GE LanPro 11 U User Manual

g
GE Digital Energy
INSTALLATION / USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY
LanPro 11 U
5/6/8/10 kVA
Manufactured by:
GE Digital Energy
LanPro-U UPS
Technology for the Digital World.
ver. 2.1 US
g
USER MANUAL LanPro 5/6/8/10-11U UPS LX-DOCFile: OPM_LPA_11U_5K0_10K_1US_V021 Software version R2.9
INSTALLATION / USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY
GE Digital Energy
LanPro® 11 U
5/6/8/10kVA
Preface
We thank you for selecting a GE (General Electric) Digital Energy Uninterruptible Power Supply (UPS) and recommend that you read these instructions carefully before installation and start-up of the LanPro
Please keep this manual in a safe place for future reference and carefully read the important safety instructions in chapter 1 before installation of this device.
®
-U UPS.
Tested
GE Digital Energy is committed to quality and individually tests each LanPro®-U UPS to ensure reliable performance for the user. All units have passed GE DE's quality control standards and conform to the tolerances in the enclosed specifications.
About GE Digital Energy
GE Digital Energy is a leading provider of mission critical power equipment, and bridges the gap between the traditional electricity supply and the critical power requirements of today’s businesses. GE designs, develops and delivers extremely reliable and intelligent power solutions, from desktop UPS to self-contained premium power systems which are supported through a global services network.
©
General Electric Digital Energy
subject to change; no liability can be accepted for any error or omission.
®
is a registered trademark of
LanPro
their respective owners.
LX: OPM_LPA_11U_5K0_10K_1US_V021
-U
. All rights reserved; reproduction in whole or in parts without permission prohibited. This manual may be
GE Digital Energy
. Trademarks of other companies used in this document are registered trademarks of
1
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
CONTENTS
GE Digital Energy
1 IMPORTANT SAFETY INSTRUCTIONS ..................................... 4
1.1 Save these instructions
1.2 General
1.3 Installation
1.4 Storage
1.5 Batteries
2 INTRODUCTION ......................................................................... 5
3 FUNCTIONAL EXPLANATION .................................................... 6
3.1 Principles of Operation
3.2 Normal Conditions
3.3 Utility Failure
3.4 Automatic Bypass Switch
3.5 Manual Bypass Switch
4 INSTALLATION ............................................................................ 8
4.1 Unpacking
4.2 Package Contents
4.3 Location
4.4 Installation
4.4.1 Installation Procedures
4.4.1.1 Standard installation procedure: Vin 208-240Vac, Vout 120/208/220/230/240Vac
4.4.1.2 Installation procedure: Vin 120Vac (optional 5/6kVA), Vout 120/208/220/230/240Vac
4.4.2 Available input voltages: hardware modifications
4.4.2.1 Input voltage 208 or 240Vac
4.4.2.2 Input voltage 120Vac (optional, 5/6kVA only)
4.4.3 Available output voltages: hardware modifications
4.4.3.1 Output voltage 208Vac
4.4.3.2 Output volatge 120Vac split-phase
4.4.3.3 Output voltage 220/230/240Vac
4.4.3.4 Output voltage 120Vac single phase
4.4.4 Input / output voltages: Software modification
4.4.5 Installation of GE DE LanPro battery extension pack(s)
4.4.6 LanPro-11U series: 2 / 3 / 4 parallel operating units – additional info
4.4.6.1 Notes concerning installation of a parallel system
4.4.6.2 Notes concerning starting up the parallel system
4.4.6.3 Notes concerning use / maintenance of a parallel system
5 OPERATION...............................................................................21
5.1 Description of Front and Rear Panel
5.2 Start-up
5.3 Use
5.3.1 Information menu
5.3.2 Status and alarm menu
5.3.3 Service menu
5.3.4 Setup menu
5.4 Test Screens
5.4.1 Battery test, general
5.4.2 Quick battery test
5.4.3 Deep battery test
5.5 Other Features
5.5.1 Shutdown
5.5.2 Mains start
5.5.3 Sleep and wake-up
5.5.4 Overload protection in bypass mode
5.5.5 ECO-Mode 5 5.6 Auto restart
5.5.7 Superior battery management
LX: OPM_LPA_11U_5K0_10K_1US_V021
2
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
GE Digital Energy
6 INTERFACING FEATURES....................................................... 34
6.1 RS232/Contact Interface
6.2 Emergency Shutdown
6.3 Relay Card (optional)
6.4 SNMP Interface (optional)
7 OPTIONAL FEATURES ............................................................. 35
7.1 Extended Runtime
7.2 Plug-in Cards
7.3 RPA-Facility (Redundant Parallel Architecture)
7.4 PDM: Power Distribution Module
7.5 Seismic Anchors
7.6 120Vac Single Phase Option Kit
8 MAINTENANCE .........................................................................37
8.1 General
8.2 Cooling fan
8.3 Batteries
8.4 Safety
8.5 Storage
9 TROUBLESHOOTING ...............................................................38
10 SPECIFICATIONS...................................................................... 39
APPENDIX: INSTALLATION DRAWINGS
LX: OPM_LPA_11U_5K0_10K_1US_V021
3
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
1 - Important Safety Instructions
1.1 Save these instructions
This manual contains important instructions for LanPro®-11U Series UPS, that should be followed during installation and maintenance of the UPS and batteries.
Before attempting to install and start up the UPS, carefully read this manual. Keep this manual next to the UPS for future references.All servicing must be done by qualified personnel. Do not attempt to service the UPS unless you have had proper training.
GE Digital Energy
CAUTION:
While every care has been taken to ensure the completeness and accuracy of this manual, GE Digital Energy assumes no responsibility or liability for any loss or damage resulting from the use
of the information contained in this document. This document shall not be copied nor reproduced without the permission of GE Digital Energy. Due to technical improvements, some of the information contained in this manual may be changed without notice.
By opening or removing covers you run the risk of exposure to dangerous voltages!
1.2 General
CAUTION: RISK OF ELECTRIC SHOCK
­inside. All maintenance and service work should be performed by qualified service personnel. The UPS contains batteries. The appliance outlet may be electrically live, even when the UPS is disconnected from the utility supply. Dangerous voltages may be present during battery operation. The batteries must be disconnected during maintenance or service work.
- The UPS contains potentially hazardous voltages.
- Do not remove fuse F4A or F4B during operation. This can result in a flame arc.
Do not remove the cover, there are no user serviceable parts
1.3 Installation
- This UPS is intended to be used in a controlled environment indoors and free of conductive contaminants.
- The UPS should only be powered from a single phase, three wire AC source equipped with an earth connection.
- In this manual "Earth" is represented with two different symbols:
= Field wiring equipment grounding terminal,
= Grounding terminals.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid getting liquids or any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 40°C (104°F). Optimal battery lifetime is obtained if the ambient temperature does not exceed 30°C (86°F).
- It is important that the unit has adequate ventilation. Maintain air movement around and through the unit. Do not block the air vents.
- Avoid placing the unit in direct sunlight or near heat sources.
- Do not plug household appliances such as electric heaters, toasters or vacuum cleaners into the UPS.
- Use insulated copper input and output wiring, rated 90°C (194°F) wire size based on the ampacities given in Tables 310-16 of the Nation Electrical code, ANSI/NFPA 70-1993. Specified in table 2 and table 3.
1.4 Storage
- Store the UPS with its batteries fully charged in a dry location, storage temperature must be within -20°C and +45°C (-4°F and 113°F). If the unit is stored for an extended period of time, the batteries must be recharged periodically, for 24 hours. Connect the unit to the utility and switch it on:
- if the storage temperature is within -20 and +30°C (-4°F and 86°F), recharge the batteries every 6 months.
- if the storage temperature is within -20 and +45°C (-4°F and 113°F), recharge the batteries every 4 months.
1.5 Batteries
NOTE
-
- When replacing the batteries, use only the same number, type and size battery.
- Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal requirements.
LX: OPM_LPA_11U_5K0_10K_1US_V021
: Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries
and the required precautions. Keep unauthorized personnel away from batteries.
®
Preferably for LanPro
LanPro
5/6-11U: Kobe HV7-12 or Panasonic LC-R127R2P
®
8/10-11U: Kobe HV12-12 or Panasonic LC-RA1212P
4
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
CAUTION:
-
CAUTION:
­toxic. If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
CAUTION:
­precautions should be observed when working on batteries:
Remove watches, rings or other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source prior ro connecting or disconnect battery terminals.
Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground.
Never dispose of batteries in a fire. The batteries may explode. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be
A battery can present a risk of electrical shock and high short circuit current. The following
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance.
GE Digital Energy
2 - Introduction
More than ever before, today's advanced electronic equipment, with complex integrated circuits and other sensitive electronics, needs a stable and continuous AC power supply to operate correctly. While the power coming from the wall outlet is often unreliable, a GE Digital Energy LanPro uninterrupted power.
A compact, truly on-line system, the GE Digital Energy LanPro power interference, including complete power failure. A simple and elegant circuit design, together with extensive protection against abnormal operating conditions (e.g. overload, short circuit, overheating), makes the LanPro exceptionally reliable.
The LanPro a result, input and output voltages do not necessarily have to be equal, making the UPS suitable for almost every situation.
®
-U UPS offers complete galvanic isolation of input and output, also when operating in bypass mode. As
®
-U UPS provides the security of completely
®
-U UPS protects your equipment from all forms of
®
-U
All units are standard equipped with a backfeed protection relay.
Figure 1: The
GE Digital Energy LanPro
®
-11U
UPS
LX: OPM_LPA_11U_5K0_10K_1US_V021
5
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
®
®
GE Digital Energy
3 - Functional Explanation
3.1 The Principles of Operation
The LanPro incoming utility power is cut off completely. Energy is stored as Direct Current (DC), while input and output energy must be Alternating Current (AC). Therefore the UPS contains an input converter (AC to DC) and an output converter (DC to AC). (fig.2)
3.2 Normal Conditions
Under normal conditions, energy from the utility is channelled through the input converter, which supplies the output converter and the battery charger. The batteries are kept in a fully charged state, and the output converter synthesizes a completely new AC output sine wave to supply the load (electrical equipment).
®
-U UPS stores electric energy in batteries. This allows the UPS to supply output power even when the
SYSTEM ON/OFF
OUTPUT: PERFECT UPS POWER
MANUAL BYPASS SWITCH
OUTPUT
TRANSFORMER
FRONT PANEL
RFI
FILTER
OUTPUT
OPTION
SLOTS for:
RPA CARD
SNMP CARD
RELAY CARD
std. installed:
RS232/
CONTACT
INTERFACE
INPUT: UTILITY POWER WITH DISTURBANCES
UTILITY
INPUT
FILTER
BYPASS
FILTER
RFI
BACKFEED
PROT.
OPTIONAL
BATTERY
EXTENSION
P.F. = 1
CONVERTER
RECTIFIER
MICRO-PROCESSOR CONTROL
BATTERY
STATIC
BYPASS
OUTPUT
CONVERTER
BATTERY
CHARGER
Figure 2. Block diagram of the
LanPro
-11U
UPS, utility present
3.3 Utility Failure
In the event of a utility power failure (i.e. absent or outside tolerance) the system uses the energy reserve stored in the battery to continue to produce AC power, ensuring unbroken output (fig. 3). No interruption or alteration will ever be noticed in the output power. In the event of an extended utility failure, the output converter will stop when the battery has been discharged. At this point, the UPS is no longer able to power the connected equipment. When the utility is re-established within tolerance, the output converter will be supplied again by the input converter and the batteries will be recharged, making them ready to support future power failures.
SYSTEM
ON/OFF
OUTPUT: PERFECT UPS POWER
MANUAL BYPASS SWITCH
OUTPUT
TRANSFORMER
FRONT PANEL
RFI
FILTER
OUTPUT
OPTION
SLOTS for:
RPA CARD
SNMP CARD
RELAY CARD
std. installed:
RS232/
CONTACT
INTERFACE
NO INPUT: UTILITY FAIL URE
RFI
FILTER
BACKFEED
PROT.
OPTIONAL
BATTERY
EXTENSION
BYPASS
FILTER
P.F. = 1
CONVERTER
RECTIFIER
MICRO-PROCESSOR CONTROL
BATTERY
STATIC
BYPASS
OUTPUT
CONVERTER
BATTERY CHARGER
Figure 3. Block diagram of the
LX: OPM_LPA_11U_5K0_10K_1US_V021
LanPro
6
-11U
UPS, utility failure
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
GE Digital Energy
3.4 Automatic Bypass Switch
If the output converter is unable to deliver the demanded output power because of overload or overtemperature, the automatic bypass switch will automatically transfer the load to the utility. When the situation is corrected the UPS will switch back to normal operation, i.e. the load is tranferred back to the output converter. Though the automatic bypass switch is shown as a simple mechanical switch in figures 2-5, the transfers are done by means of thyristors, i.e. electronically, without any interruption of the power supplied to the load. In case of a severe overload or short-circuit the magnetic bypass circuit breaker (rear panel) may trip in order to protect the UPS. If the current is insufficiently high to trip the breaker, the UPS will be switched off by the software in order to protect the UPS and connected equipment.’
MANUAL BYPASS
SYSTEM
ON/OFF
SWITCH
OUTPUT
TRANSFORMER
FRONT PANEL
RFI
FILTER
OUTPUT
OPTION
SLOTS for:
RPA CARD
SNMP CARD
RELAY CARD
std. installed:
RS232/
CONTACT
INTERFACE
UTILITY
INPUT
RFI
FILTER
BACKFEED
PROT.
OPTIONAL
BATTERY
EXTENSION
BYPASS
FILTER
P.F. = 1
CONVERTER
RECTIFIER
MICRO-PROCESSOR CONTROL
BATTERY
STATIC
BYPASS
OUTPUT
CONVERTER
BATTERY
CHARGER
Figure 4 . Bypass operation: Automatic bypass
If a power failure occurs during bypass operation, load power may be lost. If the UPS functions under overload conditions it may not be able to protect the load.
3.5 Manual Bypass Switch (Service switch)
The system can be bypassed manually using the manual bypass switch located at the rear panel. It is a two-position switch: the normal position is '1': as in figures 2-4. Position '2' is the service position: the load is directly connected to the utility input. This way maintenance of the UPS (e.g. battery replacement, as in fig. 5) is possible without interruption of the power supplied to the load.
CAUTION: REFER SERVICE TO QUALIFIED PERSONNEL ONLY
THE RFI FILTERS AND OUTPUT TRANSFORMER ARE ALWAYS ACTIVE.
BYPASS
UTILITY
INPUT
RFI
FILTER
BACKFEED
PROT.
OPTIONAL
BATTERY
EXTENSION
FILTER
P.F. = 1
CONVERTER
RECTIFIER
MICRO-PROCESSOR CONTROL
STATIC
BYPASS
OUTPUT
CONVERTER
BATTERY
CHARGER
.
MANUAL BYPASS SWITCH
OUTPUT
RFI
FILTER
OUTPUT
SYSTEM
ON/OFF
TRANSFORMER
FRONT PANEL
OPTION
SLOTS for:
RPA CARD
SNMP CARD
RELAY CARD
std. installed:
RS232/
CONTACT
INTERFACE
LX: OPM_LPA_11U_5K0_10K_1US_V021
Figure 5 . Bypass operation: Manual bypass
7
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
GE Digital Energy
4 - Installation
4.1 Unpacking
Cut the two wrapping bands, and remove the shipping box. Loosen the four bolts with which the UPS is fixed to the pallet. Remove the UPS from the pallet. UPS is equipped with castors, that allow easy displacement of the unit. Please take appropriate measures to avoid damage on vulnerable floors.
4.2 Package Contents
The shipping box contains a LanPro safety guide and this manual. If the UPS is equipped with an RPA plug-in card (Redundant Parallel Architecture, right option slot at the rear of the unit) the shipping box also contains a yellow network cable and one bus terminator. Inspect the UPS for damage after unpacking. If any damage is present please notify the carrier and place of purchase immediately.
4.3 Location
Please refer to section 1.3 of ‘IMPORTANT SAFETY INSTRUCTIONS’.
4.4 Installation
BE CAREFUL! HEAVY WEIGHT!
®
-U UPS, a CD-ROM, an RS232 cable, a link (5/6kVA models only, see 4.4.3) a
Never try to lift the unit by yourself! The
IMPORTANT
Before making any connection and switching on the LanPro
The voltage and frequency of your utility supply is 120/208/230/240 Vac and 50 or 60 Hz; from the factory the input and output of the UPS are set to 208 Vac / 60 Hz.
Be sure that the UPS is wired for the present utility voltage. This is indicated on the packaging of the UPS, as well as at the I/O terminals.
Overcurrent protection for the AC circuit is to be provided by others.
UPS model
Operating input voltage
L5-11U 35 30 40 20 25 20 L5-11U /120V 60 40 20 25 20 L6-11U 40 35 50 25 30 25 L6-11U /120V 70 50 25 30 25 L8-11U 60 45 70 35 40 35 L10-11U 70 60 80 40 50 40
:
®
-U UPS, please check the following conditions:
CAUTION: To reduce risk of fire, connect only to a circuit input/output provided with
branch circuit overcurrent protection in accordance with the National Electrical Code, ANSI / NFPA 70, as indicated below:
Input overcurrent protection
(Amps)
120V 208V 240V 120V
Output overcurrent protection
(Max. Amps)
(1 X)
120V
(2X)
208V 240V
Table 1. external input fuse value
Ensure that the total power requirement of the equipment to be protected does not exceed the rated output power of the UPS. (output power for your unit is indicated on the rating label on the rear panel).
When using the 120V split phase outputs make sure that the load per 120V output does not exceed half the rating.
The UPS may only be installed by trained personnel. The UPS must be grounded when in use: Connect the UPS to a single phase, three wire AC source equipped with an earth connection.
LX: OPM_LPA_11U_5K0_10K_1US_V021
8
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
Use insulated copper input and output wiring, rated 90°C derated to 40°C wire size based on the ampacities given in Tables 310-16 of the National Electrical code, ANSI/NFPA 70-1993.
This wiring shall have the following minimum sizes:
INPUT WIRING:
Utility voltage
UPS model 120V 208V 240V
L5-11U 6 AWG 10 AWG 10 AWG L6-11U 4 AWG 8 AWG 10 AWG L8-11U N/A 6 AWG 8 AWG L10-11U N/A 4 AWG 6 AWG
Table 2. Input wiring
OUTPUT WIRING:
Output voltage
UPS model 120V 208V 240V
L5-11U 8 AWG 10 AWG 10 AWG L6-11U 8 AWG 10 AWG 10 AWG L8-11U 6 AWG 8 AWG 8 AWG L10-11U 4 AWG 8 AWG 8 AWG
GE Digital Energy
Table 3. Output wiring
TIGHTENING TORQUE FORCE:
UPS model Tightening torque force
L5/6-11U/120V 22 Lbs/inch All other models 18-20 Lbs/inch
Table 4. Tightening torque force
LX: OPM_LPA_11U_5K0_10K_1US_V021
9
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
®
GE Digital Energy
4.4.1 Installation Procedures
4.4.1.1 Standard installation procedure: input voltage 208-240Vac, output voltage 120/208/220/230/240Vac.
If a battery extension pack is to be installed, please proceed with section 4.4.5. If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.4.6. The numbers between (brackets) refer to figure 19 in section 5.1.
1. Mount the levellers: position A to fix the UPS to the floor, position B to lift the castors from the floor.
A
2. Loosen the screws and remove the conduit box (17) and
B
1
the metal cover plate (11).
3. Make sure that all circuit breakers (7-8-9) are in ‘off’ position (down).
2
UPS UTIL. BYPASS
ON
4. Input/output connection: Lead the input/output cables through the cable inlet. If the cables come from below (recommended for 8kVA and 10kVA models), you can rotate the cable inlet 90 degrees.
OFF
3
Connect the input/output wires to the I/O terminals (11a and 11b). Please refer to section 4.4.2 1 (input) and 4.4.3 (output) for detailed information.
L1 L2
5. Re-install the metal cover plate (11) and the conduit box (17).
6. An emergency shutdown switch can be connected to connector J3 on the RS232/Contact Interface Card, between pins 3 and 4. See section 6.2 for more
4
information.
7. For advanced communication possibilities, the RS232/contact interface port (12a) can be connected to a computer system. See section 6.1 for more information.
8. The middle ‘option slot’ (13) allows easy installation of plug-in cards: SNMP Card or Relay Card. See sections
5
6.3 and 6.4 for more information.
9. The right ‘option slot’ (14) allows easy installation of the RPA-card (Redundant Parallel Architecture). If the card is
1-2 BATTERY
DISCONNECTED
3-4 EMERGENCY
SHUTDOWN
6
7
stand-alone,
see 6.3-4
and RPA card
available:
already mounted, and if the unit is intended to be used stand-alone, a bus terminator (delivered with the unit) has to be placed in one of the two bus connectors on the card. If the unit will be part of a parallel system, see sections
4.4.6 and 7.3 for more information.
10. Connect the utility power to the UPS.
11. If hardware modifications were necessary in step 4 because the I/O voltages are different from the default
8
9
see 4.4.6 / 7.3
(208Vac), software modifications should be performed as well. Proceed with 4.4.4.
Figure 6.
LanPro
5/68/10-11U:
Standard installation procedure
LX: OPM_LPA_11U_5K0_10K_1US_V021
12. For a quick start proceed with section 5.2 ‘Start-up’.
10
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
®
4.4.1.2 Installation procedure: input voltage 120Vac (optional, 5-6kVA only), output voltage 120/208/220/230/240Vac.
If a battery extension pack is to be installed, please proceed with section 4.4.5. If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.4.6. The numbers between (brackets) refer to figure 19 and 20 in section 5.1.
1. Mount the levellers: position A to fix the UPS to the floor, position B to lift the castors from the floor. Please refer to figure 6, step 1.
2. Loosen the screws and remove the conduit boxes (17, 2x) and the cover plate (11).
GE Digital Energy
2
3. Make sure that all circuit breakers (7-8-9) are in ‘off’ position (down). Please refer to fig. 6, step 3.
4. Input/output connection: Lead the input/output cables through the cable inlet. If the cables come from below (recommended for 8kVA and 10kVA models), you can rotate the cable inlet 90 degrees.
LN
Connect the input wires to the input terminals (11b). Connect the output wires to the output terminals (11a). Please refer to section 4.4.2.2 (input) and 4.4.3 (output) for detailed information.
5. Re-install the cover plate (11) and the conduit boxes (17,
4
2x).
6. An emergency shutdown switch can be connected to connector J3 on the RS232/Contact Interface Card, between pins 3 and 4. See section 6.2 for more information.
7. For advanced communication possibilities, the RS232/contact interface port (12a) can be connected to a computer system. See section 6.1 for more information.
8. The middle ‘option slot’ (13) allows easy installation of
5
plug-in cards: SNMP Card or Relay Card. See sections
6.3 and 6.4 for more information.
1-2 BATTERY
DISCONNECTED
3-4 EMERGENCY
SHUTDOWN
7
6
stand-alone,
and RPA card
8
9
Figure 7.
see 6.3-4
see 4.4.6 / 7.3
LanPro
5/6-11U:
Installation procedure 120V input
LX: OPM_LPA_11U_5K0_10K_1US_V021
avai lable:
9. The right ‘option slot’ (14) allows easy installation of the RPA-card (Redundant Parallel Architecture). If the card is already mounted, and if the unit is intended to be used stand-alone, a bus terminator (delivered with the unit) has to be placed in one of the two bus connectors on the card. If the unit will be part of a parallel system, see sections
4.4.6 and 7.3 for more information.
10. Connect the utility power to the UPS.
11. If hardware modifications were necessary in step 4 because the output voltage is different from the default (208Vac), software modifications should be performed as well. Proceed with 4.4.4.
12. For a quick start proceed with section 5.2 ‘Start-up’.
11
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
®
®
GE Digital Energy
4.4.2 Available input voltages: hardware modifications
The following input voltages are possible: 208, 240 Vac (see 4.4.2.1) and 120 Vac (see 4.4.2.2)
4.4.2.1 Input voltage 208 or 240Vac.
1. Input voltage is 208 Vac. This is the factory setting. Proceed with step 3.
2. Input voltage is 240Vac. In this case the bypass tap on the output transformer must be changed. Please refer to fig. 8 and 8a. Proceed as follows:
2.1 Remove the blue wire B from faston 74 (connect) and place this wire on faston 72 (park).
2.2 Remove the yellow wire A from faston 61 (park) and place this wire on faston 74 (connect).
Bypass tap factory setting: 208 Volt
PCB1113-D
(park) (park)
(connect)
61 72 74 73
To manual bypass switch
T1
A
B
14
Bypass tap changed to 240 Volt
PCB1113-D
(park) (park)
(connect)
Figure 8
61 72 74 73
To manual bypass switch
. LanPro
5/6/8/10-11U:
Bypass tap change
T1
A
B
14
Figure 8a.
61
72 74 73
LanPro
65 66 67
5/6/8/10-11U:
Rear view
3. Connect the utility supply wires to terminals 6 (L1), 7 (L2) and 8 (equipment grounding conductor). See figure 9. Ground connection is essential! If a neutral wire is part of the site wiring provided, we suggest to isolate this wire for future use or other applications.
gnd
L1
gnd
L2N
1 23
45 67 8
Figure 9. LanPro 5/6/8/10-11U:
Input/output terminals
4. For the output voltage proceed with 4.4.3.
LX: OPM_LPA_11U_5K0_10K_1US_V021
12
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
g
®
®
4.4.2.2 Input voltage 120Vac (optional, 5/6kVA only).
®
LanPro
input voltage of 120Vac.
1. Connect the utility supply wires to terminals L, N and GND (equipment grounding conductor). See figure 10.
-U UPS equipped with an (optional) step-up transformer (5/6kVA models only) can be connected to an
Ground connection is essential!
gnd
NL
GE Digital Energy
Figure 10.
120Vac Input terminals
2. For the output voltage proceed with 4.4.3.
4.4.3 Available output voltages: hardware modifications
The off-factory setting is 208 Vac: a link is placed between terminals 2 and 3. An extra link was delivered with the unit (in a plastic bag) to enable other output voltages (5/6kVA models only). The following voltages are available: 120, 208, 220, 230, 240 Vac.
4.4.3.1 Output voltage 208Vac
This is the off-factory setting. There is a link between terminal 2 and 3.
1. Connect the output wires to the terminals 1 (L1) and 4 (L2).
2. Connect the ground wire to terminal 5. Ground connection is essential! See figure 11.
LanPro
5/6-11U:
gnd
L1
gnd
L2N
1 23
208V
Figure 11.
208 Vac output connection
3. Return to either 4.4.1.1 step 5 or 4.4.1.2 step 5
LX: OPM_LPA_11U_5K0_10K_1US_V021
45 67 8
LanPro
5/6/8/10-11U:
13
GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)
Loading...
+ 32 hidden pages