STEP 1
Preparation of the wall
The wall case should be installed during construction
and lintels should be used to support the block above
the wall case. The case will not support the concrete
block or brick. The case is modular in height and
width:
Height — Fits 2 courses concrete block
— Fits 6 courses standard brick
— Fits 5 courses jumbo brick
Width — Fits approximately 3 stud spaces.
For existing construction, wall openings must be
made. Wall openings of the proper dimensions are
essential to avoid the necessity of fillers or additional
framing.
Note:
Use lintel to support brick, block, etc. above the air
conditioner case. (If directly under a window sill the
use of a lintel may not be necessary.)
2
STEP 2
Preparation of the case
Do not remove the cardboard stiffener inside the
case until the chassis is installed.
If field supplied case angles are to be used and must
be installed, proceed as follows:
1. Position the case angles around top and sides of
the case at the desired location (front to rear) with
angles facing toward rear (outside). Position the
case angles vertically on each side of the case to
provide a level installation.
2. Mark the case through the holes in the case angles.
3. Drill 5/32″diameter holes at marked locations
on the case and assemble the angles using only
10×1/2″ screws. Install the screws from the
outside of the case.
4. Do not drill any holes in bottom of the case.
Case
Case angle
Block
Roomside
Brick
Main stud
Jack studs
Jack stud
Cripple
Finished floor
Sub-floor
“D”*
Adjust
framing
to secure
this
dimension
(*See chart
on page 1)
Header—4″×4″ or
2—2″×4″ on edge
16
1
⁄4″ Min.
42
1
⁄4″ Min.
MINIMUM
FINISHED
OPENING
DIMENSIONS CASE DIMENSIONS
Height Width Height Width Depth
16
1
⁄4″ 421⁄2″
16″ 42″ 133⁄4″16″ 24″ 28″ 31″
16
1
⁄4″ 421⁄4″
Using
Case Angles
NOT Using
Case Angles