PVB98DT
GE Profile
™
Series 36" Telescopic Downdraft System
dImeNsIoNs ANd INstAllAtIoN INfoRmAtIoN (IN INches)
Note: Telescopic downdraft vents are not
recommended to be installed with cooktops that
are flush mounted.
Approved for use with the following GE Profile™,
and GE® Series cooktops–36" electric models,
36" gas sealed burner models and 36" induction
models.
Not Approved for use with standard burner gas
cooktops.
Note: The cooktop must be at least 26" deep
with a flat surface area of 23-1/2" or more, front
to back. In addition, other clearances to the
front edge of the countertop must be considered.
Note: Dimensions shown are for reference
only. Before cutting out countertop, refer to
instructions packed with downdraft and cooktop.
Note: Installation on cabinets/countertops
against the wall will not be possible in most
applications. Against the wall installations are
limited to dimension requirements. Refer to
installation instructions packed with product
for further details.
VeNtINg optIoNs (IN INches)
thRough the flooR
IN cABINet dIschARg e
(RIght)
IN cABINet dIschARg e
(dowN)
IN cABINet dIschARg e
(left)
JXRB67 INdooR Remote AccessoRy.
Optional accessory may be ordered for installation
of motor and blower assembly in an indoor remote
location.
For answers to your Monogram, GE Profile™ Series
or GE® Series appliance questions, visit our website
at geappliances.com or call GE Answer Center®
service, 800.626.2000.
Listed by
Underwriters
Laboratories
Speci fication Revised 10/15
![](/html/ad/ad55/ad55173c97e1f79110d2fc79c69efe020ec9176405cf0f3844dd35757eac079d/bg2.png)
PVB98DT
6" ROUND
STRAIGHT
3-1/4" X 10"
TO 6" ROUND
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
6" ROUND
STRAIGHT
3-1/4" X 10"
STRAIGHT
6"
90° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
STRAIGHT
3-1/4" X 10"
STRAIGHT
6"
90° ELBOW
6"
45° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
6" ROUND
STRAIGHT
3-1/4" X 10"
STRAIGHT
3-1/4" X 10"
90° ELBOW
6"
90° ELBOW
6"
45° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
3-1/4" X 10"
WALL CAP
WITH DAMPER
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
6" ROUND
STRAIGHT
3-1/4" X 10"
STRAIGHT
3-1/4" X 10"
90° ELBOW
3-1/4" X 10"
45° ELBOW
6"
90° ELBOW
6"
45° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
6" ROUND
ROOF CAP
3-1/4" X 10"
WALL CAP
WITH DAMPER
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
6" ROUND
STRAIGHT
3-1/4" X 10"
STRAIGHT
3-1/4" X 10"
90° ELBOW
3-1/4" X 10"
45° ELBOW
3-1/4" X 10"
45° ELBOW
6"
90° ELBOW
6"
45° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
6" ROUND
ROOF CAP
3-1/4" X 10"
WALL CAP
WITH DAMPER
6" ROUND
ROOF VENT
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
6" ROUND
STRAIGHT
3-1/4" X 10"
STRAIGHT
3-1/4" X 10"
90° ELBOW
3-1/4" X 10"
45° ELBOW
3-1/4" X 10"
45° ELBOW
6"
90° ELBOW
6"
45° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
6" ROUND
ROOF CAP
3-1/4" X 10"
WALL CAP
WITH DAMPER
6" ROUND
ROOF VENT
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
3-1/4" X 10"
WALL CAP
WITH DAMPER
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
6" ROUND
ROOF CAP
3-1/4" X 10"
WALL CAP
WITH DAMPER
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
3-1/4" X 10"
TO 6" ROUND
TRANSITION
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
3-1/4" X 10"
WALL CAP
WITH DAMPER
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
90° ELBOW
3-1/4" X 10"
WALL CAP
WITH DAMPER
3-1/4" X 10"
TO 6" ROUND
TRANSITION
90° ELBOW
6" ROUND
WALL CAP
WITH DAMPER
GE Profile
VeNtINg duct INfoRmAtIoN
duct pIeces equIVAleNt leNgth* duct pIeces equIVAleNt leNgth*
™
Series 36" Telescopic Downdraft System
3-1/4" X 10"
TO 6" ROUND
TRANSITION
6" ROUND
TO 3-1/4 X 10"
TRANSITIONS
3-1/4" X 10"
STRAIGHT
1 ft. (per foot length)
1 ft. (per foot length)
12 ft.
° ELBOW
7 ft.
2 ft.
4 ft.
4 ft.
24 ft.
plAN the ductwoRk
1. This downdraft blower system is designed for use with
3-1/4" x 10" ductwork (can be transitioned to 6" round).
Two different discharge directions are available with sideto-side adjustment for the accurate alignment of ductwork.
2. For best performance: choose the ducting option which
allows the shortest length of ductwork and a minimum
number of elbows and transitions. Check location of floor
joists, wall joists, wall studs, electrical wiring or plumbing
for possible interference.
14 ft.
12 ft.
33 ft.
2 ft.
24 ft.
6" ROUND
ROOF CAP
33 ft.
should Not eXceed 100 equIVAleNt ft.
* Equivalent length of duct pieces are based on actual
test conducted by GE Evaluation Engineering and
reflect requirements for good venting performance
with a downdraft system rated at 390 CFM
For answers to your Monogram, GE Profile™ Series
or GE® Series appliance questions, visit our website
at geappliances.com or call GE Answer Center®
service, 800.626.2000.
Right
discharge
Left discharge
(as shipped)
steps to deteRmINe fleXIBle ductINg’s
equIVAleNt leNgth
1. Measure the actual amount of offset (Maximum 3"
recommended). The effect upon airflow is dependent upon
the amount of offset.
2. Calculate the equivalent ducting allowances using:
(__in. offset) x (14 ft. per inch) =__ft. equivalent length.
3. Ensure that the total equivalent length of ducting does not
exceed the maximum recommendation of 100 feet.
Speci fication Revised 10/15