GE RAK3202 Installation manual

POWER CONNECTION CHART

GE 230/208 Volt Wall Plug Heater Wattage Power Supply Kit Configuration Circuit Protective Device @ 230/208 Volts
RAK3152 Tandem 15-Amp Time-Delay Fuse or Breaker 2.55/2.09 KW RAK3202 Perpendicular 20-Amp Time-Delay Fuse or Breaker 3.45/2.82 KW RAK3302 Large Tandem 30-Amp Time-Delay Fuse or Breaker 5.00/4.10 KW
230/208 VOLT ELECTRICAL SUPPLY
A power supply kit must be used to supply power to the Zoneline unit. The appropriate kit is determined by the voltage, the means of electrical connection, and the amperage of the branch circuit. See the POWER CONNECTION CHART to confirm the appropriate kit.
All wiring, including installation of the receptacle, must be in accordance with the NEC and local codes, ordinances, and regulations.
Installation instructions
RAK3152, RAK3202,
for your new
RAK3302
Power Supply Kit for Cord or Direct Connection
Before you begin – Read these instructions completely and carefully. IMPORTANT – OBSERVE ALL GOVERNING CODES AND ORDINANCES. Note to Installer – Be sure to leave these instructions with the Consumer. Note to Consumer – Keep these instructions with your Owner’s Manual for future reference.

TOOLS NEEDED

1/4Nut driver Phillips screwdriver
Wire cutter (For direct connect applications only.)
This kit is for use with 230/208 volt 5200, 5500, and
7500 Series GE Zoneline units only.
IMPORTANT NOTES
This unit must be properly grounded.
The electrical rating marked on the previously installed
Zoneline and power supply kit must be the same as the supply branch circuit.
Aluminum building wiring may present special
problems—consult a qualified electrician.
All wiring, including installation of the receptacle,
must be in accordance with the NEC and local codes, ordinances, and regulations.
Use ONLY the wiring size recommended for single
outlet branch circuit.
Proper current protection is the responsibility of
the owner.
Tandem
15 Amp
230/208 volt receptacle configuration
Perpendicular
20 Amp
Large Tandem
30 Amp
Power supply kit
Recommended branch circuit wire sizes*
Nameplate
maximum circuit AWG wire
breaker size size**
15A 14 20A 12 30A 10
AWG – American Wire Gauge * Single circuit breaker from main box ** Based on copper wire, single-insulated conductor at 60°C
NOTE: Use copper conductors only.
CAUTION:
Disconnect the electrical power
supply before wiring connections.
FOR 5200 AND 5500 SERIES MODELS ONLY
1. Remove the room cabinet by pulling it out at the bottom to release it (1); then lift it up to clear the rail along the unit top (2).
2. Insert the plug into the socket located in the wiring compartment, making sure the plug is firmly seated and the latches secure the connector assembly.
3. Position the cord and install the strain relief and screw as shown.
4. Reinstall the room cabinet front by positioning on the top brackets and securing the sides to the unit.
5. Install the attachment plug cap into the wall receptacle and check the Zoneline operation.
2
FOR 230/208 VOLT POWER CORD CONNECTIONS ONLY
FOR 7500 SERIES MODELS ONLY
1. Remove the front panel by removing the filter, taking out the four front screws, the upper two screws from the top of the panel, and the shipping screws on each side, if present. (Discard the two side shipping screws, if present.)
2. Remove the junction box cover and the junction box and discard.
3. Connect the power cord, with a loop, through the strain relief.
4. Replace the case front panel by replacing the four front screws and the two top screws. Replace the filter.
Strain relief
IMPORTANT:
Power cord must have a loop.
Remove junction box and cover
Side shipping screw
Side shipping screw
Screw
Plug into building receptacle
Yellow plug to chassis connector
Strain relief
Cord