The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be
reproduced, either in part or in its entirety, without the prior written consent of GE.
The illustrations and plans describing the equipment are intended as general reference only and
are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
We thank you for selecting our products and
are pleased to count you amongst our ver
valued customers at GE.
We trust that the use of the SG Serie
Uninterruptible Power Supply system,
developed and produced to the highes
standards of quality, will give you complete
satisfaction.
Please carefully read the Installation Guide.
It contains all the necessary information
about the installation of the UPS.
GE
Thank you for choosing
START UP AND COMMISSIONING
A GE Global Services Field Engineer must perform start-up and
commissioning of the UPS. Please Contact G.E. Global Services at least two
weeks prior to schedule start-up and commissioning at 1-800-637-1738, or by
E-mail at gedeservices@indsys.ge.com
Congratulations on your choice of a SG Series Uninterruptible Power Supply (UPS).
It will help eliminate Load disturbances due to unexpected power problems.
Manual
This
the switches, the meaning of the system events related to the front panel
indication, and provides procedures for starting and stopping the equipment.
Please refer to the accompanying Installations Guide, which describes how to
prepare the installation site, and it provides weight, dimensions and procedures
for moving, installing and connecting the UPS.
While every care has been taken to ensure the completeness and accuracy of this
manual, GE assumes no responsibility or liability for any losses or damages
resulting from the use of the information contained in this document.
WARNING!
SG Series 10, 20, 30 and 40 kVA, is a product that needs to be installed by a
licensed and knowledgeable contractor.
describes the function of the UPS module, the purpose and location of
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual,
please contact your Service Center before you proceed.
This document shall not be copied or reproduced without the permission of GE.
Some of the information contained in this manual may be changed without notice
to reflect technical improvements.
Safety instructions
Read the safety instructions contained on the following pages carefully before the
installation of the UPS, options and
Pay attention to the rectangular boxes included in the text:
They contain important information and warning concerning electrical connections
and personnel safety.
Battery System
.
Parallel version secured with RPA
When included in the text, this symbol refers to
operation needed only for parallel system.
This manual contains important instructions for models SG Series 50 and 80 kVA that should be
followed during installation and maintenance of the UPS and battery.
- Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
- Check for sufficient floor and elevator loading capacity.
- Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS. Contact the nearest Service Center
immediately.
- WARNING! RISK OF ELECTRICAL SHOCK: Do not remove covers; there are no user serviceable
parts inside.
- All maintenance and service work should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
- The field-wiring terminals may be electrically live, even when the UPS is disconnected from the
utility.
- Dangerous voltages may be present during battery operation.
The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
INSTALLATION
- This UPS must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the UPS, make sure that all earth connections when
reassembling, are correctly reattached
- This UPS is intended for use in a controlled indoor environment free of conductive contaminants
and protected against animals intrusion.
- HIGH GROUND LEAKAGE CURRENT: Ground connection is essential before connecting to AC
input!
- Switching OFF the unit does not isolate the UPS from the utility.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not
exceed 104°F (40°C).
- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25°C).
- It is important that air can move freely around and through the unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C)
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically
(time depending on storage temperature).
GENERAL
STORAGE
BATTERY
to
131°F (55°C).
- The battery-voltage is dangerous for person’s safety.
- When replacing the battery, use the same number, voltage (V) and capacity (Ah).
-
Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
- Never dispose of battery in a fire: They may explode.
- Do not open or mutilate battery: Their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
- Never short circuit battery.
When working with battery, remove watches, rings or other metal objects, and only use
insulated tools.
EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE
UPS BY QUALIFIED SERVICE PERSONNEL.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION AND
REFER TO THE BATTERY MANUFACTURERS INSTALLATION MANUAL
BEFORE HANDLING THE UPS AND BATTERY.
UPS INTENDED TO BE USED WITH A REMOTE BATTERY SUPPLY – ALL MODELS:
“PLEASE REFER TO THE BATTERY MANUFACTURER’S INSTALLATION MANUAL FOR
BATTERY INSTALLATION AND MAINTENANCE INSTRUCTIONS”.
DANGER!
Full voltage and current are always present at the Battery Terminals.
The Battery used in this system can provide dangerous voltages, extremely high currents and a risk of
electric shock.
They may cause severe injury if the terminals are shorted together or to ground.
You must be extremely careful to avoid electric shock and burns caused by contacting Battery Terminals or shorting terminals during battery installation.
Do not touch un-insulated Battery Terminals.
A qualified service person that is familiar with Battery systems and required precautions must install and
service the Battery.
The installation must conform to national and local codes.
Keep unauthorized personnel away from Battery.
The qualified service person must take these precautions:
1 Wear protective clothing, such as rubber gloves and boots and protective eye wear.
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated.
Remove rings and metal wristwatches or other metal objects and jewelry.
Do not carry metal objects in your pockets where the objects can fall into the Battery Cabinet.
2 Tools must have insulated handles and must be insulated so that they will not short Battery
Terminals.
Do not allow a tool to short between individual or separate Battery Terminals or to the cabinet or
rack.
Do not lay tools or metal parts on top of the Battery, and do not lay them where they could fall onto
the Battery or into the cabinet.
3 Install the Battery as shown on the drawing provided with the Battery.
When connecting cables, never allow a cable to short across a Battery’s Terminals, the string of
batteries, or to the cabinet or rack.
4 Align the cables on the Battery Terminals so that the cable lug will not contact any part of the
cabinet or rack, even if the Battery is moved.
Keep the cable away from any sharp metal edges.
5 Install the Battery Cables so the UPS or Battery Cabinet Doors cannot pinch them.
6 Do not connect the Battery Terminal to Ground.
If any Battery Terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded Battery can cause a risk of electric shock.
7 To reduce the risk of fire or electric shock, install the Battery in a temperature and humidity
controlled indoor area, free of contaminants.
8 Battery System Chassis Ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduit, this ground conductor must be routed in the same conduit as the Battery Conductors.
9 Where conductors may be exposed to physical damage, protect the conductors in accordance with
all applicable codes.
10 If you are replacing Battery or repairing Battery Connections, shut OFF the UPS and remove the
Battery Fuses or open the Battery System disconnect.
Safety warnings
The text of this manual contains some warnings to avoid risk to the persons and to avoid damages
to the UPS system and the supplied critical loads.
The non-observance of the warnings reminding hazardous situations could result in human injury
and equipment damages.
Please pay attention to the meaning of the following warnings and symbols.
Throughout this manual the following symbols are defined:
WARNING, if instruction is not followed injury or serious equipment
damage may occur!
CAUTION, internal parts have dangerous voltage present.
Risk of electric shock!
PE (Earth) – GND (Ground)
PROTECTIVE GROUNDING TERMINAL:
A terminal which must be connected to earth ground prior to making any
other connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or
voltage may be applied or supplied.
A terminal to which or from which a direct current or voltage may be
applied or supplied.
This symbol indicated the word “phase”.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.
An Uninterruptible Power Supply (UPS) provides the power for critical loads that need a
reliable, continuous, disturbance free supply.
In case the power provided by the Utility Fails, or exceeds the permitted tolerances, the power
to supply the Load is provided by the Battery for the specified time at the rated Load (or longer
at a reduced Load) or until the Utility power returns.
SG Series is a true double conversion On-line UPS system where the Load is continuously
supplied by the Inverter through the Rectifier.
In case of trouble on the Inverter Output Voltage, or when overload or short-circuit on the
output occur, the Load is instantly transferred to the Utility via the Automatic Bypass.
The UPS automatically returns to normal mode when the failure condition is restored.
Key features
• More Critical equipment supported
Rated at 0.8 Power Factor, SG Series delivers more real power than other UPS in the
market.
With today’s trend toward power factor corrected loads, SG Series can support more total
Load than any other UPS available, allowing you to support a greater number of today’s
enterprise computing Power Factor Corrected (PFC) equipment.
• No single point of failure
Redundant Parallel Architecture (RPA) is an exclusive GE technology.
With RPA, SG Series UPS are controlled in a true peer-to-peer configuration where all
critical elements and functions (including Bypass) are redundant.
SG Series is designed to be the most reliable power protection system available on the
market today.
• High Efficiency
Using IGBT technology and Space Vector Modulation (SVM) strategy, SG Series offers low
output voltage distortion and provides efficiencies up to 93%.
• Fully digital
Digital Signal Processor (DSP), Flash memory and SVM strategy, are the technology
corner stones of new age of power quality and power reliability.
• Extremely flexible
Tailor made power protection to meet your individual installation requirements; SG Series
offers various options like input harmonic filters and our comprehensive JUMP software
suite for mission control and data protection to cover all your application needs.
The SG Series system can be divided into the following main elements:
Fig. 3.1-1 Block diagram
Control System SG Series is designed with microprocessor-controlled signal
processing circuits. The interface between the operator and the unit is provided by the
monitoring system on the front panel.
This monitoring system consists of an active mimic diagram, a keyboard and a backlit
display.
Rectifier The standard Rectifier consists of a 6-pulse SCR-bridge, which
converts the 3-phase Utility Voltage into a controlled and regulated DC-voltage.
This regulated DC-voltage is used to supply power to the Inverter, and to provide charging
power to the Battery.
Inverter
The Inverter converts the DC voltage into a three-phase ACvoltage with constant amplitude and frequency, which is completely independent and isolated
from the AC-input voltage.
Automatic Bypass The Automatic Bypass consists of a static semiconductor-switch
(SSM: Static Switch Module), used to provide an uninterrupted transfer of the Load from
Inverter to Utility.
Back-feed Protection
All SG Series UPS's are equipped with an automatic system for
the protection against voltage back feeding towards Utility, through the Bypass (Applied
Standard IEC 62040-1).
This protection works automatically by opening contactor K6 and K8 (in series with the
thyristors of the static switch) and eventually K7, and acts in case of internal defects of the
system, or due to wrong manipulations on the Manual Bypass Q2.
Manual Bypass The Manual Bypass consists of a pair of manual switches (Q1
and
Load with power directly from the Utility.
, which removes the UPS from the Load for maintenance, while still supplying the
Q2)
Battery The Battery supplies the DC power to the Inverter when the
During normal operation, the Rectifier
converts input AC power to DC.
The DC power provides input power for the
Inverter and charging power for the Battery.
The Inverter converts the DC power to
continuous and regulated AC power, which
supplies the critical load.
The control panel reports the Battery charge
status and the expected backup time with the
actual load.
3.2.2 Utility failure operation
When the Utility is no longer within acceptable
tolerances, the Battery will provide the DC
power to the Inverter.
The Inverter will maintain continuous AC
power to the Load until the Battery Voltage
reaches the lower limit of the Inverter
operation capability.
During the discharge, the LCD screen displays
the estimated time the Battery can support the
critical load.
Prior to the Battery completely discharging,
the "stop operation" alarm (shutdown
imminent) warns the operator that the Battery
is almost discharged and the UPS is about to
shut down.
power to the Inverter and recharging the Battery.
If the Inverter was previously shut down due to low
Battery, the Load will be initially powered by Utility
through the
When the Battery is recharged enough to ensure a
minimum time of operation with the present load,
the Inverter will start automatically and the Load
will be transferred back to the Inverter.
When the AC input power recovers, the Rectifiers will start up sequentially, according to their
number in the parallel system. This minimizes the
The Inverters will start up automatically, but only when the Battery has recharged enough for
a
minimum runtime
When enough Inverters to supply the Load have been restarted, the Load will be transferred
from the Automatic Bypass back to the Inverter output.
In normal operation, the Load is supplied by the
Inverter.
When the control system detects a fault in the
Inverter, an overload condition or a short-circuit
condition, the Automatic Bypass will transfer the
critical Load to the Utility without interruption.
When the Inverter recovers, or the overload or
short-circuit condition is corrected, the Load will be
automatically transferred back to the Inverter.
If the UPS is unable to return to normal mode
following an automatic transfer to Bypass mode, an
alarm condition will be initiated.
A Manual Bypass (operator initiated) will not be
considered as an alarm condition.
In case of parallel operation
Each unit has it’s own internal Bypass. These units are continuously exchanging information,
enabling all of the internal Bypass circuits in a parallel system to operate simultaneously.
If the Inverter of a unit fails, it’s Bypass circuit remains available to the parallel system.
It is excluded only if the unit is separated from the common bus by opening it’s output switch Q1.
3.2.5 Manual Bypass
FIG. 3.2.4-1 BLOCK DIAGRAM AUTOMATIC
BYPASS
The Manual Bypass circuit consists of Q1 and Q2
manual switches, which permits transfer of the
Load directly to the unconditioned AC power
without interruption, leaving the UPS available for
maintenance.
Two or more equal power units can be paralleled to increase the output power (paralleling for
capacity) or to improve the overall reliability of an UPS system (paralleling for redundancy).
The outputs of parallel units are connected to a common power bus, and in normal operation
the units connected on the parallel bus share the Load equally.
The modular concept of SG Series allows parallel operation of
paralleling switchgear, external bypass circuits or common control circuitry (see Fig. 3.3.1-1).
Parallel units for power capacity
Several units can be paralleled in order to achieve output power greater than the maximum
power of a single unit.
The maximum total power shared between the paralleled units is equal to the total installed nominal power.
In the event of a failure of one unit, the power supplied by the UPS system becomes
insufficient and the Load will be transferred to the Utility Bypass source.
Parallel units for redundancy
The nominal power rating of the n+1
or greater than the required
The Load will be equally shared by the n
Should one of the n
the load, maintaining conditioned power to the critical load.
From this results higher reliability and security for the Load plus a higher MTBF (Mean
Time Between Failures).
paralleled units trip Off-line, the remaining (n+1) modules will supply
Load
out of n redundant paralleled modules must be equal to
power.
units connected on the output bus.
up to 8 units
, without using
GE
Fig. 3.3.1-1 Block diagram parallel system operation
The SG Series parallel system is designed to provide a complete
Architecture, and is free from common equipment.
Not only the Inverters are redundant, but also the Bypass functions are designed with
redundant modular concept.
When one UPS needs maintenance or service, the Load is powered by the other units
supplying the Load bus.
The redundant communication bus to which all units are connected keeps each unit informed
about the status of all the other units.
The control panel located on each unit allows controlling and monitoring the status of this
unit.
3.3.3 System control
A
high-speed redundant, serial communication
thus the communication between the CPU's of each unit.
Each module controls it's own function and operational status and communicates with all other
modules, in order to act or react if necessary, adapting it to the new conditions.
bus guarantees the exchange of data and
Redundant Parallel
3.3.4 Synchronization
All units are identical, but one unit is arbitrarily selected as the reference and all the other units
synchronize to this unit, which in turn, synchronizes to the Utility Bypass voltage, as long as
the later is within tolerances.
In case of reference failure, another unit in the parallel system is automatically chosen to take
over the reference role.
The Bypass Input for all the units of the parallel system must be supplied from the same AC
source (no phase shift allowed between them).
3.3.5 Load sharing
On each unit of the parallel system, Inverter Output Voltage and Current are measured and
applied to a Load sharing bus.
An eventual difference between the units is therefore automatically equalized.
It is strongly recommended that no transformers, automatic circuit
breakers or fuses should be inserted between the unit’s output and theLoad common bus bars.
However, it is recommended that a disconnect or isolation switch be
inserted.
A parallel system with a Common Battery for two or more Rectifiers,
requires a particular installation and adequate setting of some
parameters, (accessible only through password), and can therefore
only be done by a qualified engineer from GE.
Usually each Rectifier-Inverter Unit runs with its own Battery.
In case of parallel units are running with a Common Battery (max. 4 UPS - see Fig 4.12-1), the
sharing circuit between individual Rectifier is integrated in the communication bus of the
system in order to assure an equal sharing of the Rectifiers output currents.
1 –
Rectifier
2 –
Inverter
3 –
Automatic Bypass
4 –
Manual Bypass
5 –
Mains Power
GE
6 –
Load Bus Bar
7 –
External Battery Fuse
8 –
Battery
Fig. 3.4-1 Diagram RPA system with Rectifiers on Common Battery
Pay attention to the following recommendations:
• The units delivered for this functioning mode needs a special parameters setting, so they
must be prepared in advance before the installation.
• The installation must be performed only with the UPS system must be completely shut
down.
• The AC Rectifiers input power (5) must be the same, with clockwise phase rotation for each
unit.
• Each Rectifier must be set for the same floating DC voltage and the same Battery current
limitation.
• It is recommended to install the fuses / MCB (7) on each line connecting the Rectifiers to
the common
• In case one must be powered down for maintenance, switch-OFF the concerned unit before
open the DC fuses / MCB on the Battery line (7).
• It is recommended to connect an external NO free contact “Battery Fuses” to the UPS and
to enable the function by setting the parameter (see Section 7.1).
• If an emergency generator set supply the UPS, and the free contact “Generator ON” is
connected to the Customer interface, connect a separate NO free contact on each parallel
unit.
• The parameters enabling the Battery test, both manual and automatic, must be set in the
same mode on all the units having the Rectifiers on Common Battery.
• Do not connect the temperature sensor for automatic battery floating voltage compensation.
• Do not enable the function Boost charge (parameter 87).
The LED remains lighted (with alarm condition still present) and the
alarm
service check
Fig. 5.2.1-1 LED’s on synoptic diagram
Fig. 5.2.1-2 LCD screen
buzzer stops as the key “mute” has been pressed.
LED ON indicates that a regular maintenance service is needed.
May be reset by a service technician only.
(See chapter 10 – Maintenance)
THE LED IS ON ALSO WHEN THE OUTPUT SWITCH Q1 IS OPEN,
INDICATING THAT THE INVERTER IS IN
SUPPLYING THE LOAD.
a) LED ON indicates that the Battery reserve lasts for only 3 more
b) LED ON in case of over temperature or overload >125% together with
All LED’s ON indicate that the Battery is fully charged.
LED a Yellow
LED b, c, d
(EACH ONE INDICATING 25 % OF BATTERY BACKUP)
LED’s ON indicate the Load status of the UPS.
LED d red (≥100 % load)
LED c
LED b green (66% load)
LED a
when one or more alarm is activated. The internal buzzer is
minutes
missing
After the timeout the Inverter will shut down.
(selectable).
Utility
.
(Fixed: indicating last 25 % of Battery backup)
(Blinking: indicating Battery backup ≤ 5%)
Green
yellow (100% load)
green (33% load)
ON
SERVICE MODE, NOT
Definition of the LED’s on mimic diagram
LED 1 = Input Utility Rectifier (green)
LED 2 = Input Utility Bypass (green)
LED 3 = Rectifier ON (green)
LED 4a = Discharging (yellow)
LED 4b = Charging (green)
LED 5 = Inverter ON (green)
LED 6 = Load on Inverter (green)
LED 7 = Load on Utility (green)
LED 8
LED 9 = Manual Bypass (Q2) ON (yellow)
User LCD Interface
Consist of a LCD screen, 4 lines with 20
characters each and six keys. It offers:
The user interface consists of a back lit LCD screen having:
•
4 lines with 20 characters
And
• 6 keys (the function is described for each operating mode).
The operation is extremely simple and is structured on three important main menus related to
the UPS operation, as follows:
meteringA UPS must offer some metering information for the user to be able to
examine the operating status at any time.
alarmsIn the event of Utility failures or abnormal functioning, the UPS must keep a
history of what has happened as a series of events.
parameters The user must be able to program certain functions of the UPS (user
parameters, accessible without password) to his needs.
LCD screen standard version
metering
alarms
parameters
(standard version for Latin characters).
LCD screen
4 rows x
20 characters
+
ok
GE
The 3 buttons existing on the left side of the screen are used to activate the operating
modes, while the buttons on the right side are used to carry out functions inside these
operating modes.
The metering mode is entered any time the metering button is pressed.
While in this mode the LCD will display a series of screens containing metering information.
In this mode the buttons perform the following functions:
metering
alarms Abandons the metering mode and enters the alarms mode.
parameters Abandons the
+ Scrolls forward to the next screen.
– Scrolls backward to the previous screen.
ok Displays the main screen for this mode.
Main screen
This screen displays the current status of the UPS in a condensed form.
The information offered by this screen consists of:
• The type of the machine: Family name, series number (P + unit number for parallel
• The status of the load.
• The Load amount as a percentage of the nominal Load (referred to the most loaded phase).
• The estimated
Battery data screen
This screen displays:
• The Battery voltage.
• The Battery Current (negative values correspond to the discharge of the Battery).
• The temperature of the Battery (XXX indicates sensor disabled).
• The current charge level.
•
Bypass Utility data screen
This screen refers to the AC source supplying the Bypass. This screen displays: