GE Monogram ZV48T, Monogram ZV36T, Monogram ZV48S, Monogram ZV36S, Monogram ZV30T Installation Instructions Manual

...
Page 1
Installation Instructions
If you have questions, call 800.GE.CARES or visit our website at: www.monogram.com
30", 36" and 48" Professional Vent Hoods
Monogram.
®
1
Page 2
Installation Instructions
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT - Save these instructions for
local inspectors use.
IMPORTANT - Observe all governing codes
and ordinances.
Note to Installer - Be sure to leave these instructions with the Consumer.
Note to Consumer - Keep these instructions for future reference.
Skill Level Installation of this vent hood requires basic mechanical and electrical skills.
Completion time – 1 to 3 hours.
Proper installation is the responsibility of the installer.
Product failure due to improper installation is not
covered under the Warranty.
CAUTION:
Due to the weight and size of these vent hoods and to reduce the risk of personal injury or damage to the product, TWO PEOPLE ARE REQUIRED FOR
PROPER INSTALLATION.
PRUDENCE
À cause du poids et de la taille de ces hottes et pour reduire le risque de blessures et de dommages, IL FAUT
DEUX PERSONNES POUR FAIRE L’INSTALLATION CORRECTEMENT.
WARNING:
To reduce the risk of fire or electrical shock, do not use this range hood with any external solid-state speed control device. Any such alteration from original factory wiring could result in damage to the unit and/or create an electrical safety hazard.
AVERTISSEMENT
Pour réduire le risque dincendie ou de choc électrique, il ne faut pas utiliser cette hotte avec un régulateur de vitesse électronique externe. Toute modification de ce type du branchement dusine peute endommager lappareil ou créer un risque de choc électrique.
TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCTWORK.
WARNING:
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: A. Use this unit only in the manner intended by the
manufacturer. If you have any questions, contact the manufacturer.
B. Before servicing or cleaning unit, switch power off at
the service panel and lock service panel to prevent power from being switched on accidentally. If the service panel cannot be locked, fasten a tag or prominent warning label to the panel.
AVERTISSEMENT
POUR RÉDUIRE LE RISQUE D’INCENDIE, DE CHOC ÉLECTRIQUE OU DE BLESSURES, IL FAUT OBSERVER LES REGLES SUIVANTES: A. Utiliser cet appareil uniquement de la maniére
prévue par le fabricant. En cas de question, consulter le fabricant.
B. Avant toute intervention ou nettoyage, couper
lalimentation électrique au disjoncteur et verrouiller le panneau du disjoncteur pour éviter la mise sous tension accidentelle. Sil nest pas possible de verrouiller le panneau du disconcteur, attacher un placard ou une étiquette trés visible au panneau.
For general ventilating use only. Do not use to exhaust hazardous or explosive materials or vapors.
Structural framing, installation work and electrical wiring must be done by qualified person(s). In accordance with all applicable codes and standards including fire-rated construction.
Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturers guideline and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
Local codes vary. Installation electrical connections and grounding must comply with applicable codes. In the absence of local codes, the vent should be installed in accordance with National Electrical Code ANSI/NFPA 70-1990 or latest edition.
CAUTION: To reduce risk of fire and to
properly exhaust air, be sure to duct air outside – Do not vent exhaust air into spaces within walls or ceilings or into attics, crawl spaces, or garages.
PRUDENCEIl faut prendre soin d’installer
un conduit vers l’extérieur pour réduire le risque dincendie et pouvoir évacuer lair correctement. Il ne faut pas évacuer lair correctement. Il ne faut pas évacuer lair dans lespace entre les parois dun mur, un plafond ou un grenier, un espace sanitaire ou un garage.
2
Page 3
Installation Instructions
CONTENTS
Product Dimensions .........................................................3
Installation Clearances .....................................................4
Optional Duct Cover Accessories .................................... 4
Installation Height, Duct Cover Accessories................... 5
Advance Planning ............................................................. 6
Power Supply .................................................................... 6
Duct Fittings...................................................................... 7
Tools and Materials Required..........................................8
Remove the Packaging ..................................................... 8
PRODUCT DIMENSIONS
12"
18"
47-15/16"
Parts Provided ...................................................................9
Step 1, Determine Ductwork and Wiring Locations ....10
Step 2A, Install Hood Onto Wall ...................................11
Step 2B, Install Hood Beneath Soffit ............................ 12
Step 3, Connect Ductwork ............................................. 13
Step 4, Connect Electrical .............................................. 13
Step 5, Install Duct Covers ............................................. 13
Step 6, Install Motor .......................................................14
Step 7, Install Filters ....................................................... 14
Step 8, Install Implement Rods ..................................... 15
12"
18"
40"
25"
Model ZV48S With Straight Sides
12"
18"
25"
Model ZV36S With Straight Sides
12"
18"
35-15/16"
35-15/16"
29-15/16"
47-15/16"
25"
Model ZV48T With Tapered Sides
12"
18"
25"
Model ZV36T With Tapered Sides
12"
18"
35-15/16"
22"
47-15/16"
28"
25"
Model ZV30S With Straight Sides
29-15/16"
25"
Model ZV30T With Tapered Sides
3
29-15/16"
Page 4
Advance Planning
INSTALLATION CLEARANCES
These vent hoods are designed to be installed onto a wall or beneath a soffit or cabinet.
Install these hoods* 30" Min. to 36" Max. above the cooking surface.
*These hoods may be installed 24" min. above a gas or
electric drop-in style cooktop. Always observe the 30" to 36" clearance when installed over any professional style cooktop or range.
Note: Clearances may vary due to type of cooking product and local codes. Check with local inspectors to be sure standard is applicable.
Soffit Installation
SOFFIT
30" MIN.
36" MAX.
In this installation the ductwork running from the top of the hood will be concealed in the soffit or upper cabinetry.
Wall Mount Installation
OPTIONAL DUCT COVER ACCESSORIES
Standard and Full-Width decorative duct covers are available in 6" and 12" heights. Duct covers may be stacked, in various combinations, to conceal the ductwork running from the top of the hood to the ceiling.
Before you begin, you should determine the installation height of the hood and order the correct size duct cover. The duct covers should be ordered at the same time as the vent hood and be on site before installation. Order the duct cover corresponding to your model.
Standard Duct Covers
6" Duct Cover
12" Duct Cover
6" Duct Covers Hood Model 6” Duct Cover Dimensions
ZV48T, ZV48S ZX48DC6 6"H x 19-11/16"W x 11-7/8"D ZV36T, ZV36S ZX36DC6 6"H x 15-3/4"W x 11-7/8"D ZV30T, ZV30S ZX36DC6 6"H x 15-3/4"W x 11-7/8"D
12" Duct Covers Hood Model 12 Duct Cover Dimensions
ZV48T, ZV48S ZX48DC12 12"H x 19-11/16"W x 11-7/8"D ZV36T, ZV36S ZX36DC12 12"H x 15-3/4"W x 11-7/8"D ZV30T, ZV30S ZX36DC12 12"H x 15-3/4"W x 11-7/8"D
30" MIN.
36" MAX.
For this installation, a decorative duct cover is available to conceal the ductwork running from the top of the hood. Use of the duct cover requires special consideration to the installation height above the countertop.
Full-Width Duct Covers
Optional 6" or 12" Duct
6" Duct Covers Hood Model 6 Duct Cover Dimensions
ZV48S ZX48FWDC6 6"H x 47-15/16"W x 11-7/8"D ZV36S ZX36FWDC6 6"H x 35-15/16"W x 11-7/8"D ZV30S ZX30FWDC6 6"H x 29-15/16"W x 11-7/8"D
12" Duct Covers Hood Model 12 Duct Cover Dimensions
ZV48S ZX48FWDC12 12"H x 47-15/16"W x 11-7/8"D ZV36S ZX36FWDC12 12"H x 35-15/16"W x 11-7/8"D ZV30S ZX30FWDC12 12"H x 29-15/16"W x 11-7/8"D
Cover
4
Page 5
Advance Planning
DETERMINE INSTALLATION HEIGHT, DUCT COVER ACCESSORIES
These vent hoods must be installed 30" min. to 36" max. above the standard 36" high cooking surface. The exact hood installation height is determined by the ceiling height.
1. Measure the exact ceiling height.
2. Review the chart at right to determine the
range of possible hood installation heights that can be accomplished with one or more duct covers.
3. Increase or decrease hood installation height to accommodate the fixed 6" or 12" duct covers.
4. Duct covers may be stacked, in various combinations, to reach ceiling heights.
Straight or Taper-Sided Hoods
Duct Covers
18" Hood
Height
Ceiling Height to Floor
Installation Height
Tapered or Straight-Sided
Straight-Sided Hoods Hoods Only
w/ Standard w/ Full-Width
Duct Cover Duct Cover
*Possible Actual Hood Ceiling Installation 6" Duct 12" Duct 6" Duct 12" Duct Height Height Covers Covers Covers Covers
7' 11" 35" 1 1
8' 0" 30" 1 1 8' 0" 36" 1 1
8' 1" 31" 1 1
8' 2" 32" 1 1
8' 3" 33" 1 1
8' 4" 34" 1 1
8' 5" 35" 1 1
8' 6" 30" 1111 8' 6" 36" 1 1
8' 7" 31" 1111
8' 8" 32" 1111
8' 9" 33" 1111
8' 10"34" 1111
8' 11"35" 1111
9' 0" 30" 2 2 9' 0" 36" 1111
9' 1" 31" 2 2
9' 2" 32" 2 2
9' 3" 33" 2 2
9' 4" 34" 2 2
9' 5" 35" 2 2
9' 6" 30" 1212 9' 6" 36" 2 2
9' 7" 31" 1212
9' 8" 32" 1212
9' 9" 33" 1212
9' 10"34" 1212
9' 11"35" 1212
10' 0" 30" 3 3 10' 0" 36" 1212
10' 1" 31" 3 3
10' 2" 32" 3 3
10' 3" 33" 3 3
10' 4" 34" 3 3
*Based on 36" countertop height. Note: Additional duct covers may be used to reach higher ceilings.
5
Page 6
Advance Planning
ADVANCE PLANNING
Ductwork Planning
These vent hoods are equipped for 10" round ductwork. For best performance, use 10" round ductwork on the 48" wide hoods. 30" and 36" hoods may be transitioned to 8" round.
This hood may be vented vertically through upper cabinets, soffit or ceiling. A duct transition piece is supplied for vertical exhaust. Use locally supplied elbows to vent horizontally through the rear wall.
Determine the exact location of the vent hood.
Plan the route for venting exhaust to the outdoors.
Use the shortest and straightest duct route possible.
For satisfactory performance, duct run should not exceed 150 ft. equivalent length for any duct configurations.
Refer to Duct Fittings chart to compute the maximum permissible length for duct runs to the outdoors.
Use metal ductwork only.
Install a wall cap or roof cap with damper at the
exterior opening. Order the wall or roof cap and any transition needed in advance.
Wall Framing for Adequate Support
These vent hoods are heavy. Adequate structural support must be provided. Hoods must be secured to vertical studs in the wall.
It is strongly recommend that the vent hood with duct cover be on site before final framing and wall finishing. This will also help to accurately locate the ductwork and electrical service.
Decorative Duct Covers:
Decorative duct covers, 6" and 12" high, are available to fit all models. The duct cover conceals the ductwork running from the top of the hood to the ceiling or soffit. Stack one or more duct covers over the top of the hood to reach your ceiling height.
POWER SUPPLY
IMPORTANT - (Please read carefully)
WARNING:
FOR PERSONAL SAFETY, THIS APPLIANCE MUST BE PROPERLY GROUNDED.
AVERTISSEMENT – POUR DES
RAISONS DE SÉCURITÉ, CET APPAREIL DOIT ÊTRE CORRECTEMENT MIS À LA TERRE.
Remove house fuse or open circuit breaker before beginning installation.
Do not use an extension cord or adapter plug with this appliance. Follow National electrical codes or prevailing local codes and ordinances.
Electrical supply
These vent hoods must be supplied with 120V, 60Hz, and connected to an individual, properly grounded branch circuit, and protected by a 15 or 20 amp circuit breaker or time delay fuse.
Wiring must be 2 wire with ground.
If the electrical supply does not meet the above
requirements, call a licensed electrician before proceeding.
Route house wiring as close to the installation location as possible on the back wall or ceiling.
Connect the wiring to the house wiring in accordance with local codes.
Grounding instructions
The grounding conductor must be connected to a ground metal, permanent wiring system, or an equipment-grounding terminal or lead on the hood.
WARNING: The improper connection of
the equipment-grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service representative if you are in doubt whether the appliance is properly grounded.
AVERTISSEMENT
Le mauvais branchement du fil de mise à la terre peut causer un choc électrique. En cas de doute, consulter un électricien qualifié ou un technicien pour déterminer si lappareil est à la terre.
6
Page 7
Advance Planning
DUCT FITTINGS
Use this chart to compute maximum permissable lengths for duct runs to outdoors.
Note:
Do not exceed maximum permissable
equivalent lengths!
Maximum recommended duct length for these hoods: 150 feet
Flexible ducting:
If flexible metal ducting is used, all the equivalent feet values in the table should be doubled. The flexible metal duct should be straight and smooth and extended as much as possible.
Do NOT use flexible plastic ducting.
Note:
Any home ventilation system, such as a
ventilation hood, may interrupt the proper flow of combustion air and exhaust required by fireplaces, gas furnaces, gas water heaters and other naturally vented systems. To minimize the chance of interruption of such naturally vented systems, follow the heating equipment manufacturer’s guidelines and safety standards such as those published by NFPA and ASHRAE.
Hoods Are Equipped
For 10" Round Duct
*Hoods are supplied with a 10"
round transition. A locally supplied transition is required for other sizes.
Note:
Outlet on top of hood is
8-1/8" x 8".
Equivalent Quantity Total
Duct Piece Length* Used Length
10" round to 8" round 5 ft.
Round, 1 ft. straight (per foot
length)
3-1/4" x 10" 1 ft. 3-1/4" x 12" (per foot straight length)
8" Dia. 17 ft.
90° elbow 10" Dia. 24 ft.
8" Dia. 10 ft.
45° elbow 10" Dia. 14 ft.
3-1⁄4" x 12" 15 ft. 3-1/4" x 10" 14 ft. 90° elbow
3-1/4" x 10" 8 ft. 3-1/4" x 12" 9 ft. 45° elbow
3-1/4" x 10" 33 ft. 3-1/4" x 12" 36 ft. 90° flat elbow
10" round transition to 3-1/4" x 10" or 3-1/4" x 12" 9 ft.
3-1/4" x 10" or 3-1/4" x 12" to 10" round transition 6 ft.
10" round to 3-1/4" x 10" 16 ft. 3-1/4" x 12" transition 13 ft. 90° elbow
3-1/4" x 10" 9 ft. 3-1/4" x 12" to 10" round 8 ft. transition 90° elbow
Round 8" Dia. 32 ft. wall cap 10" Dia. 41 ft. with damper
3-1/4" x 10" 24 ft. 3-1/4" x 12" wall cap 26 ft. with damper
*Actual length of straight duct plus duct
fitting equivalent. Equivalent length of duct pieces are based on actual tests conducted by GE Evaluation Engineering and reflect requirements for good venting performance with any ventilation hood.
Round 8" Dia. 44 ft. roof cap 10" Dia. 56 ft.
Total Duct Run
7
Page 8
Installation Preparation
TOOLS AND MATERIALS REQUIRED
(NOT SUPPLIED)
Hammer
Pencil and tape measure
Spirit level
Pliers
Metal Snips
Duct tape
Wire cutter/stripper
Safety glasses
Step ladder
Saber saw or Sawsall
REMOVE THE PACKAGING
Lift out the wooden crossmember, as well as the top protective carton.
Lift out the four L shaped polystyrene protection profiles.
Remove the protection moldings around the smaller carton box.
Remove the small box housing the motor.
Lift the hood out of the box.
Wire nuts
Flashlight
Wood
Mounting
Support
Key Hole Saw
Electric or battery operated drill and 1/8", 3/8" bits
Phillips and flat
blade
screwdrdivers
120V 60Hz. 15 or 20 Amp, 2-wire with ground. Properly grounded branch circuit.
Hood
Motor
Parts
Package
10" round metal duct, length to suit installation.
Strain relief for junction cover.
CAUTION: Lift the hood by grasping
the outside edges of the inlet opening of the hood.
Do not lift the hood by the exhaust opening divider damage will occur!
Shipping Carton
Remove the shipping screws holding the wood mounting piece to the back side of the hood.
Set aside the wood mounting piece and screws for later installation. Do not discard.
Remove the V shaped carton insert.
Remove the parts package from the V shaped
cardboard insert.
Remove the junction box cover and knockout.
Install the strain relief onto the back or top of the hood.
Remove all tape and packing material from the hood,
duct transition and motor.
8
Page 9
Installation Preparation
PARTS PROVIDED
Locate the parts packed with the hood.
Allen Wrench
For Implement Rods
HARDWARE PACKAGE
Locate and check contents. Screws shown actual size.
Duct Transition
with Damper
Heat Lamp
(2 with 48" models)
2 Stainless Steel Grease Filters
(3 filters with 48" models)
2 Implement Rods and 4 Stand-offs
4 Phillips head screws to
secure the transition to the
hood outlet on the top
Wood Support
with Original Screws
2 Grease Filter Trays
(3 supports with 48" models.)
2 (3/16") hollow wall anchors
with screws to secure hood
to the wall at the bottom
6 Phillips head screws to
secure hood to the wood
support: (2 secured to
wood support)
2 flat washers
for wall anchors
4 screws to secure the wood
support to the wall
POZIDRIV 3
1 safety screw and lock
washer, to secure the
blower: (screw is marked
with red or blue paint)
9
Page 10
Installation Instructions
Top of Hood
Bottom of Hood
18"
15-3/8"
Wood
Support
*House Wiring
Location
18"
9-7/8"
STEP 1 DETERMINE HOOD, DUCTWORK AND WIRING LOCATIONS
Use a level to draw the cooktop centerline location. Draw the line to ceiling height.
Measure desired distance from the bottom of the hood to the cooking surface, 30" min. to 36" max.
Note: If you are installing the hood with duct covers, be sure to read
Using Duct Cover Accessories page 7. Exact installation height may be determined by use of one or more duct covers.
Use a level to draw a straight horizontal pencil line indicating the bottom of the hood.
From the line indicating the bottom of the hood, measure 15-3/8" up and draw another line for the location of the wood support. See illustration.
FOR VERTICAL (Straight Up) DUCTING:
Use a level to draw a centerline from the bottom of the hood to ceiling or soffit.
If venting out the ceiling, extend the centerline forward on the ceiling or soffit.
Locate the centerline of a 10-1/2" hole on the ceiling or soffit by measuring 6" from the wall.
FOR DUCTING THROUGH REAR WALL:
Measure 9-7/8" above the marked line for the top of the hood. At the centerline, mark location for a 10-1/2" diameter hole.
*Depending on
Hood width and Installation Height.
House Wiring Location:
The junction box is fastened to the back of the hood on the right side.
8-3/8"
Electrical
Area
The recessed back side of the hood provides a large area for the house wiring to exit the wall and be routed to the rear knockout and junction box.
The location for the house wiring depends on the installation height of the hood and the width of the hood.
Remove junction box cover and knockout. Install strain relief.
18-13/16" for 48" Models 12-13/16" for 36" Models
9-13/16" for 30" Models
18-1/16" for 48" Models 12-1/16" for 36" Models 9-1/16" for 30" Models
6-1/2"
Alternate Knockout Locations
If the installation requires, the junction box can be relocated from the back to the top of the hood. Remove 3 screws, align box to top knockout and secure with original screws.
Remove junction box cover and knockout. Install strain relief.
10
Page 11
Installation Instructions
Duct
Transition
Top of
Hood
STEP 2A INSTALL HOOD ONTO WALL
SKIP THIS STEP IF INSTALLING BENEATH A SOFFIT OR CABINET, GO TO STEP 2B.
Locate at least 2 vertical studs at the wood support.
Center the supplied wood support, left to right and below the
15-3/8" marked line.
Wood
15-3/8"
30"
to
36"
Centerline of Installation Space
Secure the wood support to 2 or more vertical studs, using at least 2 of the 4 supplied long screws.
IMPORTANT: Screws must penetrate at least 1-1/2" into vertical studs. Countersink screws into support.
Note: The mounting screws must remain in their original shipping location. These screws are positioned to engage the keyhole slots in the back of the hood.
Support
IMPORTANT: Framing must be capable of supporting up to 150 lbs.
Install Transition Onto Top of Hood
IMPORTANT: Remove shipping tape from damper and check that damper moves freely.
Place the transition piece over the hood exhaust and secure with 4 screws provided.
Use duct tape to seal the connection. Check to be sure the damper moves freely.
Hang Hood On Wood Support
Lift the hood and hold close to the installation location. Route house wiring through the knockout and into the junction box.
Place the hood over the wood support. Be sure the mounting screws engage the keyhole slots in the back of the hood. Tighten the screws.
WARNING: Continue to provide additional
support while the hood is mounted with only these 2 screws. These screws will not support the weight of the hood. The hood could fall resulting in damage or personal injury.
AVERTISSEMENT Continuez à fournir un soutien
additionnel pendant le montage de la hotte avec ces deux vis seulement. Ces deux vis ne soutiendront pas le poids de la hotte. La hotte peut tomber,
occasionnant des blessures corporelles ou des dommages matériels.
Check to be sure the hood is level and centered.
Original Mounting
Screws as Shipped
1/4" Gap
Adjust depth of original mounting screws in the wood support until they protrude 1/4" forward. This 1/4" gap will provide clearance to hang the hood.
30"
to
36"
Test Duct Cover Fit
Place duct cover(s) over the top of the hood to check for gaps. Adjust the hood up or down if necessary.
Install Bottom Mounting Screws
Drill 1/8" pilot holes into the two lower mounting holes. Enlarge the holes if they did not enter studs to 3/8". Insert anchors for wall fasteners into bottom holes. Remove anchor screws and add flat washers provided. Drive screws into anchors and tighten.
Install 4 additional screws through the back of the hood and into the wood support.
Centerline of Installation Space
11
Page 12
Installation Instructions
STEP 2B Alternate Mounting Method
INSTALL HOOD TO SOFFIT OR BENEATH CABINETS
SKIP THIS STEP IF USING WALL MOUNTING METHOD
When necessary, the hood may be installed so that it is supported by the soffit.
The soffit should be constructed with 2 x 4s.
Determine the installation location on the wall.
Continue the centerline forward on the bottom of the
cabinet or soffit.
The opening above the hood should allow for the 10" round duct and clearance to slide the hood back against the wall.
Requires 10-1/2" Min. Opening For Ductwork
and Hood Installation
A
A
IMPORTANT: Soffit framing must be capable of supporting up to 150 lbs.
Install Transition Onto Top of Hood
Duct
Transition
IMPORTANT: Remove shipping tape from damper and check that damper moves freely.
Top of
Hood
Place the transition piece over the hood exhaust and secure with 4 screws provided.
Use duct tape to seal the connection. Check to be sure the damper moves freely.
Mount Hood onto Soffit or Cabinet
Note: If mounting to the underside of a cabinet with a recessed bottom, install shims to fill the gap.
Cabinet
or
Soffit
The 2 x 4 studs must be located as shown in the chart, Dim. A. to accept mounting screws.
A”“B Centerline to Stud Hood Width and Keyhole Slots At the Top
ZV48T 19-9/16" 40" ZV48S 23-9/16" 47-15/16" ZV36T 13-9/16" 28" ZV36S 17-9/16" 35-15/16" ZV30T 10-9/16" 22" ZV30S 14-9/16" 29-15/16"
Top View
2"
7-1/2"
2-9/16"
A
8"
8-1/8"
C
B
Back of Hood
Front of Hood
6"
Drill 1/8" pilot holes into the studs at the locations shown in the top view illustration.
Engage Top Keyhole Slots
1/4" Gap
Push Back to Wall
Add Shims If Bottom Is Recessed
Back Wall
Drive mounting screws into the studs until they protrude 1/4". The 1/4" gap will provide clearance to engage the keyhole slots in the top of the hood.
Lift hood to installation position. Locate house wiring and route through the knockout (from the back or top of the hood).
Lift hood onto mounting screws. Slide back against the rear wall.
Tighten mounting screws.
IMPORTANT: For additional support and to minimize vibration during operation, the hood must be secured to the back wall. Use wall anchors to fasten bottom back of hood to the wall.
12
Page 13
Installation Instructions
STEP 3 CONNECT DUCTWORK
Install ductwork, making connections in direction of airflow as illustrated.
Secure joints in ductwork with sheetmetal screws.
Wrap all duct joints with duct tape for an airtight seal.
Use duct tape to seal the flange connection. Reach
inside the hood and push the damper up to be sure it moves freely.
Duct Tape Over Seam and Screw
Duct Tape
Over Transition
Air Flow
Screw
STEP 4 CONNECT ELECTRICAL
Verify that power is turned off at the source.
WARNING: If house wiring is not
2-wire with a ground wire, a ground must be provided by the installer. When house wiring is aluminum, be sure to use U.L. approved anti-oxidant compound and aluminum-to-copper connectors.
AVERTISSEMENT– Si le câblage
de la maison nest pas du type à deux fils avec un fil de terre, linstallateur doit fournir un circuit de terre. Quand les fils de la maison sont en aluminium, il prendre soin dutiliser de la pâte antioxidation approuvée par UL et des connecteurs pour laluminium-cuivre.
Remove
A
Junction Box
Cover
B
Insert Power Conduit Thru Strain Relief
and Tighten
Ground
White
Black
C
Use UL Listed
Wire Nuts
Use wire nuts to connect incoming ground to green, white to white and black to black.
Push wires into junction box and replace cover. Be sure wires are not pinched.
STEP 5 INSTALL DUCT COVERS
Note: For easier handling, remove cardboard insert after film is peeled off.
Remove protective film from duct covers. If more than one duct cover is used, secure each piece together with screws provided.
Place the duct cover(s) on top of the hood.
From inside the hood, secure the duct cover to the
top with the small Phillips head screws supplied with the covers.
13
Page 14
Installation Instructions
STEP 6 INSTALL MOTOR
Outlet
Attachment
Slot
From the inside of the hood, slip motor into the attachment slot on the left.
Rotate motor upwards until it snaps into the spring clip on the right.
Secure the motor to the hood with the machine screw and lock washer. (Screw is marked with red or blue paint.)
Top
Spring
Clip
Attachment
Screw
STEP 7 INSTALL FILTERS
Place filter drip trays into the rear of the hood.
Insert the grease filter into the opening and drop
into the trays.
To remove the filters, grasp the handle, push the filter up and lift out.
IMPORTANT: Connector ends are designed to mate only one way. Match flat and round connectors as shown.
Plug connector into the motor.
Spring
Clip
14
Page 15
Installation Instructions
STEP 8 INSTALL IMPLEMENT
RODS
Screw
Stand-offs
Into
Hood
Use Allen
Wrench to
Secure Rod
to Stand-offs
Use a flat blade screwdriver to install stand-offs into the bottom of the hood.
Align implement rod to stand-offs with the screw hole towards the inside of the hood. Secure the rod to the stand-offs with the supplied Allen wrench.
Follow the same procedure on the opposite side.
FINALIZE INSTALLATION
Install the supplied infrared bulb(s).
See the Owners Manual for instructions to test
operation.
15
Page 16
Note: While performing installations described in this book, safety glasses or goggles should be worn.
For Monogram® local service in your area, call
1.800.444.1845.
Note: Product improvement is a continuing endeavor at General Electric. Therefore, materials, appearance and specifications are subject to change without notice.
Pub. No. 49-80151-4 Dwg. No. 164D4290P108
10-06 JR
Printed in Italy
16
GE Consumer & Industrial
GE Appliances General Electric Company Louisville, KY 40225
ge.com
©2006 GE Company
Loading...