GE TX-6211-03-1, RF6211-03-1 Installation Instructions Manual

Page 1
g
Smoke Sensor 868 GEN2
Installation Instructions
1043368C • June 2008
Copyright © 2008 GE Security
Introduction
This is the GE Smoke Sensor 868 GEN2 Installation Instructions for models TX-6211-03-1 and RF6211-03-1. The unit combines a smoke sensor with an integrated fixed 135°F (57°C) tempera­ture/rate-of-rise heat detector, and an 868 GEN2 transmitter for use with compatible wireless control panels.
Under normal nonalarm conditions, the smoke sensor’s LED flashes once every nine seconds while monitoring the surrounding conditions. The smoke sensor transmits a supervi­sory signal every 64 minutes to the panel indicating its status.
In an alarm condition due to smoke or heat, the LED changes from flashing to on and the built-in sounder emits a temporal 3 pattern (a repeated series of three beeps followed by a short pause). The smoke sensor also transmits an alarm signal to the panel.
A built-in tamper switch activates whenever the smoke sensor is removed from its mounting base, causing the smoke sensor to transmit a tamper signal to the panel.
The smoke sensor is powered by two 3-volt lithium batteries (included). When battery voltage gets low, the smoke sensor transmits a low battery signal to the panel. If the batteries are not replaced within seven days, the smoke sensor’s built-in sounder emits a short beep or chirp every 45 seconds.
The smoke sensor also includes self-diagnostics, automatically adjusting its sensitivity to reduce the number of required clean­ings. When cleaning becomes necessary, the smoke sensor has a field-replaceable optical chamber.
General guidelines
Use the following guidelines when installing the smoke sensor.
• Before mounting the smoke sensor, program (learn) the smoke sensor into panel memory and do a sensor test from the smoke sensor’s intended location to ensure good RF communication to the panel.
• Locate the smoke sensor in an environmentally controlled area where the temperature range is between 40 and 100°F (4.4 and 37.8°C) and the humidity is between 0 and 90% noncondensing.
• Locate the smoke sensor away from ventilation sources that can prevent smoke from reaching the smoke sensor.
• Locate ceiling-mounted smoke sensors in the center of the room or hallway, at least 4 in. (10 cm) away from any walls or partitions.
• When mounting to suspended ceiling tile, the tile must be secured with the appropriate fastener to prevent removal.
• Do not mount the smoke sensor to the metal runners of suspended ceiling grids. The metal runners can draw the magnet’s field away from the smoke sensor’s reed switch causing a false tamper alarm.
• Locate wall-mounted smoke sensors so the top of the smoke sensor is at least 4 in. (10 cm) below the ceiling, but not more than 12 in. (31 cm).
• In rooms with sloped, peaked, or gabled ceilings, locate the smoke sensor 3 ft. (0.9 m) down or away from the hig h est point of the ceiling.
• Batteries must be installed in order to attach the smoke sensor to the mounting base.
Locations to avoid
Do not install smoke sensors in the following locations:
• In or near areas where combustion particles are normally present, such as kitchens, garages, near furnaces, hot water heaters, or gas space heaters.
• On the ceiling in rooms next to kitchen where there is no transcom between the kitchen and such rooms.
• In damp or very humid areas or next to bathrooms with showers. Locate smoke sensors at least 5 ft. (1.5 m) away from bathrooms.
• In very cold or very hot areas.
• In dusty, dirty, or insect infested areas.
• Near fresh air inlets or returns or excessively drafty areas. Heating/air conditioning vents, fans, and fresh air intakes can drive smoke away from smoke sensors.
• In dead air spaces at the top of peaked ceiling or in corners where walls and ceiling meet. Dead air may prevent smoke from reaching smoke sensors.
• Near florescent light fixtures. Locate smoke sensors at least 10 ft. (3 m) away from these fixtures.
Installation
To insta ll the smoke sens or, you will need to:
• Install batteries and program the smoke sensor in the panel.
• Verify panel communication.
• Mount the smoke sensor.
Programming
To program the smoke sensor, do the following:
1. Separate the smoke sensor from the mounting base by turning the smoke sensor counterclockwise about 15 degrees. The smoke sensor should snap off of the mounting base.
2. Slide the battery cover away from the smoke sensor to unsnap it and lift it off (Figure 1).
Figure 1. Battery cover
Battery cover
3. Observing polarity, insert the two lithium batteries (included) into the battery compartment and replace the battery cover.
Page 2
Smoke Sensor 868 GEN2
2
Installation Instructions
4. Attach the smoke sensor to the mounting base by lining up the alignment tab on the smoke sensor with the alignment arrow on the mounting base (Figure2), then put the smo ke sensor on the base and turn it clockwise about 15 degrees. The smoke sensor should snap into place.
Figure 2. Alignment tab and arrow
Tab Arrow
5. Make sure the system is disarmed, then put the panel into program mode (refer to your panel documentation).
6. Proceed to the Learn/add sensors menu (refer to your panel documentation).
7. When prompted by the panel to trip the sensor, activate the smoke sensor tamper switch by separating the smoke sensor from the mounting base.
8. Reattach the smoke sensor to the mounting base and exit program mode.
Verify panel communication
Before you mount the smoke sensor, you need to verify the smoke sensor location provides good RF communication to the panel.
To ver ify panel communication, refer to your panel documenta­tion and do the following:
1. Put the panel into sensor test mode.
2. Ta ke the smoke sensor to the mounting location and press and hold the smoke sensor test button for four seconds. The smoke sensor transmits a test signal.
3. Listen for the appropriate response from system sirens.
4. Exit sensor test mode.
Mounting
Mounting hardware (screws and anchors) is included with the smoke sensor, however you may need different hardware depending on the installation.
To mount the smoke sensor, do the following:
1. Separate the smoke sensor from the mounting base.
2. Place the mounting base on the mounting location surface and mark the mounting holes.
3. Secure the mounting base to the surface using appropriate hardware.
4. Attach the smoke sensor to the mounting base.
Testing
Test the smoke sensor using the following tests:
•Sensor test
• Smoke test
• Sensitivity test
Sensor test
The sensor test verifies good communication between the panel and the smoke sensor.
To do a sensor test, refer to your panel documentation and do the following:
1. Put the panel into sensor test mode.
2. Press and hold the smoke sensor test button for four seconds. The smoke sensor transmits a test signal.
3. Listen for appropriate response from system sirens.
4. Close the panel cover, if applicable.
Smoke test
The smoke test verifies that the smoke sensor activates when detecting smoke, that the transmitted signal is received by the panel, and that the panel reports the alarm to the central moni­toring station.
To test the smoke sens or, do the following:
1. Contact the central monitoring station and inform them that you are testing the system and they should not dispatch authorities.
2. Use Smoke! in a can (part SC008) to activate the smoke sensor. Follow the directions on the can.
3. Once activated, the transmitter LED turns on, the built-in sounder emits a temporal 3 pattern, and the smoke sensor transmits an alarm signal. The panel then processes the alarm signal and reports the alarm condition to the central monitoring station.
4. Press the smoke sensor test button to stop the built-in sounder. The smoke sensor automatically resets when smoke is no longer present and the LED should turn off and return to normal operation (one flash every eight seconds).
5. Contact the central monitoring station to verify they received the alarm report.
Be sure to alert the central monitoring station when you are finished testing.
Page 3
3
Sensitivity test
To test the smoke sensor sensitivity, do the following:
1. Press and hold the smoke sensor test button for two seconds, then release it. The smoke sensor transmits a test signal, and then does a self-test that causes the LED to flash one to nine times.
2. Count the number of LED flashes, then use Table 1 to deter­mine if any action is needed.
Table 1. Sensitivity test
Flashes Indication/action
1 Unserviceable hardware fault detected. Reset the unit by
2 to 3 Unit is becoming insensitive. Clean the unit. Reset the unit
4 to 7 Unit is within normal range. No action needed.
8 to 9 Unit is becoming too sensitive. Verify that the smoke
removing and replacing the batteries and retest. If error persists, replace the unit.
by removing and replacing the batteries and retest. If error persists, replace the unit.
chamber is snapped down securely. Clean the unit. Replace the optical chamber (part 211)
Fault conditions
Correct fault conditions as soon as possible. The smoke sensor indicates a fault condition in the following ways:
• The LED stops working (no flashing or turning on) if the smoke sensor sensitivity is not within the normal range, or if an unserviceable hardware fault is detected.
• The smoke sensor stops transmitting supervisory signals if the smoke sensor has an unserviceable hardware fault or is not sensitive enough, causing the panel to indicate the smoke sensor is in a supervisory condition. However , the smoke sensor can still transmit alarm signals.
• The smoke sensor transmits a trouble (CleanMe) signal when the smoke sensor is too sensitive. The panel announces “Sensor number, name, open or fire warning”.
Battery replacement
When the battery voltage gets low, the smoke sensor transmits a low battery signal to the panel. The panel activates trouble beeps through system sirens and identifies the smoke sensor with the low battery . If batteries are not replaced within seven days, the smoke sensor’s built-in sounder emits a short beep of chirp every 45 seconds. You can silence smoke sensor chirps for 24 hours by pressing the smoke sensor’s test button. Replace low batteries as soon as possible. Use only 3-volt lithium batteries listed in Spec-
ifications on page 4.
To replace the batteries, do the following:
1. Remove the smoke sensor from the mounting base.
2. Slide the battery compartment cover away from the smoke sensor to unsnap it and lift it off (Figure 1 on page 1).
3. Remove the batteries and dispose of them according to battery directive instructions and/or instructions from local government authorities.
4. Observing correct polarity, insert two new batteries into the battery compartment and replace the battery cover.
5. Attach the smoke sensor to the mounting base and test the system.
Maintenance
Clean the smoke sensor cover with a dry or damp (water) cloth as needed to keep it free from dust and dirt. When necessary, clean the smoke sensor interior and replace the optical chamber (part
211). To replace the optical chamber, do the following:
1. Contact the central monitoring station and inform them that you will be doing maintenance to the system.
2. Remove the smoke sensor from the mounting base and remove the batteries.
3. Slide a flat-bladed screwdriver in the slot on the smoke sensor cap and gently push the handle down to pry off the smoke sensor cap (Figure 3).
Figure 3. Removing the smoke sensor cap
4. Squeeze the optical chamber and pull it up and away from the optical base and discard (Figure 4).
Figure 4. Optical chamber
Smoke sensor cap
Optical chamber
Optical base
Smoke sensor
5. Blow out or use a soft-bristled brush to remove all dust and dirt from the optical base.
6. Line up the new optical chamber with the optical base and snap both side of the optical chamber into place.
7. To replace the smoke sensor c ap, line up the cap with the smoke sensor, insert the cap, and turn the cap approximately 15 degrees. It should snap firmly into place.
8. Observing proper polarity, install batteries and replace the battery cover.
9. Attach the smoke sensor to the mounting base and test smoke sensor sensitivity.
Page 4
Smoke Sensor 868 GEN2
4
Installation Instructions
Note: The control panel alarm and all auxiliary functions should be
verified for a complete test of the system.
Smoke sensor limitations
Smoke sensors may not work under all conditions. Smoke sensors cannot provide total protection of life or property and are not a substitute for insurance. All smoke sensors are subject to possible compromise or failure-to-warn for a variety of reasons. For example:
• This smoke sensor will not operate and an alarm will not sound if its batteries are dead, removed, or not installed correctly.
• Radio signals transmitted by this smoke sensor may be blocked or reflected by metal objects. Adjacent devices or systems using radio frequency signals may interfere with the operation of this smoke sensor. Test the system weekly to ensure signals are transmitted and received properly.
• Closed or partially closed doors and distance can block or reduce the alarm sound from this smoke sensor. This smoke sensor is not designed for the hearing impaired.
• Smoke sensors cannot detect smoke inside chimneys, walls, roofs, or smoke blocked by a closed door.
• Smoke sensors may not detect smoke on other levels of the building.
• Smoke sensors may not warn in time when fires are caused by smoking in bed, explosions, improper storage of flamma­bles, overloaded electrical circuits, or other hazardous conditions.
Specifications
Model number TX-6211-03-1, RF6211-03-1 RF frequency 868 MHz Compatibility GE Security 868 GEN2 control panels/
Battery type Two 3.0 V, 1300 mAh Lithium Recommended batteries Duracell DL 123A, Panasonic CR123A, Sanyo
Typical standby current 35 µA Estimated battery life Four to six years (at 20°C) Supervisory interval 64 minutes Typical RF output power 12 mW Sounder (temporal pattern) 85 dBa at 3 m Smoke sensor sensitivity 2.2% ± 1.3%/3 dm RF immunity 20 V/m minimum, 0 to 1000 MHz Heat detector specifications Rate-of-rise Fixed Operating temperature 40 to 100°F (4.4 to 37.8°C) Storage temperature 4 to 167°F (-20 to 75°C) Relative humidity range 0 to 95% noncondensing Dimensions (L x W x H) 5.6 x 5.6 x 2.5 in. (141 x 141 x 63 mm) Weight 288 g
receivers
CR123A
15°F/min > 105°F (8.3°C/min > 40.6°C) 135°F ± 5°F) (57.2°C ± 2.8°C)
888 GE Security (888.437.3287). Toll-free in the US, Puerto Rico, and Canada.
503.885.5700 outside the toll-free area or contact your local dealer.
Technical support
www.gesecurity.com
Loading...