The RCR detector combines range-controlled radar (RCR)
technology with a passive infrared (PIR) system to increase
false alarm immunity by allowing it to sense human-sized
objects within a specified range. Both the RCR and PIR
systems must be triggered to set off an alarm, unless inradar-
only mode.
The detector is designed to use a 12VDC power supply
provided by a UL Listed alarm control panel.
allows you to disable the PIR, and use the radar-only
mode to detect intruders faster. This mode can be used for
covert installations (mounted behind ceiling panels or
walls).
• Selectable range up to 50 feet (15.2m) - Internal jumper
allows radar range selection to optimize coverage.
• LED indicator - A multi-color LED provides detector
status.
• Tamper switch - Activated when the pins on the circuit
board are removed from the terminal sockets on the base.
50’
40’
(12.2m)
(12.2m)
(15.2m)
90°
40’
50’
(15.2m)
15°
Radar Viewing Area
PIR Viewing Area
4°
floor line
Top V iew
30’
(9.1m)
20’
(6.1m)
0’
20’
(6.1m)
30’
(9.1m)
Side View
7’
2.1m
60°30°
0°
Figure 1. Coverage Patterns
PrecisionLine RCR-50
Parts
The following parts are included:
• RCR detector
• 1 screw to join the case halves
• 3 factory-installed jumpers
Selecting a Location for the Detector
The detector can be mounted in a corner or on a flat wall.
Use the following guidelines to determine the best location to
install the detector:
• Mount the detector so the expected movement of an
intruder is across the detection pattern. See Figure 1.
• Mount the detector on a stable surface 7 to 9 feet (2.1 to
2.7m) high.
• DO NOT mount the detector within 2 feet (0.6m) of
metallic objects or within 5 feet (1.5m) of florescent lights.
• DO NOT place objects in front of the detector that may
prevent a clear line of sight. (Not applicable in radar-only
mode.)
• Avoid locations that expose the detector to possible false
alarm sources such as:
– Moving or vibrating objects (fans, pulleys, conveyor belts)
– Electronic fields (electric motors, high voltage equipment)
– Water spray or corrosive environments
– Heat sources in the field of view (heaters, radiators)
– W indows in the field of view
– Strong air drafts on the detector (fans, air conditioners)
• When installing multiple detectors:
– DO NOT mount detectors facing each other .
– Mount detectors at least 20 feet (6.1m) apart.
– Use shorter range settings to avoid overlapping radar
coverage.
– Mounting detectors back to back is not recommended, but
if an application requires such mounting, use the 20-foot
(6.1m) range and walk test the installation to ensure proper
operation.
Figure 2. Detector (Exploded)
COM
TMPR NO
TMPR
SPR
1
Installing the Detector
All wiring must conform to the National Electric Code (NEC)
and/or local codes having jurisdiction.
Important: DO NOT use this device for safety
interlock applications.
T o install the detector:
Terminal
sockets
1.Run the security system wiring to the detector location.
2.T o remove the front cover/electronic module, remove the
nameplate and loosen the screw if necessary. To remove
the nameplate, insert a small screwdriver into one of the
nameplate side slots and gently push in and pry up with
the screwdriver. See Figure 2. Then press down on the
top of the front cover with one hand, while holding the
sides at the top of the back cover and squeezing in and
pulling back with the other hand.
CAUTION
You must be free of all static electricity before
handling sensor circuit boards. Touch a
grounded, bare metal surface befor e touching
circuit boards or wear a grounding strap.
3.If necessary , set the jumpers on the circuit board. See
Setting the Jumpers.
4.Remove the appropriate wiring and mounting knockouts
from the back cover. The detector can be mounted on a
flat wall or in a corner. See Figure 3.
5.Pull the wires through the knockout holes and use screws
to attach the base to the wall. Use screw anchors if
necessary .
Corner-mount
knockouts
Flatwall-mount
knockout
Strain relief
Wiring knockout
Flat-wall mount
knockout
Figure 3. Detector Base
Wire
Corner-mount
knockouts
6.Strip 1/4 inch (6.4mm) of insulation from each wire.
7.Run each wire through the strain relief and under the
appropriate screw terminals on the base and tighten the
screws. See Figure 3.
8.Line up the tabs on the bottom of the cover/electronic
module with the corresponding tabs on bottom of the
base and snap the cover/electronic module firmly down
onto the base.
9.Tighten the screw and replace the nameplate. See
Figure 2.
10. Apply power. The green LED should light for approximately 25 seconds and then go out.
11. Walk test the coverage pattern as follows:
– Walk throughout the intended coverage area.
– Verify the detector alarms. See Understanding the LED.
Note
Most units walk test more accurately if the person
testing waits 10 seconds between tripping the unit and
walking again. This allows the detector to stabilize
between trips.
J2
Range
Figure 4. Main Circuit Board
J4
J3
Radar
only
LED Disable
2
PrecisionLine RCR-50
Setting the Jumpers
The detector provides jumpers to select the detection range
and PIR and LED operation. See Figure 4.
J2 Range -Use the jumper to cover the center pin and the
pin indicating the desired range. No jumper = 50 feet (15.2m)
and under.
50 feet (15.2m) and under 40 feet (12.2m) and under
(factory default)
50’
(15.2m)
50’
(15.2m)
SB01 Swivel-Mount Bracket
For ceiling-mount applications that require 90 degree
coverage, an optional swivel-mount bracket (SB01) is
available from GE Security. See Figure 5.
40’
(12.2m)
30’
(9.1m)
20’
(6.1m)
40’
(12.2m)
30’
(9.1m)
30 feet (9.1m) and under20 feet (6.1m) and under
50’
15.2m)
30’
(9.1m)
40’
(12.2m)
50’
(15.2m)
30’
(9.1m)
20’
(6.1m)
40’
(12.2m)
Note
You need to set J2 as close to the intended
coverage range as possible. Overshooting the
coverage area may cause false alarms.
J3 LED -
ON = LED enabled (factory default)
OFF = LED disabled
20’
(6.1m)
20’
(6.1m)
Figure 5. SBO1 Swivel-Mount Bracket
Maintaining the Detector
When installed and used properly , the detector provides many
years of service with minimal maintenance. You should walk
test the detector annually to ensure proper operation.
Clean the inside of the unit with a soft-bristled brush or
compressed air. Clean the outside with a damp (water) cloth
as needed to keep it free of dust and dirt. Always test the
unit after cleaning.
When the cover is removed, power is interrupted to the
sensor. Once the cover has been replaced, the green LED will
illuminate for 25 seconds while the sensor warms up. After
the green LED goes off, wait one minute and walk test the
sensor.
Understanding the LED
The multi-color LED located on the bottom of the detector
indicates the status of the unit as described in the following
table.
J4 PIR -
ON = Radar only enabled
OFF = PIR and Radar enabled
(factory default)
PrecisionLine RCR-50
LEDStatus
Re dPIR and Radar detection. The detector is
inalarm and the relay has switched.
GreenPIR detection only (no alarm).
YellowRadar detection only (no alarm).
In Radar-only mode:
LEDStatus
Re dRadar detection.
3
Specifications
ty
Input voltage8.5 to 18VDC (UL: 10 to 16VDC)
T ypical current27mA
Maximum current35mA
Electrical configurationForm C
Relay rating28VDC, 100mA max.
Tamper100ma, 40VDC
Detection range50' (15.2m) x 90°
T arget velocity0.5 ft/sec to 5 ft/sec
Alarm duration5 sec ± 10%
Mounting height7' to 9' (2.1m to 2.7m)
Operating temperature32° F to 122° F (0° C to 50° C)
Relative humidity5 to 93% non-condensing
Dimensions:2.8" (7.1cm) W
5.1" (13cm) H
2.3" (5.7cm) D
Weight6 oz (170g)
Colorwhite
Field wiring size12-24 A WG
Microwave frequency5.8GHz
ListingC-UL US
FCC Compliance
This device complies with Part 15 of the FCC rules.
Operation is subject to the following three conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference received,
including interference that may cause undesired
operation.
(3) Changes or modifications not expressly approved
by the party responsible for complicance could void
the user’s authority to operate the equipment.
FCC ID: CGGAA2
Product Ordering
Model NumberDescription
RCR-50Range-controlled radar, passive infrared detector with form C relay, stealth mode,
tamper contacts, 50 foot (15.2m) maximum range
Accessories
SB01Swivel-mount bracket
g
GE Securi
GE Security
12345 SW Leveton Drive
Tualatin, OR 97062
503-692-4052
USA & Canada: 800-547-2556
Tech Support
800-648-7424
FaxBack: 800-483-2495
www.ge-security.com
1036806 Rev B 04/04
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.