General features..........................................................................................................................................1–3
Order codes....................................................................................................................................................1–4
Power connector .........................................................................................................................................2–4
Indicators and switches ........................................................................................2–5
Status indicators..........................................................................................................................................2–5
Information window ............................................................................................................................... 4–10
Configuration line indicator ................................................................................................................ 4–10
Serial interface settings ........................................................................................................................ 4–13
Example ...........................................................................................................................................................6–1
Control register (Profibus control system to P485)......................................................................8–1
Control codes ................................................................................................................................................8–2
Status register (P485 to fieldbus control system).........................................................................8–2
Status codes ..................................................................................................................................................8–3
Equipment and documents....................................................................................................................9–1
System setup.................................................................................................................................................9–2
Modbus user map setup ........................................................................................9–3
PQMII user map............................................................................................................................................9–3
MM2 user map..............................................................................................................................................9–3
System configuration.............................................................................................9–5
GE Multilin warranty statement ........................................................................................................ 10–1
ivP485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE
GE Consumer & Industrial
P485 Modbus to Profibus
Converter
Chapter 1: Introduction
Introduction
Getting started
INSPECTING THE
PACKAGE AND PRODUCT
CONTACT INFORMATIONGE Multilin contact information and call center for product support is shown below:
Examine the shipping container for obvious damage prior to installing this product; notify
the carrier of any damage that you believe occurred during shipment or delivery. Inspect
the contents of this package for any signs of damage and ensure that the items listed
below are included.
Remove the items from the shipping container. Be sure to keep the shipping container
should you need to re-ship the unit at a later date.
In the event there are items missing or damaged, contact the party from whom you
purchased the product. If the unit needs to be returned, please use the original shipping
container, if possible.
GE Multilin
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
•Telephone: 905-294-6222 or 1-800-547-8629 (North America),
+34 94 485 88 00 (Europe)
Fax: 905-201-2098 (North America),
+34 94 485 88 45 (Europe)
•E-mail: multilin.tech@ge.com
•Website: http://www.GEmultilin.com
P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE1–1
INTRODUCTION
Profibus
master
Slave
GE Multilin
P485 Converter
Slave
Modbus
network
Profibus network
OUT
IN
OUT
IN
Document conventions
DESCRIPTIONThe following conventions are used throughout this document:
•Numbered lists provide sequential steps.
•Bulleted lists provide information, not procedural steps.
•The term ‘user’ refers to the person or persons responsible for installing the P485
Modbus to Profibus Converter in a network.
•Hexadecimal values are written in the format 0xNNNN, where NNNN is the
hexadecimal value.
•Decimal values are represented as NNNN, where NNNN is the decimal value.
•As in all communication systems, the terms “input” and “output” can be ambiguous,
since their meaning depends on which end of the link is being referenced. The
convention in this document is that “input” and “output” are always being referenced
to the master/scanner end of the link (see illustration below).
•The term “sub-network” is interchangeably used for “Modbus network”.
Figure 1-1: Input and output definition
GLOSSARYThe following terminology is used in the P485 manual:
•Broadcaster: A protocol specific node in the sub-network scan that holds transactions
destined for all nodes.
•Command: A protocol specific transaction.
•Fieldbus: The network to which the converter is connected (Profibus for P485).
•Frame: A higher level series of bytes forming a complete telegram on the sub-network
(Modbus).
•Monitor: A tool for debugging the P485 and network connections.
•Node: A device in the scan list that defines the communication with a slave (GE relay)
on the Modbus sub-network.
•Scan list: List of configured slaves with transactions on the sub-network.
•Sub-network: Modbus network that logically is located on a subsidiary level with
respect to the fieldbus and to which the P485 acts as a gateway.
•Transaction: A generic building block that is used in the sub-network scan list and
1–2P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE
defines the data that is sent out the sub-network.
INTRODUCTION
Profibus
master (PLC)
HMI
Profibus
slave
Profibus network
P485
PC for configuration
and monitoring
Multi-drop
Multi-node Modbus network
Single-node Modbus network
RS232 port
PC for configuration
and monitoring
Profibus slave
HMI
Profibus
master (PLC)
Profibus network
P485
About the P485 Modbus to Profibus Converter
APPLICATIONThe P485 Modbus to Profibus Converter (or P485) acts as a gateway between the Modbus
protocol and a Profibus-DP network. Integration of industrial devices is enabled without
loss of functionality, control, and reliability, both when retrofitting to existing equipment as
well as when setting up new installations.
GENERAL FEATURES•DIN-rail mountable
MODBUS NETWORK•RS232/RS422/RS485 communications
FIELDBUS INTERFACE
FEATURES
Figure 1-2: Typical applications
Features
•Save/load configuration in flash
•CE, UL, and cUL marked
•Multi-drop or single-node configurations
•Modbus RTU Master mode
•Supports up to 50 commands
•Configuration via EnerVista P485/D485 Setup software
•Complete Profibus-DP slave functionality according to IEC 61158
•Node Address range: 1 to 99 using on board switches
•Baud rate range: 9.6 kbps to 12 Mbps. Auto baud rate detection supported.
•Transmission media: Profibus bus line, type A or B specified in IEC 61158
P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE1–3
INTRODUCTION
ORDER CODESThe following table illustrates the order codes for the P485 Modbus to Profibus Converter.
Ordering
Table 1–1: P485 order codes
P485– *
Base unitP485|P485 Modbus to Profibus Converter
CWith configuration cable
XNo configuration cable
Specifications
MECHANICALHOUSING
Plastic housing with snap-on connection to DIN-rail, protection class IP20
DIMENSIONS
L x W x H:120 mm × 75 mm × 27 mm
(4.72-in × 2.95-in × 1.06-in)
PROTECTION CLASS
Protection class:IP20
ELECTRICAL
CHARACTERISTICS
POWER SUPPLY
Power:24 V ±10% (for use in class 2 circuits)
POWER CONSUMPTION
Maximum power consumption: 280 mA on 24 V
Typically power consumption: approximately 100 mA
COMMUNICATIONSBAUD RATES
Baud rate (Profibus)9.6, 19.2, 45.45, 93.75, 187.5, and 500 kbps; 1.5, 3, 6, and 12 Mbps
Baud rate (Modbus)1200, 2400, 4800, 9600, 19200, 38400, and 57600 bps
Communication profile: Profibus-DP
Supported features:synchronous, freeze, watchdog
Modbus interface:RS232, RS422, RS485
Profibus interface:RS485 (type A or B)
ENVIRONMENTALRELATIVE HUMIDITY
The product is designed for a relative humidity of 0 to 95% non-condensing
TEMPERATURE
Operating:0 to 55°C
Non Operating:–5 to 85°C
EMC COMPLIANCECE-MARK
Certified according to European standards unless otherwise is stated
Emission:according to EN 50081-2:1993
Immunity:according to EN 61000-6-2:1999
UL/C-UL COMPLIANCE
This unit is an open type listed by the Underwriters Laboratories.
The certification has been documented by UL in file E214107.
1–4P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE
GE Consumer & Industrial
P485 Modbus to Profibus
Converter
Chapter 2: Installation
Installation
Quick install
PROCEDURE1.Snap the P485 on to the DIN-rail (see DIN-rail mounting on page 2–5).
2.Connect the Profibus cable (see Profibus connector on page 2–2).
3.Connect the serial Modbus network cable (see Modbus connector on page 2–4 for
details).
4.Connect a PC using the configuration cable (see Configuration cable on page 2–3).
5.Connect the power cable and apply power to the unit (see Power connector on page
2–4 for details).
6.Start the EnerVista P485/D485 Setup software.
7.Normally, the EnerVista P485/D485 Setup detects the correct serial port. If this does
not occur, select the correct port through the Port menu item.
8.Configure the P485 using EnerVista P485/D485 Setup and download the configuration
to the unit.
9.Configure and power-up the Modbus network device for communication.
Electrical installation
OVERVIEWThe location of the various electrical connectors is shown below.
P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE2–1
INSTALLATION
E
A
B
C
D
Figure 2-1: P485 electrical connections
PROFIBUS CONNECTORThe Profibus connector is indicated as A in the figure above. This connector is used to
connect the P485 to the Profibus network.
The pin assignments for the Profibus connector are shown below.
Table 2–1: Profibus connector pin assignments
PinSignalDescription
1--
2--
3B-LinePositive RxD/TxD (RS485)
4RTS *Request To Send
5GNDBUS **Isolated ground from the RS485 side
6+5 V BUS **Isolated +5V output from the RS485 side (80 mA maximum)
7--
8A-LineNegative RxD/TxD (RS485)
9--
*Used in some equipment to determine the direction of transmission. However, in normal
applications only A-Line, B-Line and Shield are used.
** Used for bus termination. Some devices such as optical transceivers (RS485 to fibre optics) may
require power from these pins.
51
69
(female)
Figure 2-2: Profibus connector
The following Profibus connectors are recommended:
•Profibus Max standard, part number 134928 and Profibus reversed, part number
104577, from http://www.erni.com
•Fast connect bus connector, part number 6GK1500-0FC00 or 6ES7 972-0BA50-0XA0,
from http://www.siemens.com
2–2P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE
INSTALLATION
CONFIGURATION CABLEThe PC connector is indicated as B in Figure 2-1: P485 electrical connections on page 2–2.
This connector is used to connect the P485 to a PC using the configuration cable for
configuration and monitoring purposes.
A P485/D485 configuration cable can be purchased from GE Multilin. The wiring for the
configuration cable is shown below.
MODBUS CONNECTORThe Modbus connector is indicated as C in Figure 2-1: P485 electrical connections on page
2–2. This connector is used to connect the P485 to the serial network. Based on the
configuration selected in the EnerVista P485/D485 Setup software, the corresponding
signals are activated.
51
69
(female)
Figure 2-6: Modbus connector
Table 2–4: Modbus connector pin assignments
PinDescriptionRS232RS422RS485
1+5 V output (50 mA max)
2RS232 Rx3
3RS232 Tx3
4Not connected
5Ground333
6RS422 Rx +3
7RS422 Rx –3
8RS485 + / RS422 Tx+33
9RS485 – / RS422 Tx–33
2–4P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE
POWER CONNECTORThe power connector is indicated as D in Figure 2-1: P485 electrical connections on page
2–2. Use this connector to apply power to the P485.
Pin 1: +24 V DC;
Pin 2: ground
Use 60/75 or 75°C copper (CU) wire only. The terminal tightening torque must be between
5 to 7 lbs-in (0.5 to 0.8 nm).
NOTE
12
Figure 2-7: Power connector
Mechanical installation
DIN-RAIL MOUNTINGThe DIN-rail connector is internally connected to the P485.
ONOFF
Figure 2-8: Mounting the P485 to the DIN-rail
To snap the P485 on, first press the P485 downwards (1) to compress the spring on the DINrail connector, then push the P485 against the DIN-rail as to make it snap on (2)
To snap the P485 off, push the P485 downwards (1) and pull it out from the DIN-rail (2), as to
make it snap off from the DIN-rail.
INSTALLATION
11
22
Indicators and switches
STATUS INDICATORSThe status indicators for the P485 Modbus to Profibus Converter are indicated below.
1
3
5
2
4
6
Figure 2-9: P485 status indicators
P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE2–5
INSTALLATION
Table 2–5: P485 status indicators
NumberDescriptionStateStatus
1Profibus onlineOffNot online
GreenOnline
2Profibus offline OffNot offline
RedOffline
3Not used--
4Profibus
diagnostics
5Subnet status *
(Modbus)
6Device statusOffPower off
* This LED turns green when all transactions have been active at least once. This includes any
transactions using “change of state” or “change of state on trigger”. If a timeout occurs on a
transaction, this LED will turn red.
OffNo diagnostics present
Red, flashing 1 HzError in configuration
Red, flashing 2 HzError in user parameter data
Red, flashing 4 HzError in initialisation
OffPower off
Green, flashingInitializing and not running
GreenRunning
RedStopped or subnet error, or timeout
Alternating Red/
Green
GreenInitializing
Green, flashingRunning
Red, flashingIf the device status LED is flashing in a
Invalid or missing configuration
sequence starting with one or more red
flashes, note the sequence pattern and
contact GE Multilin
CONFIGURATION
SWITCHES
The configuration switches are used to set the Profibus node address. Normally, these
switches are covered by a plastic hatch. Note that the node address can not be changed
during runtime, i.e. the P485 requires a reset for any changes to have effect. Recycle the
power supply to reset the module
A
B
Figure 2-10: P485 configuration switches
The node address is configured using two rotary switches as follows:
For example, to set the node address to 42, set switch A to “2” and switch B to “4”.
When removing the hatch, avoid touching the circuit boards and components. Exercise
caution when using tools to open the hatch.
Profibus installation procedure
PROFIBUS
CONFIGURATION TOOL
Each device on a Profibus-DP network is associated with a GSD file, which contains all
necessary information about the device. This file is used by the Profibus configuration tool
during configuration of the network. The file is available for download at the GE Multilin
website at http://www.GEmultilin.com
(the GSD file is named ‘P48509E5.GSD’).
It is necessary to import the GSD file in the Profibus configuration tool in order to
incorporate the P485 as a slave in the network. The properties for the P485 must then be
configured from the Profibus configuration tool. This includes setting up the node address,
input/output data areas and offset address.
•Node address: The node address in the Profibus configuration tool should be set to
match the one selected using the on board configuration switches of the P485 (see
Configuration switches on page 2–6).
•Setting up input/output data areas: Input/output data are arranged as logic modules
in the Profibus configuration tool. Which modules to use depends on the application.
The modules are composed together in the “module list” for the P485 device.
It is possible to select modules freely to compose the required input/output sizes, see
example below.
•Offset address: The offset addresses can be chosen freely. However, certain
restrictions may apply depending on what PLC/Profibus master is used.
PROFIBUS NETWORK
TERMINATION
If the P485 is the last node on a Profibus segment, it is necessary to use a Profibus
connector with integrated termination switch.
•The termination switch should be set to ‘ON’ if...
– The P485 is the last physical node on a network segment
– No other termination is used at this end of the network
•The termination switch should be set to ‘OFF’ if...
– There are other nodes on either side of the P485 in the network segment
LINKSAdditional information about the Profibus fieldbus system can be found at http://
www.profibus.com.
P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE2–7
INSTALLATION
Troubleshooting
DESCRIPTIONProblem during configuration upload/download. The Config Line LED turns red.
•Serial communication failed – try again.
The serial port seems to be available, but it is not possible to connect to the P485.
•The serial port may be in use by another application. Exit EnerVista P485/D485 Setup
and close all other applications including the ones in the system tray and try again.
•Select another serial port and try again.
Poor performance.
•Right click ‘Modbus Network’ in the Navigation window and select ‘Modbus Network
Status’ to see status/diagnostic information about the Modbus network. If the P485
reports very many re-transmissions, check your cabling and / or try a lower baud rate
setting for the sub network (if possible).
•Is the Modbus Network Monitor in EnerVista P485/D485 Setup active? The Modbus
network monitor has a negative influence on the overall performance of the P485, and
should only be used when necessary.
•Is the Node Monitor in EnerVista P485/D485 Setup active? The node monitor has a
negative influence on the overall performance of the P485, and should only be used
when necessary.
2–8P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE
GE Consumer & Industrial
Internal Memory Buffer
Output data
(up to 244 bytes)
Input data
(up to 244 bytes)
Sub Network
Fieldbus
General data
1024 bytes
P485 Modbus to Profibus
Converter
Chapter 3: Data exchange
Data exchange
Overview
DESCRIPTIONData from the fieldbus (Profibus) and the sub network (Modbus) is stored in an internal
memory buffer. This is a easy method for data exchange where the fieldbus control
system simply reads and writes data to pre-defined memory locations, and the serial sub
network also use the same internal memory buffer to read and write data. Refer to Figure
3-2: Data exchange overview on page 3–2 for details.
INTERNAL MEMORY
BUFFER STRUCTURE
The internal memory buffer can be seen as a memory space with three different types of
data; input data, output data and general data.
•Input data: This is data that should be sent to the fieldbus. The P485 can handle up to
244 bytes of input data. The total input/output data must not exceed 416 bytes.
•Output data: this is data recieved from the fieldbus. The P485 can handle up to 244
bytes of output data.
•General data: This data cannot be accessed from the fieldbus, and is used for
transfers between nodes on the sub-network, or as a general “scratch pad” for data.
The P485 can handle up to 1024 bytes of general data.
Figure 3-1: Internal memory buffer
P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE3–1
DATA EXCHANGE
PLC memory
The PLC exchanges data
via the Profibus network
between its internal input
area and the input area
of the P485
I/O inputs
Current Ia
Profibus network
Internal memory buffer
of the P485
Input data areaOutput data areaGeneral data area
0x00000x02000x0400
Current IaCT PRIMARY
The data in the input area of
the P485 contains data received
from nodes on the Modbus
sub-network (sent in to the P485
from the sub-network)
Modbus sub-network
I/O outputs
CT PRIMARY
The data in the output area of
the P485 contains data received
from Profibus. In this case, it is
the CT PRIMARY setting of the
PQMII meter.
The PLC exchanges data
via the Profibus network
between its internal output
area and the output area
of the P485
Modbus slave (e.g. PQMII)
CT PRIMARY setting
Current Ia actual value
Figure 3-2: Data exchange overview
Memory Map
MEMORY LOCATIONSWhen configuring the sub-network, use the memory locations shown below:
AddressContentsAccess
0x0000 to 0x0001Status registerread/write
0x0002 to 0x00F3Input data arearead/write
0x00F4 to 0x01FFReserved-
0x0200 to 0x0201Control registerread only
0x0202 to 0x02F3Output data arearead only
0x02F4 to 0x03FFReserved-
0x0400 to 0x7FFGeneral data arearead/write
3–2P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE
DATA EXCHANGE
Node
Transaction
Transaction
Message frame
Byte
WordDataCRCByte
Frame objects
Message frame
ByteWordDataCRCByte
Frame objects
Message frame
Byte
WordDataCRCByte
Frame objects
•Status register (0x0000 to 0x0001): If enabled, this register occupies the first two
bytes in the input data area. For more information, see Control and status registers on
page 8–1.
•Input data area (0x002 to 0x00F3): This area holds data that should be sent to the
fieldbus (see the status and control registers).
•Control register (0x0200 to 0x0201): If enabled, these register occupies the first two
bytes in the output data area. For more information, see Control and status registers
on page 8–1.
•Output data area (0x200 to 0x2F3): This area holds data received from the fieldbus.
Data cannot be written to this area.
•General data Area (0x0400 to 0x7FF): This data cannot be accessed from the fieldbus,
and should be used for transfers between nodes on the sub-network, or as a general
“scratch pad” for data.
Protocol configuration
DESCRIPTIONIn order to be able to communicate on the Modbus sub-network, the P485 must be
supplied with a description of the required sub-net protocol. To accomplish this, the
EnerVista P485/D485 Setup software features a flexible protocol-programming system,
allowing the P485 to interpret and exchange data with almost any serial device on the
Modbus sub-network.
COMMUNICATION MODEThe P485 supports the Modbus Master communication mode. In this mode, the P485 is
setup to use the Modbus RTU protocol and implements a Modbus master for data
exchange between the fieldbus and one or more devices on the sub-network. Refer to
Chapter 5 for additional details.
PROTOCOL BUILDING
A description of the building blocks used to describe the sub-net protocol is shown below.
BLOCKS
Figure 3-3: Modbus protocol blocks
•Node: In the P485, a node holds all transactions and parameters for a particular
device on the sub network.
•Transaction: Transactions contains messages to be transmitted on the sub-network.
A transaction consists of one or more message frames (see figure above), and has a
few general parameters to specify how and when the transaction should be used on
the sub-network.
•Commands: A command is a pre-defined transaction that has been stored in a list in
the EnerVista P485/D485 Setup software. This improves readability as well as
simplifying common operations by allowing transactions to be stored and reused.
P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE3–3
DATA EXCHANGE
•Message frame: The message frame contains a description of what is actually
transmitted on the sub-network and consists of frame objects (see figure above).
•Frame object: Frame objects are used to compose a message frame. Frame objects
include fixed values, dynamic values retrieved from a specified memory location in the
P485, or strings.
3–4P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE
GE Consumer & Industrial
P485 Modbus to Profibus
Converter
Chapter 4: Software overview
Software overvie w
Introduction
DESCRIPTIONEnerVista P485/D485 Setup is a PC-based configuration software used to describe the
protocol and communication properties for a serial network. When the configuration is
finished and the functionality is tested, it is possible to send memory allocation information
to a printer using EnerVista P485/D485 Setup.
EnerVista P485/D485 Setup can also be used for troubleshooting and diagnostic of the
P485 and the serial network during runtime.
SYSTEM REQUIREMENTSThe following hardware and software is required to use the EnerVista P485/D485 Setup
software.
•Pentium 133 MHz or higher
•10 MB of free space on the hard drive
•8 MB RAM
•Windows 95/98/NT/2000/XP
•Internet Explorer 4.01 SP1 or higher
Installation procedure
DESCRIPTIONThere are two different ways of installing EnerVista P485/D485 Setup; either via the GE
EnerVista CD or from the GE Multilin website at http://www.GEmultilin.com.
INSTALLING FROM
ENERVISTA CD
INSTALLING FROM THE
GE MULTILIN WEBSITE
Run ‘setup.exe’ and follow the on screen instructions
Download the self-extracting EXE file from the GE Multilin website at http://
www.GEmultilin.com.
P485 MODBUS TO PROFIBUS CONVERTER – USER GUIDE4–1
Loading...
+ 53 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.