XA Terminals for 24Vdc Auxiliary
Power Supply connection
XB Terminals for EPO connection
SGT5000_030-040_UPS_GE_02a
SGT5000_030-040_UPS_GE_03
Q1
Q2
ON
OFF
OFF
ON
SGT5000_030-040_UPS_GE_04
4
1
3
2XBXACR
OFF
ON
OFF
ON
2.2 LAYOUT SG Series 30 & 40
Page 11
Critical Power
Modifications reserved
Page 11/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Forklift
Crane
Fig. 3.1-1 UPS cabinets moving
Transport UPS only in upright position!
The UPS is packaged on a pallet suitable for handling with
a forklift.
Pay attention to the center of gravity.
The UPS must be moved in upright position.
Do not tilt cabinets more than +/- 10° during handling.
Move the UPS in it’s original package to the final
destination site.
Do not stack other packages on top: This could damage
the UPS.
If the UPS must be lifted by crane, use suitable lifting straps
and spreader bars.
Note of the center of gravity marked on the package.
Take all necessary precautions to avoid damage to the
cabinet while hoisting the UPS.
NOTE !
Check for sufficient floor and elevator
loading capacity.
Fig. 3.1.1-1 UPS cabinet dimensions
Dimensions SG Series 10-20-30-40
(W x D x H)
26.78 x 31.50 x 70.90 inches
680 x 800 x 1,800 mm
Weight SG Series 10-20-30-40
UPS rating
kVA
UPS without battery
UPS with battery
Weight
lbs / kg
Floor loading
lbs/sq.ft - kg/m2
Weight
lbs / kg
Floor loading
lbs/sq.ft - kg/m2
SG Series 10
735 / 333
126 / 613
1,121 / 508
192 / 934
SG Series 20
763 / 346
131 / 637
1,169 / 530
200 / 975
SG Series 30
970 / 440
166 / 809
–
–
SG Series 40
1,147 / 520
196 / 956
–
–
SGSU_030-040_UPS dimensions_GE_01aUS
W
D
H
3 INSTALLATION
3.1 TRANSPORT
3.1.1 Dimensions and weight
P.S.: Weights including the 5th harmonic filter.
Page 12
Critical Power
Modifications reserved
Page 12/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
NOTE !
A DAMAGED UPS MUST NEVER BE INSTALLED OR CONNECTED TO UTILITY OR
BATTERY!
Recharge stored maintenance free battery every:
6 months when the storage temperature is 68°F (20°C)
3 months when the storage temperature is 86°F (30°C)
2 months when the storage temperature is 95°F (35°C)
3.2 DELIVERY
When delivered, inspect the package integrity and the physical conditions of the cabinets carefully.
In case of any damage sustained during transport, immediately inform the carrier and contact your
local Service Center.
A detailed report of the damage is necessary for any insurance claim.
3.3 STORAGE
3.3.1 Storage of the UPS
The UPS is carefully packed for transport and storage so that it is in perfect condition when installed.
Never leave a UPS outside the building and don’t store other packages on the top of the UPS.
It is advisable to store the UPS in its original package in a dry, dust-free room, away from chemical
substances, and with a temperature range not exceeding -13°F (-25°C) to 131°F (55°C).
In case the battery is included please refer to Section 3.3.2.
Some important functions of the UPS, such as the customized functions, are defined by parameters
stored in a RAM memory.
A small backup battery located on the Control Unit board supplies the RAM.
If the storage time of the UPS exceeds 1 year, these functions should be verified by an authorized
Service Center before putting the UPS into operation.
3.3.2 Storage of battery
When the delivery includes a maintenance free battery, keep in mind that they are subject to selfdischarge and therefore you must recharge the battery.
The storage time without battery recharge depends on the temperature of the storage site.
The optimal room temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed
the range -4°F (-20°C) to 104°F (40°C).
Page 13
Critical Power
Modifications reserved
Page 13/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
WARNING !
A QUALIFIED ELECTRICAL CONTRACTOR must carry out the installation and cabling
of the UPS.
If optional cabinets and accessories are included with the UPS, please refer to those
accompanying manuals for installation and operating instructions.
NOTE !
Temperature is very important for valve-regulated batteries (maintenance free).
Operation at temperatures higher than 77°F (25°C) will reduce battery life.
Positioning of the UPS SG Series 10-20-30-40
Fig. 3.4.1-1 SG Series10-20-30-40 clearances
The rear panel of the UPS may be mounted flush to a
wall or other structure.
Clearance around the front of the unit should be
sufficient to enable free passage of personnel with the
doors fully open, and to allow sufficient airflow to the
door vents.
Check Section 110-26(A) of the NEC code for specific
requirements.
Recommended minimum clearance between ceiling
and top of the UPS should be 16” (400 mm) for proper
cooling air exhaust.
In case of additional cabinets (external batteries or
input, output transformers) these can be placed on
either side of the cabinet.
SGSU_030-040_UPS disposition_GE_01a
16" / 400mm
Min.
3.4 PLACE OF INSTALLATION
3.4.1 UPS location
It is important to have a clean, dust-free environment provided with proper ventilation and airconditioning to keep the ambient temperature within the specified operating range.
The recommended air inlet temperature is from 68°F (20°C) to 77°F (25°C) (max. 104°F / 40°C).
Refer to Section 3.5.
Check for sufficient floor load capacity before installing the UPS and the battery.
Refer to Section 3.1.1.
For battery installation follow the local codes and the recommendation of the battery supplier.
The SG Series 10-20-30-40 UPS can radiate radio frequency energy.
Although some RFI filtering is inherent to the UPS there is no guarantee that the UPS will not influence
sensitive devices such as cameras and monitors that are positioned close by.
If interference is expected, the UPS should be moved away from the sensitive equipment.
A single-phase power outlet (120Vac) should be provided near the UPS for connection of power tools,
test equipment or connectivity devices. This outlet must be grounded.
Page 14
Critical Power
Modifications reserved
Page 14/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Openings for input and output cable connections
Fig. 3.4.1-2 Opening on top of the cabinet for input and
cables of SG Series 10 & 20
Fig. 3.4.1-3 Opening on top of the cabinet for input and
cables of SG Series 30 & 40
Fig. 3.4.1-4 Opening on the bottom of the cabinet for input and
output cables SG Series 10-20-30-40
SG Series 10-20-30-40 openings are
provided on the top and the bottom of the
UPS for the connection of input and output
cables.
Pay attention to the position of these
openings, when choosing the placement of
the UPS.
These openings are covered with a
protective plate.
Positioning of the UPS cabinet
SG Series 10-20-30-40 is equipped with
wheels for easy placement of the UPS.
To make the UPS movable on wheels, the
bolts on each leg of the cabinet have to be
turned counter-clockwise, until they are
free from the floor and thus the cabinet
supported on wheels.
After having positioned the UPS at its final
location, the cabinet has to be secured by
rotating the bolts on each leg clockwise,
but the wheels must still touch the floor.
Fig. 3.4.1-4 Bolts for the regulation of the cabinet
The UPS cabinet is free
standing and normally does
not require to be bolted to
the floor.
The UPS cabinet can be fixed
however to the floor by
bolting it with the supporting
blocks to the floor.
The supporting blocks can be
used in different positions (0°
- 360°)
These supporting blocks are
part of the shipping package.
See Fig. 3.4.1-5.
Fig. 3.4.1-5 Fixing of the UPS cabinet on the floor
SGT5000_010-020_UPS view top_01US
31.50"
800mm
9.06"
1.58"
40mm
230mm
9.06"
70mm
2.76"
26.78"
680mm
230mm
Utility input
Output Load
Battery
SGT5000_030-040_UPS view top_01US
31.50"
800mm
13.78"
1.58"
40mm
110mm
4.33"
70mm
2.76"
26.78"
680mm
350mm
Utility input
Output Load
Battery
SGT5000_030-040_UPS view bottom_01US
26.78"
680mm
7.09"
180mm
70mm
2.76"
50mm
1.97"
7.88"
200mm
31.50"
800mm
Utility input
Output Load
To lower
To lift
SGSU_050-080_UPS wheels_01aUS
SGSU_010-020_UPS fixing_01a
0 - 360°
Page 15
Critical Power
Modifications reserved
Page 15/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.4.1-6 RPA system disposition
In case of parallel system, try to place
the UPS modules in sequence of their
numbers (marked on the packing).
If the units are positioned “side by side”,
the side panels must be mounted on all
units.
NOTE !
Battery installation and connection must be performed by QUALIFIED PERSONNEL
ONLY.
Read all safety instructions before proceeding with the installation.
SGSU_050-080_RPA disposition_GE_01aUS
UPS 1
UPS
3 - 4 - 5 - 6 - 7 - 8
UPS 2
3.4.2 Battery location
Batteries require a well-ventilated room with controlled temperature to obtain reliable operation.
The battery can be install immediately adjacent to the UPS (left or right side) or remotely from the UPS.
If the battery is installed remotely from the UPS, a wall mounted DC disconnect device must be installed
within line-of-site to both the UPS and the battery.
The optimal room temperature for Battery location is 68°F (20°C) to 77°F (25°C) and shall never exceed
the range -4°F (-20°C) to 104°F (40°C).
The life of valve-regulated batteries will be reduced by 50% for each additional 18°F (10°C) that the
battery ambient temperature is above 77°F (25°C).
The battery system associated with larger UPS is usually either rack mounted or installed in multiple
battery cabinets.
Installation and assembly must be made according to the local standards and battery system
manufacturer‘s recommendations.
The battery circuit breaker or battery fuse box must be mounted as near as possible to the battery.
Page 16
Critical Power
Modifications reserved
Page 16/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.5-1 Installation on plain floor
Fig. 3.5-2 Installation on raised floor
NOTE !
Do not put anything on the top of the cabinet.
UPS rating
kVA
Losses
Cooling air flow
BTU / hr
kW
CFM
m3 / h
SG Series 10
3,036
0.89
135
230
SG Series 20
6,751
1.98
301
512
SG Series 30
8,104
2.37
361
614
SG Series 40
10,808
3.17
482
819
3.5 VENTILATION AND COOLING
The heat produced by the UPS is transferred to the environment by its ventilation.
Air inlets for UPS ventilation are located on the front of the UPS, while air outlets are on top of the
cabinet.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS room.
Air filtration systems could be required when the UPS operates in a dirty environment.
Contact your Dealer or the nearest Service Center for appropriate solutions.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air
exhaust flow rate requirement of the UPS system.
The below table indicates the heat dissipation at full load at PF = 0.8 lag. and charged battery, up to
3,280 ft (1,000 m) altitude, for cooling air 77°F (25°C) to 86°F (30°C).
Page 17
Critical Power
Modifications reserved
Page 17/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
NOTE !
Check for sufficient floor and elevator loading capacity.
Take care not to damage the UPS when moving by forklift.
Remove the cabinet from the pallet with care because of the heavy weight of the
equipment.
1 2
Make sure to have sufficient space around
the UPS before you start unpacking.
Cut the three straps “A” fixing the carton box.
Remove package “B” and “C”.
Remove the protection “D” outside the cabinet
and the accessories bag.
Remove the wooden support “E”, which must be
used to hoist the UPS.
Unscrew anchoring bolt “F” from plate on all
four legs.
3 4
Position the fork lift “G” with an opening
between the forks of 33.50” (850mm).
Insert the wooden support “E” underneath
the UPS, paying attention that the 2 guides
“E1” are positioned with the UPS in the center.
Lift the UPS cabinet.
Remove the wooden pallet “H”.
Loosen the 4 screws “I” and remove then the 4
anchoring plates “L”.
Put the UPS down on the floor.
Remove finally the wooden support “E”.
3.6 UNPACKING
The UPS and battery cabinets may be shipped packaged in carton boxes or in wooden crates (if
requested).
Move the cabinets as close as possible to the final location before removing from the pallet.
To unpack the cabinet packaged in Carton Box follow the instructions below:
Page 18
Critical Power
Modifications reserved
Page 18/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
1 2
Make sure to have sufficient space
around the UPS before you start
unpacking.
Remove the wooden sides “A” and “B” loosening the
appropriate screws.
Remove the protection “C” outside the cabinet and the
accessories bag.
Remove the wooden support “D”, which must be used
to hoist the UPS.
Unscrew anchoring bolt “E” from plate on all four legs.
3 4
Position the fork lift “F” with an opening
between the forks of 33.50” (850mm).
Insert the wooden support “D”
underneath the UPS, paying attention
that the 2 guides “D1” are positioned
with the UPS in the center.
Lift the UPS cabinet.
Remove the wooden pallet “G”.
Loosen the 4 screws “H” and remove then the 4
anchoring plates “I”.
Put the UPS down on the floor.
Remove finally the wooden support “D”.
NOTE !
A damaged UPS must never be installed or connected to mains or battery!
In case of any damage sustained during the transport, immediately inform the
shipping agent!
A detailed report of the damage is necessary for any indemnity claim.
Packing material recycling
GE, in compliance with environment protection, use only environmentally
friendly material.
UPS packing materials must be recycled in compliance with all applicable
regulations.
To unpack the cabinet packaged in Wooden Crate follow the instructions below:
Included in the delivery you can find the following parts:
An accessories bag Control Bus cables (only for RPA parallel system)
Page 19
Critical Power
Modifications reserved
Page 19/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
WARNING !
UPS installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL ONLY.
It is the responsibility of the installation technician to ensure that all local and
national electric codes are adhered to.
NOTE !
Ensure that the AC and DC external isolators are OFF and locked out to prevent their
inadvertent operation.
Do not apply power to the equipment prior to the commissioning by a qualified
service engineer.
Before any other input connection, connect and check the grounding wire.
The Bypass and Rectifier inputs are to be powered from different Utility supplies (F1 and F2 inputs).
In this case, when the Rectifier Input Fuses are opened, the Bypass and the Manual Bypass are
supplied by the other source.
In this case, REMOVE the interconnection links BR1, BR2 and BR3 on the input
terminals or bus bars.
See Fig. 3.8.4-2 for SG Series 10 & 20 and Fig. 3.8.5-2 for SG Series 30 & 40.
Common input Rectifier & Bypass
The same power source is to be used for both Bypass Supply and Rectifier Input (input F3). Bear in
mind that when the Utility Fuses are opened there is a supply failure to the Rectifier as well as to the
Bypass and Manual Bypass.
In this case, the interconnection links BR1, BR2 and BR3 on the input terminals or
bus bars MUST REMAIN CONNECTED.
See Fig. 3.8.4-2 for SG Series 10 & 20 and Fig. 3.8.5-2 for SG Series 30 & 40.
The UPS has available input terminations for the Rectifier and Bypass.
The unit may be powered from a common input source or dual input sources if desired.
Page 20
Critical Power
Modifications reserved
Page 20/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
NOTE !
If you use ELCB breaker (Earth Limiting Circuit Breaker) to protect the input
connections, consider the high leakage current generated by the noise suppression
capacitors.
If these ELCB breakers are strictly necessary, we suggest using the largest type
suitable for non-linear current and for delayed operations.
3.7.2 Input/output over current protection and wire sizing
The cabling of the UPS system has to be sized according to the UPS power rating.
Sizing of circuit breakers, fuses and cables for Input Utility, Output Load and Battery must meet the
requirements of local and national electrical codes.
Before connecting the UPS, verify that the Utility Voltage and Frequency, the Output Load Voltage and Frequency and Battery Data (cells number, floating voltage, autonomy) are according to the required
specifications.
Output load configuration may be such that one phase may carry a load current at 100% of that phases
maximum current rating while the other two phases run at 0% or any combination in between.
Ensure that the load does not consist of any equipment that may require high starting currents such as
electric motors, laser printers, etc.
This may cause the UPS to occasionally go into Bypass due to overload conditions
To choose the correct input fuses or circuit breaker, consider the available short-circuit current of the
system up-stream.
Choose the correct fuse or breaker using current data shown in the chart and the appropriate NEC
code.
The ratings indicated in the following chart do not consider any line voltage drop.
In case of optional input transformer the input protective devices should be sized to allow the
transformer magnetization inrush current.
Caution when using four-pole circuit breakers as protection.
A potential problem exists for situations with non-linear loads:
The neutral current could be greater than the phase currents.
The three-phase Utility power supply must be symmetrical with respect to ground, due to the existence
of voltage surge protection devices inside the UPS.
To ensure coordination when the UPS is configured for Separate Bypass and Rectifier Inputs, special care
must be taken in choosing the fuse or circuit breaker ratings installed in the output distribution circuits.
Protective devices on the output of the UPS should be coordinated with the Bypass Input circuit
protection.
Due to the relatively low short circuit capability of the UPS inverter, a short circuit in the load will cause
an immediate transfer to Bypass.
The largest fuse or circuit breaker in the output distribution should be rated at no more than 60% of the
rating of the protective device supplying the Bypass line.
If circuit selectivity is required while the load is fed from the inverter (Bypass Utility not available), the
largest fuse or circuit breaker should be rated at no more than 20% of the UPS output current rating.
Page 21
Critical Power
Modifications reserved
Page 21/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
The AC values below are current ratings per phase.
These maximum and nominal ratings should be considered when choosing the appropriate AC
over current protection device.
NEC (National Electric Code) Section 210-20 a rules must be applied.
DC current rating is the nominal battery discharge current which the UPS allows.
(See Fig. 3.7.1-1 and 3.7.1.2)
UPS rating
AC Input Rectifier
AC Input
Bypass
AC Input
DC Input
F1
F2
F3
F4
Nom.
Max.
Nom.
Max.
SG Series 10
17.2 A
20.2 A
12 A
17.2 A
20.2 A
19.6 A
SG Series 20
27.3 A
36.6 A
24.1 A
27.3 A
36.6 A
36 A
SG Series 30
40.4 A
53.1 A
36.1 A
40.4 A
53.1 A
55.2 A
SG Series 40
53.9 A
63.2 A
48.2 A
53.9 A
63.2 A
76 A
Size of Branch Circuit Over current Protection - All Models: - "CAUTION - To reduce the risk of fire,
only connect UPS to a circuit provided with (See below) maximum amperes branch circuit over
current protection in accordance
with the NEC (National Electric Code), NSI / NFPA 70
UPS rating
AC Input Rectifier
AC Input Bypass
AC Input
DC Input
F1
F2
F3
F4
SG Series 10
30 A
15 A
30 A
25 A
SG Series 20
50 A
35 A
50 A
50 A
SG Series 30
70 A
50 A
70 A
70 A
SG Series 40
80 A
70 A
80 A
100 A
3.7.3 Battery over current protection and wire sizing
Please read the safety precautions at the front of this guide carefully, and thoroughly review the
battery manufacturers installation and maintenance manual before connecting the batteries to the
UPS.
If the UPS system has been purchased with an accompanying battery cabinet, that cabinet should
have an integral battery circuit breaker.
If the UPS has been purchased without a battery cabinet or remote rack mounted batteries are to
be used then DC over current protection must be provided by others.
Choose an appropriate DC fuse or circuit breaker using the current data in the chart below.
Minimum battery cable requirement is based on the current data below.
Page 22
Critical Power
Modifications reserved
Page 22/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
WIRING
Wire sizing according to
NEC Section 210-20 (a) Table 310-16
Use 75°C (167°F) copper wire
Wiring requirements:
AC INPUT RECTIFIER: 3-Phase, 3 wire plus Ground
AC INPUT BYPASS: 3-Phase, 4 wire plus Ground
AC OUTPUT: 3-Phase, 4 wire plus Ground
DC INPUT: 2 wire (positive and negative) plus Ground
Maximum cable diameter that terminals can accept
Refer to torque specifications table for torque requirements
UPS rating
Rectifier Input
Bypass Input
DC Input
AC Output
GND
SG Series 10
3 AWG
3 AWG
3 AWG
3 AWG
3 AWG
SG Series 20
3 AWG
3 AWG
3 AWG
3 AWG
3 AWG
SG Series 30
1 AWG
1 AWG
1 AWG
1 AWG
1 AWG
SG Series 40
1 AWG
1 AWG
1 AWG
1 AWG
1 AWG
Page 23
Critical Power
Modifications reserved
Page 23/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Temperature Rating of Conductor (See table 310-13)
Size
60°C (140°F)
75°C (167°F)
90°C (194°F)
60°C (140°F)
75°C (167°F)
90°C (194°F)
AWG
or
kcmil
Types
TW, UF
Types
FEPW, RH, RHW,
THHW, THW,
THWN, XHHW,
USE, ZW
Types
TBS, SA, SIS, FEP,
FEPB, MI, RHH,
RHW-2, THHN,
THHW, THW-2,
THWN-2, USE-2,
XHH, XHHW,
XHHW-2,ZW-2
Types
TW, UF
Types
RH, RHW,
THHW,
THW, THWN,
XHHW, USE
Types
TBS, SA, SIS,
THHN, THHW,
THW-2,
THWN-2, RHH,
RHW-2, USE-2,
XHH, XHHW,
XHHW-2,
ZW-2
COPPER
ALUMINIUM or COPPER-CLAD ALUMINIUM
18
---
---
14
---
---
---
16
---
---
18
---
---
---
14
20
20
25
---
---
---
12
25
25
30
20
20
25
10
30
35
40
25
30
35
8
40
50
55
30
40
45
6
55
65
75
40
50
60 4 70
85
95
55
65
75
3
85
100
110
65
75
85
2
95
115
130
75
90
100
1
110
130
150
85
100
115
1/0
125
150
170
100
120
135
2/0
145
175
195
115
135
150
3/0
165
200
225
130
155
175
4/0
195
230
260
150
180
205
250
215
255
290
170
205
230
300
240
285
320
190
230
255
350
260
310
350
210
250
280
400
280
335
380
225
270
305
500
320
380
430
260
310
350
600
355
420
475
285
340
385
700
385
460
520
310
375
420
750
400
475
535
320
385
435
800
410
490
555
330
395
450
900
435
520
585
355
425
480
1000
455
545
615
375
445
500
1250
495
590
665
405
485
545
1500
520
625
705
435
520
585
1750
545
650
735
455
545
615
2000
560
665
750
470
560
630
CORRECTION FACTORS
Ambient
Temp. (°C)
For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown above by the appropriate factor
below
21 - 25
1.08
1.05
1.04
1.08
1.05
1.04
26 - 30
1.00
1.00
1.00
1.00
1.00
1.00
31 - 35
0.91
0.94
0.96
0.91
0.94
0.96
36 - 40
0.82
0.88
0.91
0.82
0.88
0.91
41 - 45
0.71
0.82
0.87
0.71
0.82
0.87
46 - 50
0.58
0.75
0.82
0.58
0.75
0.82
51 - 55
0.41
0.67
0.76
0.41
0.67
0.76
NEC SECTION 210-20 (a)
Table 310-16. Allowable Ampacities of Insulated Conductors Rated O Through 2000 Volts, 60°C Trough
90°C (140°F Trough 194°F) Not More than Three Current-Carrying Conductors in Raceway, Cable, or
Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F).
Page 24
Critical Power
Modifications reserved
Page 24/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
WARNING!
UPS installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL ONLY.
Torque Specifications
Mechanical Terminals
Input / Output / Battery and GND
UPS rating
WIRE SIZE RANGE
Lb - in
Nm
SG Series 10 & 20
20 AWG to 3 AWG
27
3
SG Series 30 & 40
16 AWG to 1 AWG
22
2.5
3.8 WIRING CONNECTION
3.8.1 Power connections
Input/output and DC connections are provided with terminal blocks.
Please refer to chart for torque specifications.
Carefully read the following recommendations before proceeding:
Ensure that the AC and DC external isolators are OFF and locked to prevent their inadvertent
operation.
Do not close any external isolators prior the commissioning of the equipment.
The preferred power cable entry location for installation purposes is from the right side of the UPS,
either top or bottom.
In case of cable entry from the top of the cabinet, remove the cover plate fitted on the roof and
provide for a suitable isolated protection cover.
In case of cable entry from the bottom remove cover plate and perform the same procedure.
The input/output cables must be connected in clockwise phase rotation for both Bypass and
Rectifier Input Terminals if separate, taking care to avoid risk of short circuit between different poles.
The grounding and neutral connection of the electrical system must be in accordance with local
regulations.
In case of additional cabinets containing batteries, input/ output transformers, etc, their ground
terminals must be connected to the UPS main ground terminal.
Once the power cables have been connected, re-install the internal safety shields and close the
cabinets by re-installing all external panels.
Page 25
Critical Power
Modifications reserved
Page 25/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
SG Series 10 & 20
How to access the terminals for the cable connections.
Fig. 3.8.1-1 Access to the input / output connections of SG Series 10 & 20
To access input, output and Battery connections proceed as follows:
Remove protection panel “A”.
Remove protection panel “B”.
Remove UPS side panel “C”.
Only for Dual Input Utility:
Remove with appropriate tool the metallic window “D” from the metal screen “C”.
A
C
B
Bottom entry cables
Top entry cables
SGUL_010-020_UPS connection_01US
D
E
!
Please remove the plate "E & F"
before drilling any wholes.
F
Page 26
Critical Power
Modifications reserved
Page 26/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
SG Series 30 & 40
How to access the terminals for the cable connections.
Fig. 3.8.1-2 Access to the input / output connections of SG Series 30 & 40
To access input, output and Battery connections proceed as follows:
Remove protection panel “A”.
Remove protection panel “B”.
Remove UPS side panel “C”.
Only for Dual Input Utility:
Remove with appropriate tool the metallic window “D” from the metal screen “C”.
D
Bottom entry cables
Top entry cables
A
B
C
E
!
before drilling any wholes.
Please remove the plate "E & F"
SGUL_030-040_UPS connection_01US
F
Page 27
Critical Power
Modifications reserved
Page 27/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.8.2-1 Power connections Common Input Utility of SG Series 10 & 20
Common Input Rectifier / Bypass
L1-1
Rectifier + Bypass Phase A
L2-1
Rectifier + Bypass Phase B
L3-1
Rectifier + Bypass Phase C
N Neutral
PE
Ground
Output Load
L1
Load Phase A
L2
Load Phase B
L3
Load Phase C
N
Load Neutral
PE
Load Ground
NOTE !
This UPS is only designed to operate in a wye-configured electrical system with a
solidly grounded neutral.
If the UPS is equipped with an input transformer, the secondary of the transformer
must be wye-configured with neutral solidly grounded.
SGT5000_010-020_UPS connection common_01US
N
L1-1
1 - INPUTLOAD
PE
L3-1
L2-1
N
L2
L1
L3
RECTIFIER
X1
PE
&
BYPASS
3.8.2Power connection with common input utility of SG Series 10 & 20
The interconnection links BR1, BR2 and BR3 MUST REMAIN CONNECTED.
Cable terminations are to the Rectifier Input Terminals and Output Terminals as shown above.
Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: see Section 3.8.1.
Page 28
Critical Power
Modifications reserved
Page 28/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.8.3-1 Power connections Common Input Utility of SG Series 30 & 40
Common Input Rectifier / Bypass
L1-1
Rectifier + Bypass Phase A
L2-1
Rectifier + Bypass Phase B
L3-1
Rectifier + Bypass Phase C
N Neutral
PE
Ground
Output Load
L1
Load Phase A
L2
Load Phase B
L3
Load Phase C
N
Load Neutral
PE
Load Ground
NOTE !
This UPS is only designed to operate in a wye-configured electrical system with a
solidly grounded neutral.
If the UPS is equipped with an input transformer, the secondary of the transformer
must be wye-configured with neutral solidly grounded.
L1-1
X1
RECTIFIER
1 -
INPUT
L1
LOAD
PE
PE
SGT5000_030-040_UPS connection common_01US
L2
L3
N
L2-1
L3-1
N
OFF
ON
OFF
ON
&
BYPASS
3.8.3Power connection with common input utility of SG Series 30 & 40
The interconnection links BR1, BR2 and BR3 MUST REMAIN CONNECTED.
Cable terminations are to the Rectifier Input Terminals and Output Terminals as shown above.
Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: see Section 3.8.1.
Page 29
Critical Power
Modifications reserved
Page 29/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.8.4-1 Power connections Dual Input Utility of SG Series 10 & 20
Dual Input Configuration Rectifier / Bypass
L1-1
Rectifier Phase A
L1-2
Bypass Phase A
L2-1
Rectifier Phase B
L2-2
Bypass Phase B
L3-1
Rectifier Phase C
L3-2
Bypass Phase C
PE
Ground
N - Bypass
Bypass Neutral
For dual input configurations, a neutral conductor is required from the bypass source only.
The interconnection links BR1, BR2 and BR3 MUST BE REMOVED (see Fig. 3.8.4-2).
Output Load
L1
Load Phase A
L2
Load Phase B
L3
Load Phase C
N
Load Neutral
PE
Load Ground
NOTE !
This UPS is only designed to operate in a wye-configured electrical system with a
solidly grounded neutral.
If the UPS is equipped with an input transformer, the secondary of the transformer
must be wye-configured with neutral solidly grounded.
SGT5000_010-020_UPS connection separate_01US
L3
L1
L2
2- INPUT BYPASS
L1-2
L2-2
L3-2
X2
N
L1-1
1 - INPUTLOAD
PE
L3-1
L2-1
N - Bypass
L2
L1
L3
RECTIFIER
X1
PE
3.8.4Power connection dual input utility of SG Series 10 & 20
SG Series 10 & 20: Max. rating X1 and X2 terminals: 3 AWG (25mm2)
Cable terminations are to the Rectifier / Bypass Input Terminals and Load Output Terminals as shown
above.
Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: see Section 3.8.1.
Page 30
Critical Power
Modifications reserved
Page 30/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Notices for installation
Fig. 3.8.4-2 Interconnection links BR1, BR2 and BR3 of SG Series 10 & 20
For separate Bypass and Rectifier Input configuration, the interconnection links BR1, BR2 and BR3
MUST BE REMOVED.
SGT5000_010-020_UPS BR1-2-3_01
X2
X1
BR2BR1
BR3
Page 31
Critical Power
Modifications reserved
Page 31/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.8.5-1 Power connections Dual Input Utility of SG Series 30 & 40
Dual Input Configuration Rectifier / Bypass
L1-1
Rectifier Phase A
L1-2
Bypass Phase A
L2-1
Rectifier Phase B
L2-2
Bypass Phase B
L3-1
Rectifier Phase C
L3-2
Bypass Phase C
PE
Ground
N - Bypass
Bypass Neutral
For dual input configurations, a neutral conductor is required from the bypass source only.
The interconnection links BR1, BR2 and BR3 MUST BE REMOVED (see Fig. 3.8.5-2).
Output Load
L1
Load Phase A
L2
Load Phase B
L3
Load Phase C
N
Load Neutral
PE
Load Ground
NOTE !
This UPS is only designed to operate in a wye-configured electrical system with a
solidly grounded neutral.
If the UPS is equipped with an input transformer, the secondary of the transformer
must be wye-configured with neutral solidly grounded.
L1-1
X1
L1
PE
PE
SGT5000_030-040_UPS connection separate_01US
L2
L3
N
L2-1
L3-1
N - Bypass
OFF
ON
OFF
ON
2- INPUT BYPASS
L1-2
L2-2
L3-2
X2
L3
L2
L1
RECTIFIER
1 - INPUTLOAD
3.8.5Power connection dual input utility of SG Series 30 & 40
SG Series 30 & 40 Max. rating X1 and X2 terminals: 1 AWG (50mm2)
Cable terminations are to the Rectifier / Bypass Input Terminals and Load Output Terminals as shown
above.
Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: see Section 3.8.1.
Page 32
Critical Power
Modifications reserved
Page 32/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Notices for installation
Fig. 3.8.5-2 Interconnection links BR1, BR2 and BR3 of SG Series 30 & 40
For separate Bypass and Rectifier Input configuration, the interconnection links BR1, BR2 and BR3
MUST BE REMOVED.
X1
SGT5000_030-040_UPS BR1-2-3_01
OFF
ON
OFF
ON
X2
BR1BR2
BR3
Page 33
Critical Power
Modifications reserved
Page 33/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.8.6-1 Power connections of internal / external battery for SG Series 10 & 20
Battery
+
Positive pole of the Battery
–
Negative pole of the Battery
Do not insert the Battery Fuses before the commissioning.
NOTE !
To meet standards concerning electromagnetic compliance, the connection
between the UPS and external battery must be done by using a shielded cable or
suitable shielded (metal) conduit!
This UPS is only designed to operate in a wye-configured electrical system with a
solidly grounded neutral.
If the UPS is equipped with an input transformer for, the secondary of the
transformer must be wye-configured with neutral solidly grounded.
NOTE !
When an additional battery cabinet is connected, no batteries must be installed
inside the UPS cabinet.
SGT5000_010-020_UPS connection battery_01
_
+
BC
When the unit is equipped with internal battery, for safety reasons it is
The battery plug "BC" must be connected to the battery connector fitted on
External battery connection
Internal battery connection
delivered with the battery fuses already inserted, but with the
battery plug "BC" disconnected.
battery enclosure just before the commissioning.
3.8.6 Battery connection of SG Series 10 & 20
Max. rating Battery terminals: 3 AWG (25mm2)
Battery cable terminations are to the Positive and Negative Terminals as shown above.
Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: See section 3.8.1.
Page 34
Critical Power
Modifications reserved
Page 34/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.8.7-1 Power connections battery of SG Series 30 & 40
Battery
+
Positive pole of the Battery
–
Negative pole of the Battery
Do not insert the Battery Fuses before the commissioning.
NOTE !
To meet standards concerning electromagnetic compliance, the connection
between the UPS and external battery must be done by using a shielded cable or
suitable shielded (metal) conduit!
This UPS is only designed to operate in a wye-configured electrical system with a
solidly grounded neutral.
If the UPS is equipped with an input transformer for, the secondary of the
transformer must be wye-configured with neutral solidly grounded.
SGT5000_030-040_UPS connection battery_01US
BATTERY
X3
+
PE
_
3.8.7 Battery connection of SG Series 30 & 40
Max. rating Battery terminals: 1 AWG (50mm2)
Battery cable terminations are to the Positive and Negative Terminals as shown above.
Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: See section 3.8.1.
Page 35
Critical Power
Modifications reserved
Page 35/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
NOTE !
The set-up for SG Series 10-20-30-40 when functioning as frequency converter
requires a particular installation and adequate setting of some parameters,
(accessible only through password), and can therefore only be done by a QUALIFIED
SERVICE ENGINEER GE.
The handle of the switch Q2 - Manual Bypass
should be removed to avoid attempts to transfer
to Manual Bypass when the UPS is being used as
a frequency converter.
As an added measure of safety the
interconnection links BR1, BR2 and BR3 should
also be removed.
See Fig. 3.8.4-2 (SG Series 10 & 20) or
Fig. 3.8.5-2 (SG Series 30 & 40).
Fig. 3.8.8-1 Switch Q2 – Manual Bypass
NOTE !
The standard SG Series 10-20-30-40 UPS may be operated at 50Hz input with
60Hz output frequency conversion.
It is recommended that the static switch bypass be electronically blocked if the
UPS is to operated as a frequency converter in order to prevent damage to the
load.
Check with a Global Services Field Service Engineer to facilitate the parameter
change.
CAUTION !
The output transformer of the UPS is designed for 60Hz only.
Operation at 50Hz, 480V output may overheat the transformer.
The optional 5th harmonic filter is designed for 60Hz operation.
If the UPS is purchased with this internal filter it may not be operated at 50Hz
input or damage to the filter could result.
3.8.8 Set-up for SG Series 10-20-30-40 when functioning as frequency converter
When the SG Series 10-20-30-40 is utilized for different output frequency compared to the input
frequency, the Automatic Bypass and Manual Bypass functions are disabled, therefore the load cannot
be transferred to Utility in case of overload, short circuit, or inverter failure.
In situations where the UPS needs to be powered down for maintenance purposes, the critical load must
also be powered down during this time, the UPS cannot be transferred to Manual Bypass, serious
damage to the load could result.
Page 36
Critical Power
Modifications reserved
Page 36/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
WARNING !
This operation must be performed by QUALIFIED SERVICE PERSONNEL ONLY before
the initial start-up.
ENSURE THAT THE UPS INSTALLATION IS COMPLETELY POWERED DOWN.
NOTE !
It is strongly recommended that no transformers, automatic circuit breakers or fuses
should be inserted between the unit’s output and the Load common bus bars.
However, it is recommended that a disconnection or isolation switch is installed in
order to totally isolate a unit if needed.
Fig. 3.9.1-1 Power wiring of RPA Parallel System
1
=
Rectifier
2
=
Inverter
3
=
Automatic Bypass
4
=
Manual Bypass
5
=
Input Utility Distribution
6
=
Unit Output Load
7
=
External Battery fuse or
MCB
8
=
External Battery
9
=
Common bus-bar and
Output Load Distribution
=
UPS Number 1
=
UPS Number 2
=
UPS Number 3
=
UPS Number 4
=
UPS Number 5
=
UPS Number 6
=
UPS Number 7
=
UPS Number 8
3.9 RPA PARALLEL SYSTEM CONNECTION
3.9.1 Power wiring of parallel units
To guarantee good Load sharing between the units of a parallel system, we recommend that the cable
length from the input distribution board (5) to the output distribution board (10) is equal for each unit
(a+b = c+d = e+f = g+h = i+l = m+n = o+p = q+r).
Tolerance: +/-10%.
The AC input power of the Bypass must be the same for all units of the parallel system - no phase shift
allowed between units.
Page 37
Critical Power
Modifications reserved
Page 37/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
NOTE !
Under no circumstance should the control bus cable connecting JA(1/2/3/4/5/6/7)
and JB (1/2/3/4/5/6/7) be connected or disconnected after the system has been
powered On.
Fig. 3.9.2-1 RPA System - Control bus connection
SGT5000_100-150_RPA-IM0048_01
JP3
JP1
JP4
IM 0048
JP2
JP1JP2
JP4
JP3
JB1
JA1
JB1
JA1
JP2JP1
JP3
JP4
JP3
JP2
JP1
JP4
IM 0048
JB2
JA2
JP1JP2JB2
JA2
JA3
JB3
JP4
JP3
JP3
JP2
JP1
JP4
IM 0048
JA1 + JB1JA2 + JB2JA3 + JB3
UPS 1UPS 2UPS 3
Next parallel
unit 4,5,6,7,8
3.9.2 Parallel control bus connection
In cases of parallel operation, the communication between the units takes place through the control
bus cables.
Each parallel unit is equipped with an additional board “P13 – RPA Board“ where the connectors J52 (A)
and J62 (B) are located.
A short control cable provided with a ferrite ring core links the parallel board “P13 – RPA Board” with the
parallel bus socket on which must be connected the control bus cables JAand JB on PCB “P34 – Bus Interface”.
All the parallel units are connected to the same control bus.
This connection allows:
The microprocessors of each unit to communicate with each other.
The oscillators of each unit to be locked together.
The regulation loops to compare the output current of each unit in order to equally share the load
current.
For increased reliability, this connection is made with redundant cables.
In this way, communication is maintained between units in case one of the control cables should fail or
be accidentally damaged or disconnected.
The standard length of the control bus cable between two parallel unit is 40 ft / 12 m.
Maximal overall length of bus connection, between the first and the last unit, should not be longer than
276 ft / 84 m.
Verify that control wiring is run in individual separate steel conduit.
The shield of the control bus cable, connected on JA and JB must be connected to ground with the
appropriate cable clamps fitted on parallel bus socket.
It is important to place the units in sequence of their assigned number.
A unit number from 1 to 8, is defined by the setting of parameters and displayed on the panel.
This number is also marked inside and outside the packaging.
Page 38
Critical Power
Modifications reserved
Page 38/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.9.2-2 Bus connection on terminal units
Terminal units
On the parallel bus PCB “P34 – Bus Interface”, of the first and last units (terminal) of the parallel
system the Jumpers JP1, JP2, JP3 and JP4 MUST BE INSERTED.
Fig. 3.9.2-3 Bus connection on intermediate units
Intermediate units
On the parallel bus PCB “P34 – Bus Interface” of the intermediate units of the parallel system the
Jumpers JP1, JP2, JP3 and JP4 MUST BE REMOVED.
NOTE !
In a parallel system composed of 2 or more units, only the first and last units (having
1 input JA and JB free) have the Jumper JP1, JP2, JP3 and JP4 inserted on parallel
bus PCB “P34 – Bus Interface” (see Fig. 3.9.2-2).
SGT5000_100-150_RPA-IM0048_02
JP3
JP1
JP4
IM 0048
JP2
JP1JP2
JP4
JP3
JB1
JA1
JB
JA
JB1
JA1
JP2JP1
JP3
JP4
JP3
JP2
JP1
JP4
IM 0048
JB2
JA2
SGT5000_100-150_RPA-IM0048_03
JA
JB
Page 39
Critical Power
Modifications reserved
Page 39/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
WARNING !
This operation must be performed by QUALIFIED SERVICE PERSONNEL ONLY before
the initial start-up.
ENSURE THAT THE UPS INSTALLATION IS COMPLETELY POWERED DOWN.
Fig. 3.9.3-1 View electronic module on intermediate unit
Access to the control bus connection.
The control bus connection between
parallel units must be made on the front
of the electronic module fitted behind
the front doors.
Fig. 3.9.3-2 Front view electronic module on intermediate unit
Control bus cables connection.
Plug the cables JA (1/2/3/4/5/6/7) and
JB (1/2/3/4/5/6/7) onto the RJ
connectors JA and JB located on
parallel bus PCB “P34 – Bus Interface”
(going to “P13 – RPA Board” J52(A) and
J62(B).
Fix both cables JA (1/2/3/4/5/6/7) and
JB (1/2/3/4/5/6/7) to parallel bus
socket connecting the cable shield to
ground by means the cable clamps “A“.
SGT5000_030-040_RPA control bus cable_01
Q1
Q2
ON
OFF
OFF
ON
SGT5000_100-150_RPA control bus cable_02US
Next parallel unit
JB2
JB1
JA2
JA1
A
A
JA
JB
3.9.3 Control bus cable location
Page 40
Critical Power
Modifications reserved
Page 40/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 3.9.3-3 Control Bus cable routing and connection
Control bus cables routing
Place and fix the cables JA-1/2/3/4/5/6/7 and JB-1/2/3/4/5/6/7 with the appropriate clamps inside
the UPS cabinets in the position shown in the drawing Fig 3.9.3-1.
Pay attention to the fact, that routing of cables shall allow the removal of the protection covers “A”.
NOTE !
Pay attention when cabling and routing the bus cables JA and JB inside the UPS
cabinet.
In case one unit should be removed from the parallel system, the bus cables JA and
JB must be removed from the cabinet without disconnecting them from the metal
plate where the sockets JA and JB are located.
For reliability reasons the cables JA-1/2/3/4/5/6/7 and JB-1/2/3/4/5/6/7 connecting the units should
be run in separated protected conduits (as indicated in Fig. 3.9.3-3) separated from the power
cables.
It is important that the cable JA must be the same length as cable JB.
WARNING !
Connection and commissioning of an additional UPS to an existing parallel system,
must be performed by a GE SERVICE ENGINEER from of your Service Center.
SGT5000_030-040_RPA control bus cable_02US
Next parallel
unit 3, 4, 5, 6, 7, 8
JB2
JA2
UPS 1
JA1
JB1
JA1
JB1
JB
JA
JB1
JB2
JB
JA
JA2
JA1
JA2
UPS 2
Q2
Q1
OFF
ON
OFF
ON
JB2
A
A
ON
OFF
Q1
Q2
ON
OFF
Page 41
Critical Power
Modifications reserved
Page 41/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 4.1-1 Customer interface
Serial port J3 - RS 232 (sub D - female 9 pin) (see Section 4.1.1)
Suitable for JUMP protocol
Pin 2: TX (out)
Pin 3: RX (in)
Pin 5: GND
J2 (subD-female 25p) – Output signals on voltage free contacts(see Section 4.1.2)
J2/1, 2, 3
NO, C, NC
Utility Failure
(default Parameter RL=1)
J2/4, 5, 6
NO, C, NC
Load on Inverter
(default Parameter RL=3)
J2/7, 8, 9
NO, C, NC
Stop Operation
(default Parameter RL=5)
J2/14, 15, 16
NO, C, NC
Load on Utility
(default Parameter RL=2)
J2/17, 18, 19
NO, C, NC
General Alarm
(default Parameter RL=4)
J2/20, 21, 22
NO, C, NC
Acoustic Alarm
(default Parameter RL=6)
Signals on terminals X1 and on connector J2 are in parallel and
therefore not separated galvanically from each other.
The programmable signals on X1 and J2 will be disabled with Q1 open, with the
exception of the signals for “16 - Manual Bypass ON” and “26 - EPO”.
XB - Terminals for EPO connection(see Section 4.1.7)
XB/1, 4 or J2/12, 25
NC
EPO (Emergency Power Off)
Note: to enable this function, remove cable short-circuiting XB / 2 – 3 and the
Jumper JP3 on P4 – Customer Interface.
X1 – Output signals on voltage free contacts – terminals (see Section 4.1.2)
X1/1, 2, 3
NO, C, NC
Utility Failure
(default Parameter RL=1)
X1/4, 5, 6
NO, C, NC
Load on Inverter
(default Parameter RL=3)
X1/7, 8, 9
NO, C, NC
Stop Operation
(default Parameter RL=5)
X1/12, 13, 14
NO, C, NC
Load on Utility
(default Parameter RL=2)
X1/15, 16, 17
NO, C, NC
General Alarm
(default Parameter RL=4)
X1/18, 19, 20
NO, C, NC
Acoustic Alarm
(default Parameter RL=6)
Input contacts (see Section 4.1.3)
X1/10, 21 or J2/10, 23
Programmable (default = RL1)
X1/11, 22 or J2/11, 24
Programmable / Generator ON (NO) (def. = RL2)
NO = Normally Open
C = Common
NC = Normally Closed
The connectors J4 and J5 can be used for additional 3-ph SNMP/WEB plug-in adapter or an additional Customer
Interface (installation only when the UPS is switched Off).
XA: terminals for 24Vdc Auxiliary Power Supply connection.XB: terminals for EPO connection.
Programmable user relays
Programmable functions on contacts (X1 - J2)
On terminals X1 or J2 connector, six of the following 26
signals can be selected from the display, entering with
the appropriate password.
Some UPS functions can be activated with
parameters when an external Normally Open
contact is closed on:
X1-10, 21 / J2-10, 23 or X1-11, 22 / J2- 11, 24
Selectable functions by changing parameters
(password required) are:
0 - No function 1 - Inverter ON
2 - Inverter OFF 3 - Print All
4 - Status Relay 5 - Generator ON
6 - External Bypass ON
7 - External Battery Fuses, or External K3
See Alarm 4104 - “Battery Fuses”
Voltage free contacts: Max. DC / AC: 24V / 1.25A
IEC 60950 (SELV circuit)
Min. Signal Level: 5Vdc/5mA
0- No Information
1- Buzzer
2- General Alarm
3- Load on Utility
4- Stop Operation
5- Load on Inverter
6- Utility Failure
7- DC Over Voltage
8- Low Battery
9- Overload
10- Over Temperature
11- Inverter-Utility not syncr.
12- Bypass Locked
13- Bypass Utility Failure
14- Rectifier Utility Failure
15- Battery Discharge
16- Manual Bypass ON
17- Rectifier ON
18- Inverter ON
19- Boost Charge
20- Battery Earth Fault
21- Battery Fault
22- Relay Input 1
23- Relay Input 2
24- Relay Output ON
25- Relay Output OFF
26- EPO(Emergency Power Off)
1
12 13
2
14
3
15
4
16
5
17
6
18
7
19
8
20
9
21
10
22
11
1
14
9
1
X1
J2
J3
SGSU_100-150_Customer interface_01
J5
J4
XA
21
XB
1
2
3
4
1
2
3
4
JP3
4 CUSTOMER INTERFACE
4.1 CUSTOMER INTERFACE
Page 42
Critical Power
Modifications reserved
Page 42/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Fig. 4.1.1-1 Serial port J3
Serial port J3 - RS-232 (sub D, female 9 pin) that allows:
Total remote management of the system using software GE Power
Diagnostics, GE Data Protection or GE Service Software for system protection
and management of the UPS systems.
Fig. 4.1.1-2 Serial port J3 connection to PC with RS232 1:1 cable DB9m – DB9f
The serial port J3 - RS232 is enabled
on all the units of the parallel system.
X1 / 1, 2, 3
or
J2 / 1, 2, 3
(NO, C, NC)
Utility Failure
X1 / 4, 5, 6
or
J2 / 4, 5, 6
(NO, C, NC)
Load on Inverter
X1 / 7, 8, 9
or
J2 / 7, 8, 9
(NO, C, NC)
Stop Operations
X1 / 12, 13, 14
or
J2 / 14, 15, 16
(NO, C, NC)
Load on Utility
X1 / 15, 16, 17
or
J2 / 17, 18, 19
(NO, C, NC)
General Alarm
X1 / 18, 19, 20
or
J2 / 20, 21, 22
(NO, C, NC)
Acoustic Alarm
NOTE !
The programmable signals on X1 and J2 will be disabled with Q1 open, with the
exception of the signals for “16 - Manual Bypass ON” and “26 - EPO”.
4
4
1
3
2
3
2
1
SGT5000_100-150_Customer interface J3_01
J3
4.1.1 Serial Port J3
4.1.2 Output free potential contacts
The interface board provides 6 voltage free relay contacts giving some UPS critical alarms and
operation mode.
These signals are available either on connector J2- (sub D, female 25 pin) or terminal blocks X1.
The meaning of the alarms on the free contacts in standard configuration (default) is the following:
In case different alarms or operating status are required, they can be configured on the same terminals
via software from the control panel.
The configuration can be changed in Parameters Mode by a trained operator using the appropriate
password.
Page 43
Critical Power
Modifications reserved
Page 43/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
X1 / 10, 21 orJ2 / 10, 23 User Input 1 (default = Not used)
X1 / 11, 22 orJ2 / 11, 24 User Input 2 (default = Emergency GEN ON)
In a parallel system a separate NO (Normally Open) contact must be connected to
each individual unit.
In a parallel system, the input on the customer interface of each unit must be
connected to a separate AUX contact of the External Maintenance Bypass Switch.
Fig. 4.1.6-1 Terminals for connection 24Vdc
XA - 1 24Vdc
XA - 2 GND
XA - 3 24Vdc
XA - 4 GND
4
1
3
2
3
2
1
SGT5000_100-150_Customer interface 24VDC_01
4
XA
4.1.3 Programmable input free contacts
Some programmable UPS functions (indicated in Section 4.1), can be activated by closing an external
contact, if connected, on:
4.1.4 Gen Set Signaling (GEN ON)
If an emergency generator set supplies the UPS in case of Mains Failure and the generator is
considerably unstable in frequency, it should be suitable to install the signal “Generator ON” on X1 / 11,
22 or J2 / 11, 24). See Fig. 4.1-1 / X1 and J2.
Since the Parameter for of the reading of the Generator function is password protected, call the nearest
Service Center for it's activation.
When this contact closes, it changes certain (programmable) functions such as:
Enabling or disabling of synchronization and consequently the Load transfer to generator.
Reduction or elimination or delay of Battery recharging during the generator operation.
4.1.5 AUX external Maintenance Bypass
If the UPS system is equipped with an external Maintenance Bypass Switch, it is possible to connect a NO
(Normally Open) voltage-free aux. contact from the External Bypass Switch to the programmable input
X1 / 10, 21 or J2 / 10, 23, making the UPS operate as if the internal switch Q2 has closed.
This function can be activated by changing a dedicated parameter (password required).
When this NO (Normally Open) contact closes, the output Inverter ContactorK7 it is automatically
opened and the Load transfer back to Inverter will be inhibited.
4.1.6 Auxiliary Power Supply (APS) 24 Vdc
Page 44
Critical Power
Modifications reserved
Page 44/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Be aware:
The reliability of the system depends on this contact NC (Normally Closed)!
Fig. 4.1.7-1 Terminals for connection EPO
An external Emergency switch (Normally Closed voltage-free
contact) can be connected on terminals XB / 1 - 4 or connector
J2 / 12 - 25of the “P4 - Customer Interface”.
NOTE !
To enable this function, remove cable shortcircuiting XB / 2 - 3 on the Terminal XB and the Jumper JP3 on “P4 - Customer Interface”, when
the cables have been already connected on XB or J2.
When opened, this contact causes the immediate opening of the
Contactors K3, K4, K6, K7 and K8, as well as the shut-down of
Rectifier, Inverter and Static-Switch.
NOTE !
This procedure could imply a load shut-down.
NOTE !
In case of parallel Customer Interface the EPO contact must be connected to one “P4
- Customer Interface” only, but the bridge on X2 and jumper JP3 on the “P4 Customer Interface” must be removed on all other boards.
In a Parallel System a separate NC (Normally Closed) contact must be connected
individually to each unit.
Fig. 4.1.7-2 XB “EPO - Emergency Power Off” – RPA Parallel System connection schematics
4.1.7 “EPO - Emergency Power Off” command connection
Page 45
Critical Power
Modifications reserved
Page 45/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
When the “EPO - Emergency Power Off” has been activated, the system must be restored as
follows:
Realize the push-button “EPO - Emergency Power Off” (contact on XB / 1, 4 is closed again).
Press the key “O”(Inverter OFF - Shut-down) on the Control Panel.
(see User Manual to Section 5.2).
In case of a Parallel System press the key “O” (Inverter OFF) on the Control Panel
of each unit connected on the Parallel Bus and having its output switch Q1
closed.
Page 46
Critical Power
Modifications reserved
Page 46/46
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Installation Guide SG Series 10-20-30-40 UL S
Date
Description
Done by
5 NOTES
5.1 NOTES FORM
It is recommended to note in this section Notes, with date and short description all the operations
performed on the UPS, as: maintenance, components replacement, abnormal situations, etc.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.