GE K0341, Druck UPS-III-IS User Manual

Page 1
GE
II2GExibIICT4
Druck UPS-III-IS
mA
mA(24V)
COM
V
Sensing
Druck UPS-III-IS
Intrinsically Safe Loop Calibrator
User manual - K0341
Page 2
Approved Service Agents
For the list of service centres visit our web site:
www.gesensing.com
Symbols
This equipment meets the requirements of all relevant European safety directives. The equipment carries the CE mark.
This symbol, on the instrument, indicates that the user should refer to the user manual.
Do not dispose of this product as household waste. Use an approved organisation that collects and/or recycles waste electrical and electronic equipment. For more information:
Contact us at www.gesensing.com
Page 3
The IECEx certificate for this equipment can be reviewed at the following web site:
www.iecex.com
i K0341 Issue No. 2
Page 4
A full copy of the ATEX certificate for this equipment can be supplied, contact us at the following web site:
K034 1 Issu e No. 2 ii
www.gesensing.com
Page 5
iii K0341 Issue No. 2
Page 6
K034 1 Issu e No. 2 iv
Page 7
UPS-III Intrinsically Safe Loop Calibrator
2
Introduction
The Druck power (
mode
The set-up menu enables the user to “source” or “measure” in either voltage or current and to perform continuity tests. and operation of the UPS III Intrinsically Safe Loop Calibrator in a hazardous area. Read the whole publication before starting.
) to perform field calibrations on 2-wire devices.
Installation Requirements in Hazardous Areas
Marking details Serial number/year of manufacture
1180 Baseefa06ATEX0224X IECEx BAS 06.0053X
UPS-III Intrinsically Safe Loop Calibrator
source mode
) and produce readings (
These instructions detail the requirements
can supply
measure
Ex ib IIC T4 (-10°C < Druck, LE6 0FH, UK (manufacturer)
Ta <+40°C)
Requirements and Conditions
Refer to the supply and input/output parameter table.
Batteries
WARNING: Only replace batteries in a safe area
Only use the battery type listed below.
Requirements
Installing should be carried out by qualified plant installation technicians in compliance with the latest issue of EN 60079-14.
Special Conditions for Use
This loop calibrator may be used in zones 1 and 2 for industries with any gas group.
Maximum component temperature class T4 (135°C).
Only use 4 x LR6 (size AA), Duracell PROCELL, Duracell PLUS, ENERGIZER ULTIMATE or GP SUPERALKALINE LR6.
Loop Calibrator Casing
Avoid impact sparking when installing in a hazardous area.
Provide additional protection for calibrators that may be damaged in service.
1 K0341 Issue No. 2
Page 8
Declaration Requirements
The Intrinsically Safe UPS-III is designed and manufactured to meet the essential health and safety requirements not covered by EC Type Examination Certificate
Baseefa06
ATEX0224 when installed as detailed above. This intrinsically safe loop calibrator is designed and manufactured to protect against other hazards as defined in paragraph 1.2.7 of Annex II of the ATEX Directive 94/9/EC.
Specifications
Accuracies
1 year for 17°C to 27°C outside these limits
...................................................................... 0.003%/°C(0.0015%/F°)
Reference.................................................. 22°C ±5°C/RH45%±15%
Mode Range Resolution Accuracy
Source 2 wire† 0 to 24 mA 0.001 Source mA 0 to 24 mA* 0.001 Measure mA 0 to 24 mA 0.001 Measure V 0 to 50V** 0.01
0.015% rdg + 2 lsd
0.015% rdg + 2 lsd
0.015% rdg + 2 lsd
0.015% rdg + 4 lsd
Continuity <100Ω*** -0.5 mA
Ω
* R max 650 ** R-measure >1M
at 20 mA lsd least significant digits
Ω
rdg reading
*** Audio + visual
maximum 24V, typically 21V
Hart® communications................menu selectable 220Ω loop resistor
Operating Temperature..................... -10°C to 40°C (14°F to 104°F)
Storage Temperature.............................-20°C to 70°C (-4°F to 158°F)
This loop calibrator meets the essential protection requirements of the relevant EEC directives.
Electrical Power Supply Only use 4 x LR6 (size AA), Duracell PROCELL, Duracell PLUS, ENERGIZER ULTIMATE or GP SUPERALKALINE LR6.
Physical
Dimensions....................................90 x 140 x 42 mm(3.5” x 5.5” x 1.7”)
Weight (nominal)........................................................460 grams (16.2 oz.)
Terminals ................................................................................ 4 mm sockets
Case ................................................................................ High impact ABS
Environmental............................................................................................ IP40
Relative Humidity........................................................................... 0 to 90%
K0341 Issue No. 2 2
Page 9
Table 1
1
2
3
44
5
6
7
Guide to supply and input/output
No. Parameter and conditions
Current measurement between mA and COM with
&
external 24V. This mode of operation inserts the apparatus in the current loop by breaking into the circuit and connecting mA (positive) and COM (negative) into the circuit.
Current measurement between mA (24V) and mA with internal 24V. Terminal mA(24V) provides the source of
power to supply remote sensor. Special condition for safe use - remote sensor MUST be isolated from all other sources of power.
Voltage measurement between V and COM
Continuity measurement between V and COM
Special condition for safe use - remote sensor MUST be isolated from all other sources of power.
Current generation between mA and COM with external 24V. This mode of operation inserts the apparatus in the
current loop by breaking into the circuit and connecting mA (positive) and COM (negative) into the circuit.
Current generation between mA (24V) and mA with internal 24V. Terminal mA (24V) provides the source of
power to supply the remote sensor. Special condition for safe use - remote sensor MUST be isolated from all other sources of power.
3 K0341 Issue No. 2
Page 10
Table 2
1
2
3
44
5
6
7
Supply and input/output parameter
Param.
U
i
I
i
P
i
U
0
I
0
P
0
C
i
L
i
C
0
L
0
&
30V 0* 50V 0* 30V 0*
100mA 0* 100mA 0* 100mA 0*
1W 0* 1W 0* 1W 0*
6.51V 25.2V 6.51V 6.51V 6.51V 25.2V
14mA 158mA 12mA 8mA 14mA 158mA
22mW 0.995W 20mW 20mW 22mW 0.995W
220pF# 220pF# 110pF 110pF 220pF# 220pF#
000000
33nF 53nF 10nF 11µF 33nF 53nF
1.5mH 500µH 1.5mH 100mH 1.5mH 500µH
* Special condition for safe use
#220pF consists of 110pF @ 6.51 V max and 110pF @ 1.6V max.
K0341 Issue No. 2 4
Page 11
OPERATION
MODE
F2
F1
SPAN CHECK
MODE
F2
F1
Keys
The key switches the loop calibrator on and off. Press and hold
for 2 seconds.
The key changes the measure or source operating mode. Pressing the
keys makes menu selections,
sets numerical values and controls step and ramp functions (up/down).
The select advanced functions shown on the bottom of the display. When no key is
pressed for 10 minutes, the loop calibrator times out and switches off. To disable this automatic time out, select autpower down in the set-up menu.
5 K0341 Issue No. 2
Page 12
Operating Modes
F1
F1
Serial number VERSION CAL. DATE HART BATTERY
Information
F2
F2
Resolution
adjust
F2
Contrast
adjust
F2
Range
4-20 mA/0-20mA
F2
Source unit
mA/%
F2
Hart® ON/OFF
F2
Aut power down
ON/OFF
F2
Decimal
.,/
F2
Access code
menu
F2
Calibration
menu
F2
F1
F2
F2
Pressing
switches the instrument on and the display shows
the start-up sequence. Pressing , at this time, the display shows the information screen:
Pressing , at this time, the display shows the set-up screen:
The calibrator can be used in two modes
Measure mode
The display shows the measured value; depending on the settings made in set-up and advanced settings:
pressing enables mA or % (value of 4 to 20 mA or 0 to 20 mA).
When measuring current pressing enables linear or flow,
When measuring voltage pressing changes the resolution
between 0.00V and 0.000V.
To measure continuity the displays shows an open or closed switch symbol with an audible signal on switch closure.
K0341 Issue No. 2 6
measure
or
source
.
Page 13
Connect the calibrator to the device to be tested:
1
+
-
Hazardous area
Safety barrier
Safe area
Advanced
%
+
100
.0%
+20.000
mA
mA
mA( 24V )
COM
V
*
2
Hazardous area
+
-
Safety barrier
Safe area
Advanced
%
+100.0%
+20.000
mA
m
A
m
A
(24V
)
COM
V
3
Advanced
%
+100.0%
+24.000
mA
mA
m
A
(
24
V
)
CO
M
V
21V
4
Advanced
%
+100.0%
mA
m
A
(2
4V
)
CO
M
V
+50.000 V
and Measure mA
Press the mode key and select [Measure mA]. An external power supply supplies a maximum of 30 V for the loop. The calibrator measures the current of the loop.
Closed loop current measurement from transmitter test terminal
Measure mA with
24 V*
Press mode key and select [Measure mA and 24V]. The calibrator supplies 24 V (maximum) for the loop, maximum 24 mA. *Special condition for safe use, see page 3.
Measure Volts
Press mode key and
select [Measure Volts], measure range 50 V, maximum impedance 1 Mohm.
7 K0341 Issue No. 2
Page 14
Continuity Test*
5
+20.000
mA
Step off
+100.0%
mA
m
A
(2
4V
)
CO
M
V
Rmax = 650 Ohms
6
+
-
Hazardous area
Safety barrier
Safe area
Advanced
%
+100.0%
mA
m
A
(
2
4
V
)
CO
M
V
+12.000 V
I/P
_
+
7
Advanced
%
+100.0%
mA
m
A
(24V
)
CO
M
V
+24.000
mA
Press mode key and select [Continuity Test].
Pressing switches the audible signal on/off.
Source Mode
The display shows the source value in mA or % value of 4 to 20 mA or 0 to 20 mA, linear or flow depending on the settings made in set-up and advanced settings. *Special condition for safe use, see page 3.
Source mA
Press mode key and select [Source mA].
Source mA with
24V*
Press mode key and select [Source mA and 24V]. The calibrator supplies loop power of: 24 V [maximum], (typically 21V) and 24 mA. *Special condition for
safe use, see page 3.
K0341 Issue No. 2 8
Page 15
Advanced Options in a Source mode
MODE
F1
Lin
Flow
Valve
Step
Auto-step
Span Check
Ramp
Time (M:SS)
Time (M:SS)
Adjust +1/ -1 second
Adjust +1/ -1 second
F2
Mode
mA source
mA source & 24V
select
Enter
Advanced
select
F2
select
F2
F2
F2
Press the key and select mA Source or mA Source & 24V.
Use and
(Enter) to select the function.
Press the key (Advanced) and the display shows: Linear simulates linear transmitters.
Flow simulates flow transmitters. Valve simulates valve control signals.
Use and
(Enter) to select the Advanced option:
Advanced
Step 25% steps for linear and flow - fixed values for
valve. Auto-step The same as step with a timed step interval. Span Check Step between 4 (or 0) mA and 20 mA. Ramp Automatic ramp between 4 (or 0) mA and 20 mA.
Note: Ramp function not available for valve selection.
Use
to quit.
The display returns to the selected source
mode with the advanced setting available.
9 K0341 Issue No. 2
Page 16
Operation of Advanced Options
Advanced
%
+100.0%
mA
m
A
(24
V
)
CO
M
V
+24.000
mA
Hart® communicator
W
220W
menu selectable loop resistor
Press the key to switch the advanced setting on and off:
e.g.
on or off
Press or to:
step the output up or down. step the span check maximum or minimum start the “ramp”.
Press then to start:
continuous auto-step. or continuous ramp cycle.
Hart® Application
This application allows mA measure and source modes to be used through the Hart® communicator.
K0341 Issue No. 2 10
Page 17
Maintenance
Return the loop calibrator to an authorised ATEX repair centre for any repairs, it cannot be repaired on-site.
To keep the loop calibrator accurate a calibration check should be carried out once per year.
Cleaning
Clean the loop calibrator leather case with a moist, lint­free cloth and weak detergent.
11 K0341 Issue No. 2
Page 18
Battery Replacement
WARNING: ONLY REPLACE BATTERIES IN A SAFE AREA
Only use the battery type listed on page two. Unscrew and remove the securing screw from the battery panel. Replace the batteries, check the polarity of the batteries. Refit and secure the battery panel.
K034 1 Issu e No. 2 12
Page 19
Calibration Instructions
WARNING:
CALIBRATE UPS-III-IS LOOP CALIBRATORS IN A SAFE AREA.
General
The instrument is supplied by the manufacturer, complete with calibration certificate(s). A calibration period of 12 months is recommended. The actual calibration interval depends on instrument usage and the total measurement uncertainty acceptable for the specified application.
The
UPS-III-IS
is a very precise measuring instrument and the test equipment and conditions of test must be suitable for the type of work. The calibration check and calibration adjustment should be carried out in a controlled environment by a calibration technician*.
The manufacturer offers a comprehensive and, if required, UKAS accredited calibration service.
*
A calibration technician must have the necessary technical knowledge, documentation, special test equipment and tools to carry out the calibration work on this equipment.
Calibration Equipment
The following tables give the accuracy requirements for the calibration equipment and the UPS-III-IS. Calibration requires a stable temperature of 21° ±1°C (70° ±2°F).
UPS-III-IS measure mode
Table 3
mA measure
Applied
Permitted UPS-III-IS
mA
0 0.002 0
4 0.002 0.00014 12 0.002 0.00030 20 0.002 0.00046
error (mA)
13 K0341 Issue No. 2
Calibrator error
(mA)
Page 20
Table 4
V measure
Applied V Permitted UPS-III-IS
error (mV)
0 0.004 0.00040 20 0.004 0.00014 40 0.005 0.00064 50 0.005 0.00070
UPS-III-IS source mode
mA source
Applied
mA
Permitted UPS-III-IS
error (mA) 0 0.002 0 4 0.002 0.00012
12 0.002 0.00011
Calibrator error
(mV)
Table 5
Calibrator error
(mA)
20 0.002 0.00015
Calibration Check
1.Connect the UPS-III-IS to the electrical calibrator. Switch on the electrical calibrator and allow it to thermally stabilise.
2.Switch on the UPS-III-IS and allow the instrument to thermally stabilise.
3.Set the UPS-III-IS to mA measure, adjust the electrical calibrator to apply the first value in the table 3. Record the reading of the UPS-III-IS.
4.Repeat step 3 for all the values in the table 3.
5.Compare the recorded values and the applied values if the difference is greater than the permitted error, the instrument requires a calibration adjustment.
6.Repeat this procedure for V measure (table 4) and mA source (table 5).
Calibration Adjustment
1.Connect the UPS-III-IS to the electrical calibrator. Switch on the electrical calibrator and allow it to thermally stabilise.
K034 1 Issu e No. 2 14
Page 21
2.Switch on the UPS-III-IS and press , within two seconds to select Calibration. Enter the access code [9410 factory setting]
and allow the instrument to thermally stabilise.
3.Select the parameter required for calibration. Use the display menu to select the calibration values. After a successful calibration enter the new calibration date.
15 K0341 Issue No. 2
Page 22
F1
F1
Enter
F2
Enter
F2
20 mA ±0.004mA
mA out cal-low
Reading:
mA out cal-high
Reading:
+
20.020
00.000
Enter
F2
mA out control
Check output
1.000
Enter
F2
Again
Check output
mA out control
20.000
Again
Enter
F2
Calibration
Cal. date
V InputV Input
mA Input
mA Output
A
Enter
F2
Calibration
Cal. date
V Input
mA Input
mA Output
Correct PIN entered
mA
Advanced
%
+100.0%
00.000
m
A
mA
m
A(24V
)
CO
M
V
1 mA ±0.002mA
mA
Advanced
%
+100.0%
+01.000
m
A
mA
mA
(24V
)
COM
V
20 mA ±1 mA
mA
Advanced
%
+100.0%
+20.020
mA
mA
mA
(24V
)
COM
V
mA
Advanced
%
+100.0%
+20.000
m
A
mA
mA
(24V)
COM
V
K034 1 Issu e No. 2 16
Page 23
F1
Enter
F2
Enter
F2
Enter
F2
20 mA ±1 mA
Calibration
Cal. date
V Input
mA Input
mA Output
mA input cal-low
Leave mA input open
-0.001
mA input cal-high
mA input ~ 20mA
00.000
+
20.020
Enter
F2
mA input control
Check reading :
1.000
Again
Enter
F2
B
A
Calibration
Cal. date
V InputV Input
mA Input
mA Output
mA
open
Advanced
%
+
1
0
0
.0
%
Leave
m
A
inputopen
mA
mA(24V)
COM
V
mA
source
Advanced
%
+
10
0.0
%
+20.020
mA
mA
mA(24V )
COM
V
mA
source
1 mA ±0.002mA
Advanced
%
+1
00
.0%
+01.000
mA
mA
mA(24V)
COM
V
17 K0341 Issue No. 2
Page 24
49V±1V
V input cal-high
V input ~ 50V
00.000
+
47.438
49V±1V
V input control
Check reading:
49.000
Again
B
CALIBRATION COMPLETE
MORE CALIBRATION SELECTIONS
Enter
F2
Enter
F2
Enter
F2
Calibration
Cal. date
V InputV Input
mA Input
mA Output
V input cal-low
Short V input.
-0.001
F1
Enter
F2
F1
F2
F2
Enter
Calibration
Cal. dateCal.
date
V Input
mA Input
mA Output
Quit
Cal. date: 01-MAR-2006
Enter
Day : 01
Enter
Calibration
Cal. dateCal.
date
V Input
mA Input
mA Output
Enter
Month : 03
Cal. date: 01-MAR-2006
F2
F2
F2
F2
Enter
Year : 2006
Cal. date: 01-MAR-2006
F1
F2
Calibration date
Enter
Again
Check date:
01 MAR 2006
V
source
Advanced
%
+
1
0
0
.
0
%
+49.000 V
Advanced
%
+
1
0
0
.0
%
Short V input
m
A
m
A
(
2
4
V
)
CO
M
V
m
A
m
A
(
2
4
V
)
CO
M
V
V
source
Advanced
%
+
1
0
0
.
0
%
Vin
p
u
t
~
5
0
V
+
4
7.438
m
A
m
A
(
2
4
V
)
CO
M
V
K034 1 Issu e No. 2 18
Loading...