GE JAS02SN4SS Installation Guide

Installation Instructions
GE Compact Electric Ranges
Questions? Call! .800.GE.CARES(1.800.432.2737)or visit www.GEAppliances.com
In Canada,call 1.800.561.3344 or visit www.GEAppliances.ca
ITI PREPARE THE OPENING (FOR INDOOR USE ONLY)
See illustrations for all rough-in and spacing dimensions. The range may be placed with 0" clearance (flush) at the back wall and side walls of the cabinet.
' L---J ,
BEFORE YOU BEGIN
Read these instructions completely and carefully,
" IMPORTANT -- Savetheseinstructions
" IMPORTANT -- Observeall
governing (:odes and ordinances.
Note to Installer- Be sure to leave these instructions with consumer.
Note to consumer - Keep these instructions for future reference.
Skill level- Installation of this appliance
requires a qualified installer or electrician.
Proper installation is the responsibility of the installer.
. Product failure due to improper installation is
not covered under warranty.
FOR YOUR SAFETY:
! A D .
Achild or adult cantip the range and be killed.
Install the anti-tip brackettothe wall orfloor.
Engagethe rangeto the anti-tip bracket bysliding the range backsuchthat the foot isengaged.
Re-engagetheanti-tip bracket ifthe range is moved.
Failureto do socan result in death or seriousburns to childrenor adults.
Tip-Over Hazard
Anti-Tip Bracket
Kit Included
ikWARNING -- Beforebeginning
If you did not receive an anti-tip bracket with your purchase, call 1.800.626.8774 to receive one at no cost. (In Canada, call 1.800.561.3344.) For installation instructions of the bracket,
visit: www.GEAppliances.com. (In Canada, www.GEAppliances.ca.)
MATERIALS YOU MAY NEED TOOLS YOU WILL NEED
@
Squeeze Connector (ULListed 40 AMP)
(For Conduit 4-Wire Cord 4' long OR
Installations Only) 3-Wire Cord 4' long
the irrstallation, switch power off at service
panel and lock the service disconnecting
means to prevent power from being switched on accidentally, When the service disconnecting means cannot be locked, securely faslen a prominent warning device, such as a tag, to the service panel.
Drill with 1/8" Bit Tin Snips Safety Glasses Tape Measure A(!justable Wrench Pliers
Level 1/4" Nut Driver
IT] REMOVE PACKAGING MATERIALS: Failureto remove packaging materials could
resultindamage to the appliance.Remove allpacking parts from oven, racks,heating elements and drawer. Also,remove protectivefilm and labelson the outer door,cooktop and controlpanel.
combustible walls above
cooking
2" side
Wall Mounted
open)
2L,
Recommended acceptable electrical outlet
area Orient the electrical receptacle so the
length is parallel to the Floor
NOTE: Use a 4' power cord to prevent interference with the storage drawer. Power cords 4_' to 6' long
may have to be dressed to allow for proper drawer (:losing.
MINIMUM DIMENSIONS BETWEEN COOKTOP, WALLS AND ABOVE THE COOKTOP:
A. Make sure the wall covering, countertop, flooring
and cabinets around the range can withstand the heat (up to 200_'F) generated by the range.
B. Allow 30" minimum clearance between surface
units and bottom of unprotected wood or metal cabinet, or allow a 24" minimum when bottom of wood or metal cabinet is protected by no less
than 1/4" thick flame retardant millboard covered with not less than No 28 MSG sheet metal, (.015"),
.015" thick stainless steel, .024"
aluminum or .020" copper.
C. This appliance has been approved for 0" spacing to acljacent surfaces above the cooktop. However,
a 2" minimum spacing to surfaces less than 15" above the cooktop and adjacent
cabinet is recommended to reduce exposure to steam, grease splatter and heat.
To reduce the risk of burns or fire when reaching over hot surface elements, cabinet storage space above the cooktop should be avoided. If cabinet storage space is to be provided above the cooktop, the risk can be reduced by installing a range hood that projects at least 5" beyond the front of the cabinets. Cabinets installed above the cooktop must be no deeper than 13".
NOTEC
Models A JAS02 44 _"
JA624 47"
B
Both Sides
A _
ELECTRICALREQUIREMENTS
AWARNING: This appliance must be properly grounded. AWARN ING: All new corrstructions, mobile homes, recreational vehicles and installations where
local codes do not allow grounding through neutral, require a 4-conductor UL-listed range cord.
AWARNIN6: Topreventfireor shock,do not useanextensioncordwith this appliance. AWARNING: To prevent shock, remove house fuse or open circuit breaker before
beginning installation,
We recommend you have the electrical wiring and hookup of your range connected by a qualified electrician, After installation, have the electrician show you how to disconnect power from the range,
You must use a single-phase, 120/208 VAC or 120/240 VAC, 60 hertz electrical system, If you connect to aluminum wiring, properly installed connectors approved for use with aluminum wiring must be
used,
Effective ,January 1, 1996, the National Electrical Code requires that new construction (not existing) utilize a 4-conductor connection to an electric range. When installing an electric range in new
construction, mobile home, recreational vehicle, or an area where local codes prohibit grounding through the neutral conductor, refer to the section on four-conductor branch circuit connections,
Check with your local utilities for electrical (:odes which apply in your area, Failure to wire your oven according to governing codes could result in a hazardous condition, If there are no local (:odes, your
oven must be wired and fused to meet the National Electrical Code, NFPA No. 70 - latest edition, available from the National Fire Protecti on Association,
This appliance must be supplied with the proper voltage and frequency, and connected to an individual, properly grounded, 40 amp (minimum) branch circuit protected by a circuit breaker
or time-delay fuse, Use only a 3-conductor or a 4-conductor UL-listed range cord, These cords may be provided with ring
terminals on wire and a strain relief device,
A range cord rated at 40 amps with 125/250 minimum volt range is required, A 50 amp range cord is not recommended but if used, it should be marked for use with nominal 1_" diameter connection
openings. Care should be taken to (:enter the (:able and strain relief within the knockout hole to keep the edge from damaging the (:able,
The rating plate is located on the side of the drawer frame or under the cooktop. Note: Use of automatic, wireless or wired external switches that shut off power to the appliances, are
not recommended for this product.
r4-1 POWER CORD AND CONDUIT INSTALLATION
r_ Remove wire (:over (on the back of range) by removing screws using a 1/4" nut driver. You can
access the terminal block by either removing a terminal block (:over (on some models) or the wire (:over, Do not discard these screws,
Back of range Back of range
5 screws to
wire
(:over
Wire cover
@
For power cord and 1" conduit only, remove the knockout ring (1_") located on bracket directly
below the terminal block. To remove the knockout, use a pair of pliers to bend the
knockout ring away from the bracket and twist until ring is removed.
Term in aIb lock _'_L--_,_.r_L_ _-.,t
(appearance ----_ _L_[_,I
ringin I r _ _ :: 1/
bracket i
Knockout ring ___
Femoved
For power cord installations only (see the next step if using conduit), assemble the strain relief in the hole. Insert
the power cord through the strain relief and tighten. Allow enough slack to easily attach the cord terminals to the terminal block. If tabs are present at the end of the winged strain relief, they
can be removed for better fit. NOTE: Do not install the power cord without a
strain relief. The strain relief bracket MUST be installed before reinstalling the rear range wiring cover.
Strain relief
Power cord
Terminal block (:over
Terminal block
Bracket
Rating
SIDE OF THE DRAWER UNDERTHECOOKTOP
Rating plate
r61For 3/4" conduit installations only, purchase a squeeze connector matching the diameter
of your conduit and assemble it in the hole, Insert the conduit through the squeeze connector and tighten, Allow enough slack to easily attach the wires to the terminal block, NOTE: Do not insta IIthe conduit without a squeeze connector. The squeeze connector MUST be installed before reinstalling the rear range wiring (:over.
block
Proceed to step 5 or 6.
r_ 3-WIRE INSTALLATION (GROUND ISTHROUGH THE NEUTRALWIRE) AWARNING: Shock Hazard
The neutral wire and ground strap must be connected as shown below for the range to be
properly grounded. Do not remove the ground strap. Failure follow this instruction may result in potential
shock hazard.
Terminal block
(appearance may vary)
Power Cord
AWARNING: Fire hazard Neutral
Terminal block screws must be securely tightened, terminal Failure to do so may result in potential fire hazard.
FOR POWER CORD INSTALLATION strap A. Remove the 3 lower screws from the terminal Ground
block. Do not loosen the upper screws, plate B. Do not cut or remove the ground strap.
C. Insert the 3 screws through each power cord Red or
terminal ring and back into the terminal block. Be Black certain the white wire is in the (:enter. Securely tighten each screw (35 to 50 in-lbs.)
FOR CONDUIT INSTALLATION A. Loosen the 3 lower screws on the terminal block. Do not
loosen the upper screws. B. Do not cut or remove the ground strap, C. Insert the bare wire tip (insulation stripped 5/8") into the
bottom terminal block openings, Be certain the white
wire is in the (:enter, On certain models, the wire must
be inserted through an opening in the ground strap,
Securely tighten each screw onto each wire (35 to 50
in-lbs.), tips NOTE; Aluminum building wire may be used but it must be rated for the correct amperage and voltage,
Power cord
PROCEEDTOSTEP7.
Conduit
Terminal
Wire
Black
Conduit
\ White
Red or Black
r_ 4-WIRE INSTALLATION (SEPARATE GROUND WIRE) AWARNING: Shock Hazard
The neutral wire and ground strap must be connected as shown below for the range to
be properly grounded. Do not remove the
ground strap. Failure follow this instruction may result in potential shock hazard.
Before-Power Cord and Conduit
Terminal //_--_/L_'x_XX_ Ground strap
AWARNING: Fire hazard
Terminal block screws must be securely tightened.Failuretodo so may resultin
potentialfirehazard. FOR POWER CORD INSTALLATION A. Remove the 3 lower screws from the
terminal block. Do not loosen the upper screws.
B. Remove the ground screw and ground plate
and retain them.
C. Cut the ground strap below the terminal __,_ #___
block and discard the lower section. Terminal
D. Insert the ground screw through the ground block ,._I_I
plate (removed earlier) and back into the °_X- range frame. Tighten securely, but do not
over-tighten (15 to 20 in-lbs.) Red or
E. Insert the 3 terminal screws through each Black _ \x_
power cord terminal ring and back into the terminal block. Be certain the white wire is
in the (:enter. Securely tighten each screw (35 to 50 in-lbs.
FOR CONDUIT INSTALLATION A. Remove the 3 lower screws from the
terminal block. Do not loosen the upper screws.
B. Remove the ground screw and ground plate
and retainthem.
C. Cut the ground strap below the terminal block
and discard the lower section.
D. Insert the bare ground bare wire tip (insulation),e![_l, inal --'-'_
stripped 5/8") between the range frame and the ground plate (removed earlier) and secure it in place with the ground Wire screw. Tighten securely, but do not over- tips tighten (15 to 20 in-lbs).
E. Insert the wire tips (insulation stripped 5/8") Black
into the bottom terminal block openings. Be certain the white wire is in the center. On
certain models, the wire must be inserted Ground through an opening in the ground strap, screw Securely tighten each screw onto each wire (35 to 50 in-lbs.)
NOTE: Aluminum building wire may be used but it must be rated for the correct amperage and voltage.
block -- ii-_}l or
Ground f _ _, strap Neutral
terminal
After-Power Cord
Neutral
Ground plate (grounding to range)
White ,_ Ground _ screw
Red or
Black
or Bare
\
After-Conduit
UIUt_R
Green
or Bare
Ground plate (grounding to
_ange)
Red or_
31-10981 08-14 GE
Loading...
+ 5 hidden pages