GENERAL DESCRIPTION
The traditional, colonial-design luminaire designated _______
(identify) shall be a GE SALEMTM luminaire, ordering number
_______ (specify TR1C, TR1R or TRCR, plus ordering number
logic from catalog), or equivalent , to operate one _______
(specify [50, 70, 100 or 150(55V)] watt high pressure sodium
[HPS], or 175 watt coated metal halide or [100 or 175] watt
coated mercury [TR1C or TR1R only]) lamp from a nominal
_______ (specify 120, 208, 240, 277, 347 or 480) volt, 60 Hertz
power source and shall be capable of starting and operating
the specified lamp within the limits specified by the lamp manufacturer. The luminaire shall contain a completely prewired integral ballast and an optical assembly that shall provide an IES
Distribution Type _______ (specify MS5, SS4, SS5 [TR1C]; MS2,
MS3, SS3 [TR1R]; or MC2, SC2 [TRCR]) according to photometric
selection table in catalog). The luminaire shall be UL/cUL Listed
SUITABLE FOR WET LOCATIONS when polycarbonate refractor
is used and “U” option is chosen. Standard construction is IP54.
Ballast, housing, optical and luminaire assembly shall all be
from the same manufacturer.
MECHANICAL CONSTRUCTION
The luminaire shall include a die-cast aluminum housing in two
sections and hinged canopy, with stainless steel latch for notool relamping, socket mounted for base-up lamp operation
(TR1C) or horizontal lamp operation (TR1R, TRCR), removable refractor panels (TR1C, TR1R) or permanently fixed flat glass lens
(TRCR) and a prewired terminal board with plug-in type ignitor
(HPS lamps only), ballast (and optional prewired photoelectric
receptacle). Housing shall have a _______ (specify black [standard], dark bronze or gray) paint finish.
BALLAST OPERATION
The luminaire shall contain a standard _______ (specify) ballast*. The terminal board, ballast and plug-in ignitor (HPS lamps
only) shall be prewired to the lamp socket requiring connection
of power supply leads only. The ballast shall be in full compliance with lamp-ballast specifications available to the fixture
manufacturer from the lamp manufacturers at the time of
fixture manufacture.
The ballast shall reliably start and operate the lamp in ambient temperatures down to -20°F for mercury and metal halide
(TR1C, TR1R) and -40°F for HPS.
OPTICAL ASSEMBLY
The optical assembly shall include _______ (specify acrylic,
white polycarbonate resin refractor panels [may be UL1572
Listed SUITABLE FOR WET LOCATIONS and CSA Certified (TR1C,
TR1R only)], or cutoff reflector with clear flat glass [TRCR only]),
and mogul base E39 socket with superior lamp gripping. The
socket shall have added insulation, giving it the ability to handle the higher pulse ratings of newer HID systems. The optical
assembly may include a photoelectric control receptacle.
* REFER TO PRODUCT PAGE FOR BALLAST
SELECTIONS. FOR MORE DEFINITIVE INFORMATION, REFER TO
BALLAST SPECIFICATIONS IN TECHNICAL DATA SECTION.
Guide Form Specifications – 2011
g
GE Lighting Solutions • 1-888-MY-GE-LED • www.gelightingsolutions.com
1 6 9 4 3 5 3 3- - -- 8 8 8
GE Lighting Solutions is a subsidiary of the General Electric Company. Evolve and other trademarks belong to GE Lighting Solutions. The GE brand and logo are trademarks of the General Electric Company.
© 2011 GE Lighting Solutions. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.