Manufacturer’s Name & Address: GE Interlogix, Inc.
2266 North Second Street
North St. Paul, MN, USA
55109
EU Representative:In te rl ogi x Eu rope & Africa
Excelsiorlaan 28
B-1930 Zaventem
Belgium
Product Identification
Product: Simon 3 Security Panels
Model Numbers: 60-911-010-4-IE, 60-911-011-4-IE, 60-911-010-4-IT, 60-911-011-4-IT
Brand: GE Interlogix
R&TTE Directive
See EMC and LVD tests below
EMC Directive
TUV Product Services & GE Interlogix
Reports: CEQP 60-911 Simon 3 Euro Rev. C
EN 50130-4 (1995), EN 61000-3-2 (1995), EN 61000-3-3 (1995), EN 55022 (1998), EN 300220-3 (2000)
LVD Directive
GE Interlogix
Report: CEQP 60-911 Simon 3 Euro Rev. C
EN 60950: 1999-4 3rd ed it ion
Means of Conformity
We declare under our sole responsibility that this product is in conformity with Directive 1999/5/EC (R&TTE); Directive 73/23/EEC (LVD); and Directive 89/
336/EEC (EMC) and based on test resu lt s using (non)-harmonized standards in accordance with the Directives mentioned.
Additional Tests: This equipment has been tested and foun d to comply with the following standards (which are no longe r re qui red for compliance).
Te sted by
Interlogix
CTR21 (1998) +EG201 121 (1998)
TÜV
Report: TBR21/110501/01
TBR21
Network Compatibility Declaration
9
We declare under our sole responsibility that this product is designed to work with the networks in the countries marked with a check (
ing problems with the countries that are not checked.
Due to the inherent differences in the individual PSTNs, certain software settings may need to be adjusted on a country to country basis. If it is desired to use this
equipment on a network other than the one on which it was originally installed, you should contact your equipment supplier.
() Austria() Denmark() Germany(9) Ireland
(
) Belgium() Finland() Greece(9) Italy
(
) France() Iceland() Liechtenstein
(
)Luxembourg
)Netherlands()Portugal()Switzerland
(
)Norway()Spain(9)United Kingdom
(
(
) Poland
) and may have network-
(
)Sweden
Telecom Approval Notice
This equipment has been approved in accordance with the Council Decision 98/482/EC for pan-European, single terminal connection to the public switched telephone network (PSTN). Howe ve r, due to the difference s bet w e en t he indi vi dua l PST N s provided in different countries, the approval does not, of itself , give an
unconditional assurance of successful operation on every PSTN network termination point. In the event of problems, you should contact your equipment supplier
in the first instance.
Electrical Requirements
This device automaticall y adjusts to voltages within the range of 220 - 240 V 50 Hz.
Fuse: T 2A 250 VAC
Technical Service and Repair
If you experience trouble with this equipment, please contact your installer for service and repair information. Changes or modifications not expressly approved
can void the user’s authorit y to o perate the equipment.
Entering Program Mode ................................................................................................................... 13
Exiting Program Mode ..................................................................................................................... 13
Reset Memory to the Factory Defaults ............................................................................................ 13
Set the Clock ........................................ .... ................................................................. .... ................... 13
Adding (Learning) Sensor s .............................................................. .... ... ......................................... 14
This manual provides informati on for planning, installing, programming, and test i ng thi s secu-
rity system. When necessary, this manual refers you to other documentation included with
compatible devices.
Planning sheets are included for you to record sensor locations and software programming set-
tings.
Planning the
Installation
Installing the
System
This section describes system capabilities to help you get familiar with the system. “Appendix
B” provides planning sheets with tables that let you record th e hardware and pr ogramming
configuration of the system. Fill in all necessary information ahead of time to help prepare for
system installation.
Panel Inputs/Outputs
The following describes the panel hardware input/output capabilities.
•Power: Input for AC power.
•2 Siren Ou tpu t s /Zone Inputs: Terminals for connecting hardwire sirens or normally
closed (NC) loop switch circuits. These terminals cannot provide both functions simultaneously.
•Phone Line Connection: Lets users access and control their system from a remote phone
and allows the panel to communicate with central monitoring station.
This section describes how to install the system control panel. Before star ting the installation,
plan your system layout and programming using the worksheets provided in “Appendix B.”
Installing the system consists of the following:
•Determining Panel and Device Locations
•Mounting the Panel
•Connecting Sirens
•Connecting Normally Closed Loop Switch Circuits
•Connecting the Phone Line to the Panel
•Connecting and Applying Power
System Components
The security system has three types of components: the control panel, devices that report to the
panel, and devices that respond to commands from the panel (see Figure 1).
Euro Simon Security System1
Page 7
M o t io n
D o o r s &
W in d o w s
S e n s o r s
A r m
3 / 4
1 / 2
S p e c ia l
D o o r s
M o t io n
C h i m e
F IR E
T e s t W e e k ly
Door/Window
Sensor
S y s te m
S t a tu s
H O M E S E C U R I T Y
D i sa r m
9 / 0
5 / 6
7 / 8
S e n s o rT im e
O f fO n
H O M E C O N T R O L
L ig h t s
E M E R G E N C Y
A U X
P O L I C E
C O D E
1
4
7
O n
E M E R G E N C Y
Keychain
Touchpad
S Y S T EM
S T A TU S
A R M
D o o rs &
W i n do w s
A R M
M o t io n
S e n so r s
D IS A R M
3
526
8 9
O ff
sP
d&sr e s H o l hB to eK y
-
Remote
Handheld
Touchpad
O N
15
13
11
UN IT C OD E
X - 1 0 P O W E R H O U S E
CO N TIN U OU S
M OM EN T AR Y
O FF
1
A
3
C
O
E
5
M
GK
7
I
9
HO U SE C OD E
SO U ND ER O NL Y
SO U ND ER & R EL AY
RE LA Y ON L Y
1
3
1 5
5
1 3
1 1
7
9
A
C
O
E
M
GK
I
1 5
1 3
1 1
O
M
X-10 Modules
Figure 1. Typical Security System Components
Motion Sensor
Smoke
Sensor
1
3
5
7
9
A
C
E
GK
I
Control Panel
The control panel is the main processing unit for all system function s. It receives and responds to
signals from wireless sensors and wireless touchpads throughout the premises. For monitored
systems, the panel can be connected to the premises phone line for central monitoring station
reporting.
Two panel models are available. One has an on-board 2-way voice microphone, the other does
®
not. The Interrogator
200 Audio Verification Module can be added to either panel.
User Interface
When the panel cover is closed, the panel buttons operate the security system. The us er op erates
the panel by pressing panel buttons or by using a touchpad. See the User Manual for complete
operation instructions.
When the panel cover is open, the buttons pr ogram the security system. The panel can be programmed on-site by the installe r or user, or from off-site using ToolBox
®
software. See the “Pro-
gramming” section of this manual for complete on-site programming instructions. See the
ToolBox manual and ToolBox on-line help for off-site programming instructions.
Panel Tamper
If the panel cover is opened while the system is armed, an intrusion alarm occurs. When the system status button is subsequently pressed, the panel voice announces System Access Alarm.
System Devices
The system can monitor up to 24 sensors and may use any of the following:
Door/Window Sensor
For intrusion protectio n, install Door /Wi ndow sensors on all ground-floo r doors and windows. At
a minimum, install them in the following locations:
•All easily accessible exterior doors and windows.
•Interior doors leading into the garage.
•Doors to areas containing valuables such as cabinets and closets.
Euro Simon Security System2
Page 8
Motion Sensor
Motion sensors are ideal whenever it is not practical to install door/window sensors on every
opening. Identify areas where an intruder is likely to walk through. Large areas in an open
floor plan, downstairs fami l y rooms, and hallways are typical locations for indoor motion sensors. For installations with pets, use pet immune motion sensors.
Smoke Sensor
Smoke sensors provi de fire p rotecti on by cau sing an alarm to s ound through out the hous e. You
can add smoke sensors near sleeping areas and on every floor of the house. Avoid areas that
could have some smoke or exhaust such as attics, kitchens, above fireplaces, dusty locations,
garages, and areas with temperature extremes. In these areas you may want to install Rate-ofRise sensors to detect extreme temperature changes. See the instructions packaged with the
smoke sensor for complete placement information.
Keychain Touchpad
The Keychain Touchpad lets you turn the system on and off from right outside the home or
activate a panic alarm if there is an emergency. If you have X-10 Lamp Modules, you can use
keychain touchpads to turn all system controlled lights on and off.
Remote Handheld Touchpad
The Remote Handheld Touchpad lets you turn the system on and off while in the home, turn
system controlled lights on and off (all or individual lights), or activate a panic alarm if there is
a non-medical emergency.
X-10 Modules
Some panel models work with any of the following modules:
•X-10 Lamp Module
•X-10 Appliance Module
•X-10 Powerhorn/Remote Siren Module
•X-10 Universal Module
Planning
Sensor Types &
Locations
The first step to an easy and successful installation is to decide what areas or items to protect,
which lights or appliances to operate, and the best location for the panel, touchpad, sensors,
and sirens.
Metal objects, mirrors, and metallic wallpaper can block signals sent by the wireless sensors.
Make sure there are no metal objects in the way when installing the system.
Use the planning tables in “Appendix B” to determine the appropriate Sensor Group for the
sensors you will be adding. You’ll need to understand the application for each sensor. For
example, Keychain Touchpads are typically programmed as sensor group 01 (Portable panic),
used to send an intrusion alarm to a central monitoring station. This sensor type is instant intrusion, it does not require res toral or su pervisory com munication with the panel and it is active in
4 arming levels (disarm, arm doors & windows, arm motion sensors and arm doors/windows
and motion sensors).
All Lamp Modules with the
same house code will tu rn
on or flash as a group during
an alarm or when operating
the “Light” button on a Keychain Touchpad.
Device Locations
Control Panel
Locate the panel where alarm sounds can be heard and is easily accessible for operation.
Do not install the panel near a window or door where it can be reached easily by an intruder.
Remote Handheld Touchpad
Locate Remote Handheld T ouch pads where they will be convenien t and of fer quick access to the
user.
Keychain Touchpad
Keychain Touchpads attach to the owner’s key ring or can be conveniently carried.
X-10 Modules
The system can control up to 8 individual unit numbers on Lamp, Appliance, and Universal Modules.
House Code and Unit Numbers
Each device (lamp, appliance, etc.) controlled by the panel must have an identification settin g.
The modules use two dials to set identification codes: one with letters A through P and one with
numbers 1 through 16.
The lettered dial sets the house code, which enables the system to differentiate this home from
other homes in the area. Set all modules (except the remote siren) and the panel to the same
house code.
Note
When unit numbers 9-16 ar e used for lamp modules, they can only be con trol l ed by an all on or all off
command. A lamp will flash to the arming level if its unit number is set to 10. A lamp set to unit number
10 will flash once if the panel is disarmed, twice if doors & windows are armed, etc. The remote siren
can be set to any unit number to hear alarm sounds. Set it to unit numbe r 9 t o also hear arming level
beeps, status beeps, and trouble beeps. Do not use a lamp module to control appliances. Use an appliance module, since the w at tag e ra ting on Lamp Modules is less than on Appliance Modules.
The numbered dial sets the unit number, which identifies and lets you control a specific device.
Each device must have a unique unit number (1-8) to be individually controlled. For example,
lights and appliances operated from a Remote Handheld Touchpad or operated by a sensor; or
lights programmed to go on during the entry/exit delay or at scheduled times.
Note
The house code instructions
that come with the Powerhorn Siren won’t work with
this panel. Follow the housecode instructions given here.
Note
If you are using a Universal
Module to operate a device,
make sure to assign a
unique unit number to this
module, choosing from 1- 8.
To Fill Out the Home Control Planning Table:
¾
1. Set the house code on all modules (except the remote siren) to the same letter.
2. Set the Remote Siren house code to the next alphabetical letter. For example, if you chose
house code B in step 1 above, set the remote siren house code to C.
3. Set the module unit numbers.
4. List the location of the lamp or appliance in the Location column of the Home Control Planning Table.
5. Write the location of each module on an adhesive note and label the module.
6. Decide if the device should be activated by sensors, entry/exit delay, time, or a combination.
An example of sensor activation is using a motion sensor to turn on a light. Record the information in the appropriate columns.
Use the following tables to help plan X-10 module installation.
House Code Assignments
House Codes Results
A through PSet all modules to the same house code except the remote
Next Higher House CodeRemote Siren must be set to the next higher alphabetical letter.
sirens.
Euro Simon Security System4
Page 10
Unit #Result
1 - 8Used for sensor-activated, time-activated, and entry/exit delay lights.
•Sensor-activated lights are enabled and disabled by pressing the Lights
Sensor button on the panel.
•Time-activated lights are enabled and disabled by pressing the Lights
Time button on the panel.
If using the universal module to operate a device, be sure to assign a unique
unit number.
•The STAR button on the Keychain Touchpad activates the universal module controlled device or turns on special lights if programmed.
Installing the
System
9
10Used for remote siren or light control.
11 - 16Used for lamp modules and controlled by an all on or all off command.
This section describes how to open the panel for mounting, mount the panel, connect sirens,
hardwire contacts, and the AC power transformer.
Used for remote siren or light control.
•For remote siren use, House Code must be set to next higher number to
hear arming level beeps, status beeps, and trouble beeps.
•For light control, lamp modules with this setting are controlled by an all
on or all off command.
•For remote siren use, House Code must be set to next higher number and
only alarm sounds occur at this setting.
•For light control, lamps will flash according to selected arming level and
are controlled by an all on or all off command.
Materials Needed
•Pencil
•Phillips Screwdriver
•Small Standard Screwdriver
Opening the Panel Cover and Chassis
Tabs at the top of the panel secure and release the front cover and the chassis. The plastic
hinges on the panel bottom allow the cover and chassis to swing down and out of the way (see
Figure 2)
Euro Simon Security System5
Page 11
Press tab with thumb,
then swing cover down.
Press tab up with
screwdriver, then
swing chassis
down.
D o o r s &
M o t io n
S t at u s
W in d o w s
S e n s o rs
A r m
1 / 2
3 / 47 / 8
S p e c ia l
M o t io n T im e
D o o r s
C h im e
F IR E P O L IC E
T e s t W e e k ly
H O M E S E C U R I T Y
S y s te m
D i sa r m
9 / 0
5 / 6
S e n s o r
C O D E
O n O ff
H O M E C O N T R O L
L ig h t s
E M E R G E N C Y
A U X
Figure 2. Opening the Panel Cover and Chassis
Mounting the Panel
Mount the panel on a wall as follows:
1. Choose a panel location and run all necessary power, phone, siren, and hardwire contact
wires to the location.
2. Hold the panel against the wall and mark the mounting hole locations with a pencil (see Figure 3).
Figure 3. Mounting Hole/Wire Access Locations
Euro Simon Security System6
Wire
Access
- - - - -
Mounting
Holes
- - - -
Wire
Access
A C A C
H W I N 2
H W I N 1D C O U T
Page 12
Note
These terminals cannot provide both functions sim u ltaneously.
Note
The total current available
from the DCOUT terminal is
250 mA at up to 50° C.
3. Insert anchors into holes where studs are not present.
4. Feed all wires through wire access areas (see Figure 3).
5. Install all screws and tighten gently.
Connecting Hardwire Devices
The panel has 5 screw terminals located on the upper-right corner of the circuit board (see Figure 3) for connecting AC power, sirens and/or hardwire detectors.
AC Terminals
A fused terminal block is used for connecting the panel to a mains supply. The terminal block
is pre-wired from the factory to a built-in step-down transformer.
HWIN1, HWIN2, and DCOUT Terminals
These terminals are dual purpose and can be used for either siren or hardwire detector connections.
Sirens
From the factory, these terminals are set up for siren operation with HWIN1 handling interior
sirens (status and alarm sounds), HWIN2 handling exterior sirens (alarm sounds only), and
DCOUT providing the positive (+) voltage.
With Option 53: Hardwire Siren Supervision turned on, sirens connected to HWIN1 and
HWIN2 are supervised and require a 4.7k resistor in the circuit. If either of these terminals is
not used with Option 53 on, you must connect a 47k resistor between the unused terminal and
DCOUT.
Hardwire Detectors
To set up HWIN1 and/or HWIN2 for hardwire detectors, make the required connections as
described under “Wiring Hardwire Detectors,” then proceed to the “Programming” section to
add (learn) them into panel memory.
Note
Do not install the resistor at
the panel terminals. This
does not provide supervision
of the wire. If you are only
installing an interior siren
and Option 53 is on, you
must connect a 47k resi st or
between th e H WIN2 and
DCOUT terminals.
Wiring Interior Sirens
Panel terminal HWIN1 can be used for connecting interior sirens and activates for status and
alarm sounds.
Interior sirens must always be wired with a resistor in the circuit. For circuit supervision which
allows the panel to detect if the siren wire is cut (open), Option 53: Hardwire Siren Supervision
must be turned on (see the “Programming” section).
Hardwire Interior Siren
Connect a hardwire interior siren to the panel using a 4.7k resistor as shown in Figure 4. The
resistor must be connected across the siren wires as close to the siren as possible.
A CA C
H W I N 2
SIREN
H W I N 1D C O U T
4.7k Resistor
(Locate at siren)
Figure 4. Hardwire Interior Siren with Supe r v ision
Euro Simon Security System7
Page 13
Note Do not install the
resistor at the panel terminals. This does not provide
supervision of the wire. If
you are only installing an
interior siren and Option 53
is on, you must connect a
47k resistor between t he
HWIN2 and DCOUT terminals.
Wiring Exterior Sirens
Panel terminal HWIN2 can be used for connecting exterior sirens and activates when intrusion
and fire alarms occur.
Exterior sirens can be wired with or without a resistor in the circuit for supervision. For circuit
supervision which allows the panel to detect if the siren wire is cut (open), Option 53: Hardw ire
Siren Supervision must be turned on (see the “Programming” section).
Hardwire Exterior Siren with Supervision
Connect a hardwire exterior siren to the panel using a 4.7k resistor as shown in Figure 5. The
resistor must be connected across the siren wires as close to the siren as possible.
A CA C
SIREN
H W I N 2
4.7k Resistor
(Locate at siren)
H W I N 1D C O U T
Figure 5. Hardwire Exterior Siren with Supervision
Hardwire Exterior Siren without Supervision
With Option 53 turned off, connect a hardwire exterior siren to the panel without a resistor as
shown in Figure 6.
A CA C
SIREN
Figure 6. Hardwire Exterior Siren without Supervision
H W I N 2
H W I N 1D C O U T
Wiring Hardwire Contacts
You can connect hardwire reed switches (normally closed loop only) to HWIN1 and/or HWIN2,
if either terminal is not being utilized for a hardwire siren.
!
Caution
Euro Simon Security System8
Connect only normally closed (N/C) reed switches to HWIN1 and/o r HWIN2. Other
types of hardwire detectors should not be used.
Page 14
Note
Do not install the resistor at
the panel terminals. This
does not provide supervision
of the wire
The total resistance of the wire loop must not exceed 3 ohms. This allows you to use up to 61 meters
of 2-conductor, .64 mm diameter stranded wire.
Connect hardwire reed switches to the panel using a 47k resistor as shown in Figure 7. The resistor
must be connected at the last switch in the circuit.
You can connect a phone line to the panel for systems monitored by a central monitoring station and/or systems that notify users by voice event notification.
Basically, there are two methods for connecting the panel to a phone line; full line seizure and
no line seizure.
Full Line Seizure
This method requires that the p a nel be w ired ahead (or in front) of all other phones, answerin g
machines, computers, or any ot her devi ces on the ph one line. This allows the p anel to tak e over
(seize) the phone line, even if another device on the line is in use.
An RJ-31X (CA-38A) jack should be installed when wiring for full line seizure. This lets the
user quickly and easily disconnect the panel from the phone line in case the panel disables the
phone line due to a malfunction.
¾
Full Line Seizure Wiring with an RJ-31X
1. Run a 4-conductor cable from the TELCO block to the RJ-31X (A in Figure 8).
2. Connect the 4-conductor cable wires to the RJ-31X (B in Figure 8).
3. Disconnect the TIP (+) and RING (-) premises phone jack wires from the TELCO block
and splice them to the 4-conductor cable Black and White (or Yellow) wires (C in Figure
8). Use weatherproof wire connectors for these splices.
4. Connect the 4-conductor cable Green wire to the TELCO block TIP (+) post and connect
the Red wire to the TELCO block RING (-) post (D in Figure 8).
5. Connect the phone cord included with the p a ne l to the RJ-31X and the panel LINE IN jack
(E in Figure 8)
Euro Simon Security System9
Page 15
BRNGRY
E
H W I N1D C O U TA C A C
- - - -
- - - - -
H W I N2
Note
If the customer ever add s a
phone or other phone device
to another phone jack, full
line seizure no longer exists.
Inform the customer to contact you if they want to add a
phone or other device so
that you can rewire for full
line seizure by adding an
RJ-31X.
GRN
Black
Green
TIP
RING
(+) (-)
D
Green
Black
C
Green
Figure 8. Full Line Seizure Wiring with RJ-31X
B
RED
Red
White
(or Yellow)
Red
White (or Yellow)
Red
A
Premises
Phone Jack
Wires
Brown
(T1)
Green
(Tip)
Gray
(R1)
Red
(Ring)
H W I N 1D C O U TAC AC
- - - -
- - - - -
H W I N 2
Figure 9. Full Line Seizure Wiring without RJ-31X
¾ Full Line Seizure Wiring without RJ-31X
1. Connect the green, red, brown, and gray wires of the 8-conductor phone cord included with
the panel as shown in Figure 9. Use weatherproof wire connectors for all splices.
2. Connect the plug end of the phone cord to the panel LINE IN jack
¾
Full Line Seizure Wiring with 1 Premises Phone
If a single phone is all that exists on the premises, full line seizure can be accomplished without
an RJ-31X.
1. Disconnect the phone from the premises phone jack and plug it into the panel PHONE jack
(A in Figure 10). This jack is disconnected automatically whenever the panel reports.
Connect the phone cord included with the panel to the panel LINE IN jack and the premises
phone jack (B in Figure 10)
Euro Simon Security System10
Page 16
Note
The panel does not have a
power switch. A readily
accessible power disconnect
device must be inco rporated in the building installation wiring to comply with
safety standards.
H W I N 1D C O U TAC AC
- - - -
- - - - -
Figure 10. Full Line Seizure Wiring with 1 Premises Phone
H W I N 2
Connecting and Applying Power
This section describes how to connect and apply AC and backup battery power to the panel.
AC Power Connections
The panel must be wired to an A C mains su ppl y wit h a vol ta ge r ange of 220-240 VAC, 50 Hz.
The panel voltage range appears on a label inside the panel (see Figure 11).
Electrical codes vary depending on the country and city where the system is installed. It is the
installer’s responsibility to ensure that the electrical installation is safe and conforms to all
applicable codes, laws, and regulations. Only qualified persons should connect the panel to the
mains supply and insert the 2 amp fuse. Read all instructions and safety warnings prior to making any conn ections.
A fused spur or other disconnect device must be installed in the building mains wiring in a
location near the panel. Wire having a cross sectional area of at least 0.75 mm
for connecting to the disconnect device. However, if the wire length between the disconnect
device and the building mains is less than 2 m, wire having a cross sectional area of 0.5 mm
can be used.
Once the panel has been connected to the mains supply, always isolate the supply before open-
ing the panel cover. After opening the panel cover, ensure the mains supply has been isolated
by checking the voltage on the mains terminal block inside the panel with a multimeter or neon
voltage tester. If the hot and neutral conductors are reversed in the building wiring, the wiring
inside the panel would still be live when the disconnect device was open.
2
must be used
2
Powering Up the Panel
Note
To avoid Low Ba tte ry me ssages, connect the backup
battery before enabling AC
power to the panel.
1. Turn off/disable the appropriate AC circuit at the mains supply.
2. Connect AC power wiring to the panel as described above and as shown in Figure 11 (A).
3. Install and connect the backup battery (B in Figure 11).
4. Turn on/enable the appropriate AC circuit at the mains supply.
!
Warning
Install/replace only with a Portalac PE6V3.2 rechargable, lead-acid battery. Observe
polarity when making battery connecti on s. Reversing the polarity may cause damage
to the panel. There is a risk of explosion if the wrong battery type is connected.
Euro Simon Security System11
Page 17
Voltage
e
Requirements
Label Here
- - - -
- - - - -
Black
-
B
+
Red
BRN
Blue
H W I N 2
N
A
H W I N 1D C O U T
L
A C
A C
Figure 11. Connecting and Applying Power
Installing X-10 Modules
¾ Lamp and Appliance Modules
1. Set the unit code dial to a unit number different from all other X-10 modules (between 1 and
8).
2. Set the house code for the installation.
3. Plug the module into a wall outlet.
4. Plug the lamp/appliance into the module.
Do not use Lamp Modules on appliances or lamps with 300-watt or larger bulbs
!
Caution
Universal Module
1. Set the unit code dial to a unit number different from all other X-10 modules (between 1 and
8).
2. Set the house code for the installation.
3. Set the module switches to momentary and relay only.
Do not put the panel antenna in the wall for installations thatrequire ant
Euro Simon Security System12
Page 18
4. Connect the module terminals to the desired device terminals.
5. Plug the universal module into a wall outlet.
Note
See “Light and Appliance
Controls” to program a Keychain Touchpad to activate a
Universal Module controlled
device.
Sensor Installation
Program sensors and devices before you install them. Use the following section to program the
panel and add the sensors to panel memory.
ProgrammingEntering Program Mode
There are 2 codes you can use to enter program mode.
Utility Access Code 1 (Dealer Code)
Depending upon how Option 54 is set, the default utility access code is 654321, 54321, 4321
(factory default), or 321. This code can be used for all programming.
Utility Access Code 2 (Installer Code)
Depending upon how Option 54 is set, the def ault access code is 654 321, 54 321, 43 21 (factor y
default), or 321. This code is limited to changing all but the following: Utility Access Code 1,
Options 4, 5, 6, 8, 9, 12, 13, 54, and 69.
1. Open the panel cover.
2. Enter Utility Access Code 1 or 2 using the numbered keys.
The panel is now in program mode. Follow the programming arrows on the panel label. The
system prompts you through programming steps with beeps and voice messages.
Note
Do not remove panel power
while in program mode. Programming changes are
saved only when exiting program mode (closing the
panel cover).
¾ Program the panel in this order:
1. Set the panel clock.
2. Add (learn) sensors.
3. Set House Code and Light & Appliance Controls (Entry/Exit activated lights, Sensor activated lights, Time activated lights).
4. Change numbered Options as needed.
Note
If Option 8: Phone Lock is
on, options 04, 05, 06, 08,
09, 12, 13, 54 and Dealer
Code will not reset to their
defaults.
Exiting Program Mode
Close the cover to exit program mode when you are finished programming.
Do not power down the panel while in program mo de or all pr o gramming will be lost.
!
Caution
The panel stores programmed information only when you exit program mode (close
the cover and leave closed for at least 5 seconds.
Reset Memory to the Factory Defaults
1. Open the panel cover and enter Utility Access code 1.
2. Unplug the transformer and disconnect the battery.
3. Simultaneously press and hold Cancel, Clock Set, and
Minutes +.
4. Restore power to the panel with either the battery or the transformer while pressing these
three buttons. The panel announces “Hello. System XX OK.” Release the buttons.
5. Connect the remaining power source to the panel.
Set the Clock
1. Press Clock Set from the Start Menu.
2. Press the Hours + and
announces the correct hour.
3. Press the Minutes + and
announces the correct minutes.
4. Press Done. The panel announces the set time.
– keys and listen to the voice prompts. Stop when panel voice
– keys and listen to the voice prompts. Stop when the panel
Euro Simon Security System13
Page 19
Adding (Learning) Sensors
These instructions describe how to add sensors, touchpads and other system devices into panel
memory. The panel recognizes a sensor when you press a sensor program button, press and
release a tamper switch, press a sensor test button, or put a sensor into alarm.
Note
The hardwire inputs must hav e si r ens or hardwire sensors with 47k Ohm re si st or s connected between
the DCOUT and HWIN1 or HWIN2 terminals before learning in a sensor. If one of these connections is
not made, the panel will learn in a hardwire zone.
Note
If you are installing a sensor on a gun case, jewelry box, or similar usage, and the sensor is active in
level one, you must sub-disarm to avoid putting the panel into alarm w hen the sensor and the magnet
are separated.
The following table, “Device Programming,” describes the programming button location for
each device
Device Programming
DeviceTo Program
Door/Window SensorPress button on top of sensor (cover removed) or trip tamper
Motion SensorPress button on back of sensor (mounting plate removed) or
Smoke SensorTrip tamper, press test button, remove from base or put sen-
Keychain TouchpadPress and hold Lock & Unlock buttons together
Remote Handheld TouchpadPress the EMERGENCY buttons
Hardwire SensorsSeparate sensor from magnet
Freeze & WaterTrip tamper or press and hold button on top of the sensor
trip tamper
sor in alarm
(cover removed) until control panel confirms programming. If button is not held down long enough, SYSTEM
STATUS reports sensor as open.
When adding (learning) sensors, the panel uses an ascending numbering sequence starting with
1. You can override this by entering the desired sensor number using the numbered keys.
Use the Table in Appendix B, which was filled o ut during the system plan
Euro Simon Security System14
Page 20
Note
For a more specific location
name, press Option # for
compass directions (north,
northeast, east, southeast,
south, southwest, west,
northwest).
Note
If you wish to use a sensor
number other than the next
one available, use the numbered keys to enter a 2 digit
sensor number imm edi atel y
after entering the sensor
type.
Version 3
Press for program
*
information.
Light
Control
Unit #
Instruction
Summary
Add Option
Option #1:
Panel Beeps
Option #2:
Panel Voice
Option #3:
Latchkey Time
Option #36:
Sensor Activated Light Lockout Start Time
Sensor Activated Light Lockout Stop Time
Option #37:
Chime Voice
Option #41:
Option #42:
Speaker Volume
Option #43:
Pager Phone Number
Option #55:
Status Beep Volume
Add Option #
Press
and follow voice prompts.
See Note
Entry/Exit
*
START MENU
Delete
Add
MAIN MENU
Sensor/
Remote
*
CONTROL MENU
Sensors
645
-
Add Access Code
Press
use red numbers to enter 4-digit code.
Set Clock
Clock Set
Press
Delay
DONE
Option #
**
Cancel
**
Add
10
Time
Minutes
Access Code
See Note
Hours
Test
AccessClock
Code
-
+
DONE
Minutes
See Note
Set
Hours
, then
System should be checked
by a qualified technician
at least every three years.
32
Note:
Hold key or press
+
repeatedly until you
hear the desired item.
978
Delete
To delete an option or access code
Delete
press
and follow the voice
prompting.
Cancel
If you make a mistake or want to
start over press
Sensor or Phone Test
DONE
To select a test, press
follow the voice prompting.
Cancel
Test
422-2806 Rev A
and
¾ To add a hardwire or RF sensor or remote control:
1. Press Add. The panel announces “Select from Main Menu.”
2. Press Sensor/Remote. The panel announces “Press button on sensor.”
3. Press the sensor program button or release sensor tamper switch. The panel announces
“Keychain Remote. Press sensor again for next name or press Done to select.”
4. Press Sensor/Remote repeatedly until you hear the name or item you want to use. An
alphabetical list of names the panel uses appears in Appendix B. Each name may be used
more than once.
5. Press DONE when you hear the desired name. The panel announces “Use numbered keys
to enter sensor group.”
6. Enter the 2-digit sensor group. The panel announces the first available sensor number and
sensor group, then prompts you to press DONE to accept.
7. Press DONE. The panel confirms programming by announcing the sensor number, name,
and group.
¾
To delete sensors:
1. Press Delete. The panel announces “Select from Main Menu.”
2. Press Sensor/Remote repeatedly until you hear the name and number you want deleted,
then press DONE. The panel announces that the sensor is deleted.
X-10 Module Operation
Use the following procedure to program X-10 module operations into panel memory. Notice
that the Light Control button is used t o program all X-10 module operat ions (li ght, appl iance,
and universal).
To program the house code:
¾
1. Press Add.
2. Press Light Control repeatedly until you hear the desired house code letter.
3. Press DONE.
4. Set the HOUSE dial on each lamp, appliance, and universal module, to the same letter.
5. Set the HOUSE dial on powerhorn/remote sirens to the next sequential alphabetical letter.
¾
To add an entry/exit activated modul e:
1. Press ADD.
2. Press Light Control.
Euro Simon Security System15
Page 21
Note
A Keychain Touchpad button
can also be programme d t o
control a light or appliance
module.
3. Press Unit # repeatedly until you hear the unit number that matches the one you chose for the
module.
4. Press Entry/Exit Delay. The panel confirms your programming.
¾
To add a sensor-activated module:
1. Press ADD.
2. Press Light Control.
3. Press Unit # repeatedly until you hear the unit number that matches the one you chose for the
module.
4. Press Sensors until you hear the sensor you want to control the light.
5. Press DONE. The panel confirms your programming.
¾
To add a time-activated module:
1. Press Add.
2. Press Light Control.
3. Press Unit # until you hear the unit number that matches the one you chose on the module.
4. Press Time.
5. Press Hours and Minutes to set the beginning of the schedule.
6. Press DONE.
7. Press Hours and Minutes to set the end of th e schedule.
8. Press DONE. The panel confirms your programming.
¾
To delete an Entry/Exit-activated module:
1. Press Delete.
2. Press Light Control.
3. Press Unit # repeatedly until you hear the unit number you want deleted.
4. Press Entry/Exit Delay, then press DONE. The panel confirms your programming.
Note
Although the panel voice
prompts you through programming, it is not nece ssary to wait for the complete
message before pressi ng
the next button in the programming sequence.
¾
To delete a sensor-activated module:
1. Press Delete.
2. Press Light Control.
3. Press Unit # repeatedly until you hear the unit number you want deleted.
4. Press Sensors until you hear the one you want deleted.
5. Press DONE. The panel confirms your programming.
¾
To delete a time-activated module:
1. Press Delete.
2. Press Light Control.
3. Press Unit # repeatedly until you hear the unit number you want deleted.
4. Press DONE. The panel confirms your programming
Numbered Options
Numbered options let you customize system operation according to dealer and user needs.
The “Numbered Options” table in Appendix B lists all system options and their characteristics.
Fill in the last column of the table before programming to help speed up the programming process.
There are two ways to reach the desired option setting.
•Press Add or Delete, then press Option # repeatedly until you hear the option you want
changed.
Or—
•Press Add or Delete, Option #, then enter the option number using the numbered keys.
The following instructions use the last method.
Euro Simon Security System16
Page 22
Option 01: Panel Piezo Beeps (Default = On)
Determines whether the panel piezo produces beeps based on system activity (on) or is silent
(off). The following table describes all possible beeps.
Panel Piezo Beeps
ActivityPiezo Beep Response
ARM Doors & WindowsExit Delay—2 beeps sound every 5 seconds and 2 times
ARM Motion SensorsExit Delay—3 beeps sound every 5 seconds and 3 times
Silent Exit—2 beeps sound at the beginning of the exit
delay and 2 more sound just before the exit delay
expires.
Entry Delay—2 beeps sound every 5 seconds and 2 times
per second during the last 10 seconds.
per second during the last 10 seconds.
Silent Exit—3 beeps sound at the beginning of the exit
delay and 3 more sound just before the exit delay
expires.
Entry Delay—3 beeps sound every 5 seconds and 3 times
per second during the last 10 seconds.
Exit Delay—4 beeps sound every 5 seconds and 4 times
per second during the last 10 seconds.
Silent Exit—4 beeps sound at the beginning of the exit
delay and 4 more sound just before the exit delay
expires.
Entry Delay—4 beeps sound every 5 seconds and 4 times
per second during the last 10 seconds.
Trouble Beeps6 beeps every minute. Press SYSTEM STATUS to stop
No Activity20 beeps every minute for 5 minutes (when programmed)
¾
To turn on Panel Piezo Beeps, press:
beeps for 4 hours.
Add—Option #—01—DONE.
To turn off Panel Piezo Beeps, press:
¾
Delete—Option #—01—DONE .
Option 02: Panel Voice (Default = On)
Determines whether the panel announces all status, alarm, and program mode messages (on),
or only announces messages for canceled alarms, open sensors (protesting), when SYSTEM
STATUS is pressed, or if the panel is in program mode (off).
¾
To turn on Panel Voice, press:
Add—Option #—02—DONE.
To turn off Panel Voice, press:
¾
Delete—Option #—02—DONE .
Option 03: Latchkey (Default = Off)
Determines whether the panel reports a Latchkey alarm if the system is not disarmed at a preset
time between midnight and 11:59
P.M. (on), or if the Latchkey feature is disabled (off).
Euro Simon Security System17
Page 23
Note
The system clock must be
set for the Latchkey feature
to work.
Note
Pressing DONE is required if
you enter fewer than 26 digits. The phone number is
automatically stored wit ho ut
pressing DONE if all 26
places are used.
Note
Pressing DONE is required if
you enter fewer than 26 digits. The phone number is
automatically stored wit ho ut
pressing DONE if all 26
places are used.
¾ To set Latchkey, press:
Add—Option #—03—Hours—Mi nutes—DONE.
To turn off Latchkey, press:
¾
Delete—Option #—03—DONE .
Option 04: Primary Phone Number (Default = none)
Lets you program up to a 26-digit central monitoring station receiver phone number for monitored systems (on), or delete a n existing primary phone number (off).
Press T est for each required paus e, Add for a *, and Delete for a # (each of which uses one of the
26 available places).
To set Primary Phone Number, press:
¾
Add—Option #—04—Up to 26 digits—DONE.
¾ To delete Primary Phone Number, press:
Delete—Option #—04—DONE .
Option 05: Secondary Phone Number (Default = none)
Lets you program up to a 26-digit central monitoring station receiver/voice event notification
phone number for monitored systems (on), or delete an existing secondary phone number (off).
Press T est for each required paus e, Add for a *, and Delete for a # (each of which uses one of the
26 available places).
¾
To set Secondary Phone Number, press:
Add—Option #—05—Up to 26 digits—DONE.
To delete Secondary Phone Number, press:
¾
Delete—Option #—05—DONE .
Option 06: Downloader Phone Number (Default = none)
Lets you program up to a 26-digit phone number for a computer modem for using ToolBox
Downloader (on), or delete an existing phone number (off).
Press T est for each required paus e, Add for a *, and Delete for a # (each of which uses one of the
26 available places).
Note
Pressing DONE is required if
you enter fewer than 26 digits. The phone number is
automatically stored wit ho ut
pressing DONE if all 26
places are used.
Note
The CID format only supports account numbers wi th
letters B through F, or numbers 0 through 9 (or a combination of those letters and
numbers).
Note
Pressing DONE is required if
you enter fewer than 10
characters. The account
number is automatica l ly
stored without pressing
DONE if 11 characters are
entered, of which only the
first 10 are stored.
¾
To set Downloader Phone Number, press:
Add—Option #—06—Up to 26 digits—DONE.
To delete Downloader Phone Number, press:
¾
Delete—Option #—06—DONE .
Option 07: Account Number (Default = 00000)
Lets you program up to a 10-character alphanumeric account number (on) or delete an existing
account number (off).
T o enter letters (A - F only), press 9 then the Minutes + button. The panel announces the letter A.
Continue pressing the Minutes + button to progress through the alphabet.
¾
To set Account Number, press:
Add—Option #—07—Up to 10 characters—DONE.
To delete Account Number, press:
¾
Delete—Option #—07—DONE .
Option 08: Phone Lock (Default = off)
Prevents resetting of phone/reporting related Options 04, 05, 06, 08, 09, 12, 13, 54 and Utility
Access Code 1 when a memory clear is performed (on), or resets these options to their default
values when a memory clear is performed (off).
¾
To turn on Phone Lock, press:
Add—Option #—08—DONE.
Euro Simon Security System18
Page 24
Note
The downloader code
should always be changed
from the default setting to
avoid competitor theft.
¾ To turn off Phone Lock, press:
Delete—Option #—08—DONE .
Option 09: Downloader Code (Default = 12345)
Lets you set a unique 5-digit code that is required for initiating ToolBox sessions (on) or sets
the code to its default (off).
The code must be 5 digits long and can range from 00000 to 99999. The Downloader Code
must match the downloader access code in the ToolBox account to perform ToolBox sessions.
¾
To set Downloader Code, press:
Add—Option #—09—5-digit code—DONE.
To delete Downloader Code (return to default), press:
¾
Delete—Option #—09—DONE .
Option 10: Entry Delay (Default = 030 sec.)
Determines how much time the user has to disarm the system after entering the armed premises
through a designated delay door, before an alarm occurs. Beeps sound during the entire delay
time to remind the user to disarm the system.
When turned on, the Entry Delay can be set from 005-254 seconds (030-254 if SIA Limits
Option 69 is on). All entries must be 3 digits. When turned off, the Entry Delay is set to 005
seconds.
¾
To set Entry Delay, press:
Add—Option #—10—3-digit delay time—DONE.
To reset Entry Delay (return to default), press:
¾
Delete—Option #—10—DONE .
Option 11: Exit Delay (Default = 060 sec.)
Determines how much time the user has to leave the premises through a design ated d elay d oor
after arming the system. Beeps sound after arming the system to remind the user to leave the
armed premises.
If a delay door is opened after the Exit Delay expires, the Entry Delay begins. If the user arms
the system with No Delay and opens a d elay do or after the Exit Delay expires, an alarm o ccurs.
When turned on, the Exit Delay can be set from 005-254 seconds (045-254 if SIA Limits
Option 69 is on). All entries must be 3 digits. When turned off, the Exit Delay is set to 005 seconds.
¾
To set Exit Delay, press:
Add—Option #—11—3-digit delay time—DONE.
To reset Exit Delay (return to default), press:
¾
Delete—Option #—11—DONE.
Option 12: Phone Mod 1 (Default = 0)
Determines the primary phone number (Option 4) report content and reporting format.
The following table describes the choices.
Phone Mod 1
Alarms include: Fire, Intrusion, Emer gen cy, Silent, and Alarm Cancels.
Setting #ContentFormat
0AllSIA
1AllContact ID
2Alarms onlySIA
3Alarms onlyContact ID
Euro Simon Security System19
Page 25
Non-alarms include: Latchkey, No Activity, Op eni ngs, Closings, Fail to Open, Fail to Close,
Force Armed, AC Power Failure, CPU Low Battery, and Trouble Restorals.
¾
To set Phone Mod 1, press:
Add—Opti on #—12—0, 1, 2, or 3—DONE.
To reset Phone Mod 1 (return to default), press:
¾
Delete—Option #—12—DONE .
Option 13: Phone Mod 2 (Default = 00)
Determines the secondary phone numb er (Option 5) report content and reporting format. The following table describes the choices. All entries must be 2 digits.
Phone Mod 2
Setting #ContentFormat
00AllSIA
01AllContact ID
02Alarms onlySIA
03Alarms onlyContact ID
04Non-Alarms onlySIA
05Non-Alarms onlyContact ID
06Phone 1 failureSIA
07Phone 1 failureContact ID
08Reserved
09Reserved
10Alarms only (See Options 43 and 44 for more
details.)
Voice Event Notifica-
tion
¾
To set Phone Mod 2, press:
Add—Opti on #—13—0, 1, 2, or 3—DONE.
To reset Phone Mod 2 (return to default), press:
¾
Delete—Option #—13—DONE .
Option 14: DTMF Dialing (Default = on)
Determines whether the panel uses DTMF (on) or pulse (off) for dialing programmed phone
numbers.
To turn on DTMF Dialing, press:
¾
Add—Option #—14—DONE.
To turn off DTMF Dialing, press:
¾
Delete—Option #—14—DONE .
Option 15: No Activity Time-out (Default = off)
¾
Determines whether the panel sends a No Activity report to a central station when the programmed time period elapses (on), or if the feature is disabled (off).
No activity means control panel, remote handheld, and keychain touchpad buttons have not be
pressed and sensors have not been tripped within a specified period of time (except sensors in
group 25).
The time-out can be set from 02 - 24 hours. All entries must be 2 digits.
¾
To set No Activity Time-out, press:
Add—Option #—15—02 - 24—DONE.
To turn off No Activity Time-out, press:
¾
Delete—Option #—15—DONE .
Euro Simon Security System20
Page 26
Note
Regardless of this option
setting, the panel always
dials immediately for alar m s
from sensors in groups 0-8,
26, for alarms triggered by
the control panel or remote
handheld touchpad emergency buttons, and for pro gramming, AC power failure,
and low battery reports.
Option 16: Auto Phone Test (Default = off)
Determines whether the panel automatically performs a periodic phone test (on) or not (off).
The test interval can be from 001 - 254 days. Entries must be 3 digits. The time of day the
panel performs the test is determined by Option 72: Supervisory Time, which must be turned
on for this feature to work.
To set Auto Phone Test, press:
¾
Add—Option #—16—001 - 254—DONE.
To turn off Auto Phone Test, press:
¾
Option 17: Dialer Delay (Default = off)
Determines whether the panel delays dialing programmed phone numbers before sending
reports (on), or if dialing begins immediately (off).
If Option 21: Opening (Disar ming) Repo rts is on, t he panel does not d elay dialing i f the system
is disarmed before the delay time expires. The pan e l dials imm ediat el y for both the alarm and
opening re port.
The delay time can be set from 005 - 254 seconds (015 to 045 if Option 69: SIA Limits is on).
Entries must be 3 digits.
To set Dialer Delay, press:
¾
Add—Option #—17—005 - 254—DONE.
To turn off Dialer Delay, press:
¾
Delete—Option #—17—DONE .
Note
Setting this feature to 2
hours (02) may cause fals e
reports.
Sets the time frame that determines whether the panel reports an alarm cancel message to the
central station.
If the system is disarmed from an alarm state within the programmed time, the panel sends an
alarm cancel message to the central station. An alarm cancel message is not reported if the system is disarmed after the programmed time expires.
The time can be set from 005 - 255 minutes. Entries must be 3 digits. When set to 255, the
panel always reports alarm cancel messages. Turning off this option disables alarm cancel
reporting.
¾
To turn on Alarm Cancel Report, press:
Add—Option #—18—005 - 255—DONE.
To turn off Alarm Cancel Report, press:
¾
Delete—Option #—18—DONE .
Option 19: RF Timeout (Default = 12 hours)
Determines the time period the panel must receive at least one supervisory signal from learned
sensors before identifying a sensor failure and sounding trouble beeps. Any sensor failure is
reported immediately and again at the supervisory time (Option 72: Supervisory Time).
The timeout can be set from 02-24 hours. Entries must be 2 digits.
To change RF Timeout, press:
¾
Add—Option #—19—02 - 24—DONE.
To reset RF Timeout (return to default), press:
¾
Delete—Option #—19—DONE .
Option 20: Manual Phone Test (Default = on)
Determines whether the user can perform a manual phone test to verify communication to a
central st ation (on), or not (off).
To turn on Manual Phone Test, press:
¾
Add—Option #—20—DONE.
Euro Simon Security System21
Page 27
¾ To turn off Manual Phone Test, press:
Delete—Option #—20—DONE .
Option 21: Opening Reports (Default = off)
Determines whether the panel sends opening reports to a central station whenever the system is
disarmed (on), or not (off).
¾
To turn on Opening Reports, press:
Add—Option #—21—DONE.
To turn off Opening Rep orts, press:
¾
Delete—Option #—21—DONE .
Option 22: Closing Reports (Default = off)
Determines whether the panel sends closing reports to a central station whenever the system is
armed (on), or not (off).
To turn on Closing Reports, press:
¾
Add—Option #—22—DONE.
¾
To turn off Closing Reports, press:
Delete—Option #—22—DONE .
Option 23: Force Armed Report (Default = off)
Determines whether the panel sends a force armed report to a central station if the user bypasses
protesting sensors (indirect bypass) when arming the system (on), or not (off).
To turn on Force Armed Report, press:
¾
Add—Option #—23—DONE.
To turn off Force Armed Report, press:
¾
Delete—Option #—23—DONE .
Option 24: AC Power Failure Report (Default = off)
Determines whether the panel sends AC power failure reports to a central station after the programmed time expires (on), or not (off).
When the panel is without AC power for 30 seconds, the panel LED’s turn off. When the panel is
without AC power for the programmed time, an AC power failure is reported. The panel reports
an AC power restoral when AC power returns to the panel.
The time can be set from 5-254 minutes. Entries must be 3 digits.
¾
T o turn on AC Power Failure Report, press:
Add—Option #—24—005 - 254—DONE.
¾
To turn off AC Power Failure Report, press:
Delete—Option #—24—DONE .
Option 25: CPU Low Battery Report (Default = on)
Determines whether the panel sends a low CPU battery report to the central station when the
panel backup battery voltage drops below 5.4 volts (on), or not (off).
To turn on CPU Low Battery Report, press:
¾
Add—Option #—25—DONE.
To turn off CPU Low Battery Report, press:
¾
Delete—Option #—25—DONE .
Euro Simon Security System22
Page 28
Option 26: Fail to Communicate (Default = on)
Determines whether the panel and interior sirens sound trouble beeps if it is unable to successfully send a report to a central station (on), or not (off).
To turn on Fail to Communicate, press:
¾
Add—Option #—26—DONE.
To turn off Fail to Communicate, press:
¾
Delete—Option #—26—DONE .
Option 27: Ring/Hang/Ring (Default = 1)
Determines when the panel answers a remote phone access or Toolbox call. Depending on
whether an answering machine exists at the panel location, off-site access to the panel can be
done with a series of phone calls or just one.
The following table shows the available settings.
Ring/Hang/Ring Settings
SettingControl Panel answers after:
1ring/hang/ring or 10 rings
2ring/hang/ring/hang/ring or 10 rings
3ring/hang/ring/hang/ring/hang/ring or 10
For off-site access where an answering machine does not exist, the user or ToolBox operator
simply calls the panel location once and listens for 10 rings. The panel should answer after the
tenth ring.
For off-site access where an answering machine exists, the user or ToolBox operator must perform the following steps:
1. Call the panel location.
2. Let the phone ring once, the n hang up.
3. W ait at least 10 seconds but not more than 40, then call the panel location again. The panel
should answer on the first ring.
If set to 1 or 5, perform steps 1 - 3 once.
If set to 2 or 6, perform steps 1 - 3 twice.
If set to 3 or 7, perform steps 1 - 3 three times.
¾
To turn on Ring/Hang/Ring, press:
Add—Opti on #—27—1, 2, 3, 4, 5, 6 or 7—DONE.
To turn off Ring/Hang/Ring (disable remote access), press:
¾
Delete—Option #—27—DONE .
Option 28: No Delay from Keychain Touchpad (Defaul t = off)
Determines whether a keychain touchpad arms th e system with no delay (on) or not (off).
Euro Simon Security System23
Page 29
Note
When this feature is on, the
system must be disarm ed
before entering the premises, since it is disabling
the Entry Delay. If Option 58:
Remote Touchpad Arming is
on, keychain touchpads cannot disarm the system and
will cause an alarm upon
entering.
¾ To turn on No Delay from Keychain Touchpad, press:
Add—Option #—28—DONE.
To turn off No Delay from Keychain Touchpad, press:
¾
Delete—Option #—28—DONE .
Option 29: Panel Piezo Alarms (Default = on)
Determines whether the panel piezo emits alarm sounds (on) or not (off).
¾
To turn on Panel Piezo Alarms, press:
Add—Option #—29—DONE.
¾
To turn off Panel Piezo Alarms, press:
Delete—Option #—29—DONE .
Option 30: Panel Panic Alarms (Default = on)
Determines whether the panel panic buttons (police, auxiliary, and fire) activate alarms when
pressed (on), or not (off).
To turn on Panel Panic Alarms, press:
¾
Add—Option #—30—DONE.
To turn off Panel Panic Alarms, press:
¾
Delete—Option #—30—DONE .
Option 31: Downloader Enable (Default = on)
Determines whether the panel can be accessed using ToolBox (on), or not (off).
Note
Panel voice announce ments are si lenced during
audio sessions. If the op er ator does not terminate the
session correctly, panel
announcements may not
occur for up to 90 seconds
after the operator hangs up.
Note
If this option is off, Option
47: 2-Way Mode and Option
48: Panic Talk—2-Way will
not work.
To turn on Downloader Enable, press:
¾
Add—Option #—31—DONE.
To turn off Downloader Enable, press:
¾
Delete—Option #—31—DONE .
Option 32: 300 Baud (Default = on)
Determines whether the baud rate used by the panel for central station or ToolBox communication is 300 bps (on) or 110 bps (off).
To turn on 300 Baud, press:
¾
Add—Option #—32—DONE.
To turn off 300 Baud, press:
¾
Delete—Option #—32—DONE .
Option 33: Audio Verification (Default = off)
Determines whether the system can perform 2-way voice audio sessions with a central station
operator ( on), or not (off).
To turn on Audio Verification, press:
¾
Add—Option #—33—DONE.
To turn off Audio Verification, press:
¾
Delete—Option #—33—DONE .
Euro Simon Security System24
Page 30
Note
System time must be set
correctly for this feature to
work.
Note
System time must be set
correctly for this feature to
work.
Note
System time must be set
correctly for this feature to
work.
Note
Both Options 36 and 37
must have a time programmed for this feature t o
work correctly.
Option 34: Fail to Open Report (Default = off)
Determines whether the panel sends a Fail to Open report to a central station if the system has
not been disarmed by the programmed time (on), or not (off).
¾ To turn on Fail to Open Report, press:
Add—Option #—34—Hours—Mi nutes—DONE.
To turn off Fail to Open Report, press:
¾
Delete—Option #—34—DONE .
Option 35: Fail to Close Report (Default = off)
Determines whether the panel sends a Fail to Close report to a central station if the system has
not been armed by the program med time (on), or not (off).
Sets the START time that determines when the panel prevents the sensor activated lights feature from turning on sensor activated lights.
When a time value is set (on) and the sensor activated lights feature is on, the panel prevents
sensor activated lights from turning on between the programmed start time (this option) and
the programmed stop time (Option 37).
When both Options 36 and 37 are turned off and the sensor activated lights feature is on, sensor activated lights turn on at all times.
To set Sensor Activated Light Lockout Start Time, press:
¾
Add—Option #—36—Hours—Mi nutes—DONE.
Note
System time must be set
correctly for this feature to
work.
Note
Both Options 36 and 37
must have a time programmed for this feature t o
work correctly.
To turn off Sensor Activated Light Lockout Start Time, press:
Sets the STOP time that determines when the panel prevents the sensor activated lights feature
from turning on sensor activated lights.
When a time value is set (on) and the sensor activated lights feature is on, the panel prevents
sensor activated lights from turning on between the programmed start time (Option 36) and the
programme d stop time (this option).
When both Options 36 and 37 are turned off and the sensor activated lights feature is on, sensor activated lights turn on at all times.
To set Sensor Activated Light Lockout Stop Time, press:
¾
Add—Option #—37—Hours—Mi nutes—DONE.
To turn off Sensor Activated Light Lockout Stop Time, press:
¾
Delete—Option #—37—DONE .
Option 38: Auto Arm (Default = off)
Determines how long the system protests (announces open/failed sensors) when attempting to
arm with open/failed sensors , before bypass ing these senso rs and automatically arming the rest
of the system.
Note
The panel protests an arming attempt when it has not received a restore (close) signal from sensors
learned into restore-specific sensor groups. Sensors learned into gr oup 26 (Fire) cannot be
bypassed. See “Sensor Group Characteristics” in “Appendix B” to identify sensor groups with restore
signal requirements.
Euro Simon Security System25
Page 31
Note
This option must be on for
Option 52: Unvacated Premises and Opt i on 59: Exit
Extensio n t o work correctly.
When this option is on, the panel announces all open/failed sensors repeatedly for 4 minutes, then
automatically bypasses the open sensors and arms the rest of the system. If a sensor is opened
during the exit delay and then left open, the panel will go into alarm after the exit delay has
expired.
Pressing the ARM Doors & Windows button a second time (before the 4-minute time expires)
bypasses all open sensors and arms the rest of the system. Pressing this butto n a third time eliminates the entry delay.
¾ To turn on Auto Arm, press:
Add—Option #—38—DONE.
When this option is off, the panel announces all open/failed sensors once, then automatically
bypasses the open sensors and arms the rest of the system after the Exit Delay has expired. If
other sensors are opened during the exit delay, they will also be bypassed if left open.
To turn off Auto Arm, press:
¾
Delete—Option #—38—DONE .
Option 39: Siren Timeout (Default = 4 min.)
Determines how long sirens sound alarms if no one is present to disarm the system.
The time can be set from 002 - 254 minutes. Entries must be 3 digits. When this feature is turned
off, sirens sound alarms until the alarm is canceled (system is disarmed).
To set Siren Timeout, press:
¾
Add—Option #—39—002 - 254—DONE.
To turn off Siren Timeout, press:
¾
Delete—Option #—39—DONE .
Option 40: Trouble Beeps (Default = on)
Determines whether the panel, X-10, and hardwire interior sirens sound six beeps every minute
when a trouble condition occurs (on) or not (off). The following conditions cause trouble beeps:
•AC power failure
•Low CPU battery
•Sensor failure (supervisory)
•Sensor trouble (low battery)
•Fail to communicate
•No Activity timer has timed out. Trouble beeps continue for 5 minutes and if the panel does
not see activity, trouble beeps stop and the panel reports the no activity to the central station.
Trouble beeps can be silenced by arming or disarming the system, or by pressing the STATUS
button. Trouble beeps resume 4 hours later if the trouble condition is not cleared.
¾
To turn on Trouble Beeps, press:
Add—Option #—40—DONE.
To turn off Trouble Beeps, press:
¾
Delete—Option #—40—DONE .
Option 41: Chime Voice (Default = off)
Determines whether the panel announces t he sensor numb er and name (on) or only sounds beeps
(off), when the CHIME Doors or CHIME Special Motion features are on and sensors in groups
10, 13, and 25 are tripped while the system is disarmed.
¾
To turn on Chime Voice, press:
Add—Option #—41—DONE.
To turn off Chime Voice, press:
¾
Delete—Option #—41—DONE .
Euro Simon Security System26
Page 32
Note
Pressing DONE is required if
you enter fewer than 26 digits. The phone number is
automatically stored wit ho ut
pressing DONE if all 26
places are used.
Option 42: Speaker Level (Default = 8)
Sets the volume of voice messages from the panel speaker.
The volume can be set from 1 (lowest) to 8 (highest). Turning off this option returns the setting
to the default value.
To set Speaker Level, press:
¾
Add—Opti on #—42—1 - 8—DONE.
To turn off Speaker Level (return to default), press:
¾
Delete—Option #—42—DONE .
Option 43: Voice Event Notification Phone Number (Default = off)
Lets you program up to a 26-digit ph one n umbe r for v oi ce event no tification (on), or delete an
existing phone number (off).
When programmed, a person at the remote phone location can hear system voice alarm
announcements. See the “Testing” section for more information.
Press Test for each required pause, Add for a *, and Delete for a # (each of which uses one of
the 26 available places).
To set Voice Event Notification Phone Number, press:
¾
Add—Option #—43—Up to 26 digits—DONE.
¾
To delete Voice Event Notification Phone Number, press:
Determines the report content and reporting format when Option 43: Numeric Pager/Voice
Event Notification Phone Number is programmed. The following table describes the choices.
All entries must be 2 digits.
Phone Mod 3
Setting #ContentFormat
08Latchkey, No Activity, Phone Test, Openings, Closings,
09Same as setting 8 plus AlarmsNumeric Pager
10Alarms onlyVoice Event Notification
¾
To set Voice Event Notification Phone Mod 3, press:
Fail to Open/Close, AC Power Restorals/Failures
Numeric Pager
Add—Option #—44—10—DONE.
To reset Voice Event Notification Phone Mod 3 (return to default), press:
¾
Delete—Option #—44—DONE .
Option 45: Sensor Alarm Restoral Report (Default = off )
Determines whether the panel reports sensor alarm restorals (on), or not (off). The following
table describes the possible settings.
Sensor Alarm Restoral Settings
SettingWhen Restorals are Reported
OffNo restoral reporting
1Immediately after sensor is closed or
restored
2After siren timeout expires
3When system is disarmed
Euro Simon Security System27
Page 33
Note
Option 33: Audio Verification
must be on for this feature to
work.
¾ To turn on Sensor Alarm Restoral Report, press:
Add—Option #—45—1, 2, or 3—DONE.
To turn off Sensor Alarm Restoral Report, press:
¾
Delete—Option #—45—DONE .
Option 46: Fire Shutdown - 2-Way (Default = off)
Determines whether system sirens are silenced during a 2-way audio session (on) or not (off).
Beeps sound every 10 seconds while sirens are silenced.
¾
To turn on Fire Shutdown - 2-Way, press:
Add—Option #—46—DONE.
To turn off Fire Shutdown - 2-Way, press:
¾
Delete—Option #—46—DONE .
Option 47: 2-Way Mode
Determines whether the panel hangs up and waits for a callback from the central station operator
before star ting a 2-way audio session (on), or stays on the line with the central station for an
instant audio session.
¾ To turn on 2-Way Mode (callback), press:
Add—Option #—47—DONE.
To turn off 2-Way Mode (instant), press:
¾
Delete—Option #—47—DONE .
Note
Option 33: Audio Verification
must be on for this feature to
work.
Option 48: Panic Talk - 2-Way (Default = off)
Determines whether the central station operator can talk to the user during a silent alarm (on) or
just listen in on the premises (off).
Silent alarms occur when sensors learned into groups 02 or 03 are tripped, when the Panic Code
is entered, or when the panel Police button is pressed and Option 74: Silent Panel Police Panic is
turned on.
¾ To turn on Panic Talk - 2-Way, press:
Add—Option #—48—DONE.
To turn off Panic Talk - 2-Way, press:
¾
Delete—Option #—48—DONE .
Option 49: Arming LEDs Shutdown (Default = off)
Determines whether the panel LEDs (buttons) turn off 30 seconds after the last button press (on),
or remain on for the entire arming period (off).
¾
To turn on Arming LEDs Shutdown, press:
Add—Option #—49—DONE.
¾
To turn off Arming LEDs Shutdown, press:
Delete—Option #—49—DONE .
Option 50: RF Jam Detect (Default = off)
Determines whether the panel checks for and reports RF interference/jam to the central station
(on), or not (off).
If this option is on and the panel receives a constant 433 MHz signal, the panel speaker
announces “Option 50 detected” and reports the condition to the central station. If this opt ion is
off, the panel does not detect an RF jam.
¾
To turn on Jam Detect, press:
Add—Option #—50—DONE.
To turn off Jam Detect, press:
¾
Euro Simon Security System28
Page 34
Note
This feat ure does not work
from a keychain touchpad.
Note
Option 38: Auto Arm must
be on for this feature to
work.
Delete—Option #—50—DONE .
Option 51: 24 Hour Sensor Tamper (Default = off)
Determines whether the system (armed or disarmed) goes into and reports an alarm anytime a
sensor tamper switch is tripped (o n), or only when the system is armed and a tamper switch of
an armed sensor is tripped (off).
To turn on 24 Hour Tamper, press:
¾
Add—Option #—51—DONE.
To turn off 24 Hour Tamper, press:
¾
Delete—Option #—51—DONE .
Option 52: Unvacated Premises (Default = off)
Determines whether the system automatically arms down to level 2 (ARM Doors & Windows)
if the user arms the system to level 4 (ARM Doors & Windows + ARM Motion Sensors) without leaving the premises (on), or remains at the armed level chosen by the user (off).
If this option is turned on and the user arms to level 4 (ARM Doors & Windows, + ARM
Motion Sensors) but does not exit the premises within the Exit Delay time, the panel automatically changes to arming level 2.
Determines whether the panel monitors hardwired sirens for open conditions (on), or not (off).
If this option is turned on, sirens connected to the panel terminals require an EOL resistor in
the wire circuit (see “Installing the System” for siren superv ision wiring). If this option is
turned off, EOL resistors are not required whether sirens are connected or not.
To turn on Hardwire Siren Supervision, press:
¾
Add—Option #—53—DONE.
To turn off Hardwire Siren Supervision, press:
¾
Delete—Option #—53—DONE .
Option 54: Access Code Length (Default = 4)
Determines how many digits are in all access codes.
Turning on this option lets you set the access code length to 3 , 4 , 5, or 6 digits. Turning off this
option resets the access code length to the default setting, resets Master, Utility 1, and Utility
access codes.
Read the following before changing this option.
•This option affects all system access codes (Master, Utility 1, Utility 2, Panic, and User).
•Changing the access code length changes the Master, Utility 1, and Utility 2 access codes
to their respective defaults as described in the following table.
Note
Changing the Access Code Length clears/deletes any User Codes that were previously programmed.
If the customer wants the Access Code Length changed, it should be se t bef or e pr ogr am m i ng any
new (unprogramme d) acc ess codes, whenever possible.
Euro Simon Security System29
Page 35
Access Code Length Defaults
SettingDefault Code
3Master—123
Utility 1—321
Utility 2—321
4Master—1234
Utility 1—4321
Utility 2—4321
5Master—12345
Utility 1—54321
Utility 2—54321
6Master—123456
Utility 1—654321
Utility 2—654321
¾ To change Access Code Length, press:
Add—Opti on #—54—3, 4, 5, or 6—DONE.
To reset Access Code Length (to default), press:
¾
Delete—Option #—54—DONE .
Option 55: Status Beep Volume (Default = 07)
Determines the panel piezo volume level for status sounds such as arming, trouble, and status
beeps.
The volume can be set from 1 (lowest) to 10 (highest). Turning off this option resets the volume
to the default setting. Entries must be 2 digits.
Note
Pressing DONE is required if
you enter fewer than 26 digits. The phone number is
automatically stored wit ho ut
pressing DONE if all 26
places are used.
Note
This option is typically used
only in Europe where a
supervisory condi t io n is
required to report as a
tamper.
To set Status Beep Volume, press:
¾
Add—Option #—55—01 - 10—DONE.
To reset Status Beep Volume (return to default), press:
¾
Delete—Option #—55—DONE .
Option 56: Call Waiting (Default = off)
Lets you program up to a 26-digit number or code that disables call waiting or any other phone
service before dialing central station or voice event notification phone numbers (on). When this
option is turned off, the panel dials only the central station phone number.
Press T est for each required paus e, Add for a *, and Delete for a # (each of which uses one of the
26 available places).
Determines whether the panel sends supervisory reports to a central station as a tamper (on) or a
supervisory (off).
¾ To report supervisories as Tamper Reports, press:
Add—Option #—57—DONE.
To report supervisories as Supervisory Reports, press:
¾
Delete—Option #—57—DONE .
Euro Simon Security System30
Page 36
Note
n
Option 38 must be ON for
exit extension to work.
Option 58: Remote Touchpad Arming (Default = off)
Determines whether keychain and remote touchpads can disarm the system only during exit
and entry delays (on), or arm and disarm the system anytime (off).
If this option and Option 28 (No Delay from Keychain Touchpad) are on, users cannot
!
Caution
To turn on Remote Touchpad Arming, press:
¾
Add—Option #—58—DONE.
To turn off Remote Touchpad Arming, press:
¾
Delete—Option #—58—DONE .
enter and/or disarm using remote touchpads , without causing an alarm.
Do not put thepanel antenna in the wall for installations thatrequire a
Option 59: Exit Extension (Default = on)
Determines whether the panel restarts the exit delay time if the user enters the armed premises
during the initial exit delay period (on), or not (off).
Turning on this feat ure allows users to re-enter du ring the exit del ay period, with out disar ming
and then re-arming the system. Turning off this feature requires the user to disarm and re-arm
the system.
¾
To turn on Exit Extension, press:
Add—Option #—59—DONE.
To turn off Exit Extension, press:
¾
Delete—Option #—59—DONE .
Option 60: Secure Arming (Default = off)
Determines whether an access code is required when arming the system (on) or not (off).
This option does not affect keychain touchpad arm/disarm operation.
¾
To turn on Secure Arming, press:
Add—Option #—60—DONE.
To turn off Secure Arming, press:
¾
Delete—Option #—60—DONE .
Option 61: Demo Mode (Default = off)
Determines whether the panel operates as a demonstration model (on) o r a stan dard panel (o f f).
Turning on this feature disables low battery supervision and allows the microphone to remain
on continuously during a 2-way audio session.
To turn on Demo Mode, press:
¾
Add—Option #—61—DONE.
To turn off Demo Mode, press:
¾
Delete—Option #—61—DONE .
Option 62: Reserved
Option 63: 24 Hour Time (Default = off )
Determines whether the panel uses a 24-hour clock (on) or 12-hour clock (off).
To turn on 24 Hour Time, press:
¾
Add—Option #—63—DONE.
To turn off 24 Hour Time, press:
¾
Euro Simon Security System31
Page 37
Delete—Option #—63—DONE .
Option 64: No Arm on Panel Low Battery (Default = off)
Determines whether the system prevents users from arming if a low CPU battery condition exists
(on) or not (off).
To turn on No Arm on Panel Low Battery, press:
¾
Add—Option #—64—DONE.
To turn off No Arm on Panel Low Battery, press:
¾
Delete—Option #—64—DONE .
Option 65: No Usage Report (Default = off)
Determines whether the panel sends a No Usage report to the central station if the user has not
operated the system before the programmed time expires (on) or not (off). The timer starts each
time the system is disarmed.
This is a customer service feature that alerts the central station if a customer is not using their
security system. The service provider can then contact the customer to find ou t why the s ystem is
not being used, and help correct any problems for the customer.
The time can be set from 001 to 254 days. Entries must be 3 digits.
¾
To turn on No Usage Report, press:
Add—Option #—65—001 - 254—DONE.
To turn off No Usage Report, press:
¾
Delete—Option #—65—DONE .
Note
Swinger Shutdown does not
affect smoke and fire se nsors.
Option 66: External Siren Delay (Default = off)
Determines whether external siren activation is delayed 30 seconds after an alarm caused by a
delayed sens or (on), or if external siren activation is immediate upon alarm activation (off).
¾
To turn on External Siren Delay, press:
Add—Option #—66—DONE.
¾
To turn off External Siren Delay, press:
Delete—Option #—66—DONE .
Option 67: Quick Exit (Default = off)
Determines whether pressing the Disarm button when the system is armed activates the exit
delay time to allow exit and re-entry without disarming the system ( on) or not ( off).
This feature is useful if the user wants to step outside briefly and return, such as to get the paper.
If the system is armed and the user presses the Disarm button, the panel announces “Exit time
on” and sounds exit delay beeps. This allows a designated entry/exit door to be open for up to 2
minutes without causing an alarm. When the door is closed, the beeps stop and the door is armed
again.
¾
T o turn on Quick Exit, press:
Add—Option #—67—DONE.
¾
To turn off Quick Exit, press:
Delete—Option #—67—DONE .
Option 68: Swinger Shutdown (Default = on)
Determines whether the panel prevents the same sensor from activating an alarm more than once
in a single arming period (on) or not (off).
¾ To turn on Swinger Shutdown, press:
Add—Option #—68—DONE.
To turn off Swinger Shutdown, press:
¾
Euro Simon Security System32
Page 38
Delete—Option #—68—DONE .
Option 69: SIA Limits (Default = on)*
Determines whether Entry, Exit, and Dialer delay times fall within SIA limits (on) or factory
ranges (off) .
The following table shows the available settings when this option is on or off.
SIA Limits
Note
If options 10, 11 or 17 are
set outside the SIA limits
while Option 69 is OFF, turning Option 69 ON will not
affect options 10, 11 or 17,
until they are manually
changed.
Important !
This option works correctly only if the panel
phone line is wired for line
seizure! If the panel is wired
in parallel with the phone
line and t his o pti on is on, t he
panel detects a “line cut”
whenever the phone is in
use.
Determines whether the panel detects and indicates a phone line failure trouble condition
before the programmed time expires (on) or not at all (off).
The range is 02-48 in 5 second incr ements, with 02 bein g a 10 second dela y and 48 being a 24 0
second delay.
To turn on Line Cut Detection, press:
¾
Add—Option #—70—02 - 48—DONE.
To turn off Line Cut Detection, press:
¾
Delete—Option #—70—DONE .
Note
The panel clock must be set
to the correct time for this
option and Option 16: Auto
Phone Test to work correctl y.
Option 71: Programming Report (Default = off)
Determines whether the panel sends a report to the central station anytime the programming
mode is entered/exited (on) or not at all (off).
The panel sends a report whenever the dealer (Utility 1) or installer (Utility 2) code is used to
enter programming mod e and anoth er report is sent when t he programming session ends (whe n
the cover is closed).
¾
To turn on Programming Report, press:
Add—Option #—71—DONE.
¾
To turn off Programming Report, press:
Delete—Option #—71—DONE .
Option 72: Supervisory Time (Default = 12:00am)
Determines when the panel reports supervisory conditions (sen sor failures) and automatic
phone tests to the central station.
¾ To set Supervisory Time, press:
Add—Option #—72—Hours—Mi nutes—DONE.
To turn off (disable) Supervisory Time, press:
¾
Delete—Option #—71—DONE .
Euro Simon Security System33
Page 39
Note
This feature should be used
only if the panel experiences
consistent trouble reporting
to the central station. Otherwise, leave this option off.
Option 73: Modem Sensitivity (Default = off)
Determines whether the modem sensitivity is set to normal (off) or high (on).
Determines whether pressing the panel police panic button causes an audible (off) or silent (on)
alarm.
To turn on Silent Panel Police Panic, press:
¾
Add—Option #—74—DONE.
To turn off Silent Panel Police Panic, press:
¾
Delete—Option #—74—DONE .
Option 75: VOX Mic Gain (Default = 14)
Sets the mic gain (sensitivity) that triggers the voice-activated switching (VOX).
Room size, acoustics, and furnishings where the panel or Interrogator 200 are located will influ-
ence the setting. The available settings are 01 (low) - 64 (high). Entries must be 2 digits.
For panels with a built-in microphone, a setting of 14 is recommended. For sy stems using the
Interrogator 200, a setting of 7 should be used.
Note
This option works in conjunction with Option 75: VOX
Mic Gain. It is important to
follow the setting recommendations as described to
achieve acceptable opera tion.
¾
To set VOX Mic Gain, press:
Add—Option #—75—01 - 64—DONE.
To reset Vox Mic Gain (return to default), press:
¾
Delete—Option #—75—DONE .
Option 76: VOX Gain Range (Default = 64)
Sets the gain range for the voice-activated switching (VOX).
The available settings are 01 (low) - 64 (high). Entries must be 2 digits.
For best results, this option should be set equal to or greater than Option 75: VOX Mic Gain. For
panels with a built-in microphone, this option should be set to the default value.
¾
To set VOX Gain Range, press:
Add—Option #—76—01 - 64—DONE.
To reset VOX Gain Range (return to default), press:
¾
Delete—Option #—76—DONE .
Option 77: Manual Mic Gain (Default = 64)
Determines the gain level (sensitivity) during 2-way audio sessions, when Option 33: Audio Verification is set to 0 or 1 (Speak).
Room size, acoustics, and furnishings where the panel or Interrogator 200 are located will influence the setting. The available settings are 01 (low) - 64 (high). Entries must be 2 digits.
For panels with a built-in microphone, a setting of 64 is recommended. For sy stems using the
Interrogator 200, a setting of 20 should be used.
¾
To set Manual Mic Gain, press:
Add—Option #—77—01 - 64—DONE.
¾
To reset Manual Mic Gain (return to default), press:
Delete—Option #—77—DONE .
Euro Simon Security System34
Page 40
Note
Changing this setting do es
not affect speaker volum e.
Option 78: VOX Receiver Gain (Default = 6)
Determines the receiver gain level during 2-way audio sessions.
If the VOX is switching the speaker on when the central station operator is not talking, lower
both this setting and Option 75: VOX Mic Gain setting. If the VOX is not switching th e
speaker on when the central station operator is talking, raise this setting and lower Option 75:
VOX Mic Gain setting.
This option can be set from 01 - 10. Entries must be 2 digits.
To set VOX Receiver Gain, press:
¾
Add—Option #—78—1 - 10—DONE.
To reset VOX Receiver Gain (return to default), press:
¾
Delete—Option #—78—DONE .
Option 79: Panel Cover Tamper (Default = off)
Determines whether the panel activates a tamper alarm anytime the cover is opened (on), or
only when the system is armed (off).
To enter program mode when this option is on, you must first enter the Master Access code,
then open the cover and enter program mode within 10 seconds.
To turn on Panel Cover Tamper, press:
¾
Add—Option #—79—DONE.
¾
To turn off Panel Cover Tamper (return to default), press:
Determines whether the panel verifies successful alarm reports to the central station with the
voice message “Phone communication okay” (on), or not (off).
To turn on Alarm Report Verification, press:
¾
Add—Option #—80—DONE.
To turn off Alarm Report Verification (return to default), press:
¾
Delete—Option #—80—DONE .
Programming System Access Codes
Utility Access Code 1 (Dealer Code)
Depending upon how Option 54 is set, the default utility access code is 654321, 54321, 4321
(factory default), or 321. This code can be used for all programming.
Utility Access Code 2 (Installer Code)
Depending upon how Option 54 is set, the def ault access code is 654 321, 54 321, 43 21 (factor y
default), or 321. This code is limited to changing all but the following: Utility Access Code 1,
Options 4, 5, 6, 8, 9, 12, 13, 54, and 69.
Master Access Code
Depending upon how Option 54 is set, the default Mast er Access Code is 123456, 12345, 1234
(factory default), or 123. This code is used to: disarm the panel, subdisarm the panel, program
light control, set the system clock, program the master code, program access codes 1-5, program the panic code, perform a sensor or phone test, and program options 1, 2, 3, 31, 36, 37,
41, 42, 43, and 55.
Access Codes (1 - 5)
The panel can have up to 5 secondary user access codes. These could be used by children, a
baby sitter, or a service person to disarm (or arm if Option 60 is on). These codes cannot be
used for programming.
Euro Simon Security System35
Page 41
Panic Code
The Panic Code is able t o arm , di s arm, or subdisarm the panel and send a silent alarm to the Central Station. There will be no indication of an alarm at the panel.
To add a code:
¾
1. Press Add.
2. Press Access Code button. Continue pressing this button until you hear the access code to be
changed.
3. Press DONE.
4. Enter the new access code by using the numbered keys. The panel announces the new code.
¾
To delete a code:
1. Press Delete.
2. Press Access Code. Continue pressing thi s button until you hear the access code to be
deleted.
3. Press DONE. The panel announces the code is deleted.
Testing the
System
Note
An access code is required
when arming if Option 60:
Secure Arming is on.
This section describes how to perform the following test procedures:
•Control Panel
•Testing sensors
•Testing phone communication
•Testing central station communications
•Testing the X-10 Lamp Modules
You should test the system after installing, after servicing, and after adding or removing devices
from the system.
Control Panel
Test the Control Panel by pressing the buttons as described below.
•ARM Doors & Windows-The panel arms Doors & Windows. Press twice to eliminate the
programmed entry delay. The button will blink when No Entry Delay is on.
•ARM Motion Sensors-The panel will arm Motion Sensors. Press twice to turn Latchkey on.
The button blinks when Latchkey is on.
•DISARM -The panel will prompt you to enter an access code. Enter the appropriate code and
the panel will disarm Doors, Windows, and Motion Sensors.
Arming Levels
Arming LevelDescription of Level
0Sub-disarms (Master Access and Panic codes only), and bypasses 24
hour intrusion senso rs (Master Access Code only). Fi re sensors (g roup
26) cannot be sub-disarmed.
•SYSTEM STATUS-Press to determine system status and system time.
Euro Simon Security System36
1Disarm the system
2Arm Doors and Windows
3Arm Motions
4Arm Doors, Windows, and Motions
•Two beeps verify that Door/Window sensors are armed.
•One beep indicates the system is disarmed
•Three beeps verify that Motion Sensors are armed.
•Four beeps verify that both Door/Window and Motion sensors are armed.
Page 42
Note
While the sensor test is a
valuable installation and service tool, it only tests sensor
operation for the current
conditions. You should perform a sensor test after any
change in environmen t,
equipment, or programm i ng.
•CHIME Doors-Press to enable two beeps that sound from interior sirens, panel siren, an d
the X-10 powerhorn siren (if set to unit number 9) when a protected door or window
learned into sensor group 10 or 13 is opened. If Option 41: Chime Voice is on, the panel
speaker also announces the sensor name and number.
•CHIME Special Motion- Press to enable three beeps that sound from interior sirens, panel
siren, and the X-10 powerhorn siren (if set to unit number 9) when a Motion Sensor that is
programmed as sensor type 25 is activated. If there are no sensors learned into sensor group
25, this function will not be available. If Option 41: Chime Voice is on, the panel speaker
also announces the sensor name and number.
•LIGHTS Time Activated-Press to enable system controlled lights to turn on/off at a scheduled time.
•LIGHTS Sensor Activated-Press to enable system controlled lights to turn on for 4 minutes
when a specific sensor is tripped.
•AUX, POLICE, FIRE-Press and hold or press twice quickly to activate a non-medical,
police, or fire emergency alarm
Sensor Testing
We recommend that you test the sensors after all programming is completed and whenever a
sensor-related problem occurs.
1. Place all sensors in their secured (non-alarm) state.
2. Open the panel cover.
3. Enter the appropriate access code.
4. Press Test.
The panel responds with Sensor test, press again to change or DONE to select.
5. Press DONE. The panel prompts you to trip each sensor one at a time. You may follow the
panel voice prompting or test the sensors in any order. Use the “Sensor Tripping Instructions” table on the next page.
Note
If a sensor does not meet
the minimum transmission
beep requirements, refer to
the “If a Sensor Fails the
Sensor Test” section of this
manual
Sensor Tripping Instructions
SensorDo This
Door/WindowOpen the secured door or window
FreezeApply ice to the sensor. Do not allow the sensor to get wet
WaterPress a wet rag or wet finger over both of the round, gold-plated ter-
Glass GuardTap the glass 7 to 10 cm from the sensor
Motion SensorAvoid the Motion Sensor field of view for 5 minutes, then enter its
Rate-of-Rise Heat
Detector
ShockTap the glass twice, away from the sensor. Wait at least 30 seconds
SmokePress and hold the test button until the system sounds transmission
Panic ButtonsPress and hold the appropriate panic button(s) for 3 seconds
KeyChain Touchpad Press and hold LOCK and UNLOCK simultaneously for 3 seconds
Remote Handheld
Touchpad
minals on the underside of the sensor
view
Rub your hands together until warm, then place one hand on the
detector for 30 seconds
before testing again
beeps
Press and hold the 2 EMERGENCY button s simu lta neous ly for 3 se c-
onds
6. Interior sirens and speakers sound transmission beeps and a v oice annou ncemen t identifies
the tripped sensor. Each beep represents one RF packet. Count the number of beeps and
refer to the “Minimum Beeps” table for minimum requirements. After the beeps, the panel
announces, Sensor Name is activated, sensor status is XX (XX = number of RF packets).
The system will continue to prompt for sensors that have not yet been tested. When all sensors have been tested the panel will announce, Sensor test complete, press DONE.
7. Press DONE. The panel announces, Sensor Test OK.
8. If Cancel or DONE is pressed and the panel has not heard from all sensors, the panel will
respond, Sensor test canceled or failure.
Improving Sensor/Panel Communication
Antenna
The panel antenna can be put into the wall to increase the panel RF range.
Do not put the panel antenna in the wall for in stallations th at r equi re antenna tamper for
!
Caution
external antennas
If a Sensor Fails the Sensor Test
If sirens do not beep when a sensor is tripped, use an RF Sniffer (60-401) test tool to verify that
the sensor is transmitting. Constant beeps from the RF Sniffer indicate a runaway (faulty) sensor .
Replace the sensor.
If possible, locate sensors within 30.5 meters of the panel. While a sensor may have a range of
152.5 meters or more out in the open, the environment at the installation site can have a signifi-
cant effect on transmitter range. A change in sensor location may help overcome adverse wireless
conditions and can be accomplished by the following:
•relocate the sensor
•if necessary, replace the sensor
¾
To relocate a sensor
1. Test the sensor a few centimeters fro m the original position.
2. Increase the distance from the original position and retest until an acceptable location is
found.
3. Mount the sensor in the new location.
4. If no location is acceptable, replace the sensor.
¾
To replace a sensor
1. Test a known good sensor at the same location.
2. If the transmission beeps remain below the minimum level, avoid mounting a sensor at that
location.
3. If the known-good sensor functions, contact GE Interlogix for repair or replacement of the
problem sensor.
Phone Communication
Perform a phone test to check the phone communication between the panel and the central station.
Euro Simon Security System38
Page 44
¾ To perform a phone test or Downloader (DL) phone test
1. Open the panel cover.
2. Enter the appropriate access code.
3. Press Test twice to perform a phone test
OR
Press Test three times to perform a DL ph one test.
4. Press DONE. The panel confirms that a phone test or downloader phone test has begun.
When the phone test is complete, the panel announces Phone Test is OK within 3 minutes.
If the test is unsuccessful, the SYSTEM STATUS button will light and the panel voice
announces Phone communication failure within 10 minutes.
If the panel announces Phone communication failure, proceed to the following instructions.
If the phone test fails
¾
1. Check that the panel is connected to the phone jack.
2. Check the phone number programmed into the panel.
3. Perform the phone test again.
4. If the phone test fails again, check the phone connection wiring.
Off-Site Phone Operation
Test the system from a remote phone using the commands in the following table.
Remote Phone Operation
System FunctionPhone Command
DISARM* + CODE + 1
ARM Doors/Windows* + CODE + 2
ARM Motion Sensors* + CODE + 3
ARM Doors/Windows with No Entry Delay* + CODE + 2 + 2
ARM Motion Sensors with Latchkey* + CODE + 3 + 3
ARM Doors/Windows and Motion Sensors* + CODE + 2 + 3
ARM Doors/Windows with No Entry Delay
and Motion Sensors with Latchkey
Toggle Lights* + CODE + 0
System Status* + CODE + # + 1
Audio Verification* + CODE + 5 + X (X = a command
Terminate Session* + CODE + 9
* + CODE + 2 + 2 + 3 + 3
from Audio Verification Set)
Central Station Communication
After performing sensor and phone tests, check that the s ystem is reporting alarms successf ully
to the central station.
To test communication with the central station:
¾
1. Call the central station and tell the operator that you will be testing the sy stem .
2. Arm the system.
3. Test each of the wireless panic buttons and trip at least one sensor of each type (fire, intrusion, etc.) to verify that the appropriate alarms are working correctly.
Euro Simon Security System39
Page 45
4. When you finish testing the system, call the central station to verify that the alarms were
received.
User Codes for Opening and Closing Reports
Arm or Disarm from:Reports as User:
Panel or Remote Handheld Touchpad0
Keychain Touc hpad1-24 (sen sor number)
Master Code30
Access Codes 1-531-35
Panic Code36
2-Way Voice Operation
To initiate an audio session, the central station operator must perform the following steps:
1. After the panel has completed reporting the alarm , pick up th e CS ph on e and pres s the
ton to start the audio session.
2. Press 1 or 0 to speak, 2 for VOX operation, and 3 or 6 to listen.
3. Press 99 to terminate the session.
Note
Panel voice announce m ents are silenced during 2-way audio sessions. If t he operator does not terminate the session correctly, panel announcements may not occur for up to 90 seconds after the operator
hangs up.
Note
T o conduct an audio session using remote phone access see the Table “Phone Commands for Remote
Access” in the “Testing” section.
‚ but-
Audio Verification Set
Phone Button(s)Function
0-1Speak
2VOX operation
3 or 6Listen
7Extend session for 90 more seconds
88Terminates session w ith cal l bac k (the p anel answers on t he firs t ring
99Terminates session with no call back
if called within 5 minutes)
Voice Event Notification
Testing this feature requires two people; one at the alarm site and the other at the location the
panel is programmed to call (Options 5 and/or 43). The panel only reports alarms when this feature is set up.
CAUTION!
If the system is moni tored by a ce ntral stat ion , con tact t hem fi rst be fore s etting off a ny al arm
s to avoid a false dispatch.
1. Contact the central monitoring station (if system is monitored) to inform them you are testing
the system and not to dispatch authorities.
2. At the system site, put the system into an alarm condition.
3. At the calling location, pick up the phone after it starts ringing. You should hear the panel
voice announce “Press star for alarm.”
Euro Simon Security System40
Page 46
Important !
You must terminate the call
by pressing
the panel may not disconnect from the phone line for
up to 2 minutes.
Note
The X-10 Siren must be set
to unit #9 to “hear” emergency alarms.
ƒ. Otherwise,
4. Press ‚ and the panel voice identifies the alarm. If there is more than one alarm in
progress, the panel voice identifies all of them.
5. After listening to the alarm information, press
ƒ to terminate the call.
X-10 Operation
The following sections describe how to test X-10 Lamp, Siren, Appliance, and Universal Module operation.
Manual Lamp Module Control
•Control Panel: Press the Lights On button and the unit # of the lamp module using the
numeric buttons to test individual lamp modules 2, 4, 6, and 8. The panel responds with
Lights # on/off.
Press the Lights On button twice to turn on all lamp modules. Press the Lights Off button
twice to turn off all lamp modules.
•Keychain Touchpad: Press the LIGHT button repeatedly to turn all light s on and of f. T he
panel responds with Lights on/off.
•Remote Handheld Touchpad: Press the Lights On button and the unit # of the lamp
module using the n umer ic bu tto ns to test individual lamp module s 2, 4, 6, and 8. The panel
responds with Lights # on/off.
X-10 Siren and Lamp Module Functions
All sirens turn off when the system is disarmed or when the siren timeout expires. Siren priority is as follows:
1. Fire (highest priority)
2. Intrusion
3. Emergency
If an alarm of greater priority occurs during an alarm of lower priority, the greater priority
alarm sirens sound. Fire alarms sound a temporal 3 pattern (0 .5 second s on, 0. 5 second s of f f or
three beeps then 1.5 seconds off).
How to clear SYSTEM STATUS (Alarm Memory)
From a disarmed state press SYSTEM STATUS, listen to the status message, then press DIS-
ARM.
Panel announces Siren 1 failure or Siren 2 failure.
•Turn option 53 off if a hardwire siren or sensor is not connected.
•Check for the correct end-of-line resistor in HWIN 1 and 2 circuits.
Panel announces Low Battery.
•Check that panel backup battery is connected.
Panel announces Option 50 Detected.
•Option 50 is RF jam detect. The control panel has detected RF interference.
Panel announces that a sensor is open.
•See Sensors section below.
Panel announces System time is not set.
•Set the system time.
Control Panel
Panel announces Function not avai lable when Chime Doors is pressed.
•No sensors are programmed using sensor type 10 or 13.
Panel announces Function not avai lable when Chime Special Motion is pressed.
•No sensors are programmed using sensor ty pe 25.
Panel announces Function not avai lable when LIGHTS Time Activated is pressed.
•No time activated lights have been programmed.
Panel announces Function not avai lable when LIGHTS Sensor Activated is pressed.
•No sensor a ctivated lights ha ve been programmed.
Panel announces Invalid. Sensor already programmed as Sensor Name.
•This sensor is already programmed. Delete sensor if not correctly programmed.
Options (Programmable by the homeowner)
Panel does not beep.
•Turn on (add) Option 1.
Latchkey does not function.
•Latchkey time (option 3) is not set. Set Latchkey time.
•Latchkey is not enabled. Enable Latchkey by pressing ARM Motion Sensors twice.
•The phone number is not p rogrammed p roperly. Reprogram the phone number. (options 13 or
43)
•System Time is not set. Set system time.
Sensors
A sensor does not work.
•Make sure the battery is fresh and installed correctly.
•Check for interference from metal objects. Move or rotate the sensor.
•Move the sensor to a new location.
Door or window is closed, but the panel announces it is open.
•Be certain the arrow on the magnet and the guide line on the transmitter are aligned and
within 1/4 inch of each other.
•The sensor tamper switch may be open (cover off).
Euro Simon Security System42
Page 48
Motion sensors go off continuously.
•Be sure the sensor is mounted on a solid surface and the viewing field is free from sources
of changing temperature.
Motion sensor does not respond to motion.
•Make sure the sensor battery is fresh and installed correctly. Wait 2 minutes after installing
a new battery to test the sensor.
•Adjust the sensor mounting.
•Leave the area for 3 minutes, then retest.
•The environment is too hot or too cold. Outdoor sensors will operate between 32° and
120°F.
•Dirt or dust may be causing the problem. Wipe the sensor with a clean, damp cloth.
X-10 Modules
All Lamp Modules or Siren not working.
•Be sure the panel transformer is plugged into an outlet that is not controlled by a switch.
•Check that the panel is powered using the line carrier power transformer.
•House code was programmed incorrectly.
One Lamp Module or Siren is not working.
•Unplug nearby equipment that may be causing interference (light dimmer switches, televisions, appliances with older motors).
•Check that the switch on the lamp or appliance is turned on and remains on.
•Make sure the lamp has a working bulb.
•Make sure the lamp or appliance is plugged into the Lamp/Appliance Module, the Module
is plugged into the outlet and the outlet is not controlled by a switch.
•Make sure the House and Unit Codes are correct.
•Move the Module to a different outlet that is on the same phase (branch) of the household
electrical circuit as the panel.
Time or sensor activated light not working.
•Make sure you have programmed the light to be activated by a timer or sensor.
•Make sure the system clock is set.
•Make sure these functions have been enabled by pressing the LIGHTS Time Activated/
Sensor Activated butto n on the panel. The functions are enabled if the button is lit.
Appendix B:
System
Configuration
Sensor
No.
01
02
03
04
05
06
07
08
09
Device
Sensor
Group
Sensor Assignments/Locations
Sensor Name/LocationNotes
Euro Simon Security System43
Page 49
Sensor Assignments/Locations
Sensor
No.
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Device
Sensor
Group
Sensor Name/LocationNotes
Alphabetical Listing of Sensor Names
Attic, Back Door, Back Window, Basement, Basement Window, Bathroom, Bath room Window,
Bedroom, Bedroom Window, Ch i ld’s Room, Child’s Room Window, Closet, Den, Den Window,
Dining Room, Dining Room Window, Downstairs, Downstairs Window, Front Door, Front Window, Garage, Garage Door, Garage Window, Guest Room, Guest Room Window, Hallway, Keychain Remote, Kitchen, Kitchen Window, Laundry Room, Laundry Room Window, Living
Room, Living Room Window, Master Bedroom, Master Bedroom Window, Medicine Cabinet,
Module, Office, Office Window, Patio Door, Phone Communication Module, Porch, Porch Window, Special Chime, System Panic, T ouchpad Remote, Upstairs, Upstairs Window, Utility Room
I = Instant Delay (no delay, immediate alarm)
S = Standard Delay (alarm sounds after programmed entry delay time)
F = Follower Delay (alarm sounds immediately if entry/exit delay is not active, otherwise alarm sounds after programmed
entry delay time)
CS report
08 Special Intrusion: such as gun cabinets and wall safes.IntrusionIYes Yes1234
09 Special Intrusion: such as gun cabinets and wall safes.IntrusionSYes Yes1234
10 Entry/Exit Delay: Entry/Exit Delay that require a standard delay time. Chime IntrusionSYes Yes24
13 Instant perimeter: Exterior doors and windows. ChimeIntrusionIYes Yes 24
14 Instant Interior: Interior doorsIntrusionFYes Yes234
15 Instant Interior: Interior PIR motion sensorsIntrusionFNo Yes 234
16 Instant Interior: Interior doorsIntrusionFYes Yes34
17 Instant Interior: PIR motion sensorsIntrusionFNo Yes 34
18 Instant Interior Cross Zone: PIR motion sensorsIntrusionFNo Yes34
19 Delayed Interior: interior doors that initiate a delay before going into alarmIntrusionSYes Yes34
20 Delayed Interior: PIR motion sensors that initiate a delay before going into
alarm
21 Local Instant Interior: 24 hour local alarm zone protecting anything that
opens and closes. No Report.
22 Local delayed interior: same as group 21, plus activation initiates a delay
before going into alarm. No report.
23 Local instant Auxiliary: 24 hour local alarm zone protecting anything that
opens and closes. No report
24 Local Instant Auxiliary: 24 hour local alarm zone protecting anything that
opens and closes. Sirens shut off at restoral. No report.
25 Local Special Chime: Notify the user when a door is opened. Sounds emit
from a local annunciator. Direct Bypass and Unbypass when no Special
Motion Chime sensors are in the security system. No report.
26 Fire: 24 hour fire, rate-of-rise heat, and smoke sensors§.FireIYes Yes01234
27 Lamp control or other customer feature. No reportSilentIYes Yes01234
28 PIR motion sensor, sound sensor, or pressure mat. No reportSilentINo Yes01234
29 Auxiliary: Freeze SensorsTrouble
32 PIR motion sensor or sound sensor. No reportSilentINo No01234
34 Carbon Monoxide AlarmEmergencyIYes Yes01234
35 Entry/Exit Delay Interior PIR MotionIntrusionSNo Yes234
36 Special Intrusion: such as gun cabinets and wall safes. Reports as a tamper
if tripped
37 Light Switch Control: X-10 Modules turn either on or off when a door is
opened. No report.
38 Auxiliary: Water Sensors.Trouble
Name/ApplicationSiren Type
EmergencyINo No01234
IntrusionSNo Yes34
IntrusionIYes Yes 1234
IntrusionSYes Yes1234
EmergencyIYes Yes01234
EmergencyIYes Yes01234
Three Beeps INo Yes 01234
Beeps
IntrusionIYes Yes 1234
SilentINo Yes01234
Beeps
Delay
Restoral
IYes Yes 01234
IYes Yes 01234
in
Levels
Supervisory
Delays:
I = Instant Delay (no delay, immediate alarm)
S = Standard Delay (alarm sounds after programmed entry delay time)
F = Follower Delay (alarm sounds immediately if entry/exit delay is not active, otherwise alarm sounds after programmed
entry delay time)
Euro Simon Security System45
Page 51
Home Control Planning Table
ModuleActivated byTime Activated
Unit #TypeLocationSensorEntry/ExitStart TimeStop Time
The factory default setting is a 4-digit access code, but the default codes will chang e whenever Option 54
(Access Code Length) is reset. The default for each access code length is listed.
69 is added
12Phone Mod 1000-3U1
13Phone Mod 2000000-10U1
14DTMFOnPulseOn/OffU1 U2
15No Activity ReportOffOff02-24 hrsU1 U2
16Auto Phone Test OffOff001-254 daysU1 U2
17Dialer DelayOffOff005-254 sec
U1 U2
015-045 is Option
69 is added
18Alarm Cancel005Off005-255 minU1 U2
19RF Timeout (SUPSYNC)12 hrs02 hrs02-24 hrsU1 U2
20Manual Phone TestOnOffOn/OffU1 U2
21Opening ReportsOffOffOn/OffU1 U2
22Closing ReportsOffOffOn/OffU1 U2
23Force Armed ReportOffOffOn/OffU1 U2
24AC Power Failure ReportOffOff005-254 minU1 U2
25CPU Low Battery Report OnOffOn/OffU1 U2
26Fail to CommunicateOnOffOn/OffU1 U2
27Ring/Hang/Ring1Off1-7U1 U2
28No Delay from Key Chain TouchpadOffOffOn/OffU1 U2
29Panel Piezo AlarmsOnOffOn/OffU1 U2
30Panic AlarmsOnOffOn/OffU1 U2
31Downloader EnableOnOffOn/OffU1 U2 M
32300 Baud Central Station CommunicationsOn110 Baud On/OffU1 U2
33Audio VerificationOffOffOn/OffU1 U2
34Fail to OpenOffOff12:00 Midnight -
11:59 PM
38Auto ArmOffOffOn/OffU1 U2
39Siren Time Out04 minSiren
never
002 - 254 minutes/
no time out
U1 U2
times
out
40Trouble BeepsOnOffOn/OffU1 U2
41Chime VoiceOffOffOn/OffU1 U2 M
42Speaker Level881-8U1 U2 M
43Voice Event Notification Phone NumberOffOff26 di gitsU1 U2 M
44Voice Event Notification Phone Mod 39908-10U1 U2
45Sensor Alarm RestoralOff (0)Off (0)0 - 3U1 U2
46Fire Shutdown - 2-WayOffOffOn/OffU1 U2
Installer
Settings
Euro Simon Security System47
Page 53
FunctionDefaultDeleteRange
Opt. #
472-Way ModeOffOffOn (Callback)
Who Can
Change:
U1 U2
Off (Instant)
48Panic Talk - 2-WayOffOffOn/OffU1 U2
49Arming LEDs ShutdownOffOffOn/OffU1 U2
50RF Jam DetectOffOffOn/OffU1 U2
5124 Hour Sensor TamperOffOffOn/OffU1 U2
52Unvacated PremisesOffOffOn/OffU1 U2
53 Hardwire Siren SupervisionOffOffOn/OffU1 U2
54Access Code Length443-6U1
55Status Beep Volume771 - 10U1 U2 M
56Call WaitingOffOff1-26 digits/OffU1 U2
57Supervisory Tamper ReportOffOffOn/OffU1 U2
58Remote Touchpad ArmingOffOffOn/OffU1 U2
59Exit ExtensionOnOffOn/OffU1 U2
60Secure ArmingOffOffOn/OffU1 U2
61Demo ModeOffOffOn/OffU1 U2
62Reserved
6324 Hour ClockOffOffOn/OffU1 U2
64No Arm on Panel Low BatteryOffOffOn/OffU1 U2
65No Usage ReportOffOff1-254/OffU1 U2
66External Siren DelayOffOffOn/OffU1 U2
67Quick ExitOffOffOn/OffU1 U2
68Swinger ShutdownOnOffOn/OffU1 U2
69SIA LimitsOnOffOn/OffU1
70Line Cut DetectionOffOff02-48 (10-240 sec
U1 U2
in 5 sec intervals)/Off
71Programming ReportOffOffOn/OffU1 U2
72Supervisory TimeMidnightOff12:00 Midnight -
U1 U2
11:59 PM
73Modem SensitivityOff (nor-
mal)
74Panel Police Panic AudioOff (audi-
ble
OffOn (high)/Off (nor-
mal)
OffOn (silent)
Off (audible)
U1 U2
U1 U2
75VOX Mic Gain14141-64U1 U2
76VOX Gain Range64641-64U1 U2
77Manual Mic Gain64641-64U1 U2
78VOX Receiver Gain060601 - 10U1 U2
79Panel Tamper AlarmOffOffOn/OffU1, U2
80Alarm Report VerificationOffOffOn/OffU1, U2
Installer
Settings
Euro Simon Security System48
Page 54
SpecificationsPower Requirements: .....220 - 240 VAC, 50 Hz.
Rechargeable Batteries: ..Portalac PE6V3.2 6.0 VDC 3.2 Ah Rechargeable Lead-Acid. The battery will
Radio Frequency: ............433 MHz
Nominal Range: ...............152.5 meters, open-air receiving range
Storage Temperature Range: -34° C to 60° C
Operating Temperature Range: 0° C to 50° C
Maximum Humid it y : ......90% relative humidity, noncondensing
Auxiliary Power: .............Unregulated 5.1 - 12 VDC, power-limited to 250 mA (maximum) @ 10 VDC
last 60 hours with no AC.
Euro Simon Security System49
Page 55
Euro Simon Security System50
Page 56
Quick Reference Tab le
How to …
How to …
Disarm the
Disarm the
System (Level 1)
System
Subdisarm the
Subdisarm the
System (Level 0)
System
Arm Only - Doors
Arm Only - Doors
& Windows
& Windows
(Level 2)
Arm Only –
Arm Only –
Motion Sensors
Motion Sensors
(Level 3)
Arm Doors,
Arm Doors,
Windows & Motion
Windows &
Sensors
Motion Sensors
(Level 4)
Activate No Entry
Activate No Entry
Delay
Delay
Activate Latchkey
Activate Latchkey
Feature
Feature
Activate a Panic
Activate a Panic
Alarm
Alarm
Check the System
Check the System
Status
Status
Set Doors or
Set Doors to
Special Motion to
Chime
Chime
Direct Bypass a
Set Special
Sensor
Motion to Chime
Turn Time
Turn Time
Activated Lights
Activated Lights
On/Off
On/Off
Turn Sensor
Turn Sensor
Activated Lights
Activated Lights
On/Off
On/OffOpen Garage
Turn On Special
Door or Turn On
Lights
Special Lights
Turn All Lights
Turn All Lights
On
On
Turn All Lights
Turn All Lights
Off
Off
Control Panel
Control Panel
Access Code
+
Access Code
+
Disarm
Disarm
Enter Master Code while
Enter Access Code while
system is disarmed
system isdisarmed
Doors &
Doors &
Windows
Windows
Press once
Press once
Arm
Arm
Motion
Motion
Sensors
Sensors
Arm
Arm
Doors &
Doors &
Windows
Windows
Arm
Doors &
Doors &
Windows
Windows
Motion
Motion
Sensors
Sensors
Arm
Arm
Arm
Motion
Motion
Sensors
Sensors
Arm
Arm
Press once
Press once
Press
Press
each
each
button
button
once
once
Press twice
Press twice
Press twice
Press twice
Press twice
Police
System
System
Status
Status
Doors
Chime
Time
Time
Sensor
Sensor
Lights
Lights
Lights
Lights
Chime
Chime
SpecialMotion
Bypass
On
MotionDoors
Bypass
Lights
Lights
On
Off
Press once
Press once
Press either
Doors or
Press once
Motion once
Press once to
bypass, press
Press once
again to
unbypass
Press once
Press once
Lights
Lights
Press once
Press once
Press twice
Press twice
Off
Press twice
Press twice
Remote Handheld
Remote Handheld
Touchpad
Touchpad
Disarm
Disarm
Enter Master Code while
Enter Access Code while
system is disarmed
system isdisarmed
ARM
ARM
Doors &
Doors &
Windows
Windows
ARM
ARM
Motion
Motion
Sensors
Sensors
ARM
ARM
Doors &
Doors &
Windows
Windows
Press each button once
Press eachbutton once
ARM
ARM
Doors &
Doors &
Windows
Windows
ARM
ARM
Motion
Motion
Sensors
Sensors
SYSTEM
SYSTEM
STATUS
STATUS
Access Code
Access Code
+
+
Press once
Press once
Press once
Press once
ARM
ARM
Motion
Motion
Sensors
Sensors
Press twice
Press twice
Press twice
Press twice
Press both
Press both
Emergency buttons
Emergency buttons
and hold for 3
and hold for 3
seconds
seconds
Press once
Press once
+ Unit #
+ Unit #
Press twice
Press twice
Press twice
Press twice
Keychain
Key Chain
Touchpad
Touchpad
Press once
Press once
Press once
Press once
Press twice
Press twice
Press once (if
Press once (if
programmed)
programmed)
Press 3 times
Press 3 times
Press both
Press both
& hold for
& hold for
3 second s
3 seconds
Press once
Press once
Press once
Press once
Press once
Press once
Remote
Remote
Phone
Phone
Press * +
Press * + Master
Code + 1
Code + 1
Press * + Master
Press * + Master
Code + 1
Code + 1
Press * + Master
Press * +
Code + 2
Code + 2
Press * +
Press* + Master
Code + 3
Code + 3
Press * +
Press* + Master
Code + 2 + 3
Code + 2 + 3
Press * +
Press* + Master
Code + 2 + 2
Code + 2 +2
Press * +
Press* + Master
Code + 3 + 3
Code + 3 +3
Press * +
Press* + Master
Code + # + 1
Code +# + 1
Press * +
Press * + Master
Code + 0
Code + 0
Press * +
Press * + Master
Code + 0
Code + 0
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.