GE SecoGear User Manual

24kV-27kV Air Insulation Switchgear
User Manual
Gear
GE
Industrial Solutions
General
Technical Specication
Enclosure design and equipment
Operations and trouble shooting
Inspection and Maintenance
Summary
Standard and Specication
Operating Conditions
Safety and Environment Protection Requirement
Handling and Storage
Installation of Switchgear
Technical specication for SecoGear Table 1
Technical specication for SecoVac VB2 Plus (Circuit breaker) Table 2
Main circuit resistance
of SecoVac VB2 plus Table 3
Technical specication for Earthing switch Table 4
Resistance to internal arc faults (Optional)
Keylock (Optional)
Padlock (Optional)
Typical Modules (Figures 3/1)
Enclosure and Partitioning (Figure 3/2)
Switchgear Structure
Cable Connections
Operations and trouble shooting
Rack Circuit Breaker out from Service Position to Test / Disconnected Position
Circuit Breaker
Earthing Swit
ch Operation
Interlocking of the Switchgear
Debugging of Combined Overcurrent Relay
Summary
Inspection and Maintenance Interval
Diagnosis and Trouble Shooting for Malfunction During Operations
Maintenance Item and Cycle
Routine Inspection
Service
Repairs
Inspection Items
Performance Test
2
7
11
16
21
2
2
3
3
4
6
7
7
7
8
8
8
10
11
11
12
15
16
17
18
18
19
20
21
21
22
22
22
23
24
24
24
Major Repairs and Examples
Spare Parts
Appendix A - Onsite Service Safety Instruction
Inspection and replacement of the main busbar
Inspection and replacement of the xed contact and spout bushing
Inspection and replacement of the shutter mechanism
Replacing the earthing switch
Replacing the current transformer
Inspection and replacement of the surge arrester
Main Busbar
25
32
32
25
26
27
27
29
30
31
SecoGear 24kV-27kV Air Insulation Switchgear
1
Safety rst!
Important Recommendations:
• Switchgear should be installed in a clean, dry, ventilated room.
• Switchgear and/or switchboards should be installed in closed rooms suitable for electrical equipment.
• Installation, operation and maintenance should be carried out by licensed electricians.
• Fully comply with the applicable standards (e.g. IEC), the utility connection requirements and the
applicable safety regulations.
• Observe the relevant instructions in the instruction manual for all actions in relation to switchgear and switchboards.
• Pay attention to the hazard notes in the instruction manual marked with this
warning symbol.
• Make sure that the specied data are not exceeded under switchgear or switchboard operating conditions.
• Keep the instruction manual accessible to all personnel involved in installation, operation and maintenance.
• The users must act responsibly in all matters aecting safety at work and correct handling of the switchgear.
Warning
• Always follow the instruction manual and respect the rules for good engineering practice!
• Hazardous voltage can cause electrical shocks and burns.
• Disconnect power, then earth and short-circuit before proceeding with any work on the equipment.
If you have any further questions about this instruction manual,
our eld team will be pleased to provide the required information.
GE Energy reserve all
rights to this publication. We do not accept
any responsibility for the information provided, which is subject to
alternation.
SecoGear 24kV-27kV Air Insulation Switchgear
2
General
Summary
This publication contains the information required for
installation, commissioning, operation and maintenance
of SecoGear. SecoGear is three-phase, metal enclosed, air-
insulated factory assembled switchgear. SecoGear is type-
tested and suitable for indoor applications up to 27 kV. The
panel is designed with withdrawable modules and is tted with
a single busbar system. The withdra
wable parts are equipped
with circuit breakers, voltage transformers, fuses or current
transformers.
Details of the technical design and conguration of individual
switchgear, such as the technical data, detailed part lists for the
individual panels and comprehensive circuit documentation etc.,
can be found in the relevant order documents.
For correct usage of the switchgear, please read this manua
l
carefully. It is always advisable to use the manual for all
operations regarding installation, commissioning, operation and
maintenance of SecoGear air-insulated switchgear.
These instructions are also used as references for personnel to
carry on regularly maintenance of the switchgear.
Standard and Specication
• SecoGear complies with the standards and specications for factory-assembled, metal enclosed and type tested high voltage
switchgears to IEC publications as given below.
IEC62271-100: 2008 …………… High-voltage alternating current circuit breakers.
IEC62271-200: 2003 …………… AC Metal enclosed switchgear and control gear for rated voltages above
1kV and up to 52kV.
IEC62271-102: 2001 …………… High-voltage alternating current Disconnector and Earthing Switches.
IEC62271
-1: 2007 …………… The common specication for high voltage switchgear and control gear
simple Standards
IEC60529:1989 …………… Degrees of protection as provided by enclosures (IP Code)
The switchgear has the following degrees of protection:
IP 4X applies for the enclosure and IP 2X applies for the partitions.
All other corresponding IEC publications, national or local safe
ty regulations must be followed during the installation and operation of
the switchgear. In addition, any project specic advice from GE must be considered.
SecoGear 24kV-27kV Air Insulation Switchgear
3
Operating Conditions
Normal operating conditions
The switchgear is fundamentally designed for the normal service conditions for indoor switchgear to IEC Publication 62271-1:2007. The
following limitations apply. (If there are others we should detailthe limitations)
• Ambient temperature
- Maximum + 40
- 24h-Medium   +35
- Minimum   -15
• The maximum site altitude is 1000 m above
sea level
• The intensity of earthquake should not exceed level 8
• Humidity
- Highest average value measured over 24 hours
o Relative humidity 95 %
- Highest average value measured over 1 month
o Relative humidity 90 %
Special operating conditions
SecoGear is suitable for operation in the climate of indoor
type according to IEC 62271-200 standard. Special operating
conditions must b
e discussed with the manufacturer in advance.
For example: At site altitudes above 1000 m, the eects of the
reduction in density of air on the dielectric properties must be
taken into account.
Increased ambient temperatures must be compensated for in
the design of the busbar and the branch conductors as well as
the withdrawable parts; otherwise the current carrying capacity
will be reduced. Fitting
additional ventilation facilities can assist
heat dissipation in the switchgear panel.
Note on any special climatic operating conditions
When the switchgear is operated in areas with high humidity
and/or major rapid temperature fluctuations, there is a risk
of condensation. Preventive actions (e.g. applying an electric
heater) must be consulted with the manufacturer to avoid
condensation and any re
sulting corrosion or other adverse
effects. The control of the heaters depends on the particular
project are available.
Safety and Environment Protection Requirement
Safety Procedure
• Wear safety uniform according to electric safety regulations before entering the site
• Comply with industry work procedure. Power supply shall be operated by authorized sta.
Environment protection requirements
The manufacturer has a product recycle policy in accordance
with related law and ISO14001. Local laws shall be observed
when the switchgear is due for recycle.
SecoGear 24kV-27kV Air Insulation Switchgear
4
Handling and Storage
Condition on delivery
Packing
Transport
At the time of dispatch, the factory assembled SecoGear will
have withdrawable parts either securely locked in the service
position or packed separately, depending on the rating of the
equipment, transport mode and destination.
The SecoGear panels are veried in the factory for completeness
as per order requirement, and also passed routine
testing as per
IEC 62271-200.
The busbars are not assembled, they are packed separately with
fasteners and accessories.
Based on the kind of transportation and country of destination,
the packing may vary. To protect against moisture a drying
agent bag is provided. IEC62271-1:2007 guidelines are followed.
• Panels with basic or no packing
• Panels with seaworthy or similar packing (including packing
for containerized shipments)
o Sealed in polyethylene sheeting
o Transport drying agent bags included
o Moisture indicator included
• Observe the directions for use of the drying agent bags. Note
the following
o Drying agent color observed blue indicates the packaged
equipment is dry condition
o Drying agent color observed pink indicates the packaging
contains m
oisture (relative humidity above 40%). Please
contact the manufacturer in this case before installation
The transport units normally comprise of individual panels and,
in exceptional cases, small groups of panels. The panels are
equipped with four (4) lifting eyebolts.
Only carry out loading operations when all precautionary
measures to protect personnel and materials have been taken,
with t
he following equipment:
• Crane of suitable capacity; the minimum capacity shall be 2
tonnes
• Fork-lift truck and/or manual trolley
• Lifting ropes/slings of appropriate load capacity with shackles
• Maintain an angle of at least 60° from the front for the ropes
leading to the crane hook (Figure 1/1)
HANG THE UNITS USING ALL 4 EYEBOLTS!
Figure 1/1: Handling by crane
(1) Lifting eyebolts (qty.4)
SecoGear 24kV-27kV Air Insulation Switchgear
5
Upon Receipt
The responsibilities of the consignee when the switchgear arrives at the site include, but are not limited to, the following:
Check the consignment is complete and without damage (e.g. look for any adverse eect caused by moisture). In case of doubt, the
packing must be opened and then properly resealed with new drying agent bags (when intermediate storage is necessary).
If any quantit
ies are short, or defects or transport damage is noted, these must be;
• Documented on the respective shipping document
• Notied to the relevant carrier or forwarding agent immediately in accordance with the relative liability regulations
Note:
Always take photographs to document any major damage.
Intermediate storage
Intermediate storage should follow the following practices to avoid any negative consequences:
Panels with basic packing or without packing
• A dry well-ventilated storeroom with a climate in accordance
with IEC62271-1:2007
• Store the panels upright
• Do not stack panels
Panels with basic packing;
• Open the packing, at least partially
Panels without packing;
• Loosely covered with polythene
• Ensure that there is sucient air circulation
Check regularly for any condensation during s
torage.
Panels with seaworthy or similar packing with internal protective
covers
• Store the transport units
a. Protected from the weather
b. In a dry place
c. Safe from any damage
• Check the packing for damage
• Check the drying agent;
d. On arrival of the consignment
e. Subsequently at regular intervals
When the maximum storage period (starting from the date of packing) has been exceeded
• The protective
function of the packing can no longer be guaranteed
• Take suitable action if intermediate storage needs to be continued
Warning
Do not walk on the top of the panels (due to rupture points in pressure
relief devices) ! The pressure relief devices can be damaged!
SecoGear 24kV-27kV Air Insulation Switchgear
6
Installation of Switchgear
In order to obtain an optimum installation sequence and ensure
high quality standards, site installation of the switchgear should
only be carried out by specially trained, or at least by supervised
personnel and monitored by responsible persons.
On commencement of installation on site, the switch-room
must be fundamentally nished, provided with lighting and the
electri
city supply, lockable, dry and with facilities for ventilation.
It is also required that the basic frame and indoor ground
for the switchgear should be checked and accepted before
the construction. It must be ensure that the ceiling height is
sucient for the opening travel of the pressure relief plates.
Tolerances for laying the oor frame are:
Evenness tolerance: ± 1mm within a measuring length o
f 1m.
Straightness tolerance: 1mm per 1m, but not more than 3mm
over entire length of frame.
Cross section view of switchgear room layout (plan view)
Switch room cable duct arrangement (Side elevation)
Detail of switchgear cable access cutout
Width Dimension
A 800 1000 B 600 800 C 595 692
290 800800
140
800 1900
70
1800
30
130
250
2400
Power Cable Duct 800*1000
3~5mm above ground
+5.0m
Figured steel plate (t=5mm)
Top Curface of basic frame
Strap of control cable duct
Control Cable Duct 250*250
Basic Frame
1200
300
A
190 130
1800
358
1700
B
4-15x20
54
Power Cable
Control Cable
144
600
1800
30
1800
70
800
Power Cable Duct
Basic Frame
150
1700
800/1000
800
1800
30
1800
70
800
Power Cable Duct
Basic Frame
150
1700
800/1000
Connection betweenSwitchgears
In order to connect the different switchgears together, here
use bolts of M8×35 to connect the panels together, the torque
requirement for the bolts is 26 N∙m, the connection points on the
switchgear is shown below.
Connection Points betweenSwitchgears
SecoGear 24kV-27kV Air Insulation Switchgear
7
Technical Specication
Technical specication for SecoGear -Table 1
Rated voltage kV 24 27
Rated power frequency withstand voltage kV 50 65
Rated lightning impulse withstand voltage kVp 125 125
Rated frequency Hz 50/60
Rated current A 1250/2500
Rated short time withstand current(3s) kA 31.5
Rated peak withstand current1) kAp 82
Resistance u
110 ( 1600A)
85 ( 2000A)
IP level for weather protection
Enclosure IP4X
Between compartment IP2X
Technical specication for SecoVac VB2 Plus (Circuit breaker) -Table 2
Main circuit resistance of SecoVac VB2 plus -Table 3
Rated voltage kV 24 27
Rated power frequency withstand voltage kV 50 65
Rated lightning impulse withstand voltage kVp 125 125
Rated frequency Hz 50/60
Rated current A 1250/2500
Rated short-circuit breaking current: kA 31.5s
Percentage of DC component Up to 52%
Rated short-circuit closing current kAp 82
Rated short time withstand current kA 31.5
Rated peak value withstand current kAp 82
Rated duration time for short
-circuit s 3
Opening Time ms 20 50
Closing Time ms 30 70
Rated auxiliary control voltage V 24*/30*/36/48/60/110/220 V DC 110/220 V AC
Operation sequence: O-0.3s-CO-15s-CO/ O-0.3s-CO-180s-CO
Mechanical life operations: Times 10000 (M 2)
Electrical Endurance Class E2
Single Capacitor Switching current A 400
*Consult with GE
Item Unit Value
Rated current A 1250 2500
Withdrawable µ
45 25
SecoGear 24kV-27kV Air Insulation Switchgear
8
Technical specication for Earthing switch -Table 4
S/N Specication Unit Data
1 Rated voltage kV 24/27
2 Rated Work frequency withstand voltage (1min) in open condition of switch kV 65
3 Rated Lighting impulse withstand voltage (peak value) in open condition of switch kVp 125
4 Rated short-time withstand current (3s) kA 31.5
5 Rated peak value withstand current kAp 82
6 Rated short circuit making current kAp 82
7 Centre distance between phases mm 220/255
8 Electric endurance Clas
s E1
9 Mechanical endurance Times 2000
Resistance to internal arc faults
Arc release
All three primary compartments of SecoGear switchgear are
provided with pressure relief aps, which will automatically open
and guide the pressurized gas to the rear side direction if an
internal arc fault occurs in an aected compartment
The pressure relief protects damage to switchgear components
and the risk of injury t
o personnel, which may endanger an
operator or extend the arc fault eect to the entire switchgear
lineup. The relief ap is xed by 3-M8 steel bolts and the other
side is xed by plastic M6 screw, The M6 screw will be broken
and ap will open along weakness area( No bend area and part
with oblong holes) when pressure increase quick by internal arc
31.5kA/1s
Keylock (Optional)
The use of key interlocks is to realizing the interlocking logics between units of switchgear, Also the functional truck can be locked in
the racked-out position and the relevant lock key can only be removed with the functional truck in disconnect position. The earthing
switch closing and opening operations can be locked by means of keys. The latter can only be removed with the e
arthing switch in an
opposed position to the lock to be made.
SecoGear 24kV-27kV Air Insulation Switchgear
9
Description of the interlock system Key Condition
Functional truck racking-in lock
Key will be free when the truck in the disconnect position Key will be trapped when the truck in the rack-in position
Earthing switch closing lock
Key will be free when the Earthing switch is open Key will trapped when the earthing switch in closed position
Earthing switch opening lock
Key will be free when the Earthing swi
tch closed
Key will trapped when the earthing switch in open position
Figure : Functional truck racking-in lock
Figure 2/5: Earthing switch in open position
Figure 2/6: Earthing switch in close position
Key lock is locked, key is free, Truck indisconnect position
Key lock can't be locked when truck in rack in position, and key is trapped
When earthing switch in open position, earthing switch can be locked by closing lock, the key of closing lock can be free. And openi
ng
lock can't be locked, the key of opening lock is trapped.
When earthing switch in close position, earthing switch can be locked by opening lock, the key of opening lock can be free. And closing
lock cant be locked, the key of closing lock is trapped.
SecoGear 24kV-27kV Air Insulation Switchgear
10
Padlock (Optional)
Padlock for Circuit breaker racking-in/out operation
Padlock for Circuit breaker racking-in/out operation will limit the access to insert crank lever to racking-in/out Circuit breaker. Racking-
in/out operation can be done only when lock cover is in the open position.
Figure 2/9: Padlock for Circuit breaker racking-in/out operation
Padlock for earthing switch operation
Padlock for earthing switch operation will limit the access to inserting the operation lever to operate earthing switch. Open/close
button can be operated only when the lock cover is in the open position.
Figure 2/8: Padlock for earthing switch operation
SecoGear 24kV-27kV Air Insulation Switchgear
11
Enclosure design and equipment
Typical modules (Figures 3/1)
With withdrawable type SecoVac VB2 Plus Vacuum
Circuit Breaker installed, SecoGear panels are used for
incoming or outgoing feeder. Each unit consists of three
high voltage compartments; Main bus bar, Circuit breaker,
Cable compartment and one Low voltage compartment for
instruments and auxiliary circuits.
For busbar sectionalizing, two
panels are necessary, the
coupling panel with the withdrawable circuit breaker part and
a bus riser panel (available with busbar metering and earthing).
In equipment without busbar sectionalizing, a direct bar
connection between the individual panels will be provided.
Figure 3/1: Typical modules
Enclosure and partitioning
High quality 2mm thick Alu-Zinc steel sheets is used for the
external enclosur
e and internal partitions. Pressure relief
aps are provided on the top of the panel for all high voltage
compartments. In case of overpressure due to internal arc
inside any of the compartments, these pressure relief aps are
designed to open quickly to release the pressure. The pressure-
relief aps are secured with steel screws on one side and
with plastic screws on the other side. In the case o
f internal
overpressure, the plastic screws are the point of rupture caused
by arc conditions. The top mounted pressure relief aps on the
enclosure are made from mesh metal.
All compartments are accessible from the front, with their
own independent doors. The front doors can be opened up to
an angle of 130° and they are arc resistant. An inspection
window made of security glass is provided on circ
uit breaker
compartment door. The panel design provides an air gap
between two adjacent panels after panels are joined together.
• Figures of the panel (Refer to gure 3/2), the oor of the cable
compartment is fitted with removable non-magnetic metal
(13).
• The rear wall of the busbar compartment (3), intermediate
wall (14), mounting plate with shutters (16) and horizontal
partition (20) form pa
rt of the internal partitioning.
• The earthed internal partitioning ensures safe access to the
circuit breaker and cable compartment (C) even when the
busbars are energized.
• The low voltage compartment (D) is fully protected from the
high voltage area with the earthed steel-sheet casing.
• On the end sides of the switchgear, end cover plates are
provided for consistent appearance, as well as mecha
nical
and thermal strength in case of internal arc fault in the end
panel.
• Doors, rea r walls and cover pla tes are treat ed aga inst
corrosion and then coated with high quality paint. The doors
for circuit breaker and cable compartment are arc resistant
with a mechanical interlock.
SecoGear 24kV-27kV Air Insulation Switchgear
12
Switchgear structure
Figure 3/2: Typical feeder panel
A. Main bus compartment
B. Breaker compartment
C. Cable compartment
D. Low voltage compartment
1. Pressure relief plate
2. Enclosure
3. Cover of main busbar compartment (can be removed)
4. Branch busbar
5. Main busbar
6. Primary disconnect spouse
7. Primary disconnect
8. Current transformer
9. Earthing switch
10. Rear door interlock
11. Bottom plate
12. Pa
rtition between breaker compartment and busbar
compartment
13. Terminal block
14. Control plug
15. Shutter
16. Vacuum circuit breaker
17. Drive screw
18. Earthing switch operation mechanism
19. Control wire duct
20. Main earthing busbar
Figure 3/3: Incoming/feeder panel(1250/2500A) Figure 3/4: Incoming With x VT panel (1250/2500A)
22
40
17
1
2
3
4
5
6 7
8
9
10
11
12
13
14
15
16
17 18
19
20
A
B
D
C
P30
P32
SCALE 1,000
10
SecoGear 24kV-27kV Air Insulation Switchgear
13
Figure 3/5: Busbar tie panel(1250/2500A) Figure 3/6: Riser panel(1250/2500A)
Figure 3/7: Measuring panel(1250/2500A) Figure 3/8: VT Panel (2500A)
P28
SCALE 1,000
10
A
B C
P29
A
B C
SCALE 1,000
P30
10
95.5
76
JSZV17-15R
15
P31
95.5
76
JSZV17-15R
15
P32
SecoGear 24kV-27kV Air Insulation Switchgear
14
Figure 3/9: Incoming with ES & VT panel (1250/2500A) Figure 3/10: Riser with ES panel (1250/2500)
Figure 3/11: CPT panel (2500A)
Figure 3/12: Typical dimensions and Weights of SecoGear (including withdrawable circuit-breaker parts)
Description
Dimension in
mm
27kV
Height A 2400
Width
Rated current of branch 1250A 31.5kA
B
800
VT
Rated current of branch 2500A 31.5kA 1000
Depth C 1800
Rated current Weight
A Kg
1250 800-1000
2500 1000-1200
P30
P31
P32
SecoGear 24kV-27kV Air Insulation Switchgear
15
Cable Connections
The cable compartment contains current transformers, voltage transformers (xed or withdrawable), and earthing switch, depending
on the individual operating requirements.
The cable compartment is constructed for installation of three current transformers. When all the three current transformers are not
required, dummies can be installed in their place to maintain the same instal
lation and connection procedures.
The xed or withdrawable voltage transformers are connected with busbar on the primary side and tted with HRC fuses. The earthing
switch can be operated manually, with position indication by mechanical indicator on the driveshaft and auxiliary switch. Three
lightning arrestors (optional) can be mounted in the space available.
Cable connection:
Rated voltage Panel width Max. number of parallel cables Max. cross section of cables Range of cable clamp Range of reducer ring
(kV) (mm ) per Phase (mm
2
) (mm) (mm)
27
800 6
630 35-54 27-62
1000 6
Figure 3/13: Cable compartment layout
NO. Parts Description
1 Cable clamp
2 Main earthing bar
3 Cable connection bar
4 Earthing Switch
1
2
3
4
This cover has been interlocked with the earthing switch and can be opened only when the earthing switch is in closed position Earthing switch can be opened only when rear cover is closed
SecoGear 24kV-27kV Air Insulation Switchgear
16
Operations and trouble shooting
Operations and trouble shooting
Before start up, the following work should be completed:
a. Check the overall condition of the switchgear and clear any
potential risk factor.
b. Check the switchtruckisolated contactor and insulating
parts etc. by visual inspection.
c. Chec k the co nnect ion betwe en e arthi ng b us b ar a nd
earthing conductor of the transformer substation out
side the
compartment is secure.
d. Remove all of the remaining materials, unnecessary objects
and tools inside of the compartment.
e. Wipe the compartment body and the insulation parts with
a soft cloth that should be clean and dry. Then wipe o any
remaining dust and grease.
f. Clean the surface of earthing busbar. The earthing loop
resistance should be less than 350 micro-ohms.
g. Re-install the cov
er removed during the period of installation,
wiring and commissioning.
Warning
a. Comply with all relevant safety regulations
b. Maintain circuit breakers in disconnection position
c. Remove earth wires and short wires of the hazardous areas
d. Pay attention to any abnormal situations
Use of hand tools
1) Gear door lock key
drawing no: 5GD.253.008
2) Rack handle for truck
drawing no: Y-002
FIG 20 : Hand Tools
h. Remove the shipping cap on the pole of the circuit breaker.
i. When
testing the power frequency withstand voltage of main
circuit, pay particular attention to sensors, cables and other
equipment during the test process.
Attention
Read the product manual carefully when testing
the VT withstand voltage; use a test voltage of appropriate
frequency to avoid core saturation.
j. Place the Circuit Breaker on auxiliary control power.
k. Perform the operation test of the ci
rcuit breaker by manual or
electric control; observe the corresponding position indicator.
l. Check the interlocking validity, both mechanical and electrical.
m.Conductive paste can be applied on the circuit breaker
primary contacts.
3) Earthin g swit ch operation handle
drawing no: 5GD.253.144
SecoGear 24kV-27kV Air Insulation Switchgear
17
Rack Circuit Breaker out from service position to test / disconnected position
Move circuit breaker truck from transfer truck into the switchgear
a. Check the fixed primary contact and apply an adequate
amo unt o f co nductive pa s t e . Check the i n t erlocki ng
mechanism and apply lubricant on the moving parts to ensure
smooth operation.
b. Place the Circuit Breaker on transfer truck and put in lock
posi
tion. (See gure 4/1).
VCB l o c k e d on
the transfer truck
Figure 4/1: VCB truck on the transfer truck
Figure 4/2: Transfer truck lock
with switchgear
Figure 4/3: Lock VCB in
switchgear
Warning
The trolley has four (4) nuts for adjusting the platform, to
the same level of the breaker compartment.
c. Move the transfer truck to the front of the switchgear, turn
the adjusting nut to adjust the height of the transfer truck
platform, (See gure 4/2). Aim the guiding pin at the guiding
jack in front of the switchgear, push and make the transfer
truck engage with the switchgear by using the lock
key. At
the same time, insert the front guide rail of the transfer truck
into the bottom guide rail groove of the switchgear truck. (See
gure 4/3).
d. Push the two sliding cranks inward under the truck to remove
the locked position with the transfer truck, and then push the
truck forward to make it enter the switchgear compartment
and lock it in the disconnect / test position. (See gure 4/4).
e.
Operate the lock key releasing lever of the transfer truck to
Figure 4/4: Lock VCB in switchgear
remove the locked relation between the transfer truck and the
switchgear, and then remove the transfer truck.
SecoGear 24kV-27kV Air Insulation Switchgear
18
Move the truck from disconnect / test position to service position
a. Make sure the front and back door of the switchgear are
closed. Make sure the earthing switch is in the open position,
the circuit breaker compartment is clear and without any
unexpected object.
b. Insert the secondary plug of the truck into the socket on the
topside of the switchgear truck compartment and put into the
lock pos
ition. (See gure 4/5 & 4/6)
Figure 4/5: Take o secondary
plug from truck
Figure 4/6: Put the secondary
plug into switchgear socket
Figure 4/7: Rack in the breaker
to work position
c. Make sure the circuit breaker is in the open position.
d. Insert the racking crank of the truck into the rectangular
cranking hole of the screw mechanism of the truck through
the operation hole under the door of the circuit breaker
compartment. (
See gure 4/7).
e. Turn the crank clockwise (approximately 20 turns) until it can't
be moved any more, listen for a strong cranking sound when
the breaker changes into the operating position.
f. The position indicator on the door of the low voltage
compartment shows the breaker is in service position.
g. Take o the racking crank. The racking operation is now
complete.
Warning
The truck is not allowed to be placed in any intermediate
position between disconnect/test position and operating
position.
Move the Circuit Breaker from service position to test position
Move the Circuit Breaker from switchgear compartment to transfer truck.
Perform the operating steps for moving the Circuit Breaker truck
from transfer truck into the switchgear in reverse order.
a. Make sure the cir
cuit breaker is in open position.
b. Perform the operating steps for moving the Circuit Breaker
into operation position in reverse order.
Circuit breaker
Earthing switch operation
For operating instructions refer to the Circuit Breaker instruction
manual.
The earthing switch has a rapid close-open mechanism, which
is independent to the rotation speed of the earth switch drive
shaft.
The closing brake
function can be quickly applied through
the rapid close-brake mechanism. The earthing switch, circuit
breaker truck and rear cover behind the panel have a closedown
device to prevent incorrect operation.
The earthing switch can be operated only when the truck is in
disconnect / test position and the rear cover of the switchgear is
in the closed position.
The operating hole of the earthing switch lo
cated in the lower
position of the right side in front of the panel. (See gure 4/8).
SecoGear 24kV-27kV Air Insulation Switchgear
19
Figure 4/8: Earthing switch operation warning
Close the earthing switch
Open the earthing switch
• Check that the voltage presence indication on the low voltage
compartment is o.
• Check other electrical interlock, if applicable, to allow the
operation.
• (See gure 4/9) Lower the operating hole shutter and insert
the operating handle, and turn the handle 180° clockwise to
close the earthing switch.
Figure 4/9: Close earth switch Figure 4/10: Open earthing switch
• Ensure the earthing switch is fully closed.
Warning
Warning
Check the position indicator on low voltage compartment
door
Check the ag adjacent to the earthing switch operating
hole
Make sure the cable compartment is clear and without
any unexpected objects
Make sure the cable compartment door is closed
completely
• Insert the earthing switch operating handle, and turn the
handle 180° counterclockwise to open the switch (See gure
4/10)
• Check the mechanical
ly interlocked label and indication light
to ensure the earthing switch is fully open
Interlocking of the switchgear
• The circuit breaker can be closed only when fully engaged in
the test or service position
• The control plug can be released when the circuit breaker is in
test or disconnected position. The secondary plug is latched
when the circuit is in service position (see gure 4/11)
Figure 4/11: Secondary plug latch
• Front Break is released only when operating lever is inserted;
and operating lever cannot be inserted when undercarriage is
in test position
• Undercarriage Interlock is released only when undercarriage
is in test position
• Undercarriage and ES interlock insures undercarriage can be
in service position only when ES is OFF
• Back Break insures ES can be switched on
ly when back door
is closed
• Back Door Interlock is released only when ES is ON
The earthing switch has been interlocked with the rear cover of cable compartment and can be opened only when the cover is closed. If found the operation of earthing switch become hard, do not apply the excessive force. This can cause damage to the parts. Ensure the cover is properly secured and then operate the earthing switch. Contact the manufacturer, if the problem still exist.
SecoGear 24kV-27kV Air Insulation Switchgear
20
Fig 4/12 Earthing switch interlock with rear cover
Fig 4/14: Earthing switch interlock VCB truck and Rear door
Fig 4/13 Breaker interlock with undercarriage
Interlock with Rear door
Interlock with VCB
undercarriage door
Padlock cover for ES operation
1. Operation Lever Insert Socket
2. Front Break
3. Undercarriage Position Interlock
4. Undercarriage and ES Interlock
5. Front Operation shaft
6. Back Break
7. Back Interlock Shaft
8. Back Door Interlock
SEQUENCE OF EARTHING SWITCH OPERATION
Closing the earthing switch:
Press the handle slide downwards; insert earthing switch operation handle
and turn the handle 180 degree clockwise to close the earthing switch,
Opening the earthing switch:
Press the handle flap downward, insert earthing switch operation handle
and turn the handle 180 degree counter clockwise to open earthing switch.
The ap will
be in lower position when earthingn switch is open
SecoGear 24kV-27kV Air Insulation Switchgear
21
Inspection and maintenance
Summary
After the process of installation and testing, the switchgear
is available to use. Timely and proper maintenance can keep
the switchgear trouble-free and can prolong the life of the
switchgear as long as possible.
The maintenance work must be carried out by certied persons
who are familiar with the related operations of the switchgear
and understand relevant IE
C and other local safety rules and
important guides established by other technical departments
as well. Allow a GE representative to assist when the switchgear
and its components need to be repaired. Users should think
about the operating environment and the operation frequency
when developing maintenance rules. Usually the inspection of
some equipment / components (such as wearable parts) and
the
maintenance intervals (maintenance period) depend on
the running time, operating frequency and the number of short
circuit cycles. The maintenance period of other parts depends on
the working situation, the degree of the load and environmental
impact (including pollution and corrosive gasses).
Inspection and maintenance interval
The maintenance interval determined by operating conditions of
the swi
tchgear depends on the operating mode, the operating
number of rated current and short circuit current, environment
temperature and pollution.
The recommending maintenance interval is showed in the
following table:
maintenance content interval(years) according to the operation
cycle of circuit breaker
inspection 2~3
1)
5000
3)
care and maintenance 2~3
2)
1) Recommended shorter interval years when operated in very
severe running conditions.
2) According to inspection results.
3) Refer to the VCB manual.
SecoGear 24kV-27kV Air Insulation Switchgear
22
Diagnosis and trouble shooting for malfunction during operations
Malfunction Reason Resolution
The circuit breaker can not be racked into service position from test position
1. The handles on the withdrawable frame is not in position.
2. The circuit breaker is closed
3. The earthing switch is closed
4. The circuit breaker is electrically interlocked (electromagnetic Y0 locked)
5. Shutter is not completely open
1. Adjust the frame and handles
2. Open the circuit breake
r
3. Open the earthing switch
4. Unlock /Check electromagnetic Y0
5. Check shutter drive mechanism
The circuit breaker can not be racked out to test position from service position
1. The circuit breaker is closed
2. The circuit breaker is electrically interlocked (electromagnetic Y0 locked)
1. Open the circuit breaker
2. Unlock /Check electromagnetic Y0
Can not lower the shutter on the earthing switch operating hole
1. The circuit breaker is not in test / disconnected position
2. The earth switch is electrically interlocked
1. Rack the circuit breaker out to test position or disconnected position
2. Unlock / Check electromagnet
Operating hole shutter can not rise back after the earthing switch is opened
Drive shaft of earthing switch has not reached intended position
Turn the crank anticlockwise
to the limit where the mechanical OPEN indication stays exactly below the operating hole
The cable compartment door can not be closed / opened
The earthing switch is not completely opened
Open the earthing switch
The circuit breaker can not be closed
1. No auxiliary power supply
2. The control plug is not inserted
3. The circuit breaker is not engaged in test / service position
4. The closing spring has
not been charged
5. The electrical interlocking in position
6. Closing release not working
1. Turn on auxiliary power supply
2. Insert and lock control plug
3. Fully engage the circuit breaker to test /service position
4. Charge the closing spring
5. Check power supply for interlocking
6. Check power supply for closing release
The circuit breaker can not be opened
1. No auxiliary power supply
2. Opening
release not working
1. Turn on auxiliary power supply
2. Check power supply for opening release
Maintenance item and cycle
Maintenance of the switchgear should be carried out by
trained personnel, who are familiar with the switchgear
characteristics, in accordance to the manufacturer's
instructions and IEC standards.
Safety measure: Routine inspection is to ensure smooth
operation of the switchgear. It does not require power
shutdown, but requires care to prevent incorrect
operations.
It is recommended any major repairs
(if required) shall be
assisted by the manufacturer or a qualied representative.
The purpose for routine inspection is to nd issues in advance so
they can be resolved immediately.
Routine Inspection
SecoGear 24kV-27kV Air Insulation Switchgear
23
Routine inspection includes:
• Check compartment doors are closed properly
• Verify the control voltage, auxiliary voltage and battery
voltage are in normal condition
• The status indication and position indication for the circuit
breaker and earthing switch etc are normal
• Check ammeter and voltmeter on the display
• Check relay indications. (The power indication should be on
and fault indication
should be o.)
• Check alarm and pre alarm indications
• Partial discharge should not occur on the surfaces of
equipment at operating voltage. This can, for example, be
detected by characteristic noises, a clearly perceptible smell
of ozone, or visible glowing in the dark;
• Check the heater condition, if installed. The relay monitoring
the heater current is in the low voltage compartment. Check
th
e heater circuit if the red current indication turn o due to
the heater losing power supply. (see gure 5/1)
Heater current indication
Figure 5/1: Heater current monitoring relay
If any abnormal condition is found, then the cause must be
identied in order to restore normal condition.
Service
Safety measure: The power must be shutdown before
scheduled switchgear service, and the work area
must be isolated. Measures must be taken to disallow
the power being switched on. Ensure proper earthing
and padlocks in place. Specially trained personnel are
required to supervise.
It is recommeded to inspect the circuit breaker every 6
months if in stand-by for a signicant period of time.
The purpo
se for the service is to guarantee the operation quality
of the switchgear and avoid any possible malfunctions. This
increases the life of the switchgear. The scope of work is as
follows:
• Inspection: Determination of the actual condition
• Servicing: Measures to preserve the specied condition
• Repair: Measures to restore the specied condition
The service interval for the switchgear depends on ext
ernal
factors including the operating environment, the operation
frequency and service age etc.
It is recommended to have switchgear serviced every 2-3 years, if installed in good environment and not frequently operated.
It is recommended to have switchgear serviced every year, if operated more than 10 times a month.
It is recommended to have switchgear serviced every half year, if installed in adve
rse environment
and frequently operated.
It is recommended to have the circuit breaker replaced, if reached its mechanicall operating cycles or rated short circuit breaking times.
SecoGear 24kV-27kV Air Insulation Switchgear
24
Repairs
Immediate repairs are required in case of following situation emerges:
• Deteriorated insulation, discharges, ashover and breakdown
• Damaged component in the switchgear
• Any other abnormal observation which may aect safety
Inspection Items
• Check all the compartments and internal components for
dampness, rust and dirt.
• Check the tightening torques of the busbar bolted connections
on select
ed samples.
• Remove the pressure aps on the busbar compartment and
remove the insulation shield (See g 5/2). Check the torque is
86 N-m using a torque wrench.
Insulation shield (for side panel)
Insulation shield (Middle panel)
Figure 5/2: Main busbar shield(Need to be replaced)
• Check the fixed contact including its profile for any sign of
sparking or wear-and-tear.
• Chec k th e sh u t ter mechanis m i
n t h e ci r cuit breake r
compartment.
• Check the interlocking between the circuit breaker and the
earthing switch.
• Check the bolted connection betwe en the power cable
connectors and lugs.
• Check earthing switch operation.
• Check the interlocking between the earthing switch and the
cable compartment door.
• Check the interlocking between the circuit breaker and the
breaker compartment door.
• Check liv
e voltage indications.
• Check the heater (If installed).
Performance test
Performance test is to validate the electrical performance of the switchgear. It is recommended to be carried out together with the
scheduled service.
Performance test includes:
• Close and open the circuit break for ve times, and check the circuit
• Check all the interlocking mechanism
• Electrical test including power frequency
withstand test, CT/VT ratio and the contact resistance for the circuit break
• Verify mechanical characteristics of the circuit break
SecoGear 24kV-27kV Air Insulation Switchgear
25
Major Repairs and examples
Be sure to comply with the applicable safety
regulations when carrying out repairs.
Verify the switchgear is de-energized and the safety
measures are in place.
Pay attention to the direction of the tapered washers
and the bolted connection torque should reach 86 N-m.
• Open the main busbar compartment and check the tightening
torques for the busbar bolted connections
• Check the main busbar and branch
busbar for any dampness
or rust.
• Check all the sidewalls for any dampness or rust.
• Check the main busbar compartment for any unexpected
object.
• Restore the insulation shield and the pressure ap on the top
of the panel.
• Check the tness of the xed contact and the surface
condition.
• Open the cable compartment and check the cable connection
as wells as the connectors for color distortion.
• Ch
eck the sealing condition of through holes for the primary
and secondary cables.
• Check the heater condition.
• Check the breaker and cable compartment for unexpected
objects.
• Check the secondary connections of the CTs.
• Check the current terminals in the low voltage compartment
for the close loop of the secondary current circuit. Check
the protection relay, ammeter, energy meter, etc. on the CT
s
econdary are in service.
Inspection and replacement of the main busbar
Unexpected objects in the busbar compartment, or a loose
bolted connection, may result heated joint or even phase fault.
The procedure to change the main busbar is as follow;
• Remove the rear covers on the busbar compartment, as well
as the same on the adjacent panels. Now the busbar is visible.
(see gure 6/1)
Figure 6/1: Busba
r after opening the rear cover
• Remove the pressure ap on the busbar compartment
• Remove the busbar insulation shield
• Remove the connection bolt on the main bar and branch
busbar
• Remove the busbar from the busbar compartment
• Install the new main busbar and fasten the joints
• Cover the busbar joints with insulation shield
• Reassemble the pressure aps and rear cover panels for the
busbar compa
rtment
SecoGear 24kV-27kV Air Insulation Switchgear
26
Verify the switchgear is de-energized and the safety
measures are in place.
Don't fasten the bolt initially when locking the xed
contact, Please fasten by applying torque when the
upper branch and main busbar, lower branch and the
current transformer are xed;
Inspection and replacement of the xed contact and spout bushing
It is normal to nd the xed contact surface oxidized due to
current ow an
d environmental factors during period of service.
However if the surface becomes rusty due to wet or corrosive
conditions, the xed contact must be replaced. The spout
bushing may be replaced depending of its condition.
Clean the contact with a cotton-free paper, and apply some
pure alcohol if necessary. Brush small amount of contact
lubrication grease (DE-G51 for example) on the surface after
wipi
ng. It is important to check any abnormal condition such as
the burning marks on the spout bushing, which may be caused
by the epoxy.
• Check and replace the xed contact
• Withdraw the circuit break . Open the shutter mechanism, and
insert two M8 bolts into the overlapping holes on the shafts
(See gure 6/2). Then the xed contact along with the spout
bushing are visible.
Figure 6/2 : shutter mechanism
• Inspect the contacts. Replace the contact if the silver coating
on copper is worn, or the surface is corroded, damaged or
over heated.
• Remove the bolts on the xed contact, and replace the xed
contact (see gure 6/3)
• Replace the spout bushing
• Remove the bolt at the joint of the upper branch and main
busbar
• Remove the bolt at the joint of the lower branch busba
r and
the current transformer
• Remove the center bolt of the xed contact and then remove
the vertical connections
Figure 6/3: Fixed contact and spout bushings
• Remove four xing screws (M12) of the spout and then the
spout can be removed (see gure 6/3)
• Replace the new spout bushing and fasten the xing screws
(M12). Inject glass glue in the clearance between the spout
bushing and the mounting m
etal frame
• Insert the upper and lower branch busbar into the spout
bushing, and x the xed contact
Attention:
The torque will be dierent based on dierent sizes of
the bolt and with/without lubrication. Corresponding torques of
dierent bolts identied below:
Silver plating xed contact
Front Rear
Fixing screws
SecoGear 24kV-27kV Air Insulation Switchgear
27
Recommend torque (N-m)
Bolt size Without lubrication (oil) With lubrication (oil)
M8 26 10
M10 50 20
M12 86 40
M16 200 80
M20 300 120
• Tighten the bolt on the upper branch and main busbar. Ensure that applied torque is 86 N-m
• Tighten the bolt of the lower branch busbar and the current transformer. Ensure applied torque is 86 N-m
• Remove the inserted bolts on the driving mechanism of the shutter, and then put down
the shutters
Inspection and replacement of the shutter mechanism
Replacing the earthing switch
In case of distortion or deformation, the driving mechanism of
the shutter shall be replaced.
The steps as follows:
• Remove the split pins of the driving mechanism of the shutters
and connection bar (see gure 6/5)
• Screw o the bolt which is used to x driving mechanism (see
gure 6/4)
The replacing of th
e earthing switch includes changing the
earthing switch along with labels for ON and OFF position, the
driving mechanism including driving gear assembly and drive
rod.
The steps for replacement are as follows.
Figure 6/4: Driving mechanism of the shutter
• Remove the 5 screws on the earthing bar, then remove the
earthing bar.
• Replace the 4 screws on the side plate of the shutter
mechanism, then remo
ve the side plate.
• Remove the 6 screws which used to x the shutter
mechanism, replace with the new parts of shutter mechanism.
• Now replacement can be done with the above instructions
following the previous instructions in reverse order.
• Rack out the circuit breaker
• Remove the compartment separating plate
• Remove the cover plate on the right side in the cable
compartment
Ensure switchgear is in Power OFF position and turn
the earthing switch to the ON position.
Remove 6 xing screws
which used to x the
ES on the side sheet
Remove 4 xing screws
Remove 6 xing screws
• Loosen the fastening screws on the drive rod, but do not
remove completely.
Split pins
Bolt
Earthing bar
SecoGear 24kV-27kV Air Insulation Switchgear
28
Both the screws can be accessed only when the
earthing switch is in OPEN position
Attention: Don't fully remove the drive rod, otherwise all
the parts will fall out.
Attention: Replace the bevel gear assembly and
earthing switch in the same way. Use care to avoid
damage as the main body is much heavier.
• Open the padlock on the operating hole of the earthing switch
• Draw out the drive rod forward,
then the parts of the drive rod
in the switchgear can be removed from backwards now.
• Completely draw out the drive rod from another side at a
slight angle.
• Loosen the 4 xing screws on the xing bracket (see gure
6/6), and then remove drive rod of the rear door interlock from
rear door, then draw out the drive rod backward.
• Unscrew both of the bolts on the bevel gear (See gure 6/7).
Fixed screw of the bevel gear
Flexible connection of the earthing switch and earthing busbar
Figure 6/7: Fixing screw of bevel gear
Figure 6/8: Flexible cable between earthing Switch and earthing
busbar
• Unscrew the exible connections between the earthing switch and common earthing busbar (see gure 6/8)
• Remove the xing screw of the earthing switch, and then push the bevel gear and the main body of the earthing switch (See gure
6/9)
• Now replacement can be done with the above instruc
tions following the previous instructions in reverse order.
Remove 6 fixing
screws o f the
earthing switch
Figure 6/9: Fixing screw of the earthing switch
SecoGear 24kV-27kV Air Insulation Switchgear
29
Replacing the current transformer
Replace the current transformer if the assembled current
transformer cannot meet the function due to a change in the
load conditions. The steps are as follows:
Conrm the equipment be powered o and make sure
to follow proper safety measures.
Conrm the earthing switch is in OPEN position.
Ensure the marking on the mounting plate for the
installing position of the current transformer before
removing the four bolts to avoid the wrong position
with the hole of the copper connections after installing
the new current transformer;
Attention: The weight is heavy
because of the current
transformer installed in the mounting plate. It is
necessary to hold the mounting plate of the current
transformer to avoid the damage for the equipment
and personnel if the mounting plate drops down after
loosening the bolt.
• Remove the back cover of the enclosure
• Remove the connection bolt between the current transformer
and the vertical copper connections (See gure 6/1
0)
• Remove the secondary wires of the current transformer
• Remove the 6 pcs of M8 bolts on the mounting plate of the
current transformer
Figure 6/11: Mounting plate of the current transformer
• Support the mounting plate of the current transformer and
then put on the ground
• Remove the four bolts which are used to x the current
transformer, and remove the current transformer
• Replace the current tr
ansformer with new one and screw on
with the four bolts
• Assemble the current transformer in its place on mounting
plate and tighten the mounting plate by tightening the 10 pcs
of M8 bolts
• Screw on the bolts on the current transformer and the both
side copper connections
• Fix the bolt of the xed contact of the earthing switch, but do
not fully tighten.
• Adjust the position of the xed contact a
fter switching the
earthing switch in ON Position and then fasten
• OPEN the earthing switch
• Fasten the bolts on the copper connections and the current
transformer mounting with a torque wrench at a torque of 86
N-m
• Fix the insulation shield, and make sure it is in a vertical
position
• Connect the secondary connection of the CT and cover it
according to the requirements
• Assemble the back cover
and compartment separating plate
of switchgear
Copper
connections
Figure 6/10: Connection busbar between current transformer
and earthing switch
3 pcs of M8 bolts on each side
SecoGear 24kV-27kV Air Insulation Switchgear
30
Inspection and replacement of the surge arrester
Inspection and replacement of potential indicator
It is necessary to replace the surge arrester based on big
dierence between reference voltage and the test data recorded
on site during the maintenance and recording. The steps are as
follows:
Mounting bracket and earthing bar for arrester
Figure 6/12: Installing surge arrester
• Remove the cable between the arrester and copper
connection (See gure 6/12)
• Remove the xed bolts on both sides of the mounting bracket
of the arrester
• Push the three arresters and the bracket
• Remove the xed bolts on the mounting bracket of the
arrester
Figure 6/13: Surge arrester mounting plate
• Install the new arrester and fasten the bolts with the mounting
bracket
• Screw both side bolts on the brackets
• Fix the connection between the arrester and copper
connection
If the display "Lock" on the potential indicator is ashing, and
an abnormal sound from the relay is continuously heard, there
may be two reasons that can cause this problem. First, t
here
may be a problem with the potential indicator contact. Second,
the display itself may have a fault despite three-phase power
condition.
Both of these situations demand to replace the display. The
steps are as follows:
Lock indicator
Test push button
Three phase c harged display
Figure 6/14: Potential indicator
There are two types potential indicators. One is with latching
contact, and another is without the latching contact. The
replacement of the two types are the same. (See gure 6/14)
• Cut o the auxiliary power of potential indicator (if any)
• Disconnect all the connection from the back of the indicator
• Remove the lock of the potential indicator, and then push it
ou
t (See gure 6/15)
• Replace with the new one, and x the lock
• Reconnect the wires at back
• Recover the auxiliary power
Lock to fix of the potential indicator
All connection on the jointing row
Figure 6/15: Removing and installing for the potential indicator
SecoGear 24kV-27kV Air Insulation Switchgear
31
Main Busbar
Rule and Note:
Every 3~4 panels use one Main Busbar. The maximum length of Main Busbar should be less than 4m.
Below is a table indicating Busbar sizing;
Rated current Busbar type Cross section (copper)
Main Busbar & Branch Busbar (Rectangle)
1250A
Branch 50x8x2
Main 80x10x1
2500A
Branch 120x8x2
Main 120x8x2
Connection mode of Main Busbar / Branch Busbar
Connection mode of Main Busbar and Grading ring
• Main Busbar and Branch Busbar
1. Main busbar
2. Wall bushing
3. Support pad
4. Main Busbar & Branch Busbar
joint insulation boot
In order to better protect the
wall bushing, it is necessary to
add a grading ring in the wall bushing to balance the voltage
between the wall bushing and main busbar. So the grading ring
and the main busbar should be connected before doing the
routine tests and installation of the Switchgear in the field. As
the grading ring is casted into the wall bushing, the wall bushing
and the main busbar should be connected by conductor.
Here, choose connect the bushing and the main busbar on
the outward side of the switchgear for convenience of the
connection. (See Figure 6/16 )
Wall Bushing
Grading Ring
Conductor
Main Busbar
Figure 6/16: Grading Ring and Connecting conductor
Before the connection of grading ring and main busbar, make
sure the through threaded ho le (M5) on the centerline of
main busbar which close the conductor have already tapped
according to the length of the conductor. The length between
the two hole's center of the conductor is 200mm. The distance
between
the center of threaded hole and the outer surface of
the wall bushing is 150mm ( See Figure 6/17).
150
Figure 6/17:Position of the threaded hole
5. Branch busbar
6. Insulation Cover
7. Support insulator
8. Spout
1
2
3
4
5
6
7
8
SecoGear 24kV-27kV Air Insulation Switchgear
32
Spare parts
Please refer to recommended spare parts list below. Other spare parts are also available based on customer's requirement.
S/N Name Unit Comments
1 Heater Piece
2 Key for door lock Piece
3 Earthing switch operating handle Piece
4 27KV Service Truck T800 Set
5 27KV Service Truck T1000 Set
Appendix A - Onsite service safety instruction
Before operating the equipment, please check and make sure to
follow all safety requirement.
If for any reason the work is interrupted, please make sure site
safety procedure is followed when restarting the
work.
• Before operating, please check site layout, both inside
and outside of the electrical operating area, earthing line
layout, ON or OFF condition of the control power, state of
the temporary power, and if any personnel is present and all
safety/emergency exits are clear.
• Ensure if safety procedures on working sheet are well
implemented, recheck if the safety procedures comply with
requiremen
ts, if isolation procedure between live equipment
and test equipment is established, and there are clear
instructions on the product labels.
The connection sequence as follows:
Conrm the equipment be powered o and make sure to
follow proper safety measures.
• One side of conductor is connected with wall bushing
by using one screw(M5X8) and a at washer, required
torque is 5Nm.
• Another side of connecting conductor is connected
with main busbar by using another screw(M5X10) and
a at washer, required torque is 5Nm.
• Replacement can be d
one with the above instructions
following the previous instructions in reverse order.
• Once equipment is in power o phase, it is strictly forbidden
to operate the circuit breaker or switch. Please switch OFF
circuit breaker and move VCB to test or withdrawn position.
Instrument and power transformer to power of the equipment
shall be switched o in order to avoid any unintended
charging of the eq
uipment.
• Please conrm the switchgear reference data and series
number to avoid working on the wrong equipment.
• All current transformer and voltage transformer secondary
winding shall only have one permanent and reliable protective
earthing.
• If it is necessary that personnel must service the switchgear,
please make sure to contact GE or that site personnel is
properly trained and are capable of
following proper safety
measures.
Cut off the heat-shrinkable tube (the surface side which close
the conductor) with the area of 30x30mm around the threaded
hole (See Figure 6/16).
Figure 6/17
Threaded Hole (M5)
Japan
11F, Akasaka Park Bldg.,5-2-20, Akasaka, Minato-ku Tokyo 107-6111 T : +81 3 3588 5288 F : +81 3 3585 3010
North Asia
Korea
22, Daewangpangyo-ro 712 beon-gil, Bundang-gu, Seongnam-si, Gyeonggi-do, 463-400, Korea T: +82-31-620-6000 F: +82-31-620-7070
Malaysia
Level 6, 1 Sentral, Jalan Travers, Kuala Lumpur Sentral Kuala Lumpur, Malaysia 50470 T : +603 2273 9788 F : +603 2273 7988
Thailand
25th floor, CRC Tower, All Seasons Place, 87/2 Wireless Road, Lumpini, Pathumwan, Bangkok 10330 T : +66 2 648 0240 F : +66 2 648 0200
Indonesia
BRI II Tower, 27th floor, Jl. Jend. Sudirman No. 44-46 Jakarta 10210 T: +62 21 573 0430 F: +62 21 574 7089
Singapore
240 Tanjong Pagar Road, #06-00 GE Tower Singapore 088540 T : +65 6326 3718 F : +65 6326 3015
Philippines
8F Net Cube Building, 30th Street, Corner 3rd Avenue, Crescent West Park, Global City Taguig 1634 T : +63 2 877 7000 F : +63 2 846 0629
Vietnam
Saigon Centre, Unit 1, Floor 7, Le Loi Boulevard, District 1 HoChiMinh City T : +84 8 3914 6700 F : +84 8 3827 8229
South East Asia
Australia
125-127 Long Street, Smithfield, Sydney, NSW 2164 T : +61 2 8788 6911 F : +61 2 8788 7224
Australia & New Zealand
New Zealand
Level 1, 8 Tangihua Street, Auckland, North Island T : +64 9 353 6706 F : +64 9 353 6707
India
Polt No. 42/1 & 45/14, Electronic City-Phase II Bangalore-560100 T: (080) 41434000 F: (080) 41434199
India
Shanghai
4F, Building 2, CTP, No.1 Hua Tuo Rd. Zhang Jiang Hi-Tech Park, Shanghai, China 201203 T : +86 21 3877 7888 F : +86 21 3877 7600
Taiwan
6F, No. 8, Min Sheng E. Rd., Sec. 3, Taipei 10480 T : +886 2 2183 7000 F : +886 2 2516 6829
Greater China
Spain
P.I. Clot del Tufau, s/n, E-08295 Sant Vicenç de Castellet T: +34 900 993 625
Belgium
Nieuwevaart 51, B-9000 Gent T: +32 (0)9 265 21 11
Finland
Kuortaneenkatu 2, FI-00510 Helsinki T: +358 (0)10 394 3760
France
Paris Nord 2, 13, rue de la Perdrix F-95958 Roissy CDG Cédex T: +33 (0)800 912 816
Poland
Ul. Odrowaza 15, 03-310 Warszawa T: +48 22 519 76 00 and Ul. Leszczyńska 6, Bielsko-Biała 43-300 T: +48 33 828 62 33
Europe & Middle East
Italy
Centro Direzionale Colleoni Via Paracelso 16, Palazzo Andromeda B1 I-20864 Agrate Brianza (MB) T: +39 039 637 3701
Netherlands
Parallelweg 10, Nl-7482 CA Haaksbergen T: +31 (0)53 573 03 03
Germany
Robert-Bosch Str. 2a, 50354 Hürth-Efferen T: +49 (0) 2233/ 9719-0
Portugal
Rua Camilo Castelo Branco, 805, Apartado 2770 4401-601 Vila Nova de Gaia T: +351 22 374 60 00
Hungary
Vaci ut 81-83. H-1139 Budapest T: +36 1 447 6050
Russia
27/8, Electrozavodskaya street, Moscow, 107023 T: +7 495 937 11 11
South Africa
Unit 4, 130 Gazelle Avenue, Corporate Park Midrand 1685 P.O. Box 76672 Wendywood 2144 T: +27 11 238 3000
United Arab Emirates
Injaz Building, 3rd Floor Dubai Internet City, PO Box 11549, Dubai T: +971 4 4546912
United Kingdom
2 The Arena, Downshire Way Bracknell, Berkshire RG12 1PU T: +44 (0) 800 587 1239
Latin America
790 N.W. 107th Avenue, Suite 200, Miami, Fl 33172 USA T: +1 305 551 5155
Chile
Vespucio Norte, Avenida Presidente Eduardo Frei Montalva 6001, Edificio N° 66 Comuna: Conchalí, Sector el Cortijo, Santiago T: (56 2) 928-4700
Latin America
Brazil
Av. María Coelho Aguiar, 215, Bloco C - 6.Andar Jd.São Luiz, 05804-900, São Paulo T: +55 11 36141900
Mexico
Av. Churubusco 3900 Nte, Col. Industrial Benito Juárez Monterrey, N.L. 64517 T: (01-800) 800-1968
USA
41 Woodford Avenue, Plainville CT, USA 06062 and 12305 Kurland Drive, Houston, TX USA 77034 T: +1 800-431-7867
North America
Shanghai GE Guangdian Co., Ltd
No.3, Lane 123, East Huancheng Rd, Fengxian District, Shanghai, China 201401 T : +86 21 6710 1888 F : +86 21 6710 1901
Printing Code: GE/PV2/MU/2013/01
Loading...