
TRANSFERRED
TRIP
AUXILIARY
RELAYS
The
tions
line
transferred
The
and
permissive
schemes
telephone
and
RI,
units
are
receiver
Type
10
its
picked
frequency
transferred
loss
of
receipt
alarm
high-speed
transferred
reclosing.
The
missive
is
used
Type
10
when
the
three
telephone
TTZ,
and
pick
up
“b”
switch
a
continuous
is
open.
purpose
scheme.
inately
external
The
TTZ
necessary
missive
The
and
permissive
reaching
involved.
necessary
two
telephone
TX,
which
NAA27H
Type
are
auxiliary
NAA27H
via
type
andatarget
auxiliaries
units
tone
up
receiver
trip
the
guard
of
a
transferred
during
trip
trip
NAA27J
cverreaching
in
conjunction
pilot
channel
BX.
6
cycles,
of
on
the
transferred
The
for
unit
It
has
cycle,
1
capacitor
unit
in
overreaching
NAA27K
schemes
It
transferred
are
relay.
APPLICATION
relays
NAA
receiver.
test.
is
provides
the
is
type
identical
relays
trip
schemes
relay
is
underreaching
10
Type
relay
units
seal-in
to
which
the
are
position
unit.
circuit
channel.
The
circuits,
signal,
relay
transferred
with
involved
Type
is
relay
type
BX
The
(60
cycle
associated
TTY
unit
in
use
a
normal
but
to
the
can,
obtain
the
transferred
schemes.
relay
is
underreaching
when
required
trip
relay
with
designed
tones,
The
by
Its
and
trip
RI
and
is
or
unit
trip
permissive
drop
11
intended
multi-terminal
units
covered
for
as
designated
unit.
guard
normally
GX
a
contact
function
to
sound
TX
The
signal
unit
including
initiates
intended
the
NAA27H
with
carrier.
50
units
designated
which
basis)
circuit
signal
is
intended
out
desired,
longer
small
trip
or
in
addition
auxiliaries.
designated
the
similar
these
by
the
in
use
described
use
for
transferred
It
includes
as
The
and
trip
included
is
normally
of
is
to
an
Unit
picks
to
is
energized
the
use
for
schemes.
trip
relay
the
NAA27L
has
a
operated
is
breaker
when
the
as
overreaching
time
of
be
used
drop
coordinating
circuit
for
use
permissive
to
units
TYPE
NAA
DESCRIPTION
TX
the
in
the
on
an
all
It
a
a
an
underreaching
Type
four
GX,
TX,
ponding
a
high-speed
channel.
type
limiting
OPERATING
shown
connection
tions
rated
available
The
and
connection
NAA27H
Table
RATINGS
Carry
Carry
Carry
Minimim
Minimum
DC
60
50
DC
Interrupting
instruc
various
in
TX,
GX
and
frequency
held
the
block
alarm
provide
received
high
on
when
It
includes
as
time
to
breaker
a
general
approxi
with
out
times.
on
on
direct
lines
the
It
includes
GX
as
below.
direct
trip
three
GX,
in
guard
upon
up
by
speed
per
relay
TTY,
delay
by
send
time
per
over-
are
other
and
in
the
The
NAA27L
carrier
50
telephone
RI,
and
GX,
and
units
It
should
units
shunt
The
operating
in
the
The
Type
are
DC
voltage
for
resistance
associated
The
combination
and
I.
30
Amos
10
Amps
continuously
Operating
Drop-out
resistance
Hz
impedance
Hz
impedance
resistive
transferred
type
TTY,
RI
in
the
relay
be
in
these
resistors.
tabulations
diagrams.
NAA
suitable
24,
values
resistors
diagram.
NAA27K
OF
for
for
(Ohms)
(Ohms)
(Ohms)
rating
relay
is
intended
trip
is
units
noted
used
relays
and
are
NAA27H
used
that
relays
as
units,
target
a
identical
to
the
are
the
relay.
key
coils
furnished
CHARACTERISTICS
characteristics
accompanying
RATINGS
relays
for
shown
48,
TARGET
(Sec)
(Sef)
(Amp)
(Amp)
(Amp)
(Amps)
continuous
on
125
of
are
target
relays
TABLE
covered
the
and
250
the
telephone
listed
and
is
I
AND
0.2
0.05
0.45
0.37
0.2
0.05
8.3
50
42
2.5
(‘125
for
applications
pilot.
designated
seal-in
with
The
type
the
of
all
of
by
these
operation
nameplate
volt
applications.
on
seal-in
rated
SEAL-IN
2.0
2.2
2.0
2.3
2.0
0.5
.24
.65
.54
Amp
VDC
use
all
the
as
the
TTY
the
type
Dual
‘2
0.6
0.5
5.0
1.2
0.6
0.15
0.78
6.2
5.1
on
direct
where
It
includes
as
unit.
corres
unit
50
carrier
telephone
with
units
internal
instruc
at
and
relays
internal
unit
in
shown
UNIT
Hated
0
30
TX,
The
surge
are
the
are
the
2.0
3.5
2.6
2.0
0.5
0.18
0.65
0.54
is
in
c-er-v
further
hc
:,ut
T:yese
posshle
purh.ers
To
ns
Instractlons
inlarmatioji
tsr-
extent
Iaruraz2ce
cc.9tngency
b
purposc,
required
desired
is
do
given
the
not
purport
be
to
or
matter
the
products
with
met
should
respect
to
in
should
cover
connection
particular
be
described
to
all
referred
local
details
with
problems
herein
codes
or
installation,
to
the
meet
and
variations
alise
General
applicable
ordinances
which
operation
are
Electric
in
ANSI,
because
equipment
or
not
Company.
IEEE
maintenance.
covered
and
they
nor
sufficiently
NEMA
vary
to
greatly.
provide
Should
standards;
for
for

1)11-74
ç30)
tripping
663
If
the
amperes,
relay
Transferred
tripping
it
is
be
used.
Trip
Auxiliary
current
recommended
should
that
Relays
exceed
an
Type
thirty
auxiliary
NAA
INSTALLATION
These
control
protect
receipt
for
any
or
damage
a
claim
company
Electric
Reasonable
ing
the
injured
If
they
should
place
chips.
The
installation
1.
2.
3.
4.
TX
UNIT
The
rated
pick
seconds
CX
voltage
p
UNIT
The
rated
voltage
out
ime
oe-eneriized
RI
UNIT
panel,
them
of
damage
should
Company
relay
or
the
that
Contacts
The
relays
The
0.005
When
hand,
inch
a
TX
time
or
CX
should
relays,
vill
against
the
relay,
sustained
resulting
hefiledatoncewiththe
and
the
care
in
adjustments
relays
be
stored
is
free
INSPECTION
relay
0.005
and
the
normally
normally
inch
the
the
gap
inch
should
should
and
CHECK
unit
should
across
at
unit
across
be
from
rated
should
0.4
rated
less.
RECEIVING
when
be
not
shipped
damage.
an
examination
during
from
rough
nearest
notified
Sales
promptly.
should
order
that
disturbed.
are
not
to
be
in
from
their
moisture,
be
inspected
following
should
open
not
contacts
be
have
closed
wipe.
telephone
open
the
wipe.
relays
contacts
closed
TESTS
pick
the
operating
voltage
pick
the
operating
to
0.5
seconds
voltage.
included
in
cartons
handling
Office
be
exercised
none
installed
original
points
tarnished.
a
gap
contacts
should
contacts
up
at
should
up
at
circuit.
as
lrnniediatelv
should
shipment.
transportation
of
of
the
immediately
cartons
dust
and
at
the
checked:
of
both
of
0.015
should
are
operated
have
should
80c
circuit.
be
80
when
the
a
part
designed
be
is
the
in
unpack
parts
metallic
time
telephone
a
or
less
8
milli
or
less
The
unit
of
upon
made
If
injury
evident.
General
are
in
inch.
have
by
0.0
15
have
of
The
of
drop
is
a
to
a
of
a
relays
Figs.
BX
UNIT
The
rated
be
95
TTY
The
rated
given
R
Ia’
e
NAA27J
NAA27L
NAA27L
NAA27L
NAA27L
TTZ
UNIT
The
rated
application
cycles.
application
cycles.
Note
that
shown
polarities
tests.
LOCATION
The
dust
and
facilitate
The
surface.
are
shown
The
covered
1
to
voltage.
to
105
UNIT
TrY
voltage.
below.
Forms
Forms
Forms
Forms
TTZ
voltage.
The
in
on
the
should
location
excessive
inspection
relays
The
in
internal
4
inclusive.
RN
unit
shonld
Pick
The
UI)
should
pickup
milliseconds.
unit
1—17
21-23
25-27
28
&
up
unit
should
with
with
many
internal
Pick
Type
pick
Type
be
time
UI)
10
up
time
50
instances
connection
observed
AND
Fig.
should
should
outline
6
vibration
and
and
and
be
testing.
be
7.
CONNECTIONS
wiring
by
these
diagrams
instructions
iliek
time
at
pick
and
Pickup
Time
Bms
or
8ms
or
2ms
or
4ms
or
2ms
or
pick
up
of
tone
ci
carrier
polarity
when
MOUNTING
clean
and
and
mounted
panel
drilling
:“
at
rated
up
at
dropout
less
less
less
less
less
at
70R
units
channels
units
channels
diagrams.
making
dry,
well
on
for
the
are
80,
voltage
8Y
Propout
Time(rns)
33
33
2nis
2ms
2nis
or
intended
intended
marks
free
lighted
a
vertical
diagrams
various
shown
or
or
is
is
should
less
time
to
to
or
or
or
less
2.75
These
check
from
50
50
less
less
less
for
1.25
for
are
to
in
s
ut
of
is
of
v’ace.
.t
Sc
-1
c
The
nds
o:d..
HI
ann
Pick
unit
drop
should
up
time
out
pick
should
tim
UI)
at
he
from
7O
Less
115
OI
less
than
to
I
of
16
1i
rateci
milli—
m.lli—
rounds
ease
with
\VJ
r(
Unless
he
a
or
mounted
the
grounded
()nductor
its
equivalent.
relay
case,
through
not
on
less
a
steel
it
than
is
a
panel
which
recommended
mounting
I2
B
&‘
S
stud
gauge
adequately
that
or
screw
copper
the