GE RAK180W1 Owner’s Manual & Installation Instructions

OWNER’S MANUAL &
INSTALLATION INSTRUCTIONS
RAK180W1
F
THERMOSTAT
Wireless Thermostat with Occupancy Sensor
49-5000416 Rev. 1 07-19 GEA
PART OF YOUR HOME.
Whether you grew up with GE Appliances, or this is
your first, we’re happy to have you in the family.
We take pride in the craftsmanship, innovation and
design that goes into every GE Appliances product,
and we think you will too.
2 49-5000416 Rev. 1
Table of Contents
Safety Information ............................................................................................................ 4
Before You Begin .................................................................................................................5
Thermostat Installation .................................................................................................... 7
Installing the Wireless Control card ........................................................................................7
Wireless Installation ...............................................................................................................10
Wired Installation ....................................................................................................................10
Thermostat Configuration ............................................................................................11
Setting the clock .....................................................................................................................12
Entering the room number ....................................................................................................13
Configuring the Equipment Settings - Compressor Type ....................................................14
Configuring the Equipment Settings - Electric Heat ............................................................15
Configuring the Equipment Settings - Reversing Valve ......................................................16
Configuring the Energy Saving Settings...............................................................................17
Custom Energy Savings Settings .............................................................................. 19
Using the Thermostat Settings Screens ...............................................................................20
01 – FAN CONTROL MODE ................................................................................................21
02 – 1ST STAGE DIFFERENTIAL - HEAT .........................................................................22
03 – 2ND STAGE DIFFERENTIAL - HEAT ........................................................................23
04 – 1ST STAGE DIFFERENTIAL - COOL ........................................................................24
05 – INCIDENTAL OCCUPANCY THRESHOLD ...............................................................25
06 – NIGHT OCCUPANCY THRESHOLD ..........................................................................26
07 – FORCED 2ND STAGE HEATING ...............................................................................27
08 – NIGHT OCCUPANCY START .....................................................................................28
09 – NIGHT OCCUPANCY END .........................................................................................29
10 – TEMPERATURE RECOVERY TIME ..........................................................................30
11 – RECOVERY TEMPERATURE - HEAT .......................................................................31
12 – TEMPERATURE SETBACK DELAY - HEAT .............................................................32
13 – MINIMUM SETBACK TEMPERATURE ......................................................................33
14 – TEMPERATURE SETBACK DELAY - COOL ............................................................34
15 – MAXIMUM SETBACK TEMPERATURE.....................................................................35
16 – RECOVERY TEMPERATURE - COOL ......................................................................36
17 – MINIMUM SET POINT .................................................................................................37
18 – MAXIMUM SET POINT ................................................................................................38
19 – TEMPERATURE CONTROL MODE ...........................................................................39
20 – AUTO CHANGEOVER SET POINT OFFSET
(DEAD BAND) ...............................................................................................................40
21 – SETBACK SET POINTS / AUTO-RESTORE .............................................................41
22 – AUTOMATIC HUMIDITY CONTROL† ........................................................................42
23 – TEMPERATURE CALIBRATION.................................................................................43
Thermostat Maintenance .............................................................................................44
Troubleshooting ................................................................................................................45
Appendix 1 - Energy Saving Presets ......................................................................48
Technical Specifications ..............................................................................................49
Limited Warranty ..............................................................................................................50
49-5000416 Rev. 1 3
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING
WARNING
• Always turn off power at the main power supply before installing, cleaning or removing the thermostat. Failure to do so could result in electrical shock hazard.
• Do not use on voltages over 30 VAC. Higher
voltages will damage the thermostat and could cause shock or fire hazard.
FIRE AND SHOCK HAZARD
NOTICE
• All wiring must conform to local and national electrical and building codes.
• Use this thermostat only as described in this manual.
Specifications.
Electrical rating: • 24 VAC (18–30 VAC)
1 amp maximum per terminal
4 amp maximum total load
Operating temperature range: 40°F–99°F (4°C–37°C) System Configurations:
* 1 stage cool, 2 stage heat (heat pump/resistance heat)
1 stage cool, 1 stage heat (resistance heat)
Terminations: *R, C, W, Y, GH, GL, B for 2-stage heat R, C, W, Y, GH, GL, for 1-stage heat
Wiring:
*Default setting
4 49-5000416 Rev. 1
Maximum wiring length is 66ft (20 meters) for
AWG18 Maximum wiring length is 60ft (18 meters) for AWG20
Before You Begin
• Determine the appropriate installation location for the thermostat
The thermostat should face the bed area of the room.
The thermostat must not be installed near or on metal structures or surfaces including metal air ducting that may be in the wall.
0HWDOVWUXFWXUHVDQGVXUIDFHVVLJQL¿FDQWO\
reduce the range of the wireless signal.
A. Refer to the Zoneline Owner’s Manual to change
the AUX setting to 6A (class 2 mode). The unit will display “use wall thermostat” when finished.
B. Zoneline output is 24VAC. Be sure the jumper on the
wireless control card is on the AC position – jumper is connecting “R” and “C” (common) pins. This is the default position.
Other Zoneline Auxilary Control Settings for use with *DBM & *EBM Models
• Mode E: Enables Zoneline Makeup air vent door control
EDVHGRQRFFXSDQF\GHIDXOWLVRႇDQGPRGHPXVWEH
turned on to utilize this feature.
• Refer to the Zonelines Owner’s Manual for instructions on how to change this AUX setting/mode.
49-5000416 Rev. 1 5
NETWORK INSTALLATION ONLY
NOTE: This section is not required unless the thermostats are
networked
Pairing the Thermostat and the Control Card: In case of Network Installation with online management, the
thermostat and the Control Card must be paired with a Network Programmer specific to the property before the installation. Note: Thermostat and Control Card are factory paired.
Thermostat
The thermostat and control card must not be powered during the pairing procedure - remove batteries from the thermostat and unplug the control card from the HVAC unit during the pairing procedure.
• Plug one programmer connector into the thermostat;
• Plug the other programmer connector into the control card.
• Push the black button on the programmer.
The red light on the programmer should turn on and remain steadily lit.
If the red light on the programmer is blinking or is not steadily lit, unplug the programmer from the thermostat and the control card and repeat the steps above.
• Unplug the programmer from the thermostat and the control card.
6 49-5000416 Rev. 1
Network
Programmer
Programmer
Connector
Control
Card
Thermostat Installation
Installing the Wireless Control Card
• Power off the Zoneline
• Insert the Control Card wiring harness into the thermostat connection port on the front of the Zoneline control box cover.
• For Makeup Air Models (*DBM and *EBM), insert the small connector into the mating CDC Connection port next to the thermostat port. (See Drawing 1)
NOTE: If not a Makeup Air Model, DO NOT plug in the CDC/ occupancy connection.
Red Aux Set Button
Remote Thermostat Connection
CDC / Occupancy Connection
AC input
Drawing 1
49-5000416 Rev. 1 7
Thermostat Installation
Installing the Wireless Control Card (cont.)
• Using the supplied double sided tape, attach the control card to the Zoneline control box cover. (See Drawing 2)Mount the control card inside of the hvac unit. The wireless control card antenna must not be touching any metal components of the hvac unit. The wireless control card antenna must face the thermostat on the wall and be oriented so that any metal parts of the Zoneline do not obstruct the wireless communication to the thermostat and, in case of a network installation, to other wireless control cards and the server. The wireless control card must not be placed in the Zoneline condensation pan and must be mounted so it cannot fall into the condensation pan.
• For wired applications, join the common and 24VAC wires with any code-approved low voltage field supplied connection method.
Control Card
Remote Thermostat Connection
CDC/ Occupancy
Drawing 2
8 49-5000416 Rev. 1
Thermostat Installation
Wiring Table – 24V AC
Wire Color Terminal Letter Terminal Connection
Black C Common
Red R 24V
Yellow Y Compressor
White W Heat
Orange O or B Reversing Valve
Green GH Fan High
Purple GL Fan Low
Brown AUX Occupancy
NOTE: If the PTAC unit has only one (1) fan speed, connect both fan control wires – Green and Purple – to the fan terminal (G).
49-5000416 Rev. 1 9
GH OB W R Y C
AUX
GL
GH OB W R Y C
AUX
GL
Thermostat Installation
Wireless Installation
F
Mounting the thermostat to the wall
• Remove the thermostat cover;
• Use the supplied wall anchors and mounting screws to secure the thermostat to the wall;
• Insert two (2) AA-cell batteries (not supplied) into the thermostat battery compartment;
• Follow the “Thermostat Configuration” instructions starting on page 11.
• Replace the thermostat cover and screw in the locking screw.
Wired Installation
F
R C
Mounting the thermostat to the wall
• Connect R & C from HVAC unit to the corresponding wires on the harness by splicing 24VAC and common wires from the thermostat into the 24VAC and common wires to the zoneline.
• Remove the thermostat cover;
• Use the supplied wall anchors and mounting screws to secure the thermostat to the wall;
• Follow the “Thermostat Configuration” instructions starting on page 11.
• Replace the thermostat cover and screw in the locking screw.
10 49-5000416 Rev. 1
Thermostat Configuration
Once the thermostat is powered, thermostat configuration settings will appear on the thermostat screen.
In order to properly operate the HVAC unit:
• Set the thermostat clock
• Enter the room number
• Configure the equipment settings
• Select Energy Savings Preset (Zoneline custom settings are the default).
The thermostat configuration screens have a 30-second time-out. If no action is taken within thirty (30) seconds, the thermostat will exit configuration settings.
NOTE: You can access Thermostat Configuration settings at any time by pressing the “Configuration” button.
NOTE: If the thermostat is connected to a network, the settings configured online will be applied.
49-5000416 Rev. 1 11
Thermostat Configuration
Setting the thermostat clock
Hours
Set the thermostat clock to current time in 24h (Military Time) format.
• Use the “Up” and “Down” buttons to set the hours
• Press the “Fan” button to advance to the minutes setting
• Use the “Up” an “Down” buttons to set the minutes
• Press the “F/C” button to advance to the next menu
Setting the clock correctly is crucial for proper operation of the thermostat.
The thermostat clock will need to be reset each time
NOTE:
the batteries are replaced.
12 49-5000416 Rev. 1
Minutes
Thermostat Configuration
Entering the room number
Enter the room number by changing the digits on the screen. Leading zeros “0” preceding other digits will be ignored, i.e. Room number “123” should be entered as “00123”.
• Use the “Up” and “Down” buttons to change the digit;
• Press the “Fan” button to advance to the next digit;
• Press the “F/C” button to advance to the next menu;
Entering the room number correctly is crucial for proper operation of networked systems.
49-5000416 Rev. 1 13
Thermostat Configuration
Configuring the Equipment Settings - Compressor Type
Compressor Type
Use the “Up” and “Down” buttons to change the compressor type by changing the first digit
0 - No Compressor 1* - Heat pump
2 - Air Conditioner
• Press the “Fan” button to advance to the next setting;
* Indicates default setting
If the Zoneline is an AZ45 model, change the
NOTE:
compressor type to a 2.
14 49-5000416 Rev. 1
Thermostat Configuration
Configuring the Equipment Settings - Electric Heat
Electric Heat
Use the “Up” and “Down” buttons to change the Electric Heat setting by changing the second digit;
0 - No Electric Heat- All Zonelines have Electric heat -
Do not select this option.
1* - Electric Heat
• Press the “Fan” button to advance to the next setting;
* Indicates default setting
49-5000416 Rev. 1 15
Thermostat Configuration
Configuring the Equipment Settings - Reversing Valve
Reversing Heat
Use the “Up” and “Down” buttons to change the reversing valve type by changing the first digit
0 - OB contact is energized to cool 1* - OB contact is energized to heat (default operation for
Zoneline heat pump models)
Refer to the HVAC unit documentation to determine the correct OB VALVE setting.
If incorrect OB VALVE Setting is selected, the HVAC unit will turn on the heating when air conditioning is requested and turn on the air conditioning when heating is
requested.
• Press the “F/C” button to advance to the next menu
• Press the “Fan” button to advance to toggle to equipment settings.
* Indicates default setting NOTE: Zonelines OB is energized in heating mode.
16 49-5000416 Rev. 1
Thermostat Configuration
Configuring the Energy Saving Settings
Use the “Up” and “Down” buttons to select the Energy Saving preset:
E-C*: Custom Energy Savings
Refer to the APPENDIX 1 on page 48 for Energy Saving Preset details.
• For details on changing the custom settings, refer to the “Custom Energy Savings Settings” section on page 19.
E-0: Energy Savings Off - No Temperature Setback; E-1: Lowest Energy Savings; E-2: Lower Energy Savings; E-3: Standard Energy Savings; E-4: Higher Energy Savings; E-5: Highest Energy Savings;
• Press the “Power” button to save the Thermostat Configuration and start using the thermostat.
* Indicates default setting
49-5000416 Rev. 1 17
Thermostat Configuration
Testing the thermostat
Following the thermostat configuration, test if the thermostat is controlling the Zoneline unit.
• Press the “Power” button to turn the thermostat ON;
• Press the “Down” button to change the temperature set point below the current room temperature to confirm that the thermostat initiates air conditioning.
• Press the “Up” button to change the temperature set point above the current room temperature to confirm that the thermostat initiates heating.
• Change the fan speed by touching the “Fan” button to test if the thermostat is controlling the fan speed.
18 49-5000416 Rev. 1
Custom Energy Savings Settings
This thermostat comes preprogrammed to use a custom energy setting. To change any of these presets, follow the instructions below.
Accessing the Thermostat Settings
With the thermostat turned on, press and hold the “Configuration” button until the first thermostat settings screen appears. The thermostat must be turned on to access the thermostat settings.
³&RQ¿JXUDWLRQ´EXWWRQ
NOTE: If the thermostat is connected to a network, the settings configured online will be applied.
• Use the “Up” and “Down” buttons to change the setting;
• Press the “F/C” button to advance to the next setting;
• Press the “Fan” button to return to the previous setting;
• Press the “Power” button to save and exit thermostat settings.
49-5000416 Rev. 1 19
Custom Energy Savings Settings
Using the Thermostat Settings Screens
Setting Value
Screen Number
• Use the “Up” and “Down” buttons to change the setting.
• Press the “F/C” button to advance to the next setting.
• Press the “Fan” button to return to the previous setting.
• Press the “Power” button to save and exit thermostat settings.
The above is a representation of how to read the digits on the thermostat screen.
20 49-5000416 Rev. 1
Custom Energy Savings Settings
01 – FAN CONTROL MODE
Select Fan Control Mode: 00 - MANUAL - guest can select automatic or continuous
fan mode.
01* - AUTOMATIC - fan runs only when there is a
demand for heating or air conditioning.
* Indicates default setting.
49-5000416 Rev. 1 21
Custom Energy Savings Settings
02 – 1ST STAGE DIFFERENTIAL - HEAT
(0.2°F - 3.0°F; 1.0°F* default setting) Select the number of degrees** the thermostat has to sense between the automatic changeover temperature for heat and the room temperature before a call for the 1st stage heating is initiated.
** above the dead band offset (refer to page 40)
22 49-5000416 Rev. 1
Custom Energy Savings Settings
03 – 2ND STAGE DIFFERENTIAL - HEAT
(1.0°F - 2.0°F; 1.0°F* default setting) Select the difference between 1st stage heating and 2nd stage heating initiation.
49-5000416 Rev. 1 23
Custom Energy Savings Settings
04 – 1ST STAGE DIFFERENTIAL - COOL
(0.2°F - 3.0°F; 1.0°F* default setting) Select the number of degrees** the thermostat has to sense between the automatic for cool and the room temperature before a call for the 1st stage cooling is initiated.
**below the dead band offset (refer to page 40)
24 49-5000416 Rev. 1
Custom Energy Savings Settings
05 – INCIDENTAL OCCUPANCY THRESHOLD
(00 - 60; 05* default setting) Select the minimum period of time (in minutes) for which occupancy needs to be detected to enter the guest occupancy mode.
When occupancy is detected, thermostat will switch to occupied mode for a duration of “Incidental Occupancy Threshold” selected here.
If occupancy is detected for a period of time shorter than the “Incidental Occupancy Threshold” selected here, the thermostat will automatically revert to unoccupied mode at the end of the “Incidental Occupancy Threshold” period and continue to observe energy saving functions that were in effect before the room became occupied. This setting allows ignoring incidental room visits.
If occupancy is detected for a period of time longer than the “Incidental Occupancy Threshold” selected here, the thermostat will enter the guest occupancy mode. When the thermostat is in the guest occupancy mode, it will revert to unoccupied mode and initiate the setback temperature only when occupancy is not detected for the duration of the setback delay (Heat or Cool) period.
49-5000416 Rev. 1 25
Custom Energy Savings Settings
06 – NIGHT OCCUPANCY THRESHOLD
(00 - 60; 01* default setting) Select the minimum period of time (in minutes) for which occupancy needs to be detected in order to consider the room occupied during the “Night Occupancy”period.
When occupancy is detected during the “Night Occupancy Period” for longer than the “Night Occupancy Threshold” selected here, the thermostat will instantaneously switch to occupied mode.
If occupancy is detected for a period of time shorter than the “Night Occupancy Threshold” selected here, the thermostat will automatically revert to unoccupied mode and continue to observe energy saving functions that were in effect before the room became occupied.
If occupancy is detected for a period of time longer than the “Night Occupancy Threshold” selected here, the thermostat will disable the occupancy sensor and consider the room occupied until the end of the “Night Occupancy” period.
This feature ensures that energy saving functions that may affect guest comfort will not come in effect during the “Night Occupancy” period.
26 49-5000416 Rev. 1
Custom Energy Savings Settings
07 – FORCED 2ND STAGE HEATING
(00 - 60; 15* default setting) Select a number of minutes 1st stage heating will run before 2nd stage heating is automatically initiated if the guest set point is not reached and the 2nd stage heating is not initiated through differential settings.
This feature allows automatically turning on 2nd stage heating to avoid excessive compressor use.
Set to 00 to disable the feature.
49-5000416 Rev. 1 27
Custom Energy Savings Settings
08 – NIGHT OCCUPANCY START
(00 - 23; 21* default setting) Select the start time (in hours
- 24-hour clock) for “Night Occupancy”
If occupancy is detected for a period of time longer than the “Night Occupancy Threshold” during “Night Occupancy” period, the thermostat will disable the occupancy sensor and consider the room occupied until the end of the “Night Occupancy” period.
This feature ensures that energy saving functions that may affect guest comfort will not come in effect during the “Night Occupancy” period if room was occupied for a
period of time longer than “Night Occupancy Threshold”.
28 49-5000416 Rev. 1
Custom Energy Savings Settings
09 – NIGHT OCCUPANCY END
(00 - 23; 09* default setting) Select the time (in hours ­24-hour clock) for “Night Occupancy” to end.
This is the time of day the “Night Occupancy” ends and the thermostat switches back to the room sensing settings
chosen in the other occupancy modes.
49-5000416 Rev. 1 29
Custom Energy Savings Settings
10 – TEMPERATURE RECOVERY TIME
(00 - 60; 15* default setting) Select the maximum time allowed for a HVAC unit to attain temperature as defined by Heat and Cool “Recovery Temperature”.
“Temperature Recovery Time” selected here and the actual temperature recovery ability of the HVAC unit are used to calculate setback temperatures. Calculated setback temperatures maximize energy savings and at the same time ensure that a comfortable room temperature (defined as Heat and Cool “Recovery Temperature”) will be restored within the selected “Temperature Recovery Time”.
Setting the “Temperature Recovery Time” to “00”, disables temperature recovery. When temperature recovery is disabled, thermostat will use the Minimum and Maximum
Setback Temperatures as setback set points.
30 49-5000416 Rev. 1
Loading...
+ 120 hidden pages