GE Kilsen KFP-CF2, Kilsen KFP-CF4, Kilsen KFP-CF8 Installation Manual

Page 1
GE
Security
P/N 501-415103-1-10 • REV 1.0 • ISS 03MAY09
Kilsen KFP-CF Series Installation Manual
Page 2
Copyright
This document may not be copied in whole or in part or otherwise reproduced without prior written consent from GE Security, Inc., except where specifically permitted under US and international copyright law.
Disclaimer
The information in this document is subject to change without notice. GE Security, Inc. (“GE Security”) assumes no responsibility for inaccuracies or
omissions and specifically disclaims any liabilities, losses, or risks, personal or otherwise, incurred as a consequence, directly or indirectly, of the use or application of any of the contents of this document. For the latest documentation, contact your local supplier or visit us online at www.gesecurity.eu.
This publication may contain examples of screen captures and reports used in daily operations. Examples may include fictitious names of individuals and companies. Any similarity to names and addresses of actual businesses or persons is entirely coincidental.
Trademarks and patents
GE and the GE monogram are trademarks of General Electric Company. CleanMe and the Kilsen KFP-CF Series name and logo are trademarks of GE Security.
Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products.
Intended use
Use this product only for the purpose it was designed for; refer to the data sheet and user documentation for details. For the latest product information, contact your local supplier or visit us online at www.gesecurity.eu.
Certification and compliance
European Union directives
2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as
unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info.
2004/108/EC (EMC directive): Non-European manufacturers must designate an authorized
representative in the Community. Our authorized manufacturing representative is:
GE Security B.V., Kelvinstraat 7, 6003 DH Weert, The Netherlands.
2006/66/EC (battery directive): This product contains a battery that cannot be disposed of as
unsorted municipal waste in the European Union. See the product documentation for specific battery information. The battery is marked with this symbol, which may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg). For proper recycling, return the battery to your supplier or to a designated collection point. For more information see: www.recyclethis.info.
Contact information
For contact information see our Web site: www.gesecurity.eu.
Page 3
Kilsen KFP-CF Series Installation Manual i
Content
Important information ii
Chapter 1 Introduction 1
Product range 2 Product compatibility 2 Operating modes 2
Chapter 2 Installation 3
Cabinet layout 4 Cabinet installation 6 Connections 8
Chapter 3 Configuration and commissioning 15
The user interface 16 Access levels and passwords 18 Configuration overview 20 Basic configuration 24 Advanced configuration 31 Expansion module configuration 39 Commissioning 42
Chapter 4 Maintenance 45
Fire alarm system maintenance 46 Battery maintenance 47
Chapter 5 Technical specifications 49
Appendix A Configura
tion presets 59
Operating mode presets 60 Expansion module presets 66
Appendix B Product compliance 69
Page 4
ii Kilsen KFP-CF Series Installation Manual
Important information
This is the installation manual for the Kilsen KFP-CF series conventional fire control panels. Read these instructions and all related documentation entirely before installing or operating this product.
Limitation of liability
Installation in accordance with this manual, applicable codes, and the instructions of the authority having jurisdiction is mandatory. GE Security shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of GE Security products beyond the cost of repair or replacement of any defective products. GE Security reserves the right to make product improvements and change product specifications at any time.
While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents, GE Security assumes no responsibility for errors or omissions.
Page 5
Kilsen KFP-CF Series Installation Manual 1
Chapter 1
Introduction
Summary
This chapter provides an introduction to your control panel and the available operating modes.
Content
Product range 2 Product compatibility 2 Operating modes 2
Page 6
Chapter 1: Introduction
2 Kilsen KFP-CF Series Installation Manual
Product range
The KFP-CF series includes the models shown below.
Model Description
KFP-CF2 Two-zone conventional fire alarm control panel
KFP-CF4 Four-zone conventional fire alarm control panel with fire routing
KFP-CF8 Eight-zone conventional fire alarm control panel with fire routing
All models have been designed in accordance with EN 54-2, EN 54-4, BS 5839-1, NBN S21-100, and NEN 2535 standards. For further details, see “Appendix B Product compliance” on page 69.
Product compatibility
For details of compatible products, see the compatibility sheet included with your control panel or consult your local supplier. Compatibility with other products cannot be guaranteed.
Operating modes
Supported operating modes are shown in the table below. The default operating mode is EN 54-2.
Table 1: Operating modes
Operating mode Region
EN 54-2 (default) European Union
EN 54-2 Evacuation European Union (Spain)
EN 54-2 Scandinavia European Union (Scandinavia)
BS 5839-1 United Kingdom
NBN S21-100 Belgium
NEN 2535 The Netherlands
Page 7
Kilsen KFP-CF Series Installation Manual 3
Chapter 2
Installation
Summary
This chapter explains how to install your control panel, and how to connect zones, fire system devices, and the power supply.
WARNING: This product must be installed and maintained by qualified personnel
adhering to the CEN/TS 54-14 standard (or the corresponding national standard) and any other applicable regulations.
Content
Cabinet layout 4
Cabinet layout for two- and four-zone control panels 4
Cabinet layout for eight-zone control panels 5 Cabinet installation 6 Connections 8
Cabling requirements 8
Overview of fire system connections 9
Connecting zones and zone devices 9
Connecting inputs 10
Connecting outputs 11
Connecting the mains power supply 12
Selecting 115 or 230 VAC operation 13
Connecting the batteries 14
Other connections 14
Page 8
Chapter 2: Installation
4 Kilsen KFP-CF Series Installation Manual
Cabinet layout
Cabinet layout for two- and four-zone control panels
Figure 1: Cabinet layout for two- and four-zone control panels
1. Seven-segment display
2. Zone and fire system connectors
3. Cable knockouts
4. Mounting screw knockouts
5. Battery area
6. Key connector
7. Alarm counter connector
8. Power supply unit
9. Power supply connector
10. Battery connector
11. Expansion module connector
12. Cable holder
13. Fuse terminal block
Note: The alarm counter and key connectors are only included on selected regional
models.
Page 9
Chapter 2: Installation
Kilsen KFP-CF Series Installation Manual 5
Cabinet layout for eight-zone control panels
Figure 2: Cabinet layout for eight-zone control panels
1. Seven-segment display
2. Zone and system connectors
3. Cable knockouts
4. Mounting screw knockouts
5. Battery area
6. Power supply unit
7. Key connector
8. Alarm counter connector
9. Fuse terminal block
10. Power supply connector
11. Battery connector
12. Expansion module connector
13. Cable holder
Note: The alarm counter and key connectors are only included on selected regional
models.
Page 10
Chapter 2: Installation
6 Kilsen KFP-CF Series Installation Manual
Cabinet installation
Before you begin
• Remove the front cover
• Remove cable knockouts from the top, bottom, and rear of the cabinet as required
Where to install the cabinet
Make sure the installation location is free from construction dust and debris, and immune to extreme temperature ranges and humidity (see “Chapter 5 Technical specifications” on page 49 for more information on the operating temperature and relative humidity specifications).
Allow for enough floor and wall space so the panel can be installed and serviced without any obstructions. The cabinet should be mounted so that the user interface is at eye level.
Page 11
Chapter 2: Installation
Kilsen KFP-CF Series Installation Manual 7
Fixing the cabinet to the wall
The requirements for nylon wall plugs and screws are shown in the following table.
Model Screws Wall plugs
Two- and four-zone control panels
4 x M4, 30 mm 4 x Ø 6 mm
Eight-zone control panel 5 x M4, 30 mm 5 x Ø 6 mm
Figure 3: Mounting hole locations
Fix the control panel cabinet to the wall as follows:
1. Mark drill points on the wall using the template provided in the product packaging
2. Drill all required holes and insert a 6 mm wall plug into each.
3. Insert screw (1) half way and hang the cabinet onto this screw.
4. insert screws (2) and tighten.
5. Insert screws (3) and tighten.
6. Tighten screw (1).
Page 12
Chapter 2: Installation
8 Kilsen KFP-CF Series Installation Manual
Connections
WARNING: Do not make any control panel or system connections while the control
panel is connected to the mains power supply.
Cabling requirements
Recommended cable
Recommended cables for your fire system are shown in the table below.
WARNING: Failure to use the recommended cable may impact system performance.
Table 2: Recommended cables
Cable Cable description Maximum cable length
Mains cable 3 x 1.5 mm N/A
Zone circuit cable (mixed zone) Twisted-pair (max. 40 / 500 nF) 2 km
Zone circuit cable (automatic or manual zones)
Twisted-pair (max. 55 / 500 nF) 2 km
Securing cables
Use 20 mm cable glands to ensure clean and secure connections at the control panel cabinet. All cables should be fed through the cable guides in the cabinet housing to eliminate movement.
Page 13
Chapter 2: Installation
Kilsen KFP-CF Series Installation Manual 9
Overview of fire system connections
Figure 4: Overview of fire system connections
Connecting zones and zone devices
Connecting zones
Connect zone wires as shown in Figure 4 above. Line resistance is shown in the table below.
Zone type Line resistance
Mixed (automatic and manual) Max. 40
Automatic Max. 55
Manual Max. 55
Note: The default zone detection settings for each operating mode can be found in
Appendix A “Configuration presets” on page 59. To change the zone detection setting, see “Advanced configuration” on page 31.
Terminating zones
Each zone circuit requires a 4.7 k end-of-line resistor for termination. If a zone is not used, the 4.7 kΩ end-of-line resistor must be installed across the unused zone terminals.
Note: For BS 5839-1 the default zone configuration is active end-of-line and an active
end-of-line module must be installed instead of an end-of-line resistor. Unused zones must be terminated with an active end-of-line module or configured as passive end­of-line and terminated with a 4.7 k end-of-line resistor as described above.
Page 14
Chapter 2: Installation
10 Kilsen KFP-CF Series Installation Manual
Connecting detectors
Connect detectors as shown in Figure 4 on page 9. Each zone circuit can support up to 20 detectors.
Connecting manual call points
Connect manual call points in parallel, as shown in Figure 4 on page 9. Each zone circuit can support up to 32 manual call points.
Manual call points must have a resistance installed in series with the normally open (NO) contact to avoid a short-circuit and to allow the control panel to identify the origin of the alarm (automatic or manual).
The resistance required will depend on the zone type as shown below.
Zone type Manual call point resistance
Mixed 100 Ω per 2 W
Manual 100 Ω to 470 Ω per 2 W
Note: The default zone detection settings for each operating mode can be found in
Appendix A “Configuration presets” on page 59. To change the zone detection setting, see “Advanced configuration” on page 31.
Connecting inputs
Input functionality
Each control panel has two inputs, marked INPUT1 and INPUT2. These circuits are connected as normally open and activated when closed.
The function of INPUT1 is defined by the panel operating mode. See Table 3 below.
Table 3: Input functionality for inputs 1 and 2
Operating mode INPUT1 INPUT2
EN 54-2 Remote reset Delays off
EN 54-2 Evacuation Remote reset Delays off
EN 54-2 Scandinavia Extended fire routing delay Delays off
BS 5839-1 Class change Delays off
NBN S21-100 Remote reset Delays off
NEN 2535 Fire routing inhibit delay Delays off
Note: INPUT1 is not used in two-zone control panels operating EN 54-2 Scandinavia mode.
Connecting inputs
Connect input switches to INPUT1 and INPUT2, as shown in Figure 4 on page 9. The circuit should have a maximum resistance of 100 (including any cable resistance).
Page 15
Chapter 2: Installation
Kilsen KFP-CF Series Installation Manual 11
Connecting outputs
Output functionality
Control panels have the following outputs:
• Two-zone control panels have two outputs, marked OUT1 and OUT2.
• Four- and eight-zone control panels have four outputs, marked OUT1, OUT2, OUT3, and OUT4.
The function of each output is defined by the panel operating mode. See Table 4 below. All outputs are overload protected.
Table 4: Output functionality for outputs 1 to 4
Operating mode OUT1 OUT2 OUT3 OUT4
EN 54-2 Sounders Sounders Sounders Fire routing
EN 54-2 Evacuation Sounders Sounders Sounders Sounders
EN 54-2 Scandinavia Sounders Sounders Sounders Fire routing
BS 5839-1 Sounders Sounders Sounders Sounders
NBN S21-100 Evacuation
sounders
Evacuation sounders
Warning sounders
Warning sounders
NEN 2535 Sounders Sounders Fire routing
(automatic)
Fire routing (manual)
Output termination
All outputs require a 15 k end-of-line resistor for termination. If an output is not used, the 15 kΩ end-of-line resistor must be installed across the unused output terminals.
Output polarity
All outputs are polarity sensitive. Observe polarity or install a 1N4007 diode to avoid inverted activation issues.
Connecting the sounders
Depending on the operating mode, up to four sounder circuits can be connected. See Table 4 above.
The sounder outputs are powered and supply 15 VDC in standby and +24 VDC (nominal value) in alarm.
The maximum current consumption for each sounder circuit is shown
below.
Two- and four-zone control panels 250 mA
Eight-zone control panel 500 mA
The sounder outputs are supervised for short circuit and open circuit.
Page 16
Chapter 2: Installation
12 Kilsen KFP-CF Series Installation Manual
Connecting fire routing equipment
Connect fire routing equipment as shown in the table below.
Operating mode Fire routing (automatic) Fire routing (manual)
EN 54-2 EN 54-2 Scandinavia
OUT4 OUT4
NEN 2535 OUT3 OUT4
The fire routing outputs are supervised for short circuit and open circuit.
Note: Fire routing in EN 54-2 operating modes makes no distinction between
automatic and manual alarms.
Connecting the mains power supply
WARNING: Connect the mains power supply before connecting the batteries.
The control panel can be operated at 110 VAC / 60 Hz or 240 VAC / 50 Hz (+10%/15%).
Mains power should be sourced directly from a separate circuit breaker in the building electrical supply distribution board. This circuit should be clearly marked, have a bipolar disconnect device, and only be used for fire detection equipment.
Feed all mains cables through the appropriate cable knockouts and connect them to the fuse terminal block as shown in Figure 5 below.
Keep mains cables separate from other cabling to avoid potential short circuits and interference. Always secure mains cables to the cabinet to prevent movement.
Figure 5: Connecting the mains power supply
1. Mains fuse
2. Live
3. Earth
4. Neutral
For fuse specifications, see Chapter 5 “Technical specifications” on page 49.
Page 17
Chapter 2: Installation
Kilsen KFP-CF Series Installation Manual 13
Selecting 115 or 230 VAC operation
WARNING: An incorrect power setting can destroy the power supply.
Power switching for 115 or 230 VAC operation is automatic for two- and four-zone control panels and no configuration is required.
For eight-zone control panels, the default power setting is 230 VAC. For 115 VAC operation, use a small screwdriver to change the power setting switch, located on the side of the power supply unit, as shown in Figure 6 below.
WARNING: Always disconnect the control panel from the mains supply before
changing the power setting.
Figure 6: Selecting 115 or 230 VAC operation
Page 18
Chapter 2: Installation
14 Kilsen KFP-CF Series Installation Manual
Connecting the batteries
The control panel requires two 12 V, 7.2 or 12 Ah rechargeable, sealed, lead-acid batteries (see “Compatible batteries” on page 47).
Batteries must be installed in series, at the base of the control panel cabinet. Use the battery lead and bridge provided and connect batteries to the BATT connector on the control panel PCB, as shown below. Polarity must be observed.
Note: If the control panel indicates a Supply Fault, then the batteries may need to be
replaced. See “Battery maintenance” on page 47.
Figure 7: Connecting the batteries
Caution: No other equipment may be connected to the BATT connector.
Other connections
Connecting auxiliary equipment
Connect the auxiliary equipment to 24 AUX as shown in Figure 4 on page 9. The 24 VDC auxiliary output is supervise
d for short circuit and voltage output.
Connecting alarm and fault relays
Connect the alarm and fault equipment to the ALARM and FAULT relays.
Each potential-free relay output will be activated in an alarm or fault situation respectively. The fault relay output is powered when there is no fault.
The maximum contact rating for each relay circuit is 2 A / 30 VDC.
Page 19
Kilsen KFP-CF Series Installation Manual 15
Chapter 3
Configuration and commissioning
Summary
This chapter includes information on how to configure and commission the control panel. Configuration is divided in basic configuration and advanced configuration options.
Content
The user interface 16
User interface for two- and four-zone
control panels 16
User interface for eight-zone control
panels 17 Access levels and passwords 18 Configuration overview 20
Configuration con
trols 20
Common configuration tasks 22
Basic configuration 24
The basic configuration menu 24 Basic default configuration 25 Operating mode 26 Sounder delay 27 Fire routing delay 28 Extended fir
e routing delay 29
Add an expansion module 30
Advanced configuration 31
The advanced configuration
menu 31
Sounder operation during a zone
test 32 Sounder re-sound 33 Sounder synchronization 33 Zone configuration 34 Zone delay 35 Zone type 36 Changing access level passwords 37 Auxiliary 24 V reset 38 Configuration, software, and PCB
identification 38
Expansion module con
figuration 39
Add an expansion module 39 Expansion module con
figuration 39
Commissioning 42
Before commissioning the control
panel 42 Commissioning the control panel 42 Functional tests 44 Response times 44
Page 20
Chapter 3: Configuration and commissioning
16 Kilsen KFP-CF Series Installation Manual
The user interface
User interface for two- and four-zone control panels
Figure 8: User interface for two- and four-zone control panels
1. Zone buttons and LEDs (Z1, Z2, etc.)
2. Supply LED
3. General Fault LED
4. General Fire Alarm LEDs
5. Sounder Fault/Disable/Test button and LED
6. Sounder Delay button and LED
7. Network Fault LED
8. Service Detector LED
9. Expansion I/O Fault/Disabled LED
10. General Disable button and LED
11. General Test button and LED
12. Configuration controls
13. Reset button and LED
14. Panel Silence button and LED
15. Sounder Start/Stop button and LED
16. System Fault LED
17. Out of Service LED
18. Earth Fault LED
19. Supply Fault LED
20. Fire Routing Delay button and LED
21. Fire Routing Start and Fault/Disable/Test button and LEDs
Note: Two-zone control panels do not include fire routing.
Page 21
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 17
User interface for eight-zone control panels
Figure 9: User interface for eight-zone control panels
1. Zone buttons and LEDs (Z1, Z2, etc.)
2. Supply LED
3. General Fault LED
4. General Fire Alarm LEDs
5. Sounder Fault/Disable/Test button and LED
6. Sounder Delay button and LED
7. Network Fault LED
8. Service Detector LED
9. Expansion I/O Fault/Disabled LED
10. General Disable button and LED
11. General Test button and LED
12. Configuration controls
13. Reset button and LED
14. Panel Silence button and LED
15. Sounder Start/Stop button and LED
16. System Fault LED
17. Out of Service LED
18. Earth Fault LED
19. Supply Fault LED
20. Fire Routing Delay button and LED
21. Fire Routing Start and Fault/Disable/Test button and LEDs
Page 22
Chapter 3: Configuration and commissioning
18 Kilsen KFP-CF Series Installation Manual
Access levels and passwords
In accordance with EN 54-2, operation and configuration of this product is restricted by access level.
Configuration tasks described in this chapter can only be performed at access level 3 basic or advanced. Passwords and indications for each access level are described in “Access level passwords and indications” on page 19.
Access level 1
Access level 1 is the default access level and allows basic operational access only, such as responding to a fire alarm or fault warning at the control panel.
Access level 2
Access level 2 allows advanced operational access. It is reserved for authorized users who have been trained to operate the control panel.
Access level 3 basic
Access level 3 basic allows control panel configuration with rapid configuration options for the most common installation requirements. It is reserved for the installation contractors responsible for the fire system installation and configuration, and for authorized maintenance contractors.
Access level 3 advanced
Access level 3 advanced allows control panel configuration with custom configuration options for all installation requirements. It is reserved for the installation contractors responsible for the fire system installation and configuration, and for authorized maintenance contractors.
Page 23
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 19
Access level passwords and indications
The default access level passwords and the corresponding LED and seven-segment display indications are shown in the table below. The seven-segment display is only visible when the control panel cover is removed. See Figure 1 on page 4 and Figure 2 on page 5.
Table 5: Access level passwords and indications
Access level Password LED Default display Custom display
1 None None None None
2 2222 The Reset LED is
steady
None None
3 basic 3333 The Reset LED is
flashing
3 advanced 4444 The Reset LED is
flashing
Note: The seven-segment display will default to the custom display (operating mode
menu) when entering basic or advanced configuration if custom zone delay, zone configuration, or zone type settings have been applied via the advanced configuration menu.
Page 24
Chapter 3: Configuration and commissioning
20 Kilsen KFP-CF Series Installation Manual
Configuration overview
To facilitate rapid configuration of the most common tasks, configuration is divided into basic and advanced configuration levels.
For basic configuration options, see “Basic configuration” on page 24. For advanced configuration options see “Advanced configuration” on page 31.
Configuration controls
The control panel is configured using the front panel configuration controls and the seven-segment display.
The configuration controls
The configuration controls are located on the control panel interface.
Figure 10: Front panel configuration controls
Button Function
1 Scroll to the next configuration menu on the seven-segment display.
2 Scroll to the next configuration value for the active menu on the seven-segment display.
3 Scroll to the previous configuration menu on the seven-segment display.
4 Scroll to the previous configuration value for the active menu on the seven-segment
display.
Enter Confirm a menu selection or a value selection entry.
Note: The configuration controls are also used to enter the access level password.
Page 25
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 21
The seven-segment display
The seven-segment display is only visible when the control panel cover is removed (see Figure 1 on page 4 and Figure 2 on page 5).
Figure 11: The seven-segment display
1. Mode LED
2. Value LED
LED Indications
Select a configuration menu using buttons 1 and 3 when this LED is steady, or Mode
Select a configuration submenu using buttons 1 and 3 when this LED is flashing.
Value Select a configuration value using buttons 2 and 4 when this LED is steady
Page 26
Chapter 3: Configuration and commissioning
22 Kilsen KFP-CF Series Installation Manual
Common configuration tasks
To enter configuration mode:
1. Remove the control panel cover so that the seven-segment display is visible.
2. Enter a valid access level 3 password (3333 for basic configuration or 4444 for advanced configuration).
3. Press Enter.
When first entering configuration mode, the Mode LED on the seven-segment display is steady. For other indications see “Access levels and passwords” on page 18.
To select a menu:
1. Select the required menu using the menu selection buttons (1 and 3).
2. Press Enter.
When a configuration menu has been selected, the Value LED on the seven-segment display is steady.
To select a value:
1. Select the required value using the value selection buttons (2 and 4).
2. Press Enter.
To exit configuration mode and save your changes:
1. Press Panel Silence.
2. Press Enter.
— or —
1. Set the display as shown below, and then press Enter.
The Panel Silence LED flashes to confirm that a configuration change has been applied.
Note: Make all required configuration changes before exiting configuration mode and
saving your changes.
Page 27
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 23
To exit configuration mode without saving your changes:
1. Press Reset
— or —
1. Set the display as shown below, and then press Enter.
The control panel will exit configuration mode after five minutes if no button is pressed.
Visual indications for current value and selected value
Current and selected values are indicated as follows.
Status Indication
Current value Both decimal points on the
display are steady
New selected value Both decimal points on the
display are flashing
Other value Both decimal points on the
display are off
To restore the previous configuration:
1. Set the display as shown below, and then press Enter.
To restore the factory configuration:
1. Set the display as shown below, and then press Enter.
Page 28
Chapter 3: Configuration and commissioning
24 Kilsen KFP-CF Series Installation Manual
Basic configuration
The default password for basic configuration is 3333. After entering the password, the first displayed menu will be Basic default configuration (indicating level 3 basic access) or Operating mode. For more information see “Access level passwords and indications” on page 19.
The basic configuration menu
Configuration options for this menu are shown in the table below. More information for each option is included in the related topic.
Table 6: The basic configuration menu
Display Menu Values Operating mode
Basic default configuration See topic All
Operating mode EN 54-2
EN 54-2 Evacuation EN 54-2 Scandinavia BS 5839-1 NBN S21-100 NEN 2535 Custom
All
Sounder delay 00 to 10 minutes EN 54-2
EN 54-2 Evacuation EN 54-2 Scandinavia NBN S21-100
Fire routing delay 00 to 10 minutes EN 54-2
EN 54-2 Scandinavia NBN S21-100 NEN 2535
Extended fire routing delay 00 to 10 minutes EN 54-2 Scandinavia
NEN 2535
Add an expansion module 00 to 04 modules All
Restore previous configuration N/A All
Restore factory configuration N/A All
Exit without saving N/A All
Exit and save N/A All
Note: Additional menu options are available if one or more expansion modules are
installed. See “Expansion module configuration” on page 39.
Page 29
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 25
Basic default configuration
Use this menu to select common operating mode configuration presets. The default setting is 01 (EN 54-2, passive end-of-line).
To select an operating mode configuration preset:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4).
See Table 7 below for descriptions of the presets.
3. Press Enter.
4. Save your changes.
A selected list of operating mode configuration presets is shown below. For a detailed list of all available configuration presets and characteristics, see Appendix A “Configuration presets” on page 59.
Table 7: Common operating mode configuration presets
Display Operating mode Zone end-of-line Zone type
01 (default) EN 54-2 Passive Mixed
05 EN 54-2 Evacuation Passive Mixed
07 EN 54-2 Scandinavia Passive Mixed
11 BS 5839-1 Active Mixed
21 NBN S21-100 Passive Automatic
31 NEN 2535 Passive Odd zones: Automatic
Even zones: Manual
The operating mode is indicated by the first digit in the display and the configuration type by the second digit. If a custom configuration has been applied (via the advanced configuration menu), then the second digit is a zero, as shown below.
Display Configuration Display Configuration
01 EN 54-2 preset configuration 00 EN 54-2 custom configuration
11 BS 5839-1 preset configuration 10 BS 5839-1 custom configuration
21 NBN S21-100 preset configuration 20 NBN S21-100 custom configuration
31 NEN 2535 preset configuration 30 NEN 2535 custom configuration
Page 30
Chapter 3: Configuration and commissioning
26 Kilsen KFP-CF Series Installation Manual
Operating mode
Use this read-only menu to view the operating mode of the control panel.
To view the operating mode:
1. Set the display as shown below, and then press Enter.
Display indications for each operating mode are shown below.
Display Operating mode
EN 54-2
EN 54-2 Evacuation
EN 54-2 Scandinavia
BS 5839-1
NBN S21-100
NEN 2535
Custom
Custom operating mode
A custom operating mode will be indicated if any of the following zone configuration settings are changed from the operating mode preset values:
• Zone delay
• Zone configuration
• Zone type
Page 31
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 27
Sounder delay
Use this menu to configure a sounder delay of up to 10 minutes in operating modes where the feature is available.
To configure a delay:
1. Set the display as shown below, and then press Enter.
The Sounder Delay LED flashes quickly to indicate that the sounder delay configuration menu is active.
2. Select a delay value from 1 to 10 minutes using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Once configured the delay must be enabled at access level 2.
To enable a configured delay:
1. Exit access level 3.
2. Enter the access level 2 password.
3. Press the Sounder Delay button.
A steady Sounder Delay LED indicates that the delay is enabled.
Default delays
Default sounder delays for each operating mode are shown below.
Operating mode Default delay in minutes
NBN S21-100 01
EN 54-2 EN 54-2 Evacuation EN 54-2 Scandinavia BS 5839-1
00
NEN 2535 This feature is not available in this operating mode.
Delay application logic
Depending on your fire alarm system configuration and the alarm activation device, a configured delay may be overridden.
Delays will only be applied when:
• The configured delay has been enabled.
• The device reporting the fire alarm is a detector installed in a mixed or automatic zone, OR a detector or manual call point installed in an automatic zone.
Page 32
Chapter 3: Configuration and commissioning
28 Kilsen KFP-CF Series Installation Manual
• The zone delay configuration is set to allow delays in the zone reporting the fire alarm. (This is the default configuration.)
If any of the above are not true, then the control panel overrides the configured delay and activates the sounders immediately.
Fire routing delay
Use this menu to configure a fire routing delay of up to 10 minutes in operating modes where the feature is available.
To configure a delay:
1. Set the display as shown below, and then press Enter.
The Fire Routing Delay LED flashes quickly to indicate that the fire routing delay configuration menu is active.
2. Select a delay value from 1 to 10 minutes using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Once configured the delay must be enabled at access level 2.
To enable a configured delay:
1. Exit access level 3.
2. Enter the access level 2 password.
3. Press the Fire Routing Delay button.
A steady Fire Routing Delay LED indicates that the delay is enabled.
Default delays
The default fire routing delay for each operating mode is shown below.
Operating mode Default delay in minutes
EN 54-2 Scandinavia 01
NEN 2535 01
EN 54-2 00
EN 54-2 Evacuation BS 5839-1 NBN S21-100
This feature is not available in these operating modes.
Page 33
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 29
Delay application logic
Depending on your fire alarm system configuration and the alarm activation device, a configured delay may be overridden.
Delays will only be applied when:
• The configured delay has been enabled.
• The device reporting the fire alarm is a detector installed in a mixed or automatic zone OR a detector or manual call point installed in an automatic zone.
• The zone delay configuration is set to allow delays in the zone reporting the fire alarm. (This is the default configuration.)
If any of the above are not true, then the control panel overrides the configured delay and activates the fire routing immediately.
Extended fire routing delay
Use this menu to configure an extended fire routing delay of up to 10 minutes in operating modes where the feature is available.
To configure an extended delay:
1. Set the display as shown below, and then press Enter.
The Fire Routing Delay LED flashes quickly to indicate that the fire routing delay configuration menu is active.
4. Select a delay value from 1 to 10 minutes using the value selection buttons (2 and 4).
This value must be greater than the configured fire routing delay.
5. Press Enter.
6. Save your changes.
Once configured the delay is enabled at the same time as the standard fire routing delay.
A steady Fire Routing Delay LED indicates that the all configured fire routing delays are enabled.
Page 34
Chapter 3: Configuration and commissioning
30 Kilsen KFP-CF Series Installation Manual
Default delays
The default extended fire routing delay for each operating mode is shown below.
Operating mode Default delay in minutes
EN 54-2 Scandinavia 03
NEN 2535 03
EN 54-2 EN 54-2 Evacuation BS 5839-1 NBN S21-100
This feature is not available in these operating modes.
Delay logic
Fire routing and extended fire routing delays elapse concurrently when a fire alarm event is reported.
In NEN 2535 operating mode, the extended fire routing delay becomes the active delay when sounders are stopped (by pressing the Sounder Start/Stop button) and remain stopped when the standard fire routing delay time has elapsed.
In EN 54-2 Scandinavia operating mode, the extended fire routing delay becomes the active delay when an extended fire routing delay switch (connected to INPUT1) is activated while the standard fire routing delay elapses.
Extended delay application logic
Depending on your fire alarm system configuration and the alarm activation device, a configured delay may be overridden.
Extended fire routing delays will only be applied when:
• Both fire routing and extended fire routing delays are configured and enabled.
• The operating mode requirements for the extended delay activation are true (see the previous topic for differences in NEN 2535 and EN 54-2 logic).
• The zone delay configuration is set to allow delays in the zone reporting the fire alarm. (This is the default configuration.)
Add an expansion module
For information on how to add an expansion module to the fire system and how to configure the module, see “Expansion module configuration” on page 39.
Page 35
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 31
Advanced configuration
The default password for advanced configuration is 4444. After entering the password, the first displayed menu is Advanced default configuration (indicating level 3 advanced access) or Operating mode. For more information see “Access level passwords and indications” on page 19.
The advanced configuration menu
Configuration options for this menu are shown in the table below. More information for each option is included in the related topic.
Note: All configurable options included in “Basic configuration” on page 24 are also
available from the advanced configuration menu.
Table 8: The advanced configuration menu
Display Menu Values Operating mode
Advanced default configuration Configuration presets, as
defined in “Basic default config
uration” on page 25
All
Sounder operation during a zone test
ON/OFF All
Sounder re-sound ON/OFF All
Sounder synchronization ON/OFF All
Software version Read only All
Configuration version Read only All
Configuration time stamp Read only All
Configuration date stamp Read only All
Zone configuration Passive EOL
Active EOL Unlatched Passive EOL with CleanMe Active EOL with CleanMe
All
Zone delay ON/OFF All
Page 36
Chapter 3: Configuration and commissioning
32 Kilsen KFP-CF Series Installation Manual
Display Menu Values Operating mode
Zone type Mixed
Automatic Manual
All
Access level 2 password 0 to 4444 All
Access level 3 basic password 0 to 4444 All
Access level 3 advanced password
0 to 4444 All
Control panel PCB serial number Read only All
Auxiliary 24 V reset ON/OFF All
Sounder operation during a zone test
Use this menu to configure the sounder operation during a zone test. The default setting for all operating modes is ON.
To configure the sounder operation during a zone test:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes quickly to indicate that the sounder operation during a zone test configuration menu is active.
7. Select a value using the value selection buttons (2 and 4).
8. Press Enter.
9. Save your changes.
The available settings for this feature are shown below.
Display Description
The internal buzzer and sounders sound for three seconds when an alarm is activated in a zone test.
The internal buzzer and sounders do not sound when an alarm is activated in a zone test.
Page 37
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 33
Sounder re-sound
Use this menu to configure the sounder re-sound, on or off. This determines sounder operation in a fire alarm event when sounders have been silenced by pressing the Sounder Start/Stop button and a new alarm event is reported. The default setting is ON.
To configure the sounder re-sound:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes quickly to indicate that the sounder re-sound configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display Description
The sounders re-sound if a new fire alarm event is reported.
The sounders do not re-sound if a new fire alarm event is reported.
Sounder synchronization
Use this menu to configure the sounder synchronization, on or off. This allows the control panel to synchronize the activation of all sounders. The default setting is on.
To configure the synchronization:
1. Set the display as shown below, and then press Enter.
The Sounders Start/Stop LED flashes quickly to indicate that the sounder synchronization configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Page 38
Chapter 3: Configuration and commissioning
34 Kilsen KFP-CF Series Installation Manual
The available settings for this feature are shown below.
Display Description
The sounders are synchronized.
The sounders are not synchronized.
Zone configuration
Use this menu to configure zone settings for each zone in your fire alarm system. The default setting for each operating mode is included in Appendix A “Configuration presets” on page 59.
To configure the zone:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
The Zone fault/test/disable LED flashes quickly to indicate that the corresponding zone configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display Description
Passive end of line
Active end of line
Unlatched (only available in BS 5839-1 mode)
Passive end of line with CleanMe
Active end of line with CleanMe
Page 39
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 35
Zone delay
Use this menu to configure zone delays, on or off, for each zone in your fire alarm system. The default setting is ON.
To configure the zone delay:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
The Zone alarm LED flashes quickly to indicate that the corresponding zone configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display Description
Configured delays are allowed in the corresponding zone.
Configured delays are not allowed in the corresponding zone
Page 40
Chapter 3: Configuration and commissioning
36 Kilsen KFP-CF Series Installation Manual
Zone type
Use this menu to configure the zone type for each zone in your fire alarm system. The default setting for each operating mode is included in Appendix A “Configuration presets” on page 59.
To configure the zone type:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
The Zone Fault/Test/Disable LED flashes quickly to indicate that the corresponding zone configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display Description
Mixed zone. The control panel automatically distinguishes between an automatic alarm (generated by a detector) and a manual alarm (generated by a manual call point fitted with a 100 resistor).
Automatic zone. All fire alarms are treated as reported by a detector, even if the fire alarm is reported by a manual call point in the zone.
Manual zone. All fire alarms are treated as reported by a manual call point, even if the fire alarm is reported by a detector in the zone.
Page 41
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 37
Changing access level passwords
Use the corresponding menu option (shown below) to change the default access level passwords.
Access level 2 password
Access level 3 basic password
Access level 3 advanced password
To change the first two digits of an access level password:
1. Set the display for the desired access level password, and then press Enter.
2. Set the display as shown below, and then press Enter.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
To change the last two digits of an access level password:
1. Set the display for the desired access level password, and then press Enter.
2. Set the display as shown below, and then press Enter.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
Page 42
Chapter 3: Configuration and commissioning
38 Kilsen KFP-CF Series Installation Manual
Auxiliary 24 V reset
Use this menu to configure the auxiliary 24 V reset setting, on or off. The default setting is OFF.
To configure the zone delay:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display Description
Resetting the control panel resets the AUX 24V output.
Resetting the control panel does not reset the AUX 24V output.
Configuration, software, and PCB identification
Use the corresponding menu option (shown below) to see the control panel configuration version and time stamp, software version, and PCB serial number. These details may be required for troubleshooting and technical support.
Software version
Configuration version
Configuration time stamp
Configuration date stamp
Control panel PCB serial number
Page 43
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 39
Expansion module configuration
Add an expansion module
Use this menu, available from the basic or advanced configuration menus, to configure the number of installed expansion modules. The default value is 00.
To add an expansion module:
1. Set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED flashes quickly to indicate that the module configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The maximum number of expansion modules that can be installed is shown below.
Two- and four-zone control panels Up to two expansion modules
Eight-zone control panel Up to four expansion modules
Expansion module configuration
Expansion module labels
For configuration purposes expansion modules are labeled A and B (for two- and four-zone control panels) or A, B, C, and D (for eight-zone control panels).
The label for a given module is defined by its position (left to right) in the control panel cabinet,. The first expansion module installed is module A, the second B, etc.
See your expansion module installation sheet for installation instructions.
Page 44
Chapter 3: Configuration and commissioning
40 Kilsen KFP-CF Series Installation Manual
Expansion module function and delay configuration
Once an expansion module is installed and added to the control panel configuration, the following additional configuration options appear on the basic and advanced configuration menus.
Note: These configuration options are repeated for each of the installed expansion
modules (A, B, C, and D).
Table 9: Expansion module A configuration options
Display Description Value
Module A function 00 to 92
Module A output 1 delay 00 to 10 minutes
Module A output 2 delay 00 to 10 minutes
Module A output 3 delay 00 to 10 minutes
Module A output 4 delay 00 to 10 minutes
Expansion module function
Use this menu to configure the expansion module function. The default value is 00. For available presets, see Appendix A “Configuration presets” on page 59.
To configure the expansion module function:
1. Set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED on the control panel interface and the ON LED on the expansion module flashes quickly to indicate that the module function configuration menu is active.
2. Select a value from 00 to 92 using the value selection buttons (2 and 4).
See Appendix A “Configuration presets” on page 59.
3. Press Enter.
4. Save your changes.
Page 45
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 41
Expansion module output delay
Use this menu to configure an expansion module output delay of up to 10 minutes, where the feature is available.
To configure an expansion module output delay:
1. For output 1 on expansion module A, set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED on the control panel interface and the Activated LED on the expansion module flashes quickly to indicate that the module delay menu is active.
2. Select a value from 00 to 10 using the value selection buttons (2 and 4).
3. Press Enter.
4. Repeat steps 1 to 3 as required for each output (1 to 4) on each installed module (A, B, C, and D) where a delay is required.
5. Save your changes.
Page 46
Chapter 3: Configuration and commissioning
42 Kilsen KFP-CF Series Installation Manual
Commissioning
Before commissioning the control panel
Before commissioning the control panel, check the following:
• That the control panel has been correctly installed
• That the mains power is 110 VAC or 240 VAC, is connected correctly, and complies with all requirements described in “Connecting the mains power supply” on page 12
• That there are no short or open circuits in any of the zone circuits
• That all zones have the correct end-of-line termination, as described in “Terminating zones” on page 9
• That all manual call points have the correct resistance for alarm identification, as described in “Connecting manual call points” on page 10
• That polarity is observed for all sounder circuits and that all end-of-line resistors are installed, as described in “Connecting the sounders” on page 11
• That any optional equipment installed (fire routing, alarm, and fault relays, etc.) is correctly connected
• That the batteries are connected correctly, and comply with all requirements described in “Connecting the batteries” on page 14
• That all fire alarm system configuration complies with the corresponding operating mode and local regulations.
Commissioning the control panel
Once all installation, connection, and configuration requirements have been checked as described above, the control panel can be powered up.
Normal start-up
After starting up the control panel, normal status (standby) is indicated as follows:
• The Supply LED is steady
• The Sounder Delay LED is steady (if a delay has been configured and enabled)
• The Fire Routing Delay LED is steady (if a delay has been configured and enabled)
If any other indicators are on, check your installation thoroughly before proceeding.
Page 47
Chapter 3: Configuration and commissioning
Kilsen KFP-CF Series Installation Manual 43
Fault start-up
In accordance with EN 54-2, the control panel has a special start-up sequence used after an internal fault has been detected by the control panel.
This is indicated as follows:
• The general Fault LED flashes quickly
• The System Fault LED flashes slowly
When this happens:
1. Enter the access level 2 password.
2. Press the Reset button to reset the control panel.
If the fault status persists after reset, the control panel will abort the start-up sequence and the System Fault LED will be steady.
When this happens, check all control panel connections and configuration, as described in “Before commissioning the control panel” on page 42.
Battery start-up
To power up the control panel from the batteries, press the battery start button on the control panel PCB (marked as BAT. START, see Figure 12 below). Keep the button pressed for approximately five seconds.
Figure 12: Battery start-up button
Page 48
Chapter 3: Configuration and commissioning
44 Kilsen KFP-CF Series Installation Manual
Functional tests
Create a short and open circuit in the zone to test fault reporting for each.
Activate a manual call point to test manual alarm reporting. The control panel should override any configured delays and activate alarm notification devices and fire routing (where applicable) immediately.
Activate a detector to test automatic alarm reporting. The control panel should initiate any configured delays and activate alarm notification devices and fire routing (where applicable) once the delay time has elapsed.
Using a multimeter, verify that the fault relay is activated when a fault is reported and that the alarm relay is activated when an alarm is reported.
Response times
Response times for standard events are as follows.
Event Response time
Alarm Less than 3 seconds
Zone fault Less than 30 seconds
Sounder fault Less than 30 seconds
Fire routing fault Less than 30 seconds
Earth fault Less than 100 seconds
attery charger fault Less than 100 seconds
Battery lost fault Less than 3 minutes
Mains fault Less than 3 minutes
Low battery fault Less than 100 seconds
Fuse/protection fault Less than 3 minutes
System fault Less than 100 seconds
Battery high resistance fault Less than 4 hours
Page 49
Kilsen KFP-CF Series Installation Manual 45
Chapter 4
Maintenance
Summary
This chapter includes information on fire alarm system maintenance and battery maintenance.
Content
Fire alarm system maintenance 46
Daily maintenance 46 Weekly maintenance 46 Quarterly maintenance 46 Annual maintenance 46 Cleaning the control panel 46
Battery maintenance 47
Page 50
Chapter 4: Maintenance
46 Kilsen KFP-CF Series Installation Manual
Fire alarm system maintenance
Perform the following maintenance tasks to ensure that the fire alarm system works correctly and complies with all required European regulations.
Caution: Before performing any tests, ensure that fire routing (if configured) is
disabled or that the fire brigade has been notified.
Daily maintenance
Check that the control panel is in standby. If it is not, investigate all system events and/or fix any reported faults.
Weekly maintenance
Activate an alarm from at least one detector or manual call point in your fire alarm system and verify that the control panel responds correctly to the alarm. If it does not, investigate all system events and/or fix any reported faults.
Caution: Perform this test from a different detector or manual call point each time.
Quarterly maintenance
Test at least one device per zone and verify that the control panel responds to all fault and alarm events. The control panel power supply and battery voltage should be checked. Batteries with low voltage must be replaced (for more information see “Battery maintenance” on page 47).
Annual maintenance
Test all system devices and verify that the control panel responds to all fault and alarm events. All electrical connections must be visually inspected to make sure that they are securely fastened, that they have not been damaged, and that they are appropriately protected.
Cleaning the control panel
Keep the outside and inside of the control panel clean. Carry out periodic cleaning using a damp cloth for the outside. Do not use products containing solvents to clean the control panel. Do not clean the inside of the cabinet with liquid products.
Page 51
Chapter 4: Maintenance
Kilsen KFP-CF Series Installation Manual 47
Battery maintenance
Compatible batteries
The control panel requires two 12V, 7.2 or 12 Ah rechargeable sealed lead-acid batteries. Compatible batteries for this product are shown in the table below.
Table 10: Compatible batteries
Model Battery type Recommended batteries
Two- and four-zone control panels
12V, 7.2 Ah GE BS127N
Fiamm FG20721/2 Yuasa NP7-12
Eight-zone control panel 12V, 7.2 Ah or 12V, 12 Ah GE BS127N (7.2 Ah)
GE BS130N (12 Ah) Fiamm FG20721/2 (7.2 Ah) Fiamm FG21201/2 (12 Ah) Yuasa NP7-12 (7 Ah) Yuasa NP12-12 (12 Ah)
Low battery indication
Battery supply and battery fuse faults are indicated by a flashing Supply Fault LED. If this LED is flashing, check the following:
• That the battery cables are in good condition
• That the battery cables are connected securely and correctly at the battery and at the control panel PCB
• That the battery voltage is greater than 19.6 V
If the cables are in good condition and all connections are correct, then the batteries should be replaced immediately.
Replacing batteries
Batteries must be replaced periodically as recommended by the battery manufacturer. The useful life of the battery is approximately four years. Avoid the total discharge of the batteries. Always use the recommended replacement batteries.
To replace the batteries:
1. Disconnect and remove the existing batteries from the cabinet.
2. Install and connect the replacement batteries using the bridge provided. Observe correct polarity.
3. Dispose of the batteries as required by local or regional regulations.
Page 52
Chapter 4: Maintenance
48 Kilsen KFP-CF Series Installation Manual
Page 53
Kilsen KFP-CF Series Installation Manual 49
Chapter 5
Technical specifications
Summary
This chapter includes technical specifications for your fire alarm control panel.
Content
Zone circuit specifications 50 Input and output specifications 51 Power supply specifications 52 Mechanical and environmental specifications 53
Page 54
Chapter 5: Technical specifications
50 Kilsen KFP-CF Series Installation Manual
Zone circuit specifications
General
Zone circuit output voltage Nominal Maximum Minimum
22 VDC 24 VDC 18 VDC
Maximum current consumption per zone circuit 65 mA
Default zone circuit configuration EN 54 NEN 2535 NBN S21-100 BS 5839-1
Passive end-of-line Passive end-of-line Passive end-of-line Active end-of-line
Zone circuit termination EN 54 NEN 2535 NBN S21-100 BS 5839-1
4.7 k end-of-line resistor
4.7 k end-of-line resistor
4.7 k end-of-line resistor Active end-of-line module
Number of detectors per zone circuit Max. 20
Number of manual call points per zone circuit Max. 32
Mixed zones
Maximum resistance per zone circuit 40
Maximum capacitance per zone circuit 500 nF
Nominal impedance Detector Manual call point
160 to 470 ±5% 100 ±5%
Detector alarm reference range Zone voltage Zone impedance
6.5 V to 14 V 145 to 470
Manual call point alarm reference range Zone voltage Zone impedance
3 V to 6.5 V 75 to 144
Short circuit reference range Zone voltage Zone impedance
< 3 V < 55
Open circuit reference range Zone impedance Zone device current consumption
> 8 k 2.6 mA
Automatic and manual zones
Maximum resistance per zone circuit 55
Maximum capacitance per zone circuit 500 nF
Nominal impedance 100 to 470 ±5%
Detector alarm reference range Zone voltage Zone impedance
3 V to 14 V 75 to 470
Page 55
Chapter 5: Technical specifications
Kilsen KFP-CF Series Installation Manual 51
Automatic and manual zones
Short circuit reference range Zone voltage Zone impedance
< 3 V < 55
Open circuit reference range Zone impedance Zone device current consumption
> 8 k 2.6 mA
Input and output specifications
Inputs
Cable resistance Activation input value Deactivation input value
100 Open circuit
Outputs
Output termination 15 k end-of-line resistor
Sounder outputs Supervised Number of outputs
Maximum current per output (2-,4-zone) Maximum current per output (8-zone) Maximum voltage in standby Maximum voltage in alarm
For open and short circuit 4 (BS 5839-1, EN 54-2 Evacuation) 3 (EN 54-2, EN 54-2 Scandinavia) 2 (NEN 2535, NBN S21-100) 250 mA 500 mA
15 VDC +28 VDC
Fire routing outputs Supervised Number of outputs (EN 54) Number of outputs (NEN 2535) Maximum current per output (2-,4-zone) Maximum current per output (8-zone) Maximum voltage in standby Maximum voltage in alarm
For open and short circuit 1 2 250 mA 500 mA
15 VDC +28 VDC
Alarm relay output Number of potential-free outputs Maximum commutation current
1 2 A at 30 VDC
Fault relay output Number of potential-free outputs Maximum commutation current Default state
1 2 A at 30 VDC Energized (fail to safe)
Auxiliary 24 VDC output Nominal output voltage Maximum output voltage Minimum output voltage Maximum current
24 VDC 28 VDC 21 VDC 250 mA
Page 56
Chapter 5: Technical specifications
52 Kilsen KFP-CF Series Installation Manual
Power supply specifications
Mains supply
Operating voltage 110 VAC / 60 Hz or 240 VAC / 50 Hz
Rated current (two- and four-zone control panels) 110 VAC 240 VAC
2 A 2 A
Rated current (eight-zone control panels) 110 VAC 240 VAC
3.15 A
1.5 A
Voltage tolerance +10% / −15%
Mains fuse 110 VAC 240 VAC
T 3.15A 250V T 2A 250V
24 VDC power supply unit
Two- and four-zone control panels DC voltage Rated current Current range Rated power Voltage tolerance
24 V 2 A 0 to 2 A 50 W ±2%
Eight-zone control panel DC voltage Rated current Current range Rated power Voltage tolerance
24 V 4 A 0 to 4 A 100 W ±2%
Batteries and battery charger
Batteries Two- and four-zone control panels Eight-zone control panel
2 x 7.2 Ah 2 x 7.2 Ah or 2 x 12 Ah
Battery type Sealed lead-acid
Battery charger voltage 27.3 V at 20ºC −36mV/ºC
Battery charger current Two- and four-zone control panels Eight-zone control panel
Max. 0.5 A Max. 0.7 A
Page 57
Chapter 5: Technical specifications
Kilsen KFP-CF Series Installation Manual 53
Mechanical and environmental specifications
Mechanical
Cabinet dimensions (no cover) Two- and four-zone control panels Eight-zone control panel
300 × 97 × 402 mm 421 × 100 × 447 mm
Weight without batteries Two- and four-zone control panels Eight-zone control panel
2.8 kg
3.9 kg
Number of cable knockouts Two- and four-zone control panels
Eight-zone control panel
14 x Ø 20 mm at top of cabinet 2 x Ø 20 mm at bottom of cabinet 12 x Ø 20 mm at rear of cabinet
20 x Ø 20 mm at top of cabinet 2 x Ø 20 mm at bottom of cabinet 26 x Ø 20 mm at rear of cabinet
IP rating IP30
Environmental
Operating temperature Storage temperature
5 to +40ºC
5 to +70ºC
Relative humidity 10 to 95% (noncondensing)
Type class conditions 3K5 of IEC 60721-3-3
Note: For detailed cabinet drawings and dimensions, see “Cabinet drawings and
dimensions” on page 54.
Page 58
Chapter 5: Technical specifications
54 Kilsen KFP-CF Series Installation Manual
Cabinet drawings and dimensions
Figure 13: Two- and four-zone cabinet with cover
Page 59
Chapter 5: Technical specifications
Kilsen KFP-CF Series Installation Manual 55
Figure 14: Two- and four-zone cabinet without cover
Page 60
Chapter 5: Technical specifications
56 Kilsen KFP-CF Series Installation Manual
Figure 15: Eight-zone cabinet with cover
Page 61
Chapter 5: Technical specifications
Kilsen KFP-CF Series Installation Manual 57
Figure 16: Eight-zone cabinet without cover
Page 62
Chapter 5: Technical specifications
58 Kilsen KFP-CF Series Installation Manual
Page 63
Kilsen KFP-CF Series Installation Manual 59
Appendix A
Configuration presets
Summary
This appendix includes detailed information on operating mode and expansion module configuration presets.
Content
Operating mode presets 60
EN 54-2 60 EN 54-2 Evacuation 61 EN 54-2 Scandinavia 62 BS 5839-1 63 NBN S21-100 64 NEN 2535 65
Expansion module presets 66
Expansion module zone configuration 66 Expansion module event configuration 68 Expansion module sounder circuit configuration 68
Page 64
Appendix A: Configuration presets
60 Kilsen KFP-CF Series Installation Manual
Operating mode presets
EN 54-2
Configuration presets for EN 54-2 are as follows.
Two-zone control panels
Code Zone EOL Sounder outputs Zone type
01 Passive 2 Mixed
02 Passive, CleanMe
enabled
2 Mixed
Note: CleanMe is not currently available for Kilsen detectors.
Four- and eight-zone control panels
Code Zone EOL Sounder outputs Fire routing outputs
Zone type
01 Passive 3 1 Mixed
02 Passive, CleanMe
enabled
3 1 Mixed
Additional configuration characteristics are shown below.
Default sounder delay 0
Default fire routing delay 0
Default zone delay 0n
Start/Restart sounders Start sounders only if there is a fire alarm
Inputs and outputs are as follows.
INPUT1 Remote reset
INPUT2 Delays off
OUT1 Sounder circuit
OUT2 Sounder circuit
OUT3 Sounder circuit
OUT4 Fire routing
Note: Two-zone control panels have only two outputs (OUT1 and OUT2).
Page 65
Appendix A: Configuration presets
Kilsen KFP-CF Series Installation Manual 61
EN 54-2 Evacuation
Configuration presets for EN 54-2 Evacuation are as follows.
Two-zone control panels
Code Zone EOL Sounder outputs Zone type
05 Passive 2 Mixed
06 Passive, CleanMe
enabled
2 Mixed
Note: CleanMe is not currently available for Kilsen detectors.
Four- and eight-zone control panels
Code Zone EOL Sounder outputs Zone type
05 Passive 4 Mixed
06 Passive, CleanMe
enabled
4 Mixed
Additional configuration characteristics are shown below.
Default sounder delay 0
Default zone delay 0n
Start/Restart sounders Start sounders or restart stopped sounders at access level 2 with or
without a fire alarm event
Inputs and outputs are as follows.
INPUT1 Remote reset
INPUT2 Delays off
OUT1 Sounder circuit
OUT2 Sounder circuit
OUT3 Sounder circuit
OUT4 Sounder circuit
Note: Two-zone control panels have only two outputs (OUT1 and OUT2).
Page 66
Appendix A: Configuration presets
62 Kilsen KFP-CF Series Installation Manual
EN 54-2 Scandinavia
Configuration presets for EN 54-2 Scandinavia are as follows.
Two-zone control panels
Code Zone EOL Sounder outputs Zone type
07 Passive 2 Mixed
08 Passive, CleanMe
enabled
2 Mixed
Note: Note: CleanMe is not currently available for Kilsen detectors.
Four- and eight-zone control panels
Code Zone EOL Sounder outputs Fire routing outputs
Zone type
07 Passive 3 1 Mixed
08 Passive, CleanMe
enabled
3 1 Mixed
Additional configuration characteristics are shown below.
Default sounder delay 0
Default fire routing delay 0
Default extended fire routing delay
0
Default zone delay 0n
Start/Restart sounders Start sounders or restart stopped sounders at access level 2 with or
without a fire alarm event
Inputs and outputs are as follows.
INPUT1 Fire routing delay / extended fire routing
delay
INPUT2 Delays off
OUT1 Sounder circuit
OUT2 Sounder circuit
OUT3 Sounder circuit
OUT4 Fire routing
Note: INPUT1 is not used on two-zone control panels. Two-zone control panels have only two outputs (OUT1 and OUT2).
Page 67
Appendix A: Configuration presets
Kilsen KFP-CF Series Installation Manual 63
BS 5839-1
Configuration presets for BS 5839-1 are as follows.
Two-zone control panels
Code Zone EOL Sounder outputs Zone type
11 Active 2 (first phase
evacuation mode)
Mixed
12 Active, CleanMe
enabled
2 (first phase evacuation mode)
Mixed
13 Active 2 (second phase
evacuation mode)
Mixed
14 Active, CleanMe
enabled
2 (second phase evacuation mode)
Mixed
Note: CleanMe is not currently available for Kilsen detectors.
Four- and eight-zone control panels
Code Zone EOL Sounder outputs Zone type
11 Active 4 (first phase
evacuation mode)
Mixed
12 Active, CleanMe
enabled
4 (first phase evacuation mode)
Mixed
13 Active 4 (second phase
evacuation mode)
Mixed
14 Active, CleanMe
enabled
4 (second phase evacuation mode)
Mixed
Additional configuration characteristics are shown below.
Default sounder delay 0
Default zone delay 0n
Start/Restart sounders Start sounders or restart stopped sounders at access level 2 with or
without a fire alarm event
Inputs and outputs are as follows.
INPUT1 Class change
INPUT2 Delays off
OUT1 Sounder circuit
OUT2 Sounder circuit
OUT3 Sounder circuit
OUT4 Sounder circuit
Note: Two-zone control panels have only two outputs (OUT1 and OUT2).
Page 68
Appendix A: Configuration presets
64 Kilsen KFP-CF Series Installation Manual
NBN S21-100
Configuration presets for NBN S21-100 are as follows.
Four- and eight-zone control panels
Code Zone EOL Warning sounder
outputs
Evacuation sounder outputs
Zone type
21 Passive 2 2 Automatic
22 Passive, CleanMe
enabled
2 2 Automatic
Note: Alarm relay follows evacuation sounders. CleanMe is not currently available for Kilsen detectors.
Additional configuration characteristics are shown below.
Default sounder delay 1 minute
Default zone delay 0n
Start/Restart sounders Start sounders or restart stopped sounders at access level 2 with or
without a fire alarm event
Inputs and outputs are as follows.
INPUT1 Remote reset
INPUT2 Delays off
OUT1 Evacuation sounders
OUT2 Evacuation sounders
OUT3 Warning sounders
OUT4 Warning sounders
Page 69
Appendix A: Configuration presets
Kilsen KFP-CF Series Installation Manual 65
NEN 2535
Configuration presets for NEN 2535 are as follows.
Four- and eight-zone control panels
Code Zone EOL Sounder outputs Fire routing outputs Zone type
31 Passive 2 2 Odd zones:
Automatic Even zones: Manual
32 Passive, CleanMe
enabled
2 2 Odd zones:
Automatic Even zones: Manual
Note: CleanMe is not currently available for Kilsen detectors.
Additional configuration characteristics are shown below.
Default fire routing delay 1 minute
Default extended fire routing delay
3 minutes
Default zone delay 0n
Start/Restart sounders Start sounders only if there is a fire alarm
Inputs and outputs are as follows.
INPUT1 Fire routing inhibit delay
INPUT2 Delays off
OUT1 Sounder circuit
OUT2 Sounder circuit
OUT3 Fire routing (automatic)
OUT4 Fire routing (manual)
Page 70
Appendix A: Configuration presets
66 Kilsen KFP-CF Series Installation Manual
Expansion module presets
The following tables include the display settings for relay and supervised output expansion module configuration presets.
Expansion module zone configuration
Relay expansion module Supervised output expansion module
Display Zone Relay Delay Display Zone Output Delay
1 1 Yes 1 1 Yes
2 2 Yes 2 2 Yes
3 3 Yes 3 3 Yes
01
4 4 Yes
51
4 4 Yes
5 1 Yes 5 1 Yes
6 2 Yes 6 2 Yes
7 3 Yes 7 3 Yes
02
8 4 Yes
52
8 4 Yes
1 Yes 1 Yes 1
2 Yes
1
2 Yes
3 Yes 3 Yes
05
2
4 Yes
55
2
4 Yes
1 Yes 1 Yes 3
2 Yes
3
2 Yes
3 Yes 3 Yes
06
4
4 Yes
56
4
4 Yes
1 Yes 1 Yes 5
2 Yes
5
2 Yes
3 Yes 3 Yes
07
6
4 Yes
57
6
4 Yes
1 Yes 1 Yes 7
2 Yes
7
2 Yes
3 Yes 3 Yes
08
8
4 Yes
58
8
4 Yes
1 or 2 1 Yes 1 or 2 1 Yes
3 or 4 2 Yes 3 or 4 2 Yes
5 or 6 3 Yes 5 or 6 3 Yes
13
7 or 8 4 Yes
63
7 or 8 4 Yes
Page 71
Appendix A: Configuration presets
Kilsen KFP-CF Series Installation Manual 67
Relay expansion module Supervised output expansion module
Display Zone Relay Delay Display Zone Output Delay
1 and 2 1 Yes 1 and 2 1 Yes
3 and 4 2 Yes 3 and 4 2 Yes
5 and 6 3 Yes 5 and 6 3 Yes
15
7 and 8 4 Yes
65
7 and 8 4 Yes
1, 2, 3, or 4 1 Yes 1, 2, 3, or 4 1 Yes
5, 6, 7, or 8 2 Yes 5, 6, 7, or 8 2 Yes
Not used 3 N/A Not used 3 N/A
17
Not used 4 N/A
67
Not used 4 N/A
1 Yes 1 Yes 1 and 2
2 Yes
1 and 2
2 Yes
3 Yes 3 Yes
18
3 and 4
4 Yes
68
3 and 4
4 Yes
1 Yes 1 Yes 5 and 6
2 Yes
5 and 6
2 Yes
3 Yes 3 Yes
19
7 and 8
4 Yes
69
7 and 8
4 Yes
Page 72
Appendix A: Configuration presets
68 Kilsen KFP-CF Series Installation Manual
Expansion module event configuration
Relay expansion module Supervised output expansion module
Display Events Relay Delay Display Events Output Delay
24 Alarm 1-4 No 74 Alarm 1-4 No
25 Fault 1-4 No 75 Fault 1-4 No
Alarm 1-2 No Alarm 1-2 No 26
Fault 3-4 No
76
Fault 3-4 No
Alarm 1 No Alarm 1 No
Fault 2 No Fault 2 No
Buzzer on 3 No Buzzer on 3 No
27
Reset 4 No
77
Reset 4 No
28 Alarm 1-4 No 78 Alarm 1-4 No
29 Fault [1] 1-4 No 79 Fault [1] 1-4 No
Alarm 1-2 No Alarm 1-2 No 30
Fault [1] 3-4 No
80
Fault [1] 3-4 No
Alarm 1 No Alarm 1 No
Fault [1] 2 No Fault [1] 2 No
Buzzer on 3 No Buzzer on 3 No
31
Reset 4 No
81
Reset 4 No
[1] Positive security mode (output is on when there is no fault)
Expansion module sounder circuit configuration
Display Events Output Delay
1 No Sounder 1 circuit
2 No
3 No
90 [1]
Sounder 2 circuit
4 No
1 No
2 No
3 No
91 Sounder 1 circuit
4 No
1 No
2 No
3 No
92 [1] Sounder 2 circuit
4 No
[1] NBN S21-100 only
Page 73
Kilsen KFP-CF Series Installation Manual 69
Appendix B
Product compliance
European standards for fire control and indicating equipment
These control panels have been designed in accordance with European EN 54-2, EN 54-4, BS 5839-1, NBN S21-100, and NEN 2535 standards.
In addition, all models comply with the following EN 54-2 optional requirements.
Option Description
7.8 Output to fire alarm devices
7.9.1 Output to fire alarm routing equipment [1]
7.11 Delays to outputs
7.13 Alarm counter [2]
8.4 Total loss of the power supply
10 Test condition
11 Standardised input/output interface
[1] Excluding two-zone models. [2] Dutch models only.
European standards for electrical safety and electromagnetic compatibility
These control panels have been designed in accordance with the following European standards for electrical safety and electromagnetic compatibility:
• EN 60950-1
• EN 50130-4
• EN 61000-6-3
• EN 61000-3-2
• EN 61000-3-3
Page 74
Appendix B: Product compliance
70 Kilsen KFP-CF Series Installation Manual
Page 75
Appendix B: Product compliance
Kilsen KFP-CF Series Installation Manual 71
Page 76
Appendix B: Product compliance
72 Kilsen KFP-CF Series Installation Manual
Loading...