GE GE-VCPL User Manual

)
SINGLE STAGE COLD ROOM PANEL
Applicable to model numbers: 2051/52/53/54/55/56
*(9&3/
Electronic Temperature Control Systems
DESCRIPTION
The VCPL series is especially designed for use in the commercial refrigeration and is available in various different models. The VCPL is also available with communication properties. In addition to extremely accurate temperature control the VCPL offers the user diagnostics, marketing information and current statistics scroll i.e. average temperature, lowest temperature, highest temperature, number of door openings, compressor cycles and compressor running hours. As standard all models in the VCPL series ar e fitted with 6 relays switching : compressor, heating element or solenoid valve, external alarm, evaporator fan, on/off switch and light(s). All relays in this unit have a switching capacity of 16 Amp. @ 240 Volt.
WARNING
This manual is part of t he product and should be kept near the inst r ument for quic k reference. The i n strument should not b e used for pu r poses other than desc ribed and /or speci fied by the manufac turer. These controls can only be used with GE double insulated sensors.
SAFETY PRECAUTIONS
Ensure that the supply voltage is correct before connecting the instrument. (240 Volt ) Ensure th at t he inst ru me nt is not e xpos ed to w ater o r any other liquid. Ensure that the current that is switched does not exceed the maximum switching capacity of the instrument. If the current to be switched is greater than the instr ument limits , a sepa rate relay sho uld be installed. Ensure that all wires are properly connected in the appropriate terminal, a loose wire could cause sparking and damage the instrument and may be dangerous.
BUTTON COMMANDS
TO SET THE T EMPERATURE
In case of a n instru ment fa ilure or faulty functio ning of the instrume nt, retur n it to your loc al dis t ribut or or direct to the ma nufacturer. If the unit is still in it s warranty period it will be rep laced free of charge. To set the temperature push the ‘
’ and the d isplay will intermittentl y show the
button
letters SP (set point) and the pre-set temperat ure. To increase the tempe rature use t he value up button (∧), to decrease the temperature use the value down button (v). Once the required tempe rat ure is selecte d, re lease the buttons and wait until the display shows the actual temperature again. The instr ument has now adopted the new setting and will operate in accordance with these new instructions.
temperature set
ACTIVATE A MANUAL
It may be possible that from time to time the user
DEFROST CYCLE
wants to use some extra defrost cycle(s). To activate a manual defrost, p ush the manual defrost button and keep it pressed for a minimum of 5 sec. Until the defrost signal shows on the display. A manual defrost may be activated as many times as required.
WARNING SIGNALS
In addition to its standard control fun ctions , the GE­VCPL series also contains a number of diagnostic functions and can show the following alarm signals: RSF – There is a refrigeration system failure. Contact your sup plie r .
EE – There is a microprocessor (electronic) failure, contact you r su pplier.
PF1 – There is a sensor failure that is very likely caused by a lo ose connection of the s ensor wire in the terminal block of the instrument. This sensor is the appliance sensor. Contact your local supplier.
PF2 – There is a sensor failure (as PF1), but in t he sensor of the evaporator.
PF3 - As PF1 and PF2 but this is the sensor connected to the condenser
AL1 – The temperature of the appliance has exceeded its maximum allowable temperature.
AL2 – The temperature of the appliance has exceeded the minimum allowable temperature.
HT – The condenser is blocke d
CHANGING PARAMETER VALUES
To change the parameter values switch the power to the unit off, push the temperature set button and keep it pushed w hilst switching t he power on aga in. The display wi ll fla sh and inter mitte ntly s how the figu res
888. Once the display stops flashing, the instrument is in parameter mode and the values can now be changed. To scroll through the parameters push the temperature set button and to change the value of the parameters use the ‘value’ buttons. When finished, release all buttons and wait until the display shows the actual temperature again.
Please note that th e VCPL has two different sets of parameters. The first batch can be accessed as described above and the second set can be accessed by holding the set button
and the up button pushed together
.
WARNING
If the power to the unit is switched off whilst the instrume nt is st ill in para me ter mode, the syste m w il l NOT accept the changes.
The GE-VCPL does NOT require any maintenance.
WARNING
To clean the fac ia of the GE-VCPL use wet soapy rag. The instrument is an electronic device, do not use water or any other cleani ng liquid to clean the facia of the instrument as this may cause serious and unnecessary damage to the system and may be dangerous.
All wiring instructio ns are pr inted on the ho using o f the unit and contain all possible information needed to connect the GE-VCPL Follow these instructions and ensure that all connections in the terminals of the instrument are properly fastened as loose connections may influence the performance of the instrument and may cause sparking. The GE-VCPL is powered by 240 Volt and should be connected dir ec t to the ma ins.
IMPORTANT
Only authorised and competent personnel should connect and/or disconnect the GE-VCPL.
MAINTENANCE
WIRING INSTRUCTIONS
The recommended hole s ize for the GE-VCPL is 9 5/32” x 3 5/8”but in addition there are the holes for the fasteners as per the drawing on the reverse of this instruction manual.
PARAMETER LISTING
Access through set button:
INSTALLATION
Param. Description Range US Upper SP limit -40/212°F
LS Lower SP limit -40/212°F DIF Differential 1.8/178°F CA1 Sensor 1 calibr. ±17.8°F CA2 Sensor 2 calibr. ±17.8°F D1 Display stability 1 to 8 D2 Display speed 1 to 255 rt Min. rest time 1 to 30 min dE Defr ost intervals 1 to 199 hrs dd Defrost duration 1 to 199 min dF Defrost method 1 = off
2 = heater 3 = hot gas
dt Max temp. in
-40/212°F appliance during defrost
SP2 Max. evap. Temp.
-40/212°F during defrost
FP Fan stop during
defrost
0 = no
1 = yes Fd Fan delay to on 0 – 60 min. CT Refr. System
1 to 255 hrs
failu re elap s e t ime
dEF Display during
defrost
0 = temp.
1 = start
temp.
2 = dEF LL Low alarm temp. -40/212°F HL High temp. alarm -40/212°F AD Alarm delay 0 – 255 mi n. B1 Buzzer off for 0 to 255 min B2 Buzzer on for 0 – 255 min
Access through set and up button Ht Blocked
176 to 250°F
condenser temp.
St Time zone for
1 to 255 hrs
reset
CF Degr C or F 0 = C
1 = F
db Displa y brightness 0 = bright
1 = dim
C1 Computer
interface
0 = wireless 1 = Infra Red
D1 Data intervals 1 – 255
minutes
FL Compressor run
after failu re
0 = yes 1 = no
GE Electronic Tempe rat ure Control Systems should not be exposed to low temperatures or high humidity, such as
outdoor or refrigerated environments. It is the customer’s responsibility to determine the proper application of the controls and to specif y the op tio nal Co nformal Co ating if the controls are going to be used in these environments.
cURus Approval Pending