GE Monogram ZV30H, Monogram ZV30HS Installation Instructions Manual

Installation Instructions
30” Wall-Mounted Hood
ZV30H
Hotte de cuisine murale de 76,2 cm (30 po)
Instructions d’installation La section française commence à la page 21
Campana Montada en Pared de 30”
31-10749
04-10 GE
Safety Information
READ AND SAVE THESE INSTRUCTIONS
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT — Save these instructions
for local inspector’s use.
IMPORTANT — Observe all governing
codes and ordinances.
Note to Installer — Be sure to leave these
instructions with the Consumer.
Note to Consumer — Keep these instruc-
tions with your Owner’s Manual for future reference.
Skill Level — Installation of this appliance re-
quires basic mechanical and electrical skills.
Completion Time — 1 to 3 Hours.
• Proper installation is the responsibility of the in­staller. Product failure due to improper installation is not covered under the warranty.
For Monogram local service in your area, call 1.800.444.1845. For Monogram service in Canada, call 1.800.561.3344. For Monogram Parts and Accessories, call 1.800.626.2002.
CAUTION: Due to the weight and size of
these vent hoods and to reduce the risk of personal injury or damage to the product, TWO PEOPLE ARE REQUIRED
FOR PROPER INSTALLATION.
WARNING: To reduce the risk of fire or
electrical shock, do not use this range hood with any external solid-state speed control device. Any such alteration from original factory wiring could result in damage to the unit and/or create an electrical safety hazard. TO REDUCE THE RISK OF FIRE, USE ONLY METAL
DUCTWORK.
WARNING: TO REDUCE THE RISK OF
FIRE, ELECTRICAL SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Use this unit only in the manner intended by the
manufacturer. If you have any questions, contact the manufacturer.
B. Before servicing or cleaning the unit, switch the
power off at the service panel and lock the service disconnecting means to prevent the power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
CAUTION: FOR GENERAL VENTILATING
USE ONLY. DO NOT USE TO EXHAUST HAZARDOUS MATERIALS, EXPLOSIVE MATERIALS OR VAPORS.
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRICAL SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
• Installation work and electrical wiring must be done by qualified person(s) in accordance with all ap­plicable codes and standards, including fire-rated construction.
• Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back-drafting. Follow the heating equipment manufacturer’s guidelines and safety standards, such as those published by the National Fire Protection Associa­tion (NFPA), the American Society for Heating, Re­frigeration and Air Conditioning Engineers (ASHRAE) and the local code authorities.
• When cutting or drilling into walls or ceilings, do not damage electrical wiring and other hidden utilities.
• Ducted systems must always be vented to the out­doors.
• Local codes vary. Installation of electrical connections and grounding must comply with applicable codes. In the absence of local codes, the vent should be in­stalled in accordance with National Electrical Code ANSI/NFPA 70-1990 or latest edition.
CAUTION: To reduce risk of fire and to
properly exhaust air, be sure to duct air outside—do not vent exhaust air into spaces within walls or ceilings or into attics, crawl spaces or garages.
2
Design Information
CONTENTS
Design Information
Models Available ................................................................................ 3
Product Dimensions ......................................................................... 3
Advance Planning
Ductwork Planning .......................................................................... 4
Adequate Support ............................................................................ 4
Installation Preparation
Duct Fittings ......................................................................................... 5
Power Supply ....................................................................................... 6
Tools and Materials Required ...................................................... 6
Remove the Packaging .................................................................. 7
Check Installation Hardware ...................................................... 7
Determine Installation Height .....................................................8
Installation Instructions
Installation – Vented to the Outside ...............................10–14
MODELS AVAILABLE
Model ZV30HS
This hood may be installed to vent to the outdoors, or installed for recirculating operation. All necessary parts for recirculating operation are supplied with the hood. No kits required.
Step 1. Ductwork, Wiring Locations ........................................10
Step 2. Wall or Ceiling and Cabinet Preparation ...............10
Step 3. Mounting Hood to Bottom of Cabinet ....................11
Step 4. Connecting Ductwork ....................................................13
Step 5. Connecting Electrical .....................................................14
Step 6. Installing Baffle Grease Filters
and Drip Tray .....................................................................14
Step 7. Finalize Installation..........................................................14
Installation Instructions
Installation – Recirculating..................................................15–18
Step 1. Wiring Locations...............................................................15
Step 2. Wall and Cabinet Preparation ....................................15
Step 3. Mounting Hood to Bottom of Cabinet ....................16
Step 4. Connecting Electrical .....................................................17
Step 5. Installing Charcoal Filter ...............................................18
Step 6. Installing Baffle Grease Filters
and Drip Tray ......................................................................18
Step 7. Finalize Installation..........................................................18
This vent hood can be installed over any 30” electric or gas cooktop including Monogram Professional cooktops or ranges less than 36”.
PRODUCT DIMENSIONS AND CLEARANCES
The vent hood must be installed 24” minimum and 36” maximum above the cooking surface.
NOTE: Installation height should be measured from the cooking surface to the lowest part of the hood. The ductwork running from the top of the hood can be concealed in the soffit and/or upper cabinet. NO duct cover accessories are provided or required.
12”
3-1/2”
10-1/2”
30”
24” Min. 36” Max.
3
Advance Planning
DUCTWORK PLANNING FOR VENTED MODE
• This vent hood is designed to be installed beneath a cabinet or beneath a cabinet mounted to a soffit.
• This hood is designed for 8” round ducting. The 8” round duct can transition to 3-1/4” x 10” or 3-1/4” x 12”.
• Plan the route for venting exhaust to the outdoors considering any transitions you may require.
Use locally supplied ducting to vent horizontally
• through the rear wall or vertically through the ceiling.
• Use the shortest and straightest duct route possible. For satisfactory performance, duct run should not exceed 100’ equivalent length for any duct configurations.
• Refer to “Duct Fittings” chart to compute the maximum permissible length for duct runs to the outdoors.
• Install a wall or roof cap with damper at the exte­rior opening. Order the wall or roof cap and any transition and length of duct needed in advance from a local hardware store.
DUCTWORK PLANNING FOR RECIRCULATION MODE
All parts are included to install in recirculation mode.
MOUNTING FOR ADEQUATE SUPPORT
• The hood must be secured to vertical studs in the wall. See the Wall or Ceiling and Cabinet Preparation section for vented or recirculationg installation.
• We strongly recommend that the vent hood be on
-site to accurately locate the ductwork and electri­cal service.
• Installation will be easier if the vent hood is in­stalled before the cooktop and countertop are installed.
IMPORTANT: The vent hood must be secured
to the cabinet and at least two wall studs and dry wall with anchors. The cabinet must be ca­pable of supporting 100 lbs.
• Determine the exact location of the vent hood.
• Wall or ceiling duct must be projected out at least 1” for duct connection.
WARNING: TO REDUCE THE RISK OF
FIRE, USE ONLY METAL DUCTWORK.
• For better air flow results, use rigid metal ductwork.
4
Installation Preparation
DUCT FITTINGS
This Hood Must Use an
8” Round Duct. It Can
Transition to 3-1/4x 10
or 3-1/4x 12Duct.
Use this chart to compute maxi­mum permissible lengths for duct runs to outdoors.
NOTE: Do not exceed maximum permissible equivalent lengths!
Maximum duct length: 100 foot for range hoods.
Flexible ducting:
If flexible metal ducting is used, all the equivalent feet values in the table should be doubled. The flexible metal duct should be straight and smooth and ex­tended as much as possible.
Total Equivalent Quantity Equivalent Duct Piece Dimensions Length* Used Length
Round, 1 ft. (per straight foot length)
3-1/4 x 10 1 ft. (per straight foot length)
90° elbow 12 ft.
45° elbow 7 ft.
3-1/4 x 10″ 14 ft. 3-1/4 x 12″ 10 ft. 90° elbow
3-1/4 x 10″ 8 ft. 3-1/4 x 12″ 6 ft. 45° elbow
3-1/4 x 10″ 33 ft. 3-1/4 x 12″ 24 ft. 90° flat elbow
DO NOT use flexible plastic ducting.
NOTE: Any home ventilation system, such as a ventilation hood, may interrupt the proper flow of combustion air and exhaust required by fireplaces, gas furnaces, gas water heat­ers and other naturally vented systems. To minimize the chance of interruption of such naturally vented systems, follow the heat­ing equipment manufacturer’s guidelines and safety standards such as those published by NFPA and ASHRAE.
8 round to 2 ft. rectangular
Rectangular to 8″ 2 ft. round
3-1/4 x 10″ 4 ft. 3-1/4 x 12 4 ft. 8 round to rectangular transition 90° elbow
3-1/4 x 10″ 4 ft. 3-1/4 x 12 4 ft. Rectangular to 8″round transition 90° elbow
Round wall cap 24 ft. with damper
3-1/4 x 10″ 24 ft. 3-1/4 x 12 18 ft. Rectangular wall cap with damper
Round roof cap 33 ft.
* Actual length of straight duct plus duct fitting
equivalent. Equivalent length of duct pieces are based on actual tests conducted by GE Evalua­tion Engineering and reflect requirements for good venting performance with any ventilation hood.
5
Total Duct Run
Installation Preparation
POWER SUPPLY
IMPORTANT – (Please read carefully)
WARNING:
FOR PERSONAL SAFETY, THIS APPLIANCE MUST BE PROPERLY GROUNDED.
Remove house fuse or open circuit breaker before beginning installation.
Do not use an extension cord or adapter plug with this appliance. Follow National Electrical Code or prevailing local codes and ordinances.
Electrical supply
This vent hood must be supplied with 120V, 60Hz, and connected to an individual, properly grounded branch circuit, and protected by a 15- or 20-amp circuit breaker or time-delay fuse.
• Wiring must be 2-wire with ground.
• If the electrical supply does not meet the above requirements, call a licensed electrician before proceeding.
• Route house wiring as close to the installation location as possible. Wiring can enter from the ceiling or rear wall. Route additional length from the ceiling or wall to reach the junction box.
TOOLS AND MATERIALS REQUIRED
(NOT SUPPLIED)
Safety glasses
Pencil and tape measure
Spirit level
Phillips screwdriver
Electric drill or cordless driver with #2 Phillips bit, 1/8”, 5/16” and wood-cutting hole saw drill bits
Utility Knife
Gloves
Hammer
Flashlight
Metal snips
Pliers
• Connect the wiring to the house wiring in accor­dance with local codes.
Grounding instructions
The grounding conductor must be connected to a ground metal, permanent wiring system, or an equipment-grounding terminal or lead on the hood.
WARNING: The improper connection
of the equipment-grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service representative if you are in doubt whether the appliance is properly grounded.
Stepladder
UL-listed wire nuts
Aluminized duct tape
Strain relief for junction box
Masking tape
Saber saw or Key Hole saw
120V 60Hz. 15- or 20-Amp, 2-wire with ground, properly grounded branch circuit
Wire cutter/stripper
8 round metal duct, length to suit installation
6
Installation Preparation
30“
REMOVE THE PACKAGING
CAUTION: Wear gloves to protect against
sharp edges. The vent hood is shipped secured to a
shipping board with 4 screws.
• Remove the accessories and Styrofoam packaging.
• Lift the hood out of the box.
• Remove and properly discard the plastic wrapping.
• Remove metal grease filters and other accessories.
Shipping board
• To remove the shipping board, locate and remove the 4 screws inside the hood on the left and right sides. Discard the shipping board.
CHECK INSTALLATION HARDWARE
Locate the hardware accessory box packed with the hood and check contents.
4 Damper assembly
screws (supplied
with damper
assembly)
10 wall/cabinet
screws
2 metal wall
fasteners
Shipping screws
Damper
assembly
3 Grease filters
26,7 cm)
10-1/2“
(14,0 cm)
5-1/2“
35,5 cm)
14“
(7,0 cm)
2-3/4“
(8,9 cm)
3-1/2“
Packaging
30“
BOTTOM OF THE HOOD
DESSOUS DE LA HOTTE PARTE INFERIOR DE LA CAMPANA
MONTANTS DU MUR. TROUS QUI SONT VIS-À-VIS DES MONTANTS DU MUR. UTILISER LES VIS SOIENT VISSÉES DANS LES IL EST IMPORTANT QU'AU MOINS DEUX TROUS POUR L'INSTALLATION AU MUR
(17,9 cm) 7-1/16“
D'ÉVACUATION ARRIÈRE SORTIE DU CONDUIT MIN. POUR LE CENTRE DE LA
SALIDA DEL CONDUCTO TRASERA CENTRO DE LA
L'AVANT.
MÍN PARA VENTILACIÓN
RECTEMENT, LA GRILLE D'AÉRATION VERS
DUCT OUTLET CENTER
L'INTÉRIEUR, INSTALLER L'ENTRETOISE COR-
MIN FOR REAR VENT
L'EXTÉRIEUR. LORSQUE L'AIR EST RECYCLÉ À TATIVE LORSQUE L'AIR EST ÉVACUÉ VERS L'INSTALLATION DE L'ENTRETOISE EST FACUL-
8-1/4“ (20,6 cm)
NOTE:
Grease tray
(76,2 cm)
(34,0 cm) 13-3/8“
THAT ALIGN WITH STUDS. TWO SCREWS. USE HOLES WALL STUDS WITH AT LEAST IT IS IMPORTANT TO ENGAGE WALL MOUNTING HOLES
L
C
ADECUADA CON LAS REJILLAS EN EL FRENTE STALAR EL ELEVADOR CON LA ORIENTACIÓN PARA RECIRCULACIÓN. ASEGÚRESE DE IN­NAL PARA APLICACIONES CON VENTILACIÓN. LA INSTALACIÓN DEL ELEVADOR ES OPCIO­NOTA:
Imprimé en Italie Impreso en Italia Printed in Italy
GABARIT D'INSTALLATION AU MUR PLANTILLA DE MONTAJE DE PARED
WALL MOUNTING TEMPLATE
TROUS PILOTES DE 7,9 mm POUR LES DISPOSITIFS D'ANCRAGE ORIFICIOS PILOTO 5/16” PARA SUJECIONES
PILOT HOLES 5/16” FOR ANCHORS PILOT HOLES DRILL 1/8” FOR STUDS
ORIFICIOS PILOTO PERFORE 1/8” PARA LOS MONTANTES TROUS PILOTES DE 3,1 mm POUR LES MONTANTS
03-10 GE 31-10750
MONTANTES. ORIFICIOS ALINEADOS CON LOS MENOS DOS TORNILLOS. UTILICE TANTES DE PARED CON POR LO ES IMPORTANTE SUJETAR A MON­ORIFICIOS DE MONTAJE DE PARED
RÉFÉRENCE – SURFACE SUPÉRIEURE DU CHÂSSIS REFERENCIA – SUPERFICIE SUPERIOR DEL CHASIS
REFERENCE - CHASSIS TOP SURFACE
RÉFÉRENCE – SURFACE SUPÉRIEURE DU PANNEAU DE L'ENTRETOISE REFERENCIA – SUPERFICIE SUPERIOR DEL PANEL DEL ELEVADOR
REFERENCE - RISER PANEL TOP SURFACE
IN FRONT PROPER ORIENTATION WITH LOUVERS LATION, BE SURE TO INSTALL RISER IN VENTED APPLICATIONS. FOR RECIRCU­RISER INSTALLATION IS OPTIONAL FOR NOTE:
Shipping screws
Riser
(PAROIARRIÈRE DE L’ARMOIRE)
DEL GABINETE)
ET L’ALIGNER PAR RAPPORT AU MUR
ALINEE CON LA PARED (PARTE TRASERA
LE GABARIT AU FOND DE L’ARMOIRE
LA PARTE INFERIOR DEL GABINETE Y
PERCERDES TROUS PILOTES. COLLER
FICIOS PILOTO. ADHIERA LA PLANTILLA A
POUR PRATIQUER LES OUVVERTURES,
PARA REALIZAR RECORTES, PERFORE ORI-
REMARQUE:
(2,8 cm)
1-1/8“
(7,9 cm)
3-1/8“
Sup # 270-026
(25,4 cm)
10“
(30,4 cm)
12“
(2,8 cm)
1-1/8“
(3,8 cm)
1-1/2“
NOTA:
(23,9 cm) 9-7/16“
(2,5 cm)
1“
TRIQUE L'ALIMENTATION ÉLEC­L'ARMOIRE POUR TROU DE 1,9 cm DANS
ELECTRIC SUPPLY
SUMINISTRO ELÉCTRICO
IN CABINET FOR
EN GABINETE PARA RECORTE MÍN DE ¾”
3/4” MIN CUT OUT
L
(67,9 cm) 26-3/4“
Cabinet Template
31-10571
ALIGN WITH WALL (CABINET BACK) BOTTOM OF THE CABINET AND HOLES. TAPE TEMPLATE TO TO MAKE CUT OUTS, DRILL PILOT NOTE:
(60,0 cm) 23-5/8“
PERCER DES TROUS PILOTES DE 3,1 mm
L'ENTRETOISE À L'ARMOIRE
TROUS POUR FIXER LA HOTTE OU
PERFORE ORIFICIOS PILOTO DE 1/8”
O ELEVADOR AL GABINETE
ORIFICIOS PARA MONTAR CAMPANA
DRILL 1/8” PILOT HOLES
HOOD OR RISER TO CABINET
HOLES FOR MOUNTING
SÓLO PARA VENTILACIÓN EXTERNA
PARTE INFERIOR RECORTADA DEL GABINETE ÉVACUATION VERS L'EXTÉRIEUR SEULEMENT OUVERTURE LARGE SOUS L'ARMOIRE POUR
FOR EXTERNAL VENT ONLY
WIDE CUT OUT BOTTOM OF CABINET
C
(76,2 cm)
GABARIT D'INSTALLATION SOUS UNE ARMOIRE
Imprimé en Italie
PLANTILLA DE MONTAJE DE GABINETE
Impreso en Italia Printed in Italy
CABINET MOUNTING TEMPLATE
(7,9 cm) 3-1/8“
ARRIÈRE DE LA HOTTE (MUR/ARRIÈRE DE L'ARMOIRE) PARTE TRASERA DE LA CAMPANA (PARTE TRASERA DE LA PARED/GABINETE)
HOOD REAR (WALL/CABINET BACK)
04-10 GE 31-10751
(35,5 cm)
14“
DEVANT DE LA HOTTE (DEVANT DE L'ARMOIRE)
(3,8 cm)
1-1/2“
FRENTE DE LA CAMPANA (FRENTE DEL GABINETE)
HOOD FRONT (CABINET FRONT)
6 riser
screws
10 flat
washers
NOTE: Additional tools, materials and hardware are required to construct your wall framing support.
1 plastic
grommet
Wall Template
31-10570
2 charcoal filters
7
Installation Preparation
DETERMINE INSTALLATION HEIGHT
This hood can be installed for vented or recirculating operation. All necessary parts are shipped with the hood for recirculation mode.
NOTE: Installation height should be measured from the cooking surface to the bottom of the hood.
The vent hood must be installed 24 min. and 36 max. above the cooking surface.
24” Min. 36” Max.
Z
Y
R=3 1/2”
B=10 1/2”
C=Ceiling
Height
X=24” Min, 36” Max
Recirculation Mode
You must use the riser with louvers facing the front side with recirculation mode. The hood height with the riser is 14”. Do not knock out the duct opening on the riser.
DO NOT knock out the duct opening for recirculation mode.
Riser
A
To determine the distance between the bottom of the hood and the cooking surface (Min 24”, Max. 36” use the following formula to solve for X:
X = C - (A + B + R + Y + Z) where A = Cooking surface to the floor B = Hood height without riser C = Ceiling height R = Riser height (must be used with recirculation
mode, optional for vent mode) Y = Cabinet height Z = Soffit/Gap between the cabinet and ceiling (may
be “0”) Example: X = 96” - (36” + 10 1/2” + 3 1/2” + 15” + 6”) X = 25”
8
Installation Preparation
Z
Y
R=3 1/2” (Optional)
B=10 1/2”
C=Ceiling
X=24” Min, 36” Max
Z=0
Y
B=10 1/2”
C=Ceiling
Height
X=24” Min, 36” Max
Height
A
Vent Mode
In vent mode, installation can be done with or with­out the riser. You must consider 3 1/2” riser height in determining the hood installation height.
To determine the hood installation height with riser: X = C - (A + B + R + Y + Z) Example: X = 96” - (36” + 10 1/2” + 3 1/2” + 15” + 6”) X = 25”
A
To determine the hood installation height without riser:
X = C - (A + B + Y + Z) Example: X = 96” - (36” + 10 1/2” + 24” + 0”) X = 25 1/2”
NOTE: Installation height should be measured from the cooking surface to the bottom of the hood. The vent hood must be installed 24” min. and 36” max. above the cooking surface. The hood installation height, from the cooking surface to the bottom of the hood, depends upon ceiling height and other factors which must be considered .
9
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
1
DUCTWORK, WIRING LOCATIONS
Determine the exact location of the vent hood.
• Locate the template packed with the literature.
– Measure 36” from the floor to the top of the cook-
ing surface. Add hood installation height deter­mined on previous pages. Mark that location.
Use a level to draw a straight pencil line on the wall.
– – Tape the template in position along the penciled
line. CHECK TO BE SURE THE TEMPLATE IS LEVEL.
6 5/8”
8-1/2” diam.
Centerline 8 1/4″ min.
above hood chassis
31-10750 02-10 GE
hole for duct
Sup # 270-025
1
DUCTWORK, WIRING LOCATIONS (Continued)
• Wiring can enter the cabinet from the ceiling or back wall.
Route additional wiring length to reach the junction box.
2
WALL OR CEILING AND CABINET PREPARATION
IMPORTANT —
to the cabinet and at least two wall studs and drywall with anchors. Cabinet must be capable of supporting 100 lbs.
• With the template taped in place, use a punch to mark all mounting screw locations. Mark duc­twork, screw and electrical holes according to your application.
• Drill a minimum 3/4” hole for electrical cable in the bottom of the cabinet.
• Drill 1/8” pilot holes at the 4 punched locations on the bottom of the cabinet.
• Drill 1/8” pilot holes at the 4 punched locations on the wall
The vent hood must be secured
Cabinet/Ceiling ducting:
If ductwork will vent straight up to the ceiling or cabinet:
• Use a level to draw a line straight up, from the cen­terline on the template to the ceiling/cabinet.
• Measure 6-5/8 from the back wall to the centerline of an 8-1/2″ hole on the ceiling/cabinet top.
NOTE: If drywall is not present, add drywall thickness to the 6-5/8 dimension.
Wall Ducting:
If ductwork will vent to the rear:
• Use a level to draw a line straight up from the centerline on the template.
• Measure at least 8 1/4" above the hood chassis top surface location shown on the template to the centerline of a 8-1/2″-dia. duct hole. (Hole may be elongated for duct elbow.)
House Wiring Location:
• The junction box is located on the top right side of the hood.
• Remove the template.
• Enlarge holes that did not enter studs to 5/16”. Tap anchors for wall fasteners into the holes.
Cabinet mounting
Cabinet template
REFERENCE - RISER PANEL TOP SURFACE
REFERENCE - CHASSIS TOP SURFACE
PILOT HOLES DRILL 1/8” FOR STUDS PILOT HOLES 5/16” FOR ANCHORS
31-10750
BOTTOM OF THE HOOD
02-10 GE
Wall template
screw locations
WALL MOUNTING HOLES IT IS IMPORTANT TO ENGAGE WALL STUDS WITH AT LEAST TWO SCREWS. USE HOLES THAT ALIGN WITH STUDS.
13-3/8“
7-1/16“
Wall mounting screw locations
NOTE: It is important to engage the wall studs with at least two screws. Use the holes which align with the studs.
10
Sup # 270-025
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
2
WALL OR CEILING AND CABINET
PREPARATION (Continued)
FOR REAR WALL DUCTING
Determine the cabinet center line.
If the hood is mounted with the riser:
• Cut a 14” diameter hole in the cabinet bottom.
• Cut an 8-1/2” diameter hole in the cabinet rear wall. You may need to add ducting between the hood exhaust outlet and the elbow.
If the hood is mounted without the riser:
• Cut a 10” diameter hole in the cabinet bottom.
• Cut the location of the 8-1/2” diameter hole in the cabinet rear wall. You may need to add ducting between the hood exhaust outlet and the elbow,
depending on the location planned for the rear wall exit.
• Depending on cabinet height, you may need to shorten the height of the 8” elbow.
FOR CEILING DUCTING
If the hood is mounted with the riser:
• Cut a 14” diameter hole in the cabinet bottom.
• Cut an 8-1/2” diameter hole in the cabinet top and ceiling 6-5/8” from wall.
If the hood is mounted without the riser:
• Cut a 10” diameter hole in the cabinet bottom 6- 5/8” from the wall.
• Cut an 8-1/2” diameter hole in the cabinet top 6-5/8” from the wall and one in the ceiling 6-5/8” from wall.
NOTE: Any exposed ducting needs to be covered us­ing your preferred method.
3
MOUNTING HOOD TO BOTTOM OF CABINET
Mounting hood to the bottom of the cabinet is dependent on your cabinet. For non-flush bottom cabinets, two (2) 4” wide (length and thickness depend on your cabinet) solid wooden fillers are required on the left and right sides of lower cabinet as shown in the picture. Use shims if neces­sary to make the wooden fillers flush.
Wooden fillers
NOTE: When securing wooden fillers to cabinet, be sure to consider hood mounting screw locations on the template. Wooden fillers must be flush or slightly less than the cabinet flange. Make sure the cabinet bottom is level.
For flush bottom cabinets, no special instructions are required.
Hood Installation with Riser:
• Remove the appropriate electrical and duct knockouts in the riser as shown in the figure.
• Install plastic grommet (from hardware bag) in electrical knockout hole to protect the cable.
Vent knock out
Electrical knock out
Plastic Grommet
11
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
3
MOUNTING HOOD TO BOTTOM OF CABINET (Continued)
• To secure the riser to the cabinet, place the riser (with louvers facing the wall) under the cabinet. Align the riser and cabinet mounting holes. Drive 4 sup­plied wood screws to install the riser to the cabinet.
NOTE: If desired, you may choose to install the
riser with the louvers facing forward.
Riser
Wood screws
• Drive 4 hood mounting screws into the threaded nuts on the bottom of the riser leaving 1/4” pro­truding from the riser. The 1/4” gap will provide the clearance to engage the key hole slots in the top of the hood.
3
MOUNTING HOOD TO BOTTOM OF CABINET (Continued)
• Lift the hood to the installation position. Locate the house wiring and route it through the knockout on top of the hood. Lift the hood and engage the key hole slots over the mounting screws and slide it back against the wall. Tighten the mounting screws. Add 2 additional screws at the front center of the riser.
• Install 4 wall screws and washers into the anchors or studs to complete the hood mounting.
Mounting screw
Key hole slot in hood
Mounting Screw
• Install the damper assembly on top of the hood with 4 Phillips screws supplied.
#2 Phillips screws
#2 Phillips
Damper assembly
screws
House wiring
Additional screws to riser
Wall screws and washers for anchors or studs
12
Installation Instructions
INSTALLATION – VENTED TO THE OUTSIDE
3
MOUNTING HOOD TO BOTTOM OF CABINET (Continued)
Hood Installation without Riser:
• Install the damper assembly on top of the hood with 4 supplied Phillips screws.
Lift the hood under the cabinet. Align the hood
• and cabinet mounting holes. Use 4 supplied wood screws and washers to secure the hood to the cabinet.
• Drill two 1/8” pilot holes in the cabinet flange. Se­cure with 2 additional wood screws, supplied. Be careful when driving screws into the front flange.
• Install 4 wall screws into the anchors or studs to complete the hood mounting.
Cabinet flange
4
CONNECTING DUCTWORK
• Install the ductwork by making connections in the direction of the airflow.
• Secure joints in ductwork with sheet metal screws, being sure to allow clearance for damper flaps to open and close.
• Wrap all duct joints with aluminized duct tape for an airtight seal.
• Use aluminized duct tape to secure the flange connection. Reach inside the hood and push the damper up to be sure it moves freely.
Screw
Aluminized duct tape
Air flow
Mounting screws
Wall screws and washers for anchors or studs
Mounting screws
Additional screws to cabinet flange
Wall screws and washers for anchors or studs
13
Installation Instructions
Front
INSTALLATION – VENTED TO THE OUTSIDE
5
CONNECTING ELECTRICAL
Verify that the power is turned off at the source.
WARNING:: If the house wiring is not
2-wire with a ground wire, a ground must be pro­vided by the installer. When house wiring is alu­minum, be sure to use UL-approved antioxidant compound and aluminum-to-copper connectors.
• Remove the junction box cover.
• Secure the house wiring to the junction box with a strain relief (not provided).
• Connect the white lead to the branch circuit white lead.
• Connect the black lead to the branch circuit black lead.
• Connect the green/yellow lead to the branch circuit green lead or bare ground lead.
• Secure all the connections with wire nuts on each electrical connector. Check for secure wiring con­nections.
• Push the wires into the junction box and replace the cover. Be sure the wires are not pinched.
• Secure the junction box cover with the 2 original screws.
Put the main power disconnect switch located on the control box cover to the ON position. Test all hood functions to ensure electrical connections. See the owner’s manual for instructions to test operations.
Strain relief
Junction box cover
House wiring
INSTALLING BAFFLE GREASE
6
FILTERS AND DRIP TRAY
Installing Drip Tray
1. Lift drip tray with slots and filter channel toward the front.
2. Align the tray with the hood drip tray channel and ease into position.
Drip tray channel
Installing Baffle Grease Filters
1. Remove protective film. Hold both filter knobs while positioning the front end
2. of the filter in the upper (front) filter channel. Pull the filter as far forward as possible into the channel.
3. Lift the opposite end of the filter, aligning with the rear (lower) filter channel.
4. Push the filter into the rear channel, allowing it to settle into the rear channel.
5. Make sure filters are seated properly.
Rear channel with grease tray
Filter
channel
UL listed wire nuts
Green/ yellow ground wires
Black leads
White leads
Filter
Filter
7
FINALIZE INSTALLATION
• Remove any remaining protective film from the front face of the hood.
• Be sure fan and lights operate correctly. Refer to the Owner’s Manual for operating instructions and Problem Solver.
14
Installation Instructions
INSTALLATION – RECIRCULATING
1
WIRING LOCATIONS
Determine the exact location of the vent hood.
• Locate the template packed with the literature. Measure 36” from the floor to the top of the cook-
ing surface. Add hood installation height deter­mined on previous pages. Mark that location.
Use a level to draw a straight pencil line on the
Wall.
– Tape the template in position along the penciled
line. CHECK TO BE SURE THE TEMPLATE IS LEVEL.
31-10750 02-10 GE
Sup # 270-025
2
WALL AND CABINET PREPARATION
IMPORTANT —
The vent hood must be secured to the cabinet and at least two wall studs and drywall with anchors. Cabinet must be capable of supporting 100 lbs.
• With the template taped in place, use a punch to
mark all mounting screw locations and electrical holes according to your application.
• Drill a minimum 3/4” hole for electrical cable in
bottom of the cabinet.
• Drill 1/8” pilot holes at the 4 punched locations on
the bottom of the cabinet.
• Drill 1/8” pilot holes at the 4 punched locations on
the wall
• Remove the template.
• Enlarge holes that did not enter studs to 5/16”.
Tap anchors for wall fasteners into the holes.
Cabinet mounting
Cabinet template
screw locations
HOUSE WIRING LOCATION:
• The junction box is located on the top right side of the hood.
• Wiring can enter the cabinet from the ceiling or from the back wall.
• Route additional wiring length to reach the junction
box.
REFERENCE - RISER PANEL TOP SURFACE
REFERENCE - CHASSIS TOP SURFACE
7-1/16“
WALL MOUNTING HOLES IT IS IMPORTANT TO ENGAGE WALL STUDS WITH AT LEAST TWO SCREWS. USE HOLES THAT ALIGN WITH STUDS.
PILOT HOLES DRILL 1/8” FOR STUDS PILOT HOLES 5/16” FOR ANCHORS
31-10750
BOTTOM OF THE HOOD
02-10 GE
Wall template
13-3/8“
Sup # 270-025
Wall mounting screw locations
NOTE: It is important to engage the wall studs with at least two screws. Use the holes which align with the studs.
15
Installation Instructions
INSTALLATION – RECIRCULATING
3
MOUNTING HOOD TO BOTTOM OF CABINET
Mounting the riser to the bottom of the cabinet is depen­dent on your cabinet. For non-flush bottom cabinets, two (2) 4” wide (length and thickness depend on your cabinet) solid wood fillers are required on the left and right sides of lower cabinet as shown. Use shims if necessary to make wooden fillers flush.
NOTE: When securing wooden fillers to cabinet, be sure to consider the hood mounting screw locations on the template. Wooden fillers must be flush or slightly less than the cabinet flange. Make sure the cabinet bottom is level.
For flush bottom cabinets, no special instructions are required.
Wooden filler boards
3
MOUNTING HOOD TO BOTTOM OF CABINET (Continued)
To secure the riser to the cabinet:
• Place the riser (with louvers facing the front) under the cabinet. Align the riser and cabinet mounting holes. Drive 4 supplied wood screws to install the riser to the cabinet.
Wood screws
• Drive 4 hood mounting screws into the threaded nuts on the bottom of the riser leaving 1/4” pro­truding from the riser. The 1/4” gap will provide the clearance to engage the key hole slots in the top of the hood.
Hole in cabinet for electrical cable
Riser
Hood and Riser Installation
• Remove the appropriate electrical knockouts in the riser as shown in the figure.
• Install plastic grommet (from hardware bag) in electrical knock out hole to protect cable.
IMPORTANT: DO NOT remove the large knock
out for RECIRCULATION installation. Louvers must face the front.
DO NOT REMOVE Vent knock out
Electrical knock out
Plastic Grommet
Mounting Screw
16
Installation Instructions
INSTALLATION – RECIRCULATING
3 4
MOUNTING HOOD TO BOTTOM OF CABINET (Continued)
• Lift the hood to the installation position. Locate the house wiring and route it through the knock­outs at the top right of the hood. Lift the hood and engage the key hole slots over the mounting screws and slide it back against the wall. Tighten the mounting screws. Add 2 additional screws at the front and center the hood on the riser.
• Install 4 wall screws into the anchors or studs to complete the hood mounting.
Mounting screw
Key hole slot in hood
CONNECTING ELECTRICAL (Continued)
• Connect the black lead to the branch circuit black lead.
• Connect the green/yellow lead to the branch cir­cuit green lead or bare ground lead.
• Secure all the connections with wire nuts on each electrical connector. Check for secure wiring con­nections.
• Push the wires into the junction box and replace the cover. Be sure the wires are not pinched.
• Secure the junction box cover with the 2 original screws.
Put the main power disconnect switch located on the control box cover to the ON position. Test all hood functions to ensure electrical connections. See the owner’s manual for instructions to test operations.
House wiring
Additional screws to riser
Wall screws
and washers for
anchors or studs
4
CONNECTING ELECTRICAL
Verify that the power is turned off at the source.
WARNING:: If the house wiring is not
2-wire with a ground wire, a ground must be pro­vided by the installer. When house wiring is alu­minum, be sure to use UL-approved antioxidant compound and aluminum-to-copper connectors.
Junction box cover
Strain relief
House wiring
UL listed wire nuts
Green/yellow ground wires
Black leads
White leads
• Remove the junction box cover.
• Secure the house wiring to the junction box with a strain relief (not provided).
• Connect the white lead to the branch circuit white lead.
17
Loading...
+ 39 hidden pages