GE MGH, MGHU Specification Sheet

GE
HAZARDOUS LIGHTING
g
Lighting Solutions
GUIDE FORM SPECIFICATIONS
MINI•GARD
UL844
YOU MUST USE TEMPERATURE PROFILE DATA TO PROPERLY SELECT LUMINAIRE
GENERAL DESCRIPTION
The complete luminaire designated ________ (identify) shall be a GE MINI.GARDTM luminaire, ordering number_______ (specify MGH or MGHU, plus ordering number logic from catalog), UL844 Listed for use in Class I, Division 2, Groups A, B, C and D; Class II, Division 1, Groups E, F and G; Class II, Division 2, Group G; Class III, Divisions 1 and 2; and Simultaneous Presence: Class I, Division 2 and Class II, Divisions 1 and 2 locations, or ap­proved equal, to operate ________ (specify one [50, 70, 100 or 150(55V)] watt high pressure sodium [HPS] or [70, 100 or 175] watt metal halide or [13 or 26] watt or two 26-watt fluorescent) lamp(s) from a nominal ________ (specify 120, 208, 240, 277, or
480) volt , 60 Hertz power source and shall be capable of start­ing and operating the specified lamp within the limits specified by the lamp manufacturer. The luminaire shall contain a com­pletely prewired integral ballast and optical assembly suitable for continuous service, either indoors or outdoors, in an ambi­ent temperature of _______ (40, 55 or 65) degrees C. Standard construction is IP65. The luminaire shall have a clearly visible NEMA lamp identifica­tion decal and a nameplate including pertinent luminaire rating data. Labeling shall be in accordance with UL and NEMA List­ings.
MECHANICAL CONSTRUCTION
For ease of installation and to facilitate maintenance and re­placement, the MGA luminaire shall be supplied as components
- ballast , mounting, optical and accessories. A lamp shall be included with fluorescent units, but shall not be installed. The MGHU unit whall be shipped all in one carton with lamp and optical installed (HPS and metal halide only).
The luminaire shall include a die-cast low copper aluminum housing with electro-epoxidized gray paint finish inside and outside. All external hardware shall be stainless steel. There shall be provision for a ballast safety chain.
The luminaire shall be ________ (specify ceiling, flexible pen­dant , angle stanchion, pendant, straight stanchion or wall) mounted. A stainless steel closure screw in the ballast housing shall mate with a polymer coated insert in the mounting com­ponent .
TM
OPTICAL ASSEMBLY
The optical assembly shall include a ________ (specify small glass globe with or without Maxi-Lux with or without Maxi-Lux® guard with a Type II or Type V dis­tribution for HPS or metal halide or large glass globe with or without Maxi-Lux® guard for fluorescent). The optical assembly shall also include as an accessory ________ (specify no reflec­tor or dome, deep dome or angle dome reflector).
External reflectors shall be aluminum with a chemically bonded lightweight non-breakable ALGLAS surfaces for corrosion resistance.
The die cast aluminum Maxi-Lux guard shall be of inverted design for improved photometric performance.
The optical assembly shall be charcoal filtered.
* FOR MORE DEFINITIVE INFORMATION, REFER TO BALLAST SPECIFICATIONS IN TECHNICAL DATA SECTION.
®
guard, refractor glass
®
finish on inside and outside
BALLAST OPERATION
The luminaire shall contain a standard ________ (specify Au­toreg; HPF Reactor or Lag; or NPF Reactor or Lag) type ballast* in full compliance with lamp-ballast specifications available to the fixture manufacturer from the lamp manufacturers at the time of fixture manufacture.
The ballast shall reliably start and operate the lamp in ambient temperatures down to - 20°F for metal halide, - 40°F for HPS and - 32°F for fluorescent .
The luminaire and ballast shall be from the same manufacturer.
Guide Form Specifications – 2011
g
GE Lighting Solutions • 1-888-MY-GE-LED • www.gelightingsolutions.com
1 6 9 4 3 5 3 3- - -- 8 8 8
GE Lighting Solutions is a subsidiary of the General Electric Company. Evolve and other trademarks belong to GE Lighting Solutions. The GE brand and logo are trademarks of the General Electric Company. © 2011 GE Lighting Solutions. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.