GE KCD09L, KCD21D, KCD15D, KCD18D, KCD24D Use and Care Manual

th~;;;;kekyour
&rConditioner
ConknW
‘“9
Adapter Plug Air Direction
Air Filter Appliance Registration
Care and Cleaning Condenser Coils
Control Settings Electrical Requirements
Energy-Saving Tips Extension Cords
Grille and Cabinet Grounding
Model and Serial Numbers Problem Solver
Repair Service Safety Instructions
I
User Maintenance Instructions 6
Warrantv
I
!
GE Answer
800.6262000
Center@
Back Cover
4,5
3 5
6
6
Use and Care of
models
Kmo9L Km21D KCS15D
3
KCS18D
2 3
2 7
7 2
KCS24D
—.
o
Help
us
hpo~nt
Safety
help you...
Before using your air conditioner, read this book carefully.
It is
intendd
maintain your new air conditioner properly.
Keep it handy for answers to your questions.
If you don’t understand something or need more help, write (include your phone number):
Consumer Affairs
Hotpoint
Appliance Park Louisville. KY 40225
Write down the model and serial numbers.
You’ll find them on a label behind the front grille on the left side wall of the air discharge duct, visible through the louvers.
These numbers are also on the Consumer Product Ownership
Registration Card that came with
your air conditioner. Before sending
in this card, please write these numbers here:
Model Number
Serial Number
Use these numbers in any correspondence or service concerning your air conditioner.
to help you operate and
calls
Instructions
Read all instructions before using this appliance.
When using this appliance, always exercise basic safety precautions, including the following:
Use this appliance only for its
intended purpose as described in this Use and Care Book.
This air conditioner must be
properly installed in accordance with the Installation Instructions before it is used. See
instructions on page 3.
Never
unplug
your air conditioner
by pulling on the power cord.
Always grip plug straight out from the receptacle.
Repair or replace immediately
all electric service cords that have become frayed or otherwise damaged. Do not use a cord that
shows cracks or abrasion damage along its length or at either the plug or connector end.
grounding
firdy
and pull
SAVE THESE
INSTRUCTIONS
Energy-saving tips
Keep the air filter clean. (See
instructions on page 6.)
c
For most efficient cooling, keep the ventilation control in the closed position except when you want to allow a small amount of outdoor air to enter the room or exhaust air, smoke or odors from the room.
Don’t let the room get too hot. Whenever possible, turn the unit on before the room heats up. When heat is “stored up” in walls, furniture, rugs and draperies, your air conditioner takes longer to produce the desired comfort condition.
. Keep windows and doors closed. Cool, dry air escapes when they’re open.
Keep furnace floor registers and
cold air returns closed. Cold air can easily escape through them.
Don’t let drapes or furniture block the front of the unit and restrict air flow when it is operating.
It’s best to operate your air conditioner at high speed during extremely hot weather.
Keep the outdoor condenser coil clean. (See page 6.)
c
Turn the air conditioner off
before vacations or extended
absences from home.
If you received a damaged air conditioner . . .
Immediately contact the dealer (or builder) that sold you the air
conditioner.
Save time and money. Before you request service . . .
Check the Problem Solver on page 7. It lists causes of minor operating problems that you can correct yourself.
2
Electrical
safety—IMPORTmT...
please
Read Carefully.
How
to connect
electricity
For personal safety, this appliance must be properly grounded.
Electrical requirement
115-volt models
volt a.c., 60 hz grounded outlet protected with a 15 amp time delay fuse or circuit breaker.
The power cord on these models has a three-prong (grounding) plug that mates with a standard three-prong (grounding) wall outlet (Fig. 1) to minimize the possibility of electric shock hazard from these appliances.
PREFERRED METHOD
p–-
.
Fig. 1
T
Where a standard two-prong wall outlet is encountered, it is your personal responsibility and to have it replaced with a properly grounded three-prong wall outlet.
DO NOT, UNDER ANY CIRCUMSTANCES, CUT OR REMOVE THE THIRD (GROUND) PRONG FROM THE POWER CORD.
230/208-volt models
own single branch circuit supplying
230/208-volt a.c., protected with a time delay fuse or circuit breaker. This is recommended for best performance and to prevent overloading house wiring circuits, which could cause a possible fire hazard from overheating wires.
The power cord on these models has a 230/208-volt perpendicular, tandem or large that mates respectively with a
require a
~
Q
T ~
%
Q
/.
n
r
INSURE PROPER
GROUNO
BEFORE USE
require their
tindem
type plug
115/120-
\
9
\
‘\
\
~bligation
1
EXISTS
230/208-volt perpendicular, tandem or large tandem type wall outlet. These types of outlets are available at most hardware stores.
@@
230/208-VOLT
PERPENDICULAR TYPE WALL OUTLET
LINE CORD PLUG
REQUIRES 20 AMP TIME DELAY FUSE
OR CIRCUIT BREAKER PROTECTION
@@
230i20i-VOLT
TANDEM TYPE WALL OUTLET
LINE CORD PLUG
REQUIRES 15 AMP TIME DELAY FUSE
OR CIRCUIT BREAKER PROTECTION
230/208-VOLT
LARGE TANDEM TYPE WALL OUTLET
LINE CORD PLUG
REQUIRES 30 AMP TIME DELAY FUSE
OR CIRCUIT BREAKER PROTECTION
MATCHING
MATCHING
MATCHING
Whether your air conditioner is a 115-volt or a 230/208-volt unit, it is important to have the wall
outlet and circuit checked by a
qualified electrician if there is any doubt as to whether a proper
ground exis~.
Use of adapter plug
(U5-volt modek
Because of potential safety hazards under certain conditions, we
strongly recommend against use of an adapter plug.
if you still elect to use an adapter, where local codes permit, a TEMPORARY may be made to a properly grounded two-prong wall outlet by use of a
UL listed adapter (Fig. 2) available
at most local hardware stores.
only)
However,
CONNE~ION
TEMPORARY METHOD
(ADAPTER PLUGS NOT
PERMITTEDINCANADA) -
The larger slot in the adapter must be aligned with the larger slot in the
wall
outlet to provide proper polarity in the connection of the power cord.
CAUTION: Attaching the adapter ground terminal to wall outlet cover screw does not ground the appliance
unless
cover screw is metal, and not insulated, and wall outlet is grounded through house wiring. You should have the circuit checked by a qualified electrician to make sure the outlet is properly grounded.
When disconnecting the power cord from the adapter,
always hold the adapter with one hand. If this is not done, the adapter ground terminal is very likely to break with repeated use.
Should
terminal break, DO
the adapter ground
N~
USE the
appliance until a proper ground has again been established.
Use of etiension cords
Because of potential safety hazards under certain conditions, we
strongly recommend against the
use of an extension cord.
if you still elect to use an extension cord, it is absolutely necessary that it be a
UL
listed 3-wire grounding type appliance extension cord and that the current carrying rating of the cord in amperes be equal to or greater than the branch circuit size shown on the rating nameplate of the appliance.
However,
3
Opemti~
Your Mr Conditioner
Controk
MASTER CONTROL
Mwter Control Switih
OFF
turns air conditioner off.
~
FAN permits low fan speed
operation without cooling. HI FAN permits high fan speed
operation without cooling.
LO
COOL permits cooling with
low fan speed operation. HI COOL permits cooling with
high fan speed operation.
THERMOSTAT
Thermo~t
When you turn the Thermostat Control to the desired setting, the thermostat will the temperature of the indoor air. The higher the number selected, the cooler the indoor air
The Save
reminder that you can conserve energy by selecting a higher room
temperature but still keep the room
cool and less humid than outside.
Control
automaticdlj
Ene~y
will
Range is
control
be.
a visual
air in
VENTILATION
air out
Ventilation Control
When the AIR IN and AIR OUT buttons are in the out position, the vent door is closed an-d only the air inside the room can be circulated and conditioned.
Push the AIR IN button and it will stay in, and the vent door will open to allow a small amount of outdoor air to enter the room. Push the AIR IN button again and it will return to the out position and the vent door will close.
Push the AIR OUT button and it will stay in, and the vent door will open to allow air, smoke and odors to be exhausted from the room. Push the AIR OUT button again and it will return to the out position and the vent door will close.
4
For normal cooling
1. Set the Master Control Switch at
HI COOL.
2. Set the Thermostat Control at the desired number (usually 4-5 is a good starting position). If room temperature is not satisfactory after a reasonable time, set the Thermostat Control at a higher number for a cooler room or at a lower number for a warmer room.
3. Be sure the AIR IN and AIR OUT buttons are in the out position.
For ni@ttime operation
During the cooler evening hours, we recommend that you set the Master Control Switch at LO COOL for very quiet operation and the Thermostat Control at mid-range (4-5).
For
efireme
For greatest economy and best performance, we suggest that you set the Master Control Switch at HI COOL in extremely hot weather.
temperatures
To adjust air direction
Up and down
For
m~imum
1. Set the Master Control Switch at
HI COOL.
2. Set the Thermostat Control at 8.
3. Be sure buttons are in the out position.
the WR
cooling
IN and AIR OUT
For quieter operation
1. Set the Master Control Switch at
LO COOL.
2. Set the Thermostat Control at desired number.
When the Thermostat Control is set on 7 or 8 and the Fan is set on low speed, moisture may freeze on the coils and prevent the unit from cooling. If this happens, set the Fan at high speed and set the Thermostat Control to a lower number.
3. Be sure the AIR IN and AIR OUT buttons are in the out position.
For ventilation
Whether the controls are set for cooling or fan only operation, setting the Ventilation Control at AIR IN allows a small amount of outside air to enter the room, and setting it to AIR OUT lets room air
be exhausted to the outside. See page 4. However, cooling effectiveness is reduced whenever the vent door is open, so we that you don’t keep it open for especially in hot, humid weather.
su~est
long—
The up-and-down air direction louvers
pressure on the louvers. They regulate air discharge upward, downward or straight out.
Side to side
For fixed side-to-side air direction, set the Circulaire Switch
to ON until the desired air direction is obtained, then move it to OFF.
For continuous side-to-side air circulation, set the Circulaire
Switch to ON and leave it there.
are controlled by fingertip
on
CIRCULAIRE
m
n
off
9
,
5
Care and Cleaning
USER
MTEN~CE
~STRUCTIONS
Turn air conditioner off and remove the plug from the wall
outlet before cleaning.
Grille & Cabinet
Wipe both sides of grille with a clean cloth lightly dampened with mild liquid or clean with a vacuum cleaner brush. Be careful not to force the movable louvers out of position.
Other areas behind the grille may be wiped or vacuumed, taking care not to damage the coil fins.
Wash cabinet with mild soap or detergent and lukewarm water.
Never use strong chemicals, solvents or bleaching agents.
dishwashing detergent,
Condemer Coih
These coils on the weather side of the unit should be checked periodically and cleaned if clogged with dirt or soot from the atmosphere. If extremely soiled, they may need to
bes-
through your Hotpoint service outlet.
cleaned, a service
atiable
Air
Hlter
The air filter behind the front grille should be checked and least every 30 days or as often as it
To remove the filter:
Grasp the unit and pull downward.
Clean the filter
cleaner to remove light dust. Wash the and rinse in clear water to remove sticky dust.
When replacing the filter, be sure the word FRONT is facing you as you slide the filter back into place.
tib
at the bottom of the
filter in lukewarm, soapy water
cleane~ at
with a vacuum
Air Inlet Grille
If your air conditioner is mounted flush inside the room or if the window sill extends farther into the room than the chassis, it may be necessary to remove the air inlet grille before the filter can be
To
remove the grille,
inlet grille out by grasping the front at one side and pushing down on the top to disengage the tab. Do the same to the other side.
The air filter can now be removed from the grille—grasp the tab on the filter and pull.
After cleaning, replace the air filter and air inlet grille, pushing the grille into place.
Remonl
pull the air
6
m
~
-
Questiom?
UseThis Woblem
Solver
PROBLEM
AIR CONDITIONER DOES
AIR CONDITIONER “DOES AS IT SHOULD”
OPERATING SOUNDS
N~
OPERATE
N~
COOL
POSSIBLE CAUSE AND REMEDY
Not
plu~ed
If plugged in, fuse could have blown or circuit breaker may have tripped,
cumins, blinds
Thermostat Control may not be set high enough. Turn control to a higher number.
Highest setting should provide maximum cooling.
Air filter dirty, should be cleaned at least every 30 days. See instructions on page 6.
G
Room may have been very hot when air conditioner was first turned on. Allow time
for it to cool down.
Cold air maybe escaping through open furnace floor registers and cold air returns.
. Vent Control maybe in the AIR IN or AIR OUT position, allowing hot outside air
to enter the room or cool inside air to leave the room through the open vent door.
Cooling coils have iced up. To melt ice, set the Master Control Switch to LO
and the Thermostat Control to a lower number.
Q
Thermostat click, a
off. This is normal. . Fan runs continuously when Master Control Switch is in Cool or Fan position. This
is normal.
in. Plug may have been bumped loose by vacuum cleaner or furniture.
or furniture blocking front of air conditioner will restrict airflow.
FAN
metilic
sound, maybe heard when compressor cycles on and
WATER DRIPPING OUTSIDE
WATER DRIPPING INSIDE
WATER IN BASE PAN (ON OUTDOOR SIDE)
If you need more help.. call, toll free: GE Answer
Centero-
8W.62h2W
consumer information service
If You Need Service
To obtain service, see your warranty on the back page of this book.
We’re proud of our service and want you to be pleased. If for some reason you are not happy with the service you receive, here are three steps to follow for further help.
FIRST, contact the people who
serviced your appliance. Explain
Excess water may overflow in extremely hot and humid weather. This is normal.
. Air conditioner must be installed level or tilted slightly to the outside for proper water disposal.
. This is normal for a short period in areas with little humidity; normal for a longer period in very humid areas. Moisture removed from indoor air drains to rear of cabinet where it is picked up by a fan and thrown against the outdoor condenser coil.
why you are not pleased. In most
cases, this will solve the problem.
NEXT, if you are still not pleased, write all the details-including your phone number—to:
Manager, Consumer Relations
Hotpoint
Appliance Park Louisville, Kentucky 40225
FINALLY, if your problem is still not resolved, write:
Major Appliance Consumer Action Panel 20 North Chicago, Illinois 60606
Wacker
Drive
7
YOUR
H~POINT
ROOM AIR CONDITIONER
Save proof of original purchase date such as your sales slip or
WHAT IS COVERED
WARRANTY
cancelled
FULL ONE-YEAR WARRANTY
For one year from date of original purchase, we will provide, free of charge, parts and service labor in your home to repair or replace
any part of the room air conditioner that fails because
of a manufacturing defect.
FULL FIVE-YEAR WARRANTY
For five years from the date of original purchase, we will provide, free of charge, parts and service
labor in your home to repair or replace
mftigem.ng system
condenser, evaporator and all connecting tubing) that fails
because of a manufacturing
defect.
For
Transportation expense to and from a service shop and shop service labor if required will be free of charge.
any part of the sealed
(the compressor,
each of the above warranties:
check to establish warranty period.
This warranty is extended to the original purchaser and any succeeding owner for products purchased for use in the 48 mainland states, Hawaii and Washington, In Alaska the warranty is the same except that it is LIMITED because you must pay to ship the product to the service shop or for the service technician’s travel costs to your
All warranty service will be provided by our Factory Service Centers or by our authorized Customer Care” servicers during normal working hours.
Look in the White or Yellow Pages of your telephone directory for HOTPOINT FACTORY SERVICE, GENERAL FACTORY SERVICE or HOTPOINT CUSTOMER CARE@ SERVICE.
ELECTRIC-HOTPOINT
D.C.
home.
~
WHAT IS N~ COVERED
Service trips to teach you how to
use the product.
Read your Use and Care material.
If you then have any questions about operating the product, please contact your dealer or our Consumer Affairs office at the address below, or call, toll free:
GE Answer
800.626.2000 consumer information service
may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Cente@
Some states do not allow the exclusion or limitation of incidental or consequential damages, so
To know what your legal rights are in your state, consult your local or state consumer affairs office or your state’s Attorney General.
If further help is needed concerning this warranty, write:
Manager—Consumer Affairs, GE Appliances, Louisville, KY 40225
Improper installation.
If you have an installation problem, or if the air conditioner is of improper cooling capacity for the intended use, contact your dealer or installer. You are
responsible for providing adequate electrical connecting facilities.
. Replacement of fuses or resetting of circuit breakers.
In commercial locations labor
necessary to move the unit to a location where it is accessible for service by an individual technician.
Warrantor: General Electric Company
Failure of the product resulting from
modifications to the product or due to unreasonable use including failure to provide reasonable and necessary maintenance.
Failure due to corrosion on models
not corrosion-protected.
Damage to the product caused
by improper power supply voltage, accident, fire, floods or acts of God.
WARRANTOR IS FOR CONSEQUENTIAL DAMAGES.
the
above limitation or exclusion
NOT
RESPONSIBLE
Pub.
l&88
No.
39-7102
KCD09L KCS18D KCD21D KCS24D KCS15D
Printed in Brazil
Loading...