GE 400, 500, SG 400, SG 500 User Manual

GE Digital Energy
Power Quality
S
G
S
_
4
0
0
5
0
0
_
S
2
_
U
P
S
_
G
E
_
0
1
User Manual
Uninterruptible Power supply
SG Series 400 & 500
400 & 500 kVA / 480Vac UL / S2
GE Consumer & Industrial SA
General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 52 52
www.gepowerquality.com
imagination at work
Model:
SG Series 400 & 500 UL S2
Issued by Product Document Department – Riazzino - CH
Date of issue: 06/15/2010
File name: OPM_SGT_USG_M40_M50_2US_V010
Revision: 1.0
Identification No.:
Up-dating
Revision Concerns Date
COPYRIGHT © 2010 by GE Consumer & Industrial SA
All rights reserved.
The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
Modifications reserved Page 3/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Dear Customer,
We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE.
We trust that the use of the SG Series 400 & 500 Uninterruptible Power Supply system, developed and produced to the highest standards of quality, will give you complete satisfaction.
Please read carefully the User Manual, which contains all the necessary information
and describes all you need
to know about the use of the UPS. Thank you for choosing GE !
START UP AND COMMISSIONING
A GE Global Services Field Engineer must perform start-up and commissioning of the UPS. Please Contact GE. Global Services at least two weeks prior to schedule start-up and commissioning at 1-800-637-1738, or by E-mail at pqservice@ge.com .
Distributed in the USA by:
Your service contact:
g
GE Consumer & Industrial SA
General Electric Company
CH – 6595 Riazzino (Locarno)
Switzerland
www.gepowerquality.com
g
GE Digital Energy
Power Quality
2501 Pecan Street
Bonham, TX 75418 T: +1 800-637-1738 F: +1 903-640-0533
E: GEPQSales@ge.com
http://www.gedigitalenergy.com/ups
Modifications reserved Page 4/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Preface
Congratulations on your choice of a SG Series Uninterruptible Power Supply (UPS). It will help eliminate Load disturbances due to unexpected power problems.
This Manual describes the function of the UPS module, the purpose and location of the switches, the meaning of the system events related to the front panel indication, and provides procedures for starting and stopping the equipment.
Please refer to the accompanying Installations Guide, which describes how to prepare the installation site, and it provides weight, dimensions and procedures for moving, installing and connecting the UPS.
While every care has been taken to ensure the completeness and accuracy of this manual, GE assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this document.
WARNING!
SG Series 400 & 500 is a product that needs to be installed by a licensed and knowledgeable contractor.
We recommend that this manual be kept next to the UPS for future references. If any problems are encountered with the procedures contained in this manual, please contact your Service Center before you proceed.
This document shall not be copied or reproduced without the permission of GE.
Some of the information contained in this manual may be changed without notice to reflect technical improvements.
Safety instructions
Read the safety instructions contained on the following pages carefully before the installation of the UPS, options and battery system.
Pay attention to the rectangular boxes included in the text: They contain important information and warning concerning electrical connections and personnel safety.
Parallel version secured with RPA
When included in the text, this symbol refers to operation needed only for parallel system.
Modifications reserved Page 5/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Table of contents Page
1
IMPORTANT SAFETY INSTRUCTIONS ........................................................................................................... 7
2 LAYOUT .......................................................................................................................................................... 10
2.1 LAYOUT SG Series 400 & 500 ........................................................................................................................................................... 10
3 INTRODUCTION ............................................................................................................................................ 11
4 DESCRIPTION ................................................................................................................................................ 12
4.1 BLOCK DIAGRAM AND MAIN ELEMENTS ..................................................................................................................................... 12
4.2 OPERATION MODES.............................................................................................................................................................................. 13
4.2.1 Normal operation mode........................................................................................................................................................................... 13
4.2.2 eBoost™ operation mode (option) ....................................................................................................................................................... 13
4.2.3 Utility failure operation ............................................................................................................................................................................. 14
4.2.4 Utility recovery operation........................................................................................................................................................................ 14
4.2.5 Automatic Bypass ....................................................................................................................................................................................... 15
4.2.6 Manual Bypass (option)............................................................................................................................................................................. 15
4.3 PARALLEL SYSTEM OPERATION....................................................................................................................................................... 16
4.3.1 Introduction to the parallel system..................................................................................................................................................... 16
4.3.2 Features of RPA parallel system........................................................................................................................................................... 17
4.3.3 System control.............................................................................................................................................................................................. 17
4.3.4 Synchronization ........................................................................................................................................................................................... 17
4.3.5 Load sharing.................................................................................................................................................................................................. 17
4.4 RECTIFIERS PARALLELED ON THE SAME BATTERY.................................................................................................................. 18
4.5 RECYCLING AT THE END OF SERVICE LIFE.................................................................................................................................. 19
5 CONTROL PANEL .......................................................................................................................................... 20
5.1 CONTROL PANEL.................................................................................................................................................................................... 20
5.2 TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL..................................................................................... 21
6 LCD SCREEN .................................................................................................................................................. 23
6.1 HOME SCREEN ........................................................................................................................................................................................23
6.2 METERING .................................................................................................................................................................................................25
6.3 ALARMS...................................................................................................................................................................................................... 28
6.3.1 Events (alarms and messages).............................................................................................................................................................. 29
6.3.2 Alarms list........................................................................................................................................................................................................ 29
6.3.3 Messages list.................................................................................................................................................................................................. 33
6.3.4 Event report SG Series 400 & 500......................................................................................................................................................... 36
6.4 SETUP 37
6.5 COMMANDS .............................................................................................................................................................................................43
7 OPERATION.................................................................................................................................................... 44
7.1 PROCEDURES FOR SINGLE SG Series 400 & 500 ..................................................................................................................... 45
7.1.1 Start-up of the SG Series 400 & 500 .................................................................................................................................................... 45
7.1.2 UPS shutdown with Load transfer on Manual Bypass Q2 (option)........................................................................................ 49
7.1.3 From Manual Bypass Q2 (option) to normal function VFI.......................................................................................................... 51
7.1.4 Complete UPS shutdown.......................................................................................................................................................................... 53
7.1.5 Restore to normal operation after “Load Off”................................................................................................................................. 54
7.1.6 Restore to normal operation after EPO (Emergency Power Off) ............................................................................................ 55
Modifications reserved Page 6/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.2 PROCEDURES FOR SG Series 400 & 500 PARALLEL SYSTEM AND PARALLEL SYSTEM WITH COMMON
BATTERY..................................................................................................................................................................................................... 56
7.2.1 SG Series 400 & 500 Parallel System start-up................................................................................................................................ 56
7.2.2 Parallel System shutdown with Load transfer on Manual Bypass Q2 (option)................................................................ 61
7.2.3 From Manual Bypass Q2 (option) to normal function VFI.......................................................................................................... 63
7.2.4 Separate a UPS Unit from the Parallel System (System Redundancy)................................................................................ 65
7.2.5 Reconnect a UPS unit to a Parallel System...................................................................................................................................... 67
7.2.6 Complete Parallel System shutdown.................................................................................................................................................. 69
7.2.7 Restore to normal operation after “Load Off”................................................................................................................................. 71
7.2.8 Restore to normal operation after EPO (Emergency Power Off) ............................................................................................ 73
8 OPTIONS......................................................................................................................................................... 75
8.1 COMMUNICATION OPTIONS ............................................................................................................................................................. 75
8.2 OPTIONS IN UPS CABINET.................................................................................................................................................................. 75
8.3 CONNECTION FOR OPTIONS............................................................................................................................................................. 76
8.3.1 Remote Signaling Box (RSB) .................................................................................................................................................................... 76
9 MAINTENANCE.............................................................................................................................................. 77
9.1 MAINTENANCE........................................................................................................................................................................................ 77
9.1.1 Service check................................................................................................................................................................................................. 77
9.1.2 Fans and ventilation................................................................................................................................................................................... 77
9.1.3 Other components with limited lifetime............................................................................................................................................ 77
9.1.4 Battery.............................................................................................................................................................................................................. 78
9.1.5 Long shut-down periods of the UPS-system .................................................................................................................................. 78
9.1.6 UPS room conditions and temperature............................................................................................................................................. 78
9.1.7 Long shut-down periods of the UPS-system .................................................................................................................................. 78
10 NOTES............................................................................................................................................................. 79
10.1 NOTES FORM............................................................................................................................................................................................ 79
Modifications reserved Page 7/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models SG Series 400 & 500 that should be followed during installation and maintenance of the UPS and battery.
GENERAL
- Move the UPS in an upright position in its original package to the final destination room. To lift the cabinets, use a forklift or lifting belts with spreader bars.
- Check for sufficient floor and elevator loading capacity.
- Check the integrity of the UPS equipment carefully. If you notice visible damage, do not install or start the UPS. Contact the nearest Service Center immediately.
- WARNING! RISK OF ELECTRICAL SHOCK: Do not remove covers, there are no user serviceable parts inside.
- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage remains at the terminals of the electrolytic capacitors.
- All maintenance and service work should be performed by qualified service personnel. The UPS contains its own energy source (battery).
- The field-wiring outlets may be electrically live, even when the UPS is disconnected from the utility.
- Dangerous voltages may be present during battery operation.
- The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
INSTALLATION
- This UPS must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the UPS, for the following: Damaged components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are correctly reattached.
- This UPS is intended for use in a controlled indoor environment free of conductive contaminants and protected against animals intrusion.
- WARNING! HIGH EARTH LEAKAGE CURRENT: Earth connection is essential before connecting to AC input!
- Switching OFF the unit does not isolate the UPS from the utility.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104°F (40°C).
- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25°C).
- It is important that air can move freely around and through the unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
STORAGE
- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55°C).
- The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range -
4°F (-20°C) to 104°F (40°C).
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time depending on storage temperature).
BATTERY
- The battery-voltage is dangerous for person’s safety.
- When replacing the battery, use the same cells number, voltage (V), capacity (Ah). All the battery used, shall be of the same manufacturer and date of production.
- Proper disposal or recycling of the battery is required. Refer to your local codes for disposal requirements.
- Never dispose of battery in a fire: they may explode.
- Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic. If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
- Never short-circuit the batteries. When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.
- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.
Modifications reserved Page 8/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Safety instructions when working with battery
EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY QUALIFIED SERVICE PERSONNEL ONLY. INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION BEFORE HANDLING THE UPS AND BATTERY.
DANGER!
Full voltage and current are always present at the battery terminals. The battery used in this system can provide dangerous voltages, extremely high currents and a risk of electric shock. If the terminals are shorted together or to ground they may cause severe injury. You must be extremely careful to avoid electric shock and burns caused by contacting battery terminals or shorting terminals during battery installation. Do not touch uninsulated battery terminals.
A qualified service person, who is familiar with battery systems and required precautions, must install and service the battery. The installation must conform to national and local codes. Keep unauthorized personnel away from the battery.
The qualified service person must take these precautions:
1 Wear protective clothing, such as rubber gloves and boots and protective eye wear
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated. Remove rings and metal wristwatches or other metal objects and jewelry. Do not carry metal objects in your pockets where the objects can fall into the battery cabinet.
2 Tools must have insulated handles and must be insulated so that they will not short battery
terminals. Do not allow a tool to short between individual or separate battery terminals or to the cabinet or rack. Do not lay tools or metal parts on top of the battery, and do not lay them where they could fall onto the battery or into the cabinet.
3 Install the battery as shown on the drawing provided with the battery.
When connecting cables, never allow a cable to short across a battery’s terminals, the string of battery, or to the cabinet or rack.
4 Align the cables on the battery terminals so that the cable lug will not contact any part of
the cabinet or rack, even if the battery is moved.
Keep the cable away from any sharp metal edges. 5 Install the battery cables in such a way that the UPS or battery cabinet doors cannot pinch them. 6 Do not connect the battery terminal to Ground.
If any battery terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock. 7 To reduce the risk of fire or electric shock, install the battery in a temperature and humidity
controlled indoor area, free of contaminants. 8 Battery system chassis ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduits, this ground conductor must be routed in the same conduit as the
battery conductors. 9 Where conductors may be exposed to physical damage, protect the conductors in
accordance with all applicable codes. 10 If you are replacing the battery or repairing battery connections, shut OFF the UPS and
remove the battery fuses.
Modifications reserved Page 9/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Safety symbols and warnings
Safety warnings The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to
the UPS system and the supplied critical loads.
The non-observance of the warnings reminding hazardous situations could result in human injury and equipment damages.
Please pay attention to the meaning of the following warnings and symbols.
Throughout this manual the following symbols are defined:
WARNING, if instruction is not followed injury or serious equipment damage may occur!
CAUTION, internal parts have dangerous voltage present. Risk of electric shock!
PE (Earth) – GND (Ground) PROTECTIVE GROUNDING TERMINAL: A terminal which must be connected to earth ground prior to making any other connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or voltage may be applied or supplied.
A terminal to which or from which a direct current or voltage may be applied or supplied.
This symbol indicated the word “phase”.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.
Modifications reserved Page 10/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
2 LAYOUT
2.1 LAYOUT SG Series 400 & 500
S
G
S
_
4
0
0
-
5
0
0
_
S
2
_
U
P
S
_
G
E
_
0
2
Fig. 2.1-1 SG Series 400 & 500 general view
Q1
0
O
F
F
I ON
Q2
0
O
F
F
I ON
S
G
S
U
_
4
0
0
-
5
0
0
_
S
2
_
U
P
S
_
0
3
11 22
10 21
2
1
18
12 13
16
1415
17
7
1 2
34
6
5
1920
8 9
4
3
2
1
15
14
131298
20
19
56
7
171618
21
10
22
11
Fig. 2.1-2 SG Series 400 & 500 general view with open doors
SGS_400-500_S2_Switches Q1-Q2_01
Q1
0
O
F
F
I ON
Q2
0
O
F
F
I ON
Fig. 2.1-3 Manual operated switches
Fig. 2.1-4 Control panel
P4
Customer Interface Board
Q1
UPS output switch
Q2
Manual Bypass switch (option)
SNMP
3-ph SNMP/WEB plug-in adapter (option)
XA
Terminals for 24Vdc Auxiliary Power Supply connection
S
G
S
_
4
0
0
-
5
0
0
_
C
u
s
t
o
m
e
r
in
t
e
r
f
a
c
e
_
0
3
P4
SNMP
Fig. 2.1-5 Connectivity Rack
XB
Terminals for EPO (Emergency Power Off) connection
Modifications reserved Page 11/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
3 INTRODUCTION
An Uninterruptible Power Supply (UPS) provides the power for critical loads that need a reliable, continuous, disturbance free supply.
In case the power provided by the Utility fails, or exceeds the permitted tolerances, the power to supply the Load is provided by the Battery for the specified time at the rated Load (or longer at a reduced Load) or until the Utility power returns.
SG Series 400 & 500 is a true double conversion VFI (Voltage Frequency Independent) UPS system where the Load is continuously supplied by the Inverter through the Rectifier.
In case of trouble on the Inverter Output Voltage, or when overload or short-circuit on the output occur, the Load is instantly transferred to the Utility via the Automatic Bypass.
The UPS automatically returns to normal mode when the failure condition is restored.
Key features:
More Critical equipment supported Rated at 0.9 Power Factor, SG Series 400 & 500 delivers more real power than other UPS in the
market. With today’s trend toward power factor corrected loads, SG Series 400 & 500 can support more total Load than any other UPS available, allowing you to support a greater number of today’s enterprise computing Power Factor Corrected (PFC) equipment.
No single point of failure Redundant Parallel Architecture (RPA) is an exclusive GE technology.
With RPA, SG Series 400 & 500 UPS are controlled in a true peer-to-peer configuration where all critical elements and functions (including Bypass) are redundant. SG Series 400 & 500 is designed to be the most reliable power protection system available on the market today.
High Efficiency Using IGBT technology and Space Vector Modulation (SVM) strategy, SG Series 400 & 500 offers low
output voltage distortion and provides efficiencies up to 93%.
Fully digital Digital Signal Processor (DSP), Flash memory and SVM strategy, are the technology corner stones of new age of power quality and power reliability.
Extremely flexible Tailor made power protection to meet your individual installation requirements; SG Series 400 & 500 offers various options like input harmonic filters and our comprehensive GE Power Diagnostic software suite for mission control and data protection to cover all your application needs.
Modifications reserved Page 12/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
4 DESCRIPTION
4.1 BLOCK DIAGRAM AND MAIN ELEMENTS
Fig. 4.1-1 Block diagram
The SG Series 400 & 500 system can be divided into the following main elements:
Control System
SG Series 400 & 500 is designed with microprocessor-controlled signal processing circuits. The interface between the operator and the unit is provided by the monitoring system on the front panel. This monitoring system consists of an active mimic diagram, a keyboard and a backlit display.
Rectifier
The standard Rectifier consists of a 6-pulse SCR-bridge, which converts the 3-phase Utility Voltage into a controlled and regulated DC-voltage. This regulated DC-voltage is used to supply power to the Inverter, and to provide charging power to the Battery.
Inverter
The Inverter converts the DC voltage into a three-phase AC-voltage with constant amplitude and frequency, which is completely independent and isolated from the AC-input voltage.
Automatic Bypass
The Automatic Bypass consists of a static semiconductor-switch (SSM: Static Switch Module), used to provide an uninterrupted transfer of the Load from Inverter to Utility.
Back-feed Protection All SG Series UPS's are equipped with an automatic system for the protection against voltage back feeding towards Utility, through the Bypass (Applied Standard IEC 62040-1). This protection works automatically by opening contactor K6 and eventually K7, and acts in case of internal defects of the system, or due to wrong manipulations on the Manual Bypass Q2 (option).
Manual Bypass (option)
The Manual Bypass consists of a pair of manual switches (Q1 and Q2), which removes the UPS from the Load for maintenance, while still supplying the Load with power directly from the Utility.
Battery
The Battery supplies the DC power to the Inverter when the Utility is out of accepted tolerances.
Modifications reserved Page 13/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
4.2 OPERATION MODES
4.2.1 Normal operation mode
During normal operation, the Rectifier converts input AC power to DC. The DC power provides input power for the Inverter and charging power for the Battery. The Inverter converts the DC power to continuous and regulated AC power, which supplies the critical load. The control panel reports the Battery charge status and the expected backup time with the actual load.
Fig. 4.2.1-1 Block diagram normal operation mode
4.2.2 eBoost™ operation mode (option)
eBoost
e high efficiency (up to 99%) Boost fast power transfer (< 4ms)
When the eBoost™ Operation Mode is selected, and the Utility Power is available, the Load is normally powered through the Automatic Bypass.
When the Utility Voltage is detected out of the prescribed tolerances, the Load is automatically transferred to the Inverter.
Fig. 4.2.2-1 Energy flow in eBoost™ Operation Mode
When the Utility recovers, the Load returns to the Automatic Bypass after a variable time defined by the control unit.
The eBoost™ Operation Mode can be configured directly by the user for scheduled activation, considering the Utility reliability and criticality of the Load.
The selection between the two operation modes “VFI Mode and eBoost™ Operation Mode”, or switching between operation modes at required time, can be done through the UPS control panel (see Section 7.4
/
eBoost).
NOTE !
The eBoost™ Operation Mode is available only if enabled at the factory or by a GE GLOBAL SERVICES FIELD ENGINEER.
Modifications reserved Page 14/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
4.2.3 Utility failure operation
When the Utility is no longer within acceptable tolerances, the Battery will provide the DC power to the Inverter. The Inverter will maintain continuous AC power to the Load until the Battery Voltage reaches the lower limit of the Inverter operation capability. During the discharge, the LCD screen displays the estimated time the Battery can support the critical Load. Prior to the Battery completely discharging, the "stop operation" alarm (shutdown imminent) warns the operator that the Battery is almost discharged and the UPS is about to shut down.
Fig. 4.2.3-1 Block diagram Utility Failure operation
In case of parallel operation
With a parallel system for power capacity (see Section 4.3)
With the Bypass Utility power available, a low Battery warning on any unit will cause the Load to
be transferred to Utility (after a selectable time delay).
With Bypass Utility power not available, a low Battery warning on any unit will start the “stop operation” timer (adjustable). The Load will shut down at the end of the “stop operation” time period.
With a parallel system for redundancy (see Section 4.3)
When a Battery low warning occurs on a unit not necessary to support the present load, this unit will shut down after a timeout period (selectable). The Load is shared between the other units. As the warning occurs on one unit necessary to support the present load, the system starts the "stop operation" timeout (selectable). The Load will shut down at the end of the “stop operation” time period.
4.2.4 Utility recovery operation
As soon as the AC input power recovers, the Rectifier will start automatically, supplying DC power to the Inverter and recharging the Battery. If the Inverter was previously shut down due to low Battery, the Load will be initially powered by Utility through the Automatic Bypass. When the Battery is recharged enough to ensure a minimum time of operation with the present load, the Inverter will start automatically and the Load will be transferred back to the Inverter.
Fig. 4.2.4-1 Block diagram Utility recovery operation
In case of parallel operation
When the AC input power recovers, the Rectifiers will start up sequentially, according to their number in the parallel system. This minimizes the initial inrush current. The Inverters will start up automatically, but only when the Battery has recharged enough for a
minimum runtime with the present load. When enough Inverters to supply the Load have been restarted, the Load will be transferred from the Automatic Bypass back to the Inverter output.
Modifications reserved Page 15/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
4.2.5 Automatic Bypass
In normal operation, the Load is supplied by the Inverter.
When the control system detects a fault in the Inverter, an overload condition or a short-circuit condition, the Automatic Bypass will transfer the critical Load to the Utility without interruption.
When the Inverter recovers, or the overload or short-circuit condition is corrected, the Load will be automatically transferred back to the Inverter.
If the UPS is unable to return to normal mode following an automatic transfer to Bypass mode, an alarm condition will be initiated.
A Manual Bypass (operator initiated) will not be considered as an alarm condition.
Fig. 4.2.5-1 Block diagram Automatic Bypass
In case of parallel operation
Each unit has its own internal Bypass. These units are continuously exchanging information, enabling all of the internal Bypass circuits in a
parallel system to operate simultaneously. If the Inverter of a unit fails, its Bypass circuit remains available to the Parallel System. It is excluded only if the unit is separated from the common bus by opening its output switch Q1.
4.2.6 Manual Bypass (option)
The Manual Bypass circuit consists of Q1 and Q2 manual switches, which permits transfer of the Load directly to the unconditioned AC power without interruption, leaving the UPS available for maintenance.
Fig. 4.2.6-1 Block diagram Manual Bypass
Modifications reserved Page 16/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
4.3 PARALLEL SYSTEM OPERATION
4.3.1 Introduction to the parallel system
Two or more equal power units can be paralleled to increase the output power (paralleling for capacity) or to improve the overall reliability of an UPS system (paralleling for redundancy). The outputs of parallel units are connected to a common power bus, and in normal operation the units connected on the parallel bus share the Load equally. The modular concept of SG Series 400 & 500 allows parallel operation of up to 6 units, without using paralleling switchgear, external bypass circuits or common control circuitry (see Fig. 4.3.1-1).
Parallel units for power capacity
Several units can be paralleled in order to achieve output power greater than the maximum power of a single unit. The maximum total power shared between the paralleled units is equal to the total installed nominal power. In the event of a failure of one unit, the power supplied by the UPS system becomes insufficient and the Load will be transferred to the Utility Bypass source.
Parallel units for redundancy The nominal power rating of the n+1
out of n redundant paralleled modules must be equal to or greater
than the required Load power. The Load will be equally shared by the n
units connected on the output bus.
Should one of the n
paralleled units trip Off-line, the remaining (n+1) modules will supply the load, maintaining conditioned power to the critical load. From this results higher reliability and security for the Load plus a higher MTBF (Mean Time Between
Failures).
Fig. 4.3.1-1 Block diagram parallel system operation
Modifications reserved Page 17/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
4.3.2 Features of RPA parallel system
The SG Series 400 & 500 Parallel System is designed to provide a complete Redundant Parallel Architecture, and is free from common equipment.
Not only the Inverters are redundant, but also the Bypass functions are designed with redundant modular concept.
When one UPS needs maintenance or service, the Load is powered by the other units supplying the Load bus.
The redundant communication bus to which all units are connected keeps each unit informed about the status of all the other units.
The control panel located on each unit allows controlling and monitoring the status of this unit.
4.3.3 System control
A high-speed redundant, serial communication bus guarantees the exchange of data and thus the communication between the CPU's of each unit.
Each module controls it's own function and operational status and communicates with all other modules, in order to act or react if necessary, adapting it to the new conditions.
4.3.4 Synchronization
All units are identical, but one unit is arbitrarily selected as the reference and all the other units synchronize to this unit, which in turn, synchronizes to the Utility Bypass voltage, as long as the later is within tolerances.
In case of reference failure, another unit in the parallel system is automatically chosen to take over the reference role.
The Bypass Input for all the units of the parallel system must be supplied from the same AC source (no phase shift allowed between them).
4.3.5 Load sharing
On each unit of the parallel system, Inverter Output Voltage and Current are measured and applied to a Load sharing bus.
An eventual difference between the units is therefore automatically equalized.
NOTE !
It is strongly recommended that no transformers, automatic circuit breakers or fuses should be inserted between the unit’s output and the Load common bus bars.
However, it is recommended that a disconnect or isolation switch be inserted.
Modifications reserved Page 18/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
4.4 RECTIFIERS PARALLELED ON THE SAME BATTERY
NOTE !
A parallel system with a Common Battery for two or more Rectifiers, requires a particular installation and adequate setting of some parameters, (accessible only through password), and can therefore only be done by a qualified engineer from GE.
Usually each Rectifier-Inverter Unit runs with its own Battery. In case of parallel units are running with a Common Battery (max. 4 UPS - see Fig 4.4-1), the sharing circuit between individual Rectifier is integrated in the communication bus of the system in order to assure an equal sharing of the Rectifiers output currents.
Fig. 4.4-1 Diagram RPA system with Rectifiers on Common Battery
1 –
2 –
3 –
4 –
5 –
6 –
7 –
8 –
Rectifier
Inverter
Automatic Bypass
Manual Bypass
Utility Power
Load Bus Bar
External Battery Fuse
Battery
Pay attention to the following recommendations:
The units delivered for this functioning mode needs a special parameters setting, so they must be
prepared in advance before the installation.
The installation must be performed only with the UPS system must be completely shut down.
The AC Rectifiers input power (5) must be the same, with clockwise phase rotation for each unit.
Each Rectifier must be set for the same floating DC voltage and the same Battery current limitation.
It is mandatory to install the fuses / MCCB (7) on each line connecting the Rectifiers to the common
Battery for maintenance / safety reasons.
In case one must be powered down for maintenance, switch-OFF the concerned unit before open
the DC fuses / MCCB on the Battery line (7).
It is mandatory to connect an external NO free contact “Battery Fuses” to the UPS and to enable the
function by setting the parameter (see Section 4.1 of the “Installation Guide”).
If an emergency generator set supply the UPS, and the free contact “Generator ON” is connected to
the Customer interface, connect a separate NO free contact on each parallel unit.
The parameters enabling the Battery test, both manual and automatic, must be set in the same
mode on all the units having the Rectifiers on Common Battery.
Do not connect the temperature sensor for automatic battery floating voltage compensation.
Do not enable the function Boost charge (parameter 87).
Modifications reserved Page 19/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
4.5 RECYCLING AT THE END OF SERVICE LIFE
NOTE !
This product has been designed to respect the environment, using materials and components respecting eco-design rules.
It does not contain CFCs (chlorofluorocarbons) or HCFCs (hydrochlorofluorocarbons).
RECYCLING AT THE END OF SERVICE LIFE !
GE, in compliance with environment protection recommends to the User that the UPS equipment, at the end of its service life, must be recovered conforming to the local applicable regulations.
WARNING !
Leads contained in the batteries is a dangerous substance for the environment, therefore it must be correctly recycled by specialized companies!
Modifications reserved Page 20/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
5 CONTROL PANEL
5.1 CONTROL PANEL
Fig. 5.1-1 Control panel
The control panel, positioned on the UPS front door, acts as the UPS user interface and comprises of the following elements:
Back lit Graphic Display (LCD) with the following characteristics:
Multilanguage communication interface:
English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch;
Synoptic Diagram indicating UPS status.
Command pushbuttons and parameters setting.
UPS status control LED.
Modifications reserved Page 21/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
5.2 TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL
Key to switch the Inverter ON ( I )
NOTE !
When eBoost™ Operation Mode is enabled, control of Inverter status and selection of the feed path is done autonomously by the UPS control logic.
Therefore, Inverter ON / Inverter OFF commands are disabled when eBoost™ Operation Mode is enabled.
Key for Inverter shutdown ( O )
Press the key to transfers the Load to Utility. Keep pressed for 5 seconds to shutdown the Inverter. This key is also used as the EPO (Emergency Power Off) reset.
NOTE !
Inverter OFF command is disabled when eBoost™ Operation Mode is enabled.
Key “Load Off”
The key “Load Off” is protected by a transparent cover. By pressing it, you immediately separate the UPS from the Load.
It is possible to activate the command “Load Off” using the following links: COMMANDS / TOTAL OFF REQUEST. See Section 6.5.
`Home\Commands
COMMANDS
RESET TOTAL OFF
REQUEST TOTAL OFF
To reset “Load Off”
Restore the command “Load Off” by entering the screen:
COMMANDS / RESET TOTAL OFF
V
For Parallel System:
If “Load Off” is pressed on one unit connected to the parallel bus (switch Q1 closed), all the units are separated from the load. The “Load Off” reset must be done only on one unit connected to the parallel bus (switch Q1 closed).
NOTE !
Special care must be taken in using this command, in order to avoid accidental load disconnection.
Modifications reserved Page 22/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
LED Stop Operation (red color)
It warns about the imminent inverter stop (default parameter = 3 min.) and the consequent load shutdown as result of:
The battery is fully discharged and the load cannot be transferred on utility.
Overtemperature or overload condition (>125%) and the load cannot be
transferred on utility.
LED Alarm (yellow color)
It blinks when one or more alarm is activated. The internal buzzer is ON. The LED remains lighted (with the alarm condition still present) and the buzzer
stops when the key “MUTE” is pressed. The LED is also lit when the load is not protected by UPS or in case Q1 is open.
LED Operation (green color)
When lit, indicates that the UPS is functioning correctly and the load is system protected (Load supplied from inverter).
When blinking, indicates that a regular maintenance service is needed (SERVICE REQUIRED). May be reset by a service technician only. See Section 9 – Maintenance – Service check.
The LED is OFF when the output switch Q1 is open, indicating that the Inverter is in service mode, not supplying the load.
User LCD Interface
The user interface consists of a Back lit Graphi
c
Display (LCD) having:
Synoptic Diagram indicating UPS status.
UPS operating, AC and DC metering
information.
History of events (alarms and messages).
Functionality can be programmed to meet
customer needs by changing parameters.
Operation commands of the UPS.
Modifications reserved Page 23/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
6 LCD SCREEN
6.1 HOME SCREEN
Fig. 6.1-1 LCD display
The buttons perform the following functions:
METER
METERING View electric parameters values and statistics of use.
See Section 6.2.
ALARM
ALARMS Shows in chronological order, all the events occurred (alarms,
messages, commands, handling, etc.). See Section 6.3.
MUTE Key to reset general alarm and buzzer.
SETUP
SETUP Allows the user to customize some UPS functions to specific
requirements and to view UPS identification data. See Section 6.4.
CMDS
COMMANDS Allows the user to execute UPS operation commands.
See Section 6.5.
The LCD screen, after 5 minutes of inactivity, shuts down the backlight. To reactivate it, it is sufficient to press any pushbuttons.
If the keypad remains inactive for 5 minutes or longer, during the viewing of a screen such as MEASURES, ALARMS, SETUP or COMMANDS, the LCD screen returns automatically to the main screen.
It is possible to view any pushbutton functional description by pushing the button for more than 3 seconds.
Pushing the pushbuttons “METER” (1st button) and “ALARM” (2nd button) together automatically sets the LCD communication for “ENGLISH”.
Modifications reserved Page 24/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
SG Series S2 500
UPS Model UPS series number UPS nominal rating (kVA)
Battery level LED
All lightning lit LED open indicate a battery autonomy of 100%.
LED A Fixed: indicates a battery autonomy between 6% and 25%.
Blinking: indicates a battery autonomy 5%.
LED A, B Indicate a battery autonomy between 26% and 50%. LED A, B, C Indicate a battery autonomy between 51% and 99%. Min: Battery autonomy time in minutes estimates with actual load.
Load level LED
All LED Off indicate a load status at 25%. LED A Indicates a load level between 26% and 50%. LED A, B Indicate a load level between 51% and 75%. LED A, B, C Indicate a load level between 76% and 100%. LED A, B, C, D Indicate a load level between 101% and 124%. LED D blinking Indicates a load level ≥125%.
Fig. 6.1-2 LEDs on Synoptic Diagram
LEDs on Synoptic Diagram
LED 1 Utility Rectifier OK LED 2 Utility Bypass OK LED 3 Rectifier ON LED 4a Discharging Battery LED 4b Charging Battery LED 5 Inverter available LED 6 Inverter ON LED 7 Q1 closed (load on UPS) LED 8 Automatic Bypass ON LED 9 Manual Bypass Q2 ON LED 10 Load on UPS
Examples of typical scenarios in the Synoptic Diagram:
Load supplied by Inverter Load supplied by Automatic Bypass
Load supplied by Battery Load supplied by eBoost™ Operation Mode (option)
When the Load is supplied by eBoost™ Operation Mode the “eBoost” text is displayed.
Modifications reserved Page 25/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
6.2 METERING
The METERING mode is entered any time the “METER” button is pressed. The LCD screen will indicate a series of screenshots showing the measures of all electric parameters like AC, DC and various statistics.
In this mode the buttons perform the following functions:
Return to HOME screen.
Scrolls backward to the previous screen.
Scrolls forward to the next screen.
It is possible to view any pushbutton functional description by pushing the button for more than 3 seconds.
`Home\Meter
BATTERY
V 545 V I 100.0 A T +25° C Charge level 80 % Autonomy 12 Min
Battery data screen
V The battery voltage.
I The battery current (negative values correspond to
the discharge of the battery).
T The temperature of the battery (“SENSOR DISABLE”
indicates sensor disabled).
Charge level The battery charge level.
Autonomy The estimated backup time with the
present load.
`Home\Meter
RECTIFIER
f : 60.0 Hz L12 : 480 V Vdc : 540 V L23 : 480 V Idc1 : 250.0 A L31 : 480 V Idc2 : 250.0 A
Rectifier utility data screen
f The input frequency of the rectifier.
L12 L23 The voltage levels between the three phases (line­L31 to-line).
Vdc Rectifier voltage output.
Idc1 Output current 1st Rectifier bridge. Idc2 Output current 2
nd
Rectifier bridge.
`Home\Meter
UTILITY
f 60 Hz L1 275 V L2 279 V L3 276 V
BYPASS FREE
Bypass utility data screen
f The frequency of the utility.
L1 L2 3-phase utility voltage PHASE /NEUTRAL. L3
Bypass Bypass status: FREE / LOCKED.
Modifications reserved Page 26/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
`Home\Meter
INVERTER
f 60 Hz L1 277 V L2 277 V L3 277 V T +25° C
SYNCHRONIZED
Inverter data screen
f The output frequency of the Inverter. L1
L2 3-phase output voltage PHASE/NEUTRAL. L3
T The temperature of the inverter bridge.
The synchronization status of the inverter with respect to utility (SYNCHRONIZED / NOT SYNCHRONIZED).
`Home\Meter
SYSTEM LOAD
L1 : 277 V 301.0 A 50 % L2 : 277 V 241.0 A 40 % L3 : 277 V 181.0 A 30 %
LOAD ON INVERTER
Load on phases screen 1
… V Output voltage PHASE/NEUTRAL for each phase.
… A The output current as RMS values (for RPA: total
value of Parallel System).
… % The output load as percentage (for RPA: with
respect to the rated power of Parallel System).
The source of the power supplied to the load:
- DETOUR ON (Q2 close) - LOAD ON INVERTER
- Q1 OPEN
- LOAD ON BYPASS
- LOAD OFF
- LOAD ON BYPASS (eBoost)
- ON BATTERY
`Home\Meter
SYSTEM LOAD
L1 : 75.0 kW 83.3 kVA PF +/-0.90 L2 : 60.1 kW 66.7 kVA PF +/-0.90 L3 : 45.0 kW 50.0 kVA PF +/-0.90
LOAD ON INVERTER
Load on phases screen 2
… kW The load active power (kW) (for RPA: total value of
Parallel System).
… kVA The load apparent power (kVA) (for RPA: total
value of Parallel System).
… PF The load power factor:
+ for inductive loads (lagging power factor).
- for capacitive loads (leading power factor).
The source of the power supplied to the load:
- DETOUR ON (Q2 close) - LOAD ON INVERTER
- Q1 OPEN
- LOAD ON BYPASS
- LOAD OFF
- LOAD ON BYPASS (eBoost)
- ON BATTERY
`Home\Meter
MODULE LOAD
Total kVA 200 kVA Percentage 40%
LOAD ON INVERTER
Module load screen
Total kVA
The load level in kVA (for RPA: only this unit).
Percentage
The load level as a percentage of the nominal rated load (for RPA: only this unit).
The source of the power supplied to the load:
- DETOUR ON (Q2 close)
- LOAD ON INVERTER
- Q1 OPEN - LOAD ON BYPASS
- LOAD OFF
- LOAD ON BYPASS (eBoost)
- ON BATTERY
Modifications reserved Page 27/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
`Home\Meter
COUNTERS
Bypass utility failure : 25 Rectifier utility failure : 14 Overloads : 15 InvOperTime [h] : 2135 UPSOperTime [h] : 3125 eBoost OperTime [h] : 1379
Statistics screen
The total number of bypass utility faults (bypass utility out of tolerance).
The total number of rectifier utility faults (rectifier utility out of tolerance).
The total number of detected output overloads.
The total operating time for the Inverter (in hours).
The total operating time for the UPS (in hours).
The total operating time for the UPS in eBoost™ Operation Mode (in hours). This counter is displayed only when eBoost™ Operation Mode is available (option).
`Home\Meter
BATTERY DISCHARGE COUNTERS
Residual Charge Level
100-81% 81-51% 50-21% 20-0%
15 7 3 1
On Battery Time [h]: 15
Statistics battery discharge screen
Residual Charge Level
The number of discharges combined with the percentage of the available residual battery capacity at the time utility power is restored.
On Battery Time [h]
The total operating time of the UPS on battery (in hours).
`Home\Meter
UTILITY
NUMBER OF FAST TRANSIENTS <2ms >2ms >5ms >10ms 25 20 7 5
eBoost rate = 70 %
eBoost™ Operation Mode statistic screen
This screen is displayed only when eBoost™ Operation Mode is available.
The number of fast transients occurred on the bypass utility on the last seven days.
The statistic evaluation in % (100= good; 0= bad) of the utility, for the eBoost™ Operation Mode.
Modifications reserved Page 28/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
6.3 ALARMS
The ALARMS mode is entered any time the “ALARM” button is pressed.
The LCD will display a series of screens corresponding to the last 255 events, two events per screen (LEVEL 1 USER).
In this mode the buttons perform the following functions:
Return to HOME screen.
Scrolls backward to the previous screen.
Scrolls forward to the next screen.
U
Move forward to the following event.
V
Move back to the following previous event.
Confirm the selection made.
It is possible to view any pushbutton functional description by pushing the button for more than 3 seconds.
The events displayed are the standard GE events as described in the Section 6.3.1 - EVENTS (Alarms and Messages).
`Home\ Alarm
ALARM
LEVEL 1 : USER
LEVEL 2 : SERVICE
V
Alarms screen
LEVEL 1 USER
Chronologically view 2 events per screenshot.
LEVEL 2 SERVICE
Chronologically view 5 events per screenshot with service related info.
`Home\Alarm\User
NR = 255 05.18.2010 15.37.25 C = 4404 K6 CLOSING FAILURE S = 00008180 NR = 254 05.15.2010 12.45.57 C = 4583 COMMAND TO SYNCHRONIZE S = 00008180
U
V
Screen of user alarms
NR Number chronologically assigned to an event (Nr.
255 is the more recent, Nr. 1 is the first). Date and exact hour of the moment when the event occurred.
C Number of standard GE code of the event and an
explicit text describing the event in the selected languages.
S Status code of the UPS.
Modifications reserved Page 29/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
6.3.1 Events (alarms and messages)
Each of the following listed events, alarm or message, can be displayed on the LCD screen, on a PC with the software “GE Data Protection” installed or with the monitoring system “GE Power Diagnostic”.
Alarms and Messages are differently specified because the alarms are indicating an abnormal functioning of the UPS (which are additionally signaled with the LED Alarm and acoustically with the buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list, but not activating the LED alarm and the acoustical alarm).
6.3.2 Alarms list
Code Alarms Meaning
4000
SETUP VALUES LOST
Parameters are lost and have been replaced with default values. Call nearest Service Center for intervention.
4001
REGULATION BOARD FAILURE
A blocked DSP on the Control board causes this alarm, and consequently the shutdown of Rectifier and Inverter and the opening of K3.
4004
UPS FAILURE ON PARALLEL
SYSTEM
The master unit detected the slave unit missing on the communication bus even though switch Q1 is still closed.
4006
BUS JA CRC FAILURE
The parallel communication bus system is subject to high errors rate on channel JA.
4007
BUS JB CRC FAILURE
The parallel communication bus system is subject to high errors rate on channel JB.
4008
BUS JA FAILURE
There is an interruption in the channel JA of the parallel communication bus system.
4009
BUS JB FAILURE
There is an interruption in the channel JB of the parallel communication bus system.
4010
CONNECTIVITY BUS FAILURE
The connectivity communication bus is faulty or interrupted.
4100
RECTIFIER FUSES FAILURE
The u-switch mounted on the Rectifier Input Fuses indicates a blown fuse, and consequently shut down. Clearance of this condition allows you to restart the Rectifier.
4102
K4 CLOSING FAILURE
K4 not closed despite a closing command being issued. Signaled by auxiliary contact. Rectifier cannot start.
4103
K4 OPENING FAILURE
K4 not open despite an opening command being issued. Signaled by auxiliary contact. Utility remains connected to Rectifier Bridge.
4104
BATTERY FUSES FAILURE
This function, when enabled on input programmable relays (password required), warns the user about the external Battery Fuses failure or MCCB opening, signaled by NO free contact.
4105
RECTIFIER OVERTEMPERATURE
Temperature sensor indicates an over temperature on the Rectifier Bridge. Only alarm is given. The Rectifier, when in Off state, cannot start as long as this condition persists.
Modifications reserved Page 30/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Code Alarms Meaning
4106
RECTIFIER TRANSFORMER
OVERTEMPERATURE
The temperature sensor inside the input transformer winding indicates over temperature. Only the alarm is given. The Rectifier, when in Off state, cannot start as long as this condition persists.
4110
RECTIFIER UTILITY OUT
OF TOLERANCE
Rectifier Input Utility is out of tolerance (voltage, frequency or phase).
4115
LOW BATTERY VOLTAGE
The Battery has been discharged and reached “stop operation” time-out (default 3 minutes), and the Inverter will be shut down. It will restart automatically only when the Battery has recharged enough for a minimum runtime.
4116
HIGH BATTERY VOLTAGE
Dangerous high DC Voltage caused Inverter shutdown. Inverter restarts automatically after Battery returns to floating voltage.
4117
BATTERY EARTH FAULT
A leakage current to earth has been detected on the DC circuit.
4118
BATTERY FAULT
During battery test the voltage falls under the critical level (depending setting parameters). Battery test is stopped.
4121
HIGH DC RIPPLE
There is a high voltage ripple on the DC Bus. Rectifier might be working in current limiting mode. Decrease the load to stabilize DC Bus.
4130
TURN ON RECT.
OR SHUTDOWN UPS
Rectifier and Inverter are OFF. The DC Power Supply is discharging the Battery. Rectifier must be restarted or Battery must be disconnected in order to avoid damage.
4140
RECTIFIER CONTROL FAILURE
Rectifier Voltage hasn’t reached the set value (probably fault on regulation loop). LED Rectifier on control panel is blinking.
4165
INPUT FILTER FAILURE
An unbalancing on the three-phase current absorbed by the input harmonic filters 5th or 11th is detected causing the opening of the contactors C50 or C110. The reset alarm can be done only from Service Center.
4301
INVERTER FUSES FAILURE
Inverter Output Fuses blown (F5, F6 and F7). Inverter can be started manually after replacement of the
fuses.
4304
K7 CLOSING FAILURE
K7 not closed despite a closing command being issued. Signaled by auxiliary contact. Load will be supplied by Utility.
4305
K7 OPENING FAILURE
K7 not open despite an opening command being issued. Signaled by auxiliary contact. Load will be supplied by Utility.
4307
INVERTER TRANSFORMER
OVERTEMPERATURE
The temperature sensor of the Inverter Transformer indicates over temperature. Elapsed “stop operation” time, Inverter shutdown. With Utility OK, Load is transferred on Utility.
4308
DC FUSES FAILURE
Blown input DC fuse(s) F1 of the Inverter. Inverter cannot be started as long as present.
Modifications reserved Page 31/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Code Alarms Meaning
4309
DRIVER FAILURE
An abnormal condition has been detected on one or more power modules of the Inverter (temperature or over current). Inverter shutdown and cannot be started as long as the alarm is present.
4312
INV. VOLTAGE OUT OF
TOLERANCE
Inverter Output Voltage is out of the tolerances (± 10%). Inverter is switched OFF.
4320
ISMAX DETECTION
Detection of Inverter Bridge (Is) current limit causing the Inverter OFF and possible automatic restart. After 3 times the Inverter switches-Off, and it can be restarted manually.
4321
HIGH CURRENT SHARING
A high exchange current value is detected between the UPS of the parallel system.
4340
INVERTER CONTROL FAILURE
The “Slave” oscillator is not in synchronized with the Master; thus causing the shutdown of it’s Inverter. If after a restart the condition remains, the LED inside the Inverter symbol on the panel will not light up, indicating that this Inverter cannot supply the Load anymore.
4400
BYPASS FUSE FAILURE Either one or all the fuses in bypass line have blown.
4404
K6 CLOSING FAILURE
K6 open despite a closing command being issued. Signaled by auxiliary contact. The Load cannot be supplied by Automatic Bypass.
4405
K6 OPENING FAILURE
K6 closed despite an opening command being issued. Signaled by auxiliary contact.
4406
SSM FAILURE
A faulty current has been detected in the static-switch causing the opening of the contactor K6 for 10 seconds. After 3 times K6 remains definitively open. The alarm reset can be done only from Service Center.
4407
SSM OVERTEMPERATURE
Temperature sensor indicates an over temperature on the Static-Switch.
4410
BYPASS UTILITY OUT
OF TOLERANCE
The Utility Bypass Voltage is out of the tolerances (± 10%). K6 opens, synchronization with Utility is inhibited and transfer to Utility is blocked.
4520
NO INVERTER POWER
The Load supplied by Utility exceeds the Inverter power. The Load remains supplied by Utility until the alarm stays ON.
4522
FAN FAILURE
A malfunction on the UPS ventilation system was detected. No change for UPS operation. Call immediately Service Center for intervention.
4530
LOAD LOCKED ON UTILITY
Load is locked on Utility because 3 transfers on Utility have been detected in a short time (default 30 seconds). The transfer will be free after a time defined in parameter (default 30 seconds).
4531
LOAD ON UTILITY BY ERROR
DETECTOR
Load is transferred to Utility because the error detector detected a disturbance on the output voltage.
4563
EMERGENCY OFF ACTIVATED
Alarm after detection of an EPO from an external safety device connected on Customer Interface Board. Consequently K4, K6, K7 open, Rectifier, Inverter and SSM are switched Off.
Modifications reserved Page 32/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Code Alarms Meaning
4570
OVERLOAD
The UPS-System is in an overload condition >125% on Inverter, or >150% on Utility. With Utility unavailable, a sequence of “stop operation” starts. Time out depends on Load quantity.
4571
OVERLOAD: LOAD ON UTILITY
With Utility Bypass supply available and load >115%, the
Load is transferred on Utility. Load will be transferred again automatically on Inverter when Load <100%.
4581
INVERTER AND UTILITY NOT
SYNCHRONIZED
The voltages of Utility and Inverter are not synchronized, which causes the opening of K6.
4608
ECO CONFIG FAILURE
The propagation of the eBoost / IEMi configuration to other units in a Parallel System failed.
4697
BATTERY OVERTEMPERATURE
Detection of Battery over temperature condition. Can be deactivated by Service Center.
4698
BATTERY POWER INSUFFICIENT
In case of Utility Failure, with the actual Load, the run time would be below stop operation time (default 3 minutes).
4700
DC LOW
Battery voltage is at the lowest limit. Will stay Off Inverter until the battery voltage reaches the value in parameter.
4701
POWER SUPPLY BOARD
FAILURE
Failure detection on the +24V derived from the DC-link voltage.
4900
LOAD LOCKED ON INVERTER
The Load is locked on Inverter after 3 Load transfers within 30 seconds. After time out (default 30 seconds) Bypass will be free.
4955
OVERTEMPERATURE
An over-temperature condition has been detected on Inverter. Elapsed “stop operation” time, Inverter shutdown. With Utility OK, Load is transferred on Utility.
4998
LOAD OFF DUE TO EXTENTED
OVERLOAD
Load Off after time-out of “stop operation” for overload on Inverter or Bypass (time depending on the % of overload).
4999
LOAD OFF DUE
TO LOW BATT. OR TEMP.
Load Off after time-out of “stop operation” with missing Utility due to Battery low voltage or over-temperature
condition.
Modifications reserved Page 33/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
6.3.3 Messages list
Code Message Meaning
4002
WATCHDOG RESET
The microprocessor has detected an incorrect operation: Transfers the Load on Utility and performs a program reset. The Inverter will restart automatically and will supply the Load.
4108
Q4 OPEN
The auxiliary contact indicates that the input rectifier switch Q4 has been opened.
4108
Q4 CLOSED
The auxiliary contact indicates that the input rectifier switch Q4 has been closed.
4111
RECTIFIER UTILITY OK
Rectifier Input Utility is again within the admitted tolerance (voltage, frequency and phase).
4119
BATTERY TEST STARTED Start of Manual or Automatic Battery Test.
4120
BATTERY TEST STOPPED End of Manual or Automatic Battery Test.
4122
MANUAL BOOST CHARGE ON
Start of Manual Boost charge (only for lead open wet batteries).
4123
AUTOMATIC BOOST CHARGE
ON
Start of Automatic Boost charge (only for lead open wet batteries).
4124
BOOST CHARGE OFF
End of Manual or Automatic Boost charge (only for lead open wet batteries).
4161
RECTIFIER ON Rectifier started.
4162
RECTIFIER OFF Rectifier shutdown.
4163
GENERATOR ON
Customer Interface Board (X1 - 11, 22) received a Gen-set ON signal.
Operating mode depend on setting of Parameters.
4164
GENERATOR OFF
Customer Interface Board (X1 - 11, 22) received a Gen-set OFF signal. Function Bypass enabled depends on setting of parameter.
4302
INVERTER CANNOT BE TURNED
ON
Inverter cannot be switched on because one of the following conditions is still present:
- Over Temperature - K7 opening Failure
- Low Battery Voltage - High Battery Voltage
- Inverter Fuses - DC Low
- Overload - EPO
4303
INVERTER CANNOT BE TURNED
OFF
Inverter cannot be switched OFF, because the Load cannot be switched to Utility (voltage out of tolerance, not synchrony, BP blocked).
4361
INVERTER ON
The command to start the Inverter has been activated on the control panel.
4362
INVERTER OFF
The command to switch OFF the Inverter has been activated by the control panel or automatically for alarm presence.
4411
BYPASS UTILITY OK
Bypass Input Utility is again within tolerance (voltage, frequency and phase).
4500
COMMAND LOAD OFF
Disconnection of the Load by opening K6 and K7 for: EPO / Load Off / Overload / Stop Operation.
4521
NO BYPASS POWER
With the Load supplied by Automatic Bypass, a Utility Failure or K6 opening occurred.
Modifications reserved Page 34/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Code Message Meaning
4534
MULTIPLE LOAD TRANSFER
2 transfers Inverter- Utility have been detected in a short time, (default 30 seconds).
4535
BYPASS LOCKED
Bypass is not available. Contactor K6 is open, SSM deactivated.
4536
BYPASS FREE
Bypass is enabled. Contactor K6 is closed.
4561
LOAD OFF
The “Load Off” key on the UPS Control Panel has been pressed, with the output circuit switch Q1 closed.
4562
DETOUR ON
The auxiliary contact indicates that External Maintenance Bypass has been closed.
4564
DETOUR OFF
The auxiliary contact indicates that External Maintenance Bypass was opened.
4567
COMMAND LOAD ON UTILITY
The control unit received a command to transfer the Load on Utility.
4568
COMMAND LOAD ON INVERTER
The control unit received a command to transfer the Load on Inverter.
4572
NO MORE OVERLOAD End of the overload condition detected with alarm 4570.
4580
INVERTER AND UTILITY
SYNCHRONIZED
The voltages of Inverter and Utility Bypass are synchronized.
4582
COMMAND NOT TO
SYNCHRONIZE
Command not to synchronize with Utility.
4583
COMMAND TO SYNCHRONIZE Command to synchronize with Utility.
4600
COMMAND UPS ON
The eBoost™ Operation Mode has been disabled or the programmed time is expired. The UPS returns to VFI Operation Mode supplying the Load normally by Inverter.
4601
COMMAND UPS STANDBY
The eBoost™ Operation Mode is enabled, and according to the time program the UPS will run in eBoost™ Operation Mode, supplying the Load normally by Utility.
4602
Q1 OPEN
The auxiliary contact indicates that the output switch Q1 has been opened.
4603
Q1 CLOSED
The auxiliary contact indicates that the output switch Q1 has been closed.
4604
COMMAND IEMi ON
The IEMi Operation Mode function is enabled, and according to the time program the UPS system will run in IEMi mode. The UPS returns to VFI Operation Mode supplying the Load normally by Inverter.
4605
COMMAND IEMi OFF
The IEMi Operation Mode has been disabled or the programmed time is expired.
4606
eBoost ACTIVATION ALLOWED
eBoost/IEMi control signal has been cleared on the Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation of the functions.
4607
eBoost ACTIVATION INHIBITED
Customer Interface Board (X1 - 11, 22) received an eBoost/IEMi control signal. eBoost™ Operation Mode and IEMi Operation Mode will be
temporarily inhibited.
Modifications reserved Page 35/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Code Message Meaning
4699
BATTERY TEST IMPOSSIBLE
Automatic Battery Test is not possible due to:
No Utility Rectifier or Bypass.
Battery not fully charged.
Load is below 10% or above 80%.
Test is postponed for 1 week.
4763
REMOTE CONTROL ON
Inverter can be started or shutdown by remote control. Commands source can be chosen depending on the value of parameter (Service only):
0 = Only Local Panel. 1 = Only Remote Control. 2 = Both.
4764
REMOTE CONTROL OFF
Inverter cannot be started or shutdown by remote control. Commands source can be chosen depending on the value of parameter (Service only):
0 = Only Local Panel. 1 = Only Remote Control. 2 = Both.
Modifications reserved Page 36/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
6.3.4 Event report SG Series 400 & 500
In case of failure or malfunctioning, before calling the nearest Service Center, please note the most important data of your UPS and the most recent events.
In order to make the diagnosis easier from our Diagnostic Center we suggest you make a copy of this page, fill it out with the requested data and send it by fax.
Unit No.: __ __ __ __ __ - __ __ __ __ - __ __ __ __ Series No.: ……..….. UPS rating: ……….….. kVA
Customer: ...................................…………….....……. Place: ......................…......................…………………………...…........
Date: ...……..... / ..…......... / ....……….……..... Sent by: ..…...........……..............…………………………............….......…
1. Record the exact UPS status on the panel
when the failure appeared.
2. On the LCD panel, enter the alarms mode and
record the alarms/messages in the list below indicating at least 5 events before the failure time.
Remark: exact data and time are very important.
Event
No.
Event
Code
UPS
Status
Date
Time
h. m. s
255 254
LED 1
ON OFF
253
LED 2
ON OFF
252
LED 3
ON OFF
251
LED 4a
ON OFF
250
LED 4b
ON OFF
249
LED 5
ON OFF
248
LED 6
ON OFF
247
LED 7
ON OFF
246
LED 8
ON OFF
245
LED 9
ON OFF
244
LED 10
ON OFF
243
LOAD
. . . . . . . . . . . . . . . . . . . . .
%
242
BATTERY
. . . . . . . . . . . . . . . . . . . . .
minutes
241 240
Description of repair actions taken:
239 238 237 236
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
235
Actual situation:
234 233 232 231
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
230
Remarks:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modifications reserved Page 37/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
6.4 SETUP
The SETUP mode is entered any time the “SETUP” button is pressed.
This screen allows the user to modify some parameters permitting to adapt some functions of the UPS to his/her needs, described as follows.
The LCD will display a series of screens containing the user parameters, accessible without password protection.
In this mode the buttons perform the following functions:
Return to HOME screen.
Scrolls backward to the previous screen.
Scrolls forward to the next screen.
Confirm selected choice of USER / SERVICE level.
Description of the pushbutton to set or modify the parameters:
ESC
Allows to exit a selected screen without making any modification.
U
Scrolls backward to the previous line.
V
Scrolls forward to the next line.
Allows to access a value to be set or modified.
Select, on the same line, the following value or letter to set or modify.
Set or modify the selected value.
Save the set or modified value and return to the selected screen.
It is possible to view any pushbutton functional description by pushing the button for more than 3 seconds.
`Home\Setup
UPS IDENTIFICATION
ID : UPS 0 Model : SG Series S2 500 S/N : P2500-2010-0001 UPS SW Version : xxx Display SW Version : xxx
UPS identification screen
ID Number of UPS in the RPA Parallel System (0
for single unit).
Model UPS model, series number and power range
S/N The UPS serial number.
UPS SW The UPS software version.
Display SW The LCD display software version.
Modifications reserved Page 38/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
`Home\Setup
SETUP
LEVEL 1 : USER
LEVEL 2 : SERVICE
V
Setup screen
LEVEL 1 USER
Displays a sequence of screens with parameters which can be user defined.
LEVEL 2 SERVICE
Only service is allowed. At this level the parameters access is protected by a code.
`Home\Setup\User
DATE AND TIME
D M Y Date : 15.05.2010 H M S Time 15:37:25
V
Date and time screen
Date You can adjust the date of the real time clock
existing in the UPS by the means of this parameter. The value you enter is thoroughly checked to be a correct date in the format “DD.MM.YY”.
Hour You can adjust the time of the real time clock
existing in the UPS by means of this parameter. The value you enter is thoroughly checked to be a correct time in the format “HH.MM.SS”. The time is specified in 24-hour format.
`Home\Setup\User
MODEM
Enabled : N Init : BEQV1X3&D0S0=2 Alarm call : N Delay : 30 sec Tel 1 : 1 Tel 1 enabled : N
V
Modem screen 1
Enabled
You can enable/disable with Y/N the remote control through modem calls by using this parameter. For modem connection, the default setting is for serial port J3 on Customer Interface.
Init
This parameter presents the modem initialization string. It can be 40 characters long.
When editing this parameter the UPS considers that a blank character terminates the string. If no blank character is found then all 40 characters are used.
Alarm call This Y/N parameter controls the automatic events signaling through modem. If this parameter is set to Y (Yes) the UPS itself will call the remote location when a new event occurs
Delay This parameter controls the delay between the occurrence of a new event and the modem dialing. It is useful because since the events typically do not occur isolated but in certain sequences, you can eliminate the need for multiple dial-outs for such a sequence of events.
Tel 1 This parameter specifies a first telephone number to be used for modem dial-out. The telephone number has a maximum 40 characters and cannot contain blanks. If the desired number is shorter than 40 characters, the string will finish with blanks.
Tel 1 enabled This parameter Y/N specifies if the first telephone number (Tel 1) will be used for dial-out.
Modifications reserved Page 39/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
`Home\Setup\User
MODEM
Tel 2 : 2 Tel 2 enabled : N Tel 3 : 3 Tel 3 enabled : N Tel 4 : 4 Tel 4 enabled : N
V
Modem screen 2
Tel 2
It records the second dial-out number.
Tel 2 enabled This parameter Y/N specifies if the second telephone number will be used for dial-out.
Tel 3 It records the third dial-out number.
Tel 3 enabled This parameter Y/N specifies if the third telephone number will be used for dial-out.
Tel 4 It records the fourth dial-out number.
Tel 4 enabled This parameter Y/N specifies if the fourth telephone number will be used for dial-out.
`Home\Setup\User
PRINTER
Baud Rate : 2400 Parity : 0 Bits : 8 Handshake : XON
V
Printer setup screen
The UPS is capable of communicating to a serial printer, to printout disparate information. Please be sure to have a serial printer with a serial RS232 interface. This is the only printer-interface supported by the UPS.
Baud Rate
This parameter controls the baud rate used for data transmission.
Parity This parameter controls the parity used for data transmission.
Odd (O) even (E) and “No Parity” (NO) can be selected. In case “No Parity” (NO) has been set, automatically the parameter “8 bits“ is used, independently of the value of “Bits“ set.
Bits This parameter controls the length of the data word on the serial line during data transmission.
Handshake This parameter is used to determine the communication protocol used when printing.
Valid values are “XON” standing for the XON/XOFF protocol or “NO” standing for any protocol.
NOTE !
Please configure your printer with the following parameters: 2400/8/N (2400 bauds/sec, 8 bits, no parity).
`Home\Setup\User
PRINTER COMMANDS
Print Measures : N Print Alarms : N Print Parameters : N Print All : N
V
Printer command screen
Print Measures This Y/N parameter is used to print only
the measurement data.
Print Alarms This Y/N parameter is used to print only
the sequence of all Alarms/Events.
Print Parameters This Y/N parameter is used to print only
the list of User and Service Parameters.
Print All This parameter Y/N is used to print all the available information in the sequence metering,
alarms, user and service parameters.
Modifications reserved Page 40/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
`Home\Setup\User
DISPLAY
UPS name : SG Series
Language : ENGLISH
Contrast
V
LCD Display screen
UPS Name The user can choose the name of the UPS
model shown on the main page (max. 9 characters).
Language This parameter allows the choice of
language used to display the information. Valid choices are: English, German, Italian,
Spanish, French, Finnish, Polish, Portuguese, Czech, Slovakian, Chinese, Swedish, Russian and Dutch.
Contrast This parameter controls the contrast of the LCD screen in ten steps (0 – 9).
`Home\Setup\User
eBoost
Enabled : N
DAY OF WEEK
d1 d2 d3 d4 d5 d6 d7
HOURS / DAY
24 24 12 12 12 12 12
eBoost™ Operation Mode screen (option)
This screen is displayed only when eBoost™ Operation Mode is available (option).
Enabled (Y / N / Wait)
Y/N
This parameter (values Y/N) enables or disables the
eBoost™ Operation Mode. If the value is Y and the current time is in the interval for the current day, the eBoost™ Operation Mode is active.
Wait The eBoost™ Operation Mode configuration is being
updated.
In case of Parallel System
If eBoost™ Operation Mode is currently disabled (N) and Q1 is closed, when programming it to enable (Y) the selected configuration will automatically be propagated to all units in the parallel system.
The activation / deactivation of eBoost™ Operation Mode is indicated each time in the event list. In order to check the inverter function, at least 1 minute of VFI Operation Mode must be programmed during the week (the Y/N parameter is automatically disabled if this condition is not satisfied). In case this minimum time in VFI Operation Mode is not respected, the eBoost™ Operation Mode will be disabled.
If the value is N, the UPS is normally operating in VFI / double conversion mode at all times.
Status of the Home Page with UPS functioning in eBoost™ Operation Mode.
DAY OF WEEK (d1 ÷ d7): Enabling time in function of weekdays
Note: the configuration of the activation schedule can only be updated when eBoost™ Operation Mode is disabled (Enabled: N).
For the weekdays from d1 to d7 (Saturday to Friday) the edit mode (edit day) allows to define time intervals when the UPS is operating in eBoost™ Operation Mode. The hour is given in 24-hour format.
These intervals are defined by: eBoost START: The hour of the day after which the eBoost™ Operation Mode is enabled. The eBoost™ Operation Mode is enabled until the following eBoost STOP time is reached (the eBoost STOP time of the same day if this is later than the eBoost START time, the eBoost STOP time of the following day otherwise).
eBoost STOP: The hour of the day before which the eBoost™ Operation Mode is enabled. The eBoost™ Operation Mode is enabled starting from the preceding eBoost START time (the eBoost START time of
the same day if this is earlier than the eBoost STOP time, the eBoost START time of the previous day otherwise). Identical times for eBoost START and eBoost STOP maintain the existing mode only in case the previous command
was eBoost START and the following command will be eBoost STOP.
HOURS / DAY: The number of eBoost™ Operation Mode hours per weekday (from d1 - Saturday to d7 - Friday) is displayed in the operation mode parameter window (ceiling value).
Modifications reserved Page 41/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
To better understand the eBoost™ programming modes, some typical examples are shown:
Example 1:
For continuous eBoost™ Operation Mode set the eBoost START times to 00:00 and the eBoost STOP times to 23:59 for all weekdays, but almost 1 day must have 1 minute of VFI programmation: i.e d2 -
Sunday 00:00 to 23:58).
Weekday d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
eBoost START
00:00 00:00 00:00 00:00 00:00 00:00 00:00
eBoost STOP
23:59 23:58 23:59 23:59 23:59 23:59 23:59
Example 2:
eBoost STOP before eBoost START. eBoost START 18:00, eBoost STOP 06:00 for weekday d4 - Tuesday. Means that on d4 - Tuesday the eBoost™ Operation Mode is active between 00:00 and 06:00 and between 18:00 and 23:59.
Weekday d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
eBoost START
00:00 00:00 00:00 18:00 00:00 00:00 00:00
eBoost STOP
23:59 23:59 23:59 06:00 23:59 23:59 23:59
Example 3:
eBoost™ Operation Mode during the night and week-end. If the eBoost™ Operation Mode must be enabled all nights (d3 - Monday ÷ d7 - Friday) between 18:00 in the evening and 06:00 of the following morning and during all Saturday (d1) and Sunday (d2), the corresponding parameters are:
Weekday d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
eBoost START
00:00 00:00 18:00 18:00 18:00 18:00 18:00
eBoost STOP
23:59 23:59 06:00 06:00 06:00 06:00 06:00
Example 4:
If the eBoost™ Operation Mode must be enabled on Monday (d3) and Tuesday (d4) between 18:00 in the evening and 06:00 of the following morning, on Friday (d7) between 12:00 and 13:00, during all Saturday
(d1) and on Sunday (d2) until 20:00, the corresponding parameters are.
Weekday d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
eBoost START
00:00 00:00 18:00 18:00 00:00 00:00 12:00
eBoost STOP
23:59 20:00 23:59 06:00 06:00 00:00 13:00
eBoost START
eBoost STOP
In dark color are displayed the times with eBoost™ Operation Mode. The arrows indicate the conditions given by the eBoost START and eBoost STOP times introduced with
the parameters. Note that on day d6 - Thursday the interval has length 0 (zero), therefore the eBoost™ Operation Mode
is not enabled on this day.
Modifications reserved Page 42/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
Example 5:
An equivalent set of parameters for Example 4 is.
Weekday
d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
eBoost START
00:00 00:00 18:00 18:00 06:00 09:00 12:00
eBoost STOP
23:59 20:00 18:00 06:00 06:00 09:00 13:00
eBoost START
eBoost STOP
The eBoost™ Operation Mode is active from 18:00 of weekday d3 - Monday until 06:00 of weekday d4 - Tuesday (as indicated by the eBoost STOP time of weekday d4 - Tuesday).
The eBoost STOP time of weekday d3 - Monday has no effect as it is followed by the eBoost STOP time of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 18:00 and 23:59.
Similarly, the eBoost™ Operation Mode is active from 18:00 of weekday d4 - Tuesday until 06:00 of weekday d5 - Wednesday.
The eBoost START time of weekday d5 - Wednesday has no effect as it is preceded by the eBoost START time of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 00:00 and 06:00.
NOTE !
To avoid undesired eBoost™ Operation Mode, verify:
Date and Time (first page of parameter).
eBoost™ screen how many hours of eBoost™ Operation Mode have been selected
for each day of the week.
NOTE !
The eBoost™ Operation Mode will become active only if the Load is supplied from the Inverter.
Modifications reserved Page 43/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
6.5 COMMANDS
The COMMANDS mode is entered any time the “CMDS” button is pressed.
Allows the user to execute UPS operation commands.
In this mode the buttons perform the following functions:
Return to HOME screen.
Scrolls forward to the next screen.
V
Scrolls forward to the next line.
Confirm the selection made.
It is possible to view any pushbutton functional description by pushing the button for more than 3 seconds.
`Home\Commands
COMMANDS
LAMP TEST INVERTER ON INVERTER OFF RECTIFIER ON
V
Commands screen 1
LAMP TEST
Signaling LEDs test and buzzer test (all LED should be lit and blinking and the acoustical alarm should be activated).
INVERTER ON Command to switch the inverter. INVERTER OFF Command to shutdown the inverter. RECTIFIER ON Command to switch the rectifier.
Only for Service Center, the command access is protected by a code.
NOTE !
When eBoost™ Operation Mode is enabled, control of Inverter status and selection of the feed path is done autonomously by the UPS control logic. Therefore, Inverter ON / Inverter OFF commands are disabled when eBoost™ Operation Mode is enabled.
`Home\ Commands
COMMANDS
RESET TOTAL OFF
REQUEST TOTAL OFF
V
Commands screen 2
RESET TOTAL OFF
Reset Total OFF command should be executed to switch ON UPS after a “Load Off” operation.
REQUEST TOTAL OFF
Command “Load Off”.
Screen sequence to execute the command Load Off”:
`Home\Commands
`Home\Commands
COMMANDS COMMANDS
RESET TOTAL OFF RESET TOTAL OFF
REQUEST TOTAL OFF CANCEL TOTAL OFF EXECUTE TOTAL OFF
V
V
As the command procedure of “Load Off” is finished the “REQUEST TOTAL OFF” screen appears again.
Modifications reserved Page 44/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7 OPERATION
START UP AND COMMISSIONING
A GE GLOBAL SERVICES FIELD ENGINEER must perform start-up and commissioning of the UPS. Please Contact GE. Global Services at least two weeks prior to schedule start-up and commissioning at 1-800-637­1738, or by E-mail at pqservice@ge.com .
This symbol refers to the operations of a parallel system.
NOTE !
Verify for correct input/output cabling before connecting Utility to the UPS.
Open only the front door, do not remove any panels.
Check after every step for correct reaction of the UPS (LED’s on the panel), and correct voltage and current measurements, before you proceed to the next step.
NOTE !
All operations (including start-up, shutdown, removing/adding a unit from/to a Parallel System) MUST BE PERFORMED with eBoost™ Operation Mode DISABLED.
Find on the following pages the descriptions of the various procedures of start-up and shutdown for UPS single and UPS Parallel System, divided into the following principal chapters:
7.1 PROCEDURES FOR SINGLE SG Series 400 & 500
7.2 PROCEDURES FOR SG Series 400 & 500 PARALLEL SYSTEM STANDARD AND PARALLEL
SYSTEM WITH COMMON BATTERY
Modifications reserved Page 45/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.1 PROCEDURES FOR SINGLE SG Series 400 & 500
7.1.1 Start-up of the SG Series 400 & 500
WARNING !
Before proceeding to Turn ON the UPS System, ensure that the AC and DC external isolators are OFF (Pos. O), and prevent their inadverted operation.
Ensure that the output load distribution can be powered and all the output isolators are open (Pos. O).
Open the front door and make sure that:
All the connections to the input/output bus bars of the UPS have been made correctly.
The safety screens are fixed in their position.
The UPS Output Switch Q1, Manual Bypass Switch Q2 (option) and the External Battery Switch or
Fuses must be open (Pos. O).
LEDs on Synoptic Diagram
SGS_400-500_S2_Switches Q1-Q2_01
Q1
0
O
F
F
I ON
Q2
0
O
F
F
I ON
Q1 UPS Output switch Q2 Manual Bypass switch (option)
LED 1 Utility Rectifier OK LED 2 Utility Bypass OK LED 3 Rectifier ON LED 4a Discharging Battery LED 4b Charging Battery LED 5 Inverter available
LED 6 Inverter ON LED 7 Q1 closed LED 8 Automatic Bypass ON LED 9 Manual Bypass Q2 ON (option) LED 10 Load on UPS
Key Key Key LED LED LED
Inverter ON Inverter OFF Load Off Stop Operation Alarm Operation
1.
Switch-ON the Utility Voltage from the input distribution (both rectifier and bypass if separated).
At this stage the electronic power supply is switched ON.
Overall test results
Test1 OK Test7 OK Test2 OK Test8 OK Test3 OK Test9 OK Test4 OK Test10 OK Test5 OK Test11 OK Test6 OK
The UPS performs a SELFTEST. A successful termination of the tests will be indicated with Overall test results “OK”. Commissioning cannot be continued should one or more tests result to be negative. Please contact in this case your Service Center.
With “Overall test results - OK” the Synoptic Diagram is displayed. LED 1 (Utility Rectifier OK) and LED 2 (Utility Bypass OK) must be ON. The buzzer sounds, press the “MUTE” key to reset acoustical alarm. LED Alarm remains lit.
Continue
Modifications reserved Page 46/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
NOTE !
During the first commissioning SG Series 400 & 500 requests a set up of the UPS configuration parameters presented in the following screens.
Without such configuration it is not possible to continue with the commissioning procedure.
WARNING !
The setup of the UPS configuration parameters must be done only by a GE GLOBAL SERVICES FIELD ENGINEER.
The setup of mistaken values could compromise the integrity and reliability of the UPS.
In this mode the keys perform the following functions:
Confirm the selection made and select the next parameter.
ESC
Re-establish default value.
Modify or insert the selected value.
Save the configuration of set parameters.
`Configuration
DISPLAY CONFIGURATION
Select language : ENGLISH
ESC
DISPLAY CONFIGURATION screen
Select language
This parameter allows the choice of language used to display
the information.
Pushing the pushbuttons “1st button” (METER) and “2nd button” (ALARM) together automatically sets the LCD communication for “ENGLISH”.
`Configuration
UPS CONFIGURATION
Input frequency : 60 Hz Output frequency : 60 Hz Inverter voltage : 277 V
ESC
UPS CONFIGURATION screen
Input frequency
Rectifier input frequency value. The default value is 60Hz and shall not be changed.
Output frequency
Inverter output frequency value. The default value is 60Hz and shall not be changed.
Inverter voltage Output voltage PHASE/NEUTRAL of the inverter (default 277V).
Continue
Modifications reserved Page 47/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
`Configuration
BATTERY CONFIGURATION
Type : Lead Acid Float voltage : 545 V Recharge current : 100.0 A Autonomy time : 012 min Stop Operation time : 003 min Capacity : 0500 Ah Cells : 240
ESC
BATTERY CONFIGURATION screen
Recharge type
Recharge type (Lead Acid / NiCd / Boost).
Lead Acid
for:
Sealed battery (VRLA), NiCd without boost­charge and open battery without boost­charge.
NiCd
for:
Nickel Cadmium battery with boost-charge.
Boost
for: O
pen battery with boost-charge.
Float voltage
Voltage to maintain battery charging. Float voltage = Number of battery cells x battery float voltage per cell. Typical battery float voltage per cell (ask the battery manufacturer for confirmation):
Sealed battery (VRLA):
2.27Vdc for cell
240 cells x 2.27Vdc = 545Vdc
NiCd without boost-charge:
1.41Vdc for cell
386 cells x 1.41Vdc = 545Vdc
NiCd with boost-charge:
1.41 (1.55 boost-charge) Vdc for cell 351 cells x 1.41Vdc = 495 (545) Vdc
O
pen battery without boost-charge: 2.23Vdc for cell
240 cells x 2.23Vdc = 535Vdc
O
pen battery with boost-charge:
2.23 (2.35 boost-charge) Vdc for cell 232 cells x 2.23Vdc = 518 (545) Vdc
Recharge current
Maximum battery recharge current. Max 20% of battery capacity (Ah). Example: 500Ah - max recharging current 100A.
Autonomy time
The autonomy time of the battery. UPS autonomy on battery mode at full load condition. This value is calculated based on the battery type, capacity and number of cells.
Stop Operation time
Residual battery autonomy time before UPS forced shutdown. Standard set 3 minutes. Settable from 1 minute to autonomy time in minutes (see tables).
Capacity
Ah capacity of the battery.
Cells Number of cells of the battery, see “Float voltage”.
Example:
240 battery cells
40 blocks / 12Vdc battery 80 blocks / 6Vdc battery 240 blocks / 2Vdc battery
NOTE !
The values indicated above, must be considered as standard values. The actual programmed values must be the ones defined from the battery manufacturer.
`Configuration
CONFIGURATION
Save and exit ?
Yes
CONFIGURATION screen
Screen to save the configuration of set parameters.
Any additional modification of setup parameters can be done only from a GE SERVICE PERSON as it requires an access code.
Continue
Modifications reserved Page 48/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
2. Close the UPS Output Switch Q1 (Pos. I).
The Load is supplied by the Utility through the Automatic Bypass.
Rectifier starts automatically, blinking LED 3 (Rectifier ON) indicates Soft-start.
At the end of Rectifier Soft-start the LED 3 (Rectifier ON) remains lit.
The Synoptic Diagram must display the status “LOAD SUPPLIED BY AUTOMATIC BYPASS”.
3. Connect the Battery to the UPS by closing (Pos. I) the External Battery Switch or Fuses.
Attention: to check the right DC polarities on both side of the switch/fuse holder! LED 4b (Charging Battery) should be lit indicating battery charge.
ATTENTION !
Before performing this operation, the LED 3 (Rectifier ON) must remain lit, thus indicating that the DC-Link has reached floating voltage (540Vdc)!
4. Insert the Inverter by pressing the “Inverter ON” ( I ) key.
Soft-start of Inverter indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
Automatic transfer from Automatic Bypass to Inverter.
UPS output LED indicates Load on Inverter.
LED Alarm turn Off and the LED Operation must be lit.
The Synoptic Diagram must display the status “LOAD SUPPLIED BY INVERTER”.
5. Load supply.
SG Series 400 & 500 is now running, supplying power to the output. Insert the loads one by one to the output of the UPS. Check the output current value of L1, L2 and L3 and check for correct load balance.
6. Operation mode selection.
SG Series 400 & 500 is delivered normally selected for permanent VFI operation. eBoost™ Operation Mode can be enabled if available, and the eBoost START time & eBoost STOP time can be programmed for each day of the week (see Section 6.4 SETUP / eBoost).
END OF PROCEDURE
NOTE !
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in case of a Utility Failure.
Modifications reserved Page 49/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.1.2 UPS shutdown with Load transfer on Manual Bypass Q2 (option)
NOTE !
Not following this procedure can cause protected loads to shut down!
Never close or open either UPS Output Switch Q1 and Manual Bypass switch Q2 (option) with the Inverter running!
Initial situation: the Load is powered by the Inverter.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
The complete UPS system has to be turned OFF, while providing the Load power by Utility through the Manual Bypass Q2 (option).
With the UPS in normal operation and the inverter supplying the Load, the UPS Output Switch Q1 is closed (Pos. I) and the Manual Bypass Switch Q2 (option) is open (Pos. O).
The External Battery Switch or Fuses are closed (Pos. I).
The Synoptic Diagram must display the statusLOAD
SUPPLIED BY INVERTER”.
1. Disconnect the Inverter by pressing the Inverter OFF ( O ) key and hold until the LED 5 (Inverter available) turns OFF.
Load is transferred to Utility by Automatic Bypass.
Inverter shuts down. LED 5 (Inverter available) must be OFF.
LED Alarm is lit and the LED Operation is Off.
The Synoptic Diagram must display the status “LOAD SUPPLIED BY AUTOMATIC BYPASS”.
2. Close the Manual Bypass Switch Q2 (Pos. I).
Load is now supplied parallel through Automatic Bypass and Manual Bypass Q2.
LED 8 (Automatic Bypass ON) and LED 9 (Manual Bypass Q2 ON) are lit.
The Synoptic Diagram must display the statusLOAD
SUPPLIED BY AUTOMATIC BYPASS AND MANUAL BYPASS Q2”.
Continue
Modifications reserved Page 50/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
3. Open the UPS Output Switch Q1 (Pos. O) and then press the “Load Off” key.
The load is now supplied only through the Manual Bypass Q2.
Rectifier shuts down and all output and input Contactors are opened.
Press “MUTE” to reset the alarm buzzer.
The Synoptic Diagram must display the status “LOAD SUPPLIED BY MANUAL BYPASS Q2”.
4. Disconnect the Battery from the UPS by opening (Pos. O) the External Battery Switch or Fuses.
Wait 5 minutes for DC-Link Capacitors discharge.
The Load is now powered from the Utility through Manual Bypass Q2 (option).
END OF PROCEDURE
WARNING!
It will take a minimum of 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
Modifications reserved Page 51/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.1.3 From Manual Bypass Q2 (option) to normal function VFI
NOTE !
UPS system has been turned OFF following the “Maintenance shutdown (Load on
Manual Bypass Q2)” procedure and the Load is still powered by Manual Bypass Q2 (option).
The Load must be transferred back to the UPS system.
Open the front door and make sure that:
The safety screens are fixed in their position.
The UPS Output Switch Q1 and the External Battery Switch or Fuses are open (Pos. O).
The Manual Bypass Switch Q2 (option) is closed (Pos. I).
LED Alarm is lit.
Initial status:
Load supplied from Manual Bypass Q2 (option).
1. If not already supplied (separate Utility Inputs), switch-ON the Utility power to the Rectifier input.
2. Close the UPS Output Switch Q1 (Pos. I).
Load is now supplied parallel through Automatic Bypass and Manual Bypass Q2. LED 8 (Automatic Bypass ON) and LED 9 (Manual Bypass Q2 ON) are lit.
Rectifier starts automatically, blinking LED 3 (Rectifier ON) indicates Soft-start.
At the end of Rectifier Soft-start the LED 3 (Rectifier ON) remains lit.
The Synoptic Diagram must display the status “LOAD SUPPLIED BY AUTOMATIC BYPASS AND MANUAL BYPASS Q2”.
3. Connect the Battery to the UPS by closing (Pos. I) the External Battery Switch or Fuses.
LED 4b (Charging Battery) should be lit indicating battery charge.
ATTENTION !
Before performing this operation, the LED 3 (Rectifier ON) must remain lit, thus indicating that the DC-Link has reached floating voltage (540Vdc)!
Continue
Modifications reserved Page 52/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
4. Open the Manual Bypass Switch Q2 (Pos. O).
The Load is supplied by the Utility through the Automatic Bypass.
LED 8 (Automatic Bypass ON) is lit and LED 9 (Manual Bypass Q2 ON) turns OFF.
The Synoptic Diagram must display the statusLOAD
SUPPLIED BY AUTOMATIC BYPASS”.
5. Insert the Inverter by pressing the “Inverter ON” ( I ) key.
Soft-start of Inverter, indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
Automatic transfer from Automatic Bypass to Inverter.
LED Alarm turn Off and the LED Operation must be lit.
The Synoptic Diagram must display the status “LOAD SUPPLIED BY INVERTER”.
END OF PROCEDURE
Modifications reserved Page 53/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.1.4 Complete UPS shutdown
NOTE !
Follow this procedure only in case the UPS system and the Load must be completely powered-down.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
Initial status:
Load supplied from Inverter.
1. Press the “Load Off” key.
Load is disconnected from UPS.
Rectifier and Inverter are shut down, all output and input
Contactors will be opened.
LED 3 (Rectifier ON), LED 5 (Inverter available) and LED 10
(Load on UPS) are OFF.
LED Alarm is lit and the LED Operation is Off.
2. Open the UPS Output Switch Q1 (Pos. O).
3. Disconnect the Battery from the UPS by opening (Pos. O) the External Battery Switch or Fuses.
Wait 5 minutes for DC-Link Capacitors discharge.
4. Disconnect the Utility from the input distribution.
Complete power shutdown will OFF the LCD Display
Panel.
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge. Open only the front door, do not open any other part of the UPS.
Modifications reserved Page 54/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.1.5 Restore to normal operation after “Load Off”
NOTE !
Make sure the UPS to be status of the activation of “Load Off”, i. e. UPS Output
Switch Q1 closed (Pos. I), Manual Bypass Switch Q2 (option) open (Pos. O) and External Battery Switch or Fuses connected (Pos. I).
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
View of the Synoptic Diagram after pressing the “Load Off” key.
All Contactors are open.
Rectifier, Inverter and Static-Switch shutdown.
LED Alarm is lit.
`Home\Commands
COMMANDS
RESET TOTAL OFF
REQUEST LOAD OFF
V
1. Reset “Load Off”.
Restore the command “Load Off” by entering the screen: COMMANDS / RESET TOTAL OFF
The Load is supplied by the Utility through the Automatic
Bypass.
Rectifier starts automatically, blinking LED 3 (Rectifier
ON) indicates Soft-start.
At the end of Soft-start the LED 3 (Rectifier ON) remains
lit.
The Synoptic Diagram must display the statusLOAD
SUPPLIED BY AUTOMATIC BYPASS”.
2. Insert the Inverter by pressing the Inverter ON” ( I ) key.
Soft-start of Inverter indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
Automatic transfer from Automatic bypass to Inverter.
LED Alarm turn Off and the LED Operation must be lit.
The Synoptic Diagram must display the status “LOAD SUPPLIED BY INVERTER”.
END OF PROCEDURE
Modifications reserved Page 55/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.1.6 Restore to normal operation after EPO (Emergency Power Off)
NOTE !
Make sure the UPS to be status of the activation of EPO, i. e. UPS Output Switch Q1 closed (Pos. I), Manual Bypass Switch Q2 (option) open (Pos. O) and External Battery Switch or Fuses connected (Pos. I).
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting this procedure.
View of the Synoptic Diagram after activation of EPO (Emergency Power Off) with Utility available.
All Contactors are open.
Rectifier, Inverter and Static-Switch shutdown.
LED Alarm is lit.
1. Reset the EPO (Emergency Power Off) key.
Press the “MUTE” key to reset alarm and acoustical alarm.
LED Alarm remains lit.
2. Press the “Inverter OFF” ( O ) key.
Load is transferred to Utility by Automatic Bypass.
Rectifier starts automatically, blinking LED 3 (Rectifier ON) indicates Soft-start.
At the end of Rectifier Soft-start the LED 3 (Rectifier ON) remains lit.
The Synoptic Diagram must display the status “LOAD SUPPLIED BY AUTOMATIC BYPASS”.
3. Insert the Inverter by pressing the Inverter ON” ( I ) key.
Soft-start of Inverter indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
The Load will be automatically transferred from Automatic Bypass to Inverter.
LED Alarm turn Off and the LED Operation must be lit.
The Synoptic Diagram must display the status “LOAD SUPPLIED BY INVERTER”.
END OF PROCEDURE
Modifications reserved Page 56/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.2 PROCEDURES FOR SG Series 400 & 500 PARALLEL SYSTEM AND PARALLEL
SYSTEM WITH COMMON BATTERY
7.2.1 SG Series 400 & 500 Parallel System start-up
WARNING !
Before proceeding to Turn ON the UPS System, ensure that the AC and DC external isolators are OFF (Pos. O), and prevent their inadverted operation.
Ensure that the output load distribution can be powered and all the output isolators are open (Pos. O).
Open the front door on all UPS units and make sure that:
All the connections to the input/output bus bars of the UPS have been made correctly.
The safety screens are fixed in their position.
The UPS Output Switch Q1, Manual Bypass Switch Q2 (option) and the External Battery Switch or
Fuses must be open (Pos. O).
LEDs on Synoptic Diagram
SGS_400-500_S2_Switches Q1-Q2_01
Q1
0
O
F
F
I ON
Q2
0
O
F
F
I ON
Q1 UPS Output Switch
Q2 Manual Bypass switch (option)
LED 1 Utility Rectifier OK LED 2 Utility Bypass OK LED 3 Rectifier ON LED 4a Discharging Battery LED 4b Charging Battery LED 5 Inverter available
LED 6 Inverter ON LED 7 Q1 closed LED 8 Automatic Bypass ON LED 9 Manual Bypass Q2 ON (option) LED 10 Load on UPS
Key Key Key LED LED LED
Inverter ON Inverter OFF Load Off Stop Operation Alarm Operation
1.
Switch-ON the Utility Voltage, on all UPS units, from the input distribution (both rectifier and bypass if separated).
At this stage the electronic power supply is switched ON.
Overall test results
Test1 OK Test7 OK Test2 OK Test8 OK Test3 OK Test9 OK Test4 OK Test10 OK Test5 OK Test11 OK Test6 OK
The UPS performs a SELFTEST. A successful termination of the tests will be indicated with Overall test results “OK”. Commissioning cannot be continued should one or more tests result to be negative. Please contact in this case your Service Center.
With “Overall test results - OK” the Synoptic Diagram is displayed. LED 1 (Utility Rectifier OK) and LED 2 (Utility Bypass OK) must be ON.
The buzzer sounds, press the “MUTE” key to reset acoustical alarm. LED Alarm remains lit.
Continue
Modifications reserved Page 57/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
NOTE !
During the first commissioning SG Series 400 & 500 requests a set up of the UPS configuration parameters presented in the following screens.
Without such configuration it is not possible to continue with the commissioning procedure.
WARNING !
The setup of the UPS configuration parameters must be done only by a GE GLOBAL SERVICES FIELD ENGINEER.
The setup of mistaken values could compromise the integrity and reliability of the UPS.
In this mode the keys perform the following functions:
Confirm the selection made and select the next parameter.
ESC
Re-establish default value.
Modify or insert the selected value.
Save the configuration of set parameters.
`Configuration
DISPLAY CONFIGURATION
Select language : ENGLISH
ESC
DISPLAY CONFIGURATION screen
Select language
This parameter allows the choice of language used to display the information.
Pushing the pushbuttons “1st button” (METER) and “2nd button” (ALARM) together automatically sets the LCD communication for “ENGLISH”.
`Configuration
UPS CONFIGURATION
Input frequency : 60 Hz Output frequency : 60 Hz Inverter voltage : 277 V
ESC
UPS CONFIGURATION screen
Input frequency
Rectifier input frequency value. The default value is 60Hz and shall not be changed.
Output frequency
Inverter output frequency value. The default value is 60Hz and shall not be changed.
Inverter voltage Output voltage PHASE/NEUTRAL of the inverter (default 277V).
Continue
Modifications reserved Page 58/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
`Configuration
BATTERY CONFIGURATION
Type : Lead Acid Float voltage : 545 V Recharge current : 050.0 A Autonomy time : 012 min Stop Operation time : 003 min Capacity : 0250 Ah Cells : 240
ESC
BATTERY CONFIGURATION screen
Recharge type
Recharge type (Lead Acid / NiCd / Boost).
Lead Acid
for:
Sealed battery (VRLA), NiCd without boost­charge and open battery without boost­charge.
NiCd
for:
Nickel Cadmium battery with boost-charge.
Boost
for: O
pen battery with boost-charge.
Float voltage
Voltage to maintain battery charging. Float voltage = Number of battery cells x battery float voltage per cell. Typical battery float voltage per cell (ask the battery manufacturer for confirmation):
Sealed battery (VRLA):
2.27Vdc for cell
240 cells x 2.27Vdc = 545Vdc
NiCd without boost-charge:
1.41Vdc for cell
386 cells x 1.41Vdc = 545Vdc
NiCd with boost-charge:
1.41 (1.55 boost-charge) Vdc for cell 351 cells x 1.41Vdc = 495 (545) Vdc
O
pen battery without boost-charge: 2.23Vdc for cell
240 cells x 2.23Vdc = 535Vdc
O
pen battery with boost-charge:
2.23 (2.35 boost-charge) Vdc for cell 232 cells x 2.23Vdc = 518 (545) Vdc
Recharge current
Maximum battery recharge current. Max 20% of battery capacity (Ah). Example: 250Ah - max recharging current 50A.
Autonomy time
The autonomy time of the battery. UPS autonomy on battery mode at full load condition. This value is calculated based on the battery type, capacity and number of cells.
Stop Operation time
Residual battery autonomy time before UPS forced shutdown. Standard set 3 minutes. Settable from 1 minute to autonomy time in minutes (see tables).
Capacity
Ah capacity of the battery.
Cells Number of cells of the battery, see “Float voltage”.
Example:
240 battery cells
40 blocks / 12Vdc battery 80 blocks / 6Vdc battery 240 blocks / 2Vdc battery
NOTE !
The values indicated above, must be considered as standard values. The actual programmed values must be the ones defined from the battery manufacturer.
`Configuration
CONFIGURATION
Save and exit ?
Yes
CONFIGURATION screen
Screen to save the configuration of set parameters.
Any additional modification of setup parameters can be done only from a GE SERVICE PERSON as it requires an access code.
Continue
Modifications reserved Page 59/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
2 Close UPS Output Switch Q1 (Pos. I) on first Unit.
Rectifiers start automatically, blinking LED 3 (Rectifier ON) indicates Soft-start.
At the end of Rectifier Soft-start, the LED 3 (Rectifier ON) remains lit.
Synoptic Diagram of first unit Synoptic Diagram of other units
3. Connect the Battery on first Unit by closing (Pos. I) its External Battery Switch or Fuses.
Attention: to check the right DC polarities on both side of the switch/fuse holder! LED 4b (Charging Battery) should be lit indicating battery charge.
ATTENTION !
Before performing this operation, the LED 3 (Rectifier ON) must remain lit, thus indicating that the DC-Link has reached floating voltage (540Vdc)!
4. Repeat the procedures 2 and 3 for each next Unit.
When closing UPS output switch Q1 on the last unit of the Parallel System, the Automatic Bypass of all Units connects to the Load.
The Synoptic Diagram, on all UPS units, must display the statusLOAD SUPPLIED BY AUTOMATIC BYPASS.
Synoptic Diagram of first unit Synoptic Diagram of other units
5. Insert the Inverter by pressing the Inverter ON ( I ) key on first unit.
Soft-start of Inverter, indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
In case of sufficient output power, the output will transfer to Inverter.
LED Alarm turn Off and the LED Operation must be lit.
Synoptic Diagram of first unit Synoptic Diagram of other units
Continue
Modifications reserved Page 60/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
6. Insert the Inverter by pressing the Inverter ON ( I ) key on all other units.
Do not start the next Inverter until the sequence of the previous ends.
As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with
running Inverter will transfer to Inverter.
LED Alarm turn Off and the LED Operation must be lit.
The Synoptic Diagram, on all UPS units, must display the statusLOAD SUPPLIED BY INVERTER”.
Synoptic Diagram of first unit Synoptic Diagram of other units
7. Load supply.
SG Series 400 & 500 Parallel System is now running, supplying power to the output. Insert the Loads one by one to the output of the SG Series 225 & 300 Parallel System. Check the output current value of L1, L2 and L3 and check for correct load balance.
8. Operation mode selection.
SG Series 400 & 500 Parallel System is delivered normally selected for permanent VFI operation. eBoost™ Operation Mode can be enabled if available, and the eBoost START time & eBoost STOP time can be programmed for each day of the week (see Section 6.4 SETUP / eBoost).
END OF PROCEDURE
NOTE !
The Battery must be charged for at least 10 hours, in order to ensure the full backup runtime in case of a Utility Failure.
Modifications reserved Page 61/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.2.2 Parallel System shutdown with Load transfer on Manual Bypass Q2 (option)
NOTE !
Not following this procedure can cause protected loads to shut down! Never close or open either UPS Output Switch Q1 and Manual Bypass switch Q2
(option) with the inverter running! Initial situation: the Load is powered by all Inverters of the Parallel System. If eBoost™ option is available, make sure that eBoost™ Operation Mode is
disabled before starting the shutdown procedure. The complete UPS Parallel System has to be turned OFF, while providing the Load
power by Utility through all Manual Bypass Q2 (option).
With the UPS Parallel System in normal operation and the Inverters supplying the Load, the UPS Output Switches Q1 are closed (Pos. I) and the Manual Bypass Switches Q2 (option) are open (Pos. O).
The External Battery Switch or Fuses are closed (Pos. I).
The Synoptic Diagram, on all UPS units, must display the statusLOAD SUPPLIED BY INVERTER.
1. Disconnect the Inverter by pressing the “Inverter OFF” ( O ) key on all Units, and hold until the LED 5 (Inverter available) turns OFF.
At no redundancy, the system will transfer to Utility supply. LED 5 (Inverter available) is Off.
LED Alarm is lit and the LED Operation is Off.
The Synoptic Diagram, on all UPS units, must display the statusLOAD SUPPLIED BY AUTOMATIC BYPASS.
Synoptic Diagram of first unit Synoptic Diagram of other units
2. Close the Manual Bypass Switch Q2 (Pos. I) on all Units.
Load is now supplied from Utility in parallel from Automatic Bypass and Manual Bypass Q2 of all Units.
LED 8 (Automatic Bypass ON) and LED 9 (Manual Bypass Q2 ON) are lit.
The Synoptic Diagram, on all UPS units, must display the status “LOAD SUPPLIED BY AUTOMATIC BYPASS AND MANUAL BYPASS Q2”.
Synoptic Diagram of first unit Synoptic Diagram of other units
Continue
Modifications reserved Page 62/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
3. Open the UPS Output Switch Q1 (Pos. O) and then press the Load Off key on all Units.
The Load is now supplied only through the Manual Bypass Q2 of all Units.
LED 8 (Automatic Bypass ON) turns OFF and LED 9 (Manual Bypass Q2 ON) stays lit.
All Rectifiers are shutdown and all output and input Contactors are opened.
The Synoptic Diagram, on all UPS units, must display the status LOAD SUPPLIED BY MANUAL BYPASS Q2.
Synoptic Diagram of first unit Synoptic Diagram of other units
4. Disconnect the Battery from on all Units by opening (Pos. O) the External Battery Switch or Fuses.
Wait 5 minutes for DC-Link Capacitors discharge.
The Load is now powered from the Utility through all Manual Bypass Q2 (option) of the Parallel
System.
END OF PROCEDURE
WARNING!
It will take a minimum of 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
Modifications reserved Page 63/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.2.3 From Manual Bypass Q2 (option) to normal function VFI
NOTE !
UPS Parallel System has been turned OFF following the “Maintenance shutdown (Load on Manual Bypass Q2)” procedure and the Load is still powered by all Manual Bypass Q2 (option).
The Load must be transferred back to the UPS Parallel System.
Open the front door on all UPS units and make sure that:
The safety screens are fixed in their position.
The UPS Output Switches Q1 and the External Battery Switch or Fuses are open (Pos. O).
The Manual Bypass Switches Q2 (option) are closed (Pos. I).
LED Alarm are lit.
Initial status:
Load supplied from all Manual Bypass Q2 of the Parallel System.
All Manual Bypass Switches Q2 of the Parallel System are closed.
1. If not already supplied (separate utility inputs), switch-ON the utility power to the rectifier input on all UPS units.
2. Close the UPS output switch Q1 (Pos. I) on first Unit.
Rectifier starts automatically, blinking LED 3 (Rectifier ON) indicates Soft-start.
At the end of Rectifier Soft-start, LED 3 (Rectifier ON) remains lit.
Synoptic diagram of first unit Synoptic diagram of other units
3. Connect the Battery on first Unit by closing (Pos. I) its External Battery Switch or Fuses.
LED 4b (charging battery) should be lit indicating battery charge.
ATTENTION !
Before performing this operation, the LED 3 (Rectifier ON) must remain lit, thus indicating that the DC-Link has reached floating voltage (540Vdc)!
Continue
Modifications reserved Page 64/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
4. Repeat the procedures 2 and 3 for each other Unit.
The Rectifiers will start automatically and at the closure of UPS output switch Q1 of the last Unit, the output will be supplied parallel from Automatic Bypass and Manual Bypass Q2 of all UPS units.
LED 8 (Automatic Bypass ON) and LED 9 (Manual Bypass Q2 ON) are lit.
Synoptic Diagram of first unit Synoptic Diagram of other units
5. Open the Manual Bypass Switch Q2 (Pos. O) on all Units.
The Load is supplied by the Utility through the Automatic Bypass of all Units.
LED 8 (Automatic Bypass ON) is lit and LED 9 (Manual Bypass Q2 ON) turns OFF.
The Synoptic Diagram, on all UPS units, must display the statusLOAD SUPPLIED BY AUTOMATIC BYPASS.
Synoptic Diagram of first unit Synoptic Diagram of other units
6. Insert the Inverter by pressing the “Inverter ON” ( I ) key on first unit.
Soft-start of Inverter, indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
In case of sufficient output power, the output will transfer to Inverter.
Synoptic Diagram of first unit Synoptic Diagram of other units
7. Insert the Inverter by pressing the Inverter ON ( I ) key on all other units.
Do not start the next Inverter until the sequence of the previous one ends.
Soft-start of Inverter, indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units
with running Inverter will transfer to Inverter.
LED Alarm turn Off and the LED Operation must be lit.
The Synoptic Diagram, on all UPS units, must display the statusLOAD SUPPLIED BY INVERTER”.
Synoptic Diagram of first unit Synoptic Diagram of other units
END OF PROCEDURE
Modifications reserved Page 65/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.2.4 Separate a UPS Unit from the Parallel System (System Redundancy)
NOTE:
The Load is powered by the UPS Redundant Parallel System. One UPS unit of the Parallel System has to be turned Off, while the Load is shared between the other units supplying the parallel bus.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting the shutdown procedure.
WARNING!
The control bus cable connecting J52 (A) and J62 (B) cannot be connected or disconnected after the system has been powered on.
Initial status:
Load supplied from all Inverters of the Redundant Parallel System.
1. Disconnect the Inverter by pressing the Inverter OFF ( O ) key and hold until the LED 5 (Inverter available) turns OFF on the Unit to separate.
With redundant system, pressing the key OFF the Inverter shuts down and it will stay OFF. If by pressing the key “O” the Load is transferred to the Utility and the Inverter remains operating, it means
the system is not redundant. In this case is not possible to switch-OFF one unit without transferring the Load on Utility.
Load supplied from Inverter(s) of the other Unit(s) of the Parallel System.
Synoptic Diagram of the unit to separate Synoptic Diagram of other units
2. Open the UPS Output Switch Q1 (Pos. O) on the Unit to separate.
LED Alarm is lit and the LED Operation is Off.
LED 6 (Inverter ON) and LED 7 (Q1 closed) must be Off.
Synoptic Diagram of the unit to separate Synoptic Diagram of other units
Continue
Modifications reserved Page 66/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
`Home\Commands
COMMANDS
RESET TOTAL OFF
REQUEST TOTAL OFF
V
3. Perform the command “Load Off” on the Unit to separate only when the LED 7 (Q1 closed) is Off.
Perform the command “Load Off” by entering the screen (see Section 7.5):
COMMANDS / REQUEST TOTAL OFF
Synoptic Diagram of the unit to separate Synoptic Diagram of other units
4. Disconnect the Battery on the Unit to separate by opening (Pos. O) the External Battery Switch or Fuses.
Wait 5 minutes for DC-Link Capacitors discharge.
5. Disconnect the Utility supply on the Unit to separate.
Complete power shutdown will OFF the LCD Display Panel.
Synoptic Diagram of the unit to separate Synoptic Diagram of other units
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge. Open only the front door, do not open any other part of the UPS.
NOTE !
For any further intervention contact nearest Service Center.
Modifications reserved Page 67/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.2.5 Reconnect a UPS unit to a Parallel System
NOTE:
The Load is still powered by the other units supplying the Parallel Bus. This UPS unit will be powered on and connected to the Parallel Bus in order to share
the Load with each other's. If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting the shutdown procedure.
WARNING !
The High Speed Bus Cable Connecting J52 (A) and J62 (B) in any case cannot be connected or disconnected after the system has been powered ON. The Bus Terminals must be properly connected before powering the additional unit.
Open the front door, of the Unit to reconnect, and make sure that:
All the connections to the input/output bus bars of the UPS have been made correctly.
The protection panels are fastened in their correct position.
The UPS Output Switch Q1, Manual Bypass Switch Q2 (option) and the External Battery Switch or
Fuses must be open (Pos. O).
1.
Switch-ON the Utility Voltage, on the Unit to reconnect, from the input distribution (both Rectifier and bypass if separated).
At this stage the electronic power supply is switched ON.
Overall test results
Test1 OK Test7 OK Test2 OK Test8 OK Test3 OK Test9 OK Test4 OK Test10 OK Test5 OK Test11 OK Test6 OK
The UPS performs a SELFTEST.
A successful termination of the tests will be indicated with Overall test results “OK”. Commissioning cannot be continued should one or more tests result to be negative. Please contact in this case your Service Center.
With “Overall test results - OK” the Synoptic Diagram is displayed. LED 1 (Utility Rectifier OK) and LED 2 (Utility Bypass OK) must be lit.
The buzzer sounds, press the “MUTE” key to reset acoustical alarm. LED Alarm remains lit.
Synoptic diagram of the unit to reconnect Synoptic diagram of other units
Continue
Modifications reserved Page 68/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
2. Close the UPS Output Switch Q1 (Pos. I) on the Unit to reconnect.
Rectifier starts automatically, blinking LED 3 (Rectifier ON) indicates Soft-start.
At the end of Rectifier Soft-start the LED 3 (Rectifier ON) remains lit.
Synoptic diagram of the unit to reconnect Synoptic diagram of other units
3. Connect the Battery on the Unit to reconnect by closing (Pos. I) the External Battery Switch or Fuses.
LED 4b (Charging Battery) should be lit indicating battery charge.
ATTENTION !
Before performing this operation, the LED 3 (Rectifier ON) must remain lit, thus indicating that the DC-Link has reached floating voltage (540Vdc)!
4. Insert the Inverter by pressing the “Inverter ON” ( I ) key on the Unit to reconnect.
The inverter will start up. LED 5 (Inverter available) must be blinking In a short time, when the Inverter voltage is confirmed, the LED 5 (Inverter available) will stop blinking and stay fixed lit. The Load will be automatically shared between the Parallel Units and this Inverter.
LED Alarm turn Off and the LED Operation must be lit.
Verify on display screen that the load should be equally shared between the parallel units.
The synoptic diagram, on all UPS units, must display the statusLOAD SUPPLIED BY INVERTER”.
Synoptic Diagram of the unit to reconnect Synoptic Diagram of other units
END OF PROCEDURE
Modifications reserved Page 69/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.2.6 Complete Parallel System shutdown
NOTE !
Follow this procedure only in case the UPS Parallel System and the Load must be completely powered-down.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting the shutdown procedure.
Initial situation:
The Load is powered by SG Series 225 & 300 Parallel System supplying the Parallel Bus.
With the UPS Parallel System in normal operation and the Inverters supplying the Load, the UPS Output Switches Q1 and the External Battery Switch or Fuses are closed (Pos. I) and the Manual Bypass Switches Q2 (option) are open (Pos. O).
Initial status:
Load supplied from all Inverters of the Parallel System.
1. Press the “Load Off” key on anyone of the Parallel Units.
Load is disconnected from UPS Parallel System.
Rectifiers and Inverters are shut down and all output and input Contactors will be opened.
LED 3 (Rectifier ON), LED 5 (Inverter available) and LED 10 (Load on UPS) are OFF.
LED Alarm is lit and the LED Operation is Off.
Synoptic Diagram of first unit Synoptic Diagram of other units
2. Open the UPS Output Switch Q1 (Pos. O) on all Units.
LED 7 (Q1 closed) is Off.
Synoptic Diagram of first unit Synoptic Diagram of other units
Continue
Modifications reserved Page 70/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
3. Disconnect on all Units the Battery from the UPS by opening (Pos. O) the External Battery Switch or Fuses.
Wait 5 minutes for DC-Link Capacitors discharge.
4. Disconnect the Utility supply on all Units.
Complete power shutdown will OFF the LCD Display Panel.
Synoptic Diagram of first unit Synoptic Diagram of other units
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge. Open only the front door, do not open any other part of the UPS.
Modifications reserved Page 71/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.2.7 Restore to normal operation after “Load Off”
NOTE !
Make sure the all Units of the Parallel System to be status of the activation of “Load Off”, i. e. UPS Output Switches Q1 closed (Pos. I), Manual Bypass Switches Q2 (option) open (Pos. O) and External Battery Switch or Fuses connected (Pos. I).
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting the shutdown procedure.
View of the synoptic diagram, on all UPS units, after pressing the Load Off” key.
All Contactors are open.
Rectifier, Inverter and Static-Switch shutdown.
LED Alarm is lit.
`Home\Commands
COMMANDS
RESET TOTAL OFF
REQUEST TOTAL OFF
V
1. Reset “Load Off” of the Parallel System.
Restore the command “Load Off”, on anyone of the Parallel Units, by entering the screen:
COMMANDS / RESET TOTAL OFF
The Load is supplied by the Utility through the
Automatic Bypass of all Units.
Rectifiers start automatically, blinking LED 3 (Rectifier
ON) indicates Soft-start.
At the end of Rectifier Soft-start, the LED 3 (Rectifier ON)
remains lit.
LED Alarm is lit.
The Synoptic Diagram, on all UPS units, must display the statusLOAD SUPPLIED BY AUTOMATIC BYPASS.
Synoptic Diagram of first unit Synoptic Diagram of other units
Continue
Modifications reserved Page 72/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
2 Insert the Inverter by pressing the Inverter ON ( I ) key on first unit.
Soft-start of Inverter, indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
In case of sufficient output power, the output will transfer to Inverter.
LED Alarm turn Off and the LED Operation must be lit.
Synoptic Diagram of first unit Synoptic Diagram of other units
3. Insert the Inverter by pressing the Inverter ON ( I ) key on all other units.
Do not start the next Inverter until the sequence of the previous ends.
Soft-start of Inverter, indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with
running Inverter will transfer to Inverter.
LED Alarm turn Off and the LED Operation must be lit.
The Synoptic Diagram, on all UPS units, must display the statusLOAD SUPPLIED BY INVERTER”.
Synoptic Diagram of first unit Synoptic Diagram of other units
END OF PROCEDURE
Modifications reserved Page 73/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
7.2.8 Restore to normal operation after EPO (Emergency Power Off)
NOTE !
Make sure the all units of the Parallel System to be status of the activation of EPO, i. e. UPS Output Switches Q1 closed (Pos. I), Manual Bypass Switches Q2 (option) open (Pos. O) and External Battery Switch or Fuses connected (Pos. I).
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled before starting the shutdown procedure.
View of the synoptic diagram, on all UPS units, after activation of EPO (Emergency Power Off) with Utility available.
All Contactors are open.
Rectifier, Inverter and Static-Switch shutdown.
LED Alarm is lit.
1. Reset the EPO (Emergency Power Off) button.
Press the “MUTE” key to reset alarm and acoustical alarm.
LED Alarm remains lit.
2. Press “Inverter OFF” ( O ) key on all Units.
Rectifiers start automatically, blinking LED 3 (Rectifier ON) indicates Soft-start.
At the end of Rectifier Soft-start, the LED 3 (Rectifier ON) remains lit.
After pressing the “Inverter OFF” key on the last unit of the Parallel System, the output of all Units
connect to Automatic Bypass.
The Synoptic Diagram, on all UPS units, must display the statusLOAD SUPPLIED BY AUTOMATIC BYPASS.
Synoptic Diagram of first unit Synoptic Diagram of other units
Continue
Modifications reserved Page 74/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
3 Insert the Inverter by pressing the Inverter ON ( I ) key on first unit.
Soft-start of Inverter, indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
In case of sufficient output power, the output will transfer to Inverter.
Synoptic Diagram of first unit Synoptic Diagram of other units
4. Insert the Inverter by pressing the Inverter ON ( I ) key on all other units.
Do not start the next Inverter until the sequence of the previous ends.
Soft-start of Inverter, indicated with blinking LED 5 (Inverter available).
At the end of Soft-start the LED 5 (Inverter available) remains lit.
As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with
running Inverter will transfer to Inverter.
LED Alarm turn Off and the LED Operation must be lit.
The Synoptic Diagram, on all UPS units, must display the statusLOAD SUPPLIED BY INVERTER”.
Synoptic Diagram of first unit Synoptic Diagram of other units
END OF PROCEDURE
Modifications reserved Page 75/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
8 OPTIONS
8.1 COMMUNICATION OPTIONS
3-ph SNMP/WEB plug-in adapter
SNMP - Simple Network Management Protocol
The 3-ph SNMP/WEB plug-in adapter is an interface to the Ethernet Network, and provides UPS information via the standard SNMP Protocol (UPS-MIB (RFC-1628); GE Single MIB; GE Parallel MIB). The UPS can therefore be managed by a Network Management System (NMS) or by our applications (for instance GE Power Diagnostics, GE Data Protection or GE Service Software), which uses this information to determine the state of the UPS in order to guarantee safe and orderly shutdown of the server, when needed.
GE Power Diagnostics
GE Power Diagnostics is an anytime, anywhere concept in UPS status monitoring and alarm notication that has been successfully implemented in numerous of installations supporting up to multi-hundred UPS. Based on the leading Intelligent Remote Information System IRIS all GE UPS types as well as 3rd party UPS are supported. Accessing the latest site information via Web and being alerted by Email, SMS or Fax, it enables the user to make timely decisions in case of changing critical conditions. With comprehensive data collection and analysis IRIS is not only a remote monitoring & diagnostics (RM&D) system but, the core of the integrated service offering GE Power Diagnostics.
GE Data Protection
GE Data Protection software can communicate with the UPS over RS-232, USB or SNMP to receive status information and measurement values of the UPS.
In case of a critical condition (time on battery, remaining battery autonomy time or low battery) for the load, the software starts a controlled shutdown. An enhanced alarm management system provides the possibility to start applications, send messages, and send e-mails for every upcoming or disappearing alarm.
Mute Test
SGT5000_OPT_RMS_01
Stop
Alarm
g
GE Digital Energy
Remote Signaling Box (RSB)
Equipped with mimic diagram, general alarm, stop operation, alarm reset and lamp.
8.2 OPTIONS IN UPS CABINET
RPA Kit (Redundant Parallel Architecture)
Up to 6 units parallel possible for redundancy or capacity in RPA configuration.
eBoost™ Operation Mode
High efficiency operating mode, where the load is supplied directly by utility and automatically transferred to inverter if the voltage is out of prescribed tolerances.
5
th
harmonic filter
Located inside UPS cabinet.
FCC Filter
Located inside UPS cabinet. Meets FCC Class A, Part 15 Standard for EMI suppression.
Modifications reserved Page 76/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
8.3 CONNECTION FOR OPTIONS
WARNING !
The installation and cabling of the options must be performed by Q U A LIFIED SERVICE PERSONNEL ONLY. Make sure that the UPS installation is completely powered down. Refer to the “Safety prescriptions - Installation” described on Section 1.
8.3.1 Remote Signaling Box (RSB)
The optional Remote Signaling Box allows monitoring of the operation of the UPS, using the potential free contacts fitted on the “P4 - Customer Interface Board“ of the UPS. It can be used by simply putting the box on a desktop or on a wall or, removing the box, it can be surface mounted.
The remote panel contains an internal buzzer and the following status indicators:
Mimic diagram With LEDs indicating the operation of Rectifier and Inverter, and the power source supplying
the critical Load.
Alarm Indicating a critical situation on the UPS (LED light and audible alarm).
Stop Indicating the UPS is preparing to shut down in a short time.
Mute Push button, resets the buzzer.
Test Push button checks all the LEDs and the buzzer of the remote panel.
The cable connecting the RSB to the UPS cabinet must be min. 16 wires / 0.25mm2. The plug B is included in the delivery of the option RSB (cable connecting UPS with RSB not included). Maximal allowable length: 985 ft (300 m). It must be wired at one end with a D - female plug- 25 pin (J2 – P4 Customer Interface Board).
NOTE !
The alarms on free potential contacts can be connected on terminals X1 instead J2 (see correlation X1 – J2 in Section 4.1 of the Installation Guide).
Mute Test
max 985ft / 300m
yellow/brown
white/yellow
1
2
4 3
5
brown/green
7 6
8
10 9
11
white/green
blue/red
violet
grey/pink
13 12
14
16 15
17
yellow
green
brown
20
22
23
19 18
21
white
24
16
COMMON ALLARM
AUX. BUZZER
STOP OPERATION
20 22 23
17 19
38
LOAD ON MAINS
LOAD ON INVERTER
56
55
50
43 44
49
40 42
SIGNALLING
UTILITY FAILURE
GND
24V
34
37
33
32
31
X15
IM6544
1 2
J2 - SUB D - MALE
REMOTE
X3
X4
A
A
B -
P4 - IM0005
B
PLUG
J2
77mm
3
in
130mm
216mm
5 1/4" in
8 1/2" in
25
black
P.S.: The above mentioned colors are
XA TERMINALS BLOCK
TERMINALS
XA
pink
red
blue
grey
pink red
grey blue
SUB D - MALE
suitables only for XY standard cable
S
G
T
5
0
0
0
_
O
P
T
_
0
1
0
-
1
5
0
_
R
M
S
_
0
1
U
S
1
12 13
2
14
3
15
4
16
5
17
6
18
7
19
8
20
9
21
10
22
11
1
14
9
1
21
1
2
3
4
1
2
3
4
J2
XA
BLOCK
BOX
Pink + Red
Grey + Blue
Stop
Alarm
g
GE Digital Energy
Customer Interface
2
1
Fig. 8.3.1-1 Remote Signaling Box connection
A Terminals X3, X4 and X15 fitted inside the Remote Signaling Box. B Plug J2 (sub D - male - 25 pin) must be connected to the connector J2 (sub D - female-25 pin) located
on “P4 - Customer Interface Board“.
XA Terminals block XA for 24Vdc supply Remote Signaling Box.
NOTE !
If the remote signal panel is plugged on connector J2, the terminal blocks X1 cannot be used to drive an external alarms monitoring device, because it is supplied by the internal UPS low voltage power supply.
Modifications reserved Page 77/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
9 MAINTENANCE
WARNING !
All maintenance and service works must be performed by QUALIFIED SERVICE PERSONNEL ONLY.
9.1 MAINTENANCE
A UPS system, like other electrical equipment, needs periodic preventive maintenance.
A regular maintenance check of your installation guarantees higher reliability of your safe critical power supply.
Preventive maintenance work on the UPS can be done only by trained Service technicians.
We therefore recommend you sign a Maintenance and Service contract with GE Global Services @ 1-
800-637-1738
9.1.1 Service check
If the LED Operation blinking during normal operation, the unit has not been serviced for the last 20,000 hours by a GE trained technician.
We highly recommend that you contact your Service Center for preventive maintenance work.
9.1.2 Fans and ventilation
We recommend a periodic cleaning of the ventilation channels and grids on the UPS system, in order to guarantee proper air circulation in the unit and in the Battery.
We recommend replacement of the fans in the units every 20,000 hours.
9.1.3 Other components with limited lifetime
We recommend the periodic replacement of the following components to guarantee higher reliability of the UPS.
Lifetime
Component
Ambient temperature
At 100% load
Up to 77°F (25°C) 50,000 hours
Filter Capacitors DC
Up to 104°F (40°C) 20,000 hours
Filter Capacitors AC
Up to 104°F (40°C) 50,000 hours
Lithium Battery on the “P3 – Control board”
Up to 104°F (40°C) 50,000 hours
Modifications reserved Page 78/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
9.1.4 Battery
We recommend a periodic Manual Battery Test, especially if the Automatic Battery Test is disabled, in order to verify if the Battery can provide the expected backup time in case of Utility Failure.
We recommend this test be performed at least every 3 months, especially if the Battery is not sufficiently discharged during normal operation. The discharge time you use should be at least half of the Battery runtime.
For Automatic Battery Test setting, a special code is required to enter user set-up parameters. The start up technician has access to this code and can program this feature during start up.
Please consider that, if you did a full Battery Test to verify the full runtime of the Battery, the charger needs at least 8 hours to recharge the Battery up to 90% of its capacity.
9.1.5 Long shut-down periods of the UPS-system
To guarantee that the Battery is fully charged, the UPS system should be in operation for at least 12 hours every 3 months.
If not the Battery may be permanently damaged.
9.1.6 UPS room conditions and temperature
The UPS room and the Battery Room have to be maintained clean and free from dust.
A high temperature of the UPS room and of the Battery Room affect the lifetime of several components inside the equipment.
The Battery is very sensitive to room temperatures above 77°F (25°C).
9.1.7 Long shut-down periods of the UPS-system
a) Cleaning, a visual inspection and a mechanical inspection of the UPS modules.
b) Replacement of defective parts or the preventive replacement of parts with a defined lifetime
c) “Updating” of the equipment (technical improvements subsequent to the delivery).
d) Check the calibration of DC voltage and Inverter Output Voltage and Frequency.
e) Check of the settings of the electronic regulation, the control and the alarm circuits of the
Rectifier(s) and Inverter(s).
f) Functional checks on Thyristors, Diodes, Transformers, Filter Components, e.g. to ensure that they
are operating within the specified design parameters.
g) Overall performance test including a Utility Failure simulation with and without the Load.
h) Monitoring Battery operation in discharge and recharge mode including any boost charge duties.
Modifications reserved Page 79/79
OPM_SGS_USM_M40_M50_2US_V010.doc User Manual SG Series 400 & 500 UL S2
10 NOTES
10.1 NOTES FORM
It is recommended to note in this section Notes, with date and short description all the operations performed on the UPS, as: maintenance, components replacement, abnormal situations, etc.
Date Description Done by
Loading...