3.9Circuit Breaker Fail and Undercurrent Protection515
3.10Broken Conductor Protection515
3.11Thermal Overload Protection515
4Monitoring, Control and Supervision516
4.1Voltage Transformer Supervision516
4.2Standard Current Transformer Supervision516
4.3Differential Current Transformer Supervision516
4.4CB State and Condition Monitoring516
4.5PSL Timers517
5Measurements and Recording518
5.1General518
5.2Disturbance Records518
5.3Event, Fault and Maintenance Records518
5.4Fault Locator518
6Ratings519
6.1AC Measuring Inputs519
6.2Current Transformer Inputs519
6.3Voltage Transformer Inputs519
6.4Auxiliary Supply Voltage519
6.5Nominal Burden520
6.6Power Supply Interruption520
6.7Battery Backup521
7Input / Output Connections522
7.1Isolated Digital Inputs522
7.1.1Nominal Pickup and Reset Thresholds522
7.2Standard Output Contacts522
7.3High Break Output Contacts523
7.4Watchdog Contacts523
8Mechanical Specifications524
8.1Physical Parameters524
8.2Enclosure Protection524
8.3Mechanical Robustness524
xviP54xMED-TM-EN-1
P54A/B/C/EContents
8.4Transit Packaging Performance524
9Type Tests525
9.1Insulation525
9.2Creepage Distances and Clearances525
9.3High Voltage (Dielectric) Withstand525
9.4Impulse Voltage Withstand Test525
10Environmental Conditions526
10.1Ambient Temperature Range526
10.2Temperature Endurance Test526
10.3Ambient Humidity Range526
10.4Corrosive Environments526
11Electromagnetic Compatibility527
11.11 MHz Burst High Frequency Disturbance Test527
11.2Damped Oscillatory Test527
11.3Immunity to Electrostatic Discharge527
11.4Electrical Fast Transient or Burst Requirements527
11.5Surge Withstand Capability527
11.6Surge Immunity Test528
11.7Immunity to Radiated Electromagnetic Energy528
11.8Radiated Immunity from Digital Communications528
11.9Radiated Immunity from Digital Radio Telephones528
11.10Immunity to Conducted Disturbances Induced by Radio Frequency Fields528
11.11Magnetic Field Immunity529
11.12Conducted Emissions529
11.13Radiated Emissions529
11.14Power Frequency529
12Regulatory Compliance530
12.1EMC Compliance: 2014/30/EU530
12.2LVD Compliance: 2014/35/EU530
12.3R&TTE Compliance: 2014/53/EU530
12.4UL/CUL Compliance530
12.5ATEX Compliance: 2014/34/EU530
Appendix AOrdering Options533
Appendix BSettings and Signals535
Appendix CWiring Diagrams537
P54xMED-TM-EN-1xvii
ContentsP54A/B/C/E
xviiiP54xMED-TM-EN-1
Table of Figures
Figure 1:Key to logic diagrams10
Figure 2:Functional Overview11
Figure 3:Hardware architecture30
Figure 4:Coprocessor hardware architecture31
Figure 5:Exploded view of IED32
Figure 6:Front panel (60TE)35
Figure 7:Rear view of populated case39
Figure 8:Terminal block types40
Figure 9:Rear connection to terminal block41
Figure 10:Main processor board42
Figure 11:Power supply board43
Figure 12:Power supply assembly44
Figure 13:Power supply terminals45
Figure 14:Watchdog contact terminals46
Figure 15:Rear serial port terminals47
Figure 16:Input module - 1 transformer board47
Figure 17:Input module schematic48
Figure 18:Transformer board49
Figure 19:Input board50
Figure 20:Standard output relay board - 8 contacts51
Figure 21:IRIG-B board52
Figure 22:Fibre optic board53
Figure 23:Rear communication board54
Figure 24:Ethernet board54
Figure 25:Redundant Ethernet board56
Figure 26:Fully populated Coprocessor board58
Figure 27:Software Architecture64
Figure 28:Frequency Response (indicative only)71
Figure 29:Navigating the HMI78
Figure 30:Default display navigation80
Figure 31:Circuit Breaker Trip Conversion Logic Diagram (Module 63)87
Figure 32:Sample multi-ended system100
Figure 33:Current differential discriminative criterion101
Figure 34:Overall scheme designed for multi-ended differential protection103
Figure 35:Two-ended transmission line104
Figure 36:Ping-pong measurement for alignment of current signals106
Figure 37:Snapshot of available data for processing at each terminal108
Figure 38:CT saturation technique109
Table of FiguresP54A/B/C/E
Figure 39:Original current waveforms110
Figure 40:Ipos and Ineg current waveforms111
Figure 41:Internal external fault binary111
Figure 42:CT Compensation112
Figure 43:Permissive Intertripping example113
Figure 44:Stub Bus protection114
Figure 45:Six terminal, four junction topology and ring structure115
Figure 46:Six terminal ring structure with channel allocation115
Figure 47:Six terminal, four junction topology116
Figure 48:Autoreclose sequence for a Transient Fault130
Figure 49:Autoreclose sequence for an evolving or permanent fault131
Figure 50:Autoreclose sequence for an evolving or permanent fault - single-phase operation131
Figure 51:Key to logic diagrams133
Figure 52:Autoreclose System Map - part 1134
Figure 53:Autoreclose System Map - part 2135
Figure 54:Autoreclose System Map - part 3136
Figure 55:Autoreclose System Map - part 4137
Figure 56:Autoreclose System Map - part 5138
Figure 57:CB State Monitor logic diagram (Module 1)148
Figure 58:Circuit Breaker Open logic diagram (Module 3)149
Figure 59:CB In Service logic diagram (Module 4)149
Figure 60:Autoreclose OK logic diagram (Module 8)150
Figure 61:Autoreclose Enable logic diagram (Module 5)150
Figure 62:Autoreclose Modes Enable logic diagram (Module 9)152
Figure 63:Force Three-phase Trip logic diagram (Module 10)152
Figure 64:Autoreclose Initiation logic diagram (Module 11)154
Figure 65:Autoreclose Trip Test logic diagram (Module 12)154
Figure 66:Autoreclose initiation by external trip or evolving conditions (Module 13)155
Figure 67:Protection Reoperation and Evolving Fault logic diagram (Module 20)156
Figure 68:Fault Memory logic diagram (Module 15)156
Figure 69:Autoreclose In Progress logic diagram (Module 16)157
Figure 70:Autoreclose Sequence Counter logic diagram (Module 18)158
Figure 71:Single-phase Autoreclose Cycle Selection logic diagram (Module 19)158
Figure 72:Three-phase Autoreclose Cycle Selection logic diagram (Module 21)159
Figure 73:Dead time Start Enable logic diagram (Module 22)160
Figure 74:Single-phase Dead Time logic diagram (Module 24)161
Figure 75:Three-phase Dead Time logic diagram (Module 25)162
Figure 76:Circuit Breaker Autoclose Logic Diagram (Module 32)163
Figure 77:Prepare Reclaim Initiation Logic Diagram (Module 34)164
Figure 78:Reclaim Time logic diagram (Module 35)164
xxP54xMED-TM-EN-1
P54A/B/C/ETable of Figures
Figure 79:Successful Autoreclose Signals logic diagram (Module 36)165
Figure 80:Autoreclose Reset Successful Indication logic diagram (Module 37)165
Figure 81:Circuit Breaker Healthy and System Check Timers Healthy logic diagram (Module 39)166
Figure 82:Autoreclose Shot Counters logic diagram (Module 41)167
Figure 83:CB Control logic diagram (Module 43)168
Figure 84:Circuit Breaker Trip Time Monitoring logic diagram (Module 53)169
Figure 85:AR Lockout Logic Diagram (Module 55)170
Figure 86:Reset Circuit Breaker Lockout Logic Diagram (Module 57)171
Figure 87:Pole Discrepancy Logic Diagram (Module 62)172
Figure 88:Circuit Breaker Trip Conversion Logic Diagram (Module 63)173
Figure 89:Check Synchronisation Monitor for CB closure (Module 60)174
Figure 90:Voltage Monitor for CB Closure (Module 59)175
Figure 91:Three-phase Autoreclose System Check Logic Diagram (Module 45)177
Figure 92:CB Manual Close System Check Logic Diagram (Module 51)178
Figure 93:Circuit Breaker Fail logic - part 1187
Figure 94:Circuit Breaker Fail logic - part 2188
Figure 95:Circuit Breaker Fail logic - part 3189
Figure 96:Circuit Breaker Fail logic - part 4190
Figure 97:CB Fail timing192
Figure 98:Phase Overcurrent Protection logic diagram198
Figure 99:Negative Phase Sequence Overcurrent Protection logic diagram200
Figure 100:IDG Characteristic203
Figure 101:Earth Fault Protection logic diagram205
Figure 102:EPATR B characteristic shown for TMS = 1.0208
Figure 103:Sensitive Earth Fault Protection logic diagram208
Figure 104:Current distribution in an insulated system with C phase fault209
Figure 105:Phasor diagrams for insulated system with C phase fault210
Figure 106:Positioning of core balance current transformers211
Figure 107:High Impedance REF principle212
Figure 108:High Impedance REF Connection213
Figure 109:Thermal overload protection logic diagram215
Figure 110:Spreadsheet calculation for dual time constant thermal characteristic216
Figure 111:Dual time constant thermal characteristic216
Figure 112:Broken conductor logic219
Figure 113:Undervoltage - single and three phase tripping mode (single stage)225
Figure 114:Overvoltage - single and three phase tripping mode (single stage)228
Figure 115:Residual Overvoltage logic232
Figure 116:Residual voltage for a solidly earthed system233
Figure 117:Residual voltage for an impedance earthed system234
Figure 118:Underfrequency logic (single stage)239
P54xMED-TM-EN-1xxi
Table of FiguresP54A/B/C/E
Figure 119:Overfrequency logic (single stage)240
Figure 120:Rate of change of frequency logic (single stage)241
Figure 121:Fault recorder stop conditions248
Figure 122:Broken Current Accumulator logic diagram253
Figure 123:CB Trip Counter logic diagram253
Figure 124:Operating Time Accumulator254
Figure 125:Excessive Fault Frequency logic diagram254
Figure 126:Reset Lockout Alarm logic diagram255
Figure 127:CB Condition Monitoring logic diagram256
Figure 128:Reset Circuit Breaker Lockout Logic Diagram (Module 57)257
Figure 129:CB State Monitor logic diagram (Module 1)260
Figure 130:Hotkey menu navigation262
Figure 131:Default function key PSL263
Figure 132:Remote Control of Circuit Breaker264
Figure 133:CB Control logic diagram (Module 43)265
Figure 134:Pole Dead logic266
Figure 135:Check Synchronisation vector diagram269
Figure 136:Voltage Monitor for CB Closure (Module 59)270
Figure 137:Check Synchronisation Monitor for CB closure (Module 60)271
Figure 138:System Check PSL272
Figure 139:Current Differential Starter Supervision Logic280
Figure 140:Current Differential function Start logic281
Figure 141:Switched Communication Path supervision282
Figure 142:Communication Asymmetry Supervision283
Figure 143:VTS logic288
Figure 144:Differential CTS290
Figure 145:Standard CTS291
Figure 146:TCS Scheme 1293
Figure 147:PSL for TCS Scheme 1294
Figure 148:TCS Scheme 2295
Figure 149:PSL for TCS Scheme 2295
Figure 150:TCS Scheme 3296
Figure 151:PSL for TCS Scheme 3296
Figure 152:Scheme Logic Interfaces301
Figure 153:Trip LED logic305
Figure 154:Fibre teleprotection connections for a six-terminal scheme315
Figure 155:Two terminal single channel scheme315
Figure 156:Two terminal dual channel scheme316
Figure 157:Three terminal scheme316
Figure 158:Four terminal scheme317
xxiiP54xMED-TM-EN-1
P54A/B/C/ETable of Figures
Figure 159:Five terminal scheme318
Figure 160:Six terminal scheme319
Figure 161:IM64 channel fail and scheme fail logic323
Figure 162:IM64 general alarm signals logic323
Figure 163:IM64 communications mode and IEEE C37.94 alarm signals324
Figure 164:IM64 two-terminal scheme extended supervision327
Figure 165:IM64 three-terminal scheme extended supervision327
Figure 166:Example assignment of InterMiCOM signals within the PSL336
Figure 167:Direct connection337
Figure 168:Indirect connection using modems337
Figure 169:RS485 biasing circuit346
Figure 170:Remote communication using K-Bus347
Figure 171:IED attached to separate LANs350
Figure 172:HSR multicast topology351
Figure 173:HSR unicast topology352
Figure 174:HSR application in the substation353
Figure 175:IED attached to redundant Ethernet star or ring circuit353
Figure 176:IED, bay computer and Ethernet switch with self healing ring facilities354
Figure 177:Redundant Ethernet ring architecture with IED, bay computer and Ethernet switches354
Figure 178:Redundant Ethernet ring architecture with IED, bay computer and Ethernet switches
after failur
e
355
Figure 179:Dual homing mechanism356
Figure 180:Application of Dual Homing Star at substation level357
Figure 181:IED and REB IP address configuration358
Figure 182:Connection using (a) an Ethernet switch and (b) a media converter362
Figure 183:Connection using (a) an Ethernet switch and (b) a media converter366
Figure 184:Control input behaviour389
Figure 185:Data model layers in IEC61850401
Figure 186:Edition 2 system - backward compatibility405
Figure 187:Edition 1 system - forward compatibility issues405
Figure 188:Example of Standby IED406
Figure 189:Standby IED Activation Process407
Figure 190:GPS Satellite timing signal410
Figure 191:Timing error using ring or line topology412
Figure 192:Default display navigation422
Figure 193:Location of battery isolation strip435
Figure 194:Rack mounting of products436
Figure 195:Terminal block types438
Figure 196:40TE case dimensions442
Figure 197:60TE case dimensions443
P54xMED-TM-EN-1xxiii
Table of FiguresP54A/B/C/E
Figure 198:80TE case dimensions444
Figure 199:RP1 physical connection460
Figure 200:Remote communication using K-bus461
Figure 201:InterMicom loopback testing464
Figure 202:Simulated input behaviour471
Figure 203:Test example 1472
Figure 204:Test example 2473
Figure 205:Test example 3474
Figure 206:Current Differential Bias Characteristics475
Figure 207:Possible terminal block types492
Figure 208:Front panel assembly494
xxivP54xMED-TM-EN-1
CHAPTER 1
INTRODUCTION
Chapter 1 - IntroductionP54A/B/C/E
2P54xMED-TM-EN-1
P54A/B/C/EChapter 1 - Introduction
1CHAPTER OVERVIEW
This chapter provides some general information about the technical manual and an introduction to the device(s)
described in this technical manual.
This chapter contains the following sections:
Chapter Overview3
eword4
For
Product Scope6
Features and Functions7
Logic Diagrams9
Functional Overview11
P54xMED-TM-EN-13
Chapter 1 - IntroductionP54A/B/C/E
2FOREWORD
This technical manual provides a functional and technical description of General Electric's P54A, P54B, P54C, P54E,
ell as a comprehensive set of instructions for using the device. The level at which this manual is written
as w
assumes that you are already familiar with protection engineering and have experience in this discipline. The
description of principles and theory is limited to that which is necessary to understand the product. For further
details on general protection engineering theory, we refer you to Alstom's publication NPAG, which is available
online or from our contact centre.
We have attempted to make this manual as accurate, comprehensive and user-friendly as possible. However we
cannot guarantee that it is free from errors. Nor can we state that it cannot be improved. We would therefore be
very pleased to hear from you if you discover any errors, or have any suggestions for improvement. Our policy is to
provide the information necessary to help you safely specify, engineer, install, commission, maintain, and
eventually dispose of this product. We consider that this manual provides the necessary information, but if you
consider that more details are needed, please contact us.
All feedback should be sent to our contact centre via the following URL:
www.gegridsolutions.com/contact
2.1TARGET AUDIENCE
This manual is aimed towards all professionals charged with installing, commissioning, maintaining,
tr
oubleshooting, or operating any of the products within the specified product range. This includes installation and
commissioning personnel as well as engineers who will be responsible for operating the product.
The level at which this manual is written assumes that installation and commissioning engineers have knowledge
of handling electronic equipment. Also, system and protection engineers have a thorough knowledge of protection
systems and associated equipment.
2.2TYPOGRAPHICAL CONVENTIONS
The following typographical conventions are used throughout this manual.
● The names for special k
For example: ENTER
● When describing software applications, menu items, buttons, labels etc as they appear on the screen are
written in bold type.
For example: Select Save from the file menu.
● Filenames and paths use the courier font
For example: Example\File.text
● Special terminology is written with leading capitals
For example: Sensitive Earth Fault
● If reference is made to the IED's internal settings and signals database, the menu group heading (column)
text is written in upper case italics
For example: The SYSTEM DATA column
● If reference is made to the IED's internal settings and signals database, the setting cells and DDB signals are
written in bold italics
For example: The Language cell in the SYSTEM DATA column
● If reference is made to the IED's internal settings and signals database, the value of a cell's content is
written in the Courier font
For example: The Language cell in the SYSTEM DATA column contains the value English
eys appear in capital letters.
4P54xMED-TM-EN-1
Loading...
+ 820 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.