Figure 131:VTS logic (P642 with 2 single-phase VTs)288
Figure 132:VTS logic (P643 and P645 with 3-phase VTs)289
Figure 133:CTS restraint region increase291
Figure 134:CTS logic diagram292
Figure 135:TCS Scheme 1294
Figure 136:PSL for TCS Scheme 1295
Figure 137:TCS Scheme 2295
Figure 138:PSL for TCS Scheme 2296
Figure 139:TCS Scheme 3296
Figure 140:PSL for TCS Scheme 3297
Figure 141:Scheme Logic Interfaces303
Figure 142:Trip LED logic307
Figure 143:RS485 biasing circuit318
Figure 144:Remote communication using K-Bus319
Figure 145:IED attached to separate LANs322
Figure 146:IED attached to redundant Ethernet star or ring circuit323
Figure 147:IED, bay computer and Ethernet switch with self healing ring facilities324
Figure 148:Redundant Ethernet ring architecture with IED, bay computer and Ethernet switches324
Figure 149:Redundant Ethernet ring architecture with IED, bay computer and Ethernet switches
after failur
e
324
Figure 150:Dual homing mechanism325
Figure 151:Application of Dual Homing Star at substation level326
Figure 152:IED and REB switch IP address configuration327
Figure 153:DIP switches for setting IP address327
Figure 154:Control input behaviour339
Figure 155:Manual selection of a disturbance record355
Figure 156:Automatic selection of disturbance record - method 1356
xxP64x-TM-EN-1.3
Page 23
P64xTable of Figures
Figure 157:Automatic selection of disturbance record - method 2357
Figure 158:Configuration file extraction358
Figure 159:Data file extraction359
Figure 160:Data model layers in IEC61850365
Figure 161:GPS Satellite timing signal371
Figure 162:Default display navigation382
Figure 163:Location of battery isolation strip395
Figure 164:Rack mounting of products396
Figure 165:Terminal block types398
Figure 166:40TE case dimensions404
Figure 167:60TE case dimensions405
Figure 168:80TE case dimensions406
Figure 169:RP1 physical connection422
Figure 170:Remote communication using K-bus423
Figure 171:Operating Characteristic Diagram429
Figure 172:Trip Time Test Plane429
Figure 173:Harmonic Restraint Test Plane430
Figure 174:Possible terminal block types442
Figure 175:Front panel assembly444
P64x-TM-EN-1.3xxi
Page 24
Table of FiguresP64x
xxiiP64x-TM-EN-1.3
Page 25
CHAPTER 1
INTRODUCTION
Page 26
Chapter 1 - IntroductionP64x
2P64x-TM-EN-1.3
Page 27
P64xChapter 1 - Introduction
1CHAPTER OVERVIEW
This chapter provides some general information about the technical manual and an introduction to the device(s)
described in this technical manual.
This chapter contains the following sections:
Chapter Overview3
eword4
For
Product Scope6
Features and Functions8
Compliance10
Functional Overview11
P64x-TM-EN-1.33
Page 28
Chapter 1 - IntroductionP64x
2FOREWORD
This technical manual provides a functional and technical description of GE's P642, P643, P645, as well as a
ehensive set of instructions for using the device. The level at which this manual is written assumes that you
compr
are already familiar with protection engineering and have experience in this discipline. The description of principles
and theory is limited to that which is necessary to understand the product. For further details on general
protection engineering theory, we refer you to Alstom's publication NPAG, which is available online or from our
contact centre.
We have attempted to make this manual as accurate, comprehensive and user-friendly as possible. However we
cannot guarantee that it is free from errors. Nor can we state that it cannot be improved. We would therefore be
very pleased to hear from you if you discover any errors, or have any suggestions for improvement. Our policy is to
provide the information necessary to help you safely specify, engineer, install, commission, maintain, and
eventually dispose of this product. We consider that this manual provides the necessary information, but if you
consider that more details are needed, please contact us.
All feedback should be sent to our contact centre via the following URL:
www.gegridsolutions.com/contact
2.1TARGET AUDIENCE
This manual is aimed towards all professionals charged with installing, commissioning, maintaining,
tr
oubleshooting, or operating any of the products within the specified product range. This includes installation and
commissioning personnel as well as engineers who will be responsible for operating the product.
The level at which this manual is written assumes that installation and commissioning engineers have knowledge
of handling electronic equipment. Also, system and protection engineers have a thorough knowledge of protection
systems and associated equipment.
2.2TYPOGRAPHICAL CONVENTIONS
The following typographical conventions are used throughout this manual.
● The names for special k
For example: ENTER
● When describing software applications, menu items, buttons, labels etc as they appear on the screen are
written in bold type.
For example: Select Save from the file menu.
● Filenames and paths use the courier font
For example: Example\File.text
● Special terminology is written with leading capitals
For example: Sensitive Earth Fault
● If reference is made to the IED's internal settings and signals database, the menu group heading (column)
text is written in upper case italics
For example: The SYSTEM DATA column
● If reference is made to the IED's internal settings and signals database, the setting cells and DDB signals are
written in bold italics
For example: The Language cell in the SYSTEM DATA column
● If reference is made to the IED's internal settings and signals database, the value of a cell's content is
written in the Courier font
For example: The Language cell in the SYSTEM DATA column contains the value English
eys appear in capital letters.
4P64x-TM-EN-1.3
Page 29
P64xChapter 1 - Introduction
2.3NOMENCLATURE
Due to the technical nature of this manual, many special terms, abbreviations and acronyms are used throughout
the manual. Some of these terms ar
specific terms used by GE. The first instance of any acronym or term used in a particular chapter is explained. In
addition, a separate glossary is available on the GE website, or from the GE contact centre.
We would like to highlight the following changes of nomenclature however:
● The word 'relay' is no longer used to describe the device itself. Instead, the device is referred to as the 'IED'
(Intelligent Electronic Device), the 'device', or the 'product'. The word 'relay' is used purely to describe the
electromechanical components within the device, i.e. the output relays.
● British English is used throughout this manual.
● The British term 'Earth' is used in favour of the American term 'Ground'.
e well-known industry-specific terms while others may be special product-
P64x-TM-EN-1.35
Page 30
Chapter 1 - IntroductionP64x
3PRODUCT SCOPE
The MiCOM P64x range of devices preserve transformer service life by offering fast protection for transformer
faults. Hosted on an adv
Fault (REF),Thermal, and Overfluxing protection, plus backup protection for uncleared external faults. Further, the
P64x devices provide a range of transformer condition monitoring functions such as Through-fault monitoring,
loss of life statistics, RTD and CLIO protection functionality.
All devices also provide a comprehensive range of additional features to aid with power system diagnosis and fault
analysis.
Model variants cover two and three winding power transformers, with up to five sets of 3-phase CT inputs. Backup
overcurrent protection can be directionalised, if you select the optional 3-phase VT input.
The P64x range consists of three models; the P642, P643, and P645.
● The P642 provides 8 on-board CTs to support two-winding 3-phase power transformers and 1or 2 single-
phase voltage transformers to support directionalisation and a range of voltage-related functions.
● The P643 provides 12 on-board CTs to support three-winding 3-phase power transformers, a single-phase
voltage transformer and an optional three-phase voltage transformer to support directionalisation and a
range of voltage-related functions including undervoltage, overvoltage and residual overvoltage protection.
● The P645 provides 18 on-board CTs to support three-winding 3-phase power transformers and other
applications needing 5 sets of 3-phase current inputs, a single-phase voltage transformer and an optional
three-phase voltage transformer to support directionalisation and a range of voltage-related functions
including undervoltage, overvoltage and residual overvoltage protection.
The difference in model variants are summarised below:
anced IED platform, the P64x products incorporate Current Differential, Restricted Earth
Feature/VariantP642P643P645
Case40TE60TE/80TE60TE/80TE
Number of CT Inputs8 (6 Bias, 2 EF)12 (9 bias, 3EF)18 (15 Bias, 3EF)
Number of VT inputs1 or 21 or 41 or 4
Number of bias inputs (3-phase CT sets)235
Optically coupled digital inputs8 - 1216 - 4016 - 40
Standard relay output contacts8 - 128 - 248 - 24
Function keysNo1010
Undervoltage/Overvoltage/Residual voltage protectionNoYesYes
Since software version 2, the evolution of the P64x product family has followed two paths as shown below:
6P64x-TM-EN-1.3
Page 31
V00035
J, K
02
·Hot-Standby Ethernet Failover
·Cyber Security
·IEC61850 9-2L Edition 1
Hardware version K (P645SV)
Software version 12
·Negative Sequence Overvoltage
·Voltage Controlled Overcurrent
·Low Impedance REF for autotransformer
·High Impedance REF
·User Alarms
·CT Exclusion
Hardware version J (P642), K (P643/5)
Software version 04
·Hot-Standby Ethernet Failover
·Cyber Security
·More Disturbance Record channels
Hardware version P (P642), M (P643/5)
Software version 05
·Extra I/O (40 opto-inputs)
·2ndharmonic blocking for E/F, REF, POC
·Setting name and DDB signal changes
·Setting range extensions
·Vector Group Reference change
·Changes to default PSL
Hardware version P (P642), M (P643/5)
Software version 06
·IEC61850 9-2LE Edition 2
Hardware version P (P645SV)
Software version 20
P64xChapter 1 - Introduction
Figure 1: P64x version evolution
3.2ORDERING OPTIONS
All current models and variants for this product are defined in an interactive spreadsheet called the CORTEC. This is
ailable on the company website.
av
Alternatively, you can obtain it via the Contact Centre at the following URL:
www.gegridsolutions.com/contact
A copy of the CORTEC is also supplied as a static table in the Appendices of this document. However, it should only
be used for guidance as it provides a snapshot of the interactive data taken at the time of publication.
This technical manual is applicable to the product version M06
P64x-TM-EN-1.37
Page 32
Chapter 1 - IntroductionP64x
4FEATURES AND FUNCTIONS
4.1PROTECTION FUNCTIONS
The P64x range of devices provides the following protection functions:
em is enclosed in brackets, this indicates that the feature is an ordering option.
If it
4.2CONTROL FUNCTIONS
FeatureIEC 61850ANSI
Watchdog contacts
Read-only mode
NERC compliant cyber-security
Function keys (up to 10)FnkGGIO
Programmable LEDs (up to 18)LedGGIO
Programmable hotkeys (2)
Programmable allocation of digital inputs and outputs
Fully customizable menu texts
Circuit breaker control, status & condition monitoringXCBR52
8P64x-TM-EN-1.3
Page 33
P64xChapter 1 - Introduction
FeatureIEC 61850ANSI
Trip circuit and coil supervision
Control inputsPloGGIO1
Power-up diagnostics and continuous self-monitoring
Dual rated 1A and 5A CT inputs
Alternative setting groups (4)
Graphical programmable scheme logic (PSL)
4.3MEASUREMENT FUNCTIONS
Measurement FunctionIEC 61850ANSI
Measurement of all instantaneous & integrated values
(Exact range of measur
Disturbance recorder for waveform capture – specified in samples per cycle RDREDFR
Fault Records
Maintenance Records
Event Records / Event loggingEvent records
Time Stamping of Opto-inputsYesYes
ements depend on the device model)
MET
4.4COMMUNICATION FUNCTIONS
The device offers the following communication functions:
FeatureANSI
NERC compliant cyber-security
Front RS232 serial communication port for configuration16S
Rear serial RS485 communication port for SCADA control16S
2nd Additional rear serial communication ports for SCADA control and
telepr
otection (fibre and copper) (optional)
Ethernet communication (optional)16E
Redundant Ethernet communication (optional)16E
Courier protocol16S
IEC 61850 protocol (optional)16E
IEC 60870-5-103 protocol (optional)16S
Modbus protocol (optional)16S
DNP3.0 protocol over serial link (optional)16S
DNP3.0 protocol over Ethernet (optional)16E
IRIG-B time synchronisation (optional)CLK
16S
P64x-TM-EN-1.39
Page 34
Chapter 1 - IntroductionP64x
5COMPLIANCE
The device has undergone a range of extensive testing and certification processes to ensure and prove
compatibility with all tar
Specifications chapter.
get markets. A detailed description of these criteria can be found in the Technical
10P64x-TM-EN-1.3
Page 35
47
51V
DT VCO
51V
IDMT VCO
E00031
2nd Remote
Comm. port
Remote
Comm. port
Local
Communication
Ethernet
Fault records
Measurements
Disturbance
Record
Self monitoring
I-HV
V
IN-HV
IN-LV
I-LV
IN-TV
I-TV
I-TV
CLIO
BINARY
I/O
RTDsMEASI
MEASO
Always Available
Optional or Specific
Transformer Differential
Protection P64x
1. The three-phase VT input is optional.
2. The 27, 59, 59N and VTS functions require the three-phase VT input.
3. The frequency required by the 81 function is obtained from any analog signal but the voltage signals have priority over the current signals.
virtual
Thru
CTS
DIFF
P64xChapter 1 - Introduction
6FUNCTIONAL OVERVIEW
Figure 2: Functional overview
P64x-TM-EN-1.311
Page 36
Chapter 1 - IntroductionP64x
12P64x-TM-EN-1.3
Page 37
CHAPTER 2
SAFETY INFORMATION
Page 38
Chapter 2 - Safety InformationP64x
14P64x-TM-EN-1.3
Page 39
P64xChapter 2 - Safety Information
1CHAPTER OVERVIEW
This chapter provides information about the safe handling of the equipment. The equipment must be properly
installed and handled in or
be familiar with information contained in this chapter before unpacking, installing, commissioning, or servicing the
equipment.
This chapter contains the following sections:
Chapter Overview15
Health and Safety16
Symbols17
Installation, Commissioning and Servicing18
Decommissioning and Disposal23
Standards Compliance24
der to maintain it in a safe condition and to keep personnel safe at all times. You must
P64x-TM-EN-1.315
Page 40
Chapter 2 - Safety InformationP64x
2HEALTH AND SAFETY
Personnel associated with the equipment must be familiar with the contents of this Safety Information.
When electrical equipment is in operation, danger
Improper use of the equipment and failure to observe warning notices will endanger personnel.
Only qualified personnel may work on or operate the equipment. Qualified personnel are individuals who are:
● familiar with the installation, commissioning, and operation of the equipment and the system to which it is
being connected.
● familiar with accepted safety engineering practises and are authorised to energise and de-energise
equipment in the correct manner.
● trained in the care and use of safety apparatus in accordance with safety engineering practises
● trained in emergency procedures (first aid).
The documentation provides instructions for installing, commissioning and operating the equipment. It cannot,
however cover all conceivable circumstances. In the event of questions or problems, do not take any action
without proper authorisation. Please contact your local sales office and request the necessary information.
ous voltages are present in certain parts of the equipment.
16P64x-TM-EN-1.3
Page 41
P64xChapter 2 - Safety Information
3SYMBOLS
Throughout this manual you will come across the following symbols. You will also see these symbols on parts of
the equipment
.
Caution:
efer to equipment documentation. Failure to do so could result in damage to the
R
equipment
Warning:
Risk of electric shock
Earth terminal. Not
is part of a terminal block or sub-assembly.
Protective conductor (earth) terminal
Instructions on disposal requirements
Note:
The t
erm 'Earth' used in this manual is the direct equivalent of the North American term 'Ground'.
e: This symbol may also be used for a protective conductor (earth) terminal if that terminal
P64x-TM-EN-1.317
Page 42
Chapter 2 - Safety InformationP64x
4INSTALLATION, COMMISSIONING AND SERVICING
4.1LIFTING HAZARDS
Many injuries are caused by:
● Lifting heavy objects
● Lifting things incorr
● Pushing or pulling heavy objects
● Using the same muscles repetitively
Plan carefully, identify any possible hazards and determine how best to move the product. Look at other ways of
moving the load to avoid manual handling. Use the correct lifting techniques and Personal Protective Equipment
(PPE) to reduce the risk of injury.
4.2ELECTRICAL HAZARDS
ectly
Caution:
All per
sonnel involved in installing, commissioning, or servicing this equipment must be
familiar with the correct working procedures.
Caution:
Consult the equipment documentation befor
the equipment.
Caution:
Alw
ays use the equipment as specified. Failure to do so will jeopardise the protection
provided by the equipment.
Warning:
emoval of equipment panels or covers may expose hazardous live parts. Do not touch
R
until the electrical power is removed. Take care when there is unlocked access to the
rear of the equipment.
Warning:
Isolat
e the equipment before working on the terminal strips.
Warning:
Use a suitable pr
electric shock due to exposed terminals.
otective barrier for areas with restricted space, where there is a risk of
e installing, commissioning, or servicing
Caution:
Disconnect pow
sensitive electronic circuitry. Take suitable precautions against electrostatic voltage
discharge (ESD) to avoid damage to the equipment.
18P64x-TM-EN-1.3
er before disassembling. Disassembly of the equipment may expose
Page 43
P64xChapter 2 - Safety Information
Caution:
NE
VER look into optical fibres or optical output connections. Always use optical power
meters to determine operation or signal level.
Warning:
esting may leave capacitors charged to dangerous voltage levels. Discharge
T
capacitors by rediucing test voltages to zero before disconnecting test leads.
Caution:
Note:
Contact f
Operat
Caution:
Befor
free cloth dampened with clean water.
ingers of test plugs are normally protected by petroleum jelly, which should not be removed.
e the equipment within the specified electrical and environmental limits.
e cleaning the equipment, ensure that no connections are energised. Use a lint
4.3UL/CSA/CUL REQUIREMENTS
The information in this section is applicable only to equipment carrying UL/CSA/CUL markings.
Caution:
Equipment int
enclosure, as defined by Underwriters Laboratories (UL).
Caution:
To maintain compliance with UL and CSA/CUL, install the equipment using UL/CSArecognised parts for: cables, protective fuses, fuse holders and circuit breakers,
insulation crimp terminals, and replacement internal batteries.
ended for rack or panel mounting is for use on a flat surface of a Type 1
4.4FUSING REQUIREMENTS
Caution:
Wher
e UL/CSA listing of the equipment is required for external fuse protection, a UL or
CSA Listed fuse must be used for the auxiliary supply. The listed protective fuse type is:
Class J time delay fuse, with a maximum current rating of 15 A and a minimum DC
rating of 250 V dc (for example type AJT15).
Caution:
e UL/CSA listing of the equipment is not required, a high rupture capacity (HRC)
Wher
fuse type with a maximum current rating of 16 Amps and a minimum dc rating of 250 V
dc may be used for the auxiliary supply (for example Red Spot type NIT or TIA).
For P50 models, use a 1A maximum T-type fuse.
For P60 models, use a 4A maximum T-type fuse.
P64x-TM-EN-1.319
Page 44
Chapter 2 - Safety InformationP64x
Caution:
Digital input cir
maximum rating of 16 A. for safety reasons, current transformer circuits must never be
fused. Other circuits should be appropriately fused to protect the wire used.
Caution:
s must NOT be fused since open circuiting them may produce lethal hazardous
CT
voltages
cuits should be protected by a high rupture capacity NIT or TIA fuse with
4.5EQUIPMENT CONNECTIONS
Warning:
Terminals exposed during installation, commissioning and maintenance may present a
hazardous voltage unless the equipment is electrically isolated.
Caution:
en M4 clamping screws of heavy duty terminal block connectors to a nominal
Tight
torque of 1.3 Nm.
Tighten captive screws of terminal blocks to 0.5 Nm minimum and 0.6 Nm maximum.
Caution:
Always use insulated crimp terminations for voltage and current connections.
Caution:
Alw
ays use the correct crimp terminal and tool according to the wire size.
Caution:
atchdog (self-monitoring) contacts are provided to indicate the health of the device
W
on some products. We strongly recommend that you hard wire these contacts into the
substation's automation system, for alarm purposes.
4.6PROTECTION CLASS 1 EQUIPMENT REQUIREMENTS
Caution:
th the equipment with the supplied PCT (Protective Conductor Terminal).
Ear
Caution:
Do not r
Caution:
The P
after adding or removing such earth connections.
20P64x-TM-EN-1.3
emove the PCT.
CT is sometimes used to terminate cable screens. Always check the PCT’s integrity
Page 45
P64xChapter 2 - Safety Information
Caution:
Use a locknut or similar mechanism t
Caution:
ecommended minimum PCT wire size is 2.5 mm² for countries whose mains supply
The r
is 230 V (e.g. Europe) and 3.3 mm² for countries whose mains supply is 110 V (e.g. North
America). This may be superseded by local or country wiring regulations.
For P60 products, the recommended minimum PCT wire size is 6 mm². See product
documentation for details.
Caution:
The PCT connection must have low-inductance and be as short as possible.
Caution:
All connections t
pre-wired, but not used, should be earthed, or connected to a common grouped
potential.
o the equipment must have a defined potential. Connections that are
cuit rating (rating label) and integrity of connections.
otective fuse or miniature circuit breaker (MCB) rating.
egrity of the PCT connection.
oltage and current rating of external wiring, ensuring it is appropriate for the
4.8PERIPHERAL CIRCUITRY
Warning:
Do not open the secondary circuit of a live CT since the high voltage produced may be
lethal to personnel and could damage insulation. Short the secondary of the line CT
before opening any connections to it.
P64x-TM-EN-1.321
Page 46
Chapter 2 - Safety InformationP64x
Note:
For most Alst
is automatically shorted if the module is removed. Therefore external shorting of the CTs may not be required. Check the
equipment documentation and wiring diagrams first to see if this applies.
om equipment with ring-terminal connections, the threaded terminal block for current transformer termination
Caution:
e external components such as resistors or voltage dependent resistors (VDRs) are
Wher
used, these may present a risk of electric shock or burns if touched.
Warning:
T
ake extreme care when using external test blocks and test plugs such as the MMLG,
MMLB and P990, as hazardous voltages may be exposed. Ensure that CT shorting links
are in place before removing test plugs, to avoid potentially lethal voltages.
4.9UPGRADING/SERVICING
Warning:
Do not inser
t or withdraw modules, PCBs or expansion boards from the equipment
while energised, as this may result in damage to the equipment. Hazardous live
voltages would also be exposed, endangering personnel.
Caution:
Int
ernal modules and assemblies can be heavy and may have sharp edges. Take care
when inserting or removing modules into or out of the IED.
22P64x-TM-EN-1.3
Page 47
P64xChapter 2 - Safety Information
5DECOMMISSIONING AND DISPOSAL
Caution:
e decommissioning, completely isolate the equipment power supplies (both poles
Befor
of any dc supply). The auxiliary supply input may have capacitors in parallel, which may
still be charged. To avoid electric shock, discharge the capacitors using the external
terminals before decommissioning.
Caution:
Av
oid incineration or disposal to water courses. Dispose of the equipment in a safe,
responsible and environmentally friendly manner, and if applicable, in accordance with
country-specific regulations.
P64x-TM-EN-1.323
Page 48
Chapter 2 - Safety InformationP64x
6STANDARDS COMPLIANCE
Compliance with the European Commission Directive on EMC and LVD is demonstrated by self certification against
international standar
6.1EMC COMPLIANCE: 2004/108/EC
Compliance with EN60255-26:2009 was used to establish conformity.
6.2PRODUCT SAFETY: 2006/95/EC
Compliance with EN60255-27:2005 was used to establish conformity.
otective Class
Pr
IEC 60255-27: 2005 Class 1 (unless otherwise specified in equipment documentation). This equipment requires a
protective conductor (earth) to ensure user safety.
ds.
Installation category
IEC 60255-27: 2005 Overvoltage Category 3. Equipment in this category is qualification tested at 5kV peak, 1.2/50
mS, 500 Ohms, 0.5 J, between all supply circuits and earth and also between independent circuits.
Environment
IEC 60255-27: 2005, IEC 60255-26:2009. The equipment is intended for indoor use only. If it is required for use in an
outdoor environment, it must be mounted in a cabinet with the appropriate degree of ingress protection.
6.3R&TTE COMPLIANCE
Radio and Telecommunications Terminal Equipment (R&TTE) directive 99/5/EC.
Conformity is demonstrated by compliance to both the EMC dir
ective and the Low Voltage directive, to zero volts.
6.4UL/CUL COMPLIANCE
If marked with this logo, the product is compliant with the requirements of the Canadian and USA Underwriters
Laboratories.
The r
elevant UL file number and ID is shown on the equipment.
6.5ATEX COMPLIANCE
If marked with the logo, the equipment is compliant with article 192 of European directive 94/9/EC. It is approved
for operation outside an A
motors with rated ATEX protection, equipment category 2, to ensure their safe operation in gas zones 1 and 2
hazardous areas.
Equipment with this marking is not itself suitable for operation within a potentially explosive
atmospher
24P64x-TM-EN-1.3
TEX hazardous area. It is however approved for connection to Increased Safety, "Ex e",
e.
Page 49
P64xChapter 2 - Safety Information
Compliance demonstrated by Notified Body Type Examination Certificate.
ATEX Potentially Explosive Atmospheres directive 94/9/EC for equipment.
P64x-TM-EN-1.325
Page 50
Chapter 2 - Safety InformationP64x
26P64x-TM-EN-1.3
Page 51
CHAPTER 3
HARDWARE DESIGN
Page 52
Chapter 3 - Hardware DesignP64x
28P64x-TM-EN-1.3
Page 53
P64xChapter 3 - Hardware Design
1CHAPTER OVERVIEW
This chapter provides information about the product's hardware design.
This chapter contains the following sections:
Chapter Overview29
dware Architecture30
Har
Mechanical Implementation31
Front Panel34
Rear Panel38
Boards and Modules40
P64x-TM-EN-1.329
Page 54
Communications
Analogue Inputs
I/O
I
n
t
e
r
c
o
n
n
e
c
t
i
o
n
Output relay boards
Opto-input boards
CTs
VTs
RS485 modules
Ethernet modules
Keypad
LCD
LEDs
Front port
Watchdog module
PSU module
Watchdog
contacts
+ LED
Auxiliary
Supply
IRIG-B module
P
r
o
c
e
s
s
o
r
m
o
d
u
l
e
F
r
o
n
t
p
a
n
e
l
H
M
I
Output relay contacts
Digital inputs
Power system currents
Power system voltages
RS485 communication
Time synchronisation
Ethernet communication
V00233
Note: Not all modules are applicable to all products
Memory
Flash memory for settings
Battery-backed SRAM
for records
Chapter 3 - Hardware DesignP64x
2HARDWARE ARCHITECTURE
The main components comprising devices based on the Px4x platform are as follows:
● The housing, consisting of a fr
ont panel and connections at the rear
● The Main processor module consisting of the main CPU (Central Processing Unit), memory and an interface
to the front panel HMI (Human Machine Interface)
● A selection of plug-in boards and modules with presentation at the rear for the power supply,
communication functions, digital I/O, analogue inputs, and time synchronisation connectivity
All boards and modules are connected by a parallel data and address bus, which allows the processor module to
send and receive information to and from the other modules as required. There is also a separate serial data bus
for conveying sampled data from the input module to the CPU. These parallel and serial databuses are shown as a
single interconnection module in the following figure, which shows typical modules and the flow of data between
them.
Figure 3: Hardware architecture
30P64x-TM-EN-1.3
Page 55
P64xChapter 3 - Hardware Design
3MECHANICAL IMPLEMENTATION
All products based on the Px4x platform have common hardware architecture. The hardware is modular and
consists of the following main par
● Case and terminal blocks
● Boards and modules
● Front panel
The case comprises the housing metalwork and terminal blocks at the rear. The boards fasten into the terminal
blocks and are connected together by a ribbon cable. This ribbon cable connects to the processor in the front
panel.
The following diagram shows an exploded view of a typical product. The diagram shown does not necessarily
represent exactly the product model described in this manual.
ts:
Figure 4: Exploded view of IED
3.1HOUSING VARIANTS
The Px4x range of products are implemented in a range of case sizes. Case dimensions for industrial products
usually follow modular measur
● 1U = 1.75 inches = 44.45 mm
● 1TE = 0.2 inches = 5.08 mm
The products are available in panel-mount or standalone versions. All products are nominally 4U high. This equates
to 177.8 mm or 7 inches.
The cases are pre-finished steel with a conductive covering of aluminium and zinc. This provides good grounding
at all joints, providing a low resistance path to earth that is essential for performance in the presence of external
noise.
The case width depends on the product type and its hardware options. There are three different case widths for
the described range of products: 40TE, 60TE and 80TE. The case dimensions and compatibility criteria are as
follows:
P64x-TM-EN-1.331
ement units based on rack sizes. These are: U for height and TE for width, where:
Page 56
Chapter 3 - Hardware DesignP64x
Case width (TE)Case width (mm)Case width (inches)
40TE203.28
60TE304.812
80TE406.416
Note:
Not all case sizes ar
e available for all models.
3.2LIST OF BOARDS
The product's hardware consists of several modules drawn from a standard range. The exact specification and
number of har
product in question will use a selection of the following boards.
Main Processor board – 40TE or smallerMain Processor board – without support for function keys
Main Processor board – 60TE or largerMain Processor board – with support for function keys
Power supply board 24/54 V DCPower supply input. Accepts DC voltage between 24 V and 54 V
Power supply board - 48/125 V DCPower supply input. Accepts DC voltage between 48 V and 125 V
Power supply board 110/250 V DCPower supply input. Accepts DC voltage between 110 V and 250 V
Instrument Transformer boardContains the voltage and current transformers
Input boardContains the A/D conversion circuitry
Input board with opto-inputsContains the A/D conversion circuitry + 8 digital opto-inputs
Opto-input boardContains 8 digital opto-inputs
Output relay boardContains 8 digital output relays
Combined Opto-input / Output relay boardContains 4 digital opto-inputs and 4 digital output relays
IRIG-B board - modulatedInterface board for modulated IRIG-B timing signal
IRIG-B - demodulated inputInterface board for demodulated IRIG-B timing signal
Fibre optic boardInterface board for fibre-based RS485 connection
dware modules depends on the model number and variant. Depending on the exact model, the
BoardUse
32P64x-TM-EN-1.3
Page 57
P64xChapter 3 - Hardware Design
BoardUse
RTD boardContains 10 Resistive Temperature Device inputs
CLIO boardContains 4 current loop inputs and 4 current loop outputs
High Break Output Relay BoardOutput relay board with high breaking capacity relays
P64x-TM-EN-1.333
Page 58
Chapter 3 - Hardware DesignP64x
4FRONT PANEL
4.1FRONT PANEL
Depending on the exact model and chosen options, the product will be housed in either a 40TE, 60TE or 80TE case.
By w
ay of example, the following diagram shows the front panel of a typical 60TE unit. The front panels of the
products based on 40TE and 80TE cases have a lot of commonality and differ only in the number of hotkeys and
user-programmable LEDs. The hinged covers at the top and bottom of the front panel are shown open. An optional
transparent front cover physically protects the front panel.
Figure 5: Front panel (60TE)
The fr
ont panel consists of:
● Top and bottom compartments with hinged cover
● LCD display
● Keypad
● 9 pin D-type serial port
● 25 pin D-type parallel port
● Fixed function LEDs
● Function keys and LEDs (60TE and 80TE models)
● Programmable LEDs (60TE and 80TE models)
4.1.1FRONT PANEL COMPARTMENTS
The top compartment contains labels for the:
● Serial number
● Curr
ent and voltage ratings.
34P64x-TM-EN-1.3
Page 59
V00262
Clear key
F
or clearing the last
command
Read key
For viewing larger
blocks of text
Cursor keys
For navigating the
menus
Enter key
For executing the
chosen option
Hot keys
For scrolling through the default display
and for control of setting groups
Function keys
For executing user programmable
functions (not all models)
tment for a 1/2 AA size backup battery (used to back up the real time clock and event, fault , and
disturbance records).
● A 9-pin female D-type front port for an EIA(RS)232 serial connection to a PC.
● A 25-pin female D-type parallel port for monitoring internal signals and downloading software and
language text.
4.1.2HMI PANEL
The keypad provides full access to the device functionality using a range of menu options. The information is
display
ed on the LCD.The LCD is a high resolution monochrome display with 16 characters by 3 lines and
controllable back light.
Figure 6: HMI panel
Not
e:
As the LCD display has a resolution of 16 characters by 3 lines, some of the information is in a condensed mnemonic form.
4.1.3FRONT SERIAL PORT (SK1)
The front serial port is a 9-pin female D-type connector, providing RS232 serial data communication. It is situated
under the bottom hinged cov
settings data between the PC and the IED.
The port is intended for temporary connection during testing, installation and commissioning. It is not intended to
be used for permanent SCADA communications. This port supports the Courier communication protocol only.
Courier is a proprietary communication protocol to allow communication with a range of protection equipment,
and between the device and the Windows-based support software package.
This port can be considered as a DCE (Data Communication Equipment) port, so you can connect this port device
to a PC with an EIA(RS)232 serial cable up to 15 m in length.
P64x-TM-EN-1.335
er, and is used to communicate with a locally connected PC. It is used to transfer
Page 60
Chapter 3 - Hardware DesignP64x
The inactivity timer for the front port is set to 15 minutes. This controls how long the unit maintains its level of
ord access on the front port. If no messages are received on the front port for 15 minutes, any password
passw
access level that has been enabled is cancelled.
Note:
The front serial port does not support automatic extraction of event and disturbance records, although this data can be
accessed manually.
4.1.3.1FRONT SERIAL PORT (SK1) CONNECTIONS
The port pin-out follows the standard for Data Communication Equipment (DCE) device with the following pin
connections on a 9-pin connector
Pin numberDescription
2Tx Transmit data
3Rx Receive data
50 V Zero volts common
.
You must use the correct serial cable, or the communication will not work. A straight-through serial cable is
r
equired, connecting pin 2 to pin 2, pin 3 to pin 3, and pin 5 to pin 5.
Once the physical connection from the unit to the PC is made, the PC’s communication settings must be set to
match those of the IED. The following table shows the unit’s communication settings for the front port.
ProtocolCourier
Baud rate19,200 bps
Courier address1
Message format11 bit - 1 start bit , 8 data bits, 1 parity bit (even parity), 1 stop bit
4.1.4FRONT PARALLEL PORT (SK2)
The front parallel port uses a 25 pin D-type connector. It is used for commissioning, downloading firmware updates
and menu text editing.
4.1.5FIXED FUNCTION LEDS
Four fixed-function LEDs on the left-hand side of the front panel indicate the following conditions.
● Trip (R
● Alarm (Yellow) flashes when the IED registers an alarm. This may be triggered by a fault, event or
● Out of service (Yellow) is ON when the IED's functions are unavailable.
● Healthy (Green) is ON when the IED is in correct working order, and should be ON at all times. It goes OFF if
ed) switches ON when the IED issues a trip signal. It is reset when the associated fault record is
cleared from the front display. Also the trip LED can be configured as self-resetting.
maintenance record. The LED flashes until the alarms have been accepted (read), then changes to
constantly ON. When the alarms are cleared, the LED switches OFF.
the unit’s self-tests show there is an error in the hardware or software. The state of the healthy LED is
reflected by the watchdog contacts at the back of the unit.
4.1.6FUNCTION KEYS
The programmable function keys are available for custom use for some models.
actory default settings associate specific functions to these keys, but by using programmable scheme logic, you
F
can change the default functions of these keys to fit specific needs. Adjacent to these function keys are
programmable LEDs, which are usually set to be associated with their respective function keys.
36P64x-TM-EN-1.3
Page 61
P64xChapter 3 - Hardware Design
4.1.7PROGRAMABLE LEDS
The device has a number of programmable LEDs, which can be associated with PSL-generated signals. The
pr
ogrammable LEDs for most models are tri-colour and can be set to RED, YELLOW or GREEN. However the
programmable LEDs for some models are single-colour (red) only. The single-colour LEDs can be recognised by
virtue of the fact they are large and slightly oval, whereas the tri-colour LEDs are small and round.
P64x-TM-EN-1.337
Page 62
Chapter 3 - Hardware DesignP64x
5REAR PANEL
The MiCOM Px40 series uses a modular construction. Most of the internal workings are on boards and modules
which fit into slots. Some of the boar
However, some boards such as the communications boards have their own connectors. The rear panel consists of
these terminal blocks plus the rears of the communications boards.
The back panel cut-outs and slot allocations vary. This depends on the product, the type of boards and the
terminal blocks needed to populate the case. The following diagram shows a typical rear view of a case populated
with various boards.
ds plug into terminal blocks, which are bolted onto the rear of the unit.
Figure 7: Rear view of populated case
e:
Not
This diagram is just an example and may not show the exact product described in this manual. It also does not show the full
range of available boards, just a typical arrangement.
Not all slots are the same size. The slot width depends on the type of board or terminal block. For example, HD
(heavy duty) terminal blocks, as r
equired for the analogue inputs, require a wider slot size than MD (medium duty)
terminal blocks. The board positions are not generally interchangeable. Each slot is designed to house a particular
type of board. Again this is model-dependent.
The device may use one or more of the terminal block types shown in the following diagram. The terminal blocks
are fastened to the rear panel with screws.
● Heavy duty (HD) terminal blocks for CT and VT circuits
● Medium duty (MD) terminal blocks for the power supply, opto-inputs, relay outputs and rear
communications port
● MiDOS terminal blocks for CT and VT circuits
● RTD/CLIO terminal block for connection to analogue transducers
38P64x-TM-EN-1.3
Page 63
P64xChapter 3 - Hardware Design
,
Figure 8: Terminal block types
e:
Not
Not all products use all types of terminal blocks. The product described in this manual may use one or more of the above
types.
P64x-TM-EN-1.339
Page 64
Chapter 3 - Hardware DesignP64x
6BOARDS AND MODULES
Each product comprises a selection of PCBs (Printed Circuit Boards) and subassemblies, depending on the chosen
configuration.
6.1PCBS
A PCB typically consists of the components, a front connector for connecting into the main system parallel bus via
a ribbon cable, and an inter
● Directly presented to the outside world (as is the case for communication boards such as Ethernet Boards)
● Presented to a connector, which in turn connects into a terminal block bolted onto the rear of the case (as is
the case for most of the other board types)
face to the rear. This rear interface may be:
Figure 9: Rear connection to terminal block
6.2SUBASSEMBLIES
A sub-assembly consists of two or more boards bolted together with spacers and connected with electrical
connectors. It may also have other special requirements such as being encased in a metal housing for shielding
against electromagnetic radiation.
Boards are designated by a part number beginning with ZN, whereas pre-assembled sub-assemblies are
designated with a part number beginning with GN. Sub-assemblies, which are put together at the production
stage, do not have a separate part number.
40P64x-TM-EN-1.3
Page 65
P64xChapter 3 - Hardware Design
The products in the Px40 series typically contain two sub-assemblies:
● The pow
● The input module comprising:
The input module is pre-assembled and is therefore assigned a GN number, whereas the power supply module is
assembled at production stage and does not therefore have an individual part number.
er supply assembly comprising:
○ A power supply board
○ An output relay board
○ One or more transformer boards, which contains the voltage and current transformers (partially or
fully populated)
○ One or more input boards
○ Metal protective covers for EM (electromagnetic) shielding
6.3MAIN PROCESSOR BOARD
Figure 10: Main processor board
The main pr
including the data communication and user interfaces. This is the only board that does not fit into one of the slots.
It resides in the front panel and connects to the rest of the system using an internal ribbon cable.
The LCD and LEDs are mounted on the processor board along with the front panel communication ports.
The memory on the main processor board is split into two categories: volatile and non-volatile. The volatile
memory is fast access SRAM, used by the processor to run the software and store data during calculations. The
non-volatile memory is sub-divided into two groups:
● Flash memory to store software code, text and configuration data including the present setting values.
● Battery-backed SRAM to store disturbance, event, fault and maintenance record data.
There are two board types available depending on the size of the case:
● For models in 40TE cases
● For models in 60TE cases and larger
ocessor board performs all calculations and controls the operation of all other modules in the IED,
P64x-TM-EN-1.341
Page 66
Chapter 3 - Hardware DesignP64x
6.4POWER SUPPLY BOARD
Figure 11: Power supply board
The pow
board can be fitted to the unit. This is specified at the time of order and depends on the magnitude of the supply
voltage that will be connected to it.
There are three board types, which support the following voltage ranges:
The power supply board connector plugs into a medium duty terminal block. This terminal block is always
positioned on the right hand side of the unit looking from the rear.
The power supply board is usually assembled together with a relay output board to form a complete subassembly,
as shown in the following diagram.
er supply board provides power to the unit. One of three different configurations of the power supply
● 24/54 V DC
● 48/125 V DC or 40-100V AC
● 110/250 V DC or 100-240V AC
42P64x-TM-EN-1.3
Page 67
P64xChapter 3 - Hardware Design
Figure 12: Power supply assembly
The power supply outputs are used to provide isolated power supply rails to the various modules within the unit.
Three voltage levels are used by the unit’s modules:
● 5.1 V for all of the digital circuits
● +/- 16 V for the analogue electronics such as on the input board
● 22 V for driving the output relay coils.
All power supply voltages, including the 0 V earth line, are distributed around the unit by the 64-way ribbon cable.
The power supply board incorporates inrush current limiting. This limits the peak inrush current to approximately
10 A.
Power is applied to pins 1 and 2 of the terminal block, where pin 1 is negative and pin 2 is positive. The pin
numbers are clearly marked on the terminal block as shown in the following diagram.
P64x-TM-EN-1.343
Page 68
Chapter 3 - Hardware DesignP64x
Figure 13: Power supply terminals
6.4.1WATCHDOG
The Watchdog contacts are also hosted on the power supply board. The Watchdog facility provides two output
r
elay contacts, one normally open and one normally closed. These are used to indicate the health of the device
and are driven by the main processor board, which continually monitors the hardware and software when the
device is in service.
44P64x-TM-EN-1.3
Page 69
P64xChapter 3 - Hardware Design
Figure 14: Watchdog contact terminals
6.4.2REAR SERIAL PORT
The rear serial port (RP1) is housed on the power supply board. This is a three-terminal EIA(RS)485 serial
communications por
SCADA communication. The interface supports half-duplex communication and provides optical isolation for the
serial data being transmitted and received.
The physical connectivity is achieved using three screw terminals; two for the signal connection, and the third for
the earth shield of the cable. These are located on pins 16, 17 and 18 of the power supply terminal block, which is
on the far right looking from the rear. The interface can be selected between RS485 and K-bus. When the K-Bus
option is selected, the two signal connections are not polarity conscious.
The polarity independent K-bus can only be used for the Courier data protocol. The polarity conscious MODBUS,
IEC 60870-5-103 and DNP3.0 protocols need RS485.
The following diagram shows the rear serial port. The pin assignments are as follows:
● Pin 16: Earth shield
● Pin 17: Negative signal
● Pin 18: Positive signal
t and is intended for use with a permanently wired connection to a remote control centre for
P64x-TM-EN-1.345
Page 70
Chapter 3 - Hardware DesignP64x
Figure 15: Rear serial port terminals
An additional serial por
t with D-type presentation is available as an optional board, if required.
6.5INPUT MODULE - 1 TRANSFORMER BOARD
Figure 16: Input module - 1 transformer board
The input module consists of the main input boar
instrument transformer board contains the voltage and current transformers, which isolate and scale the
analogue input signals delivered by the system transformers. The input board contains the A/D conversion and
digital processing circuitry, as well as eight digital isolated inputs (opto-inputs).
The boards are connected together physically and electrically. The module is encased in a metal housing for
shielding against electromagnetic interference.
46P64x-TM-EN-1.3
d coupled together with an instrument transformer board. The
Page 71
V00239
Transformer
board
Serial
interface
Serial Link
Optical
Isolator
Noise
filter
Optical
Isolator
Noise
filter
Buffer
8 digital inputs
Parallel Bus
VT
or
CT
A/D Converter
VT
or
CT
P64xChapter 3 - Hardware Design
6.5.1INPUT MODULE CIRCUIT DESCRIPTION
Figure 17: Input module schematic
A/D Conv
ersion
The differential analogue inputs from the CT and VT transformers are presented to the main input board as shown.
Each differential input is first converted to a single input quantity referenced to the input board’s earth potential.
The analogue inputs are sampled and converted to digital, then filtered to remove unwanted properties. The
samples are then passed through a serial interface module which outputs data on the serial sample data bus.
The calibration coefficients are stored in non-volatile memory. These are used by the processor board to correct
for any amplitude or phase errors introduced by the transformers and analogue circuitry.
Opto-isolated inputs
The other function of the input board is to read in the state of the digital inputs. As with the analogue inputs, the
digital inputs must be electrically isolated from the power system. This is achieved by means of the 8 on-board
optical isolators for connection of up to 8 digital signals. The digital signals are passed through an optional noise
filter before being buffered and presented to the unit’s processing boards in the form of a parallel data bus.
This selectable filtering allows the use of a pre-set filter of ½ cycle which renders the input immune to induced
power-system noise on the wiring. Although this method is secure it can be slow, particularly for inter-tripping. This
can be improved by switching off the ½ cycle filter, in which case one of the following methods to reduce ac noise
should be considered.
● Use double pole switching on the input
● Use screened twisted cable on the input circuit
The opto-isolated logic inputs can be configured for the nominal battery voltage of the circuit for which they are a
part, allowing different voltages for different circuits such as signalling and tripping.
o-input circuitry can be provided without the A/D circuitry as a separate board, which can provide supplementary
The opt
opto-inputs.
6.5.2FREQUENCY RESPONSE
With the exception of the RMS measurements, all other measurements and protection functions are based on the
Fourier
-derived fundamental component. The fundamental component is extracted by using a 24 sample Discrete
Fourier Transform (DFT). This gives good harmonic rejection for frequencies up to the 23rd harmonic. The 23rd is
the first predominant harmonic that is not attenuated by the Fourier filter and this is known as an ‘Alias’. However,
the Alias is attenuated by approximately 85% by an additional, analogue, ‘anti-aliasing’ filter (low pass filter). The
combined affect of the anti-aliasing and Fourier filters is shown below.
Figure 18: Frequency response
For pow
er frequencies that are not equal to the selected rated frequency, the harmonics are attenuated to zero
amplitude. For small deviations of +/-1 Hz, this is not a problem but to allow for larger deviations, frequency
tracking is used.
Frequency tracking automatically adjusts the sampling rate of the analog to digital conversion to match the
applied signal. In the absence of a suitable signal to amplitude track, the sample rate defaults to the selected rated
frequency (Fn). If the a signal is in the tracking range of 45 to 66 Hz, the relay locks onto the signal and the
measured frequency coincides with the power frequency. The outputs for harmonics up to the 23rd are zero. The
device frequency tracks off any voltage or current in the order VA/VB/VC/IA/IB/IC down to 10% Vn for voltage and
5%In for current.
48P64x-TM-EN-1.3
Page 73
P64xChapter 3 - Hardware Design
6.5.3TRANSFORMER BOARD
Figure 19: Transformer board
The transformer boar
voltages originating from the power systems' current and voltage transformers to levels that can be used by the
devices' electronic circuitry. In addition to this, the on-board CT and VT transformers provide electrical isolation
between the unit and the power system.
The transformer board is connected physically and electrically to the input board to form a complete input module.
For terminal connections, please refer to the wiring diagrams.
d hosts the current and voltage transformers. These are used to step down the currents and
P64x-TM-EN-1.349
Page 74
Chapter 3 - Hardware DesignP64x
6.5.4INPUT BOARD
Figure 20: Input board
The input boar
d is used to convert the analogue signals delivered by the current and voltage transformers into
digital quantities used by the IED. This input board also has on-board opto-input circuitry, providing eight opticallyisolated digital inputs and associated noise filtering and buffering. These opto-inputs are presented to the user by
means of a MD terminal block, which sits adjacent to the analogue inputs HD terminal block.
The input board is connected physically and electrically to the transformer board to form a complete input module.
The terminal numbers of the opto-inputs are as follows:
Terminal NumberOpto-input
Terminal 1Opto 1 -ve
Terminal 2Opto 1 +ve
Terminal 3Opto 2 -ve
Terminal 4Opto 2 +ve
Terminal 5Opto 3 -ve
Terminal 6Opto 3 +ve
Terminal 7Opto 4 -ve
Terminal 8Opto 4 +ve
Terminal 9Opto 5 -ve
Terminal 10Opto 5 +ve
Terminal 11Opto 6 -ve
Terminal 12Opto 6 +ve
Terminal 13Opto 7 –ve
Terminal 14Opto 7 +ve
Terminal 15Opto 8 –ve
Terminal 16Opto 8 +ve
50P64x-TM-EN-1.3
Page 75
P64xChapter 3 - Hardware Design
Terminal NumberOpto-input
Terminal 17Common
Terminal 18Common
6.6STANDARD OUTPUT RELAY BOARD
Figure 21: Standard output relay board - 8 contacts
This output r
elay board has 8 relays with 6 Normally Open contacts and 2 Changeover contacts.
The output relay board is provided together with the power supply board as a complete assembly, or
independently for the purposes of relay output expansion.
There are two cut-out locations in the board. These can be removed to allow power supply components to
protrude when coupling the output relay board to the power supply board. If the output relay board is to be used
independently, these cut-out locations remain intact.
The terminal numbers are as follows:
Terminal NumberOutput Relay
Terminal 1Relay 1 NO
Terminal 2Relay 1 NO
Terminal 3Relay 2 NO
Terminal 4Relay 2 NO
Terminal 5Relay 3 NO
Terminal 6Relay 3 NO
Terminal 7Relay 4 NO
Terminal 8Relay 4 NO
Terminal 9Relay 5 NO
Terminal 10Relay 5 NO
P64x-TM-EN-1.351
Page 76
Chapter 3 - Hardware DesignP64x
Terminal NumberOutput Relay
Terminal 11Relay 6 NO
Terminal 12Relay 6 NO
Terminal 13Relay 7 changeover
Terminal 14Relay 7 changeover
Terminal 15Relay 7 common
Terminal 16Relay 8 changeover
Terminal 17Relay 8 changeover
Terminal 18Relay 8 common
6.7IRIG-B BOARD
Figure 22: IRIG-B board
The IRIG-B boar
d can be fitted to provide an accurate timing reference for the device. The IRIG-B signal is
connected to the board via a BNC connector. The timing information is used to synchronise the IED's internal realtime clock to an accuracy of 1 ms. The internal clock is then used for time tagging events, fault, maintenance and
disturbance records.
IRIG-B interface is available in modulated or demodulated formats.
The IRIG-B facility is provided in combination with other functionality on a number of additional boards, such as:
● Fibre board with IRIG-B
● Second rear communications board with IRIG-B
● Ethernet board with IRIG-B
● Redundant Ethernet board with IRIG-B
There are two types of each of these boards; one type which accepts a modulated IRIG-B input and one type
which accepts a demodulated IRIG-B input.
52P64x-TM-EN-1.3
Page 77
P64xChapter 3 - Hardware Design
6.8FIBRE OPTIC BOARD
Figure 23: Fibre optic board
This boar
compatible protocols (Courier, IEC 60870-5-103, MODBUS and DNP 3.0). It is a fibre-optic alternative to the metallic
RS485 port presented on the power supply terminal block. The metallic and fibre optic ports are mutually exclusive.
The fibre optic port uses BFOC 2.5 ST connectors.
The board comes in two varieties; one with an IRIG-B input and one without:
d provides an interface for communicating with a master station. This communication link can use all
P64x-TM-EN-1.353
Page 78
Chapter 3 - Hardware DesignP64x
6.9REAR COMMUNICATION BOARD
Figure 24: Rear communication board
The optional communications boar
presented on 9 pin D-type connectors. These interfaces are known as SK4 and SK5. Both connectors are female
connectors, but are configured as DTE ports. This means pin 2 is used to transmit information and pin 3 to receive.
SK4 can be used with RS232, RS485 and K-bus. SK5 can only be used with RS232 and is used for electrical
teleprotection. The optional rear communications board and IRIG-B board are mutually exclusive since they use
the same hardware slot. However, the board comes in two varieties; one with an IRIG-B input and one without.
d containing the secondary communication ports provide two serial interfaces
6.10ETHERNET BOARD
Figure 25: Ethernet board
54P64x-TM-EN-1.3
Page 79
P64xChapter 3 - Hardware Design
This is a communications board that provides a standard 100-Base Ethernet interface. This board supports one
electrical copper connection and one fibr
e-pair connection.
There are several variants for this board as follows:
● 100 Mbps Ethernet board
● 100 Mbps Ethernet with on-board modulated IRIG-B input
● 100 Mbps Ethernet with on-board unmodulated IRIG-B input
Two of the variants provide an IRIG-B interface. IRIG-B provides a timing reference for the unit – one board for
modulated IRIG-B and one for demodulated. The IRIG B signal is connected to the board with a BNC connector.
The Ethernet and other connection details are described below:
IRIG-B Connector
● Centre connection: Signal
● Outer connection: Earth
LEDs
LEDFunctionOnOffFlashing
GreenLinkLink okLink broken
YellowActivityTraffic
Optical Fibre Connectors
ConnectorFunction
RxReceive
TxTransmit
RJ45connector
PinSignal nameSignal definition
1TXPTransmit (positive)
2TXNTransmit (negative)
3RXPReceive (positive)
4-Not used
5-Not used
6RXNReceive (negative)
7-Not used
8-Not used
P64x-TM-EN-1.355
Page 80
IRIG-B
Pin3
Link Fail
connector
Pin 2
Pin 1
Link channel
A (green LED)
Activity channel
A (yellow LED)
Link channel B
(green LED)
Activity channel B
(yellow LED)
A
B
C
D
V01009
Chapter 3 - Hardware DesignP64x
6.11REDUNDANT ETHERNET BOARD
Figure 26: Redundant Ethernet board
This boar
d provides dual redundant Ethernet (supported by two fibre pairs) together with an IRIG-B interface for
timing.
Different board variants are available, depending on the redundancy protocol and the type of IRIG-B signal
(unmodulated or modulated). The available redundancy protocols are:
● SHP (Self healing Protocol)
● RSTP (Rapid Spanning Tree Protocol)
● DHP (Dual Homing Protocol)
● PRP (Parallel Redundancy Protocol)
There are several variants for this board as follows:
The Ethernet and other connection details are described below:
IRIG-B Connector
● Centre connection: Signal
● Outer connection: Earth
Link Fail Connector (Ethernet Board Watchdog Relay)
PinClosedOpen
1-2Link fail Channel 1 (A)Link ok Channel 1 (A)
2-3Link fail Channel 2 (B)Link ok Channel 2 (B)
56P64x-TM-EN-1.3
Page 81
P64xChapter 3 - Hardware Design
LEDs
LEDFunctionOnOffFlashing
GreenLinkLink okLink broken
YellowActivitySHP runningPRP, RSTP or DHP traffic
Optical Fibre Connectors (ST)
ConnectorDHPRSTPSHPPRP
ARXARX1RSRXA
BTXATX1ESTXA
CRXBRX2RPRXB
DTXBTX2EPTXB
RJ45connector
PinSignal nameSignal definition
1TXPTransmit (positive)
2TXNTransmit (negative)
3RXPReceive (positive)
4-Not used
5-Not used
6RXNReceive (negative)
7-Not used
8-Not used
P64x-TM-EN-1.357
Page 82
Chapter 3 - Hardware DesignP64x
6.12RTD BOARD
Figure 27: RTD board
The R
TD board provides two banks of 15 terminals to support ten RTD inputs, of the type PT100, Ni100, or Ni120,
depending on the product. There are three terminals for each RTD, therefore 30 terminals altogether. The RTD
board fits into slot B or slot C, depending on the model variant.
The terminal numbers of the RTDs are as follows:
Terminal NumberRTD connection
Terminal 1RTD1 wire 1
Terminal 2RTD1 wire 2
Terminal 3RTD1 wire 3
Terminal 4RTD2 wire 1
Terminal 5RTD2 wire 2
Terminal 6RTD2 wire 3
Terminal 7RTD3 wire 1
Terminal 8RTD3 wire 2
Terminal 9RTD3 wire 3
Terminal 10RTD4 wire 1
Terminal 11RTD4 wire 2
Terminal 12RTD4 wire 3
Terminal 13RTD5 wire 1
Terminal 14RTD5 wire 2
Terminal 15RTD5 wire 3
Terminal 16RTD6 wire 1
58P64x-TM-EN-1.3
Page 83
P64xChapter 3 - Hardware Design
Terminal NumberRTD connection
Terminal 17RTD6 wire 2
Terminal 18RTD6 wire 3
Terminal 19RTD7 wire 1
Terminal 20RTD7 wire 2
Terminal 21RTD7 wire 3
Terminal 22RTD8 wire 1
Terminal 23RTD8 wire 2
Terminal 24RTD8 wire 3
Terminal 25RTD9 wire 1
Terminal 26RTD9 wire 2
Terminal 27RTD9 wire 3
Terminal 28RTD10 wire 1
Terminal 29RTD10 wire 2
Terminal 30RTD10 wire 3
6.13CLIO BOARD
Figure 28: RTD board
The CLIO boar
d provides two banks of 15 terminals to support four current loop inputs and four current loop
outputs. There are three terminals for each input and three for each output, therefore 24 of the terminals are used
altogether. The CLIO board fits into slot B or slot C, depending on the model variant.
The terminal numbers of the current loop inputs and outputs are as follows:
P64x-TM-EN-1.359
Page 84
Chapter 3 - Hardware DesignP64x
Terminal NumberCurrent Loop Connection
Terminal 1CLO1 - 20 mA input
Terminal 2CLO1 - 1 mA input
Terminal 3CLO1 - common input
Terminal 4Not used
Terminal 5CLO2 - 20 mA input
Terminal 6CLO2 - 1 mA input
Terminal 7CLO2 - common input
Terminal 8Not used
Terminal 9CLO3 - 20 mA input
Terminal 10CLO3 - 1 mA input
Terminal 11CLO3 - common input
Terminal 12Not used
Terminal 13CLO4 - 20 mA input
Terminal 14CLO4 - 1 mA input
Terminal 15CLO4 - common input
Terminal 16CLI1 - 20 mA input
Terminal 17CLI1 - 1 mA input
Terminal 18CLI1 - common input
Terminal 19Not used
Terminal 20CLI2 - 20 mA input
Terminal 21CLI2 - 1 mA input
Terminal 22CLI2 - common input
Terminal 23Not used
Terminal 24CLI3 - 20 mA input
Terminal 25CLI3 - 1 mA input
Terminal 26CLI3 - common input
Terminal 27Not used
Terminal 28CLI4 - 20 mA input
Terminal 29CLI4 - 1 mA input
Terminal 30CLI4 - common input
60P64x-TM-EN-1.3
Page 85
P64xChapter 3 - Hardware Design
6.14HIGH BREAK OUTPUT RELAY BOARD
Figure 29: High Break relay output board
A High Br
are suitable for high breaking loads.
A High Break contact consists of a high capacity relay with a MOSFET in parallel with it. The MOSFET has a varistor
placed across it to provide protection, which is required when switching off inductive loads. This is because the
stored energy in the inductor causes a high reverse voltage that could damage the MOSFET, if not protected.
When there is a control input command to operate an output contact the miniature relay is operated at the same
time as the MOSFET. The miniature relay contact closes in nominally 3.5 ms and is used to carry the continuous
load current. The MOSFET operates in less than 0.2 ms, but is switched off after 7.5 ms.
When the control input is reset, the MOSFET is again turned on for 7.5 mS. The miniature relay resets in nominally
3.5 ms before the MOSFET. This means the MOSFET is used to break the load. The MOSFET absorbs the energy
when breaking inductive loads and so limits the resulting voltage surge. This contact arrangement is for switching
DC circuits only.
The board number is:
High Break Contact Operation
The following figure shows the timing diagram for High Break contact operation.
eak output relay board is available as an option. It comprises four normally open output contacts, which
● ZN0042 001
P64x-TM-EN-1.361
Page 86
V00246
3.5ms + contact bounce
Load current
Relay contact
Databus
control input
MOSFET reset
MOSFET operate
on
7ms
on
3.5ms
Closed
on
7ms
off
Chapter 3 - Hardware DesignP64x
Figure 30: High Break contact operation
High Break Contact Applications
● Efficient scheme engineering
In traditional hard wired scheme designs, High Break capability could only be achieved using external
electromechanical trip relays. Instead, these internal High Break contacts can be used thus reducing space
requirements.
● Accessibility of CB auxiliary contacts
It is common practise to use circuit breaker 52a (CB Closed) auxiliary contacts to break the trip coil current
on breaker opening, thereby easing the duty on the protection contacts. In some cases (such as operation
of disconnectors, or retrofitting), it may be that 52a contacts are either unavailable or unreliable. In such
cases, High Break contacts can be used to break the trip coil current in these applications.
● Breaker fail
In the event of failure of the local circuit breaker (stuck breaker), or defective auxiliary contacts (stuck
contacts), it is incorrect to use 52a contact action. The interrupting duty at the local breaker then falls on the
relay output contacts, which may not be rated to perform this duty. High Break contacts should be used in
this case to avoid the risk of burning out relay contacts.
● Initiation of teleprotection
The High Break contacts also offer fast making, which results in faster tripping. In addition, fast keying of
teleprotection is a benefit. Fast keying bypasses the usual contact operation time, such that permissive,
blocking and intertrip commands can be routed faster.
62P64x-TM-EN-1.3
Warning:
These relay contacts are POLARITY SENSITIVE. External wiring must comply with the polarity
requirements described in the external connection diagram to ensure correct operation.
Page 87
CHAPTER 4
SOFTWARE DESIGN
Page 88
Chapter 4 - Software DesignP64x
64P64x-TM-EN-1.3
Page 89
P64xChapter 4 - Software Design
1CHAPTER OVERVIEW
This chapter describes the software design of the IED.
This chapter contains the following sections:
Chapter Overview65
ware Design Overview66
Sof
System Level Software67
Platform Software70
Protection and Control Functions71
P64x-TM-EN-1.365
Page 90
V00300
R
e
c
o
r
d
s
P
r
o
t
e
c
t
i
o
n
a
n
d
c
o
n
t
r
o
l
s
e
t
t
i
n
g
s
Protection and Control Software Layer
Fault locator
task
Disturbance
recorder task
Sampling function
Control of output contacts
and programmable LEDs
Sample data + digital
logic inputs
System Level Softw are Layer
System services (e.g. device drivers) / Real time operating system / Self-diagnostic software
Control of interfaces to keypad , LCD, LEDs,
front & rear ports.
Self-checking maintenance records
Hardware Device L ayer
LEDs / LCD / Keypad / Memory / FPGA
Protection Task
Programmable &
fixed scheme logic
Fourier signal
processing
Protection
algorithms
Supervisor task
Platform Sof tw are Layer
Event, fault,
disturbance,
maintenance record
logging
Remote
communications
interfaces
Front panel
interface
(LCD + Keypad)
Local
communications
interfaces
Settings database
Chapter 4 - Software DesignP64x
2SOFWARE DESIGN OVERVIEW
The device software can be conceptually categorized into several elements as follows:
● The system lev
el software
● The platform software
● The protection and control software
These elements are not distinguishable to the user, and the distinction is made purely for the purposes of
explanation. The following figure shows the software architecture.
Figure 31: Software Architecture
The softw
are, which executes on the main processor, can be divided into a number of functions as illustrated
above. Each function is further broken down into a number of separate tasks. These tasks are then run according
to a scheduler. They are run at either a fixed rate or they are event driven. The tasks communicate with each other
as and when required.
66P64x-TM-EN-1.3
Page 91
P64xChapter 4 - Software Design
3SYSTEM LEVEL SOFTWARE
3.1REAL TIME OPERATING SYSTEM
The real-time operating system is used to schedule the processing of the various tasks. This ensures that they are
pr
ocessed in the time available and in the desired order of priority. The operating system also plays a part in
controlling the communication between the software tasks, through the use of operating system messages.
3.2SYSTEM SERVICES SOFTWARE
The system services software provides the layer between the hardware and the higher-level functionality of the
platform softw
drivers for items such as the LCD display, the keypad and the remote communication ports. It also controls things
like the booting of the processor and the downloading of the processor code into RAM at startup.
3.3SELF-DIAGNOSTIC SOFTWARE
The device includes several self-monitoring functions to check the operation of its hardware and software while in
vice. If there is a problem with the hardware or software, it should be able to detect and report the problem, and
ser
attempt to resolve the problem by performing a reboot. In this case, the device would be out of service for a short
time, during which the ‘Healthy’ LED on the front of the device is switched OFF and the watchdog contact at the
rear is ON. If the restart fails to resolve the problem, the unit takes itself permanently out of service; the ‘Healthy’
LED stays OFF and watchdog contact stays ON.
are and the protection and control software. For example, the system services software provides
If a problem is detected by the self-monitoring functions, the device attempts to store a maintenance record to
allow the nature of the problem to be communicated to the user.
The self-monitoring is implemented in two stages: firstly a thorough diagnostic check which is performed on bootup, and secondly a continuous self-checking operation, which checks the operation of the critical functions whilst
it is in service.
3.4STARTUP SELF-TESTING
The self-testing takes a few seconds to complete, during which time the IED's measurement, recording, control,
and pr
otection functions are unavailable. On a successful start-up and self-test, the ‘health-state’ LED on the front
of the unit is switched on. If a problem is detected during the start-up testing, the device remains out of service
until it is manually restored to working order.
The operations that are performed at start-up are:
1.System boot
2.System software initialisation
3.Platform software initialisation and monitoring
3.4.1SYSTEM BOOT
The integrity of the Flash memory is verified using a checksum before the program code and stored data is loaded
into R
AM for execution by the processor. When the loading has been completed, the data held in RAM is compared
to that held in the Flash memory to ensure that no errors have occurred in the data transfer and that the two are
the same. The entry point of the software code in RAM is then called. This is the IED's initialisation code.
P64x-TM-EN-1.367
Page 92
Chapter 4 - Software DesignP64x
3.4.2SYSTEM LEVEL SOFTWARE INITIALISATION
The initialization process initializes the processor registers and interrupts, starts the watchdog timers (used by the
har
dware to determine whether the software is still running), starts the real-time operating system and creates
and starts the supervisor task. In the initialization process the device checks the following:
● The status of the backup battery
● The integrity of the battery-backed SRAM that is used to store event, fault and disturbance records
● The operation of the LCD controller
● The watchdog operation
At the conclusion of the initialization software the supervisor task begins the process of starting the platform
software.
3.4.3PLATFORM SOFTWARE INITIALISATION AND MONITORING
When starting the platform software, the IED checks the following:
● The integrity of the data held in non-v
● The operation of the real-time clock
● The optional IRIG-B function (if applicable)
● The presence and condition of the input board
● The analog data acquisition system (it does this by sampling the reference voltage)
At the successful conclusion of all of these tests the unit is entered into service and the application software is
started up.
olatile memory (using a checksum)
3.5CONTINUOUS SELF-TESTING
When the IED is in service, it continually checks the operation of the critical parts of its hardware and software. The
ing is carried out by the system services software and the results are reported to the platform software. The
check
functions that are checked are as follows:
● The Flash memory containing all program code and language text is verified by a checksum.
● The code and constant data held in system memory is checked against the corresponding data in Flash
memory to check for data corruption.
● The system memory containing all data other than the code and constant data is verified with a checksum.
● The integrity of the digital signal I/O data from the opto-inputs and the output relay coils is checked by the
data acquisition function every time it is executed.
● The operation of the analog data acquisition system is continuously checked by the acquisition function
every time it is executed. This is done by sampling the reference voltages.
● The operation of the optional Ethernet board is checked by the software on the main processor card. If the
Ethernet board fails to respond an alarm is raised and the card is reset in an attempt to resolve the problem.
● The operation of the optional IRIG-B function is checked by the software that reads the time and date from
the board.
● Where fitted, the operation of the RTD board is checked by reading the temperature indicated by the
reference resistors on the two spare RTD channels
● Where fitted, the operation of the CLIO board is checked
In the event that one of the checks detects an error in any of the subsystems, the platform software is notified and
it attempts to log a maintenance record.
If the problem is with the battery status or the IRIG-B board, the device continues in operation. For problems
detected in any other area, the device initiates a shutdown and re-boot, resulting in a period of up to 10 seconds
when the functionality is unavailable.
68P64x-TM-EN-1.3
Page 93
P64xChapter 4 - Software Design
A restart should clear most problems that may occur. If, however, the diagnostic self-check detects the same
oblem that caused the IED to restart, it is clear that the restart has not cleared the problem, and the device takes
pr
itself permanently out of service. This is indicated by the ‘’health-state’ LED on the front of the device, which
switches OFF, and the watchdog contact which switches ON.
P64x-TM-EN-1.369
Page 94
Chapter 4 - Software DesignP64x
4PLATFORM SOFTWARE
The platform software has three main functions:
o control the logging of records generated by the protection software, including alarms, events, faults, and
● T
maintenance records
● To store and maintain a database of all of the settings in non-volatile memory
● To provide the internal interface between the settings database and the user interfaces, using the front
panel interface and the front and rear communication ports
4.1RECORD LOGGING
The logging function is used to store all alarms, events, faults and maintenance records. The records are stored in
non-v
olatile memory to provide a log of what has happened. The IED maintains four types of log on a first in first
out basis (FIFO). These are:
● Alarms
● Event records
● Fault records
● Maintenance records
The logs are maintained such that the oldest record is overwritten with the newest record. The logging function
can be initiated from the protection software. The platform software is responsible for logging a maintenance
record in the event of an IED failure. This includes errors that have been detected by the platform software itself or
errors that are detected by either the system services or the protection software function. See the Monitoring and
Control chapter for further details on record logging.
4.2SETTINGS DATABASE
The settings database contains all the settings and data, which are stored in non-volatile memory. The platform
are manages the settings database and ensures that only one user interface can modify the settings at any
softw
one time. This is a necessary restriction to avoid conflict between different parts of the software during a setting
change.
Changes to protection settings and disturbance recorder settings, are first written to a temporary location SRAM
memory. This is sometimes called 'Scratchpad' memory. These settings are not written into non-volatile memory
immediately. This is because a batch of such changes should not be activated one by one, but as part of a
complete scheme. Once the complete scheme has been stored in SRAM, the batch of settings can be committed to
the non-volatile memory where they will become active.
4.3INTERFACES
The settings and measurements database must be accessible from all of the interfaces to allow read and modify
operations. The platform softw
display, keypad and all the communications interfaces).
are presents the data in the appropriate format for each of the interfaces (LCD
70P64x-TM-EN-1.3
Page 95
P64xChapter 4 - Software Design
5PROTECTION AND CONTROL FUNCTIONS
The protection and control software processes all of the protection elements and measurement functions. To
e this it has to communicate with the system services software, the platform software as well as organise its
achiev
own operations.
The protection task software has the highest priority of any of the software tasks in the main processor board. This
ensures the fastest possible protection response.
The protection and control software provides a supervisory task, which controls the start-up of the task and deals
with the exchange of messages between the task and the platform software.
5.1ACQUISITION OF SAMPLES
After initialization, the protection and control task waits until there are enough samples to process. The acquisition
of samples on the main pr
services software.
This sampling function takes samples from the input module and stores them in a two-cycle FIFO buffer. The
sample rate is 24 samples per cycle. This results in a nominal sample rate of 1,200 samples per second for a 50 Hz
system and 1,440 samples per second for a 60 Hz system. However the sample rate is not fixed. It tracks the
power system frequency as described in the next section.
ocessor board is controlled by a ‘sampling function’ which is called by the system
5.2FREQUENCY TRACKING
The device provides a frequency tracking algorithm so that there are always 24 samples per cycle irrespective of
equency drift within a certain frequency range (see technical specifications). If the frequency falls outside this
fr
range, the sample rate reverts to its default rate of 1200 Hz for 50 Hz or 1440 Hz for 60 Hz.
The frequency tracking of the analog input signals is achieved by a recursive Fourier algorithm which is applied to
one of the input signals. It works by detecting a change in the signal’s measured phase angle. The calculated value
of the frequency is used to modify the sample rate being used by the input module, in order to achieve a constant
sample rate per cycle of the power waveform. The value of the tracked frequency is also stored for use by the
protection and control task.
The frequency tracks off any voltage or current in the order VA, VB, VC, IA, IB, IC, down to 10%Vn for voltage and
5%In for current.
5.3DIRECT USE OF SAMPLE VALUES
Most of the IED’s protection functionality uses the Fourier components calculated by the device’s signal processing
are. However RMS measurements and some special protection algorithms available in some products use
softw
the sampled values directly.
The disturbance recorder also uses the samples from the input module, in an unprocessed form. This is for
waveform recording and the calculation of true RMS values of current, voltage and power for metering purposes.
In the case of special protection algorithms, using the sampled values directly provides exceptionally fast response
because you do not have to wait for the signal processing task to calculate the fundamental. You can act on the
sampled values immediately.
5.4FOURIER SIGNAL PROCESSING
When the protection and control task is re-started by the sampling function, it calculates the Fourier components
for the analog signals. Although some pr
harmonic for magnetizing inrush), most protection functions are based on the Fourier-derived fundamental
components of the measured analog signals. The Fourier components of the input current and voltage signals are
stored in memory so that they can be accessed by all of the protection elements’ algorithms.
P64x-TM-EN-1.371
otection algorithms use some Fourier-derived harmonics (e.g. second
The Fourier components are calculated using single-cycle Fourier algorithm. This Fourier algorithm always uses
the most r
ecent 24 samples from the 2-cycle buffer.
Most protection algorithms use the fundamental component. In this case, the Fourier algorithm extracts the power
frequency fundamental component from the signal to produce its magnitude and phase angle. This can be
represented in either polar format or rectangular format, depending on the functions and algorithms using it.
The Fourier function acts as a filter, with zero gain at DC and unity gain at the fundamental, but with good
harmonic rejection for all harmonic frequencies up to the nyquist frequency. Frequencies beyond this nyquist
frequency are known as alias frequencies, which are introduced when the sampling frequency becomes less than
twice the frequency component being sampled. However, the Alias frequencies are significantly attenuated by an
anti-aliasing filter (low pass filter), which acts on the analog signals before they are sampled. The ideal cut-off point
of an anti-aliasing low pass filter would be set at:
´
(samples per cycle)
(fundamental frequency)/2
At 24 samples per cycle, this would be nominally 600 Hz for a 50 Hz system, or 720 Hz for a 60 Hz system.
The following figure shows the nominal frequency response of the anti-alias filter and the Fourier filter for a 24sample single cycle fourier algorithm acting on the fundamental component:
Figure 32: Frequency Response (indicative only)
5.5PROGRAMMABLE SCHEME LOGIC
The purpose of the programmable scheme logic (PSL) is to allow you to configure your own protection schemes to
suit your particular application. This is done with programmable logic gates and delay timers. To allow greater
flexibility, different PSL is allowed for each of the four setting groups.
The input to the PSL is any combination of the status of the digital input signals from the opto-isolators on the
input board, the outputs of the protection elements such as protection starts and trips, and the outputs of the fixed
protection scheme logic (FSL). The fixed scheme logic provides the standard protection schemes. The PSL consists
of software logic gates and timers. The logic gates can be programmed to perform a range of different logic
functions and can accept any number of inputs. The timers are used either to create a programmable delay,
and/or to condition the logic outputs, such as to create a pulse of fixed duration on the output regardless of the
length of the pulse on the input. The outputs of the PSL are the LEDs on the front panel of the relay and the output
contacts at the rear.
The execution of the PSL logic is event driven. The logic is processed whenever any of its inputs change, for
example as a result of a change in one of the digital input signals or a trip output from a protection element. Also,
only the part of the PSL logic that is affected by the particular input change that has occurred is processed. This
reduces the amount of processing time that is used by the PSL. The protection & control software updates the logic
delay timers and checks for a change in the PSL input signals every time it runs.
The PSL can be configured to create very complex schemes. Because of this PSL desing is achieved by means of a
PC support package called the PSL Editor. This is available as part of the settings application software MiCOm S1
Agile, or as a standalone software module.
72P64x-TM-EN-1.3
Page 97
P64xChapter 4 - Software Design
5.6EVENT RECORDING
A change in any digital input signal or protection element output signal is used to indicate that an event has taken
place. When this happens, the pr
an event is available to be processed and writes the event data to a fast buffer controlled by the supervisor task.
When the supervisor task receives an event record, it instructs the platform software to create the appropriate log
in non-volatile memory (battery backed-up SRAM). The operation of the record logging to battery backed-up SRAM
is slower than the supervisor buffer. This means that the protection software is not delayed waiting for the records
to be logged by the platform software. However, in the rare case when a large number of records to be logged are
created in a short period of time, it is possible that some will be lost, if the supervisor buffer is full before the
platform software is able to create a new log in battery backed-up SRAM. If this occurs then an event is logged to
indicate this loss of information.
Maintenance records are created in a similar manner, with the supervisor task instructing the platform software to
log a record when it receives a maintenance record message. However, it is possible that a maintenance record
may be triggered by a fatal error in the relay in which case it may not be possible to successfully store a
maintenance record, depending on the nature of the problem.
For more information, see the Monitoring and Control chapter.
otection and control task sends a message to the supervisor task to indicate that
5.7DISTURBANCE RECORDER
The disturbance recorder operates as a separate task from the protection and control task. It can record the
w
aveforms of the calibrated analog channels, plus the values of the digital signals. The recording time is user
selectable up to a maximum of 10.5 seconds. The disturbance recorder is supplied with data by the protection and
control task once per cycle, and collates the received data into the required length disturbance record. The
disturbance records can be extracted using application software or the SCADA system, which can also store the
data in COMTRADE format, allowing the use of other packages to view the recorded data.
For more information, see the Monitoring and Control chapter.
5.8FAULT LOCATOR
The fault locator uses 12 cycles of the analog input signals to calculate the fault location. The result is returned to
otection and control task, which includes it in the fault record. The pre-fault and post-fault voltages are also
the pr
presented in the fault record. When the fault record is complete, including the fault location, the protection and
control task sends a message to the supervisor task to log the fault record.
The Fault Locator is not available on all models.
5.9FUNCTION KEY INTERFACE
The function keys interface directly into the PSL as digital input signals. A change of state is only recognized when
ey press is executed on average for longer than 200 ms. The time to register a change of state depends on
a k
whether the function key press is executed at the start or the end of a protection task cycle, with the additional
hardware and software scan time included. A function key press can provide a latched (toggled mode) or output
on key press only (normal mode) depending on how it is programmed. It can be configured to individual protection
scheme requirements. The latched state signal for each function key is written to non-volatile memory and read
from non-volatile memory during relay power up thus allowing the function key state to be reinstated after powerup, should power be inadvertently lost.
P64x-TM-EN-1.373
Page 98
Chapter 4 - Software DesignP64x
74P64x-TM-EN-1.3
Page 99
CHAPTER 5
CONFIGURATION
Page 100
Chapter 5 - ConfigurationP64x
76P64x-TM-EN-1.3
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.