GE GTX52GASPWB Specifications

SIDE VIEW
REAR VIEW
GE® 6.2 cu. ft. Capacity Aluminized Alloy Drum Gas Dryer
DIMENSIONS AND INSTALLATION INFORMATION (IN INCHES)
EXHAUST OPTION: When viewed from the
front of the unit, exhaust 3-way via rear, left and bottom. Dryer is shipped exhausted to the rear. Alternate exhausting knockouts are supplied.
GAS: An individual, properly-grounded branch circuit, with a three-prong grounding­type receptacle, protected by a 15 or 20 amp circuit breaker or a time-delay fuse is required.
GAS DRYER ELECTRIC RATING:
120V, 60Hz, 6A
GAS (BTU/HR): 22,000. Factory-equipped for natural gas. Tested for LP gas. LP gas supply requires a conversion kit. Check installation instructions for correct kit and have a qualified gas technician install a conversion kit. See dryer ducting information for proper installation.
SPECIAL INSTALLATION REQUIREMENTS ALCOVE OR CLOSET INSTALLATION:
- If your dryer is approved for installation in an alcove or closet, it will be stated on a label on the dryer back.
- The dryer MUST be exhausted to the outside.
- Minimum clearances between dryer cabinet and adjacent walls or other surfaces are:
NOTE: Dryer wall outlet must be located within 36" of service cord entry and accessible when dryer is mounted in position.
INS TA LLATI O N IN F O RMATI O N: For complete information, see installation instructions packed with your dryer.
0" either side; 1" front, top and rear
- Closet doors must be louvered or otherwise ventilated and must contain a minimum of 60 sq. in. of open area equally distributed. If this closet contains both a washer and a dryer, doors must contain a minimum of 120 sq. in. of open area equally distributed.
- No other fuel-burning appliance shall be installed in the same closet with a gas dryer.
BATHROOM OR BEDROOM INSTALLATION:
- The dryer MUST be exhausted to the outdoors.
- The installation must conform with the local codes, or in the absence of local codes, with the National Electric Code and National Fuel Gas Code, ANSI Z223 for gas dryers.
MINIMUM CLEARANCES OTHER THAN ALCOVE OR CLOSET INSTALLATION:
- Minimum clearances to combustible surfaces are: 0" both sides; 1" rear
DRYER EXHAUSTING INFORMATION :
Use metal duct only, vertical and horizontal ducting.
22-1/2"
26-3/4"
37-1/2"
4-1/4"
4"
44"
1-3/4"
3-1/4"
27"
Power Cord 4-1/2"
11-3/4"
5"
For answers to your Monogram, GE Café™ Series, GE Profile™ Series or GE Appliances product questions, visit our website at geappliances.com or call GE Answer Center® Service, 800.626.2000.
Specification Created 4/20
A
B
4"
GE Dryer Vent
B
2-1/2"
GE® 6.2 cu. ft. Capacity Aluminized Alloy Drum Gas Dryer
FOR COMPLETE INFORMATION, SEE INSTALLATION INSTRUCTIONS PACKED WITH YOUR DRYER.
DUCTING MATERIALS:
For best performance, this dryer should be vented with 4" diameter all rigid metal exhaust duct. If rigid metal duct cannot be used, then UL-listed flexible metal (semi-rigid) ducting can be used (Kit WX08X10077). In special installations, it may be necessary to connect the dryer to the house vent using a flexible metal (foil-type) duct. A UL-listed flexible metal (foil-type) duct may be used ONLY in installations where rigid metal or flexible metal (semi­rigid) ducting cannot be used AND where a 4" diameter can be maintained throughout the entire length of the transition duct. Please see installation instruction packed with your dryer for complete instructions when using flexible metal (foil type) ducting.
EXHAUST LENGTH CALCULATION:
1. Determine the number of 90° turns needed for your installation. If you exhaust to the side or bottom of dryer, add one turn.
2. The maximum length of 4" rigid (aluminum or galvanized) duct which can be tolerated
is shown in the table. A turn of 45° or less may be ignored. Two 45° turns within the duct length should be treated as a 90° elbow. A turn over 45° should be treated as a 90° elbow.
Dryers must be exhausted to the outside.
CAUTION: For personal safety do not terminate exhaust into a chimney, under any enclosed house floor (crawl space), or into an attic, since the accumulated lint could create a fire hazard or moisture could cause damage. Never terminate the exhaust into a common duct or plenum with a kitchen exhaust, since the combination of lint and grease could create a fire hazard.
Exhaust ducts should be terminated in a dampered wall cap to prevent back drafts, bird nesting, etc. The wall cap must also be located at least 12" above the ground or any other obstruction with the opening pointed down.
FOR MORE INFORMATION ON VENTING KITS AND ACCESSORIES, PLEASE CALL 1-800-GE-CARES.
DRYER EXHAUSTING INFORMATION— USE METAL DUCT ONLY VERTICAL AND HORIZONTAL DUCTING
BEST PERFORMANCE
Maximum length
A
Number
of 90°
Domestic dryer models
Long Vent 6.1-7.4 cu. ft. capacity electric & gas (GTD33, GTD42, GTD45, GTD65, GTX22, GTX33, GTX42 and GTX65)
For every extra 90° elbow, reduce the allowable vent system length by 10 ft. Two 45° elbows will be treated like one 90° elbow. For the side exhaust installations, add one 90° elbow to the chart. When calculating the total vent system length, you must add all the straight portions and elbows of the system (including the transition duct.
of 4" dia rigid metal duct
Exhaust hood type
A
turns
0 120 ft. 90 ft.
1 100 f t. 75 ft. 2 85 ft. 65 ft. 3 70 ft. 55 f t. 4 60 f t. 45 ft. 5 55 ft. 35 ft.
4"
opening
opening
B
2-1/2"
For answers to your Monogram, GE Café™ Series, GE Profile™ Series or GE Appliances product questions, visit our website at geappliances.com or call GE Answer Center® Service, 800.626.2000.
Specification Created 4/20
Loading...
+ 1 hidden pages