0
ge.com
®
Safetg Information ............. 2
Installation Instructions .... 3-14
Step-bLI-step instructions ........ 6-14
Operating Instructions
Breaking a salt bridge ............. 16
Cleaning the nozzle and
venturi assemblg .................. 16
Features .......................... 17
Service ..................... 15, 18-20
Water softener sgstem ......... 15-20
Care and Cleaning ............. 21
Troubleshooting Tips ...... 22-24
Consumer Support
Consumer Support ........ Back Cover
Parts list/catalog ............... 27-30
WarrantLl (U.S.) .................... 31
WarrantLI (Canada) ................ 32
Water
Softening
Sgstem
Models GXSH39E, GNSH45E
Sistema Suavizante
de Agua
Modelos GXSH39E, GNSH45E
La secci6n en espa_ol empieza en la p6gina 33
0
Sgstem tested and certified bg NSFInternational against NSF/ANSI Standard 44 for the
chemical reduction claims specified on the performance data sheet.
Sistema probado g certificado par NSFInternational contra norma 44 de NSF/ANSIpara las
afirmaciones de reducci6n de los productos quimicos especificadas en la hoja de datos de
funcionamiento.
Sgstem Tested and Certified bg the Water Qualitg Association against CSAB485.!.
Sistema probado g certificado par Water Qualitg Association en cumplimiento con CSAB485.!.
Write the model and serial
numbers here:
Model #
Serial #
To find these numbers, lift the
cover and look on the rim
below the control panel.
7283950 215Cl173P025
49-50180-2 09-08JR
IMPORTANT SAFETY INFORMATION.
READ ALL INSTRUCTIONS BEFORE USING.
WARNING!
For Four safet_l, the information in this manual must be followed to minimize the risk of electric
shock, property damage or personal injury.
SAFETYPRECAUTIONS
Check and comply with your state and local codes.
You must follow these guidelines.
iiiilDiiii:,
Use care when handling the water softening
system. Do not turn upside down, drop, drag
or set on sharp protrusions.
Water softening systems using sodium chloride
(salt) for recharge add sodium to the water.
Persons on sodium restricted diets should consider
the added sodium as part of their overal! intake.
Potassium chloride can be used as on alternative
to sodium chloride in your softener.
The water softening system works on 24 volt-60 Hz
electrical power only. Be sure to use only the
included transformer.
Transformer must be plugged into an indoor
120 volt, grounded outlet only.
Use clean water softening salts only, at least 99.5%
pure. NUGGET,PELLETor coarse SOLARsalts are
recommended. Do not use rock, block, granulated
or ice cream making salts. They contain dirt and
sediments, or mush and cake, and will create
maintenance problems.
Keep the salt hole cover in place on the softener
unless servicing the unit or refilling with salt.
WARN!NG:00notusewithwaterthat
ismicrobiologically unsafe or of unknown quality
without adequate disinfection before or after the
system.
PROPERINSTALLATION
This water softening system must be properly installed and located in accordance with the
Installation Instructions before it is used.
iiiilDiiii:_
Install or store where it will not be exposed to
temperatures below freezing or exposed to any
type of weather. Water freezing in the system will
break it. Do not attempt to treat water over !O0°R
Do not install in direct sunlight. Excessivesun or
heat may cause distortion or other damage to
non-metallic parts.
Properly ground to conform with all governing
codes and ordinances.
;, Use only lead-free solder and flux for all
sweat-solder connections, as required by
state and federal codes.
iiiiiiiiii;,
Thewater softening system requires a minimum
water flow of three gallons per minute at the inlet.
Maximum allowable inlet water pressure is 125 psi.
If daytime pressure is over 80 psi, nighttime pressure
may exceed the maximum. Usea pressure reducing
valve to reduce the flow if necessary.
Softener resins may degrade in the presence of
chlorine above 2 ppm. If you have chlorine in excess
of this amount, you may experience reduced life
of the resin. In these conditions, you may wish to
consider purchasing a GEpoint-of-entry household
filtration system with a chlorine reducing filter.
WARNING: Discard all unused parts
and packaging material after installation. Small
parts remaining after the installation could be
a choke hazard.
READ AND FOLLOW THISSAFETY INFORMATION CAREFULLY.
SAVE THESE INSTRUCTIONS
I
stall ti
Water Softening System
I
str cti
Models G×SH39E and GNSH45E
WARNING: Read entire manual. Failure to follow all guides and rules could cause personal
injury or property damage.
• Check with your state and/or local public works department for plumbing codes. You must follow their
guides as you install the Water Softening system.
NOTE: Failure to comply with these installation instructions will void the product warranty, and the
installer will be responsible for any service, repair or damages caused thereby.
BEFORE BEGINNING INSTALLATION
Read these instructions completely and carefully.
•IMPORTANT - Savetheseinstructions
for local inspector's use.
• IMPORTANT - Observeallgoverning
codes and ordinances.
• Note to Installer- Be sure to leave these
instructions with the Consumer.
Note to Consumer - Keep these instructions
for future reference.
Proper installation is the responsibilitg of the
installer.
Product failure due to improper installation
is not covered under the Warranty.
A shutoff valve must be available or added near
the installation point.
IMPORTANT INSTALLATION
RECOMMENDATIONS
• In the Commonwealth of Massachusetts,
Plumbing Code 248 CMR shell be adhered to.
Consult with your licensed plumber.
• Use onlg lead-free solder and flux for oil sweat-
solder connections, as required bg state and
federal codes.
IMPORTANT INSTALLATION
RECOMMENDATIONS (CONT.)
Use care when handling the softener. Do not
turn upside down, drop, drag or set on sharp
protrusions.
Maximum allowable inlet water pressure is 125
psi. If dagtime pressure is over 80 psi, nighttime
pressure mog exceed the maximum. Use o
pressure reducing valve if necessorg. (Adding o
pressure reducing valve mag reduce the flow.)
The softener works on 24 volt-60 Hz electrical
power onlg. Be sure to use the included
transformer. Be sure the electric outlet and
transformer are in an inside location to protect
from moisture.
• See Where to Install the Softener section
for more details.
-&WARNING: Do not use with water
that is microbiologicollg unsafe or of unknown
qualitg without adequate disinfection before or
after the sgstem. The water should be tested
periodicollg to verifg that the sgstem is
performing satisfactorilg.
• Small ports remaining after the installation could
be a choke hazard. Discord safelg.
• Connect the softener to the main water supplg
pipe before or ahead of the water heater.
DO NOT RUN HOT WATER THROUGH THE
SOFTENER. Temperature of water passing
through the softener must be less than 120%.
Installation Instructions
UNPACKING AND INSPECTION
Be sure to check the entire softener for ang
shipping damage or parts loss. Also note damage
to the shipping cartons. Contact the transportation
compang for all damage and loss claims. The
manufacturer is not responsible for damages
in transit.
Small parts needed to install the softener are
packaged either in a bag or on a cardboard
sheet. To avoid loss of the small parts, keep them
packaged until gou are readg to use them. Be sure
not to discard components hidden in packaging.
TOOLS AND MATERIALS REgUIRED
FOR INSTALLATION
• Pliers
• Screwdriver
• Teflon tape
• Razor knife
o
Two adjustable wrenches
o
Additional tools mag be required if modification
to home plumbing is necessarg.
In and out fittings included with the softener are
1" NPT male adapters. You should maintain the
same, or larger, pipe size as the water supplg
pipe, up to the softener inlet and outlet. Then,
use the necessorg adapters to connect the water
supplg to the 1" NPT male adapters.
Use the included bgpass valve to install the
softener. The bgpass valve allows gou to turn off
water to the softener for servicing, but still have
water in the house pipes. The in and out fittings
referred to above connect to the bgpass valve
with the included bgpass clips.
WHERE TO INSTALL THE SOFTENER
Place the softener us close as possible to a
sewer drain, or other acceptable drain point
or standpipe.
It is recommended to keep outside faucets
on hard water to save soft water and salt.
Do not install the softener in a place where it
could freeze. Freeze damage is not covered bg
the warrantg.
Do not install the softener where it would block
access to the water heater or access to the main
water shutoff.
Put the softener in a place where water damage
is least likelg to occur if a leak develops. The
manufacturer will not repair or pug for water
damage.
A 120-volt electric outlet is needed to plug in the
included transformer. The softener has a 10-foot
power cable. If the outlet is remote (up to 100
feet), use 18 gauge wire to connect. Be sure the
electric outlet and transformer are in an inside
location, to protect from wet weather. Be sure
the outlet is unswitched to prevent accidental
shutoff.
If installing in an outside location, gou must
take the steps necessarg to assure the softener,
installation plumbing, wiring, etc., are as well
protected from the elements (sunlight, rain, wind,
heat, cold), contamination, vandalism, etc., as
when installed indoors. Outdoor installation is
not recommended, and voids the warrantg.
Keep the softener out of direct sunlight.
The sun's heat mag distort non-metallic
parts and mug damage the electronics.
Use appropriate fitting/pipe material (i.e.,copper,
brass, galvanized or CPVC)to connect the 1" NTP
plastic adapters to the house plumbing.
If additional drain hose is needed for valve and
salt tank drains, it can be ordered from GE Parts
at 800.626.2002, part number WS07X10004.
If a rigid valve drain is needed to complg with
plumbing codes, gou can bug the parts needed
to connect u 1/2" copper tubing or plastic pipe
drain. See Step 5.
Clean nugget or pellet water softener salt is
needed to fill the brine tank. See Step 9.
4
Installation Instructions
PLAN HOW YOU WILL INSTALL THE
SOFTENER
You must first decide how to run in and out pipes
to the softener. Look at the house main water pipe
at the point where you will connect the softener.
Is the pipe soldered copper, glued plastic or
threaded galvanized? What is the pipe size?
TYPICAL INSTALLATION ILLUSTRATION
WARNING: Useonly lead-free solder and
flux to prevent lead poisoning.
See Typical Installation Illustration. Use this as a guide
when planning your particular installation. Be sure
to direct the incoming hard water supply to the
softener valve inlet fitting. The valve is marked
IN and OUT.
OPTIONAL 3-VALVE BYPASS
INSTALLATION ILLUSTRATION
Hard water
Soft water
24V
transformer
120-volt
outlet
to outside
PIPE faucets
Inlet
valve
F
Hard
water
Fig. 1
from the left. Include single
water
From
softener t
outlet
CROSSOVER
Use if water supply flows
or 3-valve bypass.
To softener
inlet
O-rings (2)
NOTE: See Drain
Hose Connections
section.
Soft
water
_'X O-rings (2)
INLET Clips (2)
SALT
GOES
HERE
Fig. 2
from the left. Include single
Hard
water
From
softener _,To softener
outlet inlet
CROSSOVER
Use if water supply flows
or 3-valve bypass.
Soft
water
1" NPT male
adapter (2)
3-Valve Bypass
System
For soft water
service:
• Open the inlet
and outlet
valves
• Close the
bypass valve
For bypass hard
water:
• Close the inlet
and outlet
valves
• Open the
bypass valve
Installation Instructions
BEFORE YOU BEGIN
• Turn off the gas or electric supplg to the water
heater, in the possibilitg that the water heater
mag be drained while draining pipes.
• Turn off the water supplg to pipes to be cut and
drain the house water pipes.
• Open both hot and cold faucets at the lowest
location possible.
NOTE: For easier installation, remove the top cover.
Release 2 clips at rear of cover. Rotate cover
forward and lift up.
INSTALL BYPASS VALVE
• Remove plastic shipping plug and wire from valve
outlet. Turbine
_ Valve outlet
• support
NOTE: Be sure the turbine and support are firmlg
in place in the valve outlet. Blow into the valve port
and observe the turbine for free rotation.
Push the bypass valve (lubricate o-ring seals with
silicone grease) into both ports of the valve as
shown.
Turbine shaft and
1-_ INSTALL DRAIN FITTING
• Push the drain fitting (lubricate o-ring seals
with silicone grease) into the part of the valve
as shown.
• Snap the large plastic clip in place, from the
top down as shown. Be sure the clip sneps into
piece. Pull on the drein fitting to meke sure it is
held securely in piece.
Drai
HOVE THE SOFTENER ASSEMBLY
INTO INSTALLATION POSITION
Before sliding softener in position, be sure the
installation surface is level and smooth. Sharp
objects under the tank may puncture it. If needed,
place the tank on a section of 3/4" thick (minimum)
plgwood. Then, place shims under the plgwood as
needed to level the softener. Slide softener into
position.
dapter
O-ring seal goes into the outer
groove only. The clip snaps into
the inner groove (see below).
• Snap the 2 large plastic clips in place, from the
top down, as shown.
SIDE Clip
VIEW
Valve
inlet or
• Push the NPTadapters (lubricate o-ring seals with
silicone grease) into both ports of the valve as
shown
• Snap the 2 large plastic clips in place, from the
side, as shown.
END
VIEW
valve
all the way in}
Installation Instructions
PLUMB "IN" AND "OUT" PIPES
TO AND FROM SOFTENER
-4,CAUTION: Observea,ofthefollowing
cautions as you connect inlet and outlet
plumbing, See Typical Installation lllustration.
• BE SURE INCOMING HARD WATER SUPPLY IS
DIRECTED TO THE SOFTENER VALVE INLET PORT.
If house water flow is from the left, use a plumbing
crossover as shown in Typical Installation
Illustration. If house water flows up from the floor
level, turn the bgpass valve upside down as shown.
___O_T urn bypass
valve upside
down to
connect to
floor level
IN plumbing
• With the softener in place, determine the correct
length of piping required to connect the household
plumbing to the NPT male adapter.
• Remove softener from installation space.
• If making a soldered copper installation, do all
sweat soldering before connecting pipes to the
NPT adapters and bypass valve. Torch heat will
damage plastic parts.
• When turning threaded pipe fittings onto plastic
fittings, use care not to cross-thread.
• Use Teflon Tape on all external pipe threads.
• Support inlet and outlet plumbing in some manner
(use pipe hangers)to keep the weight off of the
valve fittings.
I-_ CONNECT AND RUN THE VALVE
DRAIN HOSE
IMPORTANT: If LlOUwant to attach the drain fitting
to a rigid tube, see Connecting a Rigid Valve Drain
Tube section on next page.
Use the provided drain hose (20' length included)
to attach to the valve drain fitting. To keep water
pressure from blowing the hose off, use supplied
spring clamp to secure in place. Cut the necessary
length and use the remainder in Step 6.
1/4" NPT thread
Barbs for 3/8" I.D. tubing
Hose clamp
Drain hose
Locate the other end of the hose at a suitable
drain point (floor drain, sump, laundrg tub, etc.)
that terminates at the sewer. Check and comply
with local codes.
IMPORTANT: If more drain hose is needed, it
should be ordered from GE Parts at 800.626.2002,
part number WS07X10004. The water softener will
not work if water cannot exit this hose during
recharge.
Tie or wire the hose in place at the drain point.
High water pressure will cause it to whip during
the back-wash and fast rinse cgcles of recharge.
Also provide an air gap of at least 1-1/2"
between the end of the hose and the drain
point. An air gap prevents possible siphoning of
sewer water into the softener, if the sewer should
"back-up."
• Slide softener back into position.
• Make final connections to the bLIpass valve and
snap clips into place.
Be sure the clips for the bgpass valve and NPT
adapters snap into place. Pull on the bgpass valve
and NPT adapters to make sure the parts are held
securelg in place.
Installation Instructions
CONNECT AND RUN THE VALVE
DRAIN HOSE {CONT.)
• Elevating the drain hose may cause back
pressure that could reduce the brine draw during
recharge. If raising the drain line overhead is
required to get to the drain point, measure the
inlet water pressure to the softener first. For inlet
pressures between 20 and 50 psi, do not raise
higher than 8' above the floor. For inlet pressure
above 50 psi, the drain line Hag be raised to a
maximum height of 14'.
Blue indicator
light
Valve drain hose
on valve
Tie or
wire
hose in
place
FLOOR DRAIN
CONNECTING A RIGID VALVE DRAIN TUBE
To adapt a copper drain tube to the softener, bug a
compression fitting (1/4 NPT x 1/2" O.D. tube) and
needed tubing from gout local hardware store.
i
ii
P
g
1W' air gap
i-_ INSTALL THE BRINE TANK
OVERFLOW FITTINGS AND HOSE
• Insert the rubber grommet into the 3/4" diameter
hole in the brine tank sidewall as shown.
• Push the end of the hose adapter elbow into the
grommet as shown.
• Attach a length of hose (use remaining hose from
Step 5)to the hose adapter elbow. Use a hose
clamp to hold it in place.
• Locate the other end of the hose at the drain
point. DO NOT ELEVATEthis hose higher than the
elbow on the brine tank.
IMPORTANT: DO NOT TEE OVERFLOW HOSE TO
VALVE DRAIN HOSE.
NOTE: This drain is for safetg onlg. If the cabinet
(brine tank) should over-fill with water, the excess is
carried to the drain.
J
_.4_---- adapter
_----- Hose
t i clamp
Grommetll Do not connect
/1 to valve drain
l \\hose.
Overflow ----_
drain hose '_To acceptable
t -"drain
Hose
1/4" NPT Compression fitting
Clip thread 1/4 NPT x 1/2" O.D.
_l__)e___. vided)
Cut barbs from valve
drain elbow (pull clip 1/2" outside
and remove drain valve diameter copper
elbow from valve) tube (not provided)
Installation Instructions
I-_ INSTALL GROUNDING CLAMP
A DANGER:Failure to properly attach
ground clamp could result in electrical shock.
If plumbing is metal, to maintain electrical ground
continuity in the house cold water piping, install the
included ground clamp as shown.
• Clean pipe with emery paper in the area where
the clamp is to be installed.
• Install grounding clamps as shown, making sure
clamps fit freely around pipe.
• Make sure lock washer is in place.
• Handtighten screw, then one more full turn with
screwdriver.
NOTE: When replacing an existing softener, also
replace grounding clamps. If removing softener
completely, hard-plumb the water line with same
type of pipes as the original to assure plumbing
integrity and ground continuity over the life of
the home. To valve inlet
J_] FLUSH PIPES, EXPEL AIR FROM
SOFTENER AND TEST YOUR
INSTALLATION FOR WATER
LEAKS {CONT.)
• Place bypass valve in the "service" position
EXACTLY as follows. KEEP SOFT WATER FAUCETS
OPEN.
SLOWLY pull or slide the valve stem (out} toward
the service position, pausing several times to
allow the softener to pressurize slowly.
After about 3 minutes, open a HOT water faucet
for 1 minute, or until all air is expelled, then
close. NOTE: If water appears cloudy or has salty
taste, allow to run for several more minutes, or
until clear.
• Close all water faucets.
Check your plumbing work for leaks and fix
right away if any are found. Be sure to observe
previous caution notes.
Turn on the gas or electric supply to the water
heater. Light the pilot, if applicable.
Ground -
Clamp
From valve
_ outlet
l-_ FLUSH PIPES, EXPEL AIR FROM
SOFTENER AND TEST YOUR
INSTALLATION FOR WATER LEAKS
-ACAUTION: Toavoidwaterorair
pressure damage to softener inner parts, be
sure to do the following steps in exact order.
• Fully open 2 cold soft water faucets nearby
the softener.
• Place bypass valve in "bypass" position by
pushing the stem inward.
_1 ADD WATER AND SALT TO THE
BRINE TANK
• Lift the salt hole cover. Add about :3gallons of
water into the tank. Do not add into the brinewell.
Fill tank with NUGGET, PELLET or coarse SOLAR
water softener salt with a purity of 99.5% or
higher. Do not use rock, block, granulated and ice
cream-making salts, or salt with iron-removing
additives (except for Diamond Crystal ® Red.Out ®
brand salt). Maximum salt storage capacity is
approximately 200 Ibs. Keep the salt hole cover
closed unless servicing the unit or refilling
with salt.
NOTE: If the softener is installed in a humid
basement or other damp area, it is better to fill the
tank with less salt, more frequently. Eighty to 100
Ibs. of salt will last for several months, depending on
water hardness, family size and water softening
system model.
• Fully open the house main water pipe shutoff
valve. Observe a steady flow from both faucets
opened above.
Installation Instructions
CONNECT TO ELECTRICAL POWER
To gain access to the transformer/power cord
assemblg, remove the salt hole cover from the
softener. Unclip the tabs on the rear of the top cover
and rotate the cover upward to remove. DO NOT
PULL OR DISCONNECT WIRING.
• The softener works on 24 volt-60Hz electric
power. The included transformer changes
standard 120-volt AC house power to 24 volts.
Plug the transformer into a 120-volt outlet onlg.
Be sure the outlet is alwags live so it can not be
switched off bg mistake.
• Replace the top cover.
• Replace the salt hole cover.
PROGRAMMING THE CONTROL
CONTROL SETTINGS REgUIRED upon installation
and after an extended power outage.
NOTES:
• WHEN THE TRANSFORMER IS PLUGGED INTO THE
ELECTRICALOUTLET, 12:00 PM (flashing), and an
arrow I_ is displaLled next to PRESENT TIME on
the faceplate decal. The blue indicator light will
also flash. Program the control as instructed
below.
I- i
If ,-no--- is flashing, use the UP • button
to set the correct F or P code as follows: P39 for
GXSH39E or P4S for GNSH45E. If you pass by the
correct code number, use the DOWN • button.
Then press the MODE button to accept the
correct model.
• A "beep" sounds while pressing buttons for control
programming. One beep signals a change in the
control displaLI. Repeated beeps mean the control
will not accept a change from the button Llou have
pressed, and Llou should select another button.
• To program the control, Llou will use the UP •,
DOWN • and MODE buttons.
• Use the MODE button to scroll arrow !_ to desired
control function.
SET PRESENT TIME OF DAY
1. Press the MODE button _L 2: In
until arrow I_ points to p, __ ILl i_ PRESENTTJME
PRESENT TIME.
L
2. Press UP • or DOWN
• button to set. The UP button advances the
time; the DOWN button moves the time in reverse.
If the present time is between noon and midnight,
be sure PM shows in the displaLI. If the present time
is between midnight and noon, be sure AM shows
in the displaLI.
NOTE: Each press of an UP • or DOWN • button
changes the time bLI one minute. Holding the button
changes the time at a rapid rate.
3. When the present time is correct, press MODE to
accept.
SET WATER HARDNESS NUMBER
1. Press the MODE button &'v_ 2Ei_
until arrow I_ points to - -_
HARDNESS. .ARDNESS
2. Press UP • or DOWN •
button to set Llour water hardness number in the
displaLI. DOWN decreases the hardness value. UP
increases the hardness value.
NOTE: Each press of a button changes the displaLI
bLI 1, between 1and 25. Above 25, the displaLI
changes 5 at a time (25, 30, 35, etc.). Holding a
button in changes the numbers at a rapid rate.
.j
10
Installation Instructions
SET WATER HARDNESS NUMBER (CONT.}
3. When the display shows your water hardness
(in grains per gallon), press MODE to accept.
NOTE: If there is clear water iron in your water
supply, you will need to increase the hardness
setting by 5 for each 1 ppm of clear water iron
in your water supply.
You can get the grains per gallon (gpg}
hardness of your water supply from a water
analysis laboratory. If you are on a municipal
supply, call your local water department. Or
call Legend Technical Services, an independent
laboratory, to request a water hardness test kit
at 1.800.949.8220, Option 4. If your report shows
hardness in parts per million {ppm} or milligrams
per liter (my/I}, simply divide by 17.1 to get the
equivalent number of grains per gallon.
SET RECHARGE (STARTING} TIME
i. Press the MODE button t_l C.uu
until arrow I_ points to
RECHARG ETI M E. I _| RECHARGE
NOTE: A flashing 2:00 AM
(factory default) should show in the display. This is e
good time for recharge to start (takes about 2 hours)
in most households because water is not in use.
HARD WATER is bypassed to house faucets during
recharge.
If no change is needed, go to step 3. To change the
recharge starting time, follow step 2.
2. Press UP • or DOWN • button to set the desired
recharge start time. Be sure to observe the AM or
PM as you did when setting the time of day.
NOTE: Each press of u button changes the time by
1 hour. Holding the buttons in changes the time at
a rapid rate.
3. Press the MODE button to accept.
AM:,.nOli
I ) TIME
SET SALT LEVEL
i. Press the MODE button It_1 mm ,.] SALTLEVEL
SALT LEVEL.
until arrow I_ points to [ u.u ]
2. Determine level of salt in
brine tank using yellow indicator on side of brine
well, inside brine tank (see illustration on page 5).
.
Press UP • or DOWN •
button to set the SALT
LEVEL to correspond to
level on yellow indicator
in brine tank.
NOTE: Each press of e button changes the
level by increments of 0.5 up to 8.0. As the number
increases, the suit level burs increase on each whole
number. Lowering the suit level below zero turns the
SALT LEVEL indicator OFF.
4. Press the MODE button to
accept. The display shows the
present time of day end DAYS
TO EMPTY. RECHARGE TONIGHT
may appear if unit is new.
..... -t. 3
SALT I I h'_ _] SALT LEVEL
J
3._nl I
DAYS TO EMPTY
The words DAYS TO EMPTY and o rSALTI 3. inl 1
numberareshownthe,owerha,fI..... I
ofthe display.Thisinformationis Iml i-I--I
shown inthe normal run display. LEI J
This is to inform the user of the
number of days before the suit level in the brine
tank reaches Level 0. There will be suit left in the salt
tank, but it mug not be sufficient to fully recharge
the system. Suit should be added at this time to
avoid hard water. The value is updated daily and
whenever the SALT LEVEL value is changed.
NOTE: For the first several weeks of operation, the
DAYS TO EMPTY may provide erratic operation. For
example, the blue indicator light may flash, showing
that more salt is required when the actual salt level
in the tank is well above the Level 0. In some cases,
the DAYS TO EMPTY may even increaseovera
severalweek period.
I
It takes a couple of months for the water softener to
learn your water usage pattern. Once it does this, it
will accurately determine actual salt usage pattern.
During this first period, check salt level when blue
indicator light flashes. If the salt level in the tank is
at Level 1 or above, allow system to run. Be sure to
reset your salt level indicator each time you add salt
to the system.
ll
Installation Instructions
OPTIONAL CONTROL SETTINGS
The controller display has several options and
features.
LOW SALT ALARM [,L_ ]
The
LOW SALT ALARM, when I.--- J-I
enabled, will sound the beeper LiE 4_/ un
when the DAYS TO EMPTY value is
15 days or less. To change this setting, press and
hold the MODE button for 3 seconds. ON (factory
default) or OFF will flash in the display. Press the UP
• or DOWN • buttons to toggle this feature ON
or OFF.Press the MODE button to accept, and the
display will move to SALT EFFICIENCY.
When the SALT EFFICIENCY rl
SALT EFFICIENCY I_&__ ]
feature is ON, the unit will operate _ up-!_
at a salt efficiency of 4000 grains
of hardness removed per pound of salt. This mode
of operation is the most efficient setting for salt
usage, because the system will tend to recharge
more often, with less salt usage. Turning the feature
OFF will tend to lengthen the time between recharge
cycles, which will provide the most efficient usage
of water, but may use more salt. The degree of
difference between these two cycles is highly
dependent on the water usage and hardness
at a particular installation.
NOTE: California Regulations require this feature to
be ON for installations in California.
To change the setting, press the UP • or DOWN •
buttons to toggle the feature ON or OFF. Press the
NODE button to accept. The display will move to
SYSTEM/ELECTRONIC DIAGNOSTICS.
DIAGNOSTICS n r, n
SYSTEM/ELECTRONIC _ I_ _ I
This display contains system uuu
diagnostics information to assist in
troubleshooting problems with the system. See page
18 for details. Press the MODE button to return to
the normal run display.
J
FEATURE: OTHER DATA DISPLAYS
These models have an option to have the
run display indicate different information.
The information displayed on the top half of the
display can be changed to one of the following:
CAPACITY REMAINING - This is the percentage of
water softening capacity remaining. Immediately
after a regeneration, 100% shows. As water is
used, the percentage will decrease until the
next regeneration. During regenerations,
the percentage increments upward.
When PRESENTTIME is displayed, f_#_\l",_"_°UO I ]
press the DOWN • button; % J J_ .... t /
REH will appear in the display. J: I
The value shown is between 0 andL_! ........-;...... ! J
100 percent. This value is based on current
operating capacity. Pressing the UP • button
will return the screen to the previous display.
• AVERAGE DAILY GALLONS - The figure displayed
is the average gallons of water used by the
household each dog over the post seven-dog
period.
Press the DOWN • button again
to display the Average Daily
Gallons. ADG will appear in the
display. This value is updated
every night at midnight. Pressing the UP • button
will return the screen to the previous display.
FLOW RATE, GPH - When using soft water, this
display shows the flow rate passing through the
softener (in gallons per minute). Zero shows if
water is not passing through the softener.
Press the DOWN • button again _1 ,uc ]
todisplaytheflowrate.GPM willII ..... I
appear inthe display.Thisvalue
is updated every Vesecond. ...... ......I J
Pressing the UP • button will
return the screen to the previous display. Pressing
the DOWN • button will return the screen to the
PRESENT TIME display.
SALT 3 IT
........ CO
= 2
RECHARGE TONI6HT
I_W!o_o,Lj I I
I I'_
12
Installation Instructions
SIGNALS
LOST TIME SIGNAL
If time is lost on the display due to power
interruption, the blue indicator light will flash 4
times every second, until the present time of day
is entered.
LOW SALT SIGNAL
When the DAYS TO EMPTY drops to 15, the blue
indicator light and DAYS TO EMPTY in the display
will flash every second and the alarm will beep
every 30 seconds (from 8:00 AM to 8:00 PM),to
notify the user that the unit is running low on salt.
As soon as any button is pressed, the alarm will
stop beeping. The blue indicator light and DAYSTO
EMPTY will continue to flash. Once salt is added to
the brine tank and the SALT LEVEL is reset, the
DAYSTO EMPTY will be reset.
ERROR SIGNALS
If there is an error code detected, [t_ E r r ]
the blue indicator light will flash 4
times every second, the display will I
flash Err and the alarm will beep
every 30 seconds (from 8:00 AM to
8:00 PM) to signal that the softener requires service.
The alarm can be turned off by pressing any button,
but the blue indicator light and display will continue
to flash.
See page 18 for information to assist in
troubleshooting error codes. Once the problem is
corrected, disconnect the transformer from the wall
outlet momentarily, and plug it back in. The normal
display will appear. The motor may run for several
minutes, as the unit resets. If the problem is not
corrected, the error code will reappear in 6 minutes.
BLUE INDICATOR LIGHT
Steady blue light indicates that the unit is working
correctly. The light flashes when the unit needs
attention from the user.
J
• Light flashes and DAYSTO EMPTY flashes-check
salt level and odd salt as required.
• Light flashes and Err is in the display-electrical
problem with system-see page 18.
• Light will also flash when power to the unit has
been interrupted. Check the PRESENT TIME setting.
13
SANITIZING PROCEDURES
Installation Instructions
To complete the installation, do the following
sanitizing procedures.
Care is taken at the factory to keep your water
softener clean and sanitary. Materials used to make
the softener will not infect or contaminate your water
supply and will not cause bacteria to form or grow.
However, during shipping, storage, installation and
operation, bacteria could get into the softener. For
this reason, sanitizing as follows is suggested when
installing.
NOTE: Sanitizing is recommended by the
Water Quality Association for disinfecting.
.
Be sure to complete all installation steps, including
programming the control.
.
Pour about 3/4 oz. (1Vztablespoons) of common
5.25% unscented household bleach (Clorox, Linco,
Bo Peep, White Sail, Eagle, etc.)into the brinewell.
Refer to illustration on page 5.
. IMPORTANT: Press and hold for 3 seconds
the faceplate RECHARGE _ button to start an
immediate recharge. RECHARGE begins to flash in
the display. The bleach will be drawn through the
water softener, and out the drain. This process
takes approximately 2 hours.
4. If, after sanitization, water from the house
faucet tastes salty or has a slight color, this is a
preservative from the resin tank. Turn on the cold
soft water faucets and drain for a few minutes or
until clear.
NOTE: When the sanitizing recharge is over, all
remaining bleach is flushed from the conditioner
and your house COLD water supply is fully soft
immediately. However, your water heater is filled
with hard water and as hot water is used, it will refill
with soft water. When all the hard water is replaced
in the water heater, hot only and mixed hot and cold
water will be fully soft. If you want totally soft water
immediately, after the above recharge, drain the
water heater until the water runs cold.
-&WARNING: ,f you do drain the water
heater, use extreme care as the hot water could
cause burns. Turn the water heater off prior to
draining.
SPECIFICATIONS/D IMENSIONS
Rated Capacity*
Rated Efficiency**
Amount of High Capacity Resin (Ibs/cu. ft)
ResinTank Nominal Size (in.,dia. x height)
Service Flow Rate (gpm)
Water Supply Maximum Hardness (gpg)
Water Supply Maximum Clear Water Iron (ppm)***
Water Pressure Limits (min.-max. psi)****
Pressure Drop at Rated Service Flow (psig)
Water Temperature Limits (min.-max. °F)
Maximum Flow Rate to Drain (gpm)
These systems conform to NSF/ANS144 for the specific capacity claims as verified and substantiated by test data.
* Testing was performed using pellet grade sodium chloride as the regenerant salt.
** Efficiency rating is valid only at the lowest stated salt dosage. These softeners were efficiency rated according to
NSF/ANS144.
*** Extent of iron removal may vary with conditions. The capacity to reduce clear water iron is substantiated by WOA
test data. State of Wisconsin requires additional treatment if water supply contains greater than 5 ppm clear water
iron. Use of Diamond Crystal ® Red,Out ®or Super Iron Out® will improve iron removal. Referto Cleaning Iron Out
of the Water Softening System section.
**** Canada working pressure limits: 1.4-7.0 kg/cm<
G×SH39E
!!,700 grains with
2.3 Ibs of salt
30,800 grains with
8.5 Ibs of salt
39,000 grains with
1/4.7Ibsof salt
5,100 grains/lb.
@2.3 Ibs. of salt
56.2/1.08
9x 40
10
110
5
20-125
1/4
40-120
2.3
GNSH45E
13,300 grains with
2.6 Ibs of salt
35,500 grains with
9.8 Ibs of salt
45,100 grains with
17.0 Ibsof salt
5,!20 grains/lb.
@ 2.6 Ibs. of salt
65.0/1.25
i0 x 40
9.5
160
12
20-125
10
40-120
2.3
INLET-
OOT_ _ T/\
i -q- 19" -m_
471A"
411/4" _- 16"-_
3%" k---
-___
14
About the water softener system, ge.com
Service
When the water softening system is providing
soft water, it is called "Service." During service,
hard water flows from the house main water pipe
into the water softening system. Inside the water
softening system resin tank isa bed made up of
thousands of tiny, plastic resin beads. Ashard
water passes through the bed, each bead
attracts and holds the hard minerals. This is
called ion-exchanging. It is much like a magnet
attracting and holding metals. Water without
hard minerals (soft water) flows from the water
softening system and to the house pipes.
After a period of time, the resin beads become
coated with hard minerals and they have to be
cleaned. This cleaning is called recharge.
Recharge is started at 2:00 AM (factory setting)
by the water softening system control, and
consists of five stages or cycles. These are FILL,
BRINING, BRINE RINSE,BACKWASHand FAST
RINSE.
Automatic Hard Water Bgpass During Recharge
For emergency needs, hard water is available
to the home during the recharge cycles.
Fill
Salt dissolved in water is called brine. Brine is
needed to clean the hard minerals from resin
beads. To make the brine, water flows into the
salt storage area during the fill stage.
However, you should avoid using HOT water
because the water heater will fill with the hard
water.
Backwash
During backwash, water travels up through
the resin tank at a fast flow rate, flushing
accumulated iron, dirt and sediments
from the resin bed and to the drain.
Brining
During brining, brine travels from the salt storage
area into the resin tank. Brine isthe cleaning
agent needed to remove hard minerals from the
resin beads. The hard minerals and brine are
discharged to the drain.
The nozzle and venturi create a suction to move
the brine, maintaining a very slow rate to get the
best resin cleaning with the least salt.
Brine Rinse
After a pre-measured amount of brine is used,
the brine valve closes. Water continues to flow in
the same path as during brining, except for the
discontinued brine flow. Hard minerals and brine
flush from the resin tank to the drain.
Fast Rinse
Backwash isfollowed by a fast flow of water
down through the resin tank. The fast flow
flushes brine from the bottom of the tank,
and packs the resin bed.
After fast rinse, the water softening system
returns to soft water service.
15
About the water softener system.
Breaking a Salt Bridge
Sometimes, a hard crust or salt bridge forms in
the salt storage area. It is usuallg caused bg high
humiditg or the wrong kind of salt. When the salt
bridges, an emptg space forms between the
water and salt. Then salt will not dissolve in the
water to make brine.
If the brine tank isfull of salt, it is hard to tell
if gou have a salt bridge. Salt is loose on top, but
the bridge is under it. The following is the best
wag to check for a salt bridge.
Salt should be loose all the wag to the bottom of
the tank. Take a broom handle or like tool, and
carefullg push it down into the salt, working it up
and down. If the tool strikes a hard object (be
sure it's not the bottom or sides of the tank), it's
most likelg a salt bridge. Carefullg break the
bridge with the tool. Do not pound on the walls
of the tank.
If the wrong kind of salt made the bridge, take it
out. Then fill the tank with nugget or pellet salt
onlg. In humid areas, it is best to fill with less salt,
more often to prevent a salt bridge from forming.
Push tool into salt
bridge to break
Pencil
mark
Broom
handle
bridge
Water level
16
Cleaning the Nozzle and Venturi Assembly
A clean nozzle and venturi is needed for the
water softening system to work properly. This
small unit makes the suction to move brine from
the salt storage area to the resin tank during
recharge. If it becomes plugged with sand, dirt,
etc., the water softening sgstem will not work
and gou will get hard water.
Toget to the nozzle and venturi, remove the
water softening sgstem top cover. Be sure the
water softening sgstem is in service cgcle (no
water pressure at nozzle and venturi). Then, while
holding the nozzle and venturi housing with one
hand, remove the cap. Lift out the screen support
and screen, then the nozzle and venturi. Wash
and rinse the parts in warm water until clean. If
needed, use asmall brush to remove iron or dirt.
Also check and clean the gasket.
NOTE:Some models hove a small flow plug
located in the nozzle and venturi, and/or a small
cone shaped screen in the housing. Besure to
check and clean these parts, if gout model is
so equipped.
Carefullg replace all parts in the correct
order. Lightlg lubricate the o-ring seal with clean
silicone grease or petroleumjellg and place in
position. Install and tighten the cap, bg hand
onlg. Do not overtighten the cap.
Cap __
O-ring seal _O
Screen _@
support
Screen
_Flow plug __
Venturi
Nozzle & Z_
Gasket
i
_ Screen
_Flow __
plug
!
Nozzle & l
Venturi
housing
IMPORTANT:Be sure small holes in the gasket are
centered directlg over the small holes in the nozzle and
venturi housing,
*Install with numbered side up, concave side down.
Normal Operation, Control Displays
During normal operation, the present time of
dQy QndAM or PH and DAYSTOEMPTYshow
in the control displQy QreQ.When the demand
computer determines a rechQrge is needed,
RECHARGETONIGHT begins to flQsh in the
display along with the present time. RECHARGE
TONIGHTflashes until the next rechQrge start
time, then chQnges to RECHARGE,which flQshes
until the rechQrge isover.
Feature: Optional Recharge Controls
Sometimes, a manuQIly started rechQrge may
be desired or needed. Two exomples:
You hove used more water thQn usuQI(house
guests, extra washing, etc.) and you may run
out of soft water before the next rechQrge.
The system ran out of sQIt.
Use one of the following feQtures to start a
rechQrge immediQtely, or at the next preset
rechQrge start time.
ge.com
RECHARGE TONIGHT
Touch (do not hold) the RECHARGE_ button.
RECHARGETONIGHTflQshes in the control
displQy areQ.A rechQrge will occur at the next
preset recharge start time. If you decide to cancel
this recharge, touch the same button once more.
RECHARGE
Press and hold the RECHARGE@ button until
RECHARGEstarts to flash in the control display
area. The water softening system begins an
immediate recharge and, when over in about two
hours, you will have a new supply of soft water.
Once started, you cannot cancel this recharge.
Feature: Memory
If electrical power to the water softening system
is interrupted, the control display is blank, and
the blue indicator light is off, but the control
keeps correct time for about 6 hours. When
power isrestored, you have to reset the present
time only if the display and blue indicator light
are flashing. All other settings are maintained
and never require resetting unless a change is
desired.
If the time is flashing after a long power outage,
the water softening system continues to work as
it should to provide you with soft water. However,
recharge may occur at the wrong time of day
until you reset the control to the correct time
of day.
Feature/Service: Automatic Electronic Diagnostics
The control computer has a self-diagnostic
function for the electrical system (except input
power and water meter). The computer monitors
the electronic components and circuits for
correct operation. If a malfunction occurs,
an error code appears in the control display.
The chart on Error Codes shows the error
codes that could appear and possible reasons
for each code. See Monuo!ly Initioted Electronics
Diognostics to further isolate the defect.
17
About the water softener sgstem.
Service: Electronic Demand Time Features and Service
ERRORCODE
DISPLAYED ERR0,3 ERR04 ERR05
POSSIBLEDEFECT •Control
Toremove an error code: 1. Unplug transformer.
ERR01
• Motor
inoperative
•Wiring
harness or
connection
to switch
• Position
switch
• Control
2.Correct defect.
3.Plug transformer in.
4. Wait for at least 6 minutes. Theerror codewi!! return if the reason for
the error code was not corrected.
ERR 02
• Position
switch
•Control
.Motor
inoperative
or wiring
harness
,Control
•Position
switch or
wiring
harness
•Control
Service: Timer/Softener, Service Checkout Procedure
If you are not getting soft water, and an error
code is not displayed, use the procedures below
to find the problem. First make the following
visual checks.
VISUAL CHECKS:
1. Is there electrical power to the outlet the water
softening system transformer is plugged into?
CONTROL
DISPLAY
i
BLANK.
CONTROL SHOWS
WRONG TIHE AND
DAY,AND/OR IS
FLASHING.
Checkelectrical
power to control
transformer,
__ (outlet,
power cable,all
connections).
Electricalpower was
off. Resetthe correct
time of day.
Z Is there sufficient salt in the storage tank?
3. Is the softener bypass valve directing water
for soft water service?
4. Isthe valve drain hose open to the drain,
not more than 8' above the softener, and
unobstructed? If hose is above 8', see
page 8, step 5.
If you do not find a problem with the visual
checks, continue below.
Investigatereason for
power loss.
REPAIRAS
NEEDED
CONTROL
DEFECTIVE
diagnostics
i Domanual
to verify
proper
function.
18
CONTROL DISPLAY
SHOWS CORRECTTIHE
AND DAYAND IS
STEADY.
Domanual
diagnostics.
Service: Manually Initiated Electronics Diagnostics
ge.com
1. Toenter diagnostics, press and hold
the MODE button for 3 seconds until
the Low Salt Alarm screen shows.
LEVEL
4_/)0 rl
SALT l
to advance through Low Salt Alarm 2_ U
and Salt Efficiency options. See ftmn
2.PresstheMODEbutton2times Ft _ 1
Programming the Contro! for U U U
details on these two options.
3. OPERATION OF DIAGNOSTICS
Motor Position
Valve ] ,switch
pos,t, f
r ;L
Water meter
• Valve Position- Pressthe RECHARGE_ button to initiate
a recharge cycle. Press again to manually index valve to
next position. See Service: Monuo!ly Advance Recharge
Checkfor details.
0 - Service
i - Fill
2 - Brine
3 - Backwash
4 - Fast Rinse
Motor Operation - Two dashes will circulate around
when motor should be running.
Position Switch Operation -
r
,_- Closed - valve rotating to next position
n
u - Open - valve in position, service, fill, brine, etc.
Water Meter - Indicates whether water is flowing
through valve.
- If there is no reading in the display, with faucet open,
check the sensor. Pull the sensor from the valve outlet
port, and pass a small magnet in front of the sensor.
Counter should index in the display. If counter does
not index, check to make sure harness isconnected
to board properly. If there is a reading inthe display,
there may be a problem associated with the turbine.
Turn off water supply, close the bypass valve and
disconnect bypass valve from body. Check turbine
for binding or restriction due to debris. If this does
not correct the problem, the Timer, Sensor or Turbine
may require replacement.
4. Historical data about the softener isavailable.
Press and hold the UP • button to display the number
of days this control has had electrical power applied.
Press and hold the DOWN • button to display the
number of recharges initiated by this control since the
model code number was entered.
5. Pressthe MODE button to return to normal operation
and display.
Service: Set Model (F or P) Code
1. Tochange or check model code, first press and hold the
MODE button for 3 seconds until the Low Salt Alarm screen
shows.
2. Pressand hold the MODE button again
for 3 seconds. A display with r
__on at
the top will appear.
3. Pressthe UP • or DOWN • buttons to
select the correct model code.
P39-GXSH39E or P45-GNSH45E
4. Pressthe MODE button one time to return to normal
operation and display. If the model code was changed:
the display will go blank momentarily, then display the
model code entered.
SALT F i
..... L 0 0
p-irl
33
Position
switch
i
i housing
Valve
outlet
and shaft
support
- 000 indicates no water is flowing through the valve
- Open nearby soft water faucet
- 000 to 141 (continual) shows water is flowing. Display
repeats for each gallon of water passing through the
meter. Control will beep at every gallon.
the display will then return to the set present time display,
and the blue indicator light will flash. The control will have
to be reprogrammed. See Programming the Contro!.
NOTE:If the control is left in any of the above diagnostic
displays, or a flashing display when setting time, hardness,
etc., it will revert back to the normal display in 4 minutes.
19
About the water softener sgstem.
Service: Manuallg Advance Recharge Check
NOTE:The control display must show a steady
time (not flashing).
1. Pressthe RECHARGE@ button and hold in for
three seconds. RECHARGEbegins to flash as
the water softening system enters the fill cycle
of recharge. Remove the brinewell cover and,
using a flashlight, observe fill water entering
the brine tank. If water does not enter the tank,
look for an obstructed nozzle, venturi, fill flow
plug or brine tubing. SeeCare and Cleaning of
the Water Softener System section.
2. After observing fill, press the RECHARGE@
button to move the water softening system
into brining. A slow flow of water to the drain
will begin. Verify brine draw from the brine
tank by shining a flashlight into the brinewell
and observing a noticeable drop in the liquid
level over an extended period of time.
NOTE: Besure a salt bridge is not preventing
water from contacting salt. SeeCare and
cleaning of the water softening system section.
If the water softening sgstem does not draw
brine, check:
,, nozzle and/or venturi dirty or defective.
defective nozzle and venturi seal.
,, nozzle and venturi not seated properly
on gasket.
,, other inner valve defect (rotor seal, rotor and
disc, wave washer, etc.).
,, restricted drain (check drain fitting and
hose).
NOTE: If water system pressure is low, an
elevated drain hose may cause back pressure,
stopping brine draw.
3. Again, press the RECHARGE@ button to move
the water softening system into backwash.
Lookfor a fast flow of water from the drain
hose. A slow flow indicates a plugged top
distributor, backwash flow plug or drain hose.
4. Pressthe RECHARGE@ button to move the
water softening system into fast rinse. Again
look for a fast drain flow. Allow the water
softening system to rinse for a few minutes
to flush out any brine that may remain in
the resin tank from the brining cycle test.
5. To return the water softening system to
service, press the RECHARGE@ button.
20