GE SBSD227F, SBSD137H, SBSD107H Installation Instructions Manual

Electric Dryer
PEDESTALS FOR DRYERS
(comes with individual installation instructions)
Available models: -SBSD227F
Safety Instructions
BEFORE YOU BEGIN:
Read these instructions completely and carefully.
IMPORTANT - Save these instructions for local
inspector’s use.
IMPORTANT - Observe all governing codes and
ordinances.
Note to Installer - Be sure to leave these instructions with the customer.
Note to Customer - Keep these instructions with your Use and Care Book for future reference.
Before the old dryer is removed from service or discarded, remove the dryer door.
Service information and the wiring diagram are located in the control console.
WARNING!
FOR YOUR SAFETY:
Use only rigid metal or flexible metal 4-in. diameter ductwork for exhausting to the outdoors. Never use plastic or other combustible, easy-to-puncture ductwork.
This appliance must be properly grounded and installed as described in these instructions.
Do not install or store appliance in an area where it will be exposed to water and/or weather.
Install the dryer where the temperature is above 10° C (50°F) for satisfactory operation of the dryer control system.
This dryer must be exhausted to the outdoors.
Inspect the dryer exhaust outlet and straighten the outlet walls if they are bent.
Do not allow children on or in the appliance. Close supervision of children is necessary when the appliance is used near children.
NOTE: Installation and service of this dryer requires basic mechanical and electrical skills. It is your responsibility to contact a qualified installer to make the electrical connections.
TOOLS YOU
WILL NEED
Operating Instructions Installation InstructionsTroubleshooting Tips
SLIP JOINT PLIERS
FLAT BLADE SCREWDRIVER
PHILLIPS SCREWDRIVER
LEVEL
Step 1 Prepare the area and exhaust for installation of new dryer (see section 1). Step 2 Check and ensure the existing external exhaust is clean (see section 1) and meets attached installation specifications (see section 3). Step 3 Remove the foam shipping pads (see section 1). Step 4 Move the dryer to the desired location. Step 5 Connect the power supply (see section 2). Step 6 Connect the external exhaust (see section 4). Step 7 Level your dryer (see section 5).
1O cm (4 in.) DIA. METAL DUCT (RECOMMENDED)
1O cm (4 in.) DIA. FLEXIBLE METAL DUCT (IF NEEDED)
MATERIALS YOU
WILL NEED
1O cm (4 in.) DUCT CLAMPS (2) OR 10 cm (4 in.) SPRING CLAMPS (2)
Step 8 Check the operation of the power supply and venting. Step 9 Place the owners Use and Care in a location where it will be noticed by the owner.
For alcove or closet installation, see section 6. For bathroom or bedroom installation, see section 7. For mobile or manufactured home see, section 8. For side or bottom exhaust, see section 9.
1O cm (4 in.) METAL ELBOW
DUCT TAPE
EXHAUST HOOD
GLOVES
SAFETY GLASSES
Consumer Support
6
Electric Dryer
www.GEAppliances.ca
Minimum Clearance Other Than Alcove or Closet Installation
Minimum clearance to combustible surfaces and for air opening are: 0 cm (0 in.) clearance both sides and 2.5 cm (1 in.) rear. Consideration must be given to provide adequate clearance for installation and service.
1 2
PREPARING FOR INSTALLATION OF NEW DRYER
ELECTRICAL CONNECTION INFORMATION
Safety Instructions
EXTERNAL DUCT OPENING
DUCT TAPE OR DUCT CLAMP
10 cm (4 in.) METAL DUCT
VENT PROTECTION BRACKET
TIP: Install your dryer before installing your washer. This will allow better access when installing dryer exhaust.
DISCONTINUITY ON DUCT
DUCT TAPE OR DUCT CLAMP
Pull the vent protection bracket out until it stops, and let it rest on the floor. The bracket prevents the unit from moving too close to the wall and crushing the rear vent. Prolong by adding a DASHED FLEXIBLE duct.
REMOVING LINT FROM WALL EXHAUST OPENING & FOAM REMOVAL FROM DRYER LEGS
WALL
WARNING - TO REDUCE THE RISK
OF FIRE, ELECTRICAL SHOCK AND PERSONAL INJURY:
DO NOT USE AN EXTENSION CORD OR AND ADAPTER PLUG WITH THIS APPLIANCE.
Dryer must be electrically grounded in accordance with local codes and ordinances. Installation must be in accordance with the current CSA C22.1 Canadian Electrical code part 1. Improper connection of the equipment-grounding conductor can result in an electric shock. Check with a qualified electrician or service representative or personnel if you are in doubt as to whether the appliance is properly grounded.
Do not modify the plug provided with the appliance: if it will not fit the outlet, have a proper outlet installed by a qualified electrician.
ELECTRICAL REQUIREMENTS
This dryer must be connected to an individual branch circuit, protected by the required time-delay fuses or circuit breakers. The power supply must be of 120/240 volts, 60 Hz circuit with the wall receptacle as shown below:
Installation Instructions
Operating Instructions
Troubleshooting Tips
INTERNAL DUCT OPENING
CHECK THAT EXHAUST HOOD DAMPER OPENS AND CLOSES FREELY.
Tilt the dryer sideways and remove the foam shipping pads by pulling at the sides and breaking them away from the dryer legs. Be sure to remove all of the foam pieces around the legs.
TYPICAL 30 AMP
RECEPTACLE FOR DRYER
The power supply must be protected with 30 Amp fuses or breakers. It must be well grounded and conform to local codes.
GROUNDING INSTRUCTIONS
This appliance must be grounded. In the event of malfunction or breakdown, grounding will reduce the risk of electrical shock by providing a path of least resistance for electrical current. This appliance is equipped with a cord having an equipment-grounding conductor and a grounding plug. The plug must be plugged into an appropriate outlet that is properly installed and grounded in accordance with all local codes and ordinances.
Consumer Support
7
Electric Dryer
3 4
EXHAUST INFORMATION
WARNING - USE ONLY METAL 10 cm (4”) DUCT. DO NOT USE DUCT LONGER THAN SPECIFIED IN THE EXHAUST LENGTH TABLE.
Using exhaust longer than specified length will:
Safety Instructions
• Increase the drying times and the energy cost.
• Reduce the dryer life.
• Accumulate lint, creating a potential fire hazard.
The correct exhaust installation is YOUR RESPONSIBILITY. Problems due to incorrect installation are not covered by the warranty.
The MAXIMUM ALLOWABLE length of the exhaust system depends upon the type of duct, number of turns, the type of exhaust hood (wall cap), and all conditions noted below. Both rigid and flexible metal duct are shown in the table below.
EXHAUST CONNECTION
WARNING - TO REDUCE THE RISK
OF FIRE OR PERSONAL INJURY:
This dryer must be exhausted to the outdoors.
Use only metal duct.
Do not terminate exhaust in a chimney, any gas
vent, under an enclosed floor (crawl space), or into an attic. The accumulated lint could create a fire hazard.
Provide an access for inspection and cleaning of
the exhaust system, especially at turns. Inspect and clean at least once a year.
Never terminate the exhaust into a common duct
with a kitchen exhaust. A combination of lint and grease could create a fire hazard.
Do not obstruct incoming or exhausted air.
THIS DRYER COMES READY FOR REAR EXHAUSTING. IF SPACE IS LIMITED, USE THE INSTRUCTIONS IN SECTION 9 TO EXHAUST DIRECTLY FROM THE SIDES OR BOTTOM OF THE CABINET.
If using flexible metal duct, please refer to page 10.
EXHAUST SYSTEM CHECKLIST
HOOD OR WALLCAP
Operating Instructions Installation InstructionsTroubleshooting Tips
• Terminate in a manner to prevent back drafts or entry of birds or other wildlife.
• Termination should present minimal resistance to the exhaust air flow and should require little or no maintenance to prevent clogging.
• Never install a screen in or over the exhaust duct. This could cause lint build up, thus creating a fire hazard.
• Wall caps must be installed at least 30 cm (12 in.) above ground level or any other obstruction with the opening pointed down.
• If roof vents or louvered plenums are used, they must be equivalent to a 10 cm (4 in. ) dampened wall cap in regard to resistance to air flow, prevention of back drafts, and maintenance required to prevent clogging.
SEPARATION OF TURNS
For best performance, separate all turns by at least 1.2 m (4 ft.) of straight duct, including distance between last turn and exhaust hood.
TURNS OTHER THAN 90º
• One turn of 45º or less may be ignored.
• Two 45º turns should be treated as one 90º turn.
• Each turn over 45º should be treated as one 90º turn.
SEALING OF JOINTS
• All joints should be tight to avoid leaks. The male end of each section of
duct must point away from the dryer.
• Do not assemble the ductwork with fasteners that extend into the duct.
They will serve as a collection point for lint.
• Duct joints should be made air and moisture-tight by wrapping the
overlapped joints with duct tape.
• Horizontal runs should slope down toward the outdoors 1.2cm (1/2 in.) /ft.
INSULATION
Duct work that runs through an unheated area or is near air conditioning should be insulated to reduce condensation and lint build-up.
Consumer Support
8
STANDARD REAR EXHAUST
(Vented at floor level)
For straight line installation, connect the dryer exhaust to the external exhaust hood using duct
tape or clamp.
NOTE: WE STRONGLY RECOMMEND SOLID METAL EXHAUST DUCTING. HOWEVER, IF FLEXIBLE DUCTING IS USED IT MUST BE METAL NOT PLASTIC.
CUT THE METAL EXHAUST DUCT (NOT SUPPLIED) TO THE PROPER LENGTH.
Electric Dryer
STANDARD REAR EXHAUST
(Vented above floor level)
ELBOW HIGHLY RECOMMENDED
Safety Instructions
www.GEAppliances.ca
ELBOW HIGHLY RECOMMENDED
Installation Instructions
RECOMMENDED CONFIGURATION TO MINIMIZE EXHAUST BLOCKAGE.
NOTE: ELBOWS WILL PREVENT DUCT KINKING AND COLLAPSING.
5
LEVELING AND STABILIZING YOUR DRYER
Stand the dryer upright near the final location and adjust the 4 leveling legs, at the corners, to ensure that the dryer is level from side to side and front to rear.
LEVEL FRONT-TO-BACK
LEVEL SIDE-TO-SIDE
Operating Instructions
Troubleshooting Tips
4 LEVELING LEGS
Consumer Support
9
Electric Dryer
USING FLEXIBLE METAL DUCTS EXHAUSTING
If rigid all-metal duct cannot be used, then flexible all-metal ducting can be used, but it will reduce the maximum recommended duct length. In special installations when it is impossible to use only metal ducting, then UL-listed clothes dryer
Safety Instructions
flexible metal transition duct may be used as transition venting between the dryer and wall connection only. The use of this ducting will affect dry time.
If flexible transition duct is necessary, the following directions must be followed.
Use the shortest length possible.
Stretch the duct to its maximum length to avoid kinks.
Do not crush or collapse the duct.
Extend vent protection bracket as described in step 1.
Never use transition duct inside the wall or inside the
dryer on page 2.
Avoid resting the duct on sharp objects.
• Venting must conform to local building codes.
A CLOTHES DRYER PRODUCES COMBUSTIBLE LINT. FOR ALL INSTALLATIONS, THE DRYER MUST BE CONNECTED TO AN EXHAUST TO THE OUTDOORS.
NOTE: MOBILE HOME, BEDROOM, BATHROOM, ALCOVE OR CLOSET INSTALLATIONS MUST BE EXHAUSTED TO THE OUTDOORS.
6
ALCOVE OR CLOSET INSTALLATION
If your dryer is approved for installation in an alcove or closet,
it will be stated on a label on the dryer back.
The dryer MUST be vented to the outdoors. See the EXHAUST
INFORMATION sections 3 & 4.
Minimum clearance between dryer cabinet and adjacent walls
or other surfaces is:
0 in. either side
7.6 cm (3 in.) front and rear
Minimum vertical space from floor to overhead cabinets,
ceiling, etc. is 109 cm (43 in.) without pedestal, 140 cm (55 in.) with pedestal.
Closet doors must be louvered or otherwise ventilated and
must contain a minimum of 387 sq. cm (60 sq. in.) of open area equally distributed. If the closet contains both a washer and a dryer, doors must contain a minimum of 774 sq. cm (120 sq. in.) of open area equally distributed.
NOTE: WHEN THE EXHAUST DUCT IS LOCATED AT THE REAR OF THE DRYER, MINIMUM CLEARANCE FROM THE WALL IS 14 cm (5.5 IN.)
Operating Instructions Installation InstructionsTroubleshooting Tips
7
BATHROOM OR BEDROOM INSTALLATION
The dryer MUST be vented to the outdoors. See EXHAUST
INFORMATION section 3 & 4.
The installation must conform with local codes or, in the
absence of local codes, with the current CSA C22.1 Canadian Electrical code part 1.
8
MOBILE OR MANUFACTURED HOME INSTALLATION
Installation must conform to the current CAN/CSA Z240 MH
series Mobile Home Installation Codes.
The dryer MUST be vented to the outdoors with the
termination securely fastened to the mobile home structure. (See EXHAUST INFORMATION section 3 & 4.)
The vent MUST NOT be terminated beneath a mobile or
manufactured home.
The vent duct material MUST BE METAL.
Do not use sheet metal screws or other fastening devices
which extend into the interior of the exhaust vent.
See section 2 for electrical connection information.
Consumer Support
10
Loading...
+ 10 hidden pages