Note to Installer - Be sure to leave these instructions with the
customer.
Note to Customer - Keep these instructions with your Use
and Care Book for future reference.
Before the old dryer is removed from service or discarded,
remove the dryer door.
Service information and the wiring diagram are located in the
control console.
-SBSD137H
-SBSD107H
WARNING!
FOR YOUR SAFETY:
Use only rigid metal or flexible metal 4-in. diameter
ductwork for exhausting to the outdoors. Never use plastic
or other combustible, easy-to-puncture ductwork.
This appliance must be properly grounded and installed as
described in these instructions.
Do not install or store appliance in an area where it will be
exposed to water and/or weather.
Install the dryer where the temperature is above 10°
C (50°F) for satisfactory operation of the dryer control
system.
This dryer must be exhausted to the outdoors.
Inspect the dryer exhaust outlet and straighten the outlet
walls if they are bent.
Do not allow children on or in the appliance. Close
supervision of children is necessary when the appliance is
used near children.
NOTE: Installation and service of this dryer requires basic
mechanical and electrical skills. It is your responsibility
to contact a qualified installer to make the electrical
connections.
Step 1 Prepare the area and exhaust for installation of
new dryer (see section 1).
Step 2 Check and ensure the existing external exhaust is
clean (see section 1) and meets attached installation specifications (see section 3).
Step 3 Remove the foam shipping pads (see section 1).
Step 4 Move the dryer to the desired location.
Step 5 Connect the power supply (see section 2).
Step 6 Connect the external exhaust (see section 4).
Step 7 Level your dryer (see section 5).
1O cm (4 in.) DIA.
METAL DUCT (RECOMMENDED)
1O cm (4 in.) DIA. FLEXIBLE METAL
DUCT (IF NEEDED)
MATERIALS YOU
WILL NEED
1O cm (4 in.) DUCT
CLAMPS (2)
OR
10 cm (4 in.) SPRING
CLAMPS (2)
Step 8 Check the operation of the power supply and
venting.
Step 9 Place the owners Use and Care in a location
where it will be noticed by the owner.
For alcove or closet installation, see section 6.
For bathroom or bedroom installation, see section 7.
For mobile or manufactured home see, section 8.
For side or bottom exhaust, see section 9.
1O cm (4 in.)
METAL ELBOW
DUCT TAPE
EXHAUST
HOOD
GLOVES
SAFETY GLASSES
Consumer Support
6
Electric Dryer
www.GEAppliances.ca
Minimum Clearance Other Than Alcove or Closet Installation
Minimum clearance to combustible surfaces and for air opening are: 0 cm (0 in.) clearance both sides and 2.5 cm (1 in.) rear.
Consideration must be given to provide adequate clearance for installation and service.
12
PREPARING FOR INSTALLATION
OF NEW DRYER
ELECTRICAL CONNECTION
INFORMATION
Safety Instructions
EXTERNAL
DUCT
OPENING
DUCT TAPE OR
DUCT CLAMP
10 cm (4 in.)
METAL DUCT
VENT
PROTECTION
BRACKET
TIP: Install your dryer before installing your washer.
This will allow better access when installing dryer exhaust.
DISCONTINUITY
ON DUCT
DUCT TAPE OR
DUCT CLAMP
Pull the vent protection bracket
out until it stops, and let it rest on
the floor. The bracket prevents
the unit from moving too close
to the wall and crushing the
rear vent. Prolong by adding a
DASHED FLEXIBLE duct.
REMOVING LINT FROM WALL EXHAUST
OPENING & FOAM REMOVAL FROM
DRYER LEGS
WALL
WARNING - TO REDUCE THE RISK
OF FIRE, ELECTRICAL SHOCK AND
PERSONAL INJURY:
DO NOT USE AN EXTENSION CORD OR AND
ADAPTER PLUG WITH THIS APPLIANCE.
Dryer must be electrically grounded in accordance
with local codes and ordinances. Installation must be
in accordance with the current CSA C22.1 Canadian
Electrical code part 1. Improper connection of the
equipment-grounding conductor can result in an electric
shock. Check with a qualified electrician or service
representative or personnel if you are in doubt as to
whether the appliance is properly grounded.
Do not modify the plug provided with the appliance: if it
will not fit the outlet, have a proper outlet installed by a
qualified electrician.
ELECTRICAL REQUIREMENTS
This dryer must be connected to an individual branch
circuit, protected by the required time-delay fuses or
circuit breakers. The power supply must be of 120/240
volts, 60 Hz circuit with the wall receptacle as shown
below:
Installation Instructions
Operating Instructions
Troubleshooting Tips
INTERNAL DUCT
OPENING
CHECK THAT EXHAUST HOOD
DAMPER OPENS AND CLOSES
FREELY.
Tilt the dryer sideways
and remove the foam
shipping pads by
pulling at the sides
and breaking them
away from the dryer
legs. Be sure to
remove all of the
foam pieces around
the legs.
TYPICAL 30 AMP
RECEPTACLE FOR DRYER
The power supply must be protected with 30 Amp fuses or
breakers. It must be well grounded and conform to local
codes.
GROUNDING INSTRUCTIONS
This appliance must be grounded. In the event of malfunction
or breakdown, grounding will reduce the risk of electrical
shock by providing a path of least resistance for electrical
current. This appliance is equipped with a cord having an
equipment-grounding conductor and a grounding plug.
The plug must be plugged into an appropriate outlet that is
properly installed and grounded in accordance with all local
codes and ordinances.
Consumer Support
7
Electric Dryer
34
EXHAUST INFORMATION
WARNING - USE ONLY METAL 10 cm (4”)
DUCT. DO NOT USE DUCT LONGER THAN
SPECIFIED IN THE EXHAUST LENGTH TABLE.
Using exhaust longer than specified length will:
Safety Instructions
• Increase the drying times and the energy cost.
• Reduce the dryer life.
• Accumulate lint, creating a potential fire hazard.
The correct exhaust installation is YOUR RESPONSIBILITY.
Problems due to incorrect installation are not covered by
the warranty.
The MAXIMUM ALLOWABLE length of the exhaust system
depends upon the type of duct, number of turns, the type of
exhaust hood (wall cap), and all conditions noted below. Both
rigid and flexible metal duct are shown in the table below.
EXHAUST CONNECTION
WARNING - TO REDUCE THE RISK
OF FIRE OR PERSONAL INJURY:
This dryer must be exhausted to the outdoors.
• Use only metal duct.
• Do not terminate exhaust in a chimney, any gas
vent, under an enclosed floor (crawl space), or into
an attic. The accumulated lint could create a fire
hazard.
• Provide an access for inspection and cleaning of
the exhaust system, especially at turns. Inspect and
clean at least once a year.
• Never terminate the exhaust into a common duct
with a kitchen exhaust. A combination of lint and
grease could create a fire hazard.
• Do not obstruct incoming or exhausted air.
THIS DRYER COMES READY FOR REAR
EXHAUSTING. IF SPACE IS LIMITED, USE THE
INSTRUCTIONS IN SECTION 9 TO EXHAUST
DIRECTLY FROM THE SIDES OR BOTTOM OF
THE CABINET.
If using flexible metal duct, please refer to page 10.
• Terminate in a manner to prevent back drafts or entry of birds or other
wildlife.
• Termination should present minimal resistance to the exhaust air flow
and should require little or no maintenance to prevent clogging.
• Never install a screen in or over the exhaust duct. This could cause lint
build up, thus creating a fire hazard.
• Wall caps must be installed at least 30 cm (12 in.) above ground level or
any other obstruction with the opening pointed down.
• If roof vents or louvered plenums are used, they must be equivalent to
a 10 cm (4 in. ) dampened wall cap in regard to resistance to air flow,
prevention of back drafts, and maintenance required to prevent clogging.
SEPARATION OF TURNS
For best performance, separate all turns by at least 1.2 m (4 ft.) of straight
duct, including distance between last turn and exhaust hood.
TURNS OTHER THAN 90º
• One turn of 45º or less may be ignored.
• Two 45º turns should be treated as one 90º turn.
• Each turn over 45º should be treated as one 90º turn.
SEALING OF JOINTS
• All joints should be tight to avoid leaks. The male end of each section of
duct must point away from the dryer.
• Do not assemble the ductwork with fasteners that extend into the duct.
They will serve as a collection point for lint.
• Duct joints should be made air and moisture-tight by wrapping the
overlapped joints with duct tape.
• Horizontal runs should slope down toward the outdoors 1.2cm (1/2 in.) /ft.
INSULATION
Duct work that runs through an unheated area or is near air conditioning
should be insulated to reduce condensation and lint build-up.
Consumer Support
8
STANDARD REAR EXHAUST
(Vented at floor level)
For straight
line installation,
connect the dryer
exhaust to the
external exhaust
hood using duct
tape or clamp.
NOTE: WE STRONGLY RECOMMEND SOLID METAL EXHAUST
DUCTING. HOWEVER, IF FLEXIBLE DUCTING IS USED IT MUST BE
METAL NOT PLASTIC.
CUT THE METAL EXHAUST DUCT
(NOT SUPPLIED) TO THE PROPER
LENGTH.
Electric Dryer
STANDARD REAR EXHAUST
(Vented above floor level)
ELBOW HIGHLY
RECOMMENDED
Safety Instructions
www.GEAppliances.ca
ELBOW HIGHLY
RECOMMENDED
Installation Instructions
RECOMMENDED
CONFIGURATION
TO MINIMIZE
EXHAUST
BLOCKAGE.
NOTE: ELBOWS WILL PREVENT DUCT KINKING
AND COLLAPSING.
5
LEVELING AND STABILIZING YOUR
DRYER
Stand the dryer upright near the final location and
adjust the 4 leveling legs, at the corners, to ensure that
the dryer is level from side to side and front to rear.
LEVEL
FRONT-TO-BACK
LEVEL
SIDE-TO-SIDE
Operating Instructions
Troubleshooting Tips
4 LEVELING
LEGS
Consumer Support
9
Electric Dryer
USING FLEXIBLE METAL DUCTSEXHAUSTING
If rigid all-metal duct cannot be used, then flexible all-metal
ducting can be used, but it will reduce the maximum
recommended duct length. In special installations when it is
impossible to use only metal ducting, then UL-listed clothes dryer
Safety Instructions
flexible metal transition duct may be used as transition venting
between the dryer and wall connection only. The use of this
ducting will affect dry time.
If flexible transition duct is necessary, the following directions
must be followed.
• Use the shortest length possible.
• Stretch the duct to its maximum length to avoid kinks.
• Do not crush or collapse the duct.
• Extend vent protection bracket as described in step 1.
• Never use transition duct inside the wall or inside the
dryer on page 2.
• Avoid resting the duct on sharp objects.
• Venting must conform to local building codes.
A CLOTHES DRYER PRODUCES COMBUSTIBLE LINT. FOR
ALL INSTALLATIONS, THE DRYER MUST BE CONNECTED
TO AN EXHAUST TO THE OUTDOORS.
NOTE: MOBILE HOME, BEDROOM, BATHROOM, ALCOVE
OR CLOSET INSTALLATIONS MUST BE EXHAUSTED TO
THE OUTDOORS.
6
ALCOVE OR CLOSET INSTALLATION
• If your dryer is approved for installation in an alcove or closet,
it will be stated on a label on the dryer back.
• The dryer MUST be vented to the outdoors. See the EXHAUST
INFORMATION sections 3 & 4.
• Minimum clearance between dryer cabinet and adjacent walls
or other surfaces is:
0 in. either side
7.6 cm (3 in.) front and rear
• Minimum vertical space from floor to overhead cabinets,
ceiling, etc. is 109 cm (43 in.) without pedestal, 140 cm (55 in.)
with pedestal.
• Closet doors must be louvered or otherwise ventilated and
must contain a minimum of 387 sq. cm (60 sq. in.) of open area
equally distributed. If the closet contains both a washer and
a dryer, doors must contain a minimum of 774 sq. cm (120 sq.
in.) of open area equally distributed.
NOTE: WHEN THE EXHAUST DUCT IS LOCATED AT THE
REAR OF THE DRYER, MINIMUM CLEARANCE FROM THE
WALL IS 14 cm (5.5 IN.)