Note to Installer - Be sure to leave these instructions with the
customer.
Note to Customer - Keep these instructions with your Use
and Care Book for future reference.
Before the old dryer is removed from service or discarded,
remove the dryer door.
Service information and the wiring diagram are located in the
control console.
-SBSD137H
-SBSD107H
WARNING!
FOR YOUR SAFETY:
Use only rigid metal or flexible metal 4-in. diameter
ductwork for exhausting to the outdoors. Never use plastic
or other combustible, easy-to-puncture ductwork.
This appliance must be properly grounded and installed as
described in these instructions.
Do not install or store appliance in an area where it will be
exposed to water and/or weather.
Install the dryer where the temperature is above 10°
C (50°F) for satisfactory operation of the dryer control
system.
This dryer must be exhausted to the outdoors.
Inspect the dryer exhaust outlet and straighten the outlet
walls if they are bent.
Do not allow children on or in the appliance. Close
supervision of children is necessary when the appliance is
used near children.
NOTE: Installation and service of this dryer requires basic
mechanical and electrical skills. It is your responsibility
to contact a qualified installer to make the electrical
connections.
Step 1 Prepare the area and exhaust for installation of
new dryer (see section 1).
Step 2 Check and ensure the existing external exhaust is
clean (see section 1) and meets attached installation specifications (see section 3).
Step 3 Remove the foam shipping pads (see section 1).
Step 4 Move the dryer to the desired location.
Step 5 Connect the power supply (see section 2).
Step 6 Connect the external exhaust (see section 4).
Step 7 Level your dryer (see section 5).
1O cm (4 in.) DIA.
METAL DUCT (RECOMMENDED)
1O cm (4 in.) DIA. FLEXIBLE METAL
DUCT (IF NEEDED)
MATERIALS YOU
WILL NEED
1O cm (4 in.) DUCT
CLAMPS (2)
OR
10 cm (4 in.) SPRING
CLAMPS (2)
Step 8 Check the operation of the power supply and
venting.
Step 9 Place the owners Use and Care in a location
where it will be noticed by the owner.
For alcove or closet installation, see section 6.
For bathroom or bedroom installation, see section 7.
For mobile or manufactured home see, section 8.
For side or bottom exhaust, see section 9.
1O cm (4 in.)
METAL ELBOW
DUCT TAPE
EXHAUST
HOOD
GLOVES
SAFETY GLASSES
Consumer Support
6
Electric Dryer
www.GEAppliances.ca
Minimum Clearance Other Than Alcove or Closet Installation
Minimum clearance to combustible surfaces and for air opening are: 0 cm (0 in.) clearance both sides and 2.5 cm (1 in.) rear.
Consideration must be given to provide adequate clearance for installation and service.
12
PREPARING FOR INSTALLATION
OF NEW DRYER
ELECTRICAL CONNECTION
INFORMATION
Safety Instructions
EXTERNAL
DUCT
OPENING
DUCT TAPE OR
DUCT CLAMP
10 cm (4 in.)
METAL DUCT
VENT
PROTECTION
BRACKET
TIP: Install your dryer before installing your washer.
This will allow better access when installing dryer exhaust.
DISCONTINUITY
ON DUCT
DUCT TAPE OR
DUCT CLAMP
Pull the vent protection bracket
out until it stops, and let it rest on
the floor. The bracket prevents
the unit from moving too close
to the wall and crushing the
rear vent. Prolong by adding a
DASHED FLEXIBLE duct.
REMOVING LINT FROM WALL EXHAUST
OPENING & FOAM REMOVAL FROM
DRYER LEGS
WALL
WARNING - TO REDUCE THE RISK
OF FIRE, ELECTRICAL SHOCK AND
PERSONAL INJURY:
DO NOT USE AN EXTENSION CORD OR AND
ADAPTER PLUG WITH THIS APPLIANCE.
Dryer must be electrically grounded in accordance
with local codes and ordinances. Installation must be
in accordance with the current CSA C22.1 Canadian
Electrical code part 1. Improper connection of the
equipment-grounding conductor can result in an electric
shock. Check with a qualified electrician or service
representative or personnel if you are in doubt as to
whether the appliance is properly grounded.
Do not modify the plug provided with the appliance: if it
will not fit the outlet, have a proper outlet installed by a
qualified electrician.
ELECTRICAL REQUIREMENTS
This dryer must be connected to an individual branch
circuit, protected by the required time-delay fuses or
circuit breakers. The power supply must be of 120/240
volts, 60 Hz circuit with the wall receptacle as shown
below:
Installation Instructions
Operating Instructions
Troubleshooting Tips
INTERNAL DUCT
OPENING
CHECK THAT EXHAUST HOOD
DAMPER OPENS AND CLOSES
FREELY.
Tilt the dryer sideways
and remove the foam
shipping pads by
pulling at the sides
and breaking them
away from the dryer
legs. Be sure to
remove all of the
foam pieces around
the legs.
TYPICAL 30 AMP
RECEPTACLE FOR DRYER
The power supply must be protected with 30 Amp fuses or
breakers. It must be well grounded and conform to local
codes.
GROUNDING INSTRUCTIONS
This appliance must be grounded. In the event of malfunction
or breakdown, grounding will reduce the risk of electrical
shock by providing a path of least resistance for electrical
current. This appliance is equipped with a cord having an
equipment-grounding conductor and a grounding plug.
The plug must be plugged into an appropriate outlet that is
properly installed and grounded in accordance with all local
codes and ordinances.
Consumer Support
7
Electric Dryer
34
EXHAUST INFORMATION
WARNING - USE ONLY METAL 10 cm (4”)
DUCT. DO NOT USE DUCT LONGER THAN
SPECIFIED IN THE EXHAUST LENGTH TABLE.
Using exhaust longer than specified length will:
Safety Instructions
• Increase the drying times and the energy cost.
• Reduce the dryer life.
• Accumulate lint, creating a potential fire hazard.
The correct exhaust installation is YOUR RESPONSIBILITY.
Problems due to incorrect installation are not covered by
the warranty.
The MAXIMUM ALLOWABLE length of the exhaust system
depends upon the type of duct, number of turns, the type of
exhaust hood (wall cap), and all conditions noted below. Both
rigid and flexible metal duct are shown in the table below.
EXHAUST CONNECTION
WARNING - TO REDUCE THE RISK
OF FIRE OR PERSONAL INJURY:
This dryer must be exhausted to the outdoors.
• Use only metal duct.
• Do not terminate exhaust in a chimney, any gas
vent, under an enclosed floor (crawl space), or into
an attic. The accumulated lint could create a fire
hazard.
• Provide an access for inspection and cleaning of
the exhaust system, especially at turns. Inspect and
clean at least once a year.
• Never terminate the exhaust into a common duct
with a kitchen exhaust. A combination of lint and
grease could create a fire hazard.
• Do not obstruct incoming or exhausted air.
THIS DRYER COMES READY FOR REAR
EXHAUSTING. IF SPACE IS LIMITED, USE THE
INSTRUCTIONS IN SECTION 9 TO EXHAUST
DIRECTLY FROM THE SIDES OR BOTTOM OF
THE CABINET.
If using flexible metal duct, please refer to page 10.
• Terminate in a manner to prevent back drafts or entry of birds or other
wildlife.
• Termination should present minimal resistance to the exhaust air flow
and should require little or no maintenance to prevent clogging.
• Never install a screen in or over the exhaust duct. This could cause lint
build up, thus creating a fire hazard.
• Wall caps must be installed at least 30 cm (12 in.) above ground level or
any other obstruction with the opening pointed down.
• If roof vents or louvered plenums are used, they must be equivalent to
a 10 cm (4 in. ) dampened wall cap in regard to resistance to air flow,
prevention of back drafts, and maintenance required to prevent clogging.
SEPARATION OF TURNS
For best performance, separate all turns by at least 1.2 m (4 ft.) of straight
duct, including distance between last turn and exhaust hood.
TURNS OTHER THAN 90º
• One turn of 45º or less may be ignored.
• Two 45º turns should be treated as one 90º turn.
• Each turn over 45º should be treated as one 90º turn.
SEALING OF JOINTS
• All joints should be tight to avoid leaks. The male end of each section of
duct must point away from the dryer.
• Do not assemble the ductwork with fasteners that extend into the duct.
They will serve as a collection point for lint.
• Duct joints should be made air and moisture-tight by wrapping the
overlapped joints with duct tape.
• Horizontal runs should slope down toward the outdoors 1.2cm (1/2 in.) /ft.
INSULATION
Duct work that runs through an unheated area or is near air conditioning
should be insulated to reduce condensation and lint build-up.
Consumer Support
8
STANDARD REAR EXHAUST
(Vented at floor level)
For straight
line installation,
connect the dryer
exhaust to the
external exhaust
hood using duct
tape or clamp.
NOTE: WE STRONGLY RECOMMEND SOLID METAL EXHAUST
DUCTING. HOWEVER, IF FLEXIBLE DUCTING IS USED IT MUST BE
METAL NOT PLASTIC.
CUT THE METAL EXHAUST DUCT
(NOT SUPPLIED) TO THE PROPER
LENGTH.
Electric Dryer
STANDARD REAR EXHAUST
(Vented above floor level)
ELBOW HIGHLY
RECOMMENDED
Safety Instructions
www.GEAppliances.ca
ELBOW HIGHLY
RECOMMENDED
Installation Instructions
RECOMMENDED
CONFIGURATION
TO MINIMIZE
EXHAUST
BLOCKAGE.
NOTE: ELBOWS WILL PREVENT DUCT KINKING
AND COLLAPSING.
5
LEVELING AND STABILIZING YOUR
DRYER
Stand the dryer upright near the final location and
adjust the 4 leveling legs, at the corners, to ensure that
the dryer is level from side to side and front to rear.
LEVEL
FRONT-TO-BACK
LEVEL
SIDE-TO-SIDE
Operating Instructions
Troubleshooting Tips
4 LEVELING
LEGS
Consumer Support
9
Electric Dryer
USING FLEXIBLE METAL DUCTSEXHAUSTING
If rigid all-metal duct cannot be used, then flexible all-metal
ducting can be used, but it will reduce the maximum
recommended duct length. In special installations when it is
impossible to use only metal ducting, then UL-listed clothes dryer
Safety Instructions
flexible metal transition duct may be used as transition venting
between the dryer and wall connection only. The use of this
ducting will affect dry time.
If flexible transition duct is necessary, the following directions
must be followed.
• Use the shortest length possible.
• Stretch the duct to its maximum length to avoid kinks.
• Do not crush or collapse the duct.
• Extend vent protection bracket as described in step 1.
• Never use transition duct inside the wall or inside the
dryer on page 2.
• Avoid resting the duct on sharp objects.
• Venting must conform to local building codes.
A CLOTHES DRYER PRODUCES COMBUSTIBLE LINT. FOR
ALL INSTALLATIONS, THE DRYER MUST BE CONNECTED
TO AN EXHAUST TO THE OUTDOORS.
NOTE: MOBILE HOME, BEDROOM, BATHROOM, ALCOVE
OR CLOSET INSTALLATIONS MUST BE EXHAUSTED TO
THE OUTDOORS.
6
ALCOVE OR CLOSET INSTALLATION
• If your dryer is approved for installation in an alcove or closet,
it will be stated on a label on the dryer back.
• The dryer MUST be vented to the outdoors. See the EXHAUST
INFORMATION sections 3 & 4.
• Minimum clearance between dryer cabinet and adjacent walls
or other surfaces is:
0 in. either side
7.6 cm (3 in.) front and rear
• Minimum vertical space from floor to overhead cabinets,
ceiling, etc. is 109 cm (43 in.) without pedestal, 140 cm (55 in.)
with pedestal.
• Closet doors must be louvered or otherwise ventilated and
must contain a minimum of 387 sq. cm (60 sq. in.) of open area
equally distributed. If the closet contains both a washer and
a dryer, doors must contain a minimum of 774 sq. cm (120 sq.
in.) of open area equally distributed.
NOTE: WHEN THE EXHAUST DUCT IS LOCATED AT THE
REAR OF THE DRYER, MINIMUM CLEARANCE FROM THE
WALL IS 14 cm (5.5 IN.)
• The dryer MUST be vented to the outdoors. See EXHAUST
INFORMATION section 3 & 4.
• The installation must conform with local codes or, in the
absence of local codes, with the current CSA C22.1 Canadian
Electrical code part 1.
8
MOBILE OR MANUFACTURED HOME
INSTALLATION
• Installation must conform to the current CAN/CSA Z240 MH
series Mobile Home Installation Codes.
• The dryer MUST be vented to the outdoors with the
termination securely fastened to the mobile home structure.
(See EXHAUST INFORMATION section 3 & 4.)
• The vent MUST NOT be terminated beneath a mobile or
manufactured home.
• The vent duct material MUST BE METAL.
• Do not use sheet metal screws or other fastening devices
which extend into the interior of the exhaust vent.
• See section 2 for electrical connection information.
Consumer Support
10
Electric Dryer
9
DRYER EXHAUST TO RIGHT, LEFT OR
BOTTOM CABINET
WARNING - BEFORE PERFORMING
THIS EXHAUST INSTALLATION, BE SURE
TO DISCONNECT THE DRYER FROM ITS
ELECTRICAL SUPPLY. PROTECT YOUR
HANDS AND ARMS FROM SHARP EDGES
WHEN WORKING INSIDE THE CABINET.
BE SURE TO WEAR GLOVES.
REMOVE
SCREW
AND SAVE.
REMOVE
DESIRED
KNOCKOUT
(ONE ONLY).
Detach and remove the bottom, right or left side knockout as
desired. Remove the screw inside the dryer exhaust duct and
save. Pull the duct out of the dryer.
www.GEAppliances.ca
ADDING NEW DUCT
FIXING
HOLE
PORTION “A”
RIGHT OR
LEFT SIDE
EXHAUST
Reconnect the cut portion (A) of the duct to the blower housing.
Make sure that the shortened duct is aligned with the tab in the
base. Use the screw saved previously to secure the duct in place
through the tab on the appliance base.
ADDING ELBOW AND DUCT FOR EXHAUST
TO LEFT OR RIGHT SIDE OF CABINET
• Preassemble 10 cm (4”) elbow with 10 cm (4”) duct. Wrap duct
tape around joint.
• Insert duct assembly, elbow first , through the side opening and
connect the elbow to the dryer internal duct.
CAUTION: Be sure not to pull or damage the
electrical wires inside the dryer when
inserting the duct.
Safety Instructions
Installation Instructions
Operating Instructions
FIXING HOLE
Cut the duct as shown and keep portion A.
TAB LOCATION
BEND TAB
UP 45º
Through the rear opening, locate the tab in the middle of the
appliance base. Lift the tab to about 45º using a flat blade
screwdriver.
EXHAUST CAN BE
ADDED TO LEFT OR
RIGHT SIDE
• Apply duct tape as shown on the joint between the dryer
internal duct and the elbow.
DUCT
TAPE
CAUTION:
Internal duct joints must be
secured with tape, otherwise
they may separate and cause
a safety hazard.
Troubleshooting Tips
Consumer Support
11
Electric Dryer
DRYER EXHAUST TO RIGHT, LEFT OR
BOTTOM CABINET
• Insert the elbow through the rear opening and connect it to the
dryer internal duct.
• Apply duct tape on the joint between the dryer internal duct
Safety Instructions
and elbow, as shown on page 11.
CAUTION:
Internal duct joints must be secured with tape,
otherwise they may separate and cause a
safety hazard.
10
SERVICING
WARNING - LABEL ALL WIRES PRIOR
TO DISCONNECTING WHEN SERVICING
CONTROLS. WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERATION
AFTER SERVICING/INSTALLATION.
For servicing phone numbers for replacement parts, and other
information, refer to Owner’s Manual or visit our Web site.
ADDING COVER PLATE TO REAR OF
CABINET (SIDES AND BOTTOM EXHAUST)
Connect standard metal elbows and ducts to complete the
exhaust system. Cover back opening with a plate (Kit
WE1M454) available from your local service provider. Place
dryer in final location.
WARNING - NEVER LEAVE THE BACK
OPENING WITHOUT THE PLATE. (Kit WE1M454)
Consumer Support
12
Gas Dryer
Safety Instructions
www.GEAppliances.ca
PEDESTALS FOR DRYERS
(comes with individual installation instructions)
Available models: -SBSD227F
-SBSD137H
-SBSD107H
BEFORE YOU BEGIN:
Read these instructions completely and carefully.
IMPORTANT - Save these instructions for local
inspector’s use.
IMPORTANT - Observe all governing codes and
ordinances.
Note to Installer - Be sure to leave these instructions with the
customer.
Note to Customer - Keep these instructions with your Use
and Care Book for future reference.
Before the old dryer is removed from service or discarded,
remove the dryer door.
Service information and the wiring diagram are located in the
control console.
WARNING!
FOR YOUR SAFETY:
Use only rigid metal or flexible metal 10 cm (4 in.) diameter
ductwork for exhausting to the outdoors. Never use plastic
or other combustible, easy-to-puncture ductwork.
This appliance must be properly grounded and installed as
described in these instructions.
Do not install or store appliance in an area where it will be
exposed to water and/or weather.
Verify and conform to local regulations before installing an
appliance in the garage.
Install the dryer where the temperature is above 10°
C (50°F) for satisfactory operation of the dryer control
system.
This dryer must be exhausted to the outdoors.
Inspect the dryer exhaust outlet and straighten the outlet
walls if they are bent.
Do not allow children on or in the appliance. Close
supervision of children is necessary when the appliance is
used near children.
NOTE: Installation and service of this dryer requires basic
mechanical and electrical skills. It is your responsibility
to contact a qualified installer to make the electrical
connections.
Installation Instructions
Operating Instructions
TOOLS YOU
WILL NEED
SLIP JOINT PLIERS
10 in. ADJUSTABLE WRENCHES (2)
LEVEL
8 in. PIPE WRENCH
Step 1 Verify your gas installation (see section2).
Step 2 Prepare the area and exhaust for installation of
new dryer (see section 1).
Step 3 Check and ensure the existing external exhaust is
clean (see section 1) and meets attached installation specifications (see section 6).
Step 4 Remove the foam shipping pads (see section 1).
Step 5 Move the dryer to the desired location.
Step 6 Level your dryer (see section 8).
Step 7 Connect the gas supply (see section 3) and check
for leaks (see section 4)
FLAT BLADE SCREWDRIVER
1O cm (4 in.)
METAL ELBOW
PIPE COMPOUND
FLEXIBLE GAS LINE CONNECTOR
METAL DUCT (RECOMMENDED)
1O cm (4 in.) DIA. FLEXIBLE METAL
Step 8 Connect the external exhaust (see section 7).
Step 9 Connect the power supply (see section 5).
Step 10 Check the operation of the power supply, gas
connections and venting.
Step 11 Place the Use and Care in a location where it will be noticed by the owner.
For alcove or closet installation, see section 9.
For bathroom or bedroom installation, see section 10.
For mobile or manufactured home see, section 11.
MATERIALS YOU
WILL NEED
1O cm (4 in.) DIA.
DUCT (IF NEEDED)
GLOVES
1O cm (4
in.) DUCT
CLAMPS (2)
SAFETY GLASSES
SOAP SOLUTION FOR
LEAK DETECTION
EXHAUST HOOD
DUCT TAPE
Troubleshooting Tips
Consumer Support
13
Gas Dryer
Minimum Clearance Other Than Alcove or Closet Installation
Minimum clearance to combustible surfaces and for air opening are: 0 cm (0 in.) clearance both sides and 2.5 cm (1 in.) rear.
Consideration must be given to provide adequate clearance for installation and service.
1
PREPARING FOR INSTALLATION
OF NEW DRYER
Safety Instructions
EXTERNAL
DUCT
OPENING
DUCT
TAPE
10 cm (4 in.) METAL DUCT
VENT
PROTECTION
BRACKET
TIP: Install your dryer before installing your washer.
This will allow better access when installing dryer exhaust.
CSA (AGA) APPROVED
NEW FLEXIBLE GAS
LINE CONNECTOR
Pull the vent protection bracket
out until it stops, and let it rest on
the floor. The bracket prevents
the unit from moving too close
to the wall and crushing the
rear vent. Prolong by adding a
DASHED FLEXIBLE duct.
DISCONNECT AND DISCARD OLD
FLEXIBLE GAS CONNECTOR AND
OLD DUCTING MATERIAL
Tilt the dryer sideways
and remove the foam
shipping pads by pulling
at the sides and breaking
them away from the
dryer legs. Be sure to
remove all of the foam
pieces around the legs.
2
GAS REQUIREMENTS
WARNING!
• Installation must conform to local codes and ordinances,
or in their absence, the NCAN/CGA-B149, Natural Gas,
Installation.
• This gas dryer is equipped with a Valve & Burner Assembly
for use only with natural gas. Using conversion kit
WE25M43, your local service organization can convert this
dryer for use with propane (LP) gas. ALL CONVERSIONS
MUST BE MADE BY PROPERLY TRAINED AND QUALIFIED
PERSONNEL AND IN ACCORDANCE WITH LOCAL CODES
AND ORDINANCE REQUIREMENTS OF THE CAN/CGAB149.1 AND B149.2 INSTALLATION CODE.
• The dryer must be disconnected from the gas supply
piping system during any pressure testing of that system
at a test pressure in excess of 0.5 PSI (3.4 KPa).
• The dryer must be isolated from the gas supply piping
system by closing the equipment shut-off valve during any
pressure testing of the gas supply piping of test pressure
equal to or less than 0.5 PSI (3.4 KPa).
DRYER GAS SUPPLY CONNECTION
5 cm (2")
WARNING -NEVER REUSE OLD
FLEXIBLE CONNECTORS.
The use of old flexible connectors can cause leaks and
personal injury. Always use new flexible connectors when
installing gas appliances.
REMOVING LINT FROM WALL EXHAUST
OPENING
WALL
INTERNAL DUCT
OPENING
Consumer Support
14
CHECK THAT EXHAUST HOOD
DAMPER OPENS AND CLOSES
FREELY.
6.6 cm (2-5/8")
0.9 cm (3/8")
NOTE: Add to vertical dimension
the distance between cabinet
bottom to floor.
NPT MALE THREAD GAS SUPPLY
GAS SUPPLY
• A 0.3 cm (1/8-in.) National Pipe Taper thread plugged tapping,
accessible for test gauge connection, must be installed
immediately upstream of the gas supply connection to
the dryer. Contact your local gas utility should you have
questions on the installation of the plugged tapping.
• Supply line is to be 1.2 cm (1/2-in.) rigid pipe and equipped
with an accessible shut-off within 2 m (6 ft.) of, and in the
same room with, the dryer.
• Use pipe thread sealer compound appropriate for natural or
LP gas or use Teflon tape.
• You must use with this dryer a flexible metal connector listed
connector ANSI Z21.24 / CSA 6.10.
• Connect flexible metal connector to dryer and gas supply.
• Open shut-off valve.
Gas Dryer
3
RECONNECTING GAS
Listed connector ANSIZ21.24 / CSA 6.10
Safety Instructions
www.GEAppliances.ca
FLARE
NEW METAL
FLEXIBLE GAS LINE
CONNECTOR
ADAPTER
Note: The connector and fittings are designed for use only on the
original installation and are not to be reused for another appliance or
at another location. Keep flare end of adapter free of grease, oil and
thread sealant.
Caution: Use adapters as shown. Connector nuts must not be
connected directly to pipe threads.
NPT
ELBOW
0.9 cm
(3/8") NPT
ADAPTER
0.3 cm (1/8") NPT
PIPE PLUG FOR
CHECKING GAS
INLET PRESSURE
SHUT-OFF
VALVE
PIPE SIZE
AT LEAST
1.2 cm (1/2")
APPLY PIPE COMPOUND
TO ALL MALE THREADS.
Tighten all connections using two adjustable wrenches.
Do not overtorque gas connections!
4
LEAK TEST
Installation Instructions
Operating Instructions
APPLY PIPE COMPOUND
TO THE ADAPTER AND
DRYER GAS INLET.
WARNING -NEVER USE AN OPEN
FLAME TO TEST FOR GAS LEAKS.
OPEN GAS
VALVE.
Check all connections for leaks with soapy solution or equivalent.
Apply soap solution. Leak test solution must not contain ammoniawhich could cause damage to the brass fittings. If leaks are
found, close valve, retighten the joint, and repeat the soap test .
Troubleshooting Tips
Consumer Support
15
Gas Dryer
5
ELECTRICAL CONNECTION
INFORMATION
WARNING - TO REDUCE THE RISK OF FIRE,
ELECTRICAL SHOCK AND PERSONAL INJURY:
DO NOT USE AN EXTENSION CORD OR AN
Safety Instructions
ADAPTER PLUG WITH THIS APPLIANCE.
Dryer must be electrically grounded in accordance with local
codes and ordinances, or in the absence of local codes, in
accordance with the current CSA C22.1 Canadian Electrical
code part 1. Improper connection of the equipment-grounding
conductor can result in an electric shock. Check with a
qualified electrician or service representative or personnel
if you are in doubt as to whether the appliance is properly
grounded.
Do not modify the plug provided with the appliance: if it will
not fit the outlet, have a proper outlet installed by a qualified
electrician.
ELECTRICAL REQUIREMENTS
This appliance must be supplied with 120V, 60Hz, and connected
to a properly grounded branch circuit, protected by a 15- or 20amp circuit breaker or time-delay fuse. If electrical supply provided
does not meet the above specifications, it is recommended that a
licensed electrician install an approved outlet.
WARNING -THIS DRYER IS EQUIPPED
WITH A THREE-PRONG (GROUNDING) PLUG FOR
YOUR PROTECTION AGAINST SHOCK HAZARD AND
SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY
GROUNDED THREE-PRONG RECEPTACLE. DO NOT
CUT OR REMOVE THE GROUNDING PRONG FROM
THIS PLUG. INSTALLATION MUST BE IN ACCORDANCE
WITH THE CURRENT CSA C22.1 CANADIAN
ELECTRICAL CODE PART 1 AND/OR LOCAL CODES.
IF LOCAL CODES PERMIT, AN EXTERNAL
GROUND WIRE (NOT PROVIDED), WHICH MEETS
LOCAL CODES, MAY BE ADDED BY ATTACHING TO THE GREEN
GROUND SCREW ON THE REAR OF THE DRYER, AND TO A GROUNDED
METAL COLD WATER PIPE OR OTHER ESTABLISHED GROUND.
Consumer Support
16
6
EXHAUST INFORMATION
WARNING - USE ONLY METAL 10 cm (4in.)
DUCT. DO NOT USE DUCT LONGER THAN
SPECIFIED IN THE EXHAUST LENGTH TABLE.
Using exhaust longer than specified length will:
• Increase the drying times and the energy cost.
• Reduce the dryer life.
• Accumulate lint, creating a potential fire hazard.
The correct exhaust installation is YOUR RESPONSIBILITY.
Problems due to incorrect installation are not covered by
the warranty.
The MAXIMUM ALLOWABLE length of the exhaust system
depends upon the type of duct, number of turns, the type of
exhaust hood (wall cap), and all conditions noted below. Both
rigid and flexible metal duct are shown in the table below.
EXHAUST LENGTH
If using flexible metal duct, please refer to page 18.
EXHAUST SYSTEM CHECKLIST
HOOD OR WALLCAP
• Terminate in a manner to prevent back drafts or entry of birds or other
wildlife.
• Termination should present minimal resistance to the exhaust air flow
and should require little or no maintenance to prevent clogging.
• Never install a screen in or over the exhaust duct.
• Wall caps must be installed at least 30 cm (12 in.) above ground level or
any other obstruction with the opening pointed down.
• If roof vents or louvered plenums are used, they must be equivalent to
a 10 cm (4 in. ) dampened wall cap in regard to resistance to air flow,
prevention of back drafts, and maintenance required to prevent clogging.
SEPARATION OF TURNS
For best performance, separate all turns by at least 1.2 m (4 ft.) of straight
duct, including distance between last turn and dampened wall cap.
TURNS OTHER THAN 90º
• One turn of 45º or less may be ignored.
• Two 45º turns should be treated as one 90º turn.
• Each turn over 45º should be treated as one 90º turn.
SEALING OF JOINTS
• All joints should be tight to avoid leaks. The male end of each section of
duct must point away from the dryer.
• Do not assemble the ductwork with fasteners that extend into the duct.
They will serve as a collection point for lint.
• Duct joints should be made air- and moisture-tight by wrapping the
overlapped joints with duct tape.
• Horizontal runs should slope down toward the outdoors 1.2cm (1/2 in.) /ft.
INSULATION
Duct work that runs through an unheated area or is near air conditioning
should be insulated to reduce condensation and lint build-up.
Gas Dryer
7
EXHAUST CONNECTION
WARNING - TO REDUCE THE RISK
OF FIRE OR PERSONAL INJURY:
This dryer must be exhausted to the outdoors.
• Use only metal duct.
• Do not terminate exhaust in a chimney, any gas
vent, under an enclosed floor (crawl space), or into
an attic. The accumulated lint could create a fire
hazard.
• Provide an access for inspection and cleaning of
the exhaust system, especially at turns. Inspect and
clean at least once a year.
• Never terminate the exhaust into a common duct
with a kitchen exhaust. A combination of lint and
grease could create a fire hazard.
• Do not obstruct incoming or exhausted air.
WE RECOMMEND THAT YOU INSTALL YOUR DRYER BEFORE
YOUR WASHER. THIS WILL PERMIT DIRECT ACCESS FOR
EASIER EXHAUST CONNECTION.
ELBOW HIGHLY
RECOMMENDED
www.GEAppliances.ca
ELBOW HIGHLY
RECOMMENDED
RECOMMENDED
CONFIGURATION
TO MINIMIZE
EXHAUST
BLOCKAGE.
Safety Instructions
Installation Instructions
THIS DRYER COMES READY FOR REAR EXHAUSTING. IF
SPACE IS LIMITED, USE THE INSTRUCTIONS IN SECTION 12 TO
EXHAUST DIRECTLY FROM THE LEFT SIDE OR BOTTOM OF THE
CABINET.
STANDARD REAR EXHAUST
NOTE: ELBOWS WILL PREVENT DUCT KINKING
AND COLLAPSING.
8
LEVELING DRYER
Stand the dryer upright near the final location and
adjust the 4 leveling legs to match the height of your
washer.
LEVEL
FRONT-TO-BACK
LEVEL
SIDE-TO-SIDE
Operating Instructions
Troubleshooting Tips
WE STRONGLY RECOMMEND THE USE OF
RIGID METAL EXHAUST DUCT. IF USING
FLEXIBLE METAL DUCT, CUT IT TO THE
PROPER LENGTH AND AVOID BUNCHING
OF THE DUCT BEHIND THE DRYER.
Consumer Support
4 LEVELING
LEGS
17
Gas Dryer
USING FLEXIBLE METAL DUCTSEXHAUSTING
If rigid all-metal duct cannot be used, then flexible all-metal
venting can be used, but it will reduce the maximum
recommended duct length. In special installations when it is
impossible to use only metal ducting, then UL-listed clothes dryer
Safety Instructions
flexible metal transition duct may be used as transition venting
between the dryer and wall connection only. The use of this
ducting will affect dry time.
If flexible transition duct is necessary, the following directions
must be followed.
• Use the shortest length possible.
• Stretch the duct to its maximum length to avoid kinks.
• Do not crush or collapse the duct.
• Extend vent protection bracket as described in step 1 on
page 2.
• Never use transition duct inside the wall or inside the dryer.
• Avoid resting the duct on sharp objects.
• Venting must conform to local building codes.
A CLOTHES DRYER PRODUCES COMBUSTIBLE LINT. FOR
ALL INSTALLATIONS, THE DRYER MUST BE CONNECTED
TO AN EXHAUST TO THE OUTDOORS.
NOTE: MOBILE HOME, BEDROOM, BATHROOM, ALCOVE
OR CLOSET INSTALLATIONS MUST BE EXHAUSTED TO
THE OUTDOORS.
9
ALCOVE OR CLOSET INSTALLATION
• If your dryer is approved for installation in an alcove or closet,
it will be stated on a label on the dryer back.
• The dryer MUST be vented to the outdoors. See the EXHAUST
INFORMATION sections 3 & 4.
• Minimum clearance between dryer cabinet and adjacent walls
or other surfaces is:
0 in. either side
7.6 cm (3 in.) front and rear
• Minimum vertical space from floor to overhead cabinets,
ceiling, etc. is 109 cm (43 in.) without pedestal, 140 cm (55 in.)
with pedestal.
• Closet doors must be louvered or otherwise ventilated and
must contain a minimum of 387 sq. cm (60 sq. in.) of open area
equally distributed. If the closet contains both a washer and
a dryer, doors must contain a minimum of 774 sq. cm (120 sq.
in.) of open area equally distributed.
• The closet should be vented to the outdoors to prevent gas
pocketing in case of a gas leak in the supply line.
• No other fuel-burning appliance shall be installed in the same
closet with the dryer.
NOTE: WHEN THE EXHAUST DUCT IS LOCATED AT THE
REAR OF THE DRYER, MINIMUM CLEARANCE FROM THE
WALL IS 14 cm (5.5 IN.)
• The dryer MUST be vented to the outdoors. See EXHAUST
INFORMATION section 6.
• The installation must conform with local codes or, in the
absence of local codes, with the current CSA C22.1 Canadian
Electrical code part 1.
11
MOBILE OR MANUFACTURED HOME
INSTALLATION
• Installation must conform to the current CAN/CSA Z240 MH
series Mobile Home Installation Codes.
• The dryer MUST be vented to the outdoors with the
termination securely fastened to the mobile home structure.
(See EXHAUST INFORMATION section 6.)
• The vent MUST NOT be terminated beneath a mobile or
manufactured home.
• The vent duct material MUST BE METAL.
• KIT 14-D346-33 MUST be used to attach the dryer securely to
the structure.
• The vent MUST NOT be connected to any other duct, vent, or
chimney.
• Do not use sheet metal screws or other fastening devices
which extend into the interior of the exhaust vent.
• Provide an opening with a free area of at least 161 cm sq. (25
sq. in.) for introduction of outside air into the dryer room.
Gas Dryer
12
RESIDENTIAL GARAGE INSTALLATION
Dryers installed in residential garages must be elevated
18 inches (46 cm) above the floor.
13
DRYER EXHAUST TO LEFT OR BOTTOM
CABINET
WARNING - PROTECT YOUR
HANDS AND ARMS FROM SHARP EDGES
WHEN WORKING INSIDE THE CABINET.
REMOVE
SCREW
AND SAVE.
REMOVE
DESIRED
KNOCKOUT
Detach and remove the bottom, right or left side knockout as desired.
Remove the screw inside the dryer exhaust duct and save. Pull the
duct out of the dryer. Protect sharp edges around the knockout and
exhaust opening with the tape.
(ONE ONLY).
www.GEAppliances.ca
ADDING NEW DUCT
FIXING
HOLE
PORTION “A”
RIGHT OR
LEFT SIDE
EXHAUST
Reconnect the cut portion (A) of the duct to the blower housing.
Make sure that the fixing hole is aligned with the tab in the
base. Use the screw saved previously to secure the duct in place
through the tab on the appliance base.
ADDING ELBOW AND DUCT FOR EXHAUST
TO RIGHT SIDE OF CABINET
~ Preassemble 10 cm (4”) elbow with 10 cm (4”) duct. Wrap duct
tape around joint.
~ Insert duct assembly, elbow first , through the side opening and
connect the elbow to the dryer internal duct.
CAUTION: Be sure not to pull or damage the
electrical wires inside the dryer when
inserting the duct.
Safety Instructions
Installation Instructions
Operating Instructions
FIXING HOLE
Cut the duct as shown and keep portion A.
TAB LOCATION
BEND TAB
UP 45º
Through the rear opening, locate the tab in the middle of the
appliance base. Lift the tab to about 45º using a flat blade
screwdriver.
EXHAUST CAN BE
ADDED TO LEFT OR
RIGHT SIDE
~ Apply duct tape as shown on the joint between the dryer
internal duct and the elbow.
DUCT
TAPE
CAUTION:
Internal duct joints must be
secured with tape, otherwise
they may separate and cause
a safety hazard.
Troubleshooting Tips
Consumer Support
19
Gas Dryer
ADDING ELBOW FOR EXHAUST
THROUGH BOTTOM OF CABINET
• Insert the elbow through the rear opening and connect it to the
dryer internal duct.
• Apply duct tape on the joint between the dryer internal duct
Safety Instructions
and elbow, as shown on page 7.
CAUTION:
Internal duct joints must be secured with tape,
otherwise they may separate and cause a
safety hazard.
14
SERVICING
WARNING - LABEL ALL WIRES PRIOR
TO DISCONNECTING WHEN SERVICING
CONTROLS. WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERATION
AFTER SERVICING/INSTALLATION.
For servicing phone numbers for replacement parts, and other
information, refer to Owner’s Manual or visit our Web site.
Connect standard metal elbows and ducts to complete the
exhaust system. Cover back opening with a plate (Kit
WE1M454) available from your local service provider. Place
dryer in final location.
WARNING - NEVER LEAVE THE BACK
OPENING WITHOUT THE PLATE. (Kit WE1M454)
Consumer Support
20
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.