CyberSentry, HardFiber, Multilin, and GE Multilin are trademarks or registered trademarks
of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-0088-AE1 (January 2017)
C30 Controller System
Table of contents
1 INTRODUCTION1.1Safety symbols and definitions..................................................................... 1-1
1.1.1General cautions and warnings .................................................................................... 1-1
1.2For further assistance .................................................................................... 1-2
B.1RADIUS server configuration .........................................................................B-1
CONFIGURATION
C COMMAND LINE
C.1Command line interface .................................................................................C-1
INTERFACE
C30 CONTROLLER SYSTEM – INSTRUCTION MANUALvii
TABLE OF CONTENTS
D MISCELLANEOUSD.1 Warranty .......................................................................................................... D-1
D.2 Revision history ............................................................................................... D-1
ABBREVIATIONS
INDEX
viiiC30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
C30 Controller System
Chapter 1: Introduction
Introduction
This chapter outlines safety and technical support information.
1.1 Safety symbols and definitions
Before attempting to install or use the device, review all safety indicators in this document to help prevent injury,
equipment damage, or downtime.
The following safety and equipment symbols are used in this document.
Indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.
Indicates practices not related to personal injury.
1.1.1 General cautions and warnings
The following general safety precautions and warnings apply.
Ensure that all connections to the product are correct so as to avoid accidental risk of shock
and/or fire, for example such as can arise from high voltage connected to low voltage terminals.
Follow the requirements of this manual, including adequate wiring size and type, terminal torque settings, voltage,
current magnitudes applied, and adequate isolation/clearance in external wiring from high to low voltage circuits.
Use the device only for its intended purpose and application.
Ensure that all ground paths are uncompromised for safety purposes during device operation and service.
Ensure that the control power applied to the device, the AC current, and voltage input match the ratings specified on
the relay nameplate. Do not apply current or voltage in excess of the specified limits.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL1-1
1
FOR FURTHER ASSISTANCECHAPTER 1: INTRODUCTION
Only qualified personnel are to operate the device. Such personnel must be thoroughly familiar with all safety
cautions and warnings in this manual and with applicable country, regional, utility, and plant safety regulations.
Hazardous voltages can exist in the power supply and at the device connection to current transformers, voltage
transformers, control, and test circuit terminals. Make sure all sources of such voltages are isolated prior to
attempting work on the device.
Hazardous voltages can exist when opening the secondary circuits of live current transformers. Make sure that
current transformer secondary circuits are shorted out before making or removing any connection to the current
transformer (CT) input terminals of the device.
For tests with secondary test equipment, ensure that no other sources of voltages or currents are connected to such
equipment and that trip and close commands to the circuit breakers or other switching apparatus are isolated,
unless this is required by the test procedure and is specified by appropriate utility/plant procedure.
When the device is used to control primary equipment, such as circuit breakers, isolators, and other switching
apparatus, all control circuits from the device to the primary equipment must be isolated while personnel are working
on or around this primary equipment to prevent any inadvertent command from this device.
Use an external disconnect to isolate the mains voltage supply.
Personal safety can be affected if the product is physically modified by the end user. Modifications to the product
outside of recommended wiring configuration, hardware, or programming boundaries is not recommended end-use
practice. Product disassembly and repairs are not permitted. All service needs to be conducted by the factory.
LED transmitters are classified as IEC 60825-1 Accessible Emission Limit (AEL) Class 1M. Class 1M
devices are considered safe to the unaided eye. Do not view directly with optical instruments.
This product is rated to Class A emissions levels and is to be used in Utility, Substation Industrial
environments. Not to be used near electronic devices rated for Class B levels.
1.2 For further assistance
For product support, contact the information and call center as follows:
GE Grid Solutions
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Worldwide telephone: +1 905 927 7070
Europe/Middle East/Africa telephone: +34 94 485 88 54
North America toll-free: 1 800 547 8629
Fax: +1 905 927 5098
Worldwide e-mail: multilin.tech@ge.com
Europe e-mail: multilin.tech.euro@ge.com
Website: http://www.gegridsolutions.com/multilin
When contacting GE by e-mail, optionally include a device information file, which is generated in the EnerVista software by
clicking the Service Report button.
1-2C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 1: INTRODUCTIONFOR FURTHER ASSISTANCE
Figure 1-1: Generate service report
1
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL1-3
1
FOR FURTHER ASSISTANCECHAPTER 1: INTRODUCTION
1-4C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
C30 Controller System
Chapter 2: Product description
Product description
This chapter outlines the product, order codes, and specifications.
2.1 Product description
The C30 Controller System is part of the Universal Relay (UR) series of products. It is a microprocessor-based device
designed for power substation control and monitoring.
Diagnostic features include a sequence of records capable of storing 1024 time-tagged events. The internal clock used for
time-tagging can be synchronized with an IRIG-B signal, using the Simple Network Time Protocol (SNTP) over the Ethernet
port, or using the Precision Time Protocol (PTP). This precise time stamping allows the sequence of events to be determined
throughout the system. Events can also be programmed (via FlexLogic
that can be set to record the measured parameters before and after the event for viewing on a computer. These tools
significantly reduce troubleshooting time and simplify report generation in the event of a system fault.
Several options are available for communication. A faceplate RS232 port can be used to connect to a computer for the
programming of settings and the monitoring of actual values. The rear RS485 port allows independent access by operating
and engineering staff. It can be connected to system computers with baud rates up to 115.2 kbps. All serial ports use the
Modbus RTU protocol. The IEC 60870-5-103 protocol is supported on the RS485 interface. IEC 60870-5-103, DNP, and
Modbus cannot be enabled simultaneously on this interface. Also only one of the DNP, IEC 60870-5-103, and IEC 60870-5104 protocols can be enabled at any time on the relay. When the IEC 60870-5-103 protocol is chosen, the RS485 port has a
fixed even parity and the baud rate can be either 9.6 kbps or 19.2 kbps. The 100Base-FX or 100Base-TX Ethernet interface
provides fast, reliable communications in noisy environments. The Ethernet port supports IEC 61850, Modbus/TCP, TFTP,
and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access to the relay via any standard web browser
(C30 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet port. The Ethernet port also supports the
Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when purchased as an option.
Secure Routable GOOSE (R-GOOSE) is supported with software options.
Settings and actual values can be accessed from the front panel or EnerVista software.
The C30 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
™
equations) to trigger oscillography data capture
Table 2-1: Device functions
FunctionFunction
Breaker ControlIEC 61850 Communications
Contact Inputs (up to 96)IEC 62351-9 Data and Communications Security
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL2-1
2
SECURITYCHAPTER 2: PRODUCT DESCRIPTION
FunctionFunction
Contact Outputs (up to 64)Modbus Communications
Control PushbuttonsModbus User Map
CyberSentry
Data LoggerNon-Volatile Selector Switch
Digital Counters (8)Oscillography
Digital Elements (48)Time Synchronization over IRIG-B or IEEE 1588
Direct Inputs/Outputs (64)Time Synchronization over SNTP
Disconnect SwitchesUser Definable Displays
DNP 3.0 or IEC 60870-5-104 CommunicationsUser Programmable LEDs
Ethernet Global Data ProtocolUser Programmable Pushbuttons
Event RecorderUser Programmable Self-Tests
FlexElements
FlexLogic EquationsVirtual Outputs (96)
IEC 60870-5-103 Communications
™
SecurityNon-Volatile Latches
™
(8)Virtual Inputs (64)
2.2 Security
The following security features are available:
•Password security — Basic security present by default
•EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The
feature is present by default in the EnerVista software.
•CyberSentry security — Advanced security available using a software option. When purchased, the option is
automatically enabled, and the default Password security and EnerVista security are disabled.
2.2.0.1 EnerVista security
The EnerVista security management system is a role-based access control (RBAC) system that allows an administrator to
manage the privileges of multiple users. This allows for access control of UR devices by multiple personnel within a
substation and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security
management system is disabled by default to allow the administrator direct access to the EnerVista software after
installation. It is recommended that security be enabled before placing the device in service.
Basic password or enhanced CyberSentry security applies, depending on purchase.
2.2.0.2 Password security
Password security is a basic security feature present by default.
Two levels of password security are provided: command and setting. Use of a password for each level controls whether
users can enter commands and/or change settings.
The C30 supports password entry from a local or remote connection. Local access is defined as any access to settings or
commands via the faceplate interface. This includes both keypad entry and the through the faceplate RS232 port. Remote
access is defined as any access to settings or commands via any rear communications port. This includes both Ethernet
and RS485 connections. Any changes to the local or remote passwords enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the C30, the remote password must be used. If the
connection is to the RS232 port of the faceplate, the local password applies.
Password access events are logged in the Event Recorder.
2-2C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTIONSECURITY
2.2.0.3 CyberSentry security
CyberSentry embedded security is available using a software option (Level 1) that provide advanced security services.
When the option is purchased, the basic password security is disabled automatically.
CyberSentry provides security through the following features:
•An Authentication, Authorization, Accounting (AAA) Remote Authentication Dial-In User Service (RADIUS) client that is
centrally managed, enables user attribution, provides accounting of all user activities, and uses secure standardsbased strong cryptography for authentication and credential protection
•A Role-Based Access Control (RBAC) system that provides a permission model that allows access to UR device
operations and configurations based on specific roles and individual user accounts configured on the AAA server (that
is, Administrator, Supervisor, Engineer, Operator, Observer roles)
•Security event reporting through the Syslog protocol for supporting Security Information Event Management (SIEM)
systems for centralized cybersecurity monitoring
•Strong encryption of all access and configuration network messages between the EnerVista software and UR devices
using the Secure Shell (SSH) protocol, the Advanced Encryption Standard (AES), and 128-bit keys in Galois Counter
Mode (GCM) as specified in the U.S. National Security Agency Suite B extension for SSH and approved by the National
Institute of Standards and Technology (NIST) FIPS-140-2 standards for cryptographic systems
CyberSentry user roles
CyberSentry user roles (Administrator, Engineer, Operator, Supervisor, Observer) limit the levels of access to various UR
device functions. This means that the EnerVista software allows for access to functionality based on the user’s logged in
role.
Example: Administrative functions can be segmented away from common operator functions, or engineering type access,
all of which are defined by separate roles (see figure) so that access of UR devices by multiple personnel within a
substation is allowed.
2
Figure 2-1: CyberSentry user roles
The table lists user roles and their corresponding capabilities.
Table 2-2: Permissions by user role for CyberSentry
|--------------- Display PropertiesRWRWRRR
|--------------- Clear Relay Records
(settings)
|--------------- CommunicationsRWRWRRR
|--------------- Modbus User MapRWRWRRR
|--------------- Real Time ClockRWRWRRR
|--------------- OscillographyRWRWRRR
|--------------- Data LoggerRWRWRRR
|--------------- DemandRWRWRRR
|--------------- User-Programmable
LEDs
|--------------- User-Programmable
Self Tests
|--------------- Control Pushbuttons RWRWRRR
|--------------- User-Programmable
Pushbuttons
|--------------- Flex state
Parameters
|--------------- User-Definable
Displays
|--------------- Direct I/ORWRWRRR
|--------------- TeleprotectionRWRWRRR
|--------------- InstallationRWRWRRR
|---------- System SetupRWRWRRR
|---------- FlexLogicRWRWRRR
|---------- Grouped ElementsRWRWRRR
|---------- Control ElementsRWRWRRR
|---------- Inputs / OutputsRWRWRRR
|---------- Set Date and TimeRWRWRWRR
User DisplaysRRRRR
TargetsRRRRR
Actual ValuesRRRRR
|---------- Front panel labels designerRRRRR
|---------- StatusRRRRR
|---------- MeteringRRRRR
|---------- Transducer I/ORRRRR
|---------- RecordsRRRRR
|---------- Product InfoRRRRR
MaintenanceRWRWRRR
|---------- Modbus AnalyzerNANANANANA
|---------- Change front panelRWRWRWRR
|---------- Update firmwareYesNoNoNoNo
|---------- Retrieve fileYesNoNoNoNo
Table Notes:
RW = read and write access
R = read access
Supervisor = RW (default), Administrator = R (default), Administrator = RW (only if Supervisor role is disabled)
NA = the permission is not enforced by CyberSentry security
2
CyberSentry user authentication
The following types of authentication are supported by CyberSentry to access the UR device:
•Device Authentication (local UR device authenticates)
•Server Authentication (RADIUS server authenticates)
The EnerVista software allows access to functionality that is determined by the user role, which comes either from the local
UR device or the RADIUS server.
The EnerVista software has a device authentication option on the login screen for accessing the UR device. When the
"Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authenticate the
user. In this case, it uses its built-in roles (Administrator, Engineer, Supervisor, Observer, Operator, or Administrator and
Supervisor when Device Authentication is disabled) as login names and the associated passwords are stored on the UR
device. As such, when using the local accounts, access is not user-attributable.
In cases where user-attributable access is required especially to facilitate auditable processes for compliance reasons, use
RADIUS authentication only.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
No password or security information is displayed in plain text by the EnerVista software or UR device, nor is such
information ever transmitted without cryptographic protection.
CyberSentry server authentication
The UR has been designed to direct automatically the authentication requests based on user names. In this respect, local
account names on the UR are considered as reserved and not used on a RADIUS server.
The UR detects automatically whether an authentication request is to be handled remotely or locally. As there are five local
accounts possible on the UR, if the user ID credential does not match one of the five local accounts, the UR forwards
automatically the request to a RADIUS server when one is provided.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL2-5
2
ORDER CODESCHAPTER 2: PRODUCT DESCRIPTION
If a RADIUS server is provided, but is unreachable over the network, server authentication requests are denied. In this
situation, use local UR accounts to gain access to the UR system.
2.3 Order codes
The order code is on the product label and indicates the product options applicable.
The C30 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit. It consists of the following
modules: power supply, CPU, CT/VT, contact input and output, transducer input and output, and inter-relay
communications. Module options are specified at the time of ordering.
The order codes shown here are subject to change without notice. See the web page for the product for the latest options.
The order code depends on the mounting option (horizontal or vertical) and the type of CT/VT modules (enhanced
diagnostic CT/VT modules or HardFiber
HardFiber Bricks.
The R-GOOSE protocol described in IEC 61850-8-1 is available through the IEC 61850 software option. If R-GOOSE
security is required, the CyberSentry software option also must be purchased.
2.3.1 Order codes with enhanced CT/VT modules
TM
process bus module). The process bus module provides an interface to
Table 2-3: C30 order codes for horizontal units
BASE UNITC30| || | |||||||Base Unit
CPUT || | |||||||RS485 with 3 100Base-FX Ethernet , multimode, SFP with LC
SOFTWARE00| | |||||||No software options
C30 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount
U || | |||||||RS485 with 1 100Base-TX Ethernet , SFP RJ-45 + 2 100Base-FX Ethernet,
V || | |||||||RS485 with 3 100Base-TX Ethernet, SFP with RJ-45
01| | |||||||Ethernet Global Data (EGD)
03| | |||||||IEC 61850
04| | |||||||Ethernet Global Data (EGD) and IEC 61850
A0| | |||||||CyberSentry Lvl 1
A1| | |||||||CyberSentry Lvl 1 and Ethernet Global Data
A3| | |||||||CyberSentry Lvl 1 and IEC 61850
A4| | |||||||CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
AW | | |||||||CyberSentry Lvl 1, PID controller, and IEC 61850
B0| | |||||||IEEE 1588
B1| | |||||||IEEE 1588 and Ethernet Global Data
B3| | |||||||IEEE 1588 and IEC 61850
B4| | |||||||IEEE 1588, Ethernet Global Data, and IEC 61850
BW | | |||||||IEEE 1588, PID controller, and IEC 61850
C0| | |||||||Parallel Redundancy Protocol (PRP)
C1| | |||||||PRP and Ethernet Global Data
C3| | |||||||PRP and IEC 61850
C4| | |||||||PRP, Ethernet Global Data, and IEC 61850
CW | | |||||||PRP, PID controller, and IEC 61850
D0| | |||||||IEEE 1588 and CyberSentry Lvl 1
D1| | |||||||IEEE 1588, CyberSentry Lvl 1, and Ethernet Global Data
D3| | |||||||IEEE 1588, CyberSentry Lvl 1, and IEC 61850
D4| | |||||||IEEE 1588, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
DW | | |||||||IEEE 1588, CyberSentry Lvl 1, PID controller, and IEC 61850
E0| | |||||||IEEE 1588 and PRP
E1| | |||||||IEEE 1588, PRP, and Ethernet Global Dada
E3| | |||||||IEEE 1588, PRP, and IEC 61850
E4| | |||||||IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
EW | | |||||||IEEE 1588, PRP, PID controller, and IEC 61850
F0| | |||||||PRP and CyberSentry Lvl1
F1| | |||||||PRP, CyberSentry Lvl1, and Ethernet Global Data
F3| | |||||||PRP, CyberSentry Lvl 1, and IEC 61850
F4| | |||||||PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
FW | | |||||||PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
G0| | |||||||IEEE 1588, PRP, and CyberSentry Lvl 1
G1| | |||||||IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data
G3| | |||||||IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4| | |||||||IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
GW | | |||||||IEEE 1588, PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
J0| | |||||||IEC 60870-5-103
J1| | |||||||IEC 60870-5-103 + EGD
J3| | |||||||IEC 60870-5-103 + IEC 61850
J4| | |||||||IEC 60870-5-103 + EGD + IEC 61850
JW | | |||||||IEC 60870-5-103 + PID controller + IEC 61850
K0| | |||||||IEEE1588 + PRP + IEC 60870-5-103
K1| | |||||||IEEE1588 + PRP + IEC 60870-5-103 + EGD
K3| | |||||||IEEE1588 + PRP + IEC 60870-5-103 + IEC 61850
K4| | |||||||IEEE1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
KW | | |||||||IEEE1588 + PRP + IEC 60870-5-103 + PID controller + IEC 61850
L0| | |||||||IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1| | |||||||IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3| | |||||||IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
multimode, SFP with LC
2-6C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTIONORDER CODES
C30 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount
MOUNT/COATINGH | |||||||Horizontal (19” rack)
FACEPLATE/ DISPLAYC |||||||English display
POWER SUPPLY
(redundant supply must
be same type as main supply)
CONTACT
INPUTS/OUTPUTS
TRANSDUCER
INPUTS/OUTPUTS
(select a maximum of 3 per unit)
INTER-RELAY
COMMUNICATIONS
(select a maximum of 1 per unit)
A | |||||||Horizontal (19” rack) with harsh-environmental coating
D |||||||French display
R |||||||Russian display
A |||||||Chinese display
P |||||||English display with 4 small and 12 large programmable pushbuttons
G |||||||French display with 4 small and 12 large programmable pushbuttons
S |||||||Russian display with 4 small and 12 large programmable pushbuttons
B |||||||Chinese display with 4 small and 12 large programmable pushbuttons
K |||||||Enhanced front panel with English display
M |||||||Enhanced front panel with French display
Q |||||||Enhanced front panel with Russian display
U |||||||Enhanced front panel with Chinese display
L |||||||Enhanced front panel with English display and user-programmable pushbuttons
N |||||||Enhanced front panel with French display and user-programmable pushbuttons
T |||||||Enhanced front panel with Russian display and user-programmable pushbuttons
V |||||||Enhanced front panel with Chinese display and user-programmable pushbuttons
W |||||||Enhanced front panel with Turkish display
Y |||||||Enhanced front panel with Turkish display and user-programmable pushbuttons
I |||||||Enhanced front panel with German display
J |||||||Enhanced front panel with German display and user-programmable pushbuttons
H||||||125 / 250 V AC/DC power supply
H|||||SH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
L||||||24 to 48 V (DC only) power supply
L|||||SL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
XXXXXXXXXXXX No Module
4A4A4A4A4A4A 4 Solid-State (no monitoring) MOSFET outputs
4B4B4B4B4B4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C4C4C4C4C4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D4D4D4D4D4D 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
4L4L4L4L4L4L 14 Form-A (no monitoring) Latching outputs
676767676767 8 Form-A (no monitoring) outputs
6A6A6A6A6A6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B6B6B6B6B6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C6C6C6C6C6C 8 Form-C outputs
6D6D6D6D6D6D 16 Contact inputs
6E6E6E6E6E6E 4 Form-C outputs, 8 contact inputs
6F6F6F6F6F6F 8 Fast Form-C outputs
6G6G6G6G6G6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H6H6H6H6H6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K6K6K6K6K6K 4 Form-C and 4 Fast Form-C outputs
6L6L6L6L6L6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M6M6M6M6M6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N6N6N6N6N6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P6P6P6P6P6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R6R6R6R6R6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S6S6S6S6S6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T6T6T6T6T6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U6U6U6U6U6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V6V6V6V6V6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8
Table 2-4: C30 order codes for reduced-size vertical units
BASE UNITC30| || | |||||Base Unit
CPUT || | |||||RS485 with 3 100Base-FX Ethernet , multimode, SFP with LC
SOFTWARE00| | |||||No software options
MOUNT/COATINGV | |||||Vertical (3/4 rack)
FACEPLATE/ DISPLAYF |||||English display
C30 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see not e regarding P/R slot below)
U || | |||||RS485 with 1 100Base-TX Ethernet , SFP RJ-45 + 2 100Base-FX Ethernet, multimode, SFP with LC
V || | |||||RS485 with 3 100Base-TX Ethernet, SFP with RJ-45
01| | |||||Ethernet Global Data (EGD)
03| | |||||IEC 61850
04| | |||||Ethernet Global Data (EGD) and IEC 61850
A0| | |||||CyberSentry Lvl 1
A1| | |||||CyberSentry Lvl 1 and Ethernet Global Data
A3| | |||||CyberSentry Lvl 1 and IEC 61850
A4| | |||||CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
AW | | |||||CyberSentry Lvl 1, PID controller, and IEC 61850
B0| | |||||IEEE 1588
B1| | |||||IEEE 1588 and Ethernet Global Data
B3| | |||||IEEE 1588 and IEC 61850
B4| | |||||IEEE 1588, Ethernet Global Data, and IEC 61850
BW | | |||||IEEE 1588, PID controller, and IEC 61850
C0| | |||||Parallel Redundancy Protocol (PRP)
C1| | |||||PRP and Ethernet Global Data
C3| | |||||PRP and IEC 61850
C4| | |||||PRP, Ethernet Global Data, and IEC 61850
CW | | |||||PRP, PID controller, and IEC 61850
D0| | |||||IEEE 1588 and CyberSentry Lvl 1
D1| | |||||IEEE 1588, CyberSentry Lvl 1, and Ethernet Global Data
D3| | |||||IEEE 1588, CyberSentry Lvl 1, and IEC 61850
D4| | |||||IEEE 1588, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
DW | | |||||IEEE 1588, CyberSentry Lvl 1, PID controller, and IEC 61850
E0| | |||||IEEE 1588 and PRP
E1| | |||||IEEE 1588, PRP, and Ethernet Global Dada
E3| | |||||IEEE 1588, PRP, and IEC 61850
E4| | |||||IEEE 1588, PRP, Ethernet Global Data, and IEC 61850
EW | | |||||IEEE 1588, PRP, PID controller, and IEC 61850
F0| | |||||PRP and CyberSentry Lvl1
F1| | |||||PRP, CyberSentry Lvl1, and Ethernet Global Data
F3| | |||||PRP, CyberSentry Lvl 1, and IEC 61850
F4| | |||||PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
FW | | |||||PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
G0| | |||||IEEE 1588, PRP, and CyberSentry Lvl 1
G1| | |||||IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data
G3| | |||||IEEE 1588, PRP, CyberSentry Lvl 1, and IEC 61850
G4| | |||||IEEE 1588, PRP, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
GW | | |||||IEEE 1588, PRP, CyberSentry Lvl 1, PID controller, and IEC 61850
J0| | |||||IEC 60870-5-103
J1| | |||||IEC 60870-5-103 + EGD
J3| | |||||IEC 60870-5-103 + IEC 61850
J4| | |||||IEC 60870-5-103 + EGD + IEC 61850
JW | | |||||IEC 60870-5-103 + PID controller + IEC 61850
K0| | |||||IEEE1588 + PRP + IEC 60870-5-103
K1| | |||||IEEE1588 + PRP + IEC 60870-5-103 + EGD
K3| | |||||IEEE1588 + PRP + IEC 60870-5-103 + IEC 61850
K4| | |||||IEEE1588 + PRP + IEC 60870-5-103 + EGD + IEC 61850
KW | | |||||IEEE1588 + PRP + IEC 60870-5-103 + PID controller + IEC 61850
L0| | |||||IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1
L1| | |||||IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD
L3| | |||||IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + IEC 61850
L4| | |||||IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + EGD + IEC 61850
LW | | |||||IEC 60870-5-103 + IEEE1588 + PRP + CyberSentry Lvl 1 + PID controller + IEC 61850
P0| | |||||CyberSentry Lvl 2
P1| | |||||CyberSentry Lvl 2 + Ethernet Global Da ta
P3| | |||||CyberSentry Lvl 2 + IEC 61850
P4| | |||||CyberSentry Lvl 2 + Ethernet Global Data + IEC 61850
PW | | |||||CyberSentry Lvl 2 + PID controller + IEC 61850
Q0 | | |||||IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 2
Q1 | | |||||IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 2 + Ethernet Global Data
Q3 | | |||||IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 2 + IEC 61850
Q4 | | |||||IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 2 + Ethernet Global Data + IEC 61850
QW | | |||||IEC 60870-5-103 + IEEE 1588 + PRP + CyberSentry Lvl 2 + PID controller + IEC 61850
B | |||||Vertical (3/4 rack) with harsh-environmental coating
K |||||Enhanced front panel with English display
M |||||Enhanced front panel with French display
Q |||||Enhanced front panel with Russian display
U |||||Enhanced front panel with Chinese display
L |||||Enhanced front panel with English display a nd user-programmable pushbuttons
N |||||Enhanced front panel with French display and user-programmable pushbuttons
T |||||Enhanced front panel with Russian display and user-programmable pushbuttons
V |||||Enhanced front panel with Chinese display and user-programmable pushbuttons
W |||||Enhanced front panel with Turkish display
Y |||||Enhanced front panel with Turkish display and user-programmable pushbuttons
I |||||Enhanced front panel with German display
J |||||Enhanced front panel with German display and user-programmable pushbuttons
2-8C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTIONORDER CODES
POWER SUPPLYH||||125 / 250 V AC/DC power supply
CONTACT
INPUTS/OUTPUTS
TRANSDUCER
INPUTS/OUTPUTS
(select a maximum of 3 per unit)
INTER-RELAY
COMMUNICATIONS
(select a maximum of 1 per unit)
For the last module, slot P is used for digital and
transducer
input/output modules; slot R is used for inter-relay
communications modules.
C30 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see not e regarding P/R slot below)
L||||24 to 48 V (DC only) power supply
XXXXXXXX No Module
4A4A4A4A 4 Solid-State (no monitoring) MOSFET outputs
4B4B4B4B 4 Solid-State (voltage with optional current) MOSFET outputs
4C4C4C4C 4 Solid-State (current with optional voltage) MOSFET outputs
4D4D4D4D 16 Contact inputs with Auto-Burnishing (maximum of three modules within a case)
4L4L4L4L 14 Form-A (no monitoring) Latching outputs
67676767 8 Form-A (no monitoring) outputs
6A6A6A6A 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B6B6B6B 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C6C6C6C 8 Form-C outputs
6D6D6D6D 16 Contact inputs
6E6E6E6E 4 Form-C outputs, 8 contact inputs
6F6F6F6F 8 Fast Form-C outputs
6G6G6G6G 4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H6H6H6H 6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K6K6K6K 4 Form-C and 4 Fast Form-C outputs
6L6L6L6L 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M6M6M6M 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N6N6N6N 4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P6P6P6P 6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R6R6R6R 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S6S6S6S 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T6T6T6T 4 Form-A (no monitoring) outputs, 8 contact inputs
6U6U6U6U 6 Form-A (no monitoring) outputs, 4 contact inputs
6V6V6V6V 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 contact inputs
5A5A5A5A 4 DCmA inputs, 4 DCmA outputs (only one 5A module is allowed)
5C5C5C5C 8 RTD inputs
5D5D5D5D 4 RTD inputs, 4 DCmA outputs (only one 5D module is allowed)
5E5E5E5E 4 RTD inputs, 4 DCmA inputs
5F5F5F5F 8 DCmA inputs
A | |||||||Horizontal (19” rack) with harsh-environmental coating
D |||||||French display
R |||||||Russian display
A |||||||Chinese display
P |||||||English display with 4 small and 12 large programmable pushbuttons
G |||||||French display with 4 small and 12 large programmable pushbuttons
S |||||||Russian display with 4 small and 12 large programmable pushbuttons
B |||||||Chinese display with 4 small and 12 large programmable pushbuttons
K |||||||Enhanced front panel with English display
M |||||||Enhanced front panel with French display
Q |||||||Enhanced front panel with Russian display
U |||||||Enhanced front panel with Chinese display
L |||||||Enhanced front panel with English display and user-programmable pushbuttons
N |||||||Enhanced front panel with French display and user-programmable pushbuttons
T |||||||Enhanced front panel with Russian display and user-programmable pushbuttons
V |||||||Enhanced front panel with Chinese display and user-programmable pushbuttons
W |||||||Enhanced front panel with Turkish display
Y |||||||Enhanced front panel with Turkish display and user-programmable pushbuttons
I |||||||Enhanced front panel with German display
J |||||||Enhanced front panel with German display and user-programmable pushbu ttons
IEC 61850
61850
2-10C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTIONORDER CODES
POWER SUPPLY
(redundant supply must
be same type as main supply)
PROCESS BUS MODULEXX|XX|||None
CONTACT
INPUTS/OUTPUTS
INTER-RELAY
COMMUNICATIONS
(select a maximum of 1 per unit)
C30 - * ** - * * * - F ** - H ** - M ** - P ** - U ** - W/X ** Full Size Horizontal Mount
H||||||125 / 250 V AC/DC power supply
H|||||SH 125 / 250 V AC/DC with redundant 125 / 250 V AC/DC power supply
L||||||24 to 48 V (DC only) power supply
L|||||SL 24 to 48 V (DC only) with redundant 24 to 48 V DC power supply
|81||||Eight-port digital process bus module
XXXXXX None
4A4A|4 Solid-State (no monitoring) MOSFET outputs
4B4B|4 Solid-State (voltage with optional current) MOSFET outputs
4C4C|4 Solid-State (current with optional voltage) MOSFET outputs
4D4D|16 Contact inputs with A uto-Burnishing (maximum of three modules within a case)
4L4L|14 Form-A (no monitoring) Latching outputs
6767|8 Form-A (no monitoring) outputs
6A6A|2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
6B6B|2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
6C6C|8 Form-C outputs
6D6D|16 Contact inputs
6E6E|4 Form-C outputs, 8 contact inputs
6F6F|8 Fast Form-C outputs
6G6G|4 Form-A (voltage with optional current) outputs, 8 contact inputs
6H6H|6 Form-A (voltage with optional current) outputs, 4 contact inputs
6K6K|4 Form-C and 4 Fast Form-C outputs
6L6L|2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
6M6M|2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
6N6N|4 Form-A (current with optional voltage) outputs, 8 contact inputs
6P6P|6 Form-A (current with optional voltage) outputs, 4 contact inputs
6R6R|2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
6S6S|2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
6T6T|4 Form-A (no monitoring) outputs, 8 contact inputs
6U6U|6 Form-A (no monitoring) outputs, 4 contact inputs
6V6V|2 Form-A outputs, 1 Form-C output , 2 Form-A (no monitoring) latching outputs, 8
Table 2-6: C30 order codes for reduced-size vertical units with process bus
BASE UNITC30| || | |||||Base Unit
CPUT || | |||||RS485 with 3 100Base-FX Ethernet , multimode, SFP with LC
SOFTWARE00| | |||||No software options
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL2-11
C30 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see not e regarding P/R slot below)
U || | |||||RS485 with 1 100Base-TX Ethernet , SFP RJ-45 + 2 100Base-FX Ethernet, multimode, SFP with LC
V || | |||||RS485 with 3 100Base-TX Ethernet, SFP with RJ-45
01| | |||||Ethernet Global Data (EGD)
03| | |||||IEC 61850
04| | |||||Ethernet Global Data (EGD) and IEC 61850
A0| | |||||CyberSentry Lvl 1
A1| | |||||CyberSentry Lvl 1 and Ethernet Global Data
A3| | |||||CyberSentry Lvl 1 and IEC 61850
A4| | |||||CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
AW | | |||||CyberSentry Lvl 1, PID controller, and IEC 61850
B0| | |||||IEEE 1588
B1| | |||||IEEE 1588 and Ethernet Global Data
B3| | |||||IEEE 1588 and IEC 61850
B4| | |||||IEEE 1588, Ethernet Global Data, and IEC 61850
BW | | |||||IEEE 1588, PID controller, and IEC 61850
C0| | |||||Parallel Redundancy Protocol (PRP)
C1| | |||||PRP and Ethernet Global Data
C3| | |||||PRP and IEC 61850
C4| | |||||PRP, Ethernet Global Data, and IEC 61850
CW | | |||||PRP, PID controller, and IEC 61850
D0| | |||||IEEE 1588 and CyberSentry Lvl 1
D1| | |||||IEEE 1588, CyberSentry Lvl 1, and Ethernet Global Data
D3| | |||||IEEE 1588, CyberSentry Lvl 1, and IEC 61850
D4| | |||||IEEE 1588, CyberSentry Lvl 1, Ethernet Global Data, and IEC 61850
ORDER CODESCHAPTER 2: PRODUCT DESCRIPTION
2
C30 - * ** - * * * - F ** - H ** - M ** - P/R ** Reduced Size Vertical Mount (see not e regarding P/R slot below)
MOUNT/COATINGV | |||||Vertical (3/4 rack)
FACEPLATE/ DISPLAYF |||||English display
POWER SUPPLYH||||125 / 250 V AC/DC power supply
PROCESS BUS MODULEXX|XX|None
CONTACT
INPUTS/OUTPUTS
INTER-RELAY
COMMUNICATIONS
(select a maximum of 1 per unit)
For the last module, slot P is used for digital and transducer
input/output modules; slot R is used for inter-relay
communications modules.
B | |||||Vertical (3/4 rack) with harsh environmental coating
K |||||Enhanced front panel with English display
M |||||Enhanced front panel with French display
Q |||||Enhanced front panel with Russian display
U |||||Enhanced front panel with Chinese display
L |||||Enhanced front panel with English display a nd user-programmable pushbuttons
N |||||Enhanced front panel with French display and user-programmable pushbuttons
T |||||Enhanced front panel with Russian display and user-programmable pushbuttons
V |||||Enhanced front panel with Chinese display and user-programmable pushbuttons
W |||||Enhanced front panel with Turkish display
Y |||||Enhanced front panel with Turkish display and user-programmable pushbuttons
I |||||Enhanced front panel with German display
J |||||Enhanced front panel with German display and user-programmable pushbuttons
Replacement modules can be ordered separately. When ordering a replacement CPU module or faceplate, provide the
serial number of your existing unit.
Not all replacement modules apply to the C30 relay. The modules specified in the order codes for the C30 are available as
replacement modules for the C30.
The order codes shown here are subject to change without notice. See the web page for the product for the latest options.
Table 2-7: UR order codes for replacement modules, horizontal units
POWER SUPPLY
redundant supply only available in horizontal
units and must be same type as main supply
CPU|T| RS485 with 3 100Base-FX Ethernet, multimode, SFP with LC
FACEP LATE/D ISPL AY|3C| Horizontal faceplate with keypad and English display
CONTACT INPUTS AND OUTPUTS|4A| 4 Solid-State (no monitoring) MOSFET outputs
CT/VT MODULES|8L| Standard 4CT/4VT with enhanced diagnostics
(not available for the C30)|8N| Standard 8CT with enhanced diagnostics
|SH A | 125 / 300 V AC/DC
|SL H | 24 to 48 V (DC only)
|U| RS485 with 1 100Base-TX Ethernet, SFP RJ-45 + 2 100Base-FX Ethernet , multimode, SFP with LC
|V| RS485 with 3 100Base-TX Ethernet, SFP with RJ-45
|3D| Horizontal faceplate with keypad and French display
|3R| Horizontal faceplate with keypad and Russian display
|3A| Horizontal faceplate with keypad and Chinese display
|3P| Horizontal faceplate with keypad, user-programmable pushbuttons, and English display
|3G| Horizontal faceplate with keypad, user-programmable pushbuttons, and French display
|3S| Horizontal faceplate with keypad, user-programmable pushbuttons, and Russian display
|3B| Horizontal faceplate with keypad, user-programmable pushbuttons, and Chinese display
|3K| Enhanced front panel with English display
|3M| Enhanced front panel with French display
|3Q| Enhanced front panel with Russian display
|3U| Enhanced front panel with Chinese display
|3L| Enhanced front panel with English display and user-programmable pushbuttons
|3N| Enhanced front panel with French display and user-programmable pushbuttons
|3T| Enhanced front panel with Russian display a nd user-programmable pushbuttons
|3V| Enhanced front panel with Chinese display and user-programmable pushbuttons
|3I| Enhanced front panel with German display
|3J| Enhanced front panel with German display and user-programmable pushbuttons
|4B| 4 Solid-State (voltage with optional current) MOSFET outputs
|4C| 4 Solid-State (current with optional voltage) MOSFET outputs
|4D| 16 Contact inputs with Auto-Burnishing
|4L| 14 Form-A (no monitoring) Latching outputs
|67| 8 Form-A (no monitoring) outputs
|6A| 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
|6B| 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
|6C|8 Form-C outputs
|6D| 16 Contact inputs
|6E| 4 Form-C outputs, 8 contact inputs
|6F|8 Fast Form-C outputs
|6G| 4 Form-A (voltage with optional current) outputs, 8 contact inputs
|6H| 6 Form-A (voltage with optional current) outputs, 4 contact inputs
|6K| 4 Form-C and 4 Fast Form-C outputs
|6L| 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
|6M| 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
|6N| 4 Form-A (current with optional voltage) outputs, 8 contact inputs
|6P| 6 Form-A (current with optional voltage) outputs, 4 contact inputs
|6R| 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
|6S| 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
|6T| 4 Form-A (no monitoring) outputs, 8 contact inputs
|6U| 6 Form-A (no monitoring) outputs, 4 contact inputs
|6V| 2 Form-A outputs, 1 Form-C output , 2 Form-A (no monitoring) latching outputs, 8 contact inputs
|8M| Sensitive Ground 4CT/4VT with enhanced diagnostics
|8R| Sensitive Ground 8CT with enhanced diagnostics
|8V| Standard 8VT with enhanced diagnostics (only one module supported)
|U| RS485 with 1 100Base-TX Ethernet, SFP RJ-45 + 2 100Base-FX Ethernet , multimode, SFP with LC
|V| RS485 with 3 100Base-TX Ethernet, SFP with RJ-45
|3D| Vertical faceplate with keypad and French display
|3R| Vertica l faceplate with keypad and Russian display
|3A| Vertical faceplate with keypad and Chinese d isplay
|3K| Enhanced front panel with English display
|3M| Enhanced front panel with French display
|3Q| Enhanced front panel with Russian display
|3U| Enhanced front panel with Chinese display
|3L| Enhanced front panel with English display and user-programmable pushbuttons
|3N| Enhanced front panel with French display and user-programmable pushbuttons
|3T| Enhanced front panel with Russian display a nd user-programmable pushbuttons
|3V| Enhanced front panel with Chinese display and user-programmable pushbuttons
|3I| Enhanced front panel with German display
|3J| Enhanced front panel with German display and user-programmable pushbuttons
|4B| 4 Solid-State (voltage with optional current) MOSFET outputs
|4C| 4 Solid-State (current with optional voltage) MOSFET outputs
|4D| 16 Contact inputs with Auto-Burnishing
|4L| 14 Form-A (no monitoring) Latching outputs
|67| 8 Form-A (no monitoring) outputs
|6A| 2 Form-A (voltage with optional current) and 2 Form-C outputs, 8 contact inputs
|6B| 2 Form-A (voltage with optional current) and 4 Form-C outputs, 4 contact inputs
|6C|8 Form-C outputs
|6D| 16 Contact inputs
|6E| 4 Form-C outputs, 8 contact inputs
|6F|8 Fast Form-C outputs
|6G| 4 Form-A (voltage with optional current) outputs, 8 contact inputs
|6H| 6 Form-A (voltage with optional current) outputs, 4 contact inputs
|6K| 4 Form-C and 4 Fast Form-C outputs
|6L| 2 Form-A (current with optional voltage) and 2 Form-C outputs, 8 contact inputs
|6M| 2 Form-A (current with optional voltage) and 4 Form-C outputs, 4 contact inputs
|6N| 4 Form-A (current with optional voltage) outputs, 8 contact inputs
|6P| 6 Form-A (current with optional voltage) outputs, 4 contact inputs
|6R| 2 Form-A (no monitoring) and 2 Form-C outputs, 8 contact inputs
|6S| 2 Form-A (no monitoring) and 4 Form-C outputs, 4 contact inputs
|6T| 4 Form-A (no monitoring) outputs, 8 contact inputs
|6U| 6 Form-A (no monitoring) outputs, 4 contact inputs
|6V| 2 Form-A outputs, 1 Form-C output , 2 Form-A (no monitoring) latching outputs, 8 contact inputs
|8L| Standard 4CT/4VT with enhanced diagnostics
|8N| Standard 8CT with enhanced diagnostics
|8M| Sensitive Ground 4CT/4VT with enhanced diagnostics
|8R| Sensitive Ground 8CT with enhanced diagnostics
|8V| Standard 8VT with enhanced diagnostics
The UR series relays are microprocessor-based protective relays that are designed to measure power system conditions
directly via CT and PT inputs and via other sources of information, such as analog inputs, communications inputs and
contact inputs. The following figure shows the overall signal processing in URs.
An analog low pass anti-aliasing filter with a 3 dB corner frequency is set at 2.4 kHz and is used for current and voltage
analog filtering as well as signal conditioning. The same filtering is applied for phase, ground currents, phase-to-phase
(when applicable), and auxiliary voltages. The 2.4 kHz cut-off frequency applies to both 50 Hz and 60 Hz applications and
fixed in the hardware, and thus is not dependent on the system nominal frequency setting.
2
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL2-15
2
SIGNAL PROCESSINGCHAPTER 2: PRODUCT DESCRIPTION
Figure 2-2: UR signal processing
The UR samples its AC signals at 64 samples per cycle, that is, at 3840 Hz in 60 Hz systems, and 3200 Hz in 50 Hz systems.
The sampling rate is dynamically adjusted to the actual system frequency by an accurate and fast frequency tracking
system.
The A/D converter has the following ranges of AC signals:
Voltages:
Eq. 2-1
Currents:
Eq. 2-2
Current harmonics are estimated based on raw samples with the use of the full-cycle Fourier filter. Harmonics 2nd through
25th are estimated.
2-16C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTIONSPECIFICATIONS
True RMS value for the current is calculated on a per-phase basis. The true RMS can be used for demand recording or as an
input signal to Time Overcurrent function, if the latter is intended for thermal protection. The true RMS is calculated as per
the widely accepted definition:
Eq. 2-3
RMS values include harmonics, inter-harmonics, DC components, and so on, along with fundamental frequency values.
The true RMS value reflects thermal effects of the current and is used for the thermal related monitoring and protection
functions.
Protection and control functions respond to phasors of the fundamental and/or harmonic frequency components
(magnitudes and angles), with an exception for some functions that have an option for RMS or fundamental
measurements, or some function responding to RMS only. This type of response is explained typically in each element's
section in the instruction manual.
Currents are pre-filtered using a Finite Impulse Response (FIR) digital filter. The filter is designed to reject DC components
and low-frequency distortions, without amplifying high-frequency noise. This filter is referred to as a modified MIMIC filter,
which provides excellent filtering and overall balance between speed and accuracy of filtering. The filter is cascaded with
the full-cycle Fourier filter for the current phasor estimation.
Voltages are pre-filtered using a patented Finite Impulse Response (FIR) digital filter. The filter has been optimized to reject
voltage transformers specific distortions, such as Capacitive Voltage Transformer (CVT) noise and high-frequency
oscillatory components. The filter is cascaded with the half-cycle Fourier filter for the voltage phasor estimation.
The URs measure power system frequency using the Clarke transformation by estimating the period of the waveform from
two consecutive zero-crossings in the same direction (negative-to-positive). Voltage or current samples are pre-filtered
using a Finite Impulse Response (FIR) digital filter to remove high frequency noise contained in the signal. The period is
used after several security conditions are met, such as true RMS signal must be above 6% nominal for a certain time and
others. If these security conditions are not met, the last valid measurement is used for a specific time after which the UR
reverts to nominal system frequency.
Synchrophasors are calculated using a patented convolution integral algorithm. This algorithm allows use of the same
time-stamped samples, which are used for protection and taken at the same sampling frequency. This allows URs to use
one sampling clock for both protection algorithms and synchrophasors.
Synchrophasors on firmware versions 7.23 and up have been tested and certified to meet IEEE C.37.118-2011 and
C.37.118.1a-2014 standards for both metering and protection classes with outputs available up to 60 synchrophasors per
second for the metering class and 120 synchrophasors per second for the protection class. Synchrophasors measurement
are also available via IEC 61850-90-5 protocol.
Contact inputs threshold is settable in the firmware with 17, 33, 84, 166 VDC settings available. Inputs are scanned every
0.5 ms and can be conditioned for the critical applications, using debounce time timer, settable from 0.0 ms to 16.0 ms.
Contact inputs with auto-burnishing are available as well, when external contacts are exposed to the contamination in a
harsh industrial environment.
All measured values are available in the UR metering section on the front panel and via communications protocols.
Measured analog values and binary signals can be captured in COMTRADE format with sampling rates from 8 to 64
samples per power cycle. Analog values can be captured with Data Logger, allowing much slower rates extended over
long period of time.
Other advanced UR order code options are available to support IEC 61850 Ed2.0 (including fast GOOSE, MMS server, 61850
services, ICD/CID/IID files, and so on), IEEE 1588 (IEEE C37.238 power profile) based time synchronization, CyberSentry
(advanced cyber security), the Parallel Redundancy Protocol (PRP), IEC 60870-5-103, and so on.
2
2.5 Specifications
Specifications are subject to change without notice.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL2-17
2
SPECIFICATIONSCHAPTER 2: PRODUCT DESCRIPTION
2.5.1 Protection elements
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated. FlexLogic
operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect with other
protection or control elements of the relay, building FlexLogic equations, or interfacing with other intelligent electronic
devices (IEDs) or power system devices via communications or different output contacts. If not specified, the operate times
given here are for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
TRIP BUS (TRIP WITHOUT FLEXLOGIC)
Number of elements:6
Number of inputs:16
Operate time:<2 ms at 60 Hz
Timer accuracy:±3% or 10 ms, whichever is greater
2.5.2 User-programmable elements
FLEXLOGIC
Programming language:Reverse Polish Notation with graphical visualization (keypad programmable)
Lines of code:1024
Internal variables:64
Supported operations:NOT, XOR, OR (2 to 16 inputs), AND (2 to 16 inputs), NOR (2 to 16 inputs), NAND (2 to 16 inputs),
latch (reset-dominant), edge detectors, timers
Inputs:any logical variable, contact, or virtual input
Number of timers:32
Pickup delay:0 to 60000 (ms, sec., min.) in steps of 1
Dropout delay:0 to 60000 (ms, sec., min.) in steps of 1
FLEXCURVES™
Number:4 (A through D)
Reset points:40 (0 through 1 of pickup)
Operate points:80 (1 through 20 of pickup)
Time delay:0 to 65535 ms in steps of 1
FLEX STATES
Number:up to 256 logical variables grouped under 16 Modbus addresses
Programmability:any logical variable, contact, or virtual input
FLEXELEMENTS™
Number of elements:8
Operating signal:any analog actual value, or two values in differential mode
Operating signal mode:signed or absolute value
Operating mode:level, delta
Comparator direction:over, under
Pickup Level:–90.000 to 90.000 pu in steps of 0.001
Hysteresis:0.1 to 50.0% in steps of 0.1
Delta dt:20 ms to 60 days
Pickup and dropout delay:0.000 to 65.535 s in steps of 0.001
NON-VOLATILE LATCHES
Type:set-dominant or reset-dominant
Number:16 (individually programmed)
Output:stored in non-volatile memory
Execution sequence:as input prior to protection, control, and FlexLogic
2-18C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
Loading...
+ 386 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.