General Electric Company Telephone +41 (0)91 / 850 51 51
CH – 6595 Riazzino (Locarno)Fax+41 (0)91 / 850 51 44
SwitzerlandWebsitewww.gedigitalenergy.com
LanPro-U UPS
Technology for the Digital World.
ver. 2.1 US
Page 2
g
USER MANUAL LanPro 5/6/8/10-11U UPS
LX-DOCFile: OPM_LPA_11U_5K0_10K_1US_V021
Software version R2.9
INSTALLATION / USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY
GE Digital Energy
LanPro® 11 U
5/6/8/10kVA
Preface
We thank you for selecting a GE (General Electric) Digital Energy Uninterruptible Power Supply (UPS) and
recommend that you read these instructions carefully before installation and start-up of the LanPro
Please keep this manual in a safe place for future reference and carefully read the important safety instructions in
chapter 1 before installation of this device.
®
-U UPS.
Tested
GE Digital Energy is committed to quality and individually tests each LanPro®-U UPS to ensure reliable
performance for the user. All units have passed GE DE's quality control standards and conform to the tolerances in
the enclosed specifications.
About GE Digital Energy
GE Digital Energy is a leading provider of mission critical power equipment, and bridges the gap between the
traditional electricity supply and the critical power requirements of today’s businesses. GE designs, develops and
delivers extremely reliable and intelligent power solutions, from desktop UPS to self-contained premium power
systems which are supported through a global services network.
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 5
g
1 - Important Safety Instructions
1.1Save these instructions
This manual contains important instructions for LanPro®-11U Series UPS, that should be followed during
installation and maintenance of the UPS and batteries.
Before attempting to install and start up the UPS, carefully read this manual. Keep this manual next
to the UPS for future references.All servicing must be done by qualified personnel. Do not attempt
to service the UPS unless you have had proper training.
GE Digital Energy
CAUTION:
While every care has been taken to ensure the completeness and accuracy of this manual, GE
Digital Energy assumes no responsibility or liability for any loss or damage resulting from the use
of the information contained in this document.
This document shall not be copied nor reproduced without the permission of GE Digital Energy.
Due to technical improvements, some of the information contained in this manual may be changed
without notice.
By opening or removing covers you run the risk of exposure to dangerous voltages!
1.2General
CAUTION: RISK OF ELECTRIC SHOCK
inside. All maintenance and service work should be performed by qualified service personnel. The UPS
contains batteries. The appliance outlet may be electrically live, even when the UPS is disconnected from
the utility supply. Dangerous voltages may be present during battery operation. The batteries must be
disconnected during maintenance or service work.
- The UPS contains potentially hazardous voltages.
- Do not remove fuse F4A or F4B during operation. This can result in a flame arc.
Do not remove the cover, there are no user serviceable parts
1.3Installation
-This UPS is intended to be used in a controlled environment indoors and free of conductive contaminants.
-The UPS should only be powered from a single phase, three wire AC source equipped with an earth
connection.
-In this manual "Earth" is represented with two different symbols:
= Field wiring equipment grounding terminal,
= Grounding terminals.
-Do not install the UPS in an excessively humid environment or near water.
-Avoid getting liquids or any foreign object into the UPS.
-The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 40°C
(104°F). Optimal battery lifetime is obtained if the ambient temperature does not exceed 30°C (86°F).
-It is important that the unit has adequate ventilation. Maintain air movement around and through the unit. Do
not block the air vents.
-Avoid placing the unit in direct sunlight or near heat sources.
- Do not plug household appliances such as electric heaters, toasters or vacuum cleaners into the UPS.
-Use insulated copper input and output wiring, rated 90°C (194°F) wire size based on the ampacities given in
Tables 310-16 of the Nation Electrical code, ANSI/NFPA 70-1993. Specified in table 2 and table 3.
1.4Storage
-Store the UPS with its batteries fully charged in a dry location, storage temperature must be within -20°C
and +45°C (-4°F and 113°F).
If the unit is stored for an extended period of time, the batteries must be recharged periodically, for 24 hours.
Connect the unit to the utility and switch it on:
-if the storage temperature is within -20 and +30°C (-4°F and 86°F), recharge the batteries every 6 months.
-if the storage temperature is within -20 and +45°C (-4°F and 113°F), recharge the batteries every 4 months.
1.5Batteries
NOTE
-
- When replacing the batteries, use only the same number, type and size battery.
-Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal requirements.
LX: OPM_LPA_11U_5K0_10K_1US_V021
: Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries
and the required precautions. Keep unauthorized personnel away from batteries.
®
Preferably for LanPro
LanPro
5/6-11U: Kobe HV7-12 or Panasonic LC-R127R2P
®
8/10-11U: Kobe HV12-12 or Panasonic LC-RA1212P
4
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 6
g
CAUTION:
-
CAUTION:
toxic. If exposed to electrolyte, wash immediately with plenty of water.
-Avoid charging in a sealed container.
CAUTION:
precautions should be observed when working on batteries:
• Remove watches, rings or other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground.
Never dispose of batteries in a fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be
A battery can present a risk of electrical shock and high short circuit current. The following
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock
will be reduced if such grounds are removed during installation and maintenance.
GE Digital Energy
2 - Introduction
More than ever before, today's advanced electronic equipment, with complex integrated circuits and other sensitive
electronics, needs a stable and continuous AC power supply to operate correctly. While the power coming from the
wall outlet is often unreliable, a GE Digital EnergyLanPro
uninterrupted power.
A compact, truly on-line system, the GE Digital EnergyLanPro
power interference, including complete power failure. A simple and elegant circuit design, together with extensive
protection against abnormal operating conditions (e.g. overload, short circuit, overheating), makes the LanPro
exceptionally reliable.
The LanPro
a result, input and output voltages do not necessarily have to be equal, making the UPS suitable for almost every
situation.
®
-U UPS offers complete galvanic isolation of input and output, also when operating in bypass mode. As
®
-U UPS provides the security of completely
®
-U UPS protects your equipment from all forms of
®
-U
All units are standard equipped with a backfeed protection relay.
Figure 1: The
GE Digital Energy LanPro
®
-11U
UPS
LX: OPM_LPA_11U_5K0_10K_1US_V021
5
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 7
g
®
®
GE Digital Energy
3 - Functional Explanation
3.1The Principles of Operation
The LanPro
incoming utility power is cut off completely.
Energy is stored as Direct Current (DC), while input and output energy must be Alternating Current (AC). Therefore
the UPS contains an input converter (AC to DC) and an output converter (DC to AC). (fig.2)
3.2Normal Conditions
Under normal conditions, energy from the utility is channelled through the input converter, which supplies the output
converter and the battery charger. The batteries are kept in a fully charged state, and the output converter
synthesizes a completely new AC output sine wave to supply the load (electrical equipment).
®
-U UPS stores electric energy in batteries. This allows the UPS to supply output power even when the
SYSTEM
ON/OFF
OUTPUT:
PERFECT UPS POWER
MANUAL BYPASS
SWITCH
OUTPUT
TRANSFORMER
FRONT
PANEL
RFI
FILTER
OUTPUT
OPTION
SLOTS for:
RPA CARD
SNMP CARD
RELAY CARD
std. installed:
RS232/
CONTACT
INTERFACE
INPUT:
UTILITY POWER WITH DISTURBANCES
UTILITY
INPUT
FILTER
BYPASS
FILTER
RFI
BACKFEED
PROT.
OPTIONAL
BATTERY
EXTENSION
P.F. = 1
CONVERTER
RECTIFIER
MICRO-PROCESSOR CONTROL
BATTERY
STATIC
BYPASS
OUTPUT
CONVERTER
BATTERY
CHARGER
Figure 2. Block diagram of the
LanPro
-11U
UPS, utility present
3.3Utility Failure
In the event of a utility power failure (i.e. absent or outside tolerance) the system uses the energy reserve stored in
the battery to continue to produce AC power, ensuring unbroken output (fig. 3). No interruption or alteration will ever
be noticed in the output power.
In the event of an extended utility failure, the output converter will stop when the battery has been discharged. At this
point, the UPS is no longer able to power the connected equipment.
When the utility is re-established within tolerance, the output converter will be supplied again by the input converter
and the batteries will be recharged, making them ready to support future power failures.
SYSTEM
ON/OFF
OUTPUT:
PERFECT UPS POWER
MANUAL BYPASS
SWITCH
OUTPUT
TRANSFORMER
FRONT
PANEL
RFI
FILTER
OUTPUT
OPTION
SLOTS for:
RPA CARD
SNMP CARD
RELAY CARD
std. installed:
RS232/
CONTACT
INTERFACE
NO INPUT:
UTILITY FAIL URE
RFI
FILTER
BACKFEED
PROT.
OPTIONAL
BATTERY
EXTENSION
BYPASS
FILTER
P.F. = 1
CONVERTER
RECTIFIER
MICRO-PROCESSOR CONTROL
BATTERY
STATIC
BYPASS
OUTPUT
CONVERTER
BATTERY
CHARGER
Figure 3. Block diagram of the
LX: OPM_LPA_11U_5K0_10K_1US_V021
LanPro
6
-11U
UPS, utility failure
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 8
g
GE Digital Energy
3.4Automatic Bypass Switch
If the output converter is unable to deliver the demanded output power because of overload or overtemperature, the
automatic bypass switch will automatically transfer the load to the utility. When the situation is corrected the UPS will
switch back to normal operation, i.e. the load is tranferred back to the output converter. Though the automatic
bypass switch is shown as a simple mechanical switch in figures 2-5, the transfers are done by means of thyristors,
i.e. electronically, without any interruption of the power supplied to the load.
In case of a severe overload or short-circuit the magnetic bypass circuit breaker (rear panel) may trip in order to
protect the UPS. If the current is insufficiently high to trip the breaker, the UPS will be switched off by the software in
order to protect the UPS and connected equipment.’
MANUAL BYPASS
SYSTEM
ON/OFF
SWITCH
OUTPUT
TRANSFORMER
FRONT
PANEL
RFI
FILTER
OUTPUT
OPTION
SLOTS for:
RPA CARD
SNMP CARD
RELAY CARD
std. installed:
RS232/
CONTACT
INTERFACE
UTILITY
INPUT
RFI
FILTER
BACKFEED
PROT.
OPTIONAL
BATTERY
EXTENSION
BYPASS
FILTER
P.F. = 1
CONVERTER
RECTIFIER
MICRO-PROCESSOR CONTROL
BATTERY
STATIC
BYPASS
OUTPUT
CONVERTER
BATTERY
CHARGER
Figure 4 . Bypass operation: Automatic bypass
If a power failure occurs during bypass operation, load power may be lost. If the UPS functions under overload
conditions it may not be able to protect the load.
3.5Manual Bypass Switch (Service switch)
The system can be bypassed manually using the manual bypass switch located at the rear panel. It is a two-position
switch: the normal position is '1': as in figures 2-4. Position '2' is the service position: the load is directly connected to
the utility input. This way maintenance of the UPS (e.g. battery replacement, as in fig. 5) is possible without
interruption of the power supplied to the load.
CAUTION:REFER SERVICE TO QUALIFIED PERSONNEL ONLY
THE RFI FILTERS AND OUTPUT TRANSFORMER ARE ALWAYS ACTIVE.
BYPASS
UTILITY
INPUT
RFI
FILTER
BACKFEED
PROT.
OPTIONAL
BATTERY
EXTENSION
FILTER
P.F. = 1
CONVERTER
RECTIFIER
MICRO-PROCESSOR CONTROL
STATIC
BYPASS
OUTPUT
CONVERTER
BATTERY
CHARGER
.
MANUAL BYPASS
SWITCH
OUTPUT
RFI
FILTER
OUTPUT
SYSTEM
ON/OFF
TRANSFORMER
FRONT
PANEL
OPTION
SLOTS for:
RPA CARD
SNMP CARD
RELAY CARD
std. installed:
RS232/
CONTACT
INTERFACE
LX: OPM_LPA_11U_5K0_10K_1US_V021
Figure 5 . Bypass operation: Manual bypass
7
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 9
g
GE Digital Energy
4 - Installation
4.1Unpacking
Cut the two wrapping bands, and remove the shipping box. Loosen the four bolts with which the UPS is fixed to the
pallet. Remove the UPS from the pallet.
UPS is equipped with castors, that allow easy displacement of the unit. Please take appropriate measures to avoid
damage on vulnerable floors.
4.2Package Contents
The shipping box contains a LanPro
safety guide and this manual. If the UPS is equipped with an RPA plug-in card (Redundant Parallel Architecture,
right option slot at the rear of the unit) the shipping box also contains a yellow network cable and one bus terminator.
Inspect the UPS for damage after unpacking. If any damage is present please notify the carrier and place of
purchase immediately.
4.3Location
Please refer to section 1.3 of ‘IMPORTANT SAFETY INSTRUCTIONS’.
4.4Installation
BE CAREFUL! HEAVY WEIGHT!
®
-U UPS, a CD-ROM, an RS232 cable, a link (5/6kVA models only, see 4.4.3) a
Never try to lift the unit by yourself! The
IMPORTANT
Before making any connection and switching on the LanPro
•The voltage and frequency of your utility supply is 120/208/230/240 Vac and 50 or 60 Hz; from the factory the
input and output of the UPS are set to 208 Vac / 60 Hz.
•Be sure that the UPS is wired for the present utility voltage. This is indicated on the packaging of the UPS, as
well as at the I/O terminals.
•Overcurrent protection for the AC circuit is to be provided by others.
CAUTION: To reduce risk of fire, connect only to a circuit input/output provided with
branch circuit overcurrent protection in accordance with the National Electrical
Code, ANSI / NFPA 70, as indicated below:
Input overcurrent protection
(Amps)
120V208V240V120V
Output overcurrent protection
(Max. Amps)
(1 X)
120V
(2X)
208V240V
Table 1. external input fuse value
•Ensure that the total power requirement of the equipment to be protected does not exceed the rated output
power of the UPS. (output power for your unit is indicated on the rating label on the rear panel).
•When using the 120V split phase outputs make sure that the load per 120V output does not exceed half the
rating.
•The UPS may only be installed by trained personnel. The UPS must be grounded when in use: Connect the
UPS to a single phase, three wire AC source equipped with an earth connection.
LX: OPM_LPA_11U_5K0_10K_1US_V021
8
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 10
g
•Use insulated copper input and output wiring, rated 90°C derated to 40°C wire size based on the ampacities
given in Tables 310-16 of the National Electrical code, ANSI/NFPA 70-1993.
This wiring shall have the following minimum sizes:
L5/6-11U/120V22 Lbs/inch
All other models18-20 Lbs/inch
Table 4. Tightening torque force
LX: OPM_LPA_11U_5K0_10K_1US_V021
9
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 11
g
®
GE Digital Energy
4.4.1Installation Procedures
4.4.1.1 Standard installation procedure: input voltage 208-240Vac, output voltage 120/208/220/230/240Vac.
If a battery extension pack is to be installed, please proceed with section 4.4.5.
If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.4.6.
The numbers between (brackets) refer to figure 19 in section 5.1.
1.Mount the levellers: position A to fix the UPS to the floor,
position B to lift the castors from the floor.
A
2.Loosen the screws and remove the conduit box (17) and
B
1
the metal cover plate (11).
3.Make sure that all circuit breakers (7-8-9) are in ‘off’
position (down).
2
UPSUTIL.BYPASS
ON
4.Input/output connection:
Lead the input/output cables through the cable inlet. If the
cables come from below (recommended for 8kVA and
10kVA models), you can rotate the cable inlet 90 degrees.
OFF
3
Connect the input/output wires to the I/O terminals (11a
and 11b). Please refer to section 4.4.2 1 (input) and 4.4.3
(output) for detailed information.
L1 L2
5.Re-install the metal cover plate (11) and the conduit box
(17).
6.An emergency shutdown switch can be connected to
connector J3 on the RS232/Contact Interface Card,
between pins 3 and 4. See section 6.2 for more
4
information.
7.For advanced communication possibilities, the
RS232/contact interface port (12a) can be connected to a
computer system. See section 6.1 for more information.
8.The middle ‘option slot’ (13) allows easy installation of
plug-in cards: SNMP Card or Relay Card. See sections
5
6.3 and 6.4 for more information.
9.The right ‘option slot’ (14) allows easy installation of the
RPA-card (Redundant Parallel Architecture). If the card is
1-2 BATTERY
DISCONNECTED
3-4 EMERGENCY
SHUTDOWN
6
7
stand-alone,
see 6.3-4
and RPA card
available:
already mounted, and if the unit is intended to be used
stand-alone, a bus terminator (delivered with the unit) has
to be placed in one of the two bus connectors on the card.
If the unit will be part of a parallel system, see sections
4.4.6 and 7.3 for more information.
10. Connect the utility power to the UPS.
11. If hardware modifications were necessary in step 4
because the I/O voltages are different from the default
8
9
see 4.4.6 / 7.3
(208Vac), software modifications should be performed as
well. Proceed with 4.4.4.
Figure 6.
LanPro
5/68/10-11U:
Standard installation procedure
LX: OPM_LPA_11U_5K0_10K_1US_V021
12. For a quick start proceed with section 5.2 ‘Start-up’.
10
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 12
g
®
4.4.1.2Installation procedure:
input voltage 120Vac (optional, 5-6kVA only), output voltage 120/208/220/230/240Vac.
If a battery extension pack is to be installed, please proceed with section 4.4.5.
If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.4.6.
The numbers between (brackets) refer to figure 19 and 20 in section 5.1.
1.Mount the levellers: position A to fix the UPS to the floor,
position B to lift the castors from the floor. Please refer to
figure 6, step 1.
2.Loosen the screws and remove the conduit boxes (17, 2x)
and the cover plate (11).
GE Digital Energy
2
3.Make sure that all circuit breakers (7-8-9) are in ‘off’
position (down). Please refer to fig. 6, step 3.
4.Input/output connection:
Lead the input/output cables through the cable inlet. If the
cables come from below (recommended for 8kVA and
10kVA models), you can rotate the cable inlet 90 degrees.
LN
Connect the input wires to the input terminals (11b).
Connect the output wires to the output terminals (11a).
Please refer to section 4.4.2.2 (input) and 4.4.3 (output)
for detailed information.
5.Re-install the cover plate (11) and the conduit boxes (17,
4
2x).
6.An emergency shutdown switch can be connected to
connector J3 on the RS232/Contact Interface Card,
between pins 3 and 4. See section 6.2 for more
information.
7.For advanced communication possibilities, the
RS232/contact interface port (12a) can be connected to a
computer system. See section 6.1 for more information.
8.The middle ‘option slot’ (13) allows easy installation of
5
plug-in cards: SNMP Card or Relay Card. See sections
6.3 and 6.4 for more information.
1-2 BATTERY
DISCONNECTED
3-4 EMERGENCY
SHUTDOWN
7
6
stand-alone,
and RPA card
8
9
Figure 7.
see 6.3-4
see 4.4.6 / 7.3
LanPro
5/6-11U:
Installation procedure 120V input
LX: OPM_LPA_11U_5K0_10K_1US_V021
avai lable:
9.The right ‘option slot’ (14) allows easy installation of the
RPA-card (Redundant Parallel Architecture). If the card is
already mounted, and if the unit is intended to be used
stand-alone, a bus terminator (delivered with the unit) has
to be placed in one of the two bus connectors on the card.
If the unit will be part of a parallel system, see sections
4.4.6 and 7.3 for more information.
10. Connect the utility power to the UPS.
11. If hardware modifications were necessary in step 4
because the output voltage is different from the default
(208Vac), software modifications should be performed as
well. Proceed with 4.4.4.
12. For a quick start proceed with section 5.2 ‘Start-up’.
11
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 13
g
®
®
GE Digital Energy
4.4.2 Available input voltages: hardware modifications
The following input voltages are possible: 208, 240 Vac (see 4.4.2.1) and 120 Vac (see 4.4.2.2)
4.4.2.1Input voltage 208 or 240Vac.
1.Input voltage is 208 Vac. This is the factory setting. Proceed with step 3.
2.Input voltage is 240Vac. In this case the bypass tap on the output transformer must be changed. Please refer
to fig. 8 and 8a. Proceed as follows:
2.1 Remove the blue wire B from faston 74 (connect) and place this wire on faston 72 (park).
2.2 Remove the yellow wire A from faston 61 (park) and place this wire on faston 74 (connect).
Bypass tap factory setting: 208 Volt
PCB1113-D
(park)
(park)
(connect)
61
72
74
73
To manual bypass switch
T1
A
B
14
Bypass tap changed to 240 Volt
PCB1113-D
(park)
(park)
(connect)
Figure 8
61
72
74
73
To manual bypass switch
. LanPro
5/6/8/10-11U:
Bypass tap change
T1
A
B
14
Figure 8a.
61
72
74
73
LanPro
65
66
67
5/6/8/10-11U:
Rear view
3.Connect the utility supply wires to terminals 6 (L1), 7 (L2) and 8 (equipment grounding conductor). See
figure 9. Ground connection is essential!
If a neutral wire is part of the site wiring provided, we suggest to isolate this wire for future use or other
applications.
gnd
L1
gnd
L2N
123
45 67 8
Figure 9. LanPro 5/6/8/10-11U:
Input/output terminals
4.For the output voltage proceed with 4.4.3.
LX: OPM_LPA_11U_5K0_10K_1US_V021
12
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 14
g
®
®
4.4.2.2Input voltage 120Vac (optional, 5/6kVA only).
®
LanPro
input voltage of 120Vac.
1.Connect the utility supply wires to terminals L, N and GND (equipment grounding conductor). See figure 10.
-U UPS equipped with an (optional) step-up transformer (5/6kVA models only) can be connected to an
Ground connection is essential!
gnd
NL
GE Digital Energy
Figure 10.
120Vac Input terminals
2.For the output voltage proceed with 4.4.3.
4.4.3 Available output voltages: hardware modifications
The off-factory setting is 208 Vac: a link is placed between terminals 2 and 3. An extra link was delivered with the
unit (in a plastic bag) to enable other output voltages (5/6kVA models only).
The following voltages are available: 120, 208, 220, 230, 240 Vac.
4.4.3.1Output voltage 208Vac
This is the off-factory setting. There is a link between terminal 2 and 3.
1.Connect the output wires to the terminals 1 (L1) and 4 (L2).
2.Connect the ground wire to terminal 5. Ground connection is essential! See figure 11.
LanPro
5/6-11U:
gnd
L1
gnd
L2N
123
208V
Figure 11.
208 Vac output connection
3.Return to either 4.4.1.1 step 5 or 4.4.1.2 step 5
LX: OPM_LPA_11U_5K0_10K_1US_V021
45 67 8
LanPro
5/6/8/10-11U:
13
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 15
g
®
GE Digital Energy
4.4.3.2Output voltage 120Vac split-phase
1.The factory setting of the output tap (208Vac) has to be changed to 240Vac. Please refer to fig. 12 and 12a.
Proceed as follows:
1.1 Remove the yellow wire L from faston 67 (connect) and place this wire on faston 65 (park).
1.2 Remove the brown wire F from faston 66 (park) and place this wire on faston 67 (connect).
Output tap factory setting: 208 Volt
T1
F
32V
88V
120V
L
64
62
63
1113-D
O
Output tap changed to 240 Volt
T1
F
32V
88V
120V
L
64
62
63
O
1113-D
Figure 12. LanPro 5/6/8/10-11U:
Output tap change
PCB1113-C
(park)
65
(park)
66
(connect)
PCB1113-C
(park)
65
(park)
66
(connect)
67
61
67
72
74
73
65
66
67
Figure 12a. LanPro 5/6/8/10-11U:
Rear view
2.Connect the load wires between the terminals 1 (L1) and 2 (N) (120V), and between the terminals 3 (N) and 4
(L2) (120V). Connect the ground wire to terminal 5. Ground connection is essential! Do not remove the link
between terminals 2 and 3. See figure 13.
gnd
L2N
123
120V120V
Figure 13.
LanPro
gnd
L1
45 67 8
5/6/8/10-11U:
120 Vac split-phase output connection
3.Return to either 4.4.1.1 step 5 or 4.4.1.2 step 5
LX: OPM_LPA_11U_5K0_10K_1US_V021
14
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 16
g
®
®
4.4.3.3Output voltage 220/230/240Vac
1.The factory setting of the output tap (208Vac) has to be changed to 240Vac. Follow the procedure as described
in section 4.4.3.2 steps 1.1 and 1.2.
2.Connect the load wires between the terminals 1 (L1) and 4 (N). Connect the ground wire to terminal 5. Ground
connection is essential! Do not remove the link between terminals 2 and 3. See figure 14.
GE Digital Energy
gnd
L1
123
220/230/240 V
3.Return to either 4.4.1.1 step 5 or 4.4.1.2 step 5
4.4.3.4Output voltage 120Vac single phase
1.The factory setting of the output tap (208Vac) has to be changed to 240Vac. Follow the procedure as described
in section 4.4.3.2 steps 1.1 and 1.2.
2.Remove the link between terminals 2 and 3.
Proceed as follows: LanPro
45 67 8
LanPro
gnd
L2N
Figure 14.
220/230/240 Vac output connection
®
-U 5/6kVA: step 3-6,
®
-U 8/10kVA: step 7-10.
LanPro
5/6/8/10-11U:
For
LanPro
3.Place this link between terminal 1 and 2.
4.Place the extra link (delivered with the unit) between terminals 3 and 4.
5.Connect the load wires between connectors 1 (or 2) and 3(or 4).
6.Return to either 4.4.1.1 step 5 or 4.4.1.2 step 5.
123
120 V
Figure 15.
120 Vac single phase output connection
LX: OPM_LPA_11U_5K0_10K_1US_V021
®
5/6kVA:
-U
gnd
L1
45 67 8
LanPro
5/6/-11U:
gnd
L2N
15
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 17
g
®
For
LanPro
7.Install the optional 120Vac Single Phase Kit, art no.
8114001300550, according to fig. 15a
8.Connect the load wires to the terminals of the Single
Phase Kit, according to fig. 15a.
9.Connect the ground wire to terminal 5. Ground
connection is essential! See figure 15a.
10. Return to either 4.4.1.1 step 5 or 4.4.1.2 step 5
NOTE: following this procedure you realize that the values shown in the LCD match the the actual
input/output voltages.
1.Switch on the circuit breakers '
2.Go to the setup menu. See 5.3.4 ‘Setup Menu’
utility
' (8) and '
bypass
' (9) (see also section 5.2, step 1-2)
gnd
6(7836&5((16
(17(55(6(7H[LW
3.Using the push-buttons 'up' and 'down' you can scroll through the several setup screens. 'Enter/reset' confirms
the screen choice. Go to the setup screen 'INPUT VOLTAGE'.
,138792/7$*(
9
4.Here you can change the input voltage to 240 Volt. The value of the input voltage blinks. Scroll through its
settings by using the push-buttons 'up' and 'down', the new setting is confirmed by pressing 'enter/reset'.
,138792/7$*(
&+$1*(72
9
5.Go to the setup screen 'OUTPUT VOLTAGE'.
28738792/7$*(
9
6.Here you can change the output voltage to 240 Volt. The value of the input voltage blinks. Scroll through its
settings by using the push-buttons 'up' and 'down', the new setting is confirmed by pressing 'enter/reset'.
,138792/7$*(
&+$1*(72
7.To return to the default screen scroll to the setup screens first and press 'Enter/reset'. You can also wait 20
seconds: the time-out period of no key activity.
8.You can now proceed with 5.1 or 5.2.
LX: OPM_LPA_11U_5K0_10K_1US_V021
9
16
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 18
g
®
GE Digital Energy
4.4.5Installation of
The numbers between (brackets) refer to figures 19-21 in section 5.1.
Battery extension pack(s) are shipped with all materials necessary to connect them to the UPS. The pack(s) can be
connected to the DC connector (15) at the rear panel of the UPS. Be sure to switch off the UPS before proceeding:
be sure that the UPS can be switched off without causing damage to the load, and turn all circuit breakers (7-8-9)
into ‘off’ position (down).
11a
2
3
4
5
Figure 16
. LanPro
GE Digital Energy LanPro
5/6/8/10-11U:
®
battery extension pack(s)
-U
1.Open the DC fuse holders at the rear of the battery pack
(16) and make sure that the fuses have been removed.
1a. Open the DC fuse holders at the rear of the UPS (16) and
make sure that the fuses have been removed.
2.UPS rear panel: loosen the screws, and remove the cover
plate (11) and conduit box (17).
CAUTION!
NOT isolated from the utility.
3.Break out the indicated part of the conduit box, fix the
gland of the DC cable in this opening.
4.Connect the DC connector of the battery pack (15a) to the
DC socket of the UPS (15). Be sure that the colours
match. You will hear a click when the cable is properly
installed.
5.Re-install the cover plate and conduit box.
6.In case of 14Ah battery packs: using the DC connector of
the battery pack (15) you can install a second, third, etc.
pack. 7Ah battery packs cannot be connected in parallel.
NOTE:
battery cabinets can be connected without additional
fusing. Every two additional GE Digital Energy 14Ah
battery cabinets must be connected over a 60Amp fuse,
rated for 300Vdc.
NOTE:
over a 60Amp fuse, rated for 300Vdc, using the GE
Digital Energy external battery cable (order separately).
7.Insert the 2 (7Ah) or 4 (14Ah) DC fuses of the (each)
battery pack, insert the DC fuses of the UPS and close the
fuse holder(s) of battery pack and UPS (16).
8.In order to calculate the available back-up time related to
the actual load, information on the capacity of the battery
set is stored in the UPS. As the total battery capacity
changes when battery extension packs are installed, the
battery capacity must be re-programmed. See 5.3.4.
In case of a custom-built battery extension set you may want to
install a ‘battery disconnected’ alarm device.
9.Be sure that the UPS is switched off, and disassemble the
RS232/Contact Interface Card (12) from the unit.
card is disassembled during normal operation the UPS will
shut down!
Remove the wire from connector J3 (pin 1 and 2). Install
the wiring of a normally closed contact (e.g. an auxiliary
contact of a circuit breaker) to pin 1 and 2. Re-install the
interface card. If the contact is opened, the UPS will
generate an ‘EXTERNAL BATTERY FUSE FAILURE’.
See 5.3.2 for more information.
Proceed with 4.4.1 or 5.2.
A maximum of two GE Digital Energy 14Ah
Third party battery cabinets must be connected
The battery voltage is 240Vdc and is
If the
LX: OPM_LPA_11U_5K0_10K_1US_V021
17
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 19
g
GE Digital Energy
4.4.6
LanPro
The RPA option (Redundant Parallel Architecture) allows you to create a redundant UPS system in which 2, 3 or 4
LanPro
®
11U series: 2 / 3 / 4 parallel operating units – additional info
®
-U units operate in parallel. The following should be considered when installing units in parallel.
This section gives aditional information on:
- installation (4.4.6.1)
- start-up (4.4.6.2)
- use / maintenance (4.4.6.3)
4.4.6.1 Notes concerning installation of a parallel system
1.All inputs of the UPSs must be supplied from the same phase. This is to enable bypass operation of the
parallel system. All inputs must be individually protected by fuses in the installation. The values of these fuses
should correspond to the values mentioned in section 4.4 table 1.
2.All outputs must be connected together, supplying the load. It is advised to install switches (S 1-4, fig. 17) in
the output wiring, in order to be able to isolate a unit from the remaining system for service and maintenance
purposes. It is advised to make a Neutral-to-Ground bounding in the output junction.
3.The diameter of input and output cables must be according to the table in the installation drawings (see
appendix). Cables with different diameters can cause tripping fuses in the UPS and/or the installation.
4.The length of all input cables from the input junction (Li, fig. 17) to the UPS inputs should be equal. The same
applies to the cables from the outputs to the output junction (Lo, fig. 17). The minimum length of the input as
well as the output cables is 3 meters / 10 feet.
F 1 - 4
DISTRIBUTION
FUSE OR BREAKER
VALUES ACCORDING
TO TABLE 1
IN
LanPro
RPA
CARD
OUT
S 1 - 4
SWITCH ALLOWS
ISOLATION OF
A UNIT FROM
THE SYSTEM
Li / Lo: LENGTH OF I / O WIRING
- EQUAL FOR EACH UPS
- MINIMUM 3 METERS / 9.8 FEET
1-PHASE 3-WIRE INPUT
LiLi
F1F2F3F4
BUS
TERMINATOR
IN
LanPro
RPA
CARD
OUT
INPUT JUNCTION
LiLi
IN
LanPro
RPA
CARD
OUT
IN
LanPro
RPA
CARD
OUT
S1S2S3S4
LoLo
LoLo
MAKE
NEUTRAL-TO-GROUND
BOUNDING HERE
OUTPUT JUNCTION
TO LOAD
YELLOW NETWORK
CABLES AS DELIVERED
WITH THE UPS
BUS
TERMINATOR
Figure 17. Installation of parallel operating
LX: OPM_LPA_11U_5K0_10K_1US_V021
18
LanPro
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
®
-U
UPSs
Page 20
g
5.The right option slot (14) at the rear of the unit contains the the RPA-card. Before the parallel system can be
put into operation a unique number has to be appointed to each UPS in the system. This can be 0, 1, 2 or 3.
Start with 0 for the first unit, 1 for the second, 2 for the third and 3 for the last unit:
- loosen the screws, remove the RPA-card
- set the dipswitch to the appointed number (fig. 18)
- re-install the RPA-card, fasten the screws.
Do NOT install the network cables between the RPA-cards of the units yet!
Figure 18. Appointing a unique
= ‘on’ (3 = 1+2 ‘on’)
6.In the UPS many parameters can be set. It is advised to keep the same setting for each parameter in each
UPS in the parallel system. In any case the following parameters are critical and should have equal settings:
- autorestart (on/off, see 5.3.3)
- output voltage (120/208/220/230/240 Vac, see 5.3.4)
- output frequency (50/60 Hz, see 5.3.4)
number to each UPS in the system
GE Digital Energy
It is absolutely required that these parameters are set to the same value. Off factory this is the case. If you’re
not sure that the units have equal settings:
- be sure that the RPA-cards of the units have not been interconnected yet
- be sure that utility power is connected to the UPS
- start each unit individually (see 5.2), check / change the parameters, and switch the unit off again.
7.Interconnect the RPA-cards of the units, using the network cable that came with the UPS. See figure 17
(dotted line). Only install the cables that were delivered with the UPSs! Of the first and the last UPS in the
system only one RPA-socket is used to interconnect the UPSs. A bus terminator must be placed in the other
(free) RPA-socket. The required bus terminators have been delivered with the unit.
4.4.6.2 Notes concerning starting up the parallel system
For starting up the system please refer to section 5.2.
After switching on all units the LanPro
®
-U UPSs will show the following display:
$8725(67$572))
35(66(17(5
After pressing the enter/reset button on one of the units the system will start up. All units will display the standard
screen. The number in the lower right corner indicates the number of the UPS in the system.
/DQ3UR8
/2$'
If the parameters mentioned in 4.4.6.1 step 6 are not set to the same value the UPS will display the following screen
after start-up:
In this case check and correct the setting of the parameters as mentioned in 4.4.6.1, step 6.
LX: OPM_LPA_11U_5K0_10K_1US_V021
$8725(67$572))
6(77,1*0,60$7&+
19
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 21
g
4.4.6.3 Notes concerning use / maintenance of a parallel system
ECO-mode:
®
If LanPro
No-load shutdown:
-U units operate in parallel, the ECO-mode feature is not available.
GE Digital Energy
If LanPro
Manual bypass:
Maintenance:
To isolate a unit from the redundant system:
To re-enter the unit into the system:
®
-U units operate in parallel, the no-load shutdown function is not available.
If you want to switch one of the UPSs to bypass operation using the manual bypass switch (switch is
turned into position 2) then all UPSs in the parallel system have to be switched to bypass operation in
order to prevent damage.
1. Switch off the UPS which has to be isolated,
2. Remove the installation fuse from the input of that UPS (F1-4 in figure 17),
3. Separate the output of the UPS from the output junction (S1-4 in figure 17).
1. Reinstall the installation input fuse,
2. Connect the output of the UPS to the output junction,
3. Switch on the UPS.
LX: OPM_LPA_11U_5K0_10K_1US_V021
20
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 22
g
5 - Operation
5.1Description of Front and Rear Panel
GE Digital Energy
651243
1LCD screen
2x16 characters, shows UPS system data, status messages, settings.
The language is selectable: English, German, French, Italian,
Spanish. Section 5.3.4 describes the selection procedure.
2-4Push-buttons
With the button keypads ‘down’ (2) and ‘up’ (4) you can scroll through
the several screens, with keypad 'reset/enter' (3) a selection is
confirmed. Keypad activity is accompanied by a short beep. If there is
no keypad activity during 20 seconds the LCD screen will return to the
default screen (except for the service screens, see section 5.3.3).
5LED 'operation' indicates normal operation.
6LED ‘alarm’, indicates an alarm situation, accompanied by alarm
message(s) on the display and a sounding buzzer.
See section 5.3.2 for more information.
7Switch ‘UPS on/off’, turns on/off the complete UPS, including the
automatic bypass!
8Circuit breaker ‘Utility on/off’, protection fuse for utility input and
battery charger.
9Circuit breaker ‘Bypass on/off’, fuse to protect the system in case of
severe overload or short circuit in the UPS load.
10Manual Bypass Switch:1 = Load on UPS
2 = Load on utility
WARNING:
output is also live regardless the position of the circuit
breakers ‘utility’ and ‘bypass’.
In position 2, if the input line is energized, the
14Option slot for RPA (Redundant Parallel Architecture) Card. Not
12a
15DC socket / connector.
16Battery fuse holder
17Conduit box
14
13
12
18Cable inlet
Figure 19 :
Front and rear panel
12a- RS232 Interface Port (see section 6.1)
- Emergency shutdown (see 4.4.1 and 6.2)
- Battery disconnected, pin 1-2 (can be used for external
signaling).
- Relay Card (see 6.3)
- SNMP Card (see 6.4)
available yet.
LX: OPM_LPA_11U_5K0_10K_1US_V021
21
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 23
g
17
18
GE Digital Energy
Rear panel of the step-up transformer:
11bInput terminals L, N and GND
17Conduit box
18Cable inlet
11b
Figure 20. Rear panel of the
step-up transformer
1615
14Ah
15a
19
Figure 21. Rear panel battery
extension pack (optional)
Rear panel of (optional) battery extension pack:
15DC socket (14Ah only)
15aDC connector
16Battery fuse holder(s)
7Ah:2 fuses
14Ah:4 fuses
19Gland to fasten cable in conduit box of UPS
LX: OPM_LPA_11U_5K0_10K_1US_V021
22
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 24
g
GE Digital Energy
5.2Start-up
The numbers between (brackets) refer to figure 19 in section 5.1.
Note: the UPS can be started on battery power if the utility input voltage is not available or if circuit breaker
is in off-position: simply skip step 1. To prevent accidental discharging of the batteries, it is however
‘utility’
recommended to proceed with step 1 and start the unit only when the utility input voltage is available.
1.Turn breaker '
2.Some UPS parameters (e.g. voltage, frequency, LCD language) are user selectable. If you want to change
one or more settings, please refer to section 5.3.4 ‘Setup Menu’ now. Changing the settings later is possible,
however only after switching off the unit.
3.Turn switch
The green LED
After switching on the UPS performs a self-test and the display (front panel, 1) will show:
'UPS on/off'
(8) and breaker '
utility'
(rear panel, 7) into position ‘on’ (up).
'operation'
bypass
(front panel, 5) will illuminate.
' (9), both on the rear panel, into position ‘on’ (up).
6(/)7(67
,1352*5(66
After completion of the self-test the output voltage of the UPS is available and the unit is ready for use. The
display will show the default screen: model and actual load (values are examples)
/$13528
/2$'
In case of a system failure the self-test results in a failure message; this message is displayed for 30 seconds
before the self-test is repeated automatically. If the faulty situation persists, switch off the UPS and contact
your dealer. See chapter 9 for more information.
4.Though the batteries (the internal energy reserve) were fully charged when the UPS left the factory, they
might have lost some energy during transport and/or storage. It is recommended to allow the UPS to
recharge the batteries for a few hours. This way you ensure that the UPS can provide sufficient runtime in
case of a utility power failure.
5.If not yet switched on, the equipment connected to the LanPro
usual.
®
-U UPS can be switched on now; operate as
LX: OPM_LPA_11U_5K0_10K_1US_V021
23
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 25
g
GE Digital Energy
5.3Use
Once the unit is in operation, there is no need to switch the unit on/off during use.
If the manual bypass switch (rear panel, 10) is in position '1', switching off by the on/off switch (rear panel, 7) results
in a total absence of the output voltage (also the bypass voltage) of at least 5 secs.
If an emergency shutdown switch has been installed (see 4.4.1.1-2, step 6) the UPS will stop immediately when the
switch is opened. Restart is only possible after closing the switch and turning the UPS
UPS on/off switch (rear panel, 7).
The UPS is operated via the push-buttons (front panel, 2-3-4) and the LCD display (front panel, 1). Furthermore the
UPS can be controlled via the RS232/contact interface port (rear panel, 12a). For more information see 6.1.
The menus on the display can be divided into 5 groups:
1standard screen
2information menu (5.3.1)
3status- and alarm menu (5.3.2)
4service menu (5.3.3)
5set-up menu (5.3.4)
off
and on again with the
The
standard menu
shows UPS model and actual load.
/$13528
/2$'
5.3.1 Information Menu
When the default screen is displayed the first information screen can be entered by depressing the 'up' key (front
panel, 4). Using the 'up' and 'down' keys (front panel, 4 and 2) you can scroll through several information screens.
After the last information screen the default screen will appear.
The screens display the following information:
,1387/,1(9
Utility voltage and utility frequency, and the power delivered by the utility.
N:+]
2873879
/2$'+]
%$77(5<°&
9$
$872120<7,0(
Output voltages and output frequency, and the power delivered by the UPS (as %
of the nominal UPS rating).
The temperature near the batteries, the battery voltage and the battery current
(charging: + value, discharging: - value).
The remaining battery runtime (or autonomy) during a utility failure.
/()7
23(5$7,1*7,0(
The total operating time of the UPS.
<($5'$<6
LX: OPM_LPA_11U_5K0_10K_1US_V021
24
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 26
g
5.3.2 Status and Alarm Menu
The UPS alerts the user with a standard alarm screen that the operating mode has changed and/or that an alarm
situation occurs:
GE Digital Energy
21/,1(
$/$5035(6683
Possible operating modes:
21/,1(
21%<3$66
21%$77(5<
2873872))
210$18$/%<3$66
RQ(&2PRGH
Depressing the 'up’ key from the standard alarm screen shows, in priority order, which alarms are active,. Scroll
through the screens with the 'up' and 'down' keys. Alarm message texts can succeed each other. The following
messages are possible:
/2$'QRW3527(&7('
The actual operating mode, the possible modes are mentioned below. The lower
line -if displayed- shows that an alarm occurred. More information can be retrieved
with the 'up' key. If no further information is available, the second line is blank.
The normal operating mode. For more information see section 3.2.
Overload or failure situation. For more information see section 3.5.
For a detailed description of this mode see section 3.3.
No power is delivered to the load. This can be the result of a command via the RS232
Port, or because no electric energy is available (utility failure, depleted batteries).
Service mode. For more information see section 3.6.
ECO-Mode. See section 5.5.5
The output capacitor C2 is defective. Contact your dealer.
&$3&'()(&7
83629(5/2$'('
5('8&(/2$'
83629(5/2$'('
/2$'
The load exceeds the rated output power of the UPS, and the output voltage can
no longer be guaranteed. This text alternates with the following screen:
showing the actual load as % of the nominal UPS rating. These messages are
displayed if the load is > 100%.
If the load exceeds 150% the UPS will immediately switch to bypass, assuming
that the conditions for a transfer to bypass are fulfilled. If an overload condition
between 100-150% persists, the UPS can eventually also switch to bypass
operation due to temperature protection. If a transfer to bypass is inhibited (due to
voltage or frequency errors of the utility supply) the UPS may automatically switch
off within a few seconds (load dependent).
avoid these problems, be absolutely certain that the power demands of the
protected equipment are within the limits of the UPS.
Output power is lost at that moment.
To
/2$'QRW3527(&7('
7(03722+,*+
/2$'QRW3527(&7('
The temperature of the heatsinks or output transformer is too high. As a result the
output voltage may be transferred to bypass.
The operating temperature can rise to intolerable levels as a result of:
•extreme environmental temperature
•lack of proper ventilation
•an overload situation
•fan failure
If the UPS operates in 'on line' mode, it will switch to bypass until the temperature is
normal again. If however the UPS operates 'on battery', a shutdown will occur and
output power is lost.
The internal DC voltage is too high, internal failure
92/7$*(722+,*+
%$77(5<&+$5*(5
The output voltage of the battery charger is too high, internal failure
92/7$*(722+,*+
%$77(5<&+$5*(5
7(03722+,*+
LX: OPM_LPA_11U_5K0_10K_1US_V021
The battery temperature is too high due to a battery failure or a too high ambient
temperature
25
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 27
g
GE Digital Energy
%$77(5<&+$5*(5
12)/2$7
&$3$&,725&
&$3$&,7</2:
/2$'QRW3527(&7('
,19(57(52))
/2$'QRW3527(&7('
%$77(5<'(3/(7('
/2$'QRW3527(&7('
%$77(5</2:
8366+87'2:1
/()70,187(6
After 24 hours of charging time, the battery voltage did not reach the normal float
voltage. This may be caused by faulty batteries, too many battery packs connected
or a charger fault.
The main DC-capacitor needs replacement due to aging or failure
Due to a failure the output converter's output is not available. As a result the load
may have been transferred to bypass.
The remaining runtime is zero. As a result the load may have been transferred to
bypass.
The remaining run time is less than the set time (standard 2 minutes). This text
alternates with the following screen:
The output voltage can be lost after the indicated time due to discharged battery.
Controlled shutdown of any computer equipment is absolutely necessary at this
point. (Using the RS232 or SNMP communications interface, this procedure can be
initiated automatically on unattended systems). If the UPS operates at 100% load,
the shutdown procedure should be completed within 2 minutes after the 'battery
low' alarm started. When the batteries are fully discharged, the UPS is no longer
able to power the connected equipment.
%<3$66(5525
)86()$,/85(
,1387(5525
)86()$,/85(
,17(51$/%$77(5<
)86()$,/85(
(;7(51$/%$77(5<
)86()$,/85(
5(3/$&(%$77(5<
,1387RXW/,0,76
9+]
%<3$66RXW/,0,76
9+]
The static bypass circuit breaker (rear panel, 9) is in 'off' (down position): no bypass
voltage available. Utility voltage is available. If not manually operated, this may
have been caused by an overload situation.
The utility circuit breaker (rear panel, 8) is in the 'off' (down position): no line voltage
available, bypass voltage is available. If not manually operated, this may have been
caused by an internal system failure.
The internal battery fuse is defective; this may have been caused by an internal
system failure. This alarm also appears if no batteries are installed.
The (custom-built) battery extension set has been disconnected from the system:
its energy reserve is not available. See 4.4.2 step 12 for details.
The batteries are (almost) chemically worn out. If the batteries are aged, they must
be replaced as soon as possible to ensure full protection for your equipment (see
section 8.3).
The utility voltage or utility frequency are outside UPS input tolerance (see chapter
10, specifications)
The utility voltage or utility frequency are outside bypass input tolerance but inside
UPS (rectifier) input tolerance (see chapter 10, specifications). Bypass operation is
inhibited: if for whatever reason the output converter is unable to deliver the
required output, output power is lost.
LX: OPM_LPA_11U_5K0_10K_1US_V021
26
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 28
g
GE Digital Energy
,1387$1'287387
1276<1&+521,=('
%$77(5<5817,0(
/()7
2873872))
12,138732:(5
352*6+87'2:1
:,7+,1
352*6+87'2:1
/()7
6+87'2:1
$/$5035(6683
The output converter frequency is not synchronized to the utility (input) frequency.
In this situation the automatic bypass switch is not able to transfer the load from
output converter to bypass and reverse: automatic bypass operation is inhibited: if
for whatever reason the output converter is unable to deliver the required output,
output power is lost. (see section 3.5).
Synchronization is only possible if the utility frequency remains within certain limits
(see chapter 10).
The remaining runtime. This figure is counted down during battery operation until
either the utility returns or the batteries are depleted.
The output is switched off due to a faulty situation, indicated by the second line.
The output will be switched off by a remote command (RS232/SNMP). The second
line indicates the time until shutdown.
The output is switched off by a remote command (RS232/SNMP). The second line
indicates the time until wake-up.
The output is switched off by the 'no-load shutdown' feature: no input voltage and
load <2%. If the input voltage is restored, the output will be available again. See
also section 5.5.1
,00(',$7(
6+87'2:1
5.3.3 Service Menu
When the default screen is displayed you can enter the first service screen by depressing the keys 'down' (2) and
'enter/reset' (3) simultaneously for approx. 1 second. Using the 'up' (4) and 'down' (2) keys you can scroll through
several service screens.
6(59,&(6&5((16
The wire on connector J3 pin 3-4 (rear panel, plug-in card 12) is interrupted. The
output is no longer available. To restart the unit, restore the connection and turn the
on/off switch (rear panel, 7) off and on again.
The intro service screen. 'Enter/reset' returns to the default screen.
(17(5H[LW
6(5,$/180%(5
The serial number of the UPS.
O8$
62)7:$5(9(56,21
Release number of the installed software and production code of the UPS.
5
)$163(('
Service information about fan speed (min. 10, max. 30) and internal DC voltage.
,19'&
+($76,7(03
75$16)7(03
Service information on internal temperature levels, values in mV over the
temperature sensors.
)/2$7&+$5*(
287387)$67
LX: OPM_LPA_11U_5K0_10K_1US_V021
First line: service information on charger. ‘1’ = batteries have reached float voltage.
Second line: service information on output converter.
27
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 29
g
S
GE Digital Energy
767$034
)5(45$1*(
12/2$'
48,&.%$77(5<
7(6735(66(17(5
&$/,%5$7(%$7
35(66'2:1(17(5
3)7+<5,6725
%$777+<5,6725
9667+<5,6725
3)&219(57(5
Service information on internal timer.
Frequency tracking range: output converter frequency will follow the bypass
frequency within these limits before returning to its own internal frequency.
Standard setting: nominal ±2%. Can be changed into nominal ±4% or ±6%. See
5.3.4 Setup Menu.
No-load shutdown: after a 10 minutes delay the UPS will shut down during utility
failure if the load is < 2%. It will restart after the utility returns or when the unit is
switched off and on again.
Default setting = 1 (active). For disabling this feature see 5.3.4.
Start of the manual Quick Battery Test.
See for more information section 5.4.2 'Quick Battery Test'
Start of the manual Deep Battery Calibration Test.
See for more information sections 5.4.3 'Deep Battery Calibration Test'
Service information on internal UPS components
Service information on internal UPS components
%$7&+$5*(5
,19(57(5
/$677(677,0(
)25&(%<3$66
UHVV'2:1(17(5
$8720$7,&%<3$66
(1$%/('
%$77(5<$K
%$7&+$5*(
3///2&.63(('
1250$/
(&2',6$%/('
(17(55(6(7&+1*
Service information on internal UPS components
Batt.Charger: 0 = off, 1 = float charging; 2 = top charge, 3 = boost charging,
4 = maintenance charge
Duration of latest test performed, hh/mm/ss
The UPS transfers the load to bypass when the keys 'down' (2) and 'enter/reset' (3)
on the front panel are depressed simultaneously for approx. 1 seconds. If the
bypass supply is not within limits, the lower line will show the text 'UNAVAILABLE'.
Service set up information whether the bypass is enabled (default) or disabled. If
disabled: UPS will NOT go to bypass. For disabling the bypass refer to the setup
menu (5.3.4).
Service set up information about the total battery capacity. Information about the
actual battery charge condition. For changing the programmed battery capacity
refer to the setup menu (5.3.4).
Service set up information about frequency tracking speed for the inverter to follow
the bypass frequency, LOW (1Hz/sec.) is the normal value and default. HIGH
(5Hz/sec.) may be suitable if the UPS is connected to a generator with fast
frequency changes and the UPS must be synchronized to prevent alarms. For
changing the lock speed refer to the setup menu (5.3.4).
Service set-up information about the ECO-mode. By pressing ‘ENTER/RESET’
the ECO-mode can be enabled or disabled, depending on the actual status. In
this way the load will be supplied by way of the electronic bypass. If the ECOmode is disabled the load will be supplied by the inverter. See also 4.5.5.
$8725(67$5721
(17(55(6(7&+1*
LX: OPM_LPA_11U_5K0_10K_1US_V021
Service set-up information about the autorestart function. This function can be
switched on or off by pressing ‘ENTER/RESET’, depending on the actual status.
See also 4.5.6.
28
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 30
g
5.3.4 Setup Menu
To enter the setup menu:
1. Be sure the UPS is switched off.
2. Press push-button 'enter/reset' (front panel) and then
Keep enter/reset pressed until setup menu appears.
Using push-buttons 'up' and 'down' you can scroll through the several setup screens, 'enter/reset' confirms a screen
choice. After selecting a setup screen you can scroll through its settings using the push-buttons 'up' and 'down', a
setting is confirmed by pressing 'enter/reset'. To abort the setup procedure (i.e. without changing the setting) just
wait the 20 seconds time-out period after which the default screen will return.
turn switch ‘UPS on/off’ (rear panel) into position ‘on’ (up).
GE Digital Energy
6(7836&5((16
(17(55(6(7H[LW
:$51,1*287387
&+$1*(621/,1(
/$1*8$*(
(1*/,6+
,138792/7$*(
9
28738792/7$*(
9
287387)5(48(1&<
+]
)5(48(1&<5$1*(
The intro setup screen. 'Enter/reset' returns to the default screen. You can also wait
20 seconds: the time-out period of no key activity.
Pressing ‘up’ displays the screens in the following order:
A short reminder that the new settings will be valid immediately after depressing
the ‘enter/reset’ key.
Changes the language of the screen messages: you can select English, German,
French, Italian, Spanish.
The system input voltage: Range 120/208/240 Vac.
The system output voltage. Range: 120/208/220/230/240 Vac.
The system output frequency. Range: 50/60 Hz.
CAUTION!:
of equipment connected to the UPS: Be sure that the new frequency is
suitable for the connected equipment.
The frequency tracking range (in which the output converter frequency will follow
the bypass frequency). Range: 2/4/6 %.
If the bypass frequency is beyond the setting, the output converter will return to the
fixed crystal controlled frequency.
Changing of the output frequency can cause severe damage
3///2&.63(('
1250$/
%$77(5<&$3$&,7<
The frequency tracking speed range (in which the output converter frequency will
follow the bypass frequency).
Range: NORMAL (1Hz/sec), HIGH (5Hz/sec).
Battery capacity. Range: 7 through 590 Ah, in 1 Ah steps.
$K
)$1&859(
12/2$'6+87'2:1
<(6
LX: OPM_LPA_11U_5K0_10K_1US_V021
The fan speed. Range: 0 / 1. Proper setting optimizes the cooling capacity of the
fans installed.
of the power semiconductors.
Setting ‘YES’ means that the function is activated: the UPS will switch off during a
utility failure when the load is less than 2% of the maximum load. Range: YES/NO.
NOTE:
available. In this case do not activate this function: its setting should read "NO".
WARNING!
condition (as a result of a deep battery test) is lost. For more info see
section 5.4.3 'Deep Battery Test'.
DO NOT READJUST
if the LanPro
If you proceed, the information about the actual battery
! Incorrect setting may lead to reduced lifetime
®
-U operates in parallel the no-load shutdown function is not
29
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 31
g
GE Digital Energy
$8720$7,&%<3$66
(1$%/('
6(59,&(:$51,1*
',6$%/('
Controls functioning of the automatic bypass switch. Range:
ENABLED/DISABLED. If the UPS is used as a frequency converter you may
change the setting to ‘DISABLED’. Bypass operation will then be inhibited and all
alarms related to ‘bypass out of limits’ are suppressed.
The system can prompt for service to a user defined schedule.
Range: 8/12/16/20/24/28 months or DISABLED.
5.4Test Screens
These screens show the test procedure, either started from the service menu (front panel keys) or via the UPS
monitoring software (RS232/SNMP). The upper line indicates the kind of test, the second line its status.
Upper lines:second line:
*(1(5$/6<67(0
*(1(5$/6<67(07(6767$57
*(1(5$/6<67(0*(1(5$/6<67(0
48,&.%$77(5<
48,&.%$77(5<7(67$&7,9$7('
48,&.%$77(5<48,&.%$77(5<
&$/,%5$7(%$7
&$/,%5$7(%$77(6768&&(6)8/
&$/,%5$7(%$7&$/,%5$7(%$7
%<3$66
%<3$667(67)$,/('
%<3$66%<3$66
5.4.1 Battery Test, general
Automatic test
and the wiring are able to support power failures. The tests do not cause any interruption in the functioning of the
unit.
Manual test
-either through an interface kit, via the RS232 or SNMP Interface Port (please refer to the manual of your
-via the front panel: see below
: Every 500 operating hours the UPS conducts automatic battery tests to ensure that the batteries
: A manual battery test can be activated
interface package), or
7(6767$57
7(6767$577(6767$57
7(67$&7,9$7('
7(67$&7,9$7('7(67$&7,9$7('
7(6768&&(6)8/
7(6768&&(6)8/7(6768&&(6)8/
7(67)$,/('
7(67)$,/('7(67)$,/('
the test will start soon
the test is running
the test has been completed succesfully
the test has not been completed succesfully
5.4.2 Quick Battery Test
From the standard menu first enter the service menu (press the 'down' and 'enter/reset' keys simultaneously, then
press the 'down' key until the following screen appears:
48,&.%$77(5<
7(6735(66(17(5
The enter/reset key confirms the selection, and the screen shows:
48,&.%$77(5<
7(6767$57
The test status (indicated by the second line) can be:
7(67$&7,9$7('
7(67$&7,9$7('
7(67$&7,9$7('7(67$&7,9$7('
7(6768&&(66)8/
7(6768&&(66)8/
7(6768&&(66)8/7(6768&&(66)8/
7(67)$,/('
7(67)$,/('
7(67)$,/('7(67)$,/('
127$9$,/$%/(
127$9$,/$%/(
127$9$,/$%/(127$9$,/$%/(
If the batteries are dangerously close to being worn out, a low priority alarm 'replace battery' will be generated. The
batteries must be replaced as soon as possible (see section 8.3).
NOTE: If the manual test is started immediately after installation or after a power failure, the UPS may generate a
false 'replace battery' alarm as the batteries have been (partly) discharged during transport/storage or during the
power failure.
=testing
=battery has been tested with positive result
=the batteries should be replaced
=battery capacity too low to start the test
LX: OPM_LPA_11U_5K0_10K_1US_V021
30
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 32
g
S
5.4.3 Deep Battery Test
The runtime as shown on the LCD screen is calculated, and the value is initially based on the capacity of new
batteries. As batteries age, their capacity deteriorates, and as a result the initial battery capacity may be too
unreliable for a proper runtime prediction. The UPS is able to keep track of the aging process, if a 'deep battery test'
(battery calibration test) is executed regularly. During such a test the condition of the batteries is tested, and the
result of the test is stored, and used by the UPS system for future runtime calculations.
We advise performing a deep battery test on a regular basis. For accuracy reasons the interval should depend on
the number of discharges . With one discharge per month a 6 month interval is sufficient. If the discharge interval is
shorter than once a week a monthly deep battery test is advised.
A deep battery test can be started only if the following conditions are met:
- The load should be more than 30% of nominal load
- The batteries should be fully charged (100% on screen)
- There are no alarms at the time the test is started.
GE Digital Energy
Procedure
From the standard menu first enter the service menu (press the 'down' and 'enter/reset' keys simultaneously for 2
seconds). Subsequently press the 'down' key until the following screen appears:
:
&$/,%5$7(%$7
UHVV'2:1(17(5
Press the keys ‘down’ (2) + 'enter/reset' (3) simultaneously, for at least 1 second.
The following screen appears:
&$/,%5$7(%$7
7(67$&7,9$7('
The test is executed, this may take a few minutes with standard battery and full load. Partial load and/or batt.
extension packs can lengthen the test period considerably. Do not change the load during the test, i.e. do not switch
off or on connected equipment!
The deep battery test discharges the batteries to 'battery low' alarm level (see section 5.3.2 'battery low'). Please
note that immediately after a deep battery test the expected run time is very short: allow the UPS to recharge its
batteries.
After the test the second line informs about the result:
7(6768&&(6)8/
7(6768&&(6)8/
7(6768&&(6)8/7(6768&&(6)8/
7(67)$,/('
7(67)$,/('
7(67)$,/('7(67)$,/('
=The test has been completed succesfully
=The test could not be executed properly: not all test conditions were fulfilled.
UPS system was not informed about the actual battery condition!
The
LX: OPM_LPA_11U_5K0_10K_1US_V021
31
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 33
g
5.5Other Features
5.5.1 Shutdown
GE Digital Energy
'Remote shutdown'
controlled shutdown of the system. Subsequently the UPS will remain off for at least a few seconds (see also 6.1).
LED '
operation
'No-load shutdown'
more than 10 minutes. For more information see section 5.3.2, message 'SHUTDOWN ALARM'.
NOTE
: If the LanPro
'Emergency shutdown'
5.5.2 Mains start
The UPS is able to start, even if the batteries are not connected. Alarm messages 'BATTERY FUSE FAILURE' and
'BATTERY DEPLETED' will be shown. The run time is zero.
5.5.3 Sleep and wake-up
GE Digital Energy UPS monitoring software allows you to program a 'sleep period' of the UPS by sending two
commands to the UPS:
- shut down after # minutes, and subsequently:
- shut down during # hours.
After the first command the following screen appears:
352*6+87'2:1
:,7+,1
: Using communication capabilities, the computer can direct the UPS to turn itself off following
' will blink green. The unit will start up again as soon as the utility returns.
: The UPS will also switch off if the load is < 2% of the maximum load, and the input is absent for
®
-U UPS operates in parallel, the no-load function is not available.
: for more information see section 5.3.2, message 'IMMEDIATE SHUTDOWN'.
During the sleep period the output voltage is no longer available. LED
'operation' blinks green, and the LCD screen shows the time left until restart:
352*6+87'2:1
/()7
The sleep period can be cancelled by either turning the UPS ON/OFF switch (6) off for a few seconds or by sending
the appropriate command via the RS232/SNMP port.
5.5.4 Overload protection in bypass mode
The LanPro
the UPS will switch to bypass operation, and subsequently the bypass input fuse on the front panel will trip. The
capacity of the bypass fuse allows it to handle the inrush currents of the equipment connected to the UPS. The fuse
will only trip after more than an hour at an input current of 40Amp (L5/6-11U) or 50Amp(L8-11U) or 63Amp (L1011U).
In order to protect the UPS system the software will cut off the abnormal current:
Between 36-49Amp(L5/6-11U), 55-65Amp (L8-11U), 70-81Amp(L10-11U) the time is inversely proportional to the
input current. We advise to place a distribution fuse slow blow type between UPS input and the utility supply. Please
refer to the installation drawing.
®
-U will protect itself in case of overload. Upon an overload which is caused by abnormal circumstances
in 10 minutes:in 1 minute:
If a utility failure occurs during the sleep period and the battery voltage
eventually drops below 200Vdc, the UPS will automatically switch off in order to
save battery power. When the main returns the UPS will start up automatically.
The programmed sleep time however is lost.
LX: OPM_LPA_11U_5K0_10K_1US_V021
32
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 34
g
5.5.5ECO-mode
®
The LanPro
utility through the electronic bypass switch. If the utility is interrupted or out of limits the load is automatically
transferred to the inverter. Operating the load on utility improves the efficiency of the UPS with 5-8% and saves on
energy costs. We advise not to use the ECO-mode in case of an unstable utility.
-U UPS is equipped with the ‘ECO-mode’ feature. If the feature is enabled, the load is operated on
GE Digital Energy
After enabling the ECO-mode (please refer to service screens 5.3.3) the
standard menu
changes to:
/$13528
/2$'(&2
NOTE:
5.5.6Auto restart
If this feature is enabled and the unit has shut down (e.g. due to overload) the UPS will start up automatically when
the normal situation is restored. The off-factory setting is: enabled.
If the auto restart feature is disabled the unit will not automatically restart when the normal situation is restored but
the display will show:
If LanPro
®
-U units operate in parallel, the ECO-mode feature is not available.
$8725(67$572))
35(66(17(5
After ‘Enter’ the unit will restart. See also 5.3.3 ‘service screens’.
5.5.7Superior Battery Management
Load dependent battery-end voltage:
-
the higher the current, the lower the 'end-of-discharge' battery voltage. This gives maximum capacity without
over discharging. Over discharging results in failure to recover normal capacity and in shortened battery life.
Equalize mode:
-
hours in order to equalize all battery voltages.
Boost mode:
-
with a boost charge voltage of 285Vdc. This enables fast recharging of the batteries. The programmed
battery charging mode will change from boost charge into float charge after boost charging twice.
Temperature compensated battery charging:
-
increasing temperature (-18mV/°C or -32.4mV/°F per 12V battery). As a result poor charging of the batteries
under low temperature conditions and overcharging of the batteries under high temperature conditions are
prevented.
When switched on for the first time the UPS will start boost-charging the batteries for 15
If after a discharge the battery voltage is lower than 240Vdc, the UPS will charge the batteries
The allowable final battery voltage depends on the discharge current:
This feature reduces the battery charge voltage with
LX: OPM_LPA_11U_5K0_10K_1US_V021
33
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 35
g
GE Digital Energy
6 - Interfacing Features
The UPS is equipped with 3 ‘option slots’ (rear panel, 12-14). In the most left slot (12) an RS232/contact interface
card is factory installed. See 5.1. In the middle slot (13) additional Relay or SNMP plug-in Cards can be installed.
The most right slot (14) allows easy installation of an RPA plug–in Card (Redundant Parallel Operation).
6.1RS232 / contact interface
The RS232/Contact interface (9-pole, sub D, rear panel, 12a) enables advanced communication between the
UPS and e.g. a personal computer. An interface kit (cable and software) is delivered with the UPS. The software
supports most common operating systems incl. Novell, UNIX, VMS, Windows 3 - 95/98/2000 - NT, IBM OS/2,
LINUX, has a modular and layered architecture and works for all degrees of network complexity: stand-alone,
multi-vendor networks and large managed networks.
During a power failure the UPS software takes a number of actions: processes are stopped, open files are closed
and unattended systems will be shut down in a controlled way. When the utility power returns, the systems will
automatically start up and will be up and running as soon as possible.
For specific information on GE Digital Energy’s connectivity products please contact your dealer or internet:
www.gedigitalenergy.com.
COMMON
Pin #Function
1Battery low
2Serial data out
3Serial data in / UPS shutdown
4Not used
5Common
6Bypass active
7Plug&Play / RTS
8Utility failure
9General alarm
GENERAL ALARM
MAINS FAILURE
DATA TO UPS
UPS SHUTDOWN
PnP / RTS
DATA FROM UPS
BYPASS ACTIVE
5
9
4
DC
RS232
DC
RS232
DC
RS232
8
3
7
2
6
1
contact interface: Max 48V / 30mA
BATTERY LOW
Fig. 22: RS232 / contact interface
6.2Emergency shutdown
The emergency shutdown connector is located on the RS232/contact interface card (12). Be sure that the UPS is
switched off, and remove the card from the unit*. Remove the wire from connector J3 (pin 3 and 4). Install the wiring
of a normally closed contact to connector J3 (pin 3 and 4). Re-install the RS232 interface card. If during normal
operation of the UPS the contact is opened, the UPS will shut down. To restart the unit, restore the connection and
turn the UPS off and on again.
* If the card is removed during normal operation the UPS will shut down.
6.3Relay Card (optional)
The relay plug-in card can be installed in the middle option slot (rear panel, 13). The card is provided with four
potential free contacts representing: battery low, bypass active, utility failure and general alarm. For more information
please refer to the user manual that comes with the interface card.
6.4SNMP Interface (optional)
This SNMP plug-in card can be installed in the middle option slot (rear panel, 13). The card makes the UPS ‘SNMP
manageable’: it allows the data interface to be connected directly to an Ethernet network (thin coax, twisted pair,
AUI). For more information please refer to the user manual that comes with the interface card. When this option is
installed the RS232 communication link is no longer available.
LX: OPM_LPA_11U_5K0_10K_1US_V021
34
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 36
g
GE Digital Energy
7 - Optional Features
7.1Extended Runtime
Extended runtime versions are equipped with additional separate battery packs to increase the runtime of the unit.
Additional batteries will increase the recharging time for the unit. All other operational information is the same.
If a battery pack is connected, the UPS must be informed about the new total battery capacity to allow a reliable
recalculation of the available run time. Please refer to section 5.3.4 ‘Setup Menu’. Dependent of the charge condition
of the new batteries the new run time calculations may temporarily be unreliable.
Connecting an external charger may cause damage to the UPS. As the batteries are not galvanically separated from
the utility input, the external charger must be galvanically separated from the utility. Using an external charger will
cause a false run time prediction during charging time, the correct run time will be shown 10 hours after reaching
battery float charge. If you are in doubt, contact your dealer.
An option slot (rear panel, 13) allows easy installation of a relay or SNMP plug-in card. See sections 6.3 and 6.4 for
more information.
7.3RPA-Facility (Redundant Parallel Architecture)
Nowadays there are many mission-critical applications that need a fault tolerant, 100 % reliable availability of utility
power. By adding the RPA-facility to the LanPro
RPA-facility allows to connect 2, 3 or 4 units in parallel.
Connecting GE Digital EnergyLanPro
Redundancy
By connecting units in parallel, using the N+x system, a redundant system can be created. In this case all the
UPSs equally share the load in the system during normal operation. In this way every possible single point of
failure will be eliminated. This means that if one of the UPSs in the parallel system fails, the other(s) can still
supply the load guaranteeing full protection without any interruption.
Scalability:
Another reason for paralleling units is upgrading the power rating of the system. If e.g. a 5kVA LanPro
installed, the power rating can be upgraded to 10kVA by adding another 5kVA LanPro
investment makes sure that you don’t have to invest in advance, but only when you need to.
GE Digital Energy’s unique RPA system has the following major advantages:
•GE Digital Energy’s RPA offers true redundancy because not only the power electronics are redundant, but
also the batteries, the bypass circuit and the control logic,
•The RPA system is an option: you don’t have to buy it if you don’t need it.
: To achieve the highest possible level of power protection in a fault-tolerant network.
To add power if needed without investments beforehand.
®
®
-U (rear panel, 14), highest standards for reliability can be met. The
-U units in parallel is attractive for several reasons.
®
-U in parallel. This spread
®
-U is
LX: OPM_LPA_11U_5K0_10K_1US_V021
35
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 37
g
7.4PDM: Power Distribution Module
GE Digital Energy
This Power Distribution Module (PDM) contains 4 x Nema 5-20R, 2 x Nema L6-30R and 1 x Nema L14-30 R
Power sockets (see fig. 23). The PDM replaces the conduit box (17), and converts the LanPro
pluggable UPS. Only qualified personnel is allowed to install the PDM.
For more information please refer to the user manual that comes with the Power Distribution Module.
A
B
C
B
D
AConnector Nema L14-30R (1)
BTCBs (8)
CConnector Nema L6-30R (2)
DConnector Nema L5-20R (4)
®
-U into a
Fig. 23: Power Distribution Module
7.5Seismic anchors
Seismic anchors can be ordered separately; contact your local dealer.
7.6120Vac Single Phase Option Kit
This kit is required in case of 120Vac single phase output on 8/10kVA models This kit can be ordered separately;
contact your local dealer.
LX: OPM_LPA_11U_5K0_10K_1US_V021
36
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 38
g
GE Digital Energy
8 - Maintenance
8.1General
When used properly, the UPS is virtually maintenance free other than keeping the air inlets/outlets free from dust.
8.2Cooling fan
The expected operational life of the cooling fans is approximately 20,000 to 40,000 hours of continuous operation. A
high ambient temperature will shorten this operational life.
8.3Batteries
The service life of the battery is from 3 to 6 years, depending on the operating temperature and on the number of
discharge cycles.
As a healthy battery is essential to the performance of the UPS, an automatic battery test is performed regularly to
ensure failsafe operation (see section 5.4.1). When the condition of the battery is critical, the warning signal will be
activated (buzzer 1x per 8 secs, and alarm message 'Replace battery', see 5.3.2). The batteries must be replaced
as soon as possible. Please contact your dealer. Use only UL recognised batteries (BAZR2), valve regulated
types.
NOTE: under certain circumstances a
'QUICK BATTERY TEST'.
Regular deep battery tests are advised in order to re-calibrate the capacity of aging batteries. See section 5.4.3 for
more information.
NOTE: All maintenance and service work, including battery replacement, should be performed by qualified
service personnel.
For authorized service personnel only:
Never short the battery terminals. Shorting may cause the battery to burn. Avoid charging in a sealed container.
Proper disposal of batteries is required: refer to your local codes for disposal requirements. Never dispose of
batteries in a fire: they may explode. Never disassemble or reassemble batteries; their contents (electrolyte) may be
extremely toxic. If exposed to electrolyte, wash immeditately with plenty of water, if eye contact occurs flush with
water and contact a physician.
manual
battery test can result in a false alarm: please see section 5.4.2
8.4Safety
CAUTION:
When the
high voltages are present on all internal parts, including the battery. Even after disconnection from the
utility, all parts inside the
RS232 output).
For your safety, only authorized service personnel may remove the cabinet cover.
LanPro
®
-U
UPS is operating, all parts of the electronics are directly connected to the utility and
®
LanPro
-U
UPS, including the battery, conduct dangerous voltages (except the
8.5Storage
Always store the UPS in a dry location with the batteries in a fully charged state, storage temperature must be within
-20 and +45°C. Storing the unit for a period exceeding 3 months can reduce the life of the batteries. To maintain
their normal life expectancy, the batteries must be recharged periodically:
-if the storage temperature is within -20 and +30°C (-4°F and 86°F): every 6 months, for 24 hours,
-if the storage temperature is within -20 and +45°C (-4°F and 113°F): every 4 months, for 24 hours.
LX: OPM_LPA_11U_5K0_10K_1US_V021
37
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 39
g
GE Digital Energy
9 - Troubleshooting
Whenever a malfunction occurs, first check external factors (e.g connections, temperature, humidity or load) to
determine whether the problem is caused by the unit itself or by its environment. Subsequently check whether the
breakers/switches on the rear panel (fig. 19, 7-8-9) are in ‘on’ position. Always check these external factors before
concluding that your LanPro
The front screen will indicate the problem and solution (if the problem is due to environmental circumstances). If the
solution is not shown on the screen, please contact your dealer.
During the self-test, performed immediately after start-up, the UPS may detect a system failure. In this case a
message is displayed for 30 seconds before the self-test is repeated. If the faulty situation persists, please contact
your dealer.
(One of) the following messages can be displayed:
®
-U UPS is faulty.
6(/)7(67)$,/85(
3&%32:(56833/<
6(/)7(67)$,/85(
$&21,1387
6(/)7(67)$,/85(
,17%$77(5<)86(
6(/)7(67)$,/85(
(;7%$77(5<)86(
6(/)7(67)$,/85(
%$77(5<&+$5*(5
6(/)7(67)$,/85(
8LF722+,*+
6(/)7(67)$,/85(
7(03722+,*+
6(/)7(67)$,/85(
8ED722/2:
One or more voltages of the internal power supply is (are) outside tolerance.
Please contact your dealer
An external AC voltage (not the UPSs output voltage) was detected on the
output terminals. Please contact your dealer.
The internal battery fuse is defective. Please contact your dealer.
The battery extension circuit breaker is in 'the off' position. Please switch it to
'the on' position.
Malfunction of the battery charger. Please contact your dealer.
Malfunction of the input circuit: voltage delivered is too high. Please contact your
dealer.
The temperature of (one of) the components is (still) too high. See section
5.3.2.
The battery voltage is too low to allow start-up. Wait for a few hours, leave the
UPS switched on.*
.
6(/)7(67)$,/85(
8LF722/2:
6(/)7(67)$,/85(
41272.
* If absence of input power (utility failure, maintenance work) is expected to last longer than a few hours, switch off
the UPS to save battery power. If the UPS input power is absent for several days and the UPS remains on under noload conditions, the batteries can be discharged very deeply, resulting in a short battery life time.
LX: OPM_LPA_11U_5K0_10K_1US_V021
Malfunction of input circuit: voltage delivered is too low. The batteries may be
faulty or depleted. Wait for a few hours, leave the UPS switched on.*
Hardware output voltage detection 'Q4' is active. Please contact your dealer.
38
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 40
g
GE Digital Energy
10 - Specifications
UPS Type:L5-11UL6-11UL8-11UL10-11U
Output power (kVA/kW):5/46/4.88/6.410/8
AC input voltage:120/208/240 Vac (120V only with step-up transformer for L5/6-11U)
Input frequency:60/50 Hz
AC output voltage:120/208/220/230/240V
Output frequency:60 or 50 Hz, std. 60 Hz; selectable on front
System efficiency (full load):87%
Line input breaker (C-type):32A32A50A63A
Bypass input breaker (C-type):32A32A50A63A
Battery safety fuse (F4A):30A30A30A30A
Battery safety fuse (F4B):30A (spare)30A (spare) 30A30A
Internal safety fuse (F5A):--30A30A
Internal safety fuse (F5B):30A30A30A30A
Input/output connectors:terminals at rear of unit
INPUT
AC input voltage range (208V-240V)
at 100% load:162 - 285 V
at 50% load:146 - 285 V
at 20% load:133 - 285 V
AC input voltage range (120V, L5/6-11U)
at 100% load:81 - 141 V
at 50% load:72 - 141 V
at 20% load:66 - 141 V
Input frequency range:40-70 Hz
Input current wave form:sinusoidal
Input power factor:≥ 0.99
Max. input current at 100% load 120V :43.3A50.8An.a.n.a.
Inrush current:none
Rectified DC voltage out:380 V
208V :25.0A30.0A40.550.3
240V :21.4A25.134.842.0
BATTERY CHARGER
Characteristic:U/I-characteristic, constant current charging until boost/float voltage, then
DC input voltage range:350-450 V
DC output voltage at 20 °C:float: 273 V boost: 295 V
Output current limit (Adc):2.02.03.03.0
OUTPUT CONVERTER
Output power at pf. = 0.8, VA*:50006000800010000
Semiconductor:IGBT
AC output voltage:120/208/240V ± 1% static resistive load
Output frequency:60 or 50 Hz selectable, ± 0.1%, unless synchronized with the utility
Freq. tracking range:± 2/4/6% of nominal, user selectable
Output wave form:sine wave
Max. phase difference input-output:max 7
Harmonic distortion:2% max. with linear load
Power factor range:Any lagging or leading power factor permitted within the specified rating to pf. 0.5
Output derating altitude:Till 1000m no derating
Protection:Automatic shut down (or transfer to bypass, if bypass is available) in case of
The output is protected against connection to the utility supply
* according to EN 50091-1
LX: OPM_LPA_11U_5K0_10K_1US_V021
constant voltage charging and boost charge mode for fast recharging of batteries
120/208/240V ± 2% measured crest load 2.5:1
120/208/240V ± 2% dynamic mean deviation over one half cycle for 100% of
rated load applied or removed
150% ≥ 2 minutes
°
Above 1000m 12.5% per 1000m, max. 4000m
- low/high DC voltage
- overtemperature
- overload / short circuit
39
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Page 41
g
UPS Type:L5-11UL6-11UL8-11UL10-11U
AUTOMATIC BYPASS SWITCH
The automatic switch provides transfer of the load to the utility voltage without any interruption of the supply. The transfer is
initiated by a signal from the output converter protection circuit in case of an overload or high temperature.
When the conditions return to normal the load is automatically transferred back to the output converter. The automatic bypass
switch can be disabled by the end-user.
Bypass voltage limits:-15%, +10% of nominal
Transfer transients:typically 2% mean deviation over one half cycle.
Frequency tracking range:± 2/4/6% of nominal (user selectable)
Slew rate:max. 1Hz/sec or 5Hz/sec (user selectable)
BATTERY
Battery type:Sealed and maintenance free
Nominal voltage (V) / capacity (Ah):12/712/712/1212/12
Number of batteries:20202020
Capacity of standard battery set:7Ah7Ah12Ah12Ah
Battery recharge time:1.5 - 3 hours for 80% capacity
Battery service life:up to 6 years (depending on operating conditions)
Battery discharging:self discharge current ≤ 0.35 mA
discharge end voltage of the battery depending on the actual load
10.5Vdc < 0.2 CA till 9.0 Vdc > 2 CA
When the UPS is in sleeping mode the inverter will be switched off, battery
charger and rectifier are in operation
Runtime in minutes
VA / Watts
1000 / 800:6060120120
2000 / 1600:40406060
3000 / 2400:18184040
5000 / 4000:10102222
6000 / 4800:-81717
8000 / 6400:--1111
10000 / 8000:---8
GE Digital Energy
BATTERY EXTENSION PACKS
Sheet steel cubicle:VSDA1
Dimensions (hxwxd, mm):537x313x590
Dimensions (hxwxd, inch):21.1x12.3x23.2
Battery:240Vdc/7Ah or 240Vdc/14Ah
Weight with battery (Kg):73 or 123
Weight with battery (Lbs):161 or 271
Battery pack A (voltage V / capacity Ah):240/7240/7240/7240/7
Total capacity (Ah):14141919
Typical runtime, 100% / 50% load, min.:25/6021/5022/5016/39
Number of packs required:1111
Battery pack B (voltage V / capacity Ah):240/14240/14240/14240/14
Total capacity (Ah):21212626
Typical runtime, 100% / 50% load, min.:45/9035/7533/7025/57
Number of packs required:1111
1 - BATTERY LOW
6 - BYPASS ACTIVE
2 - SERIAL DATA OUT
7 - PLUG & PLAY / RTS
3 - SERIAL DATA IN / UPS SHUTDOWN
8 - MAINS FAILURE
4 - NOT USED
9 - GENERAL ALARM
5 - COMMON
x
y
4 x M8
w
CASTORS
h
d
CONDUIT BOX
CABLE ENTRY
A
B
POSITION A: FIX UPS TO THE F LOOR
POSITION B: LIFT UPS CASTORS FROM THE FLOOR
LEVELLER
z
L1 L2
Page 46
GE Digital Energy
g
LanPro® 5/6-11U 120V input
MANUAL BYPASS SWITCH
NORMAL: POSITION 1
(LOAD ON UPS)
SERVICE: POSITION 2
(LOAD ON BYPASS)
EARTH
CONNECTION
IS ESSENTIAL
UPS UTILITY
STATIC
BYPASS
ON
OFF
RS232 / CONTACT, SEE BELOW
SNMP CARD OR RELA Y CARD
RPA CARD
PARALLEL OPERATION
1-2 BATTERY
DISCONNECTED
3-4 EMERGENCY
SHUTDOWN
1 - BATTERY LOW
6 - BYPASS ACTIVE
2 - SERIAL DATA OUT
7 - PLUG & PLAY / RTS
3 - SERIAL DATA IN / UPS SHUTDOWN
8 - MAINS FAILURE
4 - NOT USED
9 - GENERAL ALARM
5 - COMMON
INPUT / OUTPUT TERMINALS
BATTERY FUSES
CONTROLS / CIRCUIT B REAKERS
BATTERY PACK CONNECTOR
OPTION SLOTS
RS232 / CONTACT INTE RFACE
SUB-D PINNING
EARTH
CONNECTION
IS ESSENTIAL
INPUT TERMINALS
CONDUIT BOX
CABLE ENTRY
d
h
w
z
y
POSITION A: FIX UPS TO THE FLOOR
POSITION B: LIFT UPS CASTORS FROM THE FLOOR
LEVELLER
4 x M8
CASTORS
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.