GE SCA2001F Specification

SCA2001F – Above-the-Cooktop Advantium™ Oven
TM
R
66" MIN.
Mounting
height from
floor
30"
MIN.
width
required
Exhaust outlet
connects to
3-1/4" X 10" duct
16-13/32
(Rear)
15-1/4
16
29-7/8
12"
MIN.
30 amp
Disconnect Switch
NEMA 14-30R
Wall Receptacle
Dimensional Information (in inches)
IMPORTANT: PLEASE READ CAREFULLY. FOR PERSONAL SAFETY, THIS APPLIANCE MUST BE PROPERLY GROUNDED TO AVOID SEVERE OR FATAL SHOCK.
Note: Outside venting is optional. Vent (duct) can be horizontal or vertical.
Specification Revised 7/04
240434
Insure proper ground exists before use.
Listed by Underwriters Laboratories
For answers to your Monogram,® GE Profile™ or GE appliance questions, visit our website at GEAppliances.com or call GE Answer Center
®
service, 800.626.2000.
DO NOT, UNDER ANY CIRCUMSTANCES, CUT, DEFORM, OR REMOVE ANY OF THE PRONGS FROM THE POWER CORD. DO NOT USE WITH AN EXTENSION CORD.
NEMA 14-30R Wall Receptacle
SCA2001F – Above-the-Cooktop Advantium™ Oven
TM
R
Hood Exhaust Duct
Outside ventilation requires a HOOD EXHAUST DUCT. Read the following carefully.
EXHAUST CONNECTION:
The hood exhaust has been designed to mate with a standard 3-1/4" x 10" rectangular duct.
If a round duct is required, a rectangular-to-round transition adaptor must be used. Do not use less than a 6" diameter duct.
REAR EXHAUST:
If a rear or horizontal exhaust is to be used, care should be taken to align exhaust with the space between studs, or wall should be prepared at the time it is constructed by leaving enough space between the wall studs to accommodate exhaust.
Filter Kit Accessory
Filter Kit
JX81A–Recirculating Charcoal Filter Kit
To be used when the Advantium oven
Grille
cannot be vented to the outside.
MAXIMUM DUCT LENGTH:
For satisfactory air movement, the total duct length of 3-1/4" x 10" rectangular or 6" diameter round duct should not exceed 140 equivalent feet.
ELBOWS, TRANSITIONS, WALL AND ROOF CAPS, etc., present additional resistance to airflow and are equivalent to a section of straight duct which is longer than their actual physical size. When calculating the total duct length, add the equivalent length of all transitions and adaptors plus the length of all straight duct sections. The chart below shows the approximate feet of equivalent length of some typical ducts.
Duct
Rectangular-To-round
A.
Equivalent Feet
5 ft.
Transition Adaptor
Wall Cap 40 ft.
B.
90° Elbow 10 ft.
C.
45° Elbow 5 ft.
D.
90° Elbow 25 ft.
E.
45° Elbow 5 ft.
F.
Roof Cap 24 ft.
G.
Specification Revised 7/04
240434
Listed by Underwriters Laboratories
For answers to your Monogram,® GE Profile™ or GE appliance questions, visit our website at GEAppliances.com or call GE Answer Center
®
service, 800.626.2000.