• Always turn off power at the main power supply
before installing, cleaning or removing the
thermostat. Failure to do so could result in
electrical shock hazard.
• Do not use on voltages over 30 VAC. Higher
voltages will damage the thermostat and could cause
shock or fire hazard.
NOTICE
• All wiring must conform to local and national
electrical and building codes.
• Use this thermostat only as described in this
manual.
• Refer to the Zonelines Owner’s Manual for instructions
on how to change this AUX setting/mode.
49-5000416 Rev. 0 5
NETWORK INSTALLATION ONLY
NOTE: This section is not required unless the thermostats
are networked
Pairing the Thermostat and the Control Card:
In case of Network Installation with online
management, the thermostat and the Control
Card must be paired with a Network Programmer
specific to the property before the installation. Note:
Thermostat and Control Card are factory paired.
Thermostat
Network
Programmer
Programmer
Connector
Control
Card
The thermostat and control card must not be powered
during the pairing procedure - remove batteries from the
thermostat and unplug the control card from the HVAC
unit during the pairing procedure.
• Plug one programmer connector into the thermostat;
• Plug the other programmer connector into the control card.
• Push the black button on the programmer.
•
The red light on the programmer should turn on and
remain steadily lit.
•
If the red light on the programmer is blinking or is not
steadily lit, unplug the programmer from the thermostat
and the control card and repeat the steps above.
• Unplug the programmer from the thermostat and the
control card.
649-5000416 Rev. 0
Thermostat Installation
Installing the Wireless Control Card
• Power off the Zoneline
• Insert the Control Card wiring harness into the thermostat
connection port on the front of the Zoneline control box
cover.
• For Makeup Air Models (*DBM and *EBM), insert the
small connector into the mating CDC Connection port next
to the thermostat port. (See Drawing 1)
NOTE: If not a Makeup Air Model, DO NOT plug in the CDC/
occupancy connection.
Red Aux Set
Button
Remote
Thermostat
Connection
CDC /
Occupancy
Connection
AC input
Drawing 1
49-5000416 Rev. 0 7
Thermostat Installation
Installing the Wireless Control Card (cont.)
• Using the supplied double sided tape, attach the control
card to the Zoneline control box cover. (See Drawing 2)
Mount the control card inside of the hvac unit.
The wireless control card antenna must not be touching any
metal components of the hvac unit.
The wireless control card antenna must face the thermostat
on the wall and be oriented so that any metal parts of the
Zoneline do not obstruct the wireless communication to the
thermostat and, in case of a network installation, to other
wireless control cards and the server.
The wireless control card must not be placed in the
Zoneline condensation pan and must be mounted so it
cannot fall into the condensation pan.
• For wired applications, join the common and 24VAC
wires with any code-approved low voltage field supplied
connection method.
Control
Card
Remote
Thermostat
Connection
CDC/
Occupancy
Drawing 2
849-5000416 Rev. 0
Thermostat Installation
Wiring Table – 24V AC
Wire ColorTerminal LetterTerminal Connection
BlackCCommon
RedR24V
YellowYCompressor
WhiteWHeat
OrangeO or BReversing Valve
GreenGHFan High
PurpleGLFan Low
BrownAUXOccupancy
NOTE: If the PTAC unit has only one (1) fan speed,
connect both fan control wires – Green and Purple –
to the fan terminal (G).
49-5000416 Rev. 0 9
Thermostat Installation
GH OB W R Y C
AUX
GL
GH OB W R Y C
AUX
GL
Wireless Installation
F
Mounting the thermostat to the wall
• Remove the thermostat cover;
• Use the supplied wall anchors and mounting screws to
secure the thermostat to the wall;
• Insert two (2) AA-cell batteries (not supplied) into the
thermostat battery compartment;
• Follow the “Thermostat Configuration” instructions
starting on page 11.
• Replace the thermostat cover and screw in the locking
screw.
Wired Installation
F
R C
Mounting the thermostat to the wall
• Connect R & C from HVAC unit to the corresponding
wires on the harness by splicing 24VAC and common
wires from the thermostat into the 24VAC and common
wires to the zoneline.
• Remove the thermostat cover;
• Use the supplied wall anchors and mounting screws to
secure the thermostat to the wall;
• Follow the “Thermostat Configuration” instructions
starting on page 11.
• Replace the thermostat cover and screw in the locking
screw.
1049-5000416 Rev. 0
Thermostat Configuration
Once the thermostat is powered, thermostat configuration
settings will appear on the thermostat screen.
In order to properly operate the HVAC unit:
• Set the thermostat clock
• Enter the room number
• Configure the equipment settings
• Select Energy Savings Preset (Zoneline custom settings
are the default).
The thermostat configuration screens have a 30-second
time-out. If no action is taken within thirty (30) seconds, the
thermostat will exit configuration settings.
NOTE: You
can access
Thermostat
Configuration
settings at
any time by
pressing the
“Configuration”
button.
NOTE: If the thermostat is connected to a network, the
settings configured online will be applied.
49-5000416 Rev. 0 11
Thermostat Configuration
Setting the thermostat clock
Hours
Set the thermostat clock to current time in 24h (Military Time)
format.
• Use the “Up” and “Down” buttons to set the hours
• Press the “Fan” button to advance to the minutes setting
• Use the “Up” an “Down” buttons to set the minutes
• Press the “F/C” button to advance to the next menu
Setting the clock correctly is crucial for proper operation of
the thermostat.
The thermostat clock will need to be reset each time
NOTE:
the batteries are replaced.
Minutes
1249-5000416 Rev. 0
Thermostat Configuration
Entering the room number
Enter the room number by changing the digits on the screen.
Leading zeros “0” preceding other digits will be ignored, i.e.
Room number “123” should be entered as “00123”.
• Use the “Up” and “Down” buttons to change the digit;
• Press the “Fan” button to advance to the next digit;
• Press the “F/C” button to advance to the next menu;
Entering the room number correctly is crucial for proper
operation of networked systems.
49-5000416 Rev. 0 13
Thermostat Configuration
Configuring the Equipment Settings - Compressor Type
Compressor Type
Use the “Up” and “Down” buttons to change the compressor
type by changing the first digit
0 - No Compressor
1* - Heat pump
2 - Air Conditioner
• Press the “Fan” button to advance to the next setting;
* Indicates default setting
If the Zoneline is an AZ45 model, change the
NOTE:
compressor type to a 2.
1449-5000416 Rev. 0
Thermostat Configuration
Configuring the Equipment Settings - Electric Heat
Electric Heat
Use the “Up” and “Down” buttons to change the Electric Heat
setting by changing the second digit;
0 - No Electric Heat- All Zonelines have Electric heat -
Do not select this option.
1* - Electric Heat
• Press the “Fan” button to advance to the next setting;
* Indicates default setting
49-5000416 Rev. 0 15
Loading...
+ 35 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.