GE PTR Installation Guide

GE
g
READ THOROUGHLY BEFORE INSTALLING
Lighting Solutions
WARNING
Risk of electric shock
Turn power off before servicingsee instructions
GENERAL
This luminaire is designed for use in outdoor applications and must adhere to 25°C Max ambient temperature limita­tion. Install and maintain it according to the following recommendations.
GEH-5790
INSTRUCTIONS
Patriarch™ Luminaire
A. MOUNTING
CAUTION
Unit will fall if not installed properly
Follow installation instructions
1. Place fixture on appropriately sized tenon.
2. Tighten fixture set screws to 18 to 22 ft-lbs. of torque.
3. Install Lamp (see section C of instruction sheet for lamp
instructions)
OPTIONAL PHOTO CONTROL
(Ordered separately)
Rotate base casting so that
PE window points away
from other light sources.
4. Install refractor making sure that asymmetric refractors are properly oriented with respect to their “house side” or “street side” labeling.
5. Tighten globe set screws to lightly contact globe.
6. Wire unit (see section B of instruction sheet for wiring instructions)
7. Move slide bracket to closed position if it is in open position and if no cord is present. (See illustration)
8. Close door securely.
PROTECTIVE SHIELD
SLIDE BRACKET Move bracket to open position
(as shown) for electrical cord passage. Be sure bracket is in closed position when no electrical cord is in place.
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to GE Lighting Solutions.
B. WIRING
Make all electrical connections in accordance with the National Electrical Code and any applicable local code requirements.
Verify that supply voltage is correct by comparing it to nameplate.
IF SINGLE VOLTAGE:
All single voltage ballasts are pre-wired such that user need only connect the supply conductors.
IF MULTIVOLT: (120/208/240/277 volts)
Connect the ballast lead with the insulated terminal to the desired voltage terminal as indicated on the ballast terminal nameplate.
IF MULTIWATT:
Multiwatt ballasts are available in various combinations of wattage. See wiring instructions on wiring tag inside the luminaire.
Optional Features such as fusing and photocontrols are voltage specific.
Replace power fuses only with fuses of the same type and rating.
When changing voltage on reconnectable units, move only the lead with the insulated connector.
C. LAMPS
Use only lamps specified on nameplate. Observe lamp manufacturer’s recommendations and restrictions on lamp operation, particularly ballast type, burning position, etc.
LAMP TIGHTNESS: The lamp should be securely inserted to NEMA-EEI specified torque of 35 inch-pounds, which is best achieved by very firmly tightening to insure applica­tion of sufficient torque. Tightening must be sufficient to fully depress and load center contact of socket.
NOTE: Use of lubricants on lamp base or sockets can cause rapid lamp failure and voids fixture warranty.
D. MAINTENANCE AND CLEANING
It will occasionally be necessary to clean the refractor to maintain light levels. Frequency of cleaning will depend on ambient dirt level and minimum light level which is acceptable to the user. The refractor should be washed in a solution of warm water and mild, nonabra­sive household detergent, rinsed with clean water and wiped dry.
The light output of a luminaire is dependent on the age of the lamp. In applications where the light level is critical, it may be desirable to replace lamps before they burn out. The lamp manufacturer can provide data showing how the lamp light output decreases with use.
CAUTION
Risk of burn
Allow lamp/fixture to cool before
handling
INTERNAL GLASS REFRACTOR
(optional)
Install before lamp. Find street
side labeling and align
accordingly. Secure with
supplied clamp.
FUSE BLOCK
(optional)
SOCKET Lamps should be tightened to
35 inch-pounds torque.
BALLAST CANNISTER For multivolt ballasts,
see above instructions.
SIMPLEX RECEPTACLE (optional)
TERMINAL BOARD
g
LINE
GROUND
LINE or NEUTRAL
GE Lighting Solutions • 1-888-MY-GE-LED • www.gelightingsolutions.com
16943533----888
GE Lighting Solutions is a subsidiary of the General Electric Company. Evolve and other trademarks belong to GE Lighting Solutions. The GE brand and logo are trademarks of the General Electric Company. © 2011 GE Lighting Solutions. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.
35-201578-Z9 (07/01)