GE RAK149P2 Owner’s Manual & Installation Instructions

Page 1
Owner’s Manual &
Installation Instructions
RAK149P2
IMPORTANT SAFETY
INFORMATION ............................. 2
SPECIFICATIONS ........................ 2
INTRODUCTION OVERVIEW ..... 3
INSTALLATION INSTRUCTIONS 4
CONFIGURATION MODE ............ 8
OPERATING FUNCTIONS ......... 10
PROGRAMMING ..........................13
LOW BATTERY ...........................17
POWER FAILURE INDICATOR .18
TROUBLESHOOTING TIPS .......20
LIMITED WARRANTY ...............24
DIGITAL PROGRAMMABLE
THERMOSTATS
GE is a trademark of the General Electric Company.
Manufactured under trademark license.
49-5000517 Rev. 2 10-20 GEA
Page 2
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING
WARNING
FIRE AND SHOCK HAZARD
• Always turn off power at the main power supply before installing, cleaning or removing the thermostat. Failure to do so could result in electrical shock hazard.
• Do not use on voltages over 30 VAC. Higher voltages will damage the thermostat and could cause shock or fire hazard.
• All wiring must conform to local and national electrical and building codes.
• Use this thermostat only as described in this manual.
Specifications
Electrical rating: • 24 VAC (18–30 VAC)
1 amp maximum per terminal
4 amp maximum total load
Operating temperature range: 40°F–99°F (4°C–37°C) Temperature set range: 60°F–85°F (15°C–29°C) Accuracy: ± 1°F (± 0.5°C) System configurations:
• Factory Setting: 2-stage heat (heat pump/resistance
heat), 1-stage cool, 1-speed fan
• Alternate Setting: 1-stage heat (resistance heat),
1-stage cool, 1-speed fan
Terminations: R, C, W, Y, G, B Wiring:
Maximum wiring length is 66ft (20 meters) for
AWG18 Maximum wiring length is 60ft (18 meters) for AWG20
2 49-5000517 Rev. 2
Page 3
INTRODUCTION OVERVIEW
THERMOSTAT CONTROL
Display
Up/Down Buttons
MODE HOLD
Cool Off
Function Switch
Auto
Heat
On
Fan Auto/On Switch
Mode/Hold Switch
PARTS DIAGRAM
Display
Mounting
Hole
Reset
RESET
Button
COOL OFF
Function
Switch
49-5000517 Rev. 2 3
Up/Down Buttons
B G
Y W C
AUTO ON
HEAT
Fan Auto/On
Switch
R
Mode/Hold
Switch
Wiring
Channel
Mounting
Hole
2 “AAA” Batteries
Batteries
Page 4
INSTALLATION INSTRUCTIONS
WARNING
ELECTRICAL SHOCK HAZARD—Turn off power by unplugging the unit or by removing the fuse or switching the appropriate circuit breaker to the OFF position before removing the existing thermostat. Failure to do so could result in risk of electric shock.
PACKAGE CONTENTS/ TOOLS REQUIRED
Package includes: Thermostat on base, thermostat cover,
2 “AAA” batteries, wiring labels, screws and wall anchors. Tools needed: Drill with 3/16s bit, hammer, screwdriver and putty.
TO REMOVE EXISTING THERMOSTAT
1. Turn off power to heating and cooling system by removing
the fuse or switching off the appropriate circuit breaker.
2. Remove cover of old thermostat. This should expose the wires.
3. Label the existing wires with the enclosed wire labels
before removing wires.
4. After labeling wires, remove wires from wire terminals.
5. Remove existing thermostat base from wall.
6. Refer to the following section for instructions on how to
install this thermostat.
TO INSTALL THERMOSTAT IMPORTANT:
local and national building and electrical codes and ordinances. Note: Mount the thermostat about five feet above the floor. Do
not mount the thermostat on an outside wall, in direct sunlight, behind a door or in an area affected by a vent or duct.
4 49-5000517 Rev. 2
Thermostat installation must conform to
Page 5
INSTALLATION INSTRUCTIONS
TO INSTALL THERMOSTAT (cont.)
1. Turn off power to the heating and cooling system
by removing the fuse or switching off the appropriate circuit breaker.
2. Move the Function switch on the thermostat to Off.
3. Remove the cover by inserting and twisting a coin or
screwdriver in the slots on the top of the thermostat.
4. Put thermostat base against the wall where you plan to mount it. Make sure wires will feed through the wire opening in the base of the thermostat.
5. With the base level, mark the placement of the mounting holes.
6. Set thermostat base and cover away from working area.
7. Using a 3/16s drill bit, drill holes in the locations you have
marked for mounting.
8. Use a hammer to tap supplied anchors in mounting holes.
9. Align thermostat base with mounting holes and feed the
control wires through the wire opening.
10. Seal hole for wires behind thermostat with non-flammable insulation or putty, or use a wall plate obtainable from a local hardware or home building store.
11. Use supplied screws to mount thermostat base to wall.
12. Insert stripped, labeled wires in matching wire terminals by
pressing on the corresponding terminal contact. See the “Wiring Diagrams” section of this manual.
CAUTION
does not touch other wires.
13. Gently tug wire to be sure of proper connection. Double
check that each wire is connected to the proper terminal.
49-5000517 Rev. 2 5
Make sure exposed portion of wires
Page 6
INSTALLATION INSTRUCTIONS
TO INSTALL THERMOSTAT (cont.)
14. Insert two “AAA” batteries into battery holder. Verify that
they are oriented as shown on battery holder.
15. Replace cover on thermostat by snapping it in place.
16. Plug the unit in or turn on power to the system at the main
service panel.
17. Test thermostat operation as described in the “Testing the Thermostat” section.
Wiring diagrams
Table 1: Terminals for five wires 1-stage heat/1­stage cool system
Note: Connect G terminal of thermostat to Zoneline
GL terminal for low fan speed or terminal GH for high fan speed. Only one can be selected.
6 49-5000517 Rev. 2
Page 7
INSTALLATION INSTRUCTIONS
Table 2: Terminals for six wires 2-stage heat/1­stage cool system
B G Y W C R
Note: Connect G terminal of thermostat to Zoneline GL terminal for low fan speed or terminal GH for high fan speed. Only one can be selected.
49-5000517 Rev. 2 7
Page 8
Configuration mode
The configuration mode is used to set the thermostat to match the heating/cooling system. This thermostat will function with up to 2-stage heatpump systems. To configure the thermostat, perform the following steps:
NOTE: Operation being set will blink in the display.
1. Slide the Function switch to the OFF position.
<
2. Simultaneously hold the for 6 seconds while the thermostat is in OFF mode.
3. Press the < or > button to change settings within each screen.
4. Press the Hold button to advance to the next screen. Note: The Mode button will return you to the previous screen.
5. To save the changes and exit configuration mode, slide the Function switch to Heat or Cool.
Configuration Mode Settings
The setup screens for Configuration Mode are as follows:
1. Temperature Scale (F or C)—Choose Fahrenheit or Celsius.
Press the < or > button
to select.
Press the Hold button to advance to the next screen.
NOTE: Default factory setting is Fahrenheit.
2. Heat System—Check model number on the GE PTAC
chassis to determine the primary heating method.
AZ65H/95H***** are heat pumps and is the thermostat factory
setting.
AZ45E/95E***** are electric heat models and will require a
mode setting change.
To change the heating mode configuration, press the <or
>
button. Select HPb screen for heat pump or select ELE
screen for electric heat.
Press the Hold button to advance to the next screen.
and > buttons in
8 49-5000517 Rev. 2
Page 9
Configuration mode
3. Temperature Differential—Stage 1—(1–9°F) (1–5°C)
Set the number of degrees between the “setpoint” temperature and the “turn on” temperature for first stage.
Press the Press the HOLD button to advance to the next screen.
Note: Default factory setting is 2°F/1°C for each stage.
4. Temperature Differential—Stage 2 (1–9°F/1– 5°C) Heat Pump (HPb) only
Set the number of degrees between when stage 1 turns on and stage 2 turns on.
Press the
value.
Press the HOLD button to advance to the next screen. Note: Default factory setting is 2°F/1°C for each stage.
5. Minimum Cool Setpoint (60, 64, 66, 68, 70, 72, 74, 76°F) (15, 17, 19, 20, 21, 22, 23, 24°C)
Adjust to control the minimum Cool set
temperature allowed.
Press the Press the Hold button to advance to the next screen. Note: Default factory setting is 60°F/15°C.
6. Maximum Heat Setpoint (65, 70, 72, 74, 76, 78, 80, 85°F) (18, 21, 22, 23, 24, 26, 27, 29°C)
Adjust to control the maximum Heat set
temperature allowed.
Press the Press the Hold button to advance to the next
screen.
Note: Default factory setting is 85°F/29°C.
7. Room temperature offset (+9°F to –9°F) (+5°C to –5°C)
Adjust to calibrate displayed room temperature
to match actual room temperature.
Press the Press the Hold button to advance to the next screen. Note: Move the Function switch to Heat or Cool position to lock the
settings into memory.
Note: Default factory setting is 0°F/0°C.
<
or > button to set differential value.
<
or > button to set differential
<
or > button to select.
<
or > button to select.
<
or > button to select.
:
:
49-5000517 Rev. 2 9
Page 10
Operating functions
Off
• In this mode, the thermostat will
not turn on the heating or cooling devices (manual fan can operate).
Off is also used to access Setup
and Program modes.
Cool
• In this mode, the thermostat controls the
cooling system.
• Press the Mode button to enter and exit
the Program Cool mode.
• In Program Cool mode (PROG displays), the thermostat
will follow the program schedule that is stored in memory.
Heat
• In this mode, the thermostat controls the
heating system.
• Press the Mode button to enter/exit the
Program Heat mode.
• In Program Heat mode (PROG displays), the thermostat
will follow the program schedule that is stored in memory.
Hold
• When in Programmable Cool or Programmable Heat,
you can lock in the present settings indefinitely by pressing the Hold button once (PROG flashes). Press Hold button again to leave Hold mode (PROG solid). For a temporary Hold period, raise or lower set temperature to desired set temperature. The thermostat will automatically return to programmed set temperature after 2 hours.
:
PM
OFF
COOL
:
PM
PROG
HEAT
:
PM
PROG
10 49-5000517 Rev. 2
Page 11
Testing the thermostat
Once the thermostat is installed, it should be thoroughly tested.
CAUTION
Do not use air conditioning when the
outdoor temperature is below 50 degrees. This can damage the a ir conditioning system.
Note: Before testing the thermostat, move the Fan Auto/On switch to the Auto position.
Fan Test
1. With Function switch set to Off, slide Fan Auto/On switch to On position.
2. Indoor fan turns on.
3. Slide Fan Auto/On switch to Auto
position.
4. Indoor fan turns off.
Cool Test
1. Slide Function switch to Cool position.
COOL
:
PM
Cool mode screen is displayed.
2. Adjust set temperature so it is 5 degrees below room
temperature.
3. Air conditioning should come on within a few seconds.
4. Adjust the set temperature so it is 2 degrees above the
room temperature and the A/C should turn off. Note: There is a 3 minute time delay and a 3 minute minimum run time for the compressor when it turns on/off. (On some models, the fan may also have a minimum run time/off time delay).
49-5000517 Rev. 2 11
Page 12
Testing the thermostat
Heat Test
1. Slide Function switch to Heat
position. Heat mode screen is displayed.
2. Adjust set temperature so it is 5 degrees above room temperature.
3. Heat should come on within a few seconds.
4. Adjust the set temperature so it is 2 degrees below
the room temperature and the heat should turn off. Note: There is a 3 minute time delay and a 3 minute minimum run time for the compressor when it turns on/off. (On some models, the fan may also have a minimum run time/off time delay).
HEAT
:
PM
12 49-5000517 Rev. 2
Page 13
Programming
Factory Programming Settings
The programmable thermostat comes preprogrammed with the following schedule:
MONDAY MORN 6:00 AMDAY 8:00 AMEVE 6:00 PMNITE 10:00 through HEAT 70R F HEAT 62R F HEAT 70R F HEAT 62R F
SUNDAY COOL 78R F COOL 85R F COOL 78R F COOL 82R F
Setting the time and day of the week
The time and day of the week must be set for the program schedule to operate correctly.
1. Slide the Function switch to the Off position.
:
PM
OFF
2. Press the Hold button in for 6 seconds.
3. Press the
<
or > button to adjust
:
PM
the time in hours. Press the Hold button once. Now press the
<
or > button to adjust
the time in minutes.
4. Press the Hold button while the time is displayed. The display shows the day currently set on the thermostat (01 = Monday,
:
TODAY
PM
02 = Tuesday, etc.).
5. Press the
<
or > button to set the current day of the
week.
6. Press the Hold button to go to the programming schedule or slide the Function switch to Cool or Heat positions to lock the values into memory.
PM
49-5000517 Rev. 2 13
Page 14
Programming
Program Overview The programmable thermostat has four periods (MORN,
DAY, EVE, NITE) that are customizable for each day of the
week. Each period will have a set time, heat temperature and cool temperature. The thermostat monitors the day and time, while maintaining the specific conditions that you have chosen for each period in the program.
Note: Operation being set will blink in the display.
1. Place the Function switch in the Off position.
2. Press the Hold button in
for 6 seconds.
3. Press the Hold button 3 times.
DAY (01–07) and PROG is displayed.
4. Press the the day you want to program (01-05 = Monday – Friday individually, 67 = program Saturday and Sunday at the same time, 17 = program every day of the week at the same time, 15 = program Monday – Friday at the same time).
5. Press the Hold button to advance to the next parameter.
• Period is displayed (MORN, DAY,
EVE, NITE).
Note: You can always press the Mode
button to return to the previous parameter.
6. Press the display should blink the period of the day.
7. Press the Hold button to advance to the next parameter.
Set time is displayed.
<
or > button to change
<
or > button to change period of day. The
DAY
PROG
DAY
PROG MORN
:
AM
PROG MORN
8. Press the Hold button once, and then press the
<
or > button to adjust hours. Press the
<
or > buttons
to adjust minutes.
14 49-5000517 Rev. 2
Page 15
9. Press the Hold button to advance to the next screen parameter.
Heat temperature is displayed (60°F
to 85°F) / (15°C to 29°C).
Note: Transitions required after 11:59
HEAT
:
DAY
AM
PROG MORN
PM must be programmed in the next days MORN period.
10. Press the
11. Press the Hold button to advance to
the next screen.
Cool temperature is displayed
(60°F to 85°F) / (15°C to 29°C).
<
or > button to adjust heat set temperature.
COOL
:
DAY
AM
PROG MORN
12. Press the
<
or > button to adjust cool set temperature.
13. Press the Hold button to advance to the next screen.
Repeat steps 1–13 to program each day of the week
individually.
Note: When programming is complete, slide the Function
switch to Heat or Cool to exit Programming Mode.
49-5000517 Rev. 2 15
Page 16
Programming
Use the following personal program schedule to record your settings:
MONDAY 01
MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL
TUESDAY 02
MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL
WEDNESDAY 03
MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL
THURSDAY 04
MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL
FRIDAY 05
MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL
SATURDAY 06
MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL
SUNDAY 07
MORN DAY EVE NITE HEAT HEAT HEAT HEAT COOL COOL COOL COOL
16 49-5000517 Rev. 2
Page 17
Low battery indicator
The programmable thermostats with battery backup have a low battery warning screen.
Low battery warning
The thermostat will display a low battery indication. The low battery warning will be flashing until batteries are replaced.
49-5000517 Rev. 2 17
Page 18
Power failure Indicator
The programmable thermostats with battery backup also will indicate a main power failure when the 24 VAC power from the room air conditioner is not present.
Power failure
The thermostat will display a power failure indication (“PF”) on the screen.
Note: If “PF” is displayed, it means the 24 VAC power to the thermostat is lost.
18 49-5000517 Rev. 2
Page 19
Notes
49-5000517 Rev. 2 19
Page 20
Troubleshooting tips
Problem Solution No Display Check for 24 VAC at thermostat and-
System fan does not come on properly
All thermostat buttoms are inoperative
Thermostat turns on
DQGRႇWRRIUHTXHQWO\
Program schedule activates at the wrong time
Thermostat does not follow program
352*ÀDVKHVLQ+ROG
mode) Fan runs continuously Check Fan Auto/On switch. If set to ON
Room temperature is not correct
Compressor doesn’t UXQRUWXUQRႇLPPH­diately when changing function or setting
batteries; display is blank when 24 VAC is not present and batteries are bad.
Verify that wiring is correct.
Verify that 24 VAC is present; unit will not operate when 24 VAC is not present.
$GMXVWWHPSHUDWXUHGLႇHUHQWLDOVHH &RQ¿JXUDWLRQ0RGH6HWWLQJ7HPSHUD­WXUH'LႇHUHQWLDO6WDJHDQG6WDJH
sections). Check time (AM/PM) set on thermostat
(see Programming).
Verify that it is in Program mode; PROG displays solid; check time (AM/ PM); check if in Hold mode (PROG
ÀDVKLQJ
Press Hold button to remove from Hold mode
position, fan will run continuously. Verify that wall hole is plugged with
SXWW\RULQVXODWLRQWRSUHYHQWDLUÀRZ
from the wall cavity. Adjust Temperature
2ႇVHWVHH&RQ¿JXUDWLRQ0RGH5RRP WHPSHUDWXUHRႇVHWVHFWLRQ
There is a 3 minute time delay and a 3 minute minimum run time for the
FRPSUHVVRUZKHQLWWXUQVRQRႇ
20 49-5000517 Rev. 2
Page 21
Troubleshooting tips
Problem Solution Fan doesn’t run or turn
RႇLPPHGLDWHO\ZKHQ
changing function or setting
displays on screen
“PF” displays on screen.
Display reads “12:00 PM”
Problem not listed above
This is normal. On some models, the
IDQPD\KDYHDPLQLPXPUXQWLPHRႇ
time delay.
Replace batteries with 2 fresh “AAA” alkaline batteries.
Check for 24 VAC at thermostat.
Set clock/time
Press the Reset button once. Reset button function: time, day and mode will be changed to the factory settings. Display is refreshed.
49-5000517 Rev. 2 21
Page 22
Notes
22 49-5000517 Rev. 2
Page 23
Notes
49-5000517 Rev. 2 23
Page 24
THERMOSTAT LIMITED WARRANTY
Staple your receipt here.
Proof of the original purchase date is
needed to validate the warranty.
For The Period Of: GE Appliances Will Replace:
One Year Full Replacement of the thermostat which fails
From the date of the due to a defect in materials or workmanship. original purchase For Warranty replacement, contact your distributor.
What GE Appliances Will Not Cover:
Ŷ Service trips to your location. Ŷ Improper installation. If you have an installation problem, contact
\RXULQVWDOOHU<RXDUHUHVSRQVLEOHIRUSURYLGLQJDGHTXDWHHOHFWULFDO
connections to the product.
Ŷ Failure of the product resulting from modifications to the product or
due to unreasonable use, including failure to provide reasonable and necessary maintenance.
Ŷ In commercial locations, labor necessary to move the unit, after it has
been initially installed, to a location where it is accessible for service by an individual technician; or, if th e instructions included in this manual have been disregarded.
Ŷ Replacement of location fuses or the resetting of circuit breakers. Ŷ Damage to the product caused by improper power supply voltage,
accident, fire, floods or acts of God.
Ŷ ,QFLGHQWDORUFRQVHTXHQWLDOGDPDJHFDXVHGE\SRVVLEOHGHIHFWVZLWK
this thermostat.
EXCLUSION OF IMPLIED WARRANTIES—Your sole and exclusive remedy is product exchange as provided in this Limited Warranty. Any implied warranties, including the implied warranties of merchantability or fitness for a particular purpose, are limited to one year or the shortest period allowed by law.
This limited warranty is extended to the original purchaser and any succeeding owner for p roducts purchased for use within the USA and Canada. In Alaska, the limited warranty excludes the cost of shipping or service calls to your site.
Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages. This limited warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province. To know what your legal rights are, consult your local, state or provincial consumer affairs office or your state’s Attorney General.
For service in Canada, contact your distributor.
Warrantor: GE Appliances, a Haier company
Louisville, KY 40225
24 49-5000517 Rev. 2
Loading...