Part No. t64D3333P024-2 Pub, No, 49-8768-2 D-959-0776-002 7-98 CG
Safety Information
5atetyPrecautions..... 3,4
Operating instructions
Usingthe Downdroft
5_sten ........ 5 o
Usingme 6brttroz_ 5
CJJreand Cleanir_g ..... 6
GE& YOUrA ServicePartnership.
IMPORTANT!
Insta#ation lnstl_ctions
Before YouB_ln ....... 7
/_-85ui'et_sn[s 7 9
P/zTningt:heLJuctwod(....... 70
Plan/ngt;helitlirTr_ ..... 77
lnstollin9 toe
[Jowndrafr .... 77 72
sn_//ir1_ the
[7ectrid_7/l}iirmcj....... 73
Troubleshooting Tips
Betor_7ou(;_lll
f-orSavlce ..... 74
Customer Service
ProductReais_ml/on. . . 17
W_Trmnty ..... l_
Service,>ie,pnone
NumbeLs ...... BackCJver
Fill out and return tile Consumer 1)r(iduct Regism_fion Card that is
pa(ked xdih tllis produ(L Ifvou (annl)l find it, please send in tile
dupli(ate (at(] printed in tile ba(k of this manual.
FORYOURRECORDS
Write the model and serial numbers here:
#
#
Staple sales slip or cancelled check here.
PLEASE NOTE: The downdraft vent systemyou have purchased was
designed to be used with GEProfile cooktops listed in this manual
Proof of tile original purchase date is needed 1(/(/blain ser_i(e under
tile W;lI'I_<ln/y,
READTHISMANUAl_
Inskle you will find many h elpfill hints on how to use and maintain your
vent properly.Just a little preventive care on your pro1 can save you a great
deal of time and money over tile lif> of yore vent.
You Hfind man) answers to cflmmon problems in die Before YouCafl For
Service secdon. If you re_ex_ our (:harl of Troubleshooting Tips first, you
may not need t11call for service at all.
IFYOUNEEDSERVICE
If you do need seixice, you can relax knox,ing help is only a phone call
away. A list of toll-flee customer sei_ice numbers is included in the back
2
section 11tthis guide. Or y()u can always call the GE Answer (enter (' at
800.6'26.2000, 24 h(/urs a (1W, 7 (la}:s a week.
IMPORTANTSAFETYINFORMATION.
READALLINSTRUCTIONSBEFOREUSING.
a, WARNING!
Foryour safety, the information in this manual must be followed to minimize the risk of fire or explosion,
electric shock, or toprevent property damage, personal injury, or loss of life.
WARNING--TOREDUCETHERISKOFFIRE,
ELECTRICSHOCK,ORINJURYTOPERSONS,
OBSERVETHEFOLLOWING:
A. Use this refit only in the manner intended by
the mant/f_tcturer. Ifyou have any questions
(ontact the rnantff_cttHer.
R Befbre servicing or cleaning unit, switch
power offat sewice panel and lock fl_e
service disconnecting means to prevent
power fi_m being switched on accidentally.
\,_l_en the service disconnecting means
cannot be locked, securely fhsten a
pr_)minent wanting device, such as a tag, m
the set_ice panel.
CAUTION: For general ventilating use only.
Do not use to exhaust hazardous or explosive
',, Installation wofl< and electrical wiring must
be done by qualified person(s) in
ac(:o_dan(:e with all applicable codes and
slandmds, including fire-rated (:onstmction.
When cutting or (killing into wall or ceiling,
do not damage electrical wiring and other
hidden utilities.
Dncted f_lns must always be vented to file
outdoors.
S_ttficient air is needed for proper
combustion and exhausting of gases through
the flue (chimney) offilel-burning
equipment to prevent bacl;drafling. Follow
the heating e(pfipment manttthcmrer's
glfideline and safety standards such as those
published by the National Fire Protection
Association (NFI'A), and the American
Society for Heating, Refiigeration and Air
Conditioning Engineers (ASHRAE), and the
local code authorities.
To reduce the risk of fire, use only metal
ductwork.
PVC sewer pipe can be used as duct under
concrete slab if allowed by local code board.
This unit must be grounded.
SAFETYPRECAUTIONS
WARNING--TO REDUCETHERISK OFA RANGE TOPGREASEFIRE,"
Keep fan, filters and gTease laden
surfaces clean.
:Always turn hood ON when cooking
at high heat.
Use high range settings on range onlywhen
necessary. Heat oil slowly on low to
medium setting.
:i Don't leave range unattended when cooking.
Ahvays use cookware and utensils
appropriate for the type and amount
of food being prepared.
3
IMPORTANTSAFETYINFORMATION
READALL INSTRUCTIONSBEFOREUSING.
A WARNINGf
SAFETYPRECAUTIONS
TOPERSONSIN THEEVENTOFA RANGE TOPGREASE
FIRE,OBSERVETHEFOLLOWING/
A.
SMOTHER FI[AMES with a close-fitting
lid, cookie sheet, or metal tray, then turn
off the burner. BE CAREFUL TO
PREVENT BURNS. If the flames do not go
out immediamly, E%a_CLTATE AND CALL
THE FIRE DEPARTMENT.
B. NEVER PICK UPA FI[AMING PAN--
Y(_u may be burned.
C. DO NOT USE _,%_TER, indudingwet
dishcloths or toweh-a violent steam
explosion will resuh.
D. Use an extinguisher ONLYif:
L Y(m know you h_we a Class ABC
exting_flsher, and you abeady know how u_
operate it.
Z The fire is small and contained in the m>a
where it started.
3. The fire department is being called.
4. You can fight the fire with your back
to an exit,
2%sodon "KitchenF/?esafelyTIps"publishedhyNFPA
CAUTtON: For g_nera] ventilating use onlyo
Do not use to exhaust hazmdous or explosive
Make sure aft fingers are away from the downdraR
top when it is lowered
ff YouNeed Service...
Do not attempt to l_pair or replace any part of
the downdrafi system unless it is specifically
recommended in this gafide. All other secvicing
should be refen_d to a qualified mchnician.
SERVIC/NC
Be sure electrical power is off before servicing the unit,
It may be necessa_ 7 to remove the @)wndrafi
blower system in o_,ter to sewice (omponems
suth as the blower mou)r or air vent
methanism.
Readandfollow this Informationcarefull'
READAND SAVETHESEINSTRUCTIONS
Disconnect power to fl_e cooktop and remo_v
it first. Reverse the steps in the Install the
Downdraft set fion to remove the blower.
Sel-vice parts are avaihble from a GE Service
and Parts Center.
4
Usingthedowndraftsystem.
RAISE/LOWERSwitch (3o"models only)
Tmn tile dox_ll(hafi blower ONby pressing
the PAISE/LOWER switch located at the top
right of the vent (oil some models). Place
y{)ur finger oil the "center" of the s_xitch
and hold until you observe the vent rot)ring,
then release. The air vent will rise. Use the
sele(tor s_dtch to mrn tile blower ON,OFF
or to dlange the blower speed.
Tile vent may be lowered by again pressing
the PAISE/LOWERs_a_itchat the top right side
of the vent. The blower, if left on, will
On some models, the RAISE/LOWER
switch is located at the top right of
the vent,
mltomafically go offwhen tile vent is
lowered.
NOTE:Formostconvenientoperation,set the
blower tothe speedyou usemostoften. The
blower will come onto thisspeed whenever
theunit is raised.
iii ii! i
RemoteRAISE/LOIIVERswitch
(36"modelsonly)
36" models havea remote RAISE/LOWER
sx_ch. I_ operates in _t_esame manner as
fl_es_dt(:h lot ated on the vent.
RAISE/LOWERswitch location may vary,
Use the selector switch to turn the
blower ON,OFFor to change the
blower speed,
Using the Cooktop
Caution
Be caretnl when raising or lowering tile
dox_lldrafl. Be sure pots, pot handles and
other objecls are clear of tile do_ll(hafl and
cannot be su_uckor tipped by the dox_lldrafi
being raised.
NOTE"Thereisa slight trimoverhangat each
end ofthe vent.
To avoid h-tj_v, be sure f'mgers are clear
of the dow_draft cover when it is behrig
lowered.
Keep hands and f'mgers away from all
downdraft parts.
Using the downdraft system.
Cooking Tips
The high air m_)vement of this dox_i_drafl
system can increase tile cooking times tot
some fi)ods. It may take longer to reach
high cooking temperatures ifthe (h_wndrafi
is turned to high right away. A(!just the tim
speed tor best cooking resuhs.
For best resuhs when heating oil fi_rdeep
fl)qng or when boiling water, use the fiont
smtace uniLsor wait until the water is
boiling or the oil is at flying temperatures
befi)re turning on the (h)wnchafi.
Thedowndralt may not completelycapture aft the
steamfrom panson the front burners,
Careand cleaning of the downdraft system.
Grease filters
Theefficiencyofyourdowndmftd_pendson
acbanfilter
Frequen( 7 of cleaning depends on the tTpe
of cooking you do. Grease fil_ers should be
cleaned at leas[ once a month.
Neverof)eratethe dowrl(2a)withoutthefilter:5
snplace.
Toremove:Lift up and pull _hebo{um_ ore,
Remove d_e left fil_erfirst, d_en shde d_e
righ_ fil_er u_the lef_and remo_ e h.
Catlll_
When canning tbods in a wa/er-bath canner,
a gentle but steady boil nmst be maintained
contimu)usly fi)r the required time.
When canning toods in a pressure canner,
the pressure nmst be re>tint>fined
contimu)usly fi)r the required time,
Use of the blower at HIGHspeed when
canning may reduce the temperature
enough to stop boiling. While canning,
we recommend using the downdmfi at
LOW speed and using the flont surlime unit.
Toclean: Soak and d_en agha_e in a ho_
de_ergem solution. Ligh_ brushing may be
used _o remove imbedded soil. Rinse, shake
and remove moisture before replacing.
Fil_ers may be cleaned by placing in
dishwasher, alfi_ough some sligh_ color
fT_dingmay occur afler several washings.
Whh care_ifi handling, the fiber will lasl for
yems. Ifrepla(emen[ becomes necessary,
order the par{ flom yore dealer.
Painted or metal surfaces
Clean greasysm_ilcesfiequently, using a
miM detergent.
Do not useabrasivecloth or cleaners,steel wool
padsor scouringpowder becausethey will scratch
the surface,
Installationof thedowndraft
WARNING--TO REDUCETHERiSK OFFIRE,ELECTRICSHOCK,ORiNJURY
TOPERSONS,OBSERVETHEFOLLOWING:
system. Read meso instructionscompletely and carefully
A. lns_alla_ior_ work and ele(:_rical wiring mus_ be
done by qualified persons(s) in accord race _d_
all applicable codes and s_andards, inchMing fire-
ra_edcons_rucdon.
B. Ducked f_u_s mus_ always be vetoed _o _he
outdoors.
WARNING--Toreducethe risk of fire, use onlymetal
ductwork.
Before YouBegin
IMPORTANT:Save t,_eseinstructions for the local
electrical inspector's use.
IMPORTAN_ OBSERVEALL GOVERNINGCODES
AND ORDINANCES.
NOTE TOINSTAL£ER:Leave these instructions with
the appliance after installation is completed.
NOTE TOCONSUMER:Keep this Owner's Manual
and installation instructions for future use.
NOTE."This appliance must be properly grounded.
InstallationRequirements
Before starting installation, check the following requirements:
120
4.0
Canbe tmnsitioned to round duct (6" round minimum),
This downdrah blo_ er system is designed u) be used
u_ exhaus_ smoke and odors when cooking with aH
(;E Profile electric and gas cooku_pshs_edh_dfis
manual h (::ar_be mourned in either an island or
500
3_ " X 10"_
Plan the placement of the elecuical outlet carefiflly.
It should NOT be installed on the back wall of the
cabinet be(rauseit may inter{ere with the down&aft.
It should be installed on a side wall or a(!jacent
cabinet. Make sure it iswithin reach of the unit's 2 ft.
long power cord and conforms to all local codes.
Install a stan&ud outlet to make the electrical
connection.
Plan the locathm of the gas supply pipe (for gas
Requirements for an approved installation:
26" minimum cabinet depth
_ 26" minimum flora the back of the &)_lldrafi to
the fiont of the countertop, with
23%" mininmm FIAT countertop smthce
:_Ifyou install the vent and cookt op in an island,
you may need additional island depth. 24" base to
base will not be adequate. Please see below.
cooktops) carefiflly to avoid inter[erence with the
downchaft installation.
Thisunit canbeeasilyinstalledfollowingthese
basicsteps:
[] Cut out the (ountertop opening.
[] Install the (lo_i_(hafl in the cabinet.
[] ( onnect the duclwork and electrical.
[] Install the cooklop.
Measurements
Refer to the cooktop installation instructions tot dimensions of cooktop, countertop cutout,
and cabinet requirements.
Cutout dimension and illustrations am given for 30" and 36" cooktops.
_,The 30" models will fit in most 30" wide cabinets
and the 36"models will fit ir_most 35"wide
cablneN.
:_ Check the inside dimensions of the cabinet before
beginning installation. The top of the side walls
may need to be cut to provide clearance for
mounting.
NOTE" Toinstafl a cooktop with this downdraft,
the cabinet depth must be 26"minimum
A countertop with a raised lip may not allow enough flat
countertop for a proper installation,
Installation of the downdrafl system.
Read these instructions completely and carefully.
30_!Ceektops/Dewndraft Unit J VB36
NOTE: Against-the-waft instaflations are limited due to dimension requirements.
Reter to details below,
Figure I Figure 3
Overall cooktop dimensions Cutoutfor vent
Front edge of countertop to cutout
Figure 2
Overall cutout dimensions
Minimum inside
cabinet clearance
[] [] [] [] s[] [] []
(Figure 1) (F,(gureI) (Figure I) (Figure I) (Fig_,,re3,_) (Figure 2)
Cooktop Cooktop Depth FrontEdge Min,Required
ModelNe. Width Depth Depth )owndraRVent EdgeotCutout Clearance
J P340
JP350 29-3/8" 20-1/2" 2" 22-1/2" 3" 22-11/16"
J P360
J P392 30" 20-3/4" 2" 22-3/4" 2" 23"
J P393
JGP336 30" 21" 2" 23" 3-1/4" 22-7/8"
Required to maintain UL or A6A approvals,
Overall Overall Vent Cooktop+ CounterloptoFront hside Cabinet
Min,Setback--
Exhaust(rightorleft)
Notches may not be needed
depending upon cutout width,
No gas orelectric service
inside shaded area,
[] [] [] []
(Figure2) (Figure2) CFigure3) (Figure3)
Cooktop Cooktop AdditionalDepth CutoutWidth
Cutout Cutout Required tot Required from
Width Depth Downdra[t Centerline
28_1/2" 19_9/16" 2-3/8" 28q/2"
29q/8" 19q5/16" 2-5/16" 28q/2"
28q/2" 19-1/2" 2-5/8" 28q/2"
Dewndraft
36" Cooktops/Downdraft Unit JVB66
NOTE: Against-the-wall installations are limited due to dimension requirements.
Refer to details below.
Figure I Figure3
Overall cooktop dimensions Cutoutfor vent
Island
Front edge of countertop to cutout
Figure2
Overall cutout dimensions
RemoteRAISE/LOWERswitch
(Seethe Installing the
RAISE/LOWERswitch section,)
[] [] [] [] _[]
(FigureI) (Figure I) (Figure I) (FigureI)
Cooktop Ceoktop Depth
Model No.
JP660
JP692
JP693
JGP636
*Required to maintain ULor AGA approvals.
Overall Overall Vent Ceektop +
Width Depth Depth DewndraRVent
35" 20" 2" 22"
35-1/2" 20-3/4" 2" 22-3/4"
35-1/2" 21" 2"
2-1/4"_
6-3/4"_[_
3-1/4"-_.
Exhaust(rightorleft)
Notches maynot be needed
depending upon cutout width,
Minimum inside
cabinet clearance
No gas or electric service
inside shaded area.
......... II'11'I'i
[] [] [] [] [] []
(Figure3*) (Figure2) (Figure2) (Figure2) (Figure3) (Figure 3)
Min.Setback-- DewndraR
FrontEdge Min.Required Cooktop Ceektop AdditienalDepth CuteutWidth
;ounterteptoFrent InsideCabinet Cutout Cutout Requiredfor Requiredfrom
Edgeof Cuteut Clearance Width Depth Downdraft Centerline
2-1/2" 22" 34" 19-9/16" 2-3/8" 34"
23" 34-5/8" 19-15/16" 2-5/16" 34"
23" 3-1/4" 22-11/16" 34" 19-1/16" 2-7/8" 34"
Installationofthe downdrafl system.
Read these instructions completely and carefully.
Planning the Ductwork
[] This downdrafl Uower system is designed
for use _dfl_ 3/i" x 10" (h_dwork (cm_be
mmsifi(med to 6' _ound). Two diffe_ em
discharge (]i_Te(:tionsave mailable xdd_ sMeqo-
side a({iusmmm _br accurate alignment of
Rightdis/barge
Stepsto DetermineFlexible Ducting'sEquivalentLength
] Measme the a(mal amom_t of()f_set
(Maximum 3" re(ommended). The effect
upol_ airflow is dependent upon d_e amomu
of of_get.
Calculate die equivalent duding
[]
allo_%inces using:
( __ h-l.o*_se0 x (14ft. per inch)
=__ tL e(pfi_ alent length.
Ensme diat die total e(lui_ alem lengd_ of
[]
(]u(ting does not ex(eed the maximum
recommendation o_ 150 f>et.
For best perfo_nm'_ee: ( hoose file ducd_lg
[]
option which allows d_e shortest lengfli of
dudwo_ k and a minimum mm_be_ of elbows
and transitions. Check location offiooLjoists,
waffjoists, wall studs, de( tvical _dring ov
plumbing fi, possibD int err>fence.
3X" x 10"
to 6"Round
6" Round 1ft. (per 35" x 10" 5ft.
Straight foot length) 45° Elbow
37Fx 10" 1 ft. (per 37Fx 10" Wall Cap 21 ft.
Straight foot length) 90° FlatElbow 24ft. with Damper
(_ _ 0" Round 35" x 10"
6" 15ft. to 3Y/'x 10" 7ft. Wall Cap 27 ft.
90° Elbow Transition with Damper
0" to 6" Round 5ft. 0" Round
45° Elbow 9 ft. Transition Roof Cap 20 ft.
_ 3W'x 10"
Transition
90° Elbow
0" Round
12ft.
374"x 10" Transition 20ft. 0" Round
90° Elbow 10 ft. 90° Elbow RoofVent 24 ft.
SHOULDNOTEXCEED150EOU/VALENTFT.
*Equivalentlengths of duct pieces are based on actual tests conducted by GEEvaluation Engineering
and reflect requirements for good venting performance. See chart for CFMDuct Length.
0" Round
to 3Y/'x 10"
10
Planning the Wiring
All wire connections and installations must be in
compliance with local codes In the absence of loca!
electrical codes consult the National Electric Code
The (]o_ndraf_ blower system draws 4 AMPS
[]
and requires a 120 VAt!, 60 Hz circuit,
Plan to provide a grom_ded outlet in a
[]
location _dfi(:h will all(m die mlit's p(mer
cord _o reach.
Theoutlet cannotbe located onaback wall,
The outlet needs to be momlted on the side _all
of the (abinet or it (ould be on the ba(k _all of an
adjacent (abinet _dth access dlrough an o _ening
in the sk]e wall. (Based on h)(:al (:odes,)
[_] ()n 36'model, )ian tile P_ISEt£OWER s_d_(:h.
Tile lead _o _he sx_(:h is /= long.
• . _Ott
Preparing to Install the Downdraft System
ChangingBlower Discharge
Discharge left
(shown with rectangular duct)
The vent is shipped wfih the outlet on the leR,
If die position of die dischmge needs _obe moved
so the ductwork does not inteHere with floor joists,
plumbing or wMng below, make die following
changes:
To change die dischmge ii()m left _orighh remove
the screws holding die outle_ panel _odie bottom ()i
the venL Remove and rotate the panel and fi_sten
wi_h the screws.
Preparing the Blower
A transition is provided to (onne( t a 3E" x 10" (h]ct
_o die blowe_. A_ach _he (]ud mmsi_ion _o _he _op
of die blower wi_h the screws provided. The blower
has holes dlat ma_(h die _ransifion.
Donot driftadditional holesin the blower
If r(nmd ducfing is used, mmsidon to 6' _Druid to
connect _o_he inle_ of the blower.
The bl()v, er can b e m (mn ted in tlle ca bi net (,7u nd er
die floor. The blower will fit between fl()or ioisls on
-t
_6 (:ente_ s.
/
Throughthefloor
phown withrectangularduct)
For installations where the blower is mourned
in die cabineL a_tach _he moml_ing suppo_ _sto file
corners of die blower housing on die motor side of
_hemotor housing
K Ihe blo_x er is installed raider Ihe floor, at_a(:h tlle
suppor_ legs to the corners of die blower housing on
Ihe side dla_ tlle inlet duct a_taches.
The support legs are a(]iusmble for heigh_ by sliding
die _wo halves and tightening die bobs xdlen
ex_ended to tlle desired lengdl.
Discharge right
(shown wiffl (V'round duct) _ /
Installationofthe downdraflsystem.
Read these instructions completely and carefully.
Installing the Dewndraft
[] Se_ d_e dowr_draf_ imo d_e operfir_g.
] Secure die do_,_ndraf_ _o_he (:()_]]_]_e__op as Mounting%revvs
follow, s: Hold d_e do_ ndrafi agains_ d_e ba(k
of the ( oumertop cutout and tighten the
2 ]{]]()l]n[ii]g scKews (one on erich ef]d ()f!]ni[)
on d_e underside of d_e ('oun_er_op. Use 7_
wood shim between _he soew kind _he
underside of gnmi_e coun_eHops.
Thele me holes p_()_ded _o aHa(::h die
[]
stabilizing-map u) eidler side of tile do_ ndrafi.
Fasten die odle_ end of tile sin@ to tile ba(k or
side wall of die cabinet.
If insta/fingon atile sur£ace,it may be necess-afyto
app/'/locallyapprovedcaulking alongthe back arid
sidesto coverg@s,
Installing the Ductwork
CAUTION--BEFORE CUTTkYGA HOLEIN CABINET FOR
DUCTWORK' @eck for interference with fioo,,joists,
wall studs, electrical wiring or plumbing.
[] Cut die hole in die cabinet as_ell as holes in
tile wall o_ f]oo_ as ne(:essm}.
Mount die roof or _all cap and work back
[]
to_ards tile (abinet and blo_er, mmching all
duc[v_oFk, e]bov, sand t_a_lsJtions aspfevio_as]}
}Janned. Tape aH du(:t_, ork (:onne(:dons to
make them se(:ure and air dgb.
Installing the RAISEtLOWER Switch Ig_somemodels)
The RAiSE/LOWER swit dl can be installed in tile
(:ounter_op, (abinet fh(:e or wail near tile do_ n(kafl.
Detem_ine where you t_4sh to place tile remote
mount RAISE/LOWER switch, Keep in mind t]lat the
wiring lead ]engdl for die switch is 72 inches. The
connector at die end of die leads plugs into a
madng (onnector loomed h-_the ( omro] box.
Aft e_ se]ecdng
[]
the ]ocadon of
the _witc]< dd]]
_ ]/8" hole in
the smii_ce
sele(ted_ i.e.
Countersink
] ]/]6"toa
a small knot in
tile switch leads
asshown in this
figure. The knot shouk] be as (:lose U) tile
s_,@thas possible so flint is fits imo tile
(:ountersink. This provides fi)r suain relief.
Mount tile mem] switch bracket, _it]l eidler the
s(:re_sprovided or locally approved adhesi,,e, over
the countersink.
Make surethebracket is orientedwith the centersection
touchingthemountingsurbce.
Peel tile film flom tile ba(:k of tile trim to
[]
expose die adhesi,,e and dlread die e]e(:uica]
leads dlrou£h tile moundng b_a(:ket ]/8'
hole and into tlle cabinet.
Kmounted on a tilesm_hce,make the
hole ]mge enough for wi_es (i.e. between die
se(:dons) and use locally approved cm_]king
to cover any gaps m'ound the base ()f the
Snap tile Uim body onto tile mounting
bracket and press to set die adhesive.
Attach die 2 leads to tile two-prong }Jug and
[]
p]u_int()thepan e]on tile_ent.R()_]teand tie
tile s_4t(;]l leads and any excesswi_e ]en_lh so
die,, wi]] not be phlched or caught dmin_
operadon of tile vent o_"b) an mdc]e sto_ed
_4dlin tile cabinet.
/2