GE
g
READ THOROUGHLY BEFORE INSTALLING
Lighting Solutions
WARNING
Risk of electric shock
• Turn power off before servicing
– see instructions
GENERAL
This luminaire is designed for use in outdoor applications and must adhere to 25°C Max ambient temperature
limitation. Install and maintain it according to the
following recommendations.
Make all electrical connections in accordance with
the National Electrical Code and any applicable
local code requirements.
Verify that supply voltage is correct by comparing it
to nameplate.
CAUTION
Unit will fall if not installed properly
• Follow installation instructions
GEH-5757D
INSTRUCTIONS
GE Edison V Luminaire
TRADITIONAL
COLONIAL
GLOBE
IF SINGLE VOLTAGE:
All single voltage ballasts are pre-wired such that user
need only connect the supply conductors.
IF MULTIVOLT: (120/208/240/277 volts)
Connect the ballast lead with the insulated terminal to
the desired voltage terminal as indicated on the ballast
terminal nameplate.
IF MULTIWATT:
Multiwatt ballasts are available in various combinations of
wattage. See wiring instructions on wiring tag inside the
luminaire.
GLOBE
TRADITIONAL
STANDARD
GLOBE
BALLAST COVER
OPTIONAL OUTLET RECEPTACLE
When used the access door should
be re-installed with the plug cord
positioned through wire way.
Wire way for optional
outlet receptacle
LINE
GROUND
LINE OR NEUTRAL
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or
maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred
to GE Lighting Solutions.
TERMINAL
BOARD
MOUNTING
SET SCREWS
(3 FURNISHED)
TORQUE TO 18-22
FOOT-POUNDS
GLOBE
SET SCREWS
(FURNISHED)
BASE CASTING
OPTIONAL PHOTO CONTROL
(Ordered separately)
Rotate base casting so that PE
window points away from other
light sources.
ACCESS DOOR
Remove door to install power
connections and optional photo
control.
LAMPS
CAUTION
Risk of burn
• Allow lamp/fixture to cool before
handling
Use only lamps specified on nameplate. Observe
lamp manufacturer’s recommendations and restric-
tions on lamp operation, particularly ballast type,
burning position, etc.
LAMP TIGHTNESS: The lamp should be securely
inserted to NEMA-EEI specified torque of 35 inchpounds, which is best achieved by very firmly tightening
to insure application of sufficient torque. Tightening
must be sufficient to fully depress and load center contact
of socket.
MAINTENANCE
Clean globe by washing with mild non-abrasive detergent solution. Rinse with clean water.
g
GE Lighting Solutions • 1-888-MY-GE-LED • www.gelightingsolutions.com
GE Lighting Solutions is a subsidiary of the General Electric Company. Evolve and other trademarks belong to GE Lighting Solutions. The GE brand and logo are trademarks of the General Electric Company.
© 2011 GE Lighting Solutions. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.
16943533----888
35-201578-W2 (6/04) GELS