• Independent (IS1series)
Use Starter Kit in general case. Use Starter SKU if preferred.
BEFORE YOU BEGIN
Read these instructions completely and carefully.
Important notes included below and on page 3.
WARNING/AVERTISSEMENT
RISK OF ELECTRICSHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electricalenclosure.
RISK OF ELECTRICSHOCK
• Follow all NEC and local codes.
• Use only UL approved wire for input/output connections.
Minimumsize 18 AWG or 14AWG for continuous runs.
• When using multi-branch wire circuits with a sharedneutral,do not
operate any circuit with the neutral open. Also ensure all neutral connections
are secure before energizing the circuit.An openneutral can cause an
overvoltage condition at the luminairepower supply.
RISQUES DE DÉCHARGESÉLECTRIQUES
• Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier
d’alimentationélectrique.
RISQUESD’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des fils approuvés par UL pour les entrées/sorties de
connexion. Tailleminimum 18AWG ou14 AWG pour les rangées continues.
• Lorsque vous utilisezdes circuits câblés à branches multiples avec un
neutre commun, nemettez aucuncircuit en service avec le neutre ouvert.
Assurez-vous également que tous les raccords neutres soit sécurisés avant
de mettre le circuit soustension. Un neutre ouvert peut causer une condition
de surtensionà l’alimentation du luminaire.
Installation Guide
Save These Instructions
Use only in the manner intended by the manufacturer. If
you have any questions, contact themanufacturer.
Prepare Electrical Wiring
Electrical Requirements
The LED fixturemust be supplied with 120-277VAC,
50/60Hz or 347V, 50/60Hz and protected by a max.
20 ampere circuit breaker. Use min. 75°C supply
conductor. 347V power should only be supplied to
luminaires with voltage code “D”.
Grounding Instructions
The grounding and bonding of the overall system
shall be done in accordance with National Electric
Code (NEC) Article 600 and local codes.
Components Supplied:
• Luminaire
• 2 MountingBrackets
• End Caps (2supplied with IS1 series and ISS series)
Note: In general case, with the Starter Kit, the Starter SKU
will notbe required.
Tools and Components Required:
• T15 torx or phillips #2screwdriver
• UL Listed conduit connectionsper NEC/CEC
for nominalconduit trade sizes ½” or ¾”
• UL Listed wire connectors
Table of ContentsPage
Accessory Kits
Installation of an Independent Unit (IS1)3
Installation of a Continuous Row using a Starter Kit4
Installation of a Continuous Row with Optional
Use to connect a continuous row of fixtures tosupply leads
Mounting Brackets
94210 - Standard Kit (10brackets)
Use if extra brackets are required
SuspensionKits
9308800 - Anti-snaking Kit (10brackets)
Use if installation geometry requires a mounting
point up to 1” off axis of continuous row
93026986 - Upper Mounting Kit (pack of2)
Use to provide mounting anchor infinished ceiling
210221 - Joint Spanning Kit (5 brackets)
Use if installation geometry requires a
mounting point directly over fixture/fixture
junction
93026985 - Lower Mounting Kit (pack of 2)
Use to suspend luminaire up to 10’ below fixed
structure or Upper MountingKit
93026987 - Power Feed CanopyKit (pack of 1)
Use to cover exposed junction boxin pendant mount applications
2
IMPORTANT - Maximum Length of Electrical Run
IS of First GenerationIS of Second Generation
Lumen CodeLumenCode
VoltageA E,G,S or JB,F or KM,N,P or RU,V,W or X
120V192’160’80’60’
277V or 347V400’320’188’132’
• Please see technical data sheet for electrical properties
to ensure safe installation.
• Under any circumstance, maximum driver current
through connectedfixtures shall not exceed15A for
types A, G, J,B, F, K, or E.
• Maximum drive current through connectedfixtures shall
not exceed 12A for types M, N, P, R.
IS series luminaires come in two versions: continuous units (ISC series) and independentunits (IS1 series). A continuous electrical run
will consist of a number of continuous units up to a maximum current specified above. When installing luminaires use clean gloves
in order to avoid fouling the reflective surface. To insure a clean fixture, install the fixture with the plastic bag around the fixture, and
then remove plastic bag upon completion of any and all construction related activity.
Voltage[A3][A7][B1][B4]
120V192’160’80’60’
277V or347V400’320’188’132’
• Maximum driver current through connected fixtures shall
not exceed 15A for lumen codes [42], [52], [84], or [A0].
• Maxiumum driver current through connected fixtures shall
not exceed 12A for lumen codes [65], [85], [A3], [A7], [A1],
[A2], [B1] or[B4].
[42] [84][52][A0]
If two additional circuits are included in luminaire, they must be connected in daisy chain to the same
circuit breaker as per diagram below and total current not exceeding a maximum of 15A or 12A (per
above comment).
[65] [85][A1][A2]
Breaker
Daintree Node
Identiftcation Label
Daintree Node identification label installed
1
on luminaire back reflector.
1
Remove package with smaller label. This label
2
is to beused for customer floor plan or records.
Circuit #1
Circuit #2
Installation of an Independent Unit (IS1)
Choose suspensionmethod
Carefully unpack unit and inspect for
12
defects before installing. Wear work
gloves to prevent dirt and oil from
being transferred to the luminaire.
NOTE: When installing luminaires use
clean gloves in order to avoid fouling
the reflective surface.
Attach mounting bracket to ceiling
support structure either directly or
using a GE suspension kit according
to the suspension kit instructions
(see page 2). Maximum distance
between suspensionpoints shall not
exceed the length of the luminaire.
3
ACline
Prepare luminaire for installation
3
by loosening the PSU cover screws
and removing the cover.
ACline
Connect the green (ground), black
6
(line) and white (neutral) wires of
the AC line to the similarly colored
wires of the power supply unit using
separate UL listed wire nuts.
PSU
wires
For 347V ftxture: Loosen PSU cover
4
screws and remove two covers.
Dimming line
(optional)
Dimming
wires
Optional dimmer: Install UL listed
7
electrical fitting and insert dimming
control wires through. Connect
dimming control wires (grey and violet
for 0-10V or violet and violet/white strip
for DALI) to the similarly colored fixture
wire using separate UL listed wire nuts.
Carefully remove appropriate knockout
5
for AC line input wires (inner knockout
for ½”conduit, outer knockout for
¾” conduit). Install listed electrical
fittings in the knockoutholes for wire
protection and pass supply conduit
through electrical fittings.
Clipluminairetothepreviously
8
installed mountingbrackets.
Fix the mounting position and secure
9
the suspension by tightening the two
screws on both mountingbrackets.
Replace power supply cover(s) by
10
sliding over the captive screws and
secure by tighteningthem.
Note: When installation iscomplete,
all lead wires and connectors shall
be totallyenclosed.
4
DALI
Fixture
Line
Neutral
Ground Green
DALI Violet/White
DALI Violet
Wiring Diagrams
0-10V
Fixture
Black
White
Neutral
Ground
(0-10V)+
(0-10V)–
Line
Black
White
Green
Violet
Grey
Installation of a Continuous Row using a Starter Kit
Use starter kits as a convenient way to install continuous rows. Starter kits are ordered separately (SKU 93018007provides parts for
1 continuous row, SKU 93022791 provides parts for 10 continuous rows).
CAUTION
THERE IS A REqUIRED DIRECTION FOR ASSEMBLING A CONTINUOUS ROW.
Ceiling
ACline
First fixture in
the row
Direction of continuous row installation
Continuous runs must begin with a first unit that is suspended at both ends. Use provided end-caps from starter kits to begin and
terminate the row.
The Starter & Continuous Run fixtures connect in rows
Dimming line
(optional)
Next fixture in
the row
As the name implies, the Starter (if your product has such a choice) contains the beginning of the electrical connection.
This means that this fixture has the onl
y Power Drop.
The starter, when suspended, also is normally the only fixture in the row with (2) suspension hangers.
The rest of the run may be suspended from a single hanger (positioned near the end where the next fixture will connect).
For mechanical installation, follow steps 1-6 described earlier in these install instructions.
Connectto power harness in
driverenclosure
Connect to AC line using
separateUL listed wire nuts
Use provided starter power harness as an extension
1
for the first fixture in the row.
Connectto next fixture in
continuous row
Connect to dimmingline
(optional) using separate
UL listed wirenuts
A dimming starter harness is provided to optionally
2
connect the dimming through wiring to the dimming line.
5
Connect to dimmingharness
in driverenclosure
Connectto next fixture in
continuous row
DALI
Fixture
Line
Neutral
Ground Green
DALI Violet/White
DALI Violet
Wiring Diagrams
0-10V
Fixture
Black
White
Neutral
Ground
(0-10V)+
(0-10V)–
Line
Black
White
Green
Violet
Grey
Previously
hung unit
Newunit
3
Toadd a continuous unit to a c
4
ontinuous
Remove the PSU coverfromthe
5
5
previously hung luminaire if present. run, first suspend the new unit as it is done
in steps9 and 10 for the independent unit.
Position the non-power-supply end of the
luminaire near the power-supply end of
the previously hung luminaire.
Pull out continuous wiring
Pull the continuous wiring out of the luminaire being mounted and slide the bridge of the luminaire down onto the bridge of the
6
Aligntabs
with slots
Pushdown
to engage
already installed luminaire so that the tabs and slots at top and bottom nest into one another. The bridges will engage with a
loud click whenfully mated.
Connect the power and control
7
connectors of the through wiring
harness.
Replace the PSU cover(s) and secure
10
using the mounting screws.
Note: When installation is complete,
all lead wires and connectors shall be
totally enclosed.
At the beginning of the row, push the
8
wiring inside the cavity of the bridge.
6
Clip one end-cap at the beginning
9
of the row and one at the end
(provided in the starter kits).
Installation of a Continuous Row with Optional BranchCircuit
CAUTION
THERE IS A REqUIRED DIRECTION FOR ASSEMBLING A CONTINUOUS ROW.
Ceiling
ACline
First fixture in
the row
Direction of continuous row installation
For mechanical installation, follow steps 1-6 described earlier in these installinstructions.
Dimming line
(optional)
Next fixture in
the row
AC from 1st circuit
Carefully remove appropriate knockout for AC line input
1
wires (inner knockout for ½” conduit, outer knockout
for ¾” conduit). Install listed electrical fittings in the
knockout holes for wire protection and pass supply
conduit through electrical fittings.
Starter harness
1st circuit connection: Connect the green (ground),
2
black (line) and white (neutral) wires of the AC line to
the similarly colored wires of the starter harnessusing
the provided push-in wire nuts (starter unit) or connect
using wire nuts if using a starter kit (see above).
7
Dimming line
(optional)
First circuitwires
Dimming
connections
Second circuitwires
Brown, Brown/white stripewires
Optional dimmer: Install UL listed electrical fitting and
3
insert dimming control wires through. Connect dimming
control wires (grey and violet for 0-10V or violet and
violet/white stripe for DALI) to the similarly colored
fixture wires using the provided push-in wire nuts
(starter unit) or using wire nuts (starter kit).
2nd circuit connection: Install listed electrical fittings in
4
the second knockout holes for wire protection and pass
supply conduit through electrical fittings. The second
circuit wires (line and neutral) will be connected to the
second luminaire in the continuous run. Leave them
unconnected to the brown and brown/white stripe wires
fornow.
Purple, grey
Brown, brown-white
Pull out
continuous
wiring
Pull the continuous wiring out of the next luminaire being mounted and slide the bridge of the luminaire down onto the bridge of
5
Green, black,white
Align tabs
with slots
Pushdown
to engage
the already installed luminaire so that the tabs and slots at top and bottom nest into one another. The bridges will engage with a
load click when fully mated.
Brown
Connect the power and control connectors of the
6
Brown/white stripe
through wiring harness. Connect AC Circuit #1 (black,
white and green harness) from first fixtureto AC Circuit
#1 from second fixture.Connect AC Circuit # 2 (brown
and brown/white stripe harness) from first fixture to
AC Circuit #2 from second fixtureand connect second
circuit supply lines of starter unit.
Wiring Diagrams
Circuit
#1
Circuit
#2
DALI
Fixture
Neutral
Neutral
Ground
Line
Line
DALI
DALI
Black
White
Brown
Brown/white
Green
Violet/White
Violet
Circuit
#1
Circuit
#2
0-10V
Fixture
Neutral
Neutral
Ground
Line
Line
0-10V
0-10V
Black
White
Brown
Brown/white
Green
Violet
Grey(18 AWG)
8
Connecting a Unit to AC Circuit #1 or AC Circuit #2
AC Circuit #2
Black and
white wires
PSU
Locate the black (line) and white (neutral) wires on the
7
PSU. Pull the wires out of the box to have good access.
AC Circuit #1
AC Circuit #1 ConnectionsAC Circuit #2 Connections
AC Circuit #1
Dimming
AC Circuit #2
Connect the black (line) and the white (neutral) wires
8A8B
of the PSU to the AC lines similarly colored wires using
the push-inwire nuts.
To terminate a mechanical run take the end cap from
9
the starter luminaire or starter kit and clip down onto the
last bridge.
10
Connect the black (line) of the PSU with the brown (line)
AC wire using the push-in wire nut. Connect the white
(neutral) wire of the PSU with the brown/white (neutral)
AC wire using the push-in wire nut.
Replace the PSU cover(s) and secure using the mounting
screws.
Note: When installation is complete, all wiring and
connectors shall be totally enclosed.
9
PSU Replacement Procedure
Tools and Parts Required:
• New power supply unit (PSU)
• Wire cutter
• T15 Torx or Phillips #2screwdriver
• UL approvedwire connectors (4-pin)
Disconnect the luminaire power source.
1
Mounting bracket not shown for clarity
Loosen 3 screws and remove the PSU cove r.
2
Do not cut greenAC wires
AC
Locate the DC (red and blue), AC (green, white and
3
black) and Dimming connections (purple and gray).
Remove oldPSU
Other wires hiddenfor clarity
Dimming
DC
Cut the original DC, AC (do not cut the green wire)
4
and Dimmingconnections.
Install new PSU
Other wires hiddenfor clarity
Install the new PSU using a star washer under
6
each screw.
10
Unscrew the old PSU and remove.
5
AC
Reconnect the DC, AC, and Dimming wires using
7
UL approved connectors. Reattach the PSU cover.
Dimming
DC
Light Engine Replacement Procedure
For optical codes A, B, E, F, G, J, K, M, N, P, R, S
Disconnect the luminaire power source.
1
1
22
Ceiling
1. Move suspension point to avoid
cantilever effect.
2. Remove 2 screws onPSU cover.
Disconnect wires to adjacent
fixtures.
3. Unsnapboth ends.
Remove fixture from ceiling.
2
Unscrew and remove the PSU cover.Locate AC, DC and dimming wires coming from
34
3
Fixture toreplace
Heatsink
DC wires
(blue/red)
Dimming wires
(grey/purple)
AC wires
(black/white/green)
heatsink and cut or disconnect them (other wires
not shown for clarity).
Remove ground screw and wire.
5
Groundwire
11
Pull out the thru wiring from the opposite en d.
6
Save wiring forlater.
Upper
bridge
Lower
bridge
Light engine
Remove 4 screws to detach upper bridge from
7
lower bridge and replaceable light engine.
(blue/red wires)
Top hole
Blue/red wiring
New light
engine
Pull thru wiring (saved from Step 6) through the
8
Wires exitbottom
hole of bridge
new light engine and lower bridge.
Bottomhole
(thruwiring)
At PSU side, insert light engine into bottom bridge.
9
Blue/red wiring passes through the top hole. Thru
wiring passes through the bottom hole.
Upper
bridge
Lower
bridge
Light engine
Reassemble the upper and lower bridge to the
11
fixture with 4 screws.
Reattach the ground wire and screw.
10
DCwires
(blue/red)
Reconnect DC wires according to color (other wires
12
not shown for clarity).
12
AC wires
(black/white/green)
Dimming wires
(grey/purple)
Reconnect thru wires according
13
to color (other wires not shown
for clarity).
Push wires into tray and
14
reattach cover.
How To Replace Light Engine in the Field
For LumenCode [42][52][84][A0] Only
Make sure no wires are pinched.
15
NOTE: Make sure all wires and
connectors and are properly
enclosed.
With a flathead screwdriver,
1
open accessdoor.
Remove heatsink. Reverse steps
4
to install the new light engine.
Disconnect DC power.
2
13
With a flathead screwdriver,
3
unsnap clip near the end.
Continueunsnapping
remaining clips.
How To Replace Light Engine in the Field
For LumenCode [65][85][A3][A7][A1][A2][B1][B4] Only
TURN OFF POWER. Remove PSU
1
cover.
With a flathead screwdriver,
4
unsnap clip near the end. Continue
unsnapping remaining clips.
Cut blue and red wires from
2
light engine (other wires hidden
for clarity).
Remove removeable light engine.
5
With a flathead screwdriver, open
3
access door.
New light
engine
Take the red and blue wires of the
6
new light engine and fish them
through opening.
Clip removeable light engine into
place.
Close the access door.Reconnect blue and red wires
897
from the new light engine (other
wires hidden for clarity). Reinstall
PSU cover.
14
Loading...
+ 31 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.