GE PVB98DT Specification

GE PVB98DT Specification

PVB98DT

GE ProfileSeries 36" Telescopic Downdraft System

Dimensions and Installation Information (in inches)

Note: Telescopic downdraft vents are not recommended to be installed with cooktops that are flush mounted.

Approved for use with the following GE Profile, and GE® Series cooktops–36" electric models, 36" gas sealed burner models and 36" induction models.

Not Approved for use with standard burner gas cooktops.

Note: The cooktop must be at least 26" deep with a flat surface area of 23-1/2" or more, front to back. In addition, other clearances to the front edge of the countertop must be considered.

Note: Dimensions shown are for reference only. Before cutting out countertop, refer to instructions packed with downdraft and cooktop.

Note: Installation on cabinets/countertops against the wall will not be possible in most applications. Against the wall installations are limited to dimension requirements. Refer to installation instructions packed with product for further details.

JXRB67 Indoor Remote Accessory.

Optional accessory may be ordered for installation of motor and blower assembly in an indoor remote location.

For answers to your Monogram, GE ProfileSeries or GE® Series appliance questions, visit our website at geappliances.com or call GE Answer Center® service, 800.626.2000.

Venting Options (in inches)

Through the Floor

In Cabinet Discharge

 

(Down)

In Cabinet Discharge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In Cabinet Discharge

(Right)

(Left)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Listed by

Underwriters

Laboratories

Specification Revised 10/15

PVB98DT

GE ProfileSeries 36" Telescopic Downdraft System

Venting Duct Information

Duct Pieces

Equivalent Length*

Duct Pieces

Equivalent Length*

6" ROUND

1 ft. (per foot length)

3-1/4" X 10"

2 ft.

TO 6" ROUND

STRAIGHT

 

 

TRANSITION

 

 

 

 

3-1/4" X 10"

 

6" ROUND

4 ft.

1 ft. (per foot length)

TO 3-1/4 X 10"

STRAIGHT

TRANSITIONS

 

 

 

90° ELBOW

 

6"

 

3-1/4" X 10"

4 ft.

12 ft.

TO 6" ROUND

90° ELBOW

TRANSITION

 

 

 

90° ELBOW

 

6"

7 ft.

6" ROUND

24 ft.

WALL CAP

45° ELBOW

 

 

WITH DAMPER

 

 

 

 

3-1/4" X 10"

 

3-1/4" X 10"

24 ft.

14 ft.

WALL CAP

90° ELBOW

WITH DAMPER

 

 

 

3-1/4" X 10"

12 ft.

6" ROUND

33 ft.

45° ELBOW

ROOF CAP

 

3-1/4" X 10"

33 ft.

SHOULD NOT EXCEED 100 EQUIVALENT FT.

*Equivalent length of duct pieces are based on actual

45° ELBOW

 

 

test conducted by GE Evaluation Engineering and

6" ROUND

2 ft.

reflect requirements for good venting performance

TO 3-1/4 X 10"

with a downdraft system rated at 390 CFM

TRANSITIONS

 

 

 

 

Plan the Ductwork

1.This downdraft blower system is designed for use with 3-1/4" x 10" ductwork (can be transitioned to 6" round). Two different discharge directions are available with side- to-side adjustment for the accurate alignment of ductwork.

2.For best performance: choose the ducting option which allows the shortest length of ductwork and a minimum number of elbows and transitions. Check location of floor joists, wall joists, wall studs, electrical wiring or plumbing for possible interference.

Right discharge

Left discharge (as shipped)

Steps to Determine Flexible Ducting’s Equivalent Length

1.Measure the actual amount of offset (Maximum 3" recommended). The effect upon airflow is dependent upon the amount of offset.

2.Calculate the equivalent ducting allowances using: (__in. offset) x (14 ft. per inch) =__ft. equivalent length.

3.Ensure that the total equivalent length of ducting does not exceed the maximum recommendation of 100 feet.

For answers to your Monogram, GE ProfileSeries or GE® Series appliance questions, visit our website at geappliances.com or call GE Answer Center®

service, 800.626.2000. Specification Revised 10/15